SA300. Коммуникационный протокол Modbus. Справочное руководство (англ.)

ezPAC™ Substation Automation Unit SA310/SA320/SA330 Modbus Communications Protocol Reference Guide BG0339 Rev. A7 Every effort has been made to ensure that the material herein is complete and accurate. However, the manufacturer is not responsible for any mistakes in printing or faulty instructions contained in this book. Notification of any errors or misprints will be received with appreciation. For further information regarding a particular installation, operation or maintenance of equipment, contact the manufacturer or your local representative or distributor. This document is applicable to devices with firmware versions: 10.3.XX 10.4.XX 10.5.XX 10.6.XX - Basic Basic Basic Basic Fault Fault Fault Fault + + + + IEEE 1159 IEEE 1159 + IEC 61000-4-15 Flicker EN 50160 + IEC 61000-4-15 Flicker + IEC 61000-4-7 Harmonics IEEE 1159 + Fast Analog Inputs REVISION HISTORY A5 May 2007 F/W versions 10.3.20 or later, 10.4.XX, 10.5.XX, 10.6.XX. Added 0-50mA and ±10V AI modules identification. Added cross-triggering setpoints via the Ethernet (UDP broadcast). Added Flicker registers. Added EN50160 setup registers and compliance statistics files. Added fast AI waveform channels. A6 June 2008 Fixed EN50160 harmonic and interharmonic voltage compliance record structure. A7 July 2009 F/W versions 10.XX.11 or later. Added support for 96 DI and 64 RO. Added relay blocking setup and status indication. Added SNTP client setup. Added 1PPS clock synchronization. Added a selectable EN 50160 transient overvoltage detection method option. Modbus is a trademark of Schneider Electric. 2 Table of Contents 1 GENERAL ..........................................................................................................9 2 MODBUS PROTOCOL IMPLEMENTATION....................................................10 2.1 2.2 2.3 2.4 2.5 2.6 Transmission Modes ...........................................................................................................10 Address Field.......................................................................................................................10 Function Field ......................................................................................................................10 Exception Responses..........................................................................................................10 Modbus Register Addresses ...............................................................................................10 Data Formats.......................................................................................................................11 2.6.1 16-bit Scaled Integer Format .............................................................................................................11 2.6.2 32-bit Long Integer Format ................................................................................................................12 2.6.3 32-bit Modulo-10000 Format .............................................................................................................13 2.7 2.8 2.9 User Assignable Registers ..................................................................................................13 Password Protection............................................................................................................14 Data Recording and File Transfers .....................................................................................14 2.9.1 Log File Organization.........................................................................................................................14 2.9.2 File Transfers.....................................................................................................................................16 3 MODBUS REGISTER MAP ..............................................................................19 3.1 Modbus Setup Registers .....................................................................................................19 Modbus Assignable Registers...............................................................................................................19 Assignable Registers Map ....................................................................................................................19 Modbus Conversion Scales ..................................................................................................................19 3.2 3.3 16-bit Scaled Analog Values - Basic Register Set ..............................................................20 16-bit Scaled Analog Values ...............................................................................................22 1/2-Cycle Values ...................................................................................................................................22 1-Cycle Phase Values...........................................................................................................................22 1-Cycle Low Phase Values ...................................................................................................................23 1-Cycle High Phase Values ..................................................................................................................23 1-Cycle Total Values .............................................................................................................................24 1-Cycle Auxiliary Values .......................................................................................................................24 Fundamental Phasor Values.................................................................................................................24 1-Second Phase Values........................................................................................................................25 1-Second Low Phase Values ................................................................................................................26 1-Second High Phase Values ...............................................................................................................26 1-Second Total Values..........................................................................................................................26 1-Second Auxiliary Values ....................................................................................................................27 Present Harmonic Demands .................................................................................................................27 Present Volt, Ampere and Power Demands..........................................................................................27 Symmetrical Components .....................................................................................................................28 V1 Harmonics .......................................................................................................................................28 V2 Harmonics .......................................................................................................................................28 V3 Harmonics .......................................................................................................................................29 I1 Harmonics.........................................................................................................................................29 I2 Harmonics.........................................................................................................................................29 I3 Harmonics.........................................................................................................................................29 V1 Harmonic Voltages (odd numbers) ..................................................................................................29 V2 Harmonic Voltages (odd numbers) ..................................................................................................29 V3 Harmonic Voltages (odd numbers) ..................................................................................................29 I1 Harmonic Currents (odd numbers)....................................................................................................29 I2 Harmonic Currents (odd numbers)....................................................................................................30 I3 Harmonic Currents (odd numbers)....................................................................................................30 Total Harmonic kW (odd numbers) .......................................................................................................30 Total Harmonic kvar (odd numbers)......................................................................................................30 Total Harmonic Power Factor (odd numbers) .......................................................................................30 V4 Harmonics .......................................................................................................................................30 3 Flicker ...................................................................................................................................................30 I4 Harmonics.........................................................................................................................................30 Minimum 1-Cycle Phase Values ...........................................................................................................31 Minimum 1-Cycle Total Values .............................................................................................................31 Minimum 1-Cycle Auxiliary Values ........................................................................................................32 Programmable Min/Max Minimum Values.............................................................................................32 V4 Harmonic Voltages (odd numbers) ..................................................................................................32 I4 Harmonic Currents (odd numbers)....................................................................................................32 Maximum 1-Cycle Phase Values ..........................................................................................................32 Maximum 1-Cycle Total Values ............................................................................................................33 Maximum 1-Cycle Auxiliary Values .......................................................................................................33 Maximum Demands ..............................................................................................................................34 Programmable Min/Max Maximum Values............................................................................................34 Maximum Harmonic Demands..............................................................................................................34 Scaled Analog Inputs ............................................................................................................................34 Raw Analog Inputs ................................................................................................................................35 Scaled Analog Outputs .........................................................................................................................35 Summary Energy Accumulated Demands ............................................................................................35 Summary Energy Block Demands ........................................................................................................35 Summary Energy Sliding Window Demands.........................................................................................35 Summary Energy Maximum Demands..................................................................................................35 TOU Maximum Demand Register #1 ....................................................................................................35 TOU Maximum Demand Register #4 ....................................................................................................35 TOU Maximum Demand Register #2 ....................................................................................................36 TOU Maximum Demand Register #5 ....................................................................................................36 TOU Maximum Demand Register #3 ....................................................................................................36 TOU Maximum Demand Register #6 ....................................................................................................36 TOU Maximum Demand Register #7 ....................................................................................................36 TOU Maximum Demand Register #8 ....................................................................................................36 TOU Maximum Demand Register #9 ....................................................................................................36 TOU Maximum Demand Register #10 ..................................................................................................36 TOU Maximum Demand Register #11 ..................................................................................................37 TOU Maximum Demand Register #12 ..................................................................................................37 TOU Maximum Demand Register #13 ..................................................................................................37 TOU Maximum Demand Register #14 ..................................................................................................37 TOU Maximum Demand Register #15 ..................................................................................................37 TOU Maximum Demand Register #16 ..................................................................................................37 0.2-Second RMS and Auxiliary Values .................................................................................................37 3-Second RMS and Auxiliary Values ....................................................................................................38 10-Minute RMS and Auxiliary Values....................................................................................................39 2-Hour RMS and Auxiliary Values.........................................................................................................39 0.2-Second Harmonics..........................................................................................................................40 3-Second Harmonics.............................................................................................................................41 10-Minute Harmonics ............................................................................................................................41 2-Hour Harmonics .................................................................................................................................42 3.4 32-bit Binary and Analog Values .........................................................................................44 Setpoint Status......................................................................................................................................44 Special Inputs .......................................................................................................................................44 Event Flags ...........................................................................................................................................44 Internal Pulsed Events ..........................................................................................................................44 Periodic Timers .....................................................................................................................................44 Digital Inputs .........................................................................................................................................44 Pulse Inputs ..........................................................................................................................................45 Relay Outputs .......................................................................................................................................45 Internal Static Events ............................................................................................................................45 Counters ...............................................................................................................................................45 Time/Date .............................................................................................................................................45 1/2-Cycle Values ...................................................................................................................................45 1-Cycle Phase Values...........................................................................................................................46 1-Cycle Low Phase Values ...................................................................................................................47 1-Cycle High Phase Values ..................................................................................................................47 1-Cycle Total Values .............................................................................................................................48 1-Cycle Auxiliary Values .......................................................................................................................48 4 Fundamental Phasor Values.................................................................................................................48 1-Second Phase Values........................................................................................................................49 1-Second Low Phase Values ................................................................................................................49 1-Second High Phase Values ...............................................................................................................50 1-Second Total Values..........................................................................................................................50 1-Second Auxiliary Values ....................................................................................................................50 Present Harmonic Demands .................................................................................................................51 Present Volt, Ampere and Power Demands..........................................................................................51 Total Energies.......................................................................................................................................52 Summary Energy Registers ..................................................................................................................52 Symmetrical Components .....................................................................................................................52 V1 Harmonics .......................................................................................................................................52 V2 Harmonics .......................................................................................................................................53 V3 Harmonics .......................................................................................................................................53 I1 Harmonics.........................................................................................................................................53 I2 Harmonics.........................................................................................................................................53 I3 Harmonics.........................................................................................................................................53 V1 Harmonic Voltages (odd numbers) ..................................................................................................53 V2 Harmonic Voltages (odd numbers) ..................................................................................................53 V3 Harmonic Voltages (odd numbers) ..................................................................................................53 I1 Harmonic Currents (odd numbers)....................................................................................................54 I2 Harmonic Currents (odd numbers)....................................................................................................54 I3 Harmonic Currents (odd numbers)....................................................................................................54 Total Harmonic kW (odd numbers) .......................................................................................................54 Total Harmonic kvar (odd numbers)......................................................................................................54 Total Harmonic Power Factor (odd numbers) .......................................................................................54 V4 Harmonics .......................................................................................................................................54 Flicker ...................................................................................................................................................54 I4 Harmonics.........................................................................................................................................55 Minimum 1-Cycle Phase Values ...........................................................................................................55 Minimum 1-Cycle Total Values .............................................................................................................56 Minimum 1-Cycle Auxiliary Values ........................................................................................................56 Programmable Min/Max Minimum Values.............................................................................................56 V4 Harmonic Voltages (odd numbers) ..................................................................................................56 I4 Harmonic Currents (odd numbers)....................................................................................................56 Maximum 1-Cycle Phase Values ..........................................................................................................56 Maximum 1-Cycle Total Values ............................................................................................................57 Maximum 1-Cycle Auxiliary Values .......................................................................................................57 Maximum Demands ..............................................................................................................................58 Programmable Min/Max Maximum Values............................................................................................58 Maximum Harmonic Demands..............................................................................................................58 Scaled Analog Inputs ............................................................................................................................59 Raw Analog Inputs ................................................................................................................................59 TOU Parameters...................................................................................................................................59 Scaled Analog Outputs .........................................................................................................................59 TOU Energy Register #1.......................................................................................................................59 TOU Energy Register #2.......................................................................................................................59 TOU Energy Register #3.......................................................................................................................59 TOU Energy Register #4.......................................................................................................................59 TOU Energy Register #5.......................................................................................................................60 TOU Energy Register #6.......................................................................................................................60 TOU Energy Register #7.......................................................................................................................60 TOU Energy Register #8.......................................................................................................................60 Summary Energy Accumulated Demands ............................................................................................60 Summary Energy Block Demands ........................................................................................................60 Summary Energy Sliding Window Demands.........................................................................................60 Summary Energy Maximum Demands..................................................................................................60 TOU Maximum Demand Register #1 ....................................................................................................61 TOU Maximum Demand Register #4 ....................................................................................................61 TOU Maximum Demand Register #2 ....................................................................................................61 TOU Maximum Demand Register #5 ....................................................................................................61 TOU Maximum Demand Register #3 ....................................................................................................61 TOU Maximum Demand Register #6 ....................................................................................................61 5 TOU Energy Register #9.......................................................................................................................61 TOU Energy Register #10.....................................................................................................................61 TOU Energy Register #11.....................................................................................................................62 TOU Energy Register #12.....................................................................................................................62 TOU Energy Register #13.....................................................................................................................62 TOU Energy Register #14.....................................................................................................................62 TOU Energy Register #15.....................................................................................................................62 TOU Energy Register #16.....................................................................................................................62 TOU Maximum Demand Register #7 ....................................................................................................62 TOU Maximum Demand Register #8 ....................................................................................................62 TOU Maximum Demand Register #9 ....................................................................................................63 TOU Maximum Demand Register #10 ..................................................................................................63 TOU Maximum Demand Register #11 ..................................................................................................63 TOU Maximum Demand Register #12 ..................................................................................................63 TOU Maximum Demand Register #13 ..................................................................................................63 TOU Maximum Demand Register #14 ..................................................................................................63 TOU Maximum Demand Register #15 ..................................................................................................63 TOU Maximum Demand Register #16 ..................................................................................................63 0.2-Second RMS and Auxiliary Values .................................................................................................64 3-Second RMS and Auxiliary Values ....................................................................................................64 10-Minute RMS and Auxiliary Values....................................................................................................65 2-Hour RMS and Auxiliary Values.........................................................................................................65 0.2-Second Harmonics..........................................................................................................................66 3-Second Harmonics.............................................................................................................................67 10-Minute Harmonics ............................................................................................................................68 2-Hour Harmonics .................................................................................................................................68 Generic TOU Season Energy Registers ...............................................................................................69 Generic TOU Season Maximum Demand Registers.............................................................................69 Generic Data.........................................................................................................................................69 3.5 Minimum/Maximum Log Registers ......................................................................................73 Minimum Phase Values ........................................................................................................................73 Minimum Total Values...........................................................................................................................74 Minimum Auxiliary Values .....................................................................................................................75 Programmable Min/Max Minimum Values.............................................................................................75 Maximum Phase Values .......................................................................................................................75 Maximum Total Values..........................................................................................................................77 Maximum Auxiliary Values ....................................................................................................................77 Summary Energy Maximum Demands..................................................................................................78 Maximum Demands ..............................................................................................................................78 Programmable Min/Max Maximum Values............................................................................................79 Maximum Harmonic Demands..............................................................................................................79 TOU Maximum Demand Register #1 ....................................................................................................80 TOU Maximum Demand Register #4 ....................................................................................................80 TOU Maximum Demand Register #2 ....................................................................................................80 TOU Maximum Demand Register #5 ....................................................................................................80 TOU Maximum Demand Register #3 ....................................................................................................80 TOU Maximum Demand Register #6 ....................................................................................................81 TOU Maximum Demand Register #7 ....................................................................................................81 TOU Maximum Demand Register #8 ....................................................................................................81 TOU Maximum Demand Register #9 ....................................................................................................81 TOU Maximum Demand Register #10 ..................................................................................................81 TOU Maximum Demand Register #11 ..................................................................................................82 TOU Maximum Demand Register #12 ..................................................................................................82 TOU Maximum Demand Register #13 ..................................................................................................82 TOU Maximum Demand Register #14 ..................................................................................................82 TOU Maximum Demand Register #15 ..................................................................................................82 TOU Maximum Demand Register #16 ..................................................................................................83 3.6 Device Control and Status Registers ..................................................................................84 Event Flags Registers (bit map)............................................................................................................84 Remote Relay Control Registers (bit map)............................................................................................84 Reset/Clear Registers ...........................................................................................................................84 Device Mode Control Registers ............................................................................................................85 Memory Status Registers......................................................................................................................85 6 Log Notification Registers (bit map) ......................................................................................................85 Setpoint Status Registers (bit map) ......................................................................................................85 Setpoint Alarm Latch Registers (bit map)..............................................................................................85 Device Diagnostics Register (bit map) ..................................................................................................85 Port Identification ..................................................................................................................................85 Current Network Settings ......................................................................................................................86 Device Authorization Register...............................................................................................................86 Factory Diagnostic Registers ................................................................................................................86 3.7 Device Setup Registers .......................................................................................................87 Device Identification ..............................................................................................................................87 Factory Device Settings ........................................................................................................................87 Basic Setup...........................................................................................................................................87 Demands Setup ....................................................................................................................................88 Device Options Setup ...........................................................................................................................88 Time/Date Setup ...................................................................................................................................89 Clock Setup and Status.........................................................................................................................89 Communication Ports Setup .................................................................................................................89 Network Setup ......................................................................................................................................90 Password Setup....................................................................................................................................90 Expert Power Service Setup .................................................................................................................91 Internet Service Provider (ISP) accounts ..............................................................................................91 SNTP Client Setup ................................................................................................................................91 EN50160 PQ Recorder Triggers Setup (EN50160 voltage characteristics) ..........................................91 Advanced EN50160 Setup....................................................................................................................92 EN50160 Harmonic Voltage Limits .......................................................................................................93 EN50160 Interharmonic Voltage Limits.................................................................................................93 DNP Options Setup...............................................................................................................................93 DNP Events Setup ................................................................................................................................94 DNP Class 0 Point Assignment.............................................................................................................94 SOE Log Labels....................................................................................................................................95 Fault Log Triggers Setup.......................................................................................................................95 Fault Log Recording Setup ...................................................................................................................95 IEEE 1159 PQ Log Triggers Setup (IEEE 1159 disturbance categories) ..............................................96 File Setup..............................................................................................................................................96 Waveform Log Recorder Setup.............................................................................................................97 Data Log Setup .....................................................................................................................................98 Programmable Min/Max Log Setup.......................................................................................................99 TOU Daily Profile Setup ........................................................................................................................99 TOU Calendar Years Setup ................................................................................................................100 TOU Calendar Setup ..........................................................................................................................100 Summary Energy/TOU Registers Setup .............................................................................................103 Summary Energy/TOU Registers Source Setup .................................................................................103 Control Setpoints Setup ......................................................................................................................103 Periodic Timers Setup.........................................................................................................................104 Energy Pulse Source Setup ................................................................................................................105 Counters Setup ...................................................................................................................................105 Counter Source Setup.........................................................................................................................105 Digital Inputs Setup DI1-DI64..............................................................................................................105 Digital Inputs Setup DI65-DI96............................................................................................................105 Relay Outputs Setup ...........................................................................................................................106 Analog Inputs Setup............................................................................................................................106 Analog Outputs Setup .........................................................................................................................106 3.8 Expansion I/O Slots Configuration ................................................................................... 108 Expansion I/O Slots Configuration Info ...............................................................................................108 Expansion I/O Modules Type Info .......................................................................................................108 3.9 File Transfer Blocks.......................................................................................................... 110 File Transfer Control Blocks................................................................................................................110 File Info Response Block (Variation 0 – File info) ...............................................................................111 File Info Response Block (Variation 1 – Current record info) ..............................................................112 File Info Response Block (Variation 2 – Data log record structure).....................................................112 Event Log Response Block .................................................................................................................113 Data Log Response Block...................................................................................................................113 Waveform Log Response Block..........................................................................................................114 7 Sequence of Events (SOE) Log Response Block ...............................................................................114 Power Quality (PQ) Log Response Block ...........................................................................................115 Fault Log Response Block ..................................................................................................................116 File Response Block Alias...................................................................................................................117 Power Quality (PQ) Log Response Block Alias...................................................................................117 3.10 EN 50160 Compliance Statistics Data Log ...................................................................... 119 3.11 EN 50160 Harmonics Survey Statistics Data Log ............................................................ 125 3.12 Billing/TOU Daily and Monthly Profile Data Logs ............................................................. 126 4 DATA SCALES AND UNITS ..........................................................................128 Data Scales.........................................................................................................................................128 Data Units ...........................................................................................................................................128 5 DATA FORMATS ...........................................................................................129 Timestamp ..........................................................................................................................................129 File ID..................................................................................................................................................129 File Attributes ......................................................................................................................................129 File Status Word (bitmap) ...................................................................................................................129 File Record Status Word (bitmap) .......................................................................................................129 TOU Profile Log Channel ID ...............................................................................................................129 Waveform Log Channel ID..................................................................................................................129 TOU Profile Log Channel Mask (bitmap) ............................................................................................130 Waveform Log Channel Mask (bitmap)...............................................................................................130 TOU Tariff Change Time.....................................................................................................................130 Summary Energy Register Source ID .................................................................................................130 Setpoint Trigger Parameters ID ..........................................................................................................131 Setpoint Relational Operator...............................................................................................................131 Setpoint Action ID ...............................................................................................................................131 Energy Pulse Source ID......................................................................................................................131 Counter Source ID ..............................................................................................................................131 Relay Output Pulse Source ID ............................................................................................................131 AO Parameters ID (see Section 3.4 for data scales) ..........................................................................131 Event Source/Point ID.........................................................................................................................132 Event Effect ID ....................................................................................................................................133 Data/Function Point ID ........................................................................................................................133 Event Type ID .....................................................................................................................................134 Device Diagnostics (bitmap) ...............................................................................................................135 DNP Object Types ..............................................................................................................................135 DNP Class 0 Objects ..........................................................................................................................136 Wiring Mode........................................................................................................................................136 8 1 General This document specifies a subset of the Modbus communications protocol used to transfer data between a master computer station and the SA300. The document provides the complete information necessary to develop third-party communications software capable of communication with the SA300. Refer to the SA300 Installation Manual and SA300 Operation Manual for more information on communication connections and configuring communication parameters in your device. 9 2 Modbus Protocol Implementation For detailed information on the Modbus protocol, message framing and error checking, refer to the Modbus Protocol Reference Guide. It can be downloaded from the ModbusIDA Website at http://www.modbus.org/. The following paragraphs outline some issues concerning the implementation of the Modbus protocol in the SA300. 2.1 Transmission Modes The SA300 can be set up to communicate on a serial Modbus network using either RTU, or ASCII serial transmission mode, and via the Internet using Modbus/TCP mode. Refer to the SA300 Operation Manual for information on selecting the transmission mode in your device. 2.2 Address Field The address field contains a user assigned address of the instrument (1-247) on a Modbus network. Broadcast mode using address 0 is not supported. When communicating via the Internet, the address field is not checked and is returned in the response message header. 2.3 Function Field The Modbus functions implemented in the SA300 are shown in Table 2-1. Function 04 can be used in the same context as function 03. Table 2-1 Modbus Function Codes Code (decimal) 1 Meaning in Modbus Action 03 Read holding registers Read multiple registers 04 Read input registers Read multiple registers 06 Preset single register Write single register 16 Preset multiple registers Write multiple registers 22 Mask write Set or clear individual bits 081 Loop-back test Communications test The SA300 supports only diagnostic code 0 - return query data. 2.4 Exception Responses The instrument sends an exception response when an error is detected in the received message. To indicate that the response is notification of an error, the high order bit of the function code is set to 1. Implemented exception response codes: 01 - Illegal function 02 - Illegal data address 03 - Illegal data value 04 - Device failure When the character framing, parity, or redundancy check detects a communication error, processing of the master's request stops. The instrument will not act on or respond to the message. 2.5 Modbus Register Addresses The SA300 Modbus registers are numbered in the range of 0 to 65535. From the Modbus applications, the SA300 Modbus registers can be accessed by simulating 10 holding registers of the Modicon 584, 884 or 984 Programmable Controller, using a 5digit “4XXXX” or 6-digit “4XXXXX” addressing scheme. To map the SA300 register address to the range of the Modbus holding registers, add a value of 40001 to the SA300 register address. When a register address exceeds 9999, use a 6-digit addressing scheme by adding 400001 to the SA300 register address. 2.6 Data Formats The SA300 uses three data formats to pass data between a master application and the instrument: 16-bit short integer, 32-bit long integer and 32-bit modulo-10000 formats. Binary values and counters are always transmitted in 32-bit registers, while analog values can be read both in 32-bit and in 16-bit scaled registers. Analog registers 256 through 308 and 4320 through 10751 contain scaled 16-bit values. 2.6.1 16-bit Scaled Integer Format 16-bit scaled data is transmitted in a single 16-bit Modbus register as unsigned (UINT16) integer (whole) numbers using the linear conversion to accommodate largescale and fractional numbers to a 16-bit register format. The linear conversion uses two scales to read the raw data from the device and convert it into engineering units: the device original engineering scale and the Modbus conversion scale. When transmitting measured data, the device scales it into the range of Modbus Low and High conversion scales. To reconstruct data in the original engineering units, perform the reverse conversion according to the following formula: Engineering _ Units = Raw _ Data × (ENG _ HI − ENG _ LO) + ENG _ LO RAW _ HI − RAW _ LO where: ENG_LO and ENG_HI - reading low and high scales in engineering units RAW_LO and RAW_HI - raw data low and high scales (by default, 0 and 9999) Raw_Data - raw input data in the range of RAW_LO to RAW_HI Engineering_Units - true value in engineering units The default Modbus conversion scales are 0 for the low scale and 9999 for the high scale. This means that the scaled analog data is always transmitted in the range of 0 to 9999. The Modbus conversion scales can be changed through communications via registers 240 and 241. The engineering scales are separately indicated for each scaled 16-bit register. For data scales and measurement units that depend on the device input scales (such as volts, amps and powers), refer to Chapter 4 “Data Scales and Units”. Conversion Examples 1. Voltage readings a) Assume device settings (direct wiring): PT ratio = 1. Voltage engineering scales (see Chapter 4): HI_ENG = Vmax = 828.0 × PT ratio = 828.0 × 1 = 828.0V LO_ENG = 0V If the raw data reading is 1449 then the voltage reading in engineering units will be as follows: Volts reading = 1449 × (828.0 - 0)/(9999 - 0) + 0 = 120.0V b) Assume device settings (wiring via PT): PT ratio = 14,400V : 120V = 120. Voltage engineering scales (see Chapter 4): HI_ENG = Vmax = 828.0 × PT ratio = 828 × 120 = 99,360V LO_ENG = 0V If the raw data reading is 1449 then the voltage reading in engineering units will be as follows: 11 Volts reading = 1449 × (99360 - 0)/(9999 - 0) + 0 = 14,399V 2. Current readings Assume device settings: CT primary current = 200A; current input overload = 400% (20A). Current engineering scales (see Chapter 4): HI_ENG = Imax = CT primary current × 4 = 200.00 × 4 = 800.00A LO_ENG = 0A If the raw data reading is 250 then the current reading in engineering units will be as follows: Amps reading = 250 × (800.00 - 0)/(9999 - 0) + 0 = 20.00A 3. Power readings a) Assume device settings (direct wiring): PT = 1; CT primary current = 200A; current input overload = 400% (20A). Active Power engineering scales (see Chapter 4): HI_ENG = Pmax = Vmax × Imax × 2 = (828.0 × 1) × (200.00 × 4) × 2 = 1,324,800W = 1324.800kW LO_ENG = -Pmax = -1324.800kW If the raw data reading is 5500 then the power reading in engineering units will be as follows: Watts reading = 5500 × (1324.800 - (-1324.800))/(9999 - 0) + (-1324.800) = 132.626kW If the raw data reading is 500 then the power reading in engineering units will be as follows: Watts reading = 500 × (1324.800 - (-1324.800))/(9999 - 0) + (-1324.800) = -1192.307kW b) Assume device settings (wiring via PT): PT = 120; CT primary current = 200A; current input overload = 400% (20A). Active Power engineering scales (see Chapter 4): HI_ENG = Pmax = Vmax × Imax × 2 = (828 × 120) × (200.00 × 4) × 2/1000 = 158976kW LO_ENG = -Pmax = -158976kW If the raw data reading is 5500 then the power reading in engineering units will be as follows: Watts reading = 5500 × (158976 - (-158976))/(9999 - 0) + (-158976) = 15915kW If the raw data reading is 500 then the power reading in engineering units will be as follows: Watts reading = 500 × (158976 - (-158976))/(9999 - 0) + (-158976) = -143077kW 4. Power Factor readings Power factor engineering scales (see Chapter 4): HI_ENG = 1.000. LO_ENG = -1.000. If the raw data reading is 8900 then the power factor in engineering units will be as follows: Power factor reading = 8900 × (1.000 - (-1.000))/(9999 - 0) + (-1.000) = 0.78 2.6.2 32-bit Long Integer Format 32-bit long integer data is transmitted in two adjacent 16-bit Modbus registers as unsigned (UINT32) or signed (INT32) whole numbers. The first register contains the low-order word (lower 16 bits) and the second register contains the high order word (higher 16 bits). The low-order word always starts at an even Modbus address. The value range for unsigned data is 0 to 4,294,967,295; for signed data the range is 2,147,483,648 to 2,147,483,647. If your Modbus driver does not support a 32-bit long integer format, you can read the two 16-bit registers separately, and then convert them into a 32-bit value as follows (using C notation): 32-bit value = (signed short)high_order_register × 65536L + (unsigned short)low_order_register 12 Examples 1. Unsigned 32-bit Values If you read unsigned Voltage V1 of 69,000V from registers 13952-13953, then the register readings will be as follows: (13952) = 3464 (13953) = 1 The 32-bit value is (1 x 65536 + 3464) = 69000V. 2. Signed 32-bit Values If you read signed kW of -789kW from registers 14336-14337, then the register readings will be: (14336) = 64747 (unsigned) (14337) = 65535 (unsigned) or -1(signed value). To take the high order register as a signed value, compare it with 32767. If the value is less or equal to 32767, use it as is. If it is greater than 32767, then this is a negative number in a two's complement code (like in our example) - just subtract it from 65536 to get the original negative value. The 32-bit reading is (-1 x 65536 + 64747) = -789kW. Fractional 32-bit data is transmitted using decimal scaling to pass fractional numbers in integer format. Fractional numbers are pre-multiplied by 10 to the power N, where N is the number of digits in the fractional part. For example, the frequency reading of 50.01 Hz is transmitted as 5001, having been pre-multiplied by 100. Whenever a data register contains a fractional number, the register measurement unit is given with a multiplier ×0.1, ×0.01 or ×0.001, showing the weight of the least significant decimal digit. To get an actual fractional number with specified precision, multiply the register value by the given multiplier. To write a fractional number into the register, divide the number by the given multiplier. 2.6.3 32-bit Modulo-10000 Format Energy counters 287-294 and 301-302 are read in two contiguous 16-bit registers in a modulo-10000 format. The first (low order) register contains the value mod 10000, and the second (high order) register contains the value/10000. To get the true energy reading, the high order register value should be multiplied by 10,000 and added to the low order register. 2.7 User Assignable Registers The SA300 provides 120 user assignable registers in the address range of 0 to 119. You can re-map any register available in the device to any assignable register so that Modbus registers that reside at different locations may be simply accessed using a single request by re-mapping them to adjacent addresses. The actual addresses of the assignable registers, which are accessed via addresses 0 through 119, are specified in the register map (registers 120 through 239), where register 120 contains the actual address of the register accessed via register 0, register 121 contains the actual address of the register accessed via register 1, and so on. The assignable registers and the map registers themselves may not be re-mapped. Initially these registers are reserved and none of them points to an actual register address. To build your own register map, write to map registers 120 to 239 the actual addresses you want to read from or write to via the assignable area (registers 0 to 119). 32-bit long registers should always be aligned at even addresses. For example, to read registers 4672 (1-second V1 voltage, scaled short integer) and 14720-14721 (kWh Import, long integer) via registers 0-2, do the following: - write 14720 to register 120 - write 14721 to register 121 - write 4672 to register 122 13 Reading from registers 0-2 will return the kWh reading in registers 0 (low 16 bits) and 1 (high 16 bits), and the voltage reading in register 2. 2.8 Password Protection The SA300 has a password protection option allowing you to protect your setups, cumulative registers and logs from being changed or cleared through communications. You can disable or enable password protection through communications, the RDM or via the Terminal. For details, refer to your instrument Operation Manual. A user password must be written into the device authorization register (44378-44379) before another write request is issued. If the correct password is not supplied while password protection is enabled, the device will respond to all write requests with the exception code 01 (illegal operation). It is recommended to clear the password register after you have completed your changes in order to activate password protection. 2.9 Data Recording and File Transfers 2.9.1 Log File Organization Historical files are stored to the non-volatile memory with battery backup. Memory is allocated for each file statically when you set up your files and will not change unless you re-organize the files. The SA300 automatically performs de-fragmentation of the memory each time you re-organize your files. This prevents possible leakage of memory caused by fragmentation. Data records in a file are arranged in the order of their recording. Each record has a unique 16-bit sequence number that is incremented modulo 65536 with each new record. The sequence number can be used to point to a particular record in the file, or to check the sequence of records when uploading files from the device. Each file has a write position pointer that indicates the place where the next record will be recorded, and a read position pointer that indicates the place from where the current record will be read. Both pointers show sequence numbers of the records they point to rather than record offsets in the file. After acknowledging a record you have read, the read pointer automatically advances to the next record in the file. When the read pointer gets to the record to which the file write pointer points, the end-of-file (EOF) flag is set. It is automatically cleared when a new record is added to the file, or when you explicitly move the read pointer to any record within a file. If a file has a wrap-around attribute (circular file), the most recent records can overwrite the oldest records. When this happens at the current read position, the read pointer automatically advances forward in order to point to the oldest record in the file. The SA300 keeps a separate read pointer for each communication port so that access to the same file through a different port will not affect current active sessions for other ports. Multi-section Files Log files can have one or more (up to 32) sections for multi-channel recording. An ordinal file consists of a single section. Some files, such as TOU profile log files and waveform log files, are arranged as multi-section files. A multi-section file is subdivided into multiple sections of the same structure, one section per recording channel. The number of sections in each file is defined at the time you set up your files and may not change unless you re-organize the file. Sections within a multi-section file can be addressed by a section number, or by a section channel ID. A multi-section file has a single write position pointer for all sections and stores data in all sections simultaneously. This means that records with the same sequence number in all sections are associated with the same event. A multi-section file has also a single read position pointer for all sections. 14 Data Log Files Conventional data log files can store up to 16 measured parameters per a record. Any data measured by the device can be stored in the log file. The number of parameters that each record will hold and the list of parameters you want to be recorded in the file can be selected through the Data log setup registers for a particular file. Recording data to data log files can be triggered through the setpoints, either on a time basis, or upon any event detected by the setpoints. TOU Profile Log Files Data log files #15 and #16 can be configured for monthly and daily profile logs of the energy usage and maximum demand registers. A profile log file is organized as a multi-section file that has a separate section for each energy and maximum demand register. See Section 3.12 for more information on the file record structure. A file record stores all tariff data for each configured Summary/TOU register. The number of sections is taken automatically from the Summary/TOU Registers setup. In order to correctly allocate memory space, configure your TOU registers before you set up TOU profile files. Since each Summary/TOU energy register has a shadow maximum demand register, the number of sections in the file will be twice the number of the allocated Summary/TOU registers. Power Quality Statistics Log Files Data log files #9 and #10 are configured to store the power quality statistics data on a daily or weekly basis. They are organized as multi-section files. See Sections 3.10-3.11 for more information on the file record structure. You can review the list of parameters recorded to the files through the file info request/response blocks using info requests with variation 2 (see Section 3.9). Waveform Log Files Waveform log files are organized as multi-section files that store data for each recording channel in a separate section. A waveform log file can record up to 12 channels simultaneously: eight AC channels (four voltages and four currents), a VDC channel, and 3x16 digital inputs DI1:16, DI17:32, DI33:48 that are recorded as three 16-bit analog channels. In devices with a fast AI option, a file can additionally record 16 analog input channels. The number of sections, or channels, that a file can store, is defined in the file setup. The waveform log setup allows selecting channels that a file will record. All selected channels are recorded in successive file sections. A waveform file has a single read pointer for all sections, so that data from all channels of a single record can be read together without repositioning the file pointer. When you point to a particular file record, data from all sections related to the same event are all available for a read. Moreover, the SA300 takes all channel data for the currently accessed record to a separate buffer, so that even when the record is overwritten at the time of reading, you are still prevented from receiving partially updated data. You can also read a file in a common sequential manner section-by-section. A single waveform record for a channel can contain up to 512 points of the sampled input signal. VDC, DI and AI channels are sampled at different rates than AC channels and may contain fewer points than the corresponding AC records. Refer to the sampling rate field in the channel records to correctly set up the time scale for the VDC, DI and AI waveforms. If the record contains less than 512 points, the value of unused points is unpredictable. If a waveform log is configured to record more samples per event than a single record can hold, the waveform recorder will store as many records per event as required to record the entire event. All waveform records related to the event are merged in a series and have the same series number, so that they can all be plotted together. Each record within a series has a unique serial number that allows tracking the sequence of records in the series. A single waveform series can hold up to 347,136 points (10,848 cycles at a rate of 32 samples per cycle) of a sampled AC signal. 15 2.9.2 File Transfers File transfer protocol provides both data transfer and information services. File transfer is performed through two blocks of registers: a 32-word master request block and a 1792-word read-only file response block. After a master application has written the request into the file request block, the requested data is available for a read through the file response block registers. File transfer functions allow changing the file or section position in order to point to the desired record. The information service uses separate 8-word file info request and 200-word file info response blocks. The extended file information is available including current file pointers’ positions, file contents, the number of records in the file, allocated file size, time of file creation, time of the last file update and reset, and more. Common File Transfer Log files can be read either in a sequence record-by-record, or in a random order. Each Read-File request fills the file response block with the data of the record pointed to by the file (or section) read pointer. If you want to begin reading a file from a particular record, which sequence number is known, you can change the pointer position by issuing the Set-File-Position request with the desired sequence number. If you want to read a file from the beginning, send the Reset-File-Position request that moves the pointer to the oldest file record. If you do not change the file position, then you will continue reading the file from the record following the one you have read the last time you accessed the file. You need not explicitly move the file position to the following record if you want to continue reading a file in sequence after you have uploaded the current record. Instead, issue an acknowledgment request that automatically advances the file pointer to the next record, and then read the record data through the file response block. The file response block can contain more than one record. The number of records available in the block and the file record size in words are always reported in the block heading. There are no special rules on how to read records from the file transfer block. You can read a single record or all records together, or begin reading from the last record and end with the first record. However, you should remember: 1) after an acknowledgment, the file position moves to the record following the last one you have accessed in the file transfer block; and 2) data in the file transfer block does not change until you either issue an acknowledgment, or explicitly change the file position by the Set-File-Position or Reset-File-Position requests. The file transfer is completed after you have read the last record of the file. Before storing a file record to your database, always check bit 9 in the record status word, which contains the end-of-file (EOF) flag. This bit set to 1 indicates that the file read pointer does not point to any record within the file, and you should not store any record that has this bit set. The EOF flag is set only after you have acknowledged the last record of the file, so that testing for end-of-file requires one extra read. If you wish to stop the transfer just after storing the last file record, acknowledge the record and check bit 0 in the record status word. Bit 0 is set to 1 only once when you read the last record of the file. The following gives a summary of steps you should do to read an ordinal log file: 1. If you want to begin reading a file from a particular record or from the first record, use either the Set-File-Position request with the desired record sequence number, or the Reset-File-Position request. Preset a section number and channel ID to zero. 2. Write the Read-File request with a section number and channel ID set to zero. 3. Read the record data from the file response block. 4. Write an acknowledgment for the file. You need not fill all the request fields: only the file function is required. The file pointer will be moved to the next file record. Repeat steps 3-4 until all the file records are read. Reading Multi-section Data Log Files In a multi-section data log file, all user requests including an acknowledgment, the Read-File, Set-File-Position and Reset-File-Position requests, relate to a particular file 16 section rather than to the file itself. The only request that affects the entire file is the Erase-File that clears all the file sections together. A file section can be requested either by a section number, or by a section channel ID. If you use a channel ID, preset the section number field to 0xFFFF. If a section number is specified, the channel ID field will not be checked. The device returns both fields in the response block heading, so you can always identify what channel data is being read from the present file section. If you want to know which channels are recorded to the file sections, check the file channel mask in the file info block. This is a bitmap that contains one in a bit position if a channel with an ID equal to the bit number is recorded to the file, and contains zero if it is not. The following gives a summary of steps for reading a multi-section data log file: 5. If you wish to begin reading a file section from a particular record or from the first record, use either the Set-File-Position request with the desired record sequence number, or the Reset-File-Position request. Specify either a section number, or the channel ID for the section from where you want to read data. If you use a channel ID, preset the section number field to 0xFFFF. 6. Write the Read-File request with the section number and channel ID as shown in the previous step. 7. Read the record data from the file response block. 8. Write an acknowledgment for the file. The file section pointer will be moved to the next record. Repeat steps 3-4 until all the section records are read. Reading Multi-section Waveform Files Waveform files can be read as conventional multi-section files in the order described above. Another way is to take advantage of the fact that waveform files have a single read pointer for all file sections, so you can read records of all the channels related to the same event at once without repositioning the file pointer. The following gives a summary of steps for reading waveform files: 1. If you want to begin reading a file from a particular record or from the first record, use either the Set-File-Position request with the desired record sequence number, or the Reset-File-Position request. Preset the section field to zero. 2. Write the Read-File request. Address you request to the first file section (its number is always zero), or to the first file channel (if you know channel’s ID). If you use a channel ID, preset the section number field to 0xFFFF. 3. Read the channel’s data from the file response block. Store the received record’s sequence number. 4. Write the Read-File request for the next file section or channel using the stored record sequence number. The file response block will be refilled with the data for the requested channel that is related to the record with the same sequence number. 5. Repeat steps 3, 4 until all the channel records with the current sequence number are read. 6. Write an acknowledgment. The file pointer will be moved to the next record. Repeat steps 2-6 until all the file records are read. Reading Real-time Waveforms Real-time waveforms are accessed through the same transfer blocks just like the waveform log files by addressing file 128. Writing the Read-File request for file 128 provides a simultaneous capture of 6 real-time waveform records – three voltage and three current waveforms – into a communication buffer that can be read through the common file response block. The following gives a summary of steps for reading realtime waveforms: 17 1. Write the Read-File request for file 128. Address you request to the first file section (its number is always zero), or to the first file channel (if you know channel’s ID). If you use a channel ID, preset the section number field to 0xFFFF. 2. Read the channel’s data from the file response block. 3. Write the Read-File request for the next file section or channel. The file response block will be refilled with the data for the requested channel. 4. Repeat steps 3, 4 until all the channel records are read. Write an acknowledgment to release the buffer. 18 3 Modbus Register Map 3.1 Modbus Setup Registers Address Point ID Description Modbus Assignable Registers 0-119 +0 Register 0 contents +1 Register 1 contents ... +119 Register 119 contents Assignable Registers Map 120-239 +0 Register 0 address +1 Register 1 address Options/Range +119 Register 119 address Modbus Conversion Scales 240 Low raw scale 241 High raw scale 242 Voltage scale, secondary volts 243 Current scale, secondary amps Units Type R/W 0-65535 0-65535 UINT16 UINT16 R/W R/W 0-65535 UINT16 R/W 0-65535 0-65535 UINT16 UINT16 R/W R/W 0-65535 UINT16 R/W 0-65535 (default 0) 1023-65535 (default 9999) 60-828 (default 828V) 10-200 (default CT secondary current x Current Overload) UINT16 UINT16 UINT16 UINT16 R/W R/W R/W R/W 1V ×0.1A Notes 19 3.2 16-bit Scaled Analog Values - Basic Register Set Address 256-308 +0 +1 +2 +3 +4 +5 +6 +7 +8 +9 +10 +11 +12 +13 +14 +15 +16 +17 +18 +19 +20 +21 +22 +23 +24 +25 +26 +27 +28 +29 +30 +31 +32 +33 +34 +35 +36 +37 20 Point ID 0x1100 0x1101 0x1102 0x1103 0x1104 0x1105 0x1106 0x1107 0x1108 0x1109 0x110A 0x110B 0x110C 0x110D 0x110E 0x110F 0x1110 0x1111 0x1403 0x1400 0x1401 0x1402 0x1501 0x1502 0x3709 0x160F 0x370B 0x1611 0x3703 0x3704 0x3705 2 2 Description Low and High Scales Units Type R/W Notes 1-Second Values V1/V12 voltage V2/V23 voltage V3/V31 voltage I1 current I2 current I3 current kW L1 kW L2 kW L3 kvar L1 kvar L2 kvar L3 kVA L1 kVA L2 kVA L3 Power factor L1 Power factor L2 Power factor L3 Total PF Total kW Total kvar Total kVA In current Frequency Maximum kW import sliding window demand kW import accumulated demand Maximum kVA sliding window demand kVA accumulated demand I1 Maximum ampere demand I2 Maximum ampere demand I3 Maximum ampere demand kWh import (low) kWh import (high) kWh export (low) kWh export (high) +kvarh net (low) +kvarh net (high) -kvarh net (low) 0-Vmax 0-Vmax 0-Vmax 0-Imax 0-Imax 0-Imax -Pmax-Pmax -Pmax-Pmax -Pmax-Pmax -Pmax-Pmax -Pmax-Pmax -Pmax-Pmax -Pmax-Pmax -Pmax-Pmax -Pmax-Pmax -1.000-1.000 -1.000-1.000 -1.000-1.000 -1.000-1.000 -Pmax-Pmax -Pmax-Pmax -Pmax-Pmax 0-Imax 45.00-65.00 -Pmax-Pmax -Pmax-Pmax -Pmax-Pmax -Pmax-Pmax -Pmax-Pmax -Pmax-Pmax -Pmax-Pmax 0-9999 0-9999 0-9999 0-9999 0-9999 0-9999 0-9999 U1 U1 U1 U2 U2 U2 U3 U3 U3 U3 U3 U3 U3 U3 U3 0.001 0.001 0.001 0.001 U3 U3 U3 U2 0.01Hz U3 U3 U3 U3 U2 U2 U2 ×0.1 kWh ×1 MWh ×0.1 kWh ×1 MWh ×0.1 kvarh ×1 Mvarh ×0.1 kvarh UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 INT16 INT16 INT16 INT16 INT16 INT16 UINT16 UINT16 UINT16 INT16 INT16 INT16 INT16 INT16 INT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R 1 1 1 6 6 6 6 4, 6 4, 6 5, 6 Address Point ID +38 +39 +40 +41 +42 +43 +44 +45 +46 +47 +48 +49 +50 +51 +52 0x1112 0x1113 0x1114 0x1115 0x1116 0x1117 0x1609 0x160B 0x1615 0x111B 0x111C 0x111D Description -kvarh net (high) V1/V12 voltage THD V2/V23 voltage THD V3/V31 voltage THD I1 current THD I2 current THD I3 current THD kVAh (low) kVAh (high) Present kW import sliding window demand Present kVA sliding window demand PF (import) at Max. kVA sliding window demand I1 current TDD I2 current TDD I3 current TDD 2 Low and High Scales 0-9999 0-999.9 0-999.9 0-999.9 0-999.9 0-999.9 0-999.9 0-9999 0-9999 -Pmax-Pmax -Pmax-Pmax 0-1.000 0-100.0 0-100.0 0-100.0 2 Units ×1 Mvarh 0.1% 0.1% 0.1% 0.1% 0.1% 0.1% ×0.1 kVAh ×1 MVAh U3 U3 0.001 0.1% 0.1% 0.1% Type R/W Notes UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 R R R R R R R R R R R R R R R 5, 6 3 3 3 3 3 3 6 6 3 3 3 NOTES: 1 When the 4LN3, 3LN3 or 3BLN3 wiring mode is selected, the voltages will be line-to-neutral; for any other wiring mode, they will be line-to-line voltages. 2 For volts, amps and power scales refer to Chapter 4 ”Data Scales and Units”. 3 On a 3-s interval. 4 Positive readings of kvarh net 5 Negative readings of kvarh net 6 If you use these energy registers instead of 32-bit registers, limit the energy roll value to 8 digits (see Advanced Device Setup) to avoid early overflow. 21 3.3 16-bit Scaled Analog Values Address 4320-4344 +0 +1 +2 +3 +4 +5 +5 +7 +8 +9 +10 +11 +12 +13 +14 +15 +16 +17 +18 +19 +20 +21 +22 +23 +24 4352-4387 +0 +1 +2 +3 +4 +5 +6 +7 +8 +9 +10 +11 22 Point ID 0x0B80 0x0B81 0x0B82 0x0B83 0x0B84 0x0B85 0x0B86 0x0B87 0x0B88 0x0B89 0x0B8A 0x0B8B 0x0B8C 0x0B8D 0x0B8E 0x0B8F 0x0B90 0x0B91 0x0B92 0x0B93 0x0B94 0x0B95 0x0B96 0x0B97 0x0B98 0x0C00 0x0C01 0x0C02 0x0C03 0x0C04 0x0C05 0x0C06 0x0C07 0x0C08 0x0C09 0x0C0A 0x0C0B Description 1/2-Cycle Values V1 voltage V2 voltage V3 voltage V4 voltage V12 voltage V23 voltage V31 voltage I1 current I2 current I3 current I4 current In current I1x current I2x current I3x current I4x current Inx current Zero-sequence voltage Zero-sequence current Ix Zero-sequence current Voltage unbalance Current unbalance Ix current unbalance DC voltage Frequency (1-cycle) 1-Cycle Phase Values V1 voltage V2 voltage V3 voltage I1 current I2 current I3 current kW L1 kW L2 kW L3 kvar L1 kvar L2 kvar L3 3 3 Low and High Scales Units Type R/W Notes 0-Vmax 0-Vmax 0-Vmax 0-V4max 0-Vmax 0-Vmax 0-Vmax 0-Imax 0-Imax 0-Imax 0-I4max 0-Imax 0-Ixmax 0-Ixmax 0-Ixmax 0-I4xmax 0-Ixmax 0-Vmax 0-Imax 0-Ixmax 0-300.0 0-300.0 0-300.0 0-9999.00 0-100.00 U1 U1 U1 U4 U1 U1 U1 U2 U2 U2 U2 U2 U2 U2 U2 U2 U2 U1 U2 U2 0.1% 0.1% 0.1% 0.01V 0.01Hz UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 R R R R R R R R R R R R R R R R R R R R R R R R R 1 0-Vmax 0-Vmax 0-Vmax 0-Imax 0-Imax 0-Imax -Pmax-Pmax -Pmax-Pmax -Pmax-Pmax -Pmax-Pmax -Pmax-Pmax -Pmax-Pmax U1 U1 U1 U2 U2 U2 U3 U3 U3 U3 U3 U3 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 INT16 INT16 INT16 INT16 INT16 INT16 R R R R R R R R R R R R 1 1 1 1 1 Address +12 +13 +14 +15 +16 +17 +18 +19 +20 +21 +22 +23 +24 +25 +26 +27 +28 +29 +30 +31 +32 +33 +34 +35 4416-4429 +0 +1 +2 +3 +4 +5 +5 +7 +8 +9 +10 +11 +12 +13 4480-4493 +0 +1 +2 Point ID Description 0x0C0C 0x0C0D 0x0C0E 0x0C0F 0x0C10 0x0C11 0x0C12 0x0C13 0x0C14 0x0C15 0x0C16 0x0C17 0x0C18 0x0C19 0x0C1A 0x0C1B 0x0C1C 0x0C1D 0x0C1E 0x0C1F 0x0C20 0x0C21 0x0C22 0x0C23 kVA L1 kVA L2 kVA L3 Power factor L1 Power factor L2 Power factor L3 V1 voltage THD V2 voltage THD V3 voltage THD I1 current THD I2 current THD I3 current THD I1 K-Factor I2 K-Factor I3 K-Factor I1 current TDD I2 current TDD I3 current TDD V12 voltage V23 voltage V31 voltage I1x current I2x current I3x current 1-Cycle Low Phase Values Low L-N voltage Low current Low kW Low kvar Low kVA Low PF Lag Low PF Lead Low voltage THD Low current THD Low K-Factor Low current TDD Low L-L voltage Low voltage interharmonics THD Low current interharmonics THD 1-Cycle High Phase Values High L-N voltage High current High kW 0x0D00 0x0D01 0x0D02 0x0D03 0x0D04 0x0D05 0x0D06 0x0D07 0x0D08 0x0D09 0x0D0A 0x0D0B 0x0D0C 0x0D0D 0x0E00 0x0E01 0x0E02 3 3 Low and High Scales 0-Pmax 0-Pmax 0-Pmax -1.000-1.000 -1.000-1.000 -1.000-1.000 0-999.9 0-999.9 0-999.9 0-999.9 0-999.9 0-999.9 1.0-999.9 1.0-999.9 1.0-999.9 0-100.0 0-100.0 0-100.0 0-Vmax 0-Vmax 0-Vmax 0-Ixmax 0-Ixmax 0-Ixmax Units U3 U3 U3 0.001 0.001 0.001 0.1% 0.1% 0.1% 0.1% 0.1% 0.1% 0.1 0.1 0.1 0.1% 0.1% 0.1% U1 U1 U1 U2 U2 U2 Type R/W UINT16 UINT16 UINT16 INT16 INT16 INT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 R R R R R R R R R R R R R R R R R R R R R R R R 0-Vmax 0-Imax -Pmax-Pmax -Pmax-Pmax 0-Pmax 0-1.000 0-1.000 0-999.9 0-999.9 1.0-999.9 0-100.0 0-Vmax 0-999.9 0-999.9 U1 U2 U3 U3 U3 0.001 0.001 0.1% 0.1% 0.1 0.1% U1 0.1% 0.1% UINT16 UINT16 INT16 INT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 R R R R R R R R R R R R R R 0-Vmax 0-Imax -Pmax-Pmax U1 U2 U3 UINT16 UINT16 INT16 R R R Notes 2, 4 2, 4 2, 4 4 4 4 4 4 4 4 4 4 2, 4 4 4 4 2, 4 4 23 Address +3 +4 +5 +5 +7 +8 +9 +10 +11 +12 +13 4544-4557 +0 +1 +2 +3 +4 +5 +5 +7 +8 +9 +10 +11 +12 +13 4608-4556 +0 +1 +2 +3 +4 +5 +5 +7 4640-4655 +0 +1 +2 +3 +4 +5 +5 24 Point ID Description 0x0E03 0x0E04 0x0E05 0x0E06 0x0E07 0x0E08 0x0E09 0x0E0A 0x0E0B 0x0E0C 0x0E0D High kvar High kVA High PF Lag High PF Lead High voltage THD High current THD High K-Factor High current TDD High L-L voltage High voltage interharmonics THD High current interharmonics THD 1-Cycle Total Values Total kW Total kvar Total kVA Total PF Total PF lag Total PF lead Total kW import Total kW export Total kvar import Total kvar export 3-phase average L-N voltage 3-phase average L-L voltage 3-phase average current 3-phase average current, extended inputs I1x-I3x 1-Cycle Auxiliary Values I4 current In current Frequency Voltage unbalance Current unbalance DC voltage V4 voltage I4x current Fundamental Phasor Values V1 voltage magnitude V2 voltage magnitude V3 voltage magnitude V4 voltage magnitude I1 current magnitude I2 current magnitude I3 current magnitude 0x0F00 0x0F01 0x0F02 0x0F03 0x0F04 0x0F05 0x0F06 0x0F07 0x0F08 0x0F09 0x0F0A 0x0F0B 0x0F0C 0x0F0D 0x1000 0x1001 0x1002 0x1003 0x1004 0x1005 0x1006 0x1007 0x1080 0x1081 0x1082 0x1083 0x1084 0x1085 0x1086 3 3 Low and High Scales -Pmax-Pmax 0-Pmax 0-1.000 0-1.000 0-999.9 0-999.9 1.0-999.9 0-100.0 0-Vmax 0-999.9 0-999.9 Units U3 U3 0.001 0.001 0.1% 0.1% 0.1 0.1% U1 0.1% 0.1% Type R/W INT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 R R R R R R R R R R R -Pmax-Pmax -Pmax-Pmax 0-Pmax -1.000-1.000 0-1.000 0-1.000 0-Pmax 0-Pmax 0-Pmax 0-Pmax 0-Vmax 0-Vmax 0-Imax 0-Ixmax U3 U3 U3 0.001 0.001 0.001 U3 U3 U3 U3 U1 U1 U2 U2 INT16 INT16 UINT16 INT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 R R R R R 0-I4max 0-Imax 0-100.00 0-300.0 0-300.0 0-9999.00 0-V4max 0-I4xmax U2 U2 0.01Hz 0.1% 0.1% 0.01V U4 U2 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 R R R R R R R R 0-Vmax 0-Vmax 0-Vmax 0-V4max 0-Imax 0-Imax 0-Imax U1 U1 U1 U1 U2 U2 U2 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 R R R R R R R Notes 2, 4 4 4 4 2, 4 4 R R R R R R R 2 2 2 Address +7 +8 +9 +10 +11 +12 +13 +14 +15 4672-4707 +0 +1 +2 +3 +4 +5 +6 +7 +8 +9 +10 +11 +12 +13 +14 +15 +16 +17 +18 +19 +20 +21 +22 +23 +24 +25 +26 +27 +28 +29 +30 +31 +32 Point ID Description 0x1087 0x1088 0x1089 0x108A 0x108B 0x108C 0x108D 0x108E 0x108F I4 current magnitude V1 voltage angle V2 voltage angle V3 voltage angle V4 voltage angle I1 current angle I2 current angle I3 current angle I4 current angle 1-Second Phase Values V1 voltage V2 voltage V3 voltage I1 current I2 current I3 current kW L1 kW L2 kW L3 kvar L1 kvar L2 kvar L3 kVA L1 kVA L2 kVA L3 Power factor L1 Power factor L2 Power factor L3 V1 voltage THD V2 voltage THD V3 voltage THD I1 current THD I2 current THD I3 current THD I1 K-Factor I2 K-Factor I3 K-Factor I1 current TDD I2 current TDD I3 current TDD V12 voltage V23 voltage V31 voltage 0x1100 0x1101 0x1102 0x1103 0x1104 0x1105 0x1106 0x1107 0x1108 0x1109 0x110A 0x110B 0x110C 0x110D 0x110E 0x110F 0x1110 0x1111 0x1112 0x1113 0x1114 0x1115 0x1116 0x1117 0x1118 0x1119 0x111A 0x111B 0x111C 0x111D 0x111E 0x111F 0x1120 3 3 Low and High Scales 0-Imax -180.0-180.0 -180.0-180.0 -180.0-180.0 -180.0-180.0 -180.0-180.0 -180.0-180.0 -180.0-180.0 -180.0-180.0 Units U2 0.1º 0.1º 0.1º 0.1º 0.1º 0.1º 0.1º 0.1º Type R/W UINT16 INT16 INT16 INT16 INT16 INT16 INT16 INT16 INT16 R R R R R R R R R 0-Vmax 0-Vmax 0-Vmax 0-Imax 0-Imax 0-Imax -Pmax-Pmax -Pmax-Pmax -Pmax-Pmax -Pmax-Pmax -Pmax-Pmax -Pmax-Pmax 0-Pmax 0-Pmax 0-Pmax -1.000-1.000 -1.000-1.000 -1.000-1.000 0-999.9 0-999.9 0-999.9 0-999.9 0-999.9 0-999.9 1.0-999.9 1.0-999.9 1.0-999.9 0-100.0 0-100.0 0-100.0 0-Vmax 0-Vmax 0-Vmax U1 U1 U1 U2 U2 U2 U3 U3 U3 U3 U3 U3 U3 U3 U3 0.001 0.001 0.001 0.1% 0.1% 0.1% 0.1% 0.1% 0.1% 0.1 0.1 0.1 0.1% 0.1% 0.1% U1 U1 U1 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 INT16 INT16 INT16 INT16 INT16 INT16 UINT16 UINT16 UINT16 INT16 INT16 INT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R Notes 2 2 2 1 1 1 2, 5 2, 5 2, 5 5 5 5 5 5 5 5 5 5 25 Address +33 +34 +35 4736-4749 +0 +1 +2 +3 +4 +5 +5 +7 +8 +9 +10 +11 +12 +13 4800-4813 +0 +1 +2 +3 +4 +5 +5 +7 +8 +9 +10 +11 +12 +13 4864-4877 +0 +1 +2 +3 +4 +5 +5 +7 +8 26 Point ID Description 0x1121 0x1122 0x1123 I1x current I2x current I3x current 1-Second Low Phase Values Low L-N voltage Low current Low kW Low kvar Low kVA Low PF Lag Low PF Lead Low voltage THD Low current THD Low K-Factor Low current TDD Low L-L voltage Low voltage interharmonics THD Low current interharmonics THD 1-Second High Phase Values High L-N voltage High current High kW High kvar High kVA High PF Lag High PF Lead High voltage THD High current THD High K-Factor High current TDD High L-L voltage High voltage interharmonics THD High current interharmonics THD 1-Second Total Values Total kW Total kvar Total kVA Total PF Total PF lag Total PF lead Total kW import Total kW export Total kvar import 0x1200 0x1201 0x1202 0x1203 0x1204 0x1205 0x1206 0x1207 0x1208 0x1209 0x120A 0x120B 0x120C 0x120D 0x1300 0x1301 0x1302 0x1303 0x1304 0x1305 0x1306 0x1307 0x1308 0x1309 0x130A 0x130B 0x130C 0x130D 0x1400 0x1401 0x1402 0x1403 0x1404 0x1405 0x1406 0x1407 0x1408 3 3 Low and High Scales 0-Ixmax 0-Ixmax 0-Ixmax Units U2 U2 U2 Type R/W UINT16 UINT16 UINT16 R R R 0-Vmax 0-Imax -Pmax-Pmax -Pmax-Pmax 0-Pmax 0-1.000 0-1.000 0-999.9 0-999.9 1.0-999.9 0-100.0 0-Vmax 0-999.9 0-999.9 U1 U2 U3 U3 U3 0.001 0.001 0.1% 0.1% 0.1 0.1% U1 0.1% 0.1% UINT16 UINT16 INT16 INT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 R R R R R R R R R R R R R R 0-Vmax 0-Imax -Pmax-Pmax -Pmax-Pmax 0-Pmax 0-1.000 0-1.000 0-999.9 0-999.9 1.0-999.9 0-100.0 0-Vmax 0-999.9 0-999.9 U1 U2 U3 U3 U3 0.001 0.001 0.1% 0.1% 0.1 0.1% U1 0.1% 0.1% UINT16 UINT16 INT16 INT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 R R R R R R R R R R R R R R -Pmax-Pmax -Pmax-Pmax 0-Pmax -1.000-1.000 0-1.000 0-1.000 0-Pmax 0-Pmax 0-Pmax U3 U3 U3 0.001 0.001 0.001 U3 U3 U3 INT16 INT16 UINT16 INT16 UINT16 UINT16 UINT16 UINT16 UINT16 R R R R R R R Notes 2, 5 5 5 5 2, 5 5 2, 5 5 5 5 2, 5 5 Address +9 +10 +11 +12 +13 4928-4935 +0 +1 +2 +3 +4 +5 +5 +7 4960-4971 +0 +1 +2 +3 +4 +5 +5 +7 +8 +9 +10 +11 4992-5026 +0 +1 +2 +3 +4 +5 +6 +7 +8 +9 +10 +11 +12 +13 +14 Point ID Description 0x1409 0x140A 0x140B 0x140C 0x140D Total kvar export 3-phase average L-N voltage 3-phase average L-L voltage 3-phase average current 3-phase average current, extended inputs I1x-I3x 1-Second Auxiliary Values I4 current In current Frequency Voltage unbalance Current unbalance DC voltage V4 voltage I4x current Present Harmonic Demands V1 THD demand V2 THD demand V3 THD demand V4 THD demand I1 THD demand I2 THD demand I3 THD demand I4 THD demand I1 TDD demand I2 TDD demand I3 TDD demand I4 TDD demand Present Volt, Ampere and Power Demands V1 Volt demand V2 Volt demand V3 Volt demand I1 Ampere demand I2 Ampere demand I3 Ampere demand kW import block demand kvar import block demand kVA block demand kW import sliding window demand kvar import sliding window demand kVA sliding window demand Not used Not used Not used 0x1500 0x1501 0x1502 0x1503 0x1504 0x1505 0x1506 0x1507 0x1580 0x1581 0x1582 0x1583 0x1584 0x1585 0x1586 0x1587 0x1588 0x1589 0x158A 0x158B 0x1600 0x1601 0x1602 0x1603 0x1604 0x1605 0x1606 0x1607 0x1608 0x1609 0x160A 0x160B 0x160C 0x160D 0x160E 3 3 Low and High Scales 0-Pmax 0-Vmax 0-Vmax 0-Imax 0-Ixmax Units U3 U1 U1 U2 U2 Type R/W UINT16 UINT16 UINT16 UINT16 UINT16 R R R R R Notes 0-I4max 0-Imax 0-100.00 0-300.0 0-300.0 0-9999.00 0-V4max 0-I4xmax U2 U2 0.01Hz 0.1% 0.1% 0.01V U4 U2 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 R R R R R R R R 0-999.9 0-999.9 0-999.9 0-999.9 0-999.9 0-999.9 0-999.9 0-999.9 0-100.0 0-100.0 0-100.0 0-100.0 0.1% 0.1% 0.1% 0.1% 0.1% 0.1% 0.1% 0.1% 0.1% 0.1% 0.1% 0.1% UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 R R R R R R R R R R R R 2 0-Vmax 0-Vmax 0-Vmax 0-Imax 0-Imax 0-Imax 0-Pmax 0-Pmax 0-Pmax 0-Pmax 0-Pmax 0-Pmax 0 0 0 U1 U1 U1 U2 U2 U2 U3 U3 U3 U3 U3 U3 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 R R R R R R R R R R R R R R R 2 2 2 2 2 27 Address +15 +16 +17 +18 +19 +20 +21 +22 +23 +24 +25 +26 +27 +28 +29 +30 +31 +32 +33 +34 5152-5161 +0 +1 +2 +3 +4 +5 +6 +7 +8 +9 5184-5246 +0 +1 Point ID Description 0x160F 0x1610 0x1611 0x1612 0x1613 0x1614 0x1615 0x1616 0x1617 0x1618 0x1619 0x161A 0x161B 0x161C 0x161D 0x161E 0x161F 0x1620 0x1621 0x1622 kW import accumulated demand kvar import accumulated demand kVA accumulated demand kW import predicted sliding window demand kvar import predicted sliding window demand kVA predicted sliding window demand PF (import) at Max. kVA sliding window demand kW export block demand kvar export block demand kW export sliding window demand kvar export sliding window demand kW export accumulated demand kvar export accumulated demand kW export predicted sliding window demand kvar export predicted sliding window demand Not used Not used V4 volt demand I4 ampere demand In ampere demand Symmetrical Components Positive-sequence voltage Negative-sequence voltage Zero-sequence voltage Negative-sequence voltage unbalance Zero-sequence voltage unbalance Positive-sequence current Negative-sequence current Zero-sequence current Negative-sequence current unbalance Zero-sequence current unbalance V1 Harmonics H01 Harmonic distortion H02 Harmonic distortion ... H63 Harmonic distortion V2 Harmonics H01 Harmonic distortion H02 Harmonic distortion ... H63 Harmonic distortion 0x1880 0x1881 0x1882 0x1883 0x1884 0x1885 0x1886 0x1887 0x1888 0x1889 0x1900 0x1901 +62 0x193E 5248-5310 +0 0x1A00 +1 0x1A01 +62 0x1A3E 28 3 3 Type R/W U4 U2 U2 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 R R R R R R R R R R R R R R R R R R R R 0-Vmax 0-Vmax 0-Vmax 0-300.0 0-300.0 0-Imax 0-Imax 0-Imax 0-300.0 0-300.0 U1 U1 U1 0.1% 0.1% U2 U2 U2 0.1% 0.1% UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 R R R R R R R R R R 0-100.00 0-100.00 0.01% 0.01% UINT16 UINT16 R R 0-100.00 0.01% UINT16 R 0-100.00 0-100.00 0.01% 0.01% UINT16 UINT16 R R 0-100.00 0.01% UINT16 R Low and High Scales 0-Pmax 0-Pmax 0-Pmax 0-Pmax 0-Pmax 0-Pmax 0-1.000 0-Pmax 0-Pmax 0-Pmax 0-Pmax 0-Pmax 0-Pmax 0-Pmax 0-Pmax 0 0 0-Vmax 0-Imax 0-Imax Units U3 U3 U3 U3 U3 U3 0.001 U3 U3 U3 U3 U3 U3 U3 U3 Notes 2 2 Address Point ID 5312-5374 +0 0x1B00 +1 0x1B01 +62 0x1B3E 5376-5438 +0 0x1C00 +1 0x1C01 +62 0x1C3E 5440-5502 +0 0x1D00 +1 0x1D01 +62 0x1D3E 5504-5566 +0 0x1E00 +1 0x1E01 +62 0x1E3E 5568-5599 +0 0x1F00 +1 0x1F01 +31 0x1F3E 5632-5663 +0 0x2000 +1 0x2001 +31 0x203E 5696-5727 +0 0x2100 +1 0x2101 +31 0x213E 5760-5791 +0 0x2200 +1 0x2201 +31 0x223E Description V3 Harmonics H01 Harmonic distortion H02 Harmonic distortion ... H63 Harmonic distortion I1 Harmonics H01 Harmonic distortion H02 Harmonic distortion ... H63 Harmonic distortion I2 Harmonics H01 Harmonic distortion H02 Harmonic distortion ... H63 Harmonic distortion I3 Harmonics H01 Harmonic distortion H02 Harmonic distortion ... H63 Harmonic distortion V1 Harmonic Voltages (odd numbers) H01 Harmonic voltage H03 Harmonic voltage ... H63 Harmonic voltage V2 Harmonic Voltages (odd numbers) H01 Harmonic voltage H03 Harmonic voltage ... H63 Harmonic voltage V3 Harmonic Voltages (odd numbers) H01 Harmonic voltage H03 Harmonic voltage ... H63 Harmonic voltage I1 Harmonic Currents (odd numbers) H01 Harmonic current H03 Harmonic current ... H63 Harmonic current 3 3 Low and High Scales Units Type R/W 0-100.00 0-100.00 0.01% 0.01% UINT16 UINT16 R R 0-100.00 0.01% UINT16 R 0-100.00 0-100.00 0.01% 0.01% UINT16 UINT16 R R 0-100.00 0.01% UINT16 R 0-100.00 0-100.00 0.01% 0.01% UINT16 UINT16 R R 0-100.00 0.01% UINT16 R 0-100.00 0-100.00 0.01% 0.01% UINT16 UINT16 R R 0-100.00 0.01% UINT16 R 0-Vmax 0-Vmax U1 U1 UINT16 UINT16 R R 0-Vmax U1 UINT16 R 0-Vmax 0-Vmax U1 U1 UINT16 UINT16 R R 0-Vmax U1 UINT16 R 0-Vmax 0-Vmax U1 U1 UINT16 UINT16 R R 0-Vmax U1 UINT16 R 0-Imax 0-Imax U2 U2 UINT16 UINT16 R R 0-Imax U2 UINT16 R Notes 2 2 2 2 29 Address Point ID 5824-5855 +0 0x2300 +1 0x2301 +31 0x233E 5888-5919 +0 0x2400 +1 0x2401 +31 0x243E 5952-5983 +0 0x2500 +1 0x2501 +31 0x253E 6016-6047 +0 0x2600 +1 0x2601 +31 0x263E 6080-6111 +0 0x2700 +1 0x2701 +31 0x273E 6144-6206 +0 0x2800 +1 0x2801 +62 6240-6245 +0 +1 +2 +3 +4 +5 6336-6398 +0 +1 30 0x283E 0x2980 0x2981 0x2982 0x2983 0x2984 0x2985 0x2B00 0x2B01 Description I2 Harmonic Currents (odd numbers) H01 Harmonic current H03 Harmonic current ... H63 Harmonic current I3 Harmonic Currents (odd numbers) H01 Harmonic current H03 Harmonic current ... H63 Harmonic current Total Harmonic kW (odd numbers) H01 Harmonic kW H03 Harmonic kW ... H63 Harmonic kW Total Harmonic kvar (odd numbers) H01 Harmonic kvar H03 Harmonic kvar ... H63 Harmonic kvar Total Harmonic Power Factor (odd numbers) H01 Harmonic PF H03 Harmonic PF ... H63 Harmonic PF V4 Harmonics H01 Harmonic distortion H02 Harmonic distortion ... H63 Harmonic distortion Flicker V1 Pst V2 Pst V3 Pst V1 Plt V2 Plt V3 Plt I4 Harmonics H01 Harmonic distortion H02 Harmonic distortion ... 3 3 Low and High Scales Units Type R/W 0-Imax 0-Imax U2 U2 UINT16 UINT16 R R 0-Imax U2 UINT16 R 0-Imax 0-Imax U2 U2 UINT16 UINT16 R R 0-Imax U2 UINT16 R -Pmax -Pmax -Pmax -Pmax U3 U3 INT16 INT16 R R -Pmax -Pmax U3 INT16 R -Pmax -Pmax -Pmax -Pmax U3 U3 INT16 INT16 R R -Pmax -Pmax U3 INT16 R -1.000-1.000 -1.000-1.000 0.001 0.001 INT16 INT16 R R -1.000-1.000 0.001 INT16 R 0-100.00 0-100.00 0.01% 0.01% UINT16 UINT16 R R 0-100.00 0.01% UINT16 R 0-100.00 0-100.00 0-100.00 0-100.00 0-100.00 0-100.00 0.01 0.01 0.01 0.01 0.01 0.01 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 R R R R R R 0-100.00 0-100.00 0.01% 0.01% UINT16 UINT16 R R Notes 2 2 2 2 2 2 Address +62 6400-6435 +0 +1 +2 +3 +4 +5 +6 +7 +8 +9 +10 +11 +12 +13 +14 +15 +16 +17 +18 +19 +20 +21 +22 +23 +24 +25 +26 +27 +28 +29 +30 +31 +32 +33 +34 +35 6464-6469 +0 +1 +2 +3 Point ID 0x2B3E 0x2C00 0x2C01 0x2C02 0x2C03 0x2C04 0x2C05 0x2C06 0x2C07 0x2C08 0x2C09 0x2C0A 0x2C0B 0x2C0C 0x2C0D 0x2C0E 0x2C0F 0x2C10 0x2C11 0x2C12 0x2C13 0x2C14 0x2C15 0x2C16 0x2C17 0x2C18 0x2C19 0x2C1A 0x2C1B 0x2C1C 0x2C1D 0x2C1E 0x2C1F 0x2C20 0x2C21 0x2C22 0x2C23 0x2D00 0x2D01 0x2D02 0x2D03 Description H63 Harmonic distortion Minimum 1-Cycle Phase Values V1 voltage V2 voltage V3 voltage I1 current I2 current I3 current kW L1 kW L2 kW L3 kvar L1 kvar L2 kvar L3 kVA L1 kVA L2 kVA L3 Power factor L1 Power factor L2 Power factor L3 V1 voltage THD V2 voltage THD V3 voltage THD I1 current THD I2 current THD I3 current THD I1 K-Factor I2 K-Factor I3 K-Factor I1 current TDD I2 current TDD I3 current TDD V12 voltage V23 voltage V31 voltage I1x current I2x current I3x current Minimum 1-Cycle Total Values Total kW Total kvar Total kVA Total PF 3 3 Low and High Scales 0-100.00 Units 0.01% Type R/W UINT16 R 0-Vmax 0-Vmax 0-Vmax 0-Imax 0-Imax 0-Imax -Pmax-Pmax -Pmax-Pmax -Pmax-Pmax -Pmax-Pmax -Pmax-Pmax -Pmax-Pmax 0-Pmax 0-Pmax 0-Pmax 0-1.000 0-1.000 0-1.000 0-9999 0-9999 0-999.9 0-999.9 0-999.9 0-999.9 1.0-999.9 1.0-999.9 1.0-999.9 0-100.0 0-100.0 0-100.0 0-Vmax 0-Vmax 0-Vmax 0-Ixmax 0-Ixmax 0-Ixmax U1 U1 U1 U2 U2 U2 U3 U3 U3 U3 U3 U3 U3 U3 U3 0.001 0.001 0.001 0.1% 0.1% 0.1% 0.1% 0.1% 0.1% 0.1 0.1 0.1 0.1% 0.1% 0.1% U1 U1 U1 U2 U2 U2 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 INT16 INT16 INT16 INT16 INT16 INT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R -Pmax-Pmax -Pmax-Pmax 0-Pmax 0-1.000 U3 U3 U3 0.001 INT16 INT16 UINT16 UINT16 R R R R Notes 1 1 1 Absolute value Absolute value Absolute value 2, 4 2, 4 2, 4 4 4 4 4 4 4 4 4 4 Absolute value 31 Address +4 +5 6528-6538 +0 +1 +2 +3 +4 +5 +6 +7 +8 +9 +10 6656-6671 +0 +1 Point ID Description 0x2D04 0x2D05 Total PF lag Total PF lead Minimum 1-Cycle Auxiliary Values I4 current In current Frequency Voltage unbalance Current unbalance DC voltage V4 voltage I4x current V4 THD I4x THD I4x TDD Programmable Min/Max Minimum Values Min/Max Register #1 Min/Max Register #2 … Min/Max Register #16 V4 Harmonic Voltages (odd numbers) H01 Harmonic voltage H03 Harmonic voltage ... H63 Harmonic voltage I4 Harmonic Currents (odd numbers) H01 Harmonic current H03 Harmonic current ... H63 Harmonic current Maximum 1-Cycle Phase Values V1 voltage V2 voltage V3 voltage I1 current I2 current I3 current kW L1 kW L2 kW L3 kvar L1 kvar L2 kvar L3 0x2E00 0x2E01 0x2E02 0x2E03 0x2E04 0x2E05 0x2E06 0x2E07 0x2E08 0x2E09 0x2E0A 0x3000 0x3001 +15 0x300F 6720-6751 +0 0x3100 +1 0x3101 +31 0x313E 6784-6815 +0 0x3200 +1 0x3201 +31 6912-6947 +0 +1 +2 +3 +4 +5 +6 +7 +8 +9 +10 +11 32 0x323E 0x3400 0x3401 0x3402 0x3403 0x3404 0x3405 0x3406 0x3407 0x3408 0x3409 0x340A 0x340B 3 3 Low and High Scales 0-1.000 0-1.000 Units 0.001 0.001 Type R/W UINT16 UINT16 R R 0-I4max 0-Imax 0-100.00 0-300.0 0-300.0 0-9999.00 0-V4max 0-I4xmax 0-999.9 0-999.9 0-100.0 U2 U2 0.01Hz 0.1% 0.1% 0.01V U4 U2 0.1% 0.1% 0.1% UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 R R R R R R R R R R R UINT16 UINT16 R R UINT16 R 0-Vmax 0-Vmax U1 U1 UINT16 UINT16 R R 0-Vmax U1 UINT16 R 0-Imax 0-Imax U2 U2 UINT16 UINT16 R R 0-Imax U2 UINT16 R 0-Vmax 0-Vmax 0-Vmax 0-Imax 0-Imax 0-Imax -Pmax-Pmax -Pmax-Pmax -Pmax-Pmax -Pmax-Pmax -Pmax-Pmax -Pmax-Pmax U1 U1 U1 U2 U2 U2 U3 U3 U3 U3 U3 U3 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 INT16 INT16 INT16 INT16 INT16 INT16 R R R R R R R R R R R R Notes 4 4 4 1 1 1 Address +12 +13 +14 +15 +16 +17 +18 +19 +20 +21 +22 +23 +24 +25 +26 +27 +28 +29 +30 +31 +32 +33 +34 +35 6976-6981 +0 +1 +2 +3 +4 +5 7040-7050 +0 +1 +2 +3 +4 +5 +6 +7 +8 +9 +10 Point ID Description 0x340C 0x340D 0x340E 0x340F 0x3410 0x3411 0x3412 0x3413 0x3414 0x3415 0x3416 0x3417 0x3418 0x3419 0x341A 0x341B 0x341C 0x341D 0x341E 0x341F 0x3420 0x3421 0x3422 0x3423 kVA L1 kVA L2 kVA L3 Power factor L1 Power factor L2 Power factor L3 V1 voltage THD V2 voltage THD V3 voltage THD I1 current THD I2 current THD I3 current THD I1 K-Factor I2 K-Factor I3 K-Factor I1 current TDD I2 current TDD I3 current TDD V12 voltage V23 voltage V31 voltage I1x current I2x current I3x current Maximum 1-Cycle Total Values Total kW Total kvar Total kVA Total PF Total PF lag Total PF lead Maximum 1-Cycle Auxiliary Values I4 current In current Frequency Voltage unbalance Current unbalance DC voltage V4 voltage I4x current V4 THD I4x THD I4x TDD 0x3500 0x3501 0x3502 0x3503 0x3504 0x3505 0x3600 0x3601 0x3602 0x3603 0x3604 0x3605 0x3606 0x3607 0x3608 0x3609 0x360A 3 3 Low and High Scales 0-Pmax 0-Pmax 0-Pmax 0-1.000 0-1.000 0-1.000 0-999.9 0-999.9 0-999.9 0-999.9 0-999.9 0-999.9 1.0-999.9 1.0-999.9 1.0-999.9 0-100.0 0-100.0 0-100.0 0-Vmax 0-Vmax 0-Vmax 0-Ixmax 0-Ixmax 0-Ixmax Units U3 U3 U3 0.001 0.001 0.001 0.1% 0.1% 0.1% 0.1% 0.1% 0.1% 0.1 0.1 0.1 0.1% 0.1% 0.1% U1 U1 U1 U2 U2 U2 Type R/W UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 R R R R R R R R R R R R R R R R R R R R R R R R -Pmax-Pmax -Pmax-Pmax 0-Pmax 0-1.000 0-1.000 0-1.000 U3 U3 U3 0.001 0.001 0.001 INT16 INT16 UINT16 UINT16 UINT16 UINT16 R R R R R R 0-I4max 0-Imax 0-100.00 0-300.0 0-300.0 0-9999.00 0-V4max 0-I4xmax 0-999.9 0-999.9 0-100.0 U2 U2 0.01Hz 0.1% 0.1% 0.01V U4 U2 0.1% 0.1% 0.1% UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 R R R R R R R R R R R Notes Absolute value Absolute value Absolute value 2, 4 2, 4 2, 4 4 4 4 4 4 4 4 4 4 Absolute value 4 4 4 33 Address 7104-71025 +0 +1 +2 +3 +4 +5 +6 +7 +8 +9 +10 +11 +12 +13 +14 +15 +16 +17 +18 +19 +20 +21 7168-7183 +0 +1 +15 7200-7211 +0 +1 +2 +3 +4 +5 +6 +7 +8 +9 +10 +11 7360-7375 +0 34 Point ID 0x3700 0x3701 0x3702 0x3703 0x3704 0x3705 0x3706 0x3707 0x3708 0x3709 0x370A 0x370B 0x370C 0x370D 0x370E 0x370F 0x3710 0x3711 0x3712 0x3713 0x3714 0x3715 0x3800 0x3801 0x380F 0x3880 0x3881 0x3882 0x3883 0x3884 0x3885 0x3886 0x3887 0x3888 0x3889 0x388A 0x388B 0x3B00 Description Maximum Demands V1 Maximum volt demand V2 Maximum volt demand V3 Maximum volt demand I1 Maximum ampere demand I2 Maximum ampere demand I3 Maximum ampere demand Not used Not used Not used Maximum kW import sliding window demand Maximum kvar import sliding window demand Maximum kVA sliding window demand Not used Not used Not used Maximum kW export sliding window demand Maximum kvar export sliding window demand Not used Not used V4 Maximum volt demand I4 Maximum ampere demand In Maximum ampere demand Programmable Min/Max Maximum Values Min/Max Register #1 Min/Max Register #2 … Min/Max Register #16 Maximum Harmonic Demands V1 THD demand V2 THD demand V3 THD demand V4 THD demand I1 THD demand I2 THD demand I3 THD demand I4 THD demand I1 TDD demand I2 TDD demand I3 TDD demand I4 TDD demand Scaled Analog Inputs Analog input AI1 3 3 Low and High Scales Units Type R/W Notes 0-Vmax 0-Vmax 0-Vmax 0-Imax 0-Imax 0-Imax 0 0 0 0-Pmax 0-Pmax 0-Pmax 0 0 0 0-Pmax 0-Pmax 0 0 0-Vmax 0-I4max 0-Imax U1 U1 U1 U2 U2 U2 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 R R R R R R R R R R R R R R R R R R R R R R 2 UINT16 UINT16 R R UINT16 R UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 R R R R R R R R R R R R UINT16 R 0-999.9 0-999.9 0-999.9 0-999.9 0-999.9 0-999.9 0-999.9 0-999.9 0-100.0 0-100.0 0-100.0 0-100.0 AI1min-AI1max U3 U3 U3 U3 U3 U4 U2 U2 0.1% 0.1% 0.1% 0.1% 0.1% 0.1% 0.1% 0.1% 0.1% 0.1% 0.1% 0.1% 2 2 2 2 2 Address Point ID +1 0x3B01 +15 0x3B0F 7392-7407 +0 0x3B80 +1 0x3B81 +15 0x3B8F 7424-7439 +0 0x3C80 +1 0x3C81 +15 0x3C8F 8000-8015 +0 0x4500 +1 0x4501 +15 0x4503 8032-8047 +0 0x4580 +1 0x4581 +15 0x4583 8064-8079 +0 0x4600 +1 0x4601 +15 0x4603 8160-8175 +0 0x4780 +1 0x4781 +15 0x4783 8192-8207 +0 0x4800 +1 0x4801 +15 0x480F 8224-8239 +0 0x4880 +1 0x4881 Description Analog input AI2 … Analog input AI16 Raw Analog Inputs Analog input AI1 Analog input AI2 … Analog input AI16 Scaled Analog Outputs Analog input AO1 Analog input AO2 … Analog input AO16 Summary Energy Accumulated Demands Summary register #1 Summary register #2 … Summary register #16 Summary Energy Block Demands Summary register #1 Summary register #2 … Summary register #16 Summary Energy Sliding Window Demands Summary register #1 Summary register #2 … Summary register #16 Summary Energy Maximum Demands Summary register #1 Summary register #2 … Summary register #16 TOU Maximum Demand Register #1 Tariff #1 register Tariff #2 register … Tariff #16 register TOU Maximum Demand Register #4 Tariff #1 register Tariff #2 register 3 3 Type R/W UINT16 R AI16min-AI16max UINT16 R 0-4095 0-4095 UINT16 UINT16 R R 0-4095 UINT16 R 0-4095 0-4095 UINT16 UINT16 R/W R/W 0-4095 UINT16 R/W Low and High Scales AI2min-AI2max Units 0-Pmax 0-Pmax U3 U3 UINT16 UINT16 R R 0-Pmax U3 UINT16 R 0-Pmax 0-Pmax U3 U3 UINT16 UINT16 R R 0-Pmax U3 UINT16 R 0-Pmax 0-Pmax U3 U3 UINT16 UINT16 R R 0-Pmax U3 UINT16 R 0-Pmax 0-Pmax U3 U3 UINT16 UINT16 R R 0-Pmax U3 UINT16 R 0-Pmax 0-Pmax U3 U3 UINT16 UINT16 0-Pmax U3 UINT16 R R R R 0-Pmax 0-Pmax U3 U3 UINT16 UINT16 R R Notes 35 Address Point ID +15 0x488F 8256-8271 +0 0x4900 +1 0x4901 +15 0x490F 8288-8303 +0 0x4980 +1 0x4981 +15 0x498F 8320-8335 +0 0x4A00 +1 0x4A01 +15 0x4A0F 8352-8367 +0 0x4A80 +1 0x4A81 +15 0x4A8F 8896-8911 +0 0x5300 +1 0x5301 +15 0x530F 8928-8943 +0 0x5380 +1 0x5381 +15 0x538F 8960-8975 +0 0x5400 +1 0x5401 +15 0x540F 8992-9007 +0 0x5480 +1 0x5481 36 Description … Tariff #16 register TOU Maximum Demand Register #2 Tariff #1 register Tariff #2 register … Tariff #16 register TOU Maximum Demand Register #5 Tariff #1 register Tariff #2 register … Tariff #16 register TOU Maximum Demand Register #3 Tariff #1 register Tariff #2 register … Tariff #16 register TOU Maximum Demand Register #6 Tariff #1 register Tariff #2 register … Tariff #16 register TOU Maximum Demand Register #7 Tariff #1 register Tariff #2 register … Tariff #16 register TOU Maximum Demand Register #8 Tariff #1 register Tariff #2 register … Tariff #16 register TOU Maximum Demand Register #9 Tariff #1 register Tariff #2 register … Tariff #16 register TOU Maximum Demand Register #10 Tariff #1 register Tariff #2 register … 3 Low and High Scales 3 Units Type R/W R R 0-Pmax U3 UINT16 0-Pmax 0-Pmax U3 U3 UINT16 UINT16 0-Pmax U3 UINT16 0-Pmax 0-Pmax U3 U3 UINT16 UINT16 0-Pmax U3 UINT16 0-Pmax 0-Pmax U3 U3 UINT16 UINT16 0-Pmax U3 UINT16 0-Pmax 0-Pmax U3 U3 UINT16 UINT16 0-Pmax U3 UINT16 0-Pmax 0-Pmax U3 U3 UINT16 UINT16 0-Pmax U3 UINT16 0-Pmax 0-Pmax U3 U3 UINT16 UINT16 0-Pmax U3 UINT16 0-Pmax 0-Pmax U3 U3 UINT16 UINT16 0-Pmax U3 UINT16 0-Pmax 0-Pmax U3 U3 UINT16 UINT16 R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R Notes Address Point ID +15 0x548F 9024-9039 +0 0x5500 +1 0x5501 +15 0x550F 9056-9071 +0 0x5580 +1 0x5581 +15 0x558F 9088-9103 +0 0x5600 +1 0x5601 +15 0x560F 9120-9135 +0 0x5680 +1 0x5681 +15 0x568F 9152-9167 +0 0x5700 +1 0x5701 +15 0x570F 9184-9199 +0 0x5780 +1 0x5781 +15 10496-10520 +0 +1 +2 +3 +4 +5 +6 +7 +8 0x578F 0x6C00 0x6C01 0x6C02 0x6C03 0x6C04 0x6C05 0x6C06 0x6C07 0x6C08 Description Tariff #16 register TOU Maximum Demand Register #11 Tariff #1 register Tariff #2 register … Tariff #16 register TOU Maximum Demand Register #12 Tariff #1 register Tariff #2 register … Tariff #16 register TOU Maximum Demand Register #13 Tariff #1 register Tariff #2 register … Tariff #16 register TOU Maximum Demand Register #14 Tariff #1 register Tariff #2 register … Tariff #16 register TOU Maximum Demand Register #15 Tariff #1 register Tariff #2 register … Tariff #16 register TOU Maximum Demand Register #16 Tariff #1 register Tariff #2 register … Tariff #16 register 0.2-Second RMS and Auxiliary Values V1 voltage V2 voltage V3 voltage V4 voltage V12 voltage V23 voltage V31 voltage I1 current I2 current 3 3 Low and High Scales 0-Pmax Units U3 Type R/W UINT16 R 0-Pmax 0-Pmax U3 U3 UINT16 UINT16 0-Pmax U3 UINT16 R R R R 0-Pmax 0-Pmax U3 U3 UINT16 UINT16 0-Pmax U3 UINT16 0-Pmax 0-Pmax U3 U3 UINT16 UINT16 0-Pmax U3 UINT16 0-Pmax 0-Pmax U3 U3 UINT16 UINT16 0-Pmax U3 UINT16 0-Pmax 0-Pmax U3 U3 UINT16 UINT16 0-Pmax U3 UINT16 0-Pmax 0-Pmax U3 U3 UINT16 UINT16 0-Pmax U3 UINT16 R R R R 0-Vmax 0-Vmax 0-Vmax 0-V4max 0-Vmax 0-Vmax 0-Vmax 0-Imax 0-Imax U1 U1 U1 U4 U1 U1 U1 U2 U2 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 R R R R R R R R R Notes R R R R R R R R R R R R R R R R 1 1 1 37 Address +9 +10 +11 +12 +13 +14 +15 +16 +17 +18 +19 +20 +21 +22 +23 +24 10528-10552 +0 +1 +2 +3 +4 +5 +6 +7 +8 +9 +10 +11 +12 +13 +14 +15 +16 +17 +18 +19 +20 +21 +22 +23 +24 38 Point ID Description 0x6C09 0x6C0A 0x6C0B 0x6C0C 0x6C0D 0x6C0E 0x6C0F 0x6C10 0x6C11 0x6C12 0x6C13 0x6C14 0x6C15 0x6C16 0x6C17 0x6C18 I3 current I4 current In current I1x current I2x current I3x current I4x current Inx current Zero-sequence voltage Zero-sequence current Ix Zero-sequence current Voltage unbalance Current unbalance Ix current unbalance DC voltage Frequency 3-Second RMS and Auxiliary Values V1 voltage V2 voltage V3 voltage V4 voltage V12 voltage V23 voltage V31 voltage I1 current I2 current I3 current I4 current In current I1x current I2x current I3x current I4x current Inx current Zero-sequence voltage Zero-sequence current Ix Zero-sequence current Voltage unbalance Current unbalance Ix current unbalance DC voltage Frequency 0x6C80 0x6C81 0x6C82 0x6C83 0x6C84 0x6C85 0x6C86 0x6C87 0x6C88 0x6C89 0x6C8A 0x6C8B 0x6C8C 0x6C8D 0x6C8E 0x6C8F 0x6C90 0x6C91 0x6C92 0x6C93 0x6C94 0x6C95 0x6C96 0x6C97 0x6C98 3 3 Low and High Scales 0-Imax 0-I4max 0-Imax 0-Ixmax 0-Ixmax 0-Ixmax 0-I4xmax 0-Ixmax 0-Vmax 0-Imax 0-Ixmax 0-300.0 0-300.0 0-300.0 0-9999.00 0-100.00 Units U2 U2 U2 U2 U2 U2 U2 U2 U1 U2 U2 0.1% 0.1% 0.1% 0.01V 0.01Hz Type R/W UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 R R R R R R R R R R R R R R R R 0-Vmax 0-Vmax 0-Vmax 0-V4max 0-Vmax 0-Vmax 0-Vmax 0-Imax 0-Imax 0-Imax 0-I4max 0-Imax 0-Ixmax 0-Ixmax 0-Ixmax 0-I4xmax 0-Ixmax 0-Vmax 0-Imax 0-Ixmax 0-300.0 0-300.0 0-300.0 0-9999.00 0-100.00 U1 U1 U1 U4 U1 U1 U1 U2 U2 U2 U2 U2 U2 U2 U2 U2 U2 U1 U2 U2 0.1% 0.1% 0.1% 0.01V 0.01Hz UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 R R R R R R R R R R R R R R R R R R R R R R R R R Notes 1 1 1 Address 10560-10584 +0 +1 +2 +3 +4 +5 +6 +7 +8 +9 +10 +11 +12 +13 +14 +15 +16 +17 +18 +19 +20 +21 +22 +23 +24 10592-10616 +0 +1 +2 +3 +4 +5 +6 +7 +8 +9 +10 +11 +12 +13 +14 +15 Point ID 0x6D00 0x6D01 0x6D02 0x6D03 0x6D04 0x6D05 0x6D06 0x6D07 0x6D08 0x6D09 0x6D0A 0x6D0B 0x6D0C 0x6D0D 0x6D0E 0x6D0F 0x6D10 0x6D11 0x6D12 0x6D13 0x6D14 0x6D15 0x6D16 0x6D17 0x6D18 0x6D80 0x6D81 0x6D82 0x6D83 0x6D84 0x6D85 0x6D86 0x6D87 0x6D88 0x6D89 0x6D8A 0x6D8B 0x6D8C 0x6D8D 0x6D8E 0x6D8F Description 10-Minute RMS and Auxiliary Values V1 voltage V2 voltage V3 voltage V4 voltage V12 voltage V23 voltage V31 voltage I1 current I2 current I3 current I4 current In current I1x current I2x current I3x current I4x current Inx current Zero-sequence voltage Zero-sequence current Ix Zero-sequence current Voltage unbalance Current unbalance Ix current unbalance DC voltage Frequency 2-Hour RMS and Auxiliary Values V1 voltage V2 voltage V3 voltage V4 voltage V12 voltage V23 voltage V31 voltage I1 current I2 current I3 current I4 current In current I1x current I2x current I3x current I4x current 3 3 Low and High Scales Units Type R/W Notes 0-Vmax 0-Vmax 0-Vmax 0-V4max 0-Vmax 0-Vmax 0-Vmax 0-Imax 0-Imax 0-Imax 0-I4max 0-Imax 0-Ixmax 0-Ixmax 0-Ixmax 0-I4xmax 0-Ixmax 0-Vmax 0-Imax 0-Ixmax 0-300.0 0-300.0 0-300.0 0-9999.00 0-100.00 U1 U1 U1 U4 U1 U1 U1 U2 U2 U2 U2 U2 U2 U2 U2 U2 U2 U1 U2 U2 0.1% 0.1% 0.1% 0.01V 0.01Hz UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 R R R R R R R R R R R R R R R R R R R R R R R R R 1 0-Vmax 0-Vmax 0-Vmax 0-V4max 0-Vmax 0-Vmax 0-Vmax 0-Imax 0-Imax 0-Imax 0-I4max 0-Imax 0-Ixmax 0-Ixmax 0-Ixmax 0-I4xmax U1 U1 U1 U4 U1 U1 U1 U2 U2 U2 U2 U2 U2 U2 U2 U2 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 R R R R R R R R R R R R R R R R 1 1 1 1 1 39 Address +16 +17 +18 +19 +20 +21 +22 +23 +24 10624-10655 +0 +1 +2 +3 +4 +5 +6 +7 +8 +9 +10 +11 +12 +13 +14 +15 +16 +17 +18 +19 +20 +21 +22 +23 +24 +25 +26 +27 +28 +29 +30 +31 40 Point ID Description 0x6D90 0x6D91 0x6D92 0x6D93 0x6D94 0x6D95 0x6D96 0x6D97 0x6D98 Inx current Zero-sequence voltage Zero-sequence current Ix Zero-sequence current Voltage unbalance Current unbalance Ix current unbalance DC voltage Frequency 0.2-Second Harmonics V1 THD V2 THD V3 THD V4 THD I1 THD I2 THD I3 THD I4 THD V1 interharmonics THD V2 interharmonics THD V3 interharmonics THD V4 interharmonics THD I1 interharmonics THD I2 interharmonics THD I3 interharmonics THD I4 interharmonics THD I1 TDD I2 TDD I3 TDD I4 TDD I1 K-Factor I2 K-Factor I3 K-Factor I4 K-Factor V1 Crest Factor V2 Crest Factor V3 Crest Factor V4 Crest Factor I1 Crest Factor I2 Crest Factor I3 Crest Factor I4 Crest Factor 0x6E00 0x6E01 0x6E02 0x6E03 0x6E04 0x6E05 0x6E06 0x6E07 0x6E08 0x6E09 0x6E0A 0x6E0B 0x6E0C 0x6E0D 0x6E0E 0x6E0F 0x6E10 0x6E11 0x6E12 0x6E13 0x6E14 0x6E15 0x6E16 0x6E17 0x6E18 0x6E19 0x6E1A 0x6E1B 0x6E1C 0x6E1D 0x6E1E 0x6E1F 3 3 Low and High Scales 0-Ixmax 0-Vmax 0-Imax 0-Ixmax 0-300.0 0-300.0 0-300.0 0-9999.00 0-100.00 Units U2 U1 U2 U2 0.1% 0.1% 0.1% 0.01V 0.01Hz Type R/W UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 R R R R R R R R R 0-999.9 0-999.9 0-999.9 0-999.9 0-999.9 0-999.9 0-999.9 0-999.9 0-999.9 0-999.9 0-999.9 0-999.9 0-999.9 0-999.9 0-999.9 0-999.9 0-100.0 0-100.0 0-100.0 0-100.0 1.0-999.9 1.0-999.9 1.0-999.9 1.0-999.9 0-100.00 0-100.00 0-100.00 0-100.00 0-100.00 0-100.00 0-100.00 0-100.00 0.1% 0.1% 0.1% 0.1% 0.1% 0.1% 0.1% 0.1% 0.1% 0.1% 0.1% 0.1% 0.1% 0.1% 0.1% 0.1% 0.1% 0.1% 0.1% 0.1% 0.1 0.1 0.1 0.1 0.01 0.01 0.01 0.01 0.01 0.01 0.01 0.01 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R Notes 2 2 2 2 2 2 2 2 2 Address 10656-10687 +0 +1 +2 +3 +4 +5 +6 +7 +8 +9 +10 +11 +12 +13 +14 +15 +16 +17 +18 +19 +20 +21 +22 +23 +24 +25 +26 +27 +28 +29 +30 +31 10688-10719 +0 +1 +2 +3 +4 +5 +6 +7 +8 Point ID 0x6E80 0x6E81 0x6E82 0x6E83 0x6E84 0x6E85 0x6E86 0x6E87 0x6E88 0x6E89 0x6E8A 0x6E8B 0x6E6E 0x6E8D 0x6E8E 0x6E8F 0x6E90 0x6E91 0x6E92 0x6E93 0x6E94 0x6E95 0x6E96 0x6E97 0x6E98 0x6E99 0x6E9A 0x6E9B 0x6E9C 0x6E9D 0x6E9E 0x6E9F 0x6F00 0x6F01 0x6F02 0x6F03 0x6F04 0x6F05 0x6F06 0x6F07 0x6F08 Description 3-Second Harmonics V1 THD V2 THD V3 THD V4 THD I1 THD I2 THD I3 THD I4 THD V1 interharmonics THD V2 interharmonics THD V3 interharmonics THD V4 interharmonics THD I1 interharmonics THD I2 interharmonics THD I3 interharmonics THD I4 interharmonics THD I1 TDD I2 TDD I3 TDD I4 TDD I1 K-Factor I2 K-Factor I3 K-Factor I4 K-Factor V1 Crest Factor V2 Crest Factor V3 Crest Factor V4 Crest Factor I1 Crest Factor I2 Crest Factor I3 Crest Factor I4 Crest Factor 10-Minute Harmonics V1 THD V2 THD V3 THD V4 THD I1 THD I2 THD I3 THD I4 THD V1 interharmonics THD 3 3 Low and High Scales Units Type R/W Notes 0-999.9 0-999.9 0-999.9 0-999.9 0-999.9 0-999.9 0-999.9 0-999.9 0-999.9 0-999.9 0-999.9 0-999.9 0-999.9 0-999.9 0-999.9 0-999.9 0-100.0 0-100.0 0-100.0 0-100.0 1.0-999.9 1.0-999.9 1.0-999.9 1.0-999.9 0-100.00 0-100.00 0-100.00 0-100.00 0-100.00 0-100.00 0-100.00 0-100.00 0.1% 0.1% 0.1% 0.1% 0.1% 0.1% 0.1% 0.1% 0.1% 0.1% 0.1% 0.1% 0.1% 0.1% 0.1% 0.1% 0.1% 0.1% 0.1% 0.1% 0.1 0.1 0.1 0.1 0.01 0.01 0.01 0.01 0.01 0.01 0.01 0.01 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R 2 0-999.9 0-999.9 0-999.9 0-999.9 0-999.9 0-999.9 0-999.9 0-999.9 0-999.9 0.1% 0.1% 0.1% 0.1% 0.1% 0.1% 0.1% 0.1% 0.1% UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 R R R R R R R R R 2 2 2 2 2 2 2 2 2 2 2 2 41 Address +9 +10 +11 +12 +13 +14 +15 +16 +17 +18 +19 +20 +21 +22 +23 +24 +25 +26 +27 +28 +29 +30 +31 10720-10751 +0 +1 +2 +3 +4 +5 +6 +7 +8 +9 +10 +11 +12 +13 +14 +15 +16 +17 +18 42 Point ID Description 0x6F09 0x6F0A 0x6F0B 0x6F0C 0x6F0D 0x6F0E 0x6F0F 0x6F10 0x6F11 0x6F12 0x6F13 0x6F14 0x6F15 0x6F16 0x6F17 0x6F18 0x6F19 0x6F1A 0x6F1B 0x6F1C 0x6F1D 0x6F1E 0x6F1F V2 interharmonics THD V3 interharmonics THD V4 interharmonics THD I1 interharmonics THD I2 interharmonics THD I3 interharmonics THD I4 interharmonics THD I1 TDD I2 TDD I3 TDD I4 TDD I1 K-Factor I2 K-Factor I3 K-Factor I4 K-Factor V1 Crest Factor V2 Crest Factor V3 Crest Factor V4 Crest Factor I1 Crest Factor I2 Crest Factor I3 Crest Factor I4 Crest Factor 2-Hour Harmonics V1 THD V2 THD V3 THD V4 THD I1 THD I2 THD I3 THD I4 THD V1 interharmonics THD V2 interharmonics THD V3 interharmonics THD V4 interharmonics THD I1 interharmonics THD I2 interharmonics THD I3 interharmonics THD I4 interharmonics THD I1 TDD I2 TDD I3 TDD 0x6F80 0x6F81 0x6F82 0x6F83 0x6F84 0x6F85 0x6F86 0x6F87 0x6F88 0x6F89 0x6F8A 0x6F8B 0x6F8C 0x6F8D 0x6F8E 0x6F8F 0x6F90 0x6F91 0x6F92 3 3 Low and High Scales 0-999.9 0-999.9 0-999.9 0-999.9 0-999.9 0-999.9 0-999.9 0-100.0 0-100.0 0-100.0 0-100.0 1.0-999.9 1.0-999.9 1.0-999.9 1.0-999.9 0-100.00 0-100.00 0-100.00 0-100.00 0-100.00 0-100.00 0-100.00 0-100.00 Units 0.1% 0.1% 0.1% 0.1% 0.1% 0.1% 0.1% 0.1% 0.1% 0.1% 0.1% 0.1 0.1 0.1 0.1 0.01 0.01 0.01 0.01 0.01 0.01 0.01 0.01 Type R/W Notes UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 R R R R R R R R R R R R R R R R R R R R R R R 2 0-999.9 0-999.9 0-999.9 0-999.9 0-999.9 0-999.9 0-999.9 0-999.9 0-999.9 0-999.9 0-999.9 0-999.9 0-999.9 0-999.9 0-999.9 0-999.9 0-100.0 0-100.0 0-100.0 0.1% 0.1% 0.1% 0.1% 0.1% 0.1% 0.1% 0.1% 0.1% 0.1% 0.1% 0.1% 0.1% 0.1% 0.1% 0.1% 0.1% 0.1% 0.1% UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 R R R R R R R R R R R R R R R R R R R 2 2 2 2 2 2 2 2 2 2 Address +19 +20 +21 +22 +23 +24 +25 +26 +27 +28 +29 +30 +31 Point ID Description 0x6F93 0x6F94 0x6F95 0x6F96 0x6F97 0x6F98 0x6F99 0x6F9A 0x6F9B 0x6F9C 0x6F9D 0x6F9E 0x6F9F I4 TDD I1 K-Factor I2 K-Factor I3 K-Factor I4 K-Factor V1 Crest Factor V2 Crest Factor V3 Crest Factor V4 Crest Factor I1 Crest Factor I2 Crest Factor I3 Crest Factor I4 Crest Factor 3 Low and High Scales 0-100.0 1.0-999.9 1.0-999.9 1.0-999.9 1.0-999.9 0-100.00 0-100.00 0-100.00 0-100.00 0-100.00 0-100.00 0-100.00 0-100.00 3 Units 0.1% 0.1 0.1 0.1 0.1 0.01 0.01 0.01 0.01 0.01 0.01 0.01 0.01 Type R/W UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 R R R R R R R R R R R R R Notes 2 2 2 NOTES: 1 When the 4LN3, 4LL3, 3LN3, 3LL3, 3BLN3 or 3BLL3 wiring mode is selected, the voltages will be line-to-neutral; for any other wiring mode, they will be line-to-line. 2 When the 4LN3, 3LN3 or 3BLN3 wiring mode is selected, the voltages will be line-to-neutral; for any other wiring mode, they will be line-to-line voltages. 3 For volts, amps, power and frequency scales and units, refer to Section 4 ”Data Scales and Units”. 4 On a 0.2-s interval. 5 On a 3-s interval. 43 3.4 32-bit Binary and Analog Values Address Point ID 11776-11777 0x0000 11840-11841 0x0080 0x0081 0x009F 11904-11907 +0,1 0x0100 +2,3 0x0101 12160-12161 0x0300 0x0301 0x031F 0x0400 0x0401 0x0402 0x0403 0x0404 0x0405 0x0406 0x0407 0x0408 0x0500 0x0501 0x050F 12544-12545 12608-12609 12672-12673 0x0600 0x0601 0x065F 44 Description None Setpoint Status Setpoint #1 Setpoint #2 ... Setpoint #32 Special Inputs Voltage disturbance Phase rotation order Event Flags Event flags 1-32 Event flag #1 Event flag #2 ... Event flag #32 Internal Pulsed Events kWh Import pulse kWh Export pulse kWh Total pulse kvarh Import pulse kvarh Export pulse kvarh Total pulse kVAh pulse Start of power demand interval pulse Start of tariff interval pulse Periodic Timers Timer #1 Timer #2 ... Timer #16 Digital Inputs Digital inputs DI1–DI32 Digital inputs DI33–DI64 Digital inputs DI65–DI96 Digital input DI1 Digital input DI2 ... Digital input DI96 3 Options/Range 0 0x00000000 - 0xFFFFFFFF 0/1 0/1 3 Units 0/1 0-100 0 = error, 1 = positive (ABC), 2 = negative (CBA) 0x00000000 - 0xFFFFFFF 0/1 0/1 % Type R/W UINT32 R UINT32 UINT32 R R UINT32 R UINT32 UINT32 R R UINT32 R TRG TRG 0/1 TRG 0/1 0/1 0/1 0/1 0/1 0/1 0/1 0/1 0/1 TRG TRG TRG TRG TRG TRG TRG TRG TRG 0/1 0/1 TRG TRG 0/1 TRG Notes 6 0x00000000 - 0xFFFFFFFF 0x00000000 - 0xFFFFFFFF 0x00000000 - 0x0000FFFF 0/1 0/1 0/1 UINT32 UINT32 UINT32 R R R TRG TRG TRG Address Point ID 0x0700 0x0701 0x075F 12800-12801 12864-12865 0x0800 0x0801 0x083F 0x0900 0x0901 0x0902 0x0903 0x0904 0x0905 0x0906 0x0907 0x0908 13056-13119 +0,1 0x0A00 +2,3 0x0A01 +62,63 0x0A1F 0x0B00 0x0B01 0x0B02 0x0B03 0x0B04 0x0B05 0x0B06 0x0B07 0x0B08 13248-13297 +0,1 +2,3 +4,5 +6,7 +8,9 0x0B80 0x0B81 0x0B82 0x0B83 0x0B84 Description Pulse Inputs Digital input DI1 Digital input DI2 ... Digital input DI96 Relay Outputs Relay outputs RO1–RO32 Relay outputs RO1–RO64 Relay output RO1 Relay output RO2 ... Relay output RO64 Internal Static Events Phase order error Positive phase order Negative phase order PQ event General fault event Fault detected External fault trigger Device fault (non-critical error) No voltage Counters Counter #1 Counter #2 ... Counter #32 Time/Date Packed date Packed time Day of week Year Month Day of month Hours Minutes Seconds 1/2-Cycle Values V1 voltage V2 voltage V3 voltage V4 voltage V12 voltage Options/Range 3 3 Units Type R/W Notes 7 0/1 0/1 TRG TRG 0/1 TRG 0x00000000 - 0xFFFFFFFF 0x00000000 - 0xFFFFFFFF 0/1 0/1 UINT32 UINT32 R R TRG TRG 0/1 TRG 0/1 0/1 0/1 0/1 0/1 0/1 0/1 0/1 0/1 TRG TRG TRG TRG TRG TRG TRG TRG TRG 0 - 999,999,999 0 - 999,999,999 UINT32 UINT32 R/W R/W 0 - 999,999,999 UINT32 R/W YYMMDD hhmmss 1-7, 1 = Sun, 7 = Sat 0-99 1-12 1-31 0-23 0-59 0-59 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 TRG TRG TRG TRG TRG TRG TRG TRG TRG UINT32 UINT32 UINT32 UINT32 UINT32 R R R R R 0-Vmax 0-Vmax 0-Vmax 0-V4max 0-Vmax U1 U1 U1 U4 U1 1 1 1 45 Address +10,11 +12,13 +14,15 +16,17 +18,19 +20,21 +22,23 +24,25 +26,27 +28,29 +30,31 +32,33 +34,35 +36,37 +38,39 +40,41 +42,43 +44,45 +46,47 +48,49 13312-13383 +0,1 +2,3 +4,5 +6,7 +8,9 +10,11 +12,13 +14,15 +16,17 +18,19 +20,21 +22,23 +24,25 +26,27 +28,29 +30,31 +32,33 +34,35 +36,37 +38,39 +40,41 +42,43 46 Point ID Description 0x0B85 0x0B86 0x0B87 0x0B88 0x0B89 0x0B8A 0x0B8B 0x0B8C 0x0B8D 0x0B8E 0x0B8F 0x0B90 0x0B91 0x0B92 0x0B93 0x0B94 0x0B95 0x0B96 0x0B97 0x0B98 V23 voltage V31 voltage I1 current I2 current I3 current I4 current In current I1x current I2x current I3x current I4x current Inx current Zero-sequence voltage Zero-sequence current Ix Zero-sequence current Voltage unbalance Current unbalance Ix current unbalance DC voltage Frequency (1-cycle) 1-Cycle Phase Values V1 voltage V2 voltage V3 voltage I1 current I2 current I3 current kW L1 kW L2 kW L3 kvar L1 kvar L2 kvar L3 kVA L1 kVA L2 kVA L3 Power factor L1 Power factor L2 Power factor L3 V1 voltage THD V2 voltage THD V3 voltage THD I1 current THD 0x0C00 0x0C01 0x0C02 0x0C03 0x0C04 0x0C05 0x0C06 0x0C07 0x0C08 0x0C09 0x0C0A 0x0C0B 0x0C0C 0x0C0D 0x0C0E 0x0C0F 0x0C10 0x0C11 0x0C12 0x0C13 0x0C14 0x0C15 Options/Range 0-Vmax 0-Vmax 0-Imax 0-Imax 0-Imax 0-I4max 0-Imax 0-Ixmax 0-Ixmax 0-Ixmax 0-I4xmax 0-Ixmax 0-Vmax 0-Imax 0-Ixmax 0-3000 0-3000 0-3000 0-999900 0-10000 0-Vmax 0-Vmax 0-Vmax 0-Imax 0-Imax 0-Imax -Pmax-Pmax -Pmax-Pmax -Pmax-Pmax -Pmax-Pmax -Pmax-Pmax -Pmax-Pmax 0-Pmax 0-Pmax 0-Pmax -1000-1000 -1000-1000 -1000-1000 0-9999 0-9999 0-9999 0-9999 3 3 Units U1 U1 U2 U2 U2 U2 U2 U2 U2 U2 U2 U2 U1 U2 U2 ×0.1% ×0.1% ×0.1% ×0.01V ×0.01Hz Type R/W UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 R R R R R R R R R R R R R R R R R R R R U1 U1 U1 U2 U2 U2 U3 U3 U3 U3 U3 U3 U3 U3 U3 ×0.001 ×0.001 ×0.001 ×0.1% ×0.1% ×0.1% ×0.1% UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 INT32 INT32 INT32 INT32 INT32 INT32 UINT32 UINT32 UINT32 INT32 INT32 INT32 UINT32 UINT32 UINT32 UINT32 R R R R R R R R R R R R R R R R R R R R R R Notes 1 1 1 2, 4 2, 4 2, 4 4 Address +44,45 +46,47 +48,49 +50,51 +52,53 +54,55 +56,57 +58,59 +60,61 +62,63 +64,65 +66,67 +68,69 +70,71 13440-13467 +0,1 +2,3 +4,5 +6,7 +8,9 +10,11 +12,13 +14,15 +16,17 +18,19 +20,21 +22,23 +24,25 +26,27 13568-13595 +0,1 +2,3 +4,5 +6,7 +8,9 +10,11 +12,13 +14,15 +16,17 +18,19 +20,21 +22,23 +24,25 Point ID Description 0x0C16 0x0C17 0x0C18 0x0C19 0x0C1A 0x0C1B 0x0C1C 0x0C1D 0x0C1E 0x0C1F 0x0C20 0x0C21 0x0C22 0x0C23 I2 current THD I3 current THD I1 K-Factor I2 K-Factor I3 K-Factor I1 current TDD I2 current TDD I3 current TDD V12 voltage V23 voltage V31 voltage I1x current I2x current I3x current 1-Cycle Low Phase Values Low L-N voltage Low current Low kW Low kvar Low kVA Low PF Lag Low PF Lead Low voltage THD Low current THD Low K-Factor Low current TDD Low L-L voltage Low voltage interharmonics THD Low current interharmonics THD 1-Cycle High Phase Values High L-N voltage High current High kW High kvar High kVA High PF Lag High PF Lead High voltage THD High current THD High K-Factor High current TDD High L-L voltage High voltage interharmonics THD 0x0D00 0x0D01 0x0D02 0x0D03 0x0D04 0x0D05 0x0D06 0x0D07 0x0D08 0x0D09 0x0D0A 0x0D0B 0x0D0C 0x0D0D 0x0E00 0x0E01 0x0E02 0x0E03 0x0E04 0x0E05 0x0E06 0x0E07 0x0E08 0x0E09 0x0E0A 0x0E0B 0x0E0C 3 3 Units ×0.1% ×0.1% ×0.1 ×0.1 ×0.1 ×0.1% ×0.1% ×0.1% U1 U1 U1 U2 U2 U2 Type R/W Notes UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 R R R R R R R R R R R R R R 4 0-Vmax 0-Imax -Pmax-Pmax -Pmax-Pmax 0-Pmax 0-1000 0-1000 0-9999 0-9999 10-9999 0-1000 0-Vmax 0-9999 0-9999 U1 U2 U3 U3 U3 ×0.001 ×0.001 ×0.1% ×0.1% ×0.1 ×0.1% U1 ×0.1% ×0.1% UINT32 UINT32 INT32 INT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 R R R R R R R R R R R R R R 0-Vmax 0-Imax -Pmax-Pmax -Pmax-Pmax 0-Pmax 0-1000 0-1000 0-9999 0-9999 10-9999 0-1000 0-Vmax 0-9999 U1 U2 U3 U3 U3 ×0.001 ×0.001 ×0.1% ×0.1% ×0.1 ×0.1% U1 ×0.1% UINT32 UINT32 INT32 INT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 R R R R R R R R R R R R R Options/Range 0-9999 0-9999 10-9999 10-9999 10-9999 0-1000 0-1000 0-1000 0-Vmax 0-Vmax 0-Vmax 0-Ixmax 0-Ixmax 0-Ixmax 4 4 4 4 4 4 4 2, 4 4 4 4 2, 4 4 2, 4 4 4 4 2, 4 47 Address +26,27 13696-13723 +0,1 +2,3 +4,5 +6,7 +8,9 +10,11 +12,13 +14,15 +16,17 +18,19 +20,21 +22,23 +24,25 +26,27 13824-13721 +0,1 +2,3 +4,5 +6,7 +8,9 +10,11 +12,13 +14,15 13888-13919 +0, 1 +2, 3 +4, 5 +6, 7 +8, 9 +10, 11 +12, 13 +14, 15 +16, 17 +18, 19 +20, 21 +22, 23 +24, 25 +26, 27 +28, 29 +30, 31 48 Point ID Description 0x0E0D High current interharmonics THD 1-Cycle Total Values Total kW Total kvar Total kVA Total PF Total PF lag Total PF lead Total kW import Total kW export Total kvar import Total kvar export 3-phase average L-N voltage 3-phase average L-L voltage 3-phase average current 3-phase average current, extended inputs I1x-I3x 1-Cycle Auxiliary Values I4 current In current Frequency Voltage unbalance Current unbalance DC voltage V4 voltage I4x current Fundamental Phasor Values V1 voltage magnitude V2 voltage magnitude V3 voltage magnitude V4 voltage magnitude I1 current magnitude I2 current magnitude I3 current magnitude I4 current magnitude V1 voltage angle V2 voltage angle V3 voltage angle V4 voltage angle I1 current angle I2 current angle I3 current angle I4 current angle 0x0F00 0x0F01 0x0F02 0x0F03 0x0F04 0x0F05 0x0F06 0x0F07 0x0F08 0x0F09 0x0F0A 0x0F0B 0x0F0C 0x0F0D 0x1000 0x1001 0x1002 0x1003 0x1004 0x1005 0x1006 0x1007 0x1080 0x1081 0x1082 0x1083 0x1084 0x1085 0x1086 0x1087 0x1088 0x1089 0x108A 0x108B 0x108C 0x108D 0x108E 0x108F 3 3 Units ×0.1% Type R/W Notes UINT32 R 4 -Pmax-Pmax -Pmax-Pmax 0-Pmax -1000-1000 0-1000 0-1000 0-Pmax 0-Pmax 0-Pmax 0-Pmax 0-Vmax 0-Vmax 0-Imax 0-Ixmax U3 U3 U3 ×0.001 ×0.001 ×0.001 U3 U3 U3 U3 U1 U1 U2 U2 INT32 INT32 UINT32 INT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 R R R R R 0-Imax 0-Imax 0-10000 0-3000 0-3000 0-999900 0-V4max 0-Ixmax U2 U2 ×0.01Hz ×0.1% ×0.1% ×0.01V U4 U2 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 R R R R R R R R 0-Vmax 0-Vmax 0-Vmax 0-V4max 0-Imax 0-Imax 0-Imax 0-Imax -1800-1800 -1800-1800 -1800-1800 -1800-1800 -1800-1800 -1800-1800 -1800-1800 -1800-1800 U1 U1 U1 U1 U2 U2 U2 U2 ×0.1º ×0.1º ×0.1º ×0.1º ×0.1º ×0.1º ×0.1º ×0.1º UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 INT32 INT32 INT32 INT32 INT32 INT32 INT32 INT32 R R R R R R R R R R R R R R R R Options/Range 0-9999 R R R R R R R 2 2 2 2 2 2 Address 13952-14023 +0, 1 +2, 3 +4, 5 +6, 7 +8, 9 +10, 11 +12, 13 +14, 15 +16, 17 +18, 19 +20, 21 +22, 23 +24, 25 +26, 27 +28, 29 +30, 31 +32, 33 +34, 35 +36, 37 +38, 39 +40, 41 +42, 43 +44, 45 +46, 47 +48, 49 +50, 51 +52, 53 +54, 55 +56, 57 +58, 59 +60, 61 +62, 63 +64, 65 +66, 67 +68, 69 +70, 71 14080-14107 +0, 1 +2, 3 +4, 5 +6, 7 +8, 9 Point ID 0x1100 0x1101 0x1102 0x1103 0x1104 0x1105 0x1106 0x1107 0x1108 0x1109 0x110A 0x110B 0x110C 0x110D 0x110E 0x110F 0x1110 0x1111 0x1112 0x1113 0x1114 0x1115 0x1116 0x1117 0x1118 0x1119 0x111A 0x111B 0x111C 0x111D 0x111E 0x111F 0x1120 0x1121 0x1122 0x1123 0x1200 0x1201 0x1202 0x1203 0x1204 Description 1-Second Phase Values V1 voltage V2 voltage V3 voltage I1 current I2 current I3 current kW L1 kW L2 kW L3 kvar L1 kvar L2 kvar L3 kVA L1 kVA L2 kVA L3 Power factor L1 Power factor L2 Power factor L3 V1 voltage THD V2 voltage THD V3 voltage THD I1 current THD I2 current THD I3 current THD I1 K-Factor I2 K-Factor I3 K-Factor I1 current TDD I2 current TDD I3 current TDD V12 voltage V23 voltage V31 voltage I1x current I2x current I3x current 1-Second Low Phase Values Low L-N voltage Low current Low kW Low kvar Low kVA 3 3 Units Type R/W Notes 0-Vmax 0-Vmax 0-Vmax 0-Imax 0-Imax 0-Imax -Pmax-Pmax -Pmax-Pmax -Pmax-Pmax -Pmax-Pmax -Pmax-Pmax -Pmax-Pmax 0-Pmax 0-Pmax 0-Pmax -1000-1000 -1000-1000 -1000-1000 0-9999 0-9999 0-9999 0-9999 0-9999 0-9999 10-9999 10-9999 10-9999 0-1000 0-1000 0-1000 0-Vmax 0-Vmax 0-Vmax 0-Ixmax 0-Ixmax 0-Ixmax U1 U1 U1 U2 U2 U2 U3 U3 U3 U3 U3 U3 U3 U3 U3 ×0.001 ×0.001 ×0.001 ×0.1% ×0.1% ×0.1% ×0.1% ×0.1% ×0.1% ×0.1 ×0.1 ×0.1 ×0.1% ×0.1% ×0.1% U1 U1 U1 U2 U2 U2 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 INT32 INT32 INT32 INT32 INT32 INT32 UINT32 UINT32 UINT32 INT32 INT32 INT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R 1 0-Vmax 0-Imax -Pmax-Pmax -Pmax-Pmax 0-Pmax U1 U2 U3 U3 U3 UINT32 UINT32 INT32 INT32 UINT32 R R R R R Options/Range 1 1 2, 5 2, 5 2, 5 5 5 5 5 5 5 5 5 5 49 Address +10, 11 +12, 13 +14, 15 +16, 17 +18, 19 +20, 21 +22, 23 +24, 25 +26, 27 14208-14235 +0, 1 +2, 3 +4, 5 +6, 7 +8, 9 +10, 11 +12, 13 +14, 15 +16, 17 +18, 19 +20, 21 +22, 23 +24, 25 +26, 27 14336-14363 +0, 1 +2, 3 +4, 5 +6, 7 +8, 9 +10, 11 +12, 13 +14, 15 +16, 17 +18, 19 +20, 21 +22, 23 +24, 25 +26, 27 14464-14479 +0, 1 +2, 3 +4, 5 50 Point ID Description 0x1205 0x1206 0x1207 0x1208 0x1209 0x120A 0x120B 0x120C 0x120D Low PF Lag Low PF Lead Low voltage THD Low current THD Low K-Factor Low current TDD Low L-L voltage Low voltage interharmonics THD Low current interharmonics THD 1-Second High Phase Values High L-N voltage High current High kW High kvar High kVA High PF Lag High PF Lead High voltage THD High current THD High K-Factor High current TDD High L-L voltage High voltage interharmonics THD High current interharmonics THD 1-Second Total Values Total kW Total kvar Total kVA Total PF Total PF lag Total PF lead Total kW import Total kW export Total kvar import Total kvar export 3-phase average L-N voltage 3-phase average L-L voltage 3-phase average current 3-phase average current, extended inputs I1x-I3x 1-Second Auxiliary Values I4 current In current Frequency 0x1300 0x1301 0x1302 0x1303 0x1304 0x1305 0x1306 0x1307 0x1308 0x1309 0x130A 0x130B 0x130C 0x130D 0x1400 0x1401 0x1402 0x1403 0x1404 0x1405 0x1406 0x1407 0x1408 0x1409 0x140A 0x140B 0x140C 0x140D 0x1500 0x1501 0x1502 3 3 Units ×0.001 ×0.001 ×0.1% ×0.1% ×0.1 ×0.1% U1 ×0.1% ×0.1% Type R/W UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 R R R R R R R R R 0-Vmax 0-Imax -Pmax-Pmax -Pmax-Pmax 0-Pmax 0-1000 0-1000 0-9999 0-9999 10-9999 0-1000 0-Vmax 0-9999 0-9999 U1 U2 U3 U3 U3 ×0.001 ×0.001 ×0.1% ×0.1% ×0.1 ×0.1% U1 ×0.1% ×0.1% UINT32 UINT32 INT32 INT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 R R R R R R R R R R R R R R -Pmax-Pmax -Pmax-Pmax 0-Pmax -1000-1000 0-1000 0-1000 0-Pmax 0-Pmax 0-Pmax 0-Pmax 0-Vmax 0-Vmax 0-Imax 0-Ixmax U3 U3 U3 ×0.001 ×0.001 ×0.001 U3 U3 U3 U3 U1 U1 U2 U2 INT32 INT32 UINT32 INT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 R R R R R 0-Imax 0-Imax 0-10000 U2 U2 ×0.01Hz UINT32 UINT32 UINT32 R R R Options/Range 0-1000 0-1000 0-9999 0-9999 10-9999 0-1000 0-Vmax 0-9999 0-9999 R R R R R R R Notes 2, 5 5 5 5 2, 5 5 2, 5 5 5 5 2, 5 5 Address +6, 7 +8, 9 +10, 11 +12, 13 +14, 15 14528-14551 +0, 1 +2, 3 +4, 5 +6, 7 +8, 9 +10, 11 +12, 13 +14, 15 +16, 17 +18, 19 +20, 21 +22, 23 14592-14661 +0, 1 +2, 3 +4, 5 +6, 7 +8, 9 +10, 11 +12, 13 +14, 15 +16, 17 +18, 19 +20, 21 +22, 23 +24, 25 +26, 27 +28, 29 +30, 31 +32, 33 +34, 35 +36, 37 +38, 39 +40, 41 +42, 43 +44, 45 +46, 47 Point ID Description 0x1503 0x1504 0x1505 0x1506 0x1507 Voltage unbalance Current unbalance DC voltage V4 voltage I4x current Present Harmonic Demands V1 THD demand V2 THD demand V3 THD demand V4 THD demand I1 THD demand I2 THD demand I3 THD demand I4 THD demand I1 TDD demand I2 TDD demand I3 TDD demand I4 TDD demand Present Volt, Ampere and Power Demands V1 volt demand V2 volt demand V3 volt demand I1 ampere demand I2 ampere demand I3 ampere demand kW import block demand kvar import block demand kVA block demand kW import sliding window demand kvar import sliding window demand kVA sliding window demand Not used Not used Not used kW import accumulated demand kvar import accumulated demand kVA accumulated demand kW import predicted sliding window demand kvar import predicted sliding window demand kVA predicted sliding window demand PF (import) at Max. kVA sliding window demand kW export block demand kvar export block demand 0x1580 0x1581 0x1582 0x1583 0x1584 0x1585 0x1586 0x1587 0x1588 0x1589 0x158A 0x158B 0x1600 0x1601 0x1602 0x1603 0x1604 0x1605 0x1606 0x1607 0x1608 0x1609 0x160A 0x160B 0x160C 0x160D 0x160E 0x160F 0x1610 0x1611 0x1612 0x1613 0x1614 0x1615 0x1616 0x1617 3 3 Units ×0.1% ×0.1% ×0.01V U4 U2 Type R/W UINT32 UINT32 UINT32 UINT32 UINT32 R R R R R 0-9999 0-9999 0-9999 0-9999 0-9999 0-9999 0-9999 0-9999 0-1000 0-1000 0-1000 0-1000 ×0.1% ×0.1% ×0.1% ×0.1% ×0.1% ×0.1% ×0.1% ×0.1% ×0.1% ×0.1% ×0.1% ×0.1% UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 R R R R R R R R R R R R 2 0-Vmax 0-Vmax 0-Vmax 0-Imax 0-Imax 0-Imax 0-Pmax 0-Pmax 0-Pmax 0-Pmax 0-Pmax 0-Pmax 0 0 0 0-Pmax 0-Pmax 0-Pmax 0-Pmax 0-Pmax 0-Pmax 0-1000 0-Pmax 0-Pmax U1 U1 U1 U2 U2 U2 U3 U3 U3 U3 U3 U3 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 R R R R R R R R R R R R R R R R R R R R R R R R 2 Options/Range 0-3000 0-3000 0-999900 0-V4max 0-Ixmax U3 U3 U3 U3 U3 U3 ×0.001 U3 U3 Notes 2 2 2 2 51 Address +48, 49 +50, 51 +52, 53 +54, 55 +56, 57 +58, 59 +60, 61 +62, 63 +64, 65 +66, 67 +68, 69 14720-14741 +0, 1 +2, 3 +4, 5 +6, 7 +8, 9 +10, 11 +12, 13 +14, 15 +16, 17 +18, 19 +20, 21 14784-14815 +0, 1 +2, 3 +30, 31 14912-14931 +0, 1 +2, 3 +4, 5 +6, 7 +8, 9 +10, 11 +12, 13 +14, 15 +16, 17 +18, 19 14976-15101 +0, 1 +2, 3 52 Point ID Description 0x1618 0x1619 0x161A 0x161B 0x161C 0x161D 0x161E 0x161F 0x1620 0x1621 0x1622 kW export sliding window demand kvar export sliding window demand kW export accumulated demand kvar export accumulated demand kW export predicted sliding window demand kvar export predicted sliding window demand Not used Not used V4 volt demand I4 ampere demand In ampere demand Total Energies kWh import kWh export kWh net kWh total kvarh import kvarh export kvarh net kvarh total kVAh total Vh total Ah total Summary Energy Registers Summary energy register #1 Summary energy register #2 … Summary energy register #16 Symmetrical Components Positive-sequence voltage Negative-sequence voltage Zero-sequence voltage Negative-sequence voltage unbalance Zero-sequence voltage unbalance Positive-sequence current Negative-sequence current Zero-sequence current Negative-sequence current unbalance Zero-sequence current unbalance V1 Harmonics H01 Harmonic distortion H02 Harmonic distortion 0x1700 0x1701 0x1702 0x1703 0x1704 0x1705 0x1706 0x1707 0x1708 0x1709 0x170A 0x1780 0x1781 0x178F 0x1880 0x1881 0x1882 0x1883 0x1884 0x1885 0x1886 0x1887 0x1888 0x1889 0x1900 0x1901 3 3 Type R/W U4 U2 U2 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 R R R R R R R R R R R 0-999,999,999 0-999,999,999 -999,999,999-999,999,999 0-999,999,999 0-999,999,999 0-999,999,999 -999,999,999-999,999,999 0-999,999,999 0-999,999,999 0-999,999,999 0-999,999,999 1 1 1 1 1 1 1 1 1 1 1 UINT32 UINT32 INT32 UINT32 UINT32 UINT32 INT32 UINT32 UINT32 UINT32 UINT32 R R R R R R R R R R R 0-999,999,999 0-999,999,999 1 kWh 1 kWh UINT32 UINT32 R R 0-999,999,999 1 kWh UINT32 R 0-Vmax 0-Vmax 0-Vmax 0-3000 0-3000 0-Imax 0-Imax 0-Imax 0-3000 0-3000 U1 U1 U1 ×0.1% ×0.1% U2 U2 U2 ×0.1% ×0.1% UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 R R R R R R R R R R 0-10000 0-10000 ×0.01% ×0.01% UINT32 UINT32 R R Options/Range 0-Pmax 0-Pmax 0-Pmax 0-Pmax 0-Pmax 0-Pmax 0 0 0-Vmax 0-Imax 0-Imax Units U3 U3 U3 U3 U3 U3 kWh kWh kWh kWh kvarh kvarh kvarh kvarh kVAh Vh Ah Notes 2 Address Point ID +124, 125 0x193E 15104-15229 +0, 1 0x1A00 +2, 3 0x1A01 +124, 125 0x1A3E 15232-15357 +0, 1 0x1B00 +2, 3 0x1B01 +124, 125 0x1B3E 15360-15485 +0, 1 0x1C00 +2, 3 0x1C01 +124, 125 0x1C3E 15488-15613 +0, 1 0x1D00 +2, 3 0x1D01 +124, 125 0x1D3E 15616-15741 +0, 1 0x1E00 +2, 3 0x1E01 +124, 125 0x1E3E 15744-15807 +0, 1 0x1F00 +2, 3 0x1F01 +62, 63 0x1F3E 15872-15935 +0, 1 0x2000 +2, 3 0x2001 +62, 63 0x203E 16000-16063 +0, 1 0x2100 +2, 3 0x2101 Description ... H63 Harmonic distortion V2 Harmonics H01 Harmonic distortion H02 Harmonic distortion ... H63 Harmonic distortion V3 Harmonics H01 Harmonic distortion H02 Harmonic distortion ... H63 Harmonic distortion I1 Harmonics H01 Harmonic distortion H02 Harmonic distortion ... H63 Harmonic distortion I2 Harmonics H01 Harmonic distortion H02 Harmonic distortion ... H63 Harmonic distortion I3 Harmonics H01 Harmonic distortion H02 Harmonic distortion ... H63 Harmonic distortion V1 Harmonic Voltages (odd numbers) H01 Harmonic voltage H03 Harmonic voltage ... H63 Harmonic voltage V2 Harmonic Voltages (odd numbers) H01 Harmonic voltage H03 Harmonic voltage ... H63 Harmonic voltage V3 Harmonic Voltages (odd numbers) H01 Harmonic voltage H03 Harmonic voltage ... 3 3 Units Type R/W 0-10000 ×0.01% UINT32 R 0-10000 0-10000 ×0.01% ×0.01% UINT32 UINT32 R R 0-10000 ×0.01% UINT32 R 0-10000 0-10000 ×0.01% ×0.01% UINT32 UINT32 R R 0-10000 ×0.01% UINT32 R 0-10000 0-10000 ×0.01% ×0.01% UINT32 UINT32 R R 0-10000 ×0.01% UINT32 R 0-10000 0-10000 ×0.01% ×0.01% UINT32 UINT32 R R 0-10000 ×0.01% UINT32 R 0-10000 0-10000 ×0.01% ×0.01% UINT32 UINT32 R R 0-10000 ×0.01% UINT32 R 0-Vmax 0-Vmax U1 U1 UINT32 UINT32 R R 0-Vmax U1 UINT32 R 0-Vmax 0-Vmax U1 U1 UINT32 UINT32 R R 0-Vmax U1 UINT32 R 0-Vmax 0-Vmax U1 U1 UINT32 UINT32 R R Options/Range Notes 2 2 2 2 2 53 Address Point ID +62, 63 0x213E 16128-16191 +0, 1 0x2200 +2, 3 0x2201 +62, 63 0x223E 16256-16319 +0, 1 0x2300 +2, 3 0x2301 +62, 63 0x233E 16384-16447 +0, 1 0x2400 +2, 3 0x2401 +62, 63 0x243E 16512-16575 +0, 1 0x2500 +2, 3 0x2501 +62, 63 0x253E 16640-16703 +0, 1 0x2600 +2, 3 0x2601 +62, 63 0x263E 16768-16831 +0, 1 0x2700 +2, 3 0x2701 +62, 63 0x273E 16896-17021 +0, 1 0x2800 +2, 3 0x2801 +124, 125 17088-17099 +0,1 +2,3 +4,5 +6,7 54 0x283E 0x2980 0x2981 0x2982 0x2983 Description H63 Harmonic voltage I1 Harmonic Currents (odd numbers) H01 Harmonic current H03 Harmonic current ... H63 Harmonic current I2 Harmonic Currents (odd numbers) H01 Harmonic current H03 Harmonic current ... H63 Harmonic current I3 Harmonic Currents (odd numbers) H01 Harmonic current H03 Harmonic current ... H63 Harmonic current Total Harmonic kW (odd numbers) H01 Harmonic kW H03 Harmonic kW ... H63 Harmonic kW Total Harmonic kvar (odd numbers) H01 Harmonic kvar H03 Harmonic kvar ... H63 Harmonic kvar Total Harmonic Power Factor (odd numbers) H01 Harmonic PF H03 Harmonic PF ... H63 Harmonic PF V4 Harmonics H01 Harmonic distortion H02 Harmonic distortion ... H63 Harmonic distortion Flicker V1 Pst V2 Pst V3 Pst V1 Plt 3 3 Units U1 Type R/W UINT32 R 0-Imax 0-Imax U2 U2 UINT32 UINT32 R R 0-Imax U2 UINT32 R 0-Imax 0-Imax U2 U2 UINT32 UINT32 R R 0-Imax U2 UINT32 R 0-Imax 0-Imax U2 U2 UINT32 UINT32 R R 0-Imax U2 UINT32 R -Pmax -Pmax -Pmax -Pmax U3 U3 INT32 INT32 R R -Pmax -Pmax U3 INT32 R -Pmax -Pmax -Pmax -Pmax U3 U3 INT32 INT32 R R -Pmax -Pmax U3 INT32 R -1000-1000 -1000-1000 ×0.001 ×0.001 INT32 INT32 R R -1000-1000 ×0.001 INT32 R 0-10000 0-10000 0.01% 0.01% UINT32 UINT32 R R 0-10000 0.01% UINT32 R 0-10000 0-10000 0-10000 0-10000 ×0.01 ×0.01 ×0.01 ×0.01 UINT32 UINT32 UINT32 UINT32 R R R R Options/Range 0-Vmax Notes Address +8,9 +10,11 17280-17405 +0, 1 +2, 3 +124, 125 17408-17479 +0, 1 +2, 3 +4, 5 +6, 7 +8, 9 +10, 11 +12, 13 +14, 15 +16, 17 +18, 19 +20, 21 +22, 23 +24, 25 +26, 27 +28, 29 +30, 31 +32, 33 +34, 35 +36, 37 +38, 39 +40, 41 +42, 43 +44, 45 +46, 47 +48, 49 +50, 51 +52, 53 +54, 55 +56, 57 +58, 59 +60, 61 +62, 63 +64, 65 +66, 67 Point ID Description 0x2984 0x2985 V2 Plt V3 Plt I4 Harmonics H01 Harmonic distortion H02 Harmonic distortion ... H63 Harmonic distortion Minimum 1-Cycle Phase Values V1 voltage V2 voltage V3 voltage I1 current I2 current I3 current kW L1 kW L2 kW L3 kvar L1 kvar L2 kvar L3 kVA L1 kVA L2 kVA L3 Power factor L1 Power factor L2 Power factor L3 V1 voltage THD V2 voltage THD V3 voltage THD I1 current THD I2 current THD I3 current THD I1 K-Factor I2 K-Factor I3 K-Factor I1 current TDD I2 current TDD I3 current TDD V12 voltage V23 voltage V31 voltage I1x current 0x2B00 0x2B01 0x2B3E 0x2C00 0x2C01 0x2C02 0x2C03 0x2C04 0x2C05 0x2C06 0x2C07 0x2C08 0x2C09 0x2C0A 0x2C0B 0x2C0C 0x2C0D 0x2C0E 0x2C0F 0x2C10 0x2C11 0x2C12 0x2C13 0x2C14 0x2C15 0x2C16 0x2C17 0x2C18 0x2C19 0x2C1A 0x2C1B 0x2C1C 0x2C1D 0x2C1E 0x2C1F 0x2C20 0x2C21 3 3 Units ×0.01 ×0.01 Type R/W UINT32 UINT32 R R 0-10000 0-10000 0.01% 0.01% UINT32 UINT32 R R 0-10000 0.01% UINT32 R 0-Vmax 0-Vmax 0-Vmax 0-Imax 0-Imax 0-Imax -Pmax-Pmax -Pmax-Pmax -Pmax-Pmax -Pmax-Pmax -Pmax-Pmax -Pmax-Pmax 0-Pmax 0-Pmax 0-Pmax 0-1000 0-1000 0-1000 0-9999 0-9999 0-9999 0-9999 0-9999 0-9999 10-9999 10-9999 10-9999 0-1000 0-1000 0-1000 0-Vmax 0-Vmax 0-Vmax 0-Ixmax U1 U1 U1 U2 U2 U2 U3 U3 U3 U3 U3 U3 U3 U3 U3 ×0.001 ×0.001 ×0.001 ×0.1% ×0.1% ×0.1% ×0.1% ×0.1% ×0.1% ×0.1 ×0.1 ×0.1 ×0.1% ×0.1% ×0.1% U1 U1 U1 U2 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 INT32 INT32 INT32 INT32 INT32 INT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R Options/Range 0-10000 0-10000 Notes 1 1 1 Absolute value Absolute value Absolute value 2, 4 2, 4 2, 4 4 4 4 4 4 4 4 4 4 55 Address +68, 69 +70, 71 17536-17547 +0, 1 +2, 3 +4, 5 +6, 7 +8, 9 +10, 11 17664-17685 +0, 1 +2, 3 +4, 5 +6, 7 +8, 9 +10, 11 +12, 13 +14, 15 +16, 17 +18, 19 +20, 21 17920-17951 +0, 1 +2, 3 Point ID Description 0x2C22 0x2C23 I2x current I3x current Minimum 1-Cycle Total Values Total kW Total kvar Total kVA Total PF Total PF lag Total PF lead Minimum 1-Cycle Auxiliary Values I4 current In current Frequency Voltage unbalance Current unbalance DC voltage V4 voltage I4x current V4 THD I4x THD I4x TDD Programmable Min/Max Minimum Values Min/Max Register #1 Min/Max Register #2 … Min/Max Register #16 V4 Harmonic Voltages (odd numbers) H01 Harmonic voltage H03 Harmonic voltage ... H63 Harmonic voltage I4 Harmonic Currents (odd numbers) H01 Harmonic current H03 Harmonic current ... H63 Harmonic current Maximum 1-Cycle Phase Values V1 voltage V2 voltage V3 voltage I1 current I2 current 0x2D00 0x2D01 0x2D02 0x2D03 0x2D04 0x2D05 0x2E00 0x2E01 0x2E02 0x2E03 0x2E04 0x2E05 0x2E06 0x2E07 0x2E08 0x2E09 0x2E0A 0x3000 0x3001 +30, 31 0x300F 18048-18111 +0, 1 0x3100 +2, 3 0x3101 +62, 63 0x313E 18176-18239 +0, 1 0x3200 +2, 3 0x3201 +62, 63 18432-18503 +0, 1 +2, 3 +4, 5 +6, 7 +8, 9 56 0x323E 0x3400 0x3401 0x3402 0x3403 0x3404 3 3 Units U2 U2 Type R/W UINT32 UINT32 R R -Pmax-Pmax -Pmax-Pmax 0-Pmax 0-1000 0-1000 0-1000 U3 U3 U3 ×0.001 ×0.001 ×0.001 INT32 INT32 UINT32 UINT32 UINT32 UINT32 R R R R R R 0-Imax 0-Imax 0-10000 0-3000 0-3000 0-999900 0-V4max 0-Ixmax 0-9999 0-9999 0-1000 U2 U2 ×0.01Hz ×0.1% ×0.1% ×0.01V U4 U2 ×0.1% ×0.1% ×0.1% UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 R R R R R R R R R R R UINT32 UINT32 R R UINT32 R Options/Range 0-Ixmax 0-Ixmax 0-Vmax 0-Vmax U1 U1 UINT32 UINT32 R R 0-Vmax U1 UINT32 R 0-Imax 0-Imax U2 U2 UINT32 UINT32 R R 0-Imax U2 UINT32 R 0-Vmax 0-Vmax 0-Vmax 0-Imax 0-Imax U1 U1 U1 U2 U2 UINT32 UINT32 UINT32 UINT32 UINT32 R R R R R Notes Absolute value 4 4 4 1 1 1 Address +10, 11 +12, 13 +14, 15 +16, 17 +18, 19 +20, 21 +22, 23 +24, 25 +26, 27 +28, 29 +30, 31 +32, 33 +34, 35 +36, 37 +38, 39 +40, 41 +42, 43 +44, 45 +46, 47 +48, 49 +50, 51 +52, 53 +54, 55 +56, 57 +58, 59 +60, 61 +62, 63 +64, 65 +66, 67 +68, 69 +70, 71 18560-18571 +0, 1 +2, 3 +4, 5 +6, 7 +8, 9 +10, 11 18668-18689 +0, 1 +2, 3 +4, 5 +6, 7 Point ID Description 0x3405 0x3406 0x3407 0x3408 0x3409 0x340A 0x340B 0x340C 0x340D 0x340E 0x340F 0x3410 0x3411 0x3412 0x3413 0x3414 0x3415 0x3416 0x3417 0x3418 0x3419 0x341A 0x341B 0x341C 0x341D 0x341E 0x341F 0x3420 0x3421 0x3422 0x3423 I3 current kW L1 kW L2 kW L3 kvar L1 kvar L2 kvar L3 kVA L1 kVA L2 kVA L3 Power factor L1 Power factor L2 Power factor L3 V1 voltage THD V2 voltage THD V3 voltage THD I1 current THD I2 current THD I3 current THD I1 K-Factor I2 K-Factor I3 K-Factor I1 current TDD I2 current TDD I3 current TDD V12 voltage V23 voltage V31 voltage I1x current I2x current I3x current Maximum 1-Cycle Total Values Total kW Total kvar Total kVA Total PF Total PF lag Total PF lead Maximum 1-Cycle Auxiliary Values I4 current In current Frequency Voltage unbalance 0x3500 0x3501 0x3502 0x3503 0x3504 0x3505 0x3600 0x3601 0x3602 0x3603 3 3 Units U2 U3 U3 U3 U3 U3 U3 U3 U3 U3 ×0.001 ×0.001 ×0.001 ×0.1% ×0.1% ×0.1% ×0.1% ×0.1% ×0.1% ×0.1 ×0.1 ×0.1 ×0.1% ×0.1% ×0.1% U1 U1 U1 U2 U2 U2 Type R/W UINT32 INT32 INT32 INT32 INT32 INT32 INT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R -Pmax-Pmax -Pmax-Pmax 0-Pmax 0-1000 0-1000 0-1000 U3 U3 U3 ×0.001 ×0.001 ×0.001 INT32 INT32 UINT32 UINT32 UINT32 UINT32 R R R R R R 0-Imax 0-Imax 0-10000 0-3000 U2 U2 ×0.01Hz ×0.1% UINT32 UINT32 UINT32 UINT32 R R R R Options/Range 0-Imax -Pmax-Pmax -Pmax-Pmax -Pmax-Pmax -Pmax-Pmax -Pmax-Pmax -Pmax-Pmax 0-Pmax 0-Pmax 0-Pmax 0-1000 0-1000 0-1000 0-9999 0-9999 0-9999 0-9999 0-9999 0-9999 10-9999 10-9999 10-9999 0-1000 0-1000 0-1000 0-Vmax 0-Vmax 0-Vmax 0-Ixmax 0-Ixmax 0-Ixmax Notes Absolute value Absolute value Absolute value 2, 4 2, 4 2, 4 4 4 4 4 4 4 4 4 4 Absolute value 57 Address +8, 9 +10, 11 +12, 13 +14, 15 +16, 17 +18, 19 +20, 21 18816-18859 +0, 1 +2, 3 +4, 5 +6, 7 +8, 9 +10, 11 +12, 13 +14, 15 +16, 17 +18, 19 +20, 21 +22, 23 +24, 25 +26, 27 +28, 29 +30, 31 +32, 33 +34, 35 +36, 37 +38, 39 +40, 41 +42, 43 18944-18975 +0, 1 +2, 3 +30, 31 19008-19031 +0, 1 +2, 3 +4, 5 +6, 7 +8, 9 +10, 11 +12, 13 58 Point ID Description 0x3604 0x3605 0x3606 0x3607 0x3608 0x3609 0x360A Current unbalance DC voltage V4 voltage I4x current V4 THD I4x THD I4x TDD Maximum Demands V1 Maximum volt demand V2 Maximum volt demand V3 Maximum volt demand I1 Maximum ampere demand I2 Maximum ampere demand I3 Maximum ampere demand Not used Not used Not used Maximum kW import sliding window demand Maximum kvar import sliding window demand Maximum kVA sliding window demand Not used Not used Not used Maximum kW export sliding window demand Maximum kvar export sliding window demand Not used Not used V4 Maximum volt demand I4 Maximum ampere demand In Maximum ampere demand Programmable Min/Max Maximum Values Min/Max Register #1 Min/Max Register #2 … Min/Max Register #16 Maximum Harmonic Demands V1 THD demand V2 THD demand V3 THD demand V4 THD demand I1 THD demand I2 THD demand I3 THD demand 0x3700 0x3701 0x3702 0x3703 0x3704 0x3705 0x3706 0x3707 0x3708 0x3709 0x370A 0x370B 0x3737 0x370D 0x370E 0x370F 0x3710 0x3737 0x3712 0x3713 0x3714 0x3715 0x3800 0x3801 0x380F 0x3880 0x3881 0x3882 0x3883 0x3884 0x3885 0x3886 Options/Range 0-3000 0-999900 0-V4max 0-Ixmax 0-9999 0-9999 0-1000 0-Vmax 0-Vmax 0-Vmax 0-Imax 0-Imax 0-Imax 0 0 0 0-Pmax 0-Pmax 0-Pmax 0 0 0 0-Pmax 0-Pmax 0 0 0-Vmax 0-I4max 0-Imax 0-9999 0-9999 0-9999 0-9999 0-9999 0-9999 0-9999 3 3 Units ×0.1% ×0.01V U4 U2 ×0.1% ×0.1% ×0.1% U1 U1 U1 U2 U2 U2 U3 U3 U3 U3 U3 U4 U2 U2 ×0.1% ×0.1% ×0.1% ×0.1% ×0.1% ×0.1% ×0.1% Type R/W UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 R R R R R R R UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 R R R R R R R R R R R R R R R R R R R R R R UINT32 UINT32 R R UINT32 R UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 R R R R R R R Notes 4 4 4 2 2 2 2 2 2 Address +14, 15 +16, 17 +18, 19 +20, 21 +22, 23 19328-19359 +0, 1 +2, 3 Point ID Description 0x3887 0x3888 0x3889 0x388A 0x388B I4 THD demand I1 TDD demand I2 TDD demand I3 TDD demand I4 TDD demand Scaled Analog Inputs Analog input AI1 Analog input AI2 … Analog input AI16 Raw Analog Inputs Analog input AI1 Analog input AI2 … Analog input AI16 TOU Parameters Active tariff Active profile Scaled Analog Outputs Analog input AO1 Analog input AO2 … Analog input AO16 TOU Energy Register #1 Tariff #1 register Tariff #2 register … Tariff #16 register TOU Energy Register #2 Tariff #1 register Tariff #2 register … Tariff #16 register TOU Energy Register #3 Tariff #1 register Tariff #2 register … Tariff #16 register TOU Energy Register #4 Tariff #1 register Tariff #2 register … 0x3B00 0x3B01 +30, 31 0x3B0F 19392-19423 +0, 1 0x3B80 +2, 3 0x3B81 +30, 31 19456-19459 +0, 1 +2, 3 19520-19551 +0, 1 +2, 3 0x3B8F 0x3C00 0x3C01 0x3C80 0x3C81 +30, 31 0x3C8F 19584-19615 +0, 1 0x3D00 +2, 3 0x3D01 +30, 31 0x3D0F 19712-19743 +0, 1 0x3E00 +2, 3 0x3E01 +30, 31 0x3E0F 19840-19871 +0, 1 0x3F00 +2, 3 0x3F01 +30, 31 0x3F0F 19968-19999 +0, 1 0x4000 +2, 3 0x4001 3 3 Type R/W UINT32 UINT32 UINT32 UINT32 UINT32 R R R R R AI1min-AI1max AI2min-AI2max UINT32 UINT32 R R AI16min-AI16max UINT32 R 0-4095 0-4095 UINT32 UINT32 R R 0-4095 UINT32 R 0-15 0-15 UINT32 UINT32 R R 0-4095 0-4095 UINT32 UINT32 R/W R/W 0-4095 UINT32 R/W R R R R Options/Range 0-9999 0-1000 0-1000 0-1000 0-1000 Units ×0.1% ×0.1% ×0.1% ×0.1% ×0.1% -999,999,999-999,999,999 -999,999,999-999,999,999 1 kWh 1 kWh UINT32 UINT32 -999,999,999-999,999,999 1 kWh UINT32 -999,999,999-999,999,999 -999,999,999-999,999,999 1 kWh 1 kWh UINT32 UINT32 -999,999,999-999,999,999 1 kWh UINT32 -999,999,999-999,999,999 -999,999,999-999,999,999 1 kWh 1 kWh UINT32 UINT32 -999,999,999-999,999,999 1 kWh UINT32 -999,999,999-999,999,999 -999,999,999-999,999,999 1 kWh 1 kWh UINT32 UINT32 Notes R R R R R R R R R R R 59 Address Point ID +30, 31 0x400F 20096-20127 +0, 1 0x4100 +2, 3 0x4101 +30, 31 0x410F 20224-20255 +0, 1 0x4200 +2, 3 0x4201 +30, 31 0x420F 20352-20383 +0, 1 0x4300 +2, 3 0x4301 +30, 31 0x430F 20480-20511 +0, 1 0x4400 +2, 3 0x4401 +30, 31 0x440F 20608-20639 +0, 1 0x4500 +2, 3 0x4501 +30, 31 0x4503 20672-20703 +0, 1 0x4580 +2, 3 0x4581 +30, 31 0x4583 20736-20767 +0, 1 0x4600 +2, 3 0x4601 +30, 31 0x4603 20928-20959 +0, 1 0x4780 +2, 3 0x4781 60 Description Tariff #16 register TOU Energy Register #5 Tariff #1 register Tariff #2 register … Tariff #16 register TOU Energy Register #6 Tariff #1 register Tariff #2 register … Tariff #16 register TOU Energy Register #7 Tariff #1 register Tariff #2 register … Tariff #16 register TOU Energy Register #8 Tariff #1 register Tariff #2 register … Tariff #16 register Summary Energy Accumulated Demands Summary register #1 Summary register #2 … Summary register #16 Summary Energy Block Demands Summary register #1 Summary register #2 … Summary register #16 Summary Energy Sliding Window Demands Summary register #1 Summary register #2 … Summary register #16 Summary Energy Maximum Demands Summary register #1 Summary register #2 … 3 3 Options/Range -999,999,999-999,999,999 Units 1 kWh Type R/W UINT32 R -999,999,999-999,999,999 -999,999,999-999,999,999 1 kWh 1 kWh UINT32 UINT32 -999,999,999-999,999,999 1 kWh UINT32 R R R R -999,999,999-999,999,999 -999,999,999-999,999,999 1 kWh 1 kWh UINT32 UINT32 -999,999,999-999,999,999 1 kWh UINT32 -999,999,999-999,999,999 -999,999,999-999,999,999 1 kWh 1 kWh UINT32 UINT32 -999,999,999-999,999,999 1 kWh UINT32 -999,999,999-999,999,999 -999,999,999-999,999,999 1 kWh 1 kWh UINT32 UINT32 -999,999,999-999,999,999 1 kWh UINT32 R R R R 0-Pmax 0-Pmax U3 U3 UINT32 UINT32 R R 0-Pmax U3 UINT32 R 0-Pmax 0-Pmax U3 U3 UINT32 UINT32 R R 0-Pmax U3 UINT32 R 0-Pmax 0-Pmax U3 U3 UINT32 UINT32 R R 0-Pmax U3 UINT32 R 0-Pmax 0-Pmax U3 U3 UINT32 UINT32 R R R R R R R R R R Notes Address Point ID +30, 31 0x4783 20992-21023 +0, 1 0x4800 +2, 3 0x4801 +30, 31 0x480F 21056-21087 +0, 1 0x4880 +2, 3 0x4881 +30, 31 0x488F 21120-21151 +0, 1 0x4900 +2, 3 0x4901 +30, 31 0x490F 21184-21215 +0, 1 0x4980 +2, 3 0x4981 +30, 31 0x498F 21248-21279 +0, 1 0x4A00 +2, 3 0x4A01 +30, 31 0x4A0F 21312-21343 +0, 1 0x4A80 +2, 3 0x4A81 +30, 31 0x4A8F 21376-21407 +0, 1 0x4B00 +2, 3 0x4B01 +30, 31 0x4B0F 21504-21535 +0, 1 0x4C00 +2, 3 0x4C01 Description Summary register #16 TOU Maximum Demand Register #1 Tariff #1 register Tariff #2 register … Tariff #16 register TOU Maximum Demand Register #4 Tariff #1 register Tariff #2 register … Tariff #16 register TOU Maximum Demand Register #2 Tariff #1 register Tariff #2 register … Tariff #16 register TOU Maximum Demand Register #5 Tariff #1 register Tariff #2 register … Tariff #16 register TOU Maximum Demand Register #3 Tariff #1 register Tariff #2 register … Tariff #16 register TOU Maximum Demand Register #6 Tariff #1 register Tariff #2 register … Tariff #16 register TOU Energy Register #9 Tariff #1 register Tariff #2 register … Tariff #16 register TOU Energy Register #10 Tariff #1 register Tariff #2 register … 3 3 Units U3 Type R/W UINT32 R 0-Pmax 0-Pmax U3 U3 UINT32 UINT32 0-Pmax U3 UINT32 R R R R 0-Pmax 0-Pmax U3 U3 UINT32 UINT32 0-Pmax U3 UINT32 0-Pmax 0-Pmax U3 U3 UINT32 UINT32 0-Pmax U3 UINT32 0-Pmax 0-Pmax U3 U3 UINT32 UINT32 0-Pmax U3 UINT32 0-Pmax 0-Pmax U3 U3 UINT32 UINT32 0-Pmax U3 UINT32 0-Pmax 0-Pmax U3 U3 UINT32 UINT32 0-Pmax U3 UINT32 -999,999,999-999,999,999 -999,999,999-999,999,999 1 kWh 1 kWh UINT32 UINT32 -999,999,999-999,999,999 1 kWh UINT32 -999,999,999-999,999,999 -999,999,999-999,999,999 1 kWh 1 kWh UINT32 UINT32 Options/Range 0-Pmax Notes R R R R R R R R R R R R R R R R R R R R R R R R R R R 61 Address Point ID +30, 31 0x4C0F 21632-21663 +0, 1 0x4D00 +2, 3 0x4D01 +30, 31 0x4D0F 21760-21791 +0, 1 0x4E00 +2, 3 0x4E01 +30, 31 0x4E0F 21888-21919 +0, 1 0x4F00 +2, 3 0x4F01 +30, 31 0x4F0F 22016-22047 +0, 1 0x5000 +2, 3 0x5001 +30, 31 0x500F 22144-22175 +0, 1 0x5100 +2, 3 0x5101 +30, 31 0x510F 22272-22303 +0, 1 0x5200 +2, 3 0x5201 +30, 31 0x520F 22400-22431 +0, 1 0x5300 +2, 3 0x5301 +30, 31 0x530F 22464-22495 +0, 1 0x5380 +2, 3 0x5381 62 Description Tariff #16 register TOU Energy Register #11 Tariff #1 register Tariff #2 register … Tariff #16 register TOU Energy Register #12 Tariff #1 register Tariff #2 register … Tariff #16 register TOU Energy Register #13 Tariff #1 register Tariff #2 register … Tariff #16 register TOU Energy Register #14 Tariff #1 register Tariff #2 register … Tariff #16 register TOU Energy Register #15 Tariff #1 register Tariff #2 register … Tariff #16 register TOU Energy Register #16 Tariff #1 register Tariff #2 register … Tariff #16 register TOU Maximum Demand Register #7 Tariff #1 register Tariff #2 register … Tariff #16 register TOU Maximum Demand Register #8 Tariff #1 register Tariff #2 register … 3 3 Options/Range -999,999,999-999,999,999 Units 1 kWh Type R/W UINT32 R -999,999,999-999,999,999 -999,999,999-999,999,999 1 kWh 1 kWh UINT32 UINT32 -999,999,999-999,999,999 1 kWh UINT32 R R R R -999,999,999-999,999,999 -999,999,999-999,999,999 1 kWh 1 kWh UINT32 UINT32 -999,999,999-999,999,999 1 kWh UINT32 -999,999,999-999,999,999 -999,999,999-999,999,999 1 kWh 1 kWh UINT32 UINT32 -999,999,999-999,999,999 1 kWh UINT32 -999,999,999-999,999,999 -999,999,999-999,999,999 1 kWh 1 kWh UINT32 UINT32 -999,999,999-999,999,999 1 kWh UINT32 -999,999,999-999,999,999 -999,999,999-999,999,999 1 kWh 1 kWh UINT32 UINT32 -999,999,999-999,999,999 1 kWh UINT32 -999,999,999-999,999,999 -999,999,999-999,999,999 1 kWh 1 kWh UINT32 UINT32 -999,999,999-999,999,999 1 kWh UINT32 0-Pmax 0-Pmax U3 U3 UINT32 UINT32 0-Pmax U3 UINT32 0-Pmax 0-Pmax U3 U3 UINT32 UINT32 R R R R R R R R R R R R R R R R R R R R R R R R R R R Notes Address Point ID +30, 31 0x538F 22528-22559 +0, 1 0x5400 +2, 3 0x5401 +30, 31 0x540F 22592-22623 +0, 1 0x5480 +2, 3 0x5481 +30, 31 0x548F 22656-22687 +0, 1 0x5500 +2, 3 0x5501 +30, 31 0x550F 22720-22751 +0, 1 0x5580 +2, 3 0x5581 +30, 31 0x558F 22784-22815 +0, 1 0x5600 +2, 3 0x5601 +30, 31 0x560F 22848-22879 +0, 1 0x5680 +2, 3 0x5681 +30, 31 0x568F 22912-22943 +0, 1 0x5700 +2, 3 0x5701 +30, 31 0x570F 22976-23007 +0, 1 0x5780 +2, 3 0x5781 Description Tariff #16 register TOU Maximum Demand Register #9 Tariff #1 register Tariff #2 register … Tariff #16 register TOU Maximum Demand Register #10 Tariff #1 register Tariff #2 register … Tariff #16 register TOU Maximum Demand Register #11 Tariff #1 register Tariff #2 register … Tariff #16 register TOU Maximum Demand Register #12 Tariff #1 register Tariff #2 register … Tariff #16 register TOU Maximum Demand Register #13 Tariff #1 register Tariff #2 register … Tariff #16 register TOU Maximum Demand Register #14 Tariff #1 register Tariff #2 register … Tariff #16 register TOU Maximum Demand Register #15 Tariff #1 register Tariff #2 register … Tariff #16 register TOU Maximum Demand Register #16 Tariff #1 register Tariff #2 register … 3 3 Units U3 Type R/W UINT32 R 0-Pmax 0-Pmax U3 U3 UINT32 UINT32 0-Pmax U3 UINT32 R R R R 0-Pmax 0-Pmax U3 U3 UINT32 UINT32 0-Pmax U3 UINT32 0-Pmax 0-Pmax U3 U3 UINT32 UINT32 0-Pmax U3 UINT32 0-Pmax 0-Pmax U3 U3 UINT32 UINT32 0-Pmax U3 UINT32 0-Pmax 0-Pmax U3 U3 UINT32 UINT32 0-Pmax U3 UINT32 0-Pmax 0-Pmax U3 U3 UINT32 UINT32 0-Pmax U3 UINT32 0-Pmax 0-Pmax U3 U3 UINT32 UINT32 0-Pmax U3 UINT32 0-Pmax 0-Pmax U3 U3 UINT32 UINT32 Options/Range 0-Pmax Notes R R R R R R R R R R R R R R R R R R R R R R R R R R R 63 Address +30, 31 25600-25649 +0, 1 +2, 3 +4, 5 +6, 7 +8, 9 +10, 11 +12, 13 +14, 15 +16, 17 +18, 19 +20, 21 +22, 23 +24, 25 +26, 27 +28, 29 +30, 31 +32, 33 +34, 35 +36, 37 +38, 39 +40, 41 +42, 43 +44, 45 +46, 47 +48, 49 25664-25713 +0, 1 +2, 3 +4, 5 +6, 7 +8, 9 +10, 11 +12, 13 +14, 15 +16, 17 +18, 19 +20, 21 +22, 23 +24, 25 +26, 27 +28, 29 64 Point ID 0x578F 0x6C00 0x6C01 0x6C02 0x6C03 0x6C04 0x6C05 0x6C06 0x6C07 0x6C08 0x6C09 0x6C0A 0x6C0B 0x6C0C 0x6C0D 0x6C0E 0x6C0F 0x6C10 0x6C11 0x6C12 0x6C13 0x6C14 0x6C15 0x6C16 0x6C17 0x6C18 0x6C80 0x6C81 0x6C82 0x6C83 0x6C84 0x6C85 0x6C86 0x6C87 0x6C88 0x6C89 0x6C8A 0x6C8B 0x6C8C 0x6C8D 0x6C8E Description Tariff #16 register 0.2-Second RMS and Auxiliary Values V1 voltage V2 voltage V3 voltage V4 voltage V12 voltage V23 voltage V31 voltage I1 current I2 current I3 current I4 current In current I1x current I2x current I3x current I4x current Inx current Zero-sequence voltage Zero-sequence current Ix Zero-sequence current Voltage unbalance Current unbalance Ix current unbalance DC voltage Frequency 3-Second RMS and Auxiliary Values V1 voltage V2 voltage V3 voltage V4 voltage V12 voltage V23 voltage V31 voltage I1 current I2 current I3 current I4 current In current I1x current I2x current I3x current 3 3 Units U3 Type R/W UINT32 R 0-Vmax 0-Vmax 0-Vmax 0-V4max 0-Vmax 0-Vmax 0-Vmax 0-Imax 0-Imax 0-Imax 0-I4max 0-Imax 0-Ixmax 0-Ixmax 0-Ixmax 0-I4xmax 0-Ixmax 0-Vmax 0-Imax 0-Ixmax 0-3000 0-3000 0-3000 0-999900 0-10000 U1 U1 U1 U4 U1 U1 U1 U2 U2 U2 U2 U2 U2 U2 U2 U2 U2 U1 U2 U2 ×0.1% ×0.1% ×0.1% ×0.01V ×0.01Hz UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 R R R R R R R R R R R R R R R R R R R R R R R R R 1 0-Vmax 0-Vmax 0-Vmax 0-V4max 0-Vmax 0-Vmax 0-Vmax 0-Imax 0-Imax 0-Imax 0-I4max 0-Imax 0-Ixmax 0-Ixmax 0-Ixmax U1 U1 U1 U4 U1 U1 U1 U2 U2 U2 U2 U2 U2 U2 U2 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 R R R R R R R R R R R R R R R 1 Options/Range 0-Pmax Notes 1 1 1 1 Address +30, 31 +32, 33 +34, 35 +36, 37 +38, 39 +40, 41 +42, 43 +44, 45 +46, 47 +48, 49 25728-25777 +0, 1 +2, 3 +4, 5 +6, 7 +8, 9 +10, 11 +12, 13 +14, 15 +16, 17 +18, 19 +20, 21 +22, 23 +24, 25 +26, 27 +28, 29 +30, 31 +32, 33 +34, 35 +36, 37 +38, 39 +40, 41 +42, 43 +44, 45 +46, 47 +48, 49 25792-25841 +0, 1 +2, 3 +4, 5 +6, 7 +8, 9 +10, 11 Point ID Description 0x6C8F 0x6C90 0x6C91 0x6C92 0x6C93 0x6C94 0x6C95 0x6C96 0x6C97 0x6C98 I4x current Inx current Zero-sequence voltage Zero-sequence current Ix Zero-sequence current Voltage unbalance Current unbalance Ix current unbalance DC voltage Frequency 10-Minute RMS and Auxiliary Values V1 voltage V2 voltage V3 voltage V4 voltage V12 voltage V23 voltage V31 voltage I1 current I2 current I3 current I4 current In current I1x current I2x current I3x current I4x current Inx current Zero-sequence voltage Zero-sequence current Ix Zero-sequence current Voltage unbalance Current unbalance Ix current unbalance DC voltage Frequency 2-Hour RMS and Auxiliary Values V1 voltage V2 voltage V3 voltage V4 voltage V12 voltage V23 voltage 0x6D00 0x6D01 0x6D02 0x6D03 0x6D04 0x6D05 0x6D06 0x6D07 0x6D08 0x6D09 0x6D0A 0x6D0B 0x6D0C 0x6D0D 0x6D0E 0x6D0F 0x6D10 0x6D11 0x6D12 0x6D13 0x6D14 0x6D15 0x6D16 0x6D17 0x6D18 0x6D80 0x6D81 0x6D82 0x6D83 0x6D84 0x6D85 3 3 Units U2 U2 U1 U2 U2 ×0.1% ×0.1% ×0.1% ×0.01V ×0.01Hz Type R/W UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 R R R R R R R R R R 0-Vmax 0-Vmax 0-Vmax 0-V4max 0-Vmax 0-Vmax 0-Vmax 0-Imax 0-Imax 0-Imax 0-I4max 0-Imax 0-Ixmax 0-Ixmax 0-Ixmax 0-I4xmax 0-Ixmax 0-Vmax 0-Imax 0-Ixmax 0-3000 0-3000 0-3000 0-999900 0-10000 U1 U1 U1 U4 U1 U1 U1 U2 U2 U2 U2 U2 U2 U2 U2 U2 U2 U1 U2 U2 ×0.1% ×0.1% ×0.1% ×0.01V ×0.01Hz UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 R R R R R R R R R R R R R R R R R R R R R R R R R 1 0-Vmax 0-Vmax 0-Vmax 0-V4max 0-Vmax 0-Vmax U1 U1 U1 U4 U1 U1 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 R R R R R R 1 Options/Range 0-I4xmax 0-Ixmax 0-Vmax 0-Imax 0-Ixmax 0-3000 0-3000 0-3000 0-999900 0-10000 Notes 1 1 1 1 65 Address +12, 13 +14, 15 +16, 17 +18, 19 +20, 21 +22, 23 +24, 25 +26, 27 +28, 29 +30, 31 +32, 33 +34, 35 +36, 37 +38, 39 +40, 41 +42, 43 +44, 45 +46, 47 +48, 49 25856-25905 +0, 1 +2, 3 +4, 5 +6, 7 +8, 9 +10, 11 +12, 13 +14, 15 +16, 17 +18, 19 +20, 21 +22, 23 +24, 25 +26, 27 +28, 29 +30, 31 +32, 33 +34, 35 +36, 37 +38, 39 +40, 41 +42, 43 66 Point ID Description 0x6D86 0x6D87 0x6D88 0x6D89 0x6D8A 0x6D8B 0x6D8C 0x6D8D 0x6D8E 0x6D8F 0x6D90 0x6D91 0x6D92 0x6D93 0x6D94 0x6D95 0x6D96 0x6D97 0x6D98 V31 voltage I1 current I2 current I3 current I4 current In current I1x current I2x current I3x current I4x current Inx current Zero-sequence voltage Zero-sequence current Ix Zero-sequence current Voltage unbalance Current unbalance Ix current unbalance DC voltage Frequency 0.2-Second Harmonics V1 THD V2 THD V3 THD V4 THD I1 THD I2 THD I3 THD I4 THD V1 interharmonics THD V2 interharmonics THD V3 interharmonics THD V4 interharmonics THD I1 interharmonics THD I2 interharmonics THD I3 interharmonics THD I4 interharmonics THD I1 TDD I2 TDD I3 TDD I4 TDD I1 K-Factor I2 K-Factor 0x6E00 0x6E01 0x6E02 0x6E03 0x6E04 0x6E05 0x6E06 0x6E07 0x6E08 0x6E09 0x6E0A 0x6E0B 0x6E0C 0x6E0D 0x6E0E 0x6E0F 0x6E10 0x6E11 0x6E12 0x6E13 0x6E14 0x6E15 Options/Range 0-Vmax 0-Imax 0-Imax 0-Imax 0-I4max 0-Imax 0-Ixmax 0-Ixmax 0-Ixmax 0-I4xmax 0-Ixmax 0-Vmax 0-Imax 0-Ixmax 0-3000 0-3000 0-3000 0-999900 0-10000 0-9999 0-9999 0-9999 0-9999 0-9999 0-9999 0-9999 0-9999 0-9999 0-9999 0-9999 0-9999 0-9999 0-9999 0-9999 0-9999 0-1000 0-1000 0-1000 0-1000 10-9999 10-9999 3 3 Units U1 U2 U2 U2 U2 U2 U2 U2 U2 U2 U2 U1 U2 U2 ×0.1% ×0.1% ×0.1% ×0.01V ×0.01Hz Type R/W UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 R R R R R R R R R R R R R R R R R R R ×0.1% ×0.1% ×0.1% ×0.1% ×0.1% ×0.1% ×0.1% ×0.1% ×0.1% ×0.1% ×0.1% ×0.1% ×0.1% ×0.1% ×0.1% ×0.1% ×0.1% ×0.1% ×0.1% ×0.1% ×0.1 ×0.1 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 R R R R R R R R R R R R R R R R R R R R R R Notes 2 2 2 2 2 2 Address +44, 45 +46, 47 +48, 49 +50, 51 +52, 53 +54, 55 +56, 57 +58, 59 +60, 61 +62, 63 25920-25969 +0, 1 +2, 3 +4, 5 +6, 7 +8, 9 +10, 11 +12, 13 +14, 15 +16, 17 +18, 19 +20, 21 +22, 23 +24, 25 +26, 27 +28, 29 +30, 31 +32, 33 +34, 35 +36, 37 +38, 39 +40, 41 +42, 43 +44, 45 +46, 47 +48, 49 +50, 51 +52, 53 +54, 55 +56, 57 +58, 59 +60, 61 Point ID Description 0x6E16 0x6E17 0x6E18 0x6E19 0x6E1A 0x6E1B 0x6E1C 0x6E1D 0x6E1E 0x6E1F I3 K-Factor I4 K-Factor V1 Crest Factor V2 Crest Factor V3 Crest Factor V4 Crest Factor I1 Crest Factor I2 Crest Factor I3 Crest Factor I4 Crest Factor 3-Second Harmonics V1 THD V2 THD V3 THD V4 THD I1 THD I2 THD I3 THD I4 THD V1 interharmonics THD V2 interharmonics THD V3 interharmonics THD V4 interharmonics THD I1 interharmonics THD I2 interharmonics THD I3 interharmonics THD I4 interharmonics THD I1 TDD I2 TDD I3 TDD I4 TDD I1 K-Factor I2 K-Factor I3 K-Factor I4 K-Factor V1 Crest Factor V2 Crest Factor V3 Crest Factor V4 Crest Factor I1 Crest Factor I2 Crest Factor I3 Crest Factor 0x6E80 0x6E81 0x6E82 0x6E83 0x6E84 0x6E85 0x6E86 0x6E87 0x6E88 0x6E89 0x6E8A 0x6E8B 0x6E6E 0x6E8D 0x6E8E 0x6E8F 0x6E90 0x6E91 0x6E92 0x6E93 0x6E94 0x6E95 0x6E96 0x6E97 0x6E98 0x6E99 0x6E9A 0x6E9B 0x6E9C 0x6E9D 0x6E9E Options/Range 10-9999 10-9999 0-10000 0-10000 0-10000 0-10000 0-10000 0-10000 0-10000 0-10000 0-9999 0-9999 0-9999 0-9999 0-9999 0-9999 0-9999 0-9999 0-9999 0-9999 0-9999 0-9999 0-9999 0-9999 0-9999 0-9999 0-1000 0-1000 0-1000 0-1000 10-9999 10-9999 10-9999 10-9999 0-10000 0-10000 0-10000 0-10000 0-10000 0-10000 0-10000 3 3 Units ×0.1 ×0.1 ×0.01 ×0.01 ×0.01 ×0.01 ×0.01 ×0.01 ×0.01 ×0.01 Type R/W UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 R R R R R R R R R R ×0.1% ×0.1% ×0.1% ×0.1% ×0.1% ×0.1% ×0.1% ×0.1% ×0.1% ×0.1% ×0.1% ×0.1% ×0.1% ×0.1% ×0.1% ×0.1% ×0.1% ×0.1% ×0.1% ×0.1% ×0.1 ×0.1 ×0.1 ×0.1 ×0.01 ×0.01 ×0.01 ×0.01 ×0.01 ×0.01 ×0.01 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R Notes 2 2 2 2 2 2 2 2 2 2 2 2 67 Address +62, 63 25984-26033 +0, 1 +2, 3 +4, 5 +6, 7 +8, 9 +10, 11 +12, 13 +14, 15 +16, 17 +18, 19 +20, 21 +22, 23 +24, 25 +26, 27 +28, 29 +30, 31 +32, 33 +34, 35 +36, 37 +38, 39 +40, 41 +42, 43 +44, 45 +46, 47 +48, 49 +50, 51 +52, 53 +54, 55 +56, 57 +58, 59 +60, 61 +62, 63 26046-26097 +0, 1 +2, 3 +4, 5 +6, 7 +8, 9 +10, 11 +12, 13 68 Point ID Description 0x6E9F I4 Crest Factor 10-Minute Harmonics V1 THD V2 THD V3 THD V4 THD I1 THD I2 THD I3 THD I4 THD V1 interharmonics THD V2 interharmonics THD V3 interharmonics THD V4 interharmonics THD I1 interharmonics THD I2 interharmonics THD I3 interharmonics THD I4 interharmonics THD I1 TDD I2 TDD I3 TDD I4 TDD I1 K-Factor I2 K-Factor I3 K-Factor I4 K-Factor V1 Crest Factor V2 Crest Factor V3 Crest Factor V4 Crest Factor I1 Crest Factor I2 Crest Factor I3 Crest Factor I4 Crest Factor 2-Hour Harmonics V1 THD V2 THD V3 THD V4 THD I1 THD I2 THD I3 THD 0x6F00 0x6F01 0x6F02 0x6F03 0x6F04 0x6F05 0x6F06 0x6F07 0x6F08 0x6F09 0x6F0A 0x6F0B 0x6F0C 0x6F0D 0x6F0E 0x6F0F 0x6F10 0x6F11 0x6F12 0x6F13 0x6F14 0x6F15 0x6F16 0x6F17 0x6F18 0x6F19 0x6F1A 0x6F1B 0x6F1C 0x6F1D 0x6F1E 0x6F1F 0x6F80 0x6F81 0x6F82 0x6F83 0x6F84 0x6F85 0x6F86 3 3 Units ×0.01 Type R/W UINT32 R 0-9999 0-9999 0-9999 0-9999 0-9999 0-9999 0-9999 0-9999 0-9999 0-9999 0-9999 0-9999 0-9999 0-9999 0-9999 0-9999 0-1000 0-1000 0-1000 0-1000 10-9999 10-9999 10-9999 10-9999 0-10000 0-10000 0-10000 0-10000 0-10000 0-10000 0-10000 0-10000 ×0.1% ×0.1% ×0.1% ×0.1% ×0.1% ×0.1% ×0.1% ×0.1% ×0.1% ×0.1% ×0.1% ×0.1% ×0.1% ×0.1% ×0.1% ×0.1% ×0.1% ×0.1% ×0.1% ×0.1% ×0.1 ×0.1 ×0.1 ×0.1 ×0.01 ×0.01 ×0.01 ×0.01 ×0.01 ×0.01 ×0.01 ×0.01 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R 2 0-9999 0-9999 0-9999 0-9999 0-9999 0-9999 0-9999 ×0.1% ×0.1% ×0.1% ×0.1% ×0.1% ×0.1% ×0.1% UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 R R R R R R R 2 Options/Range 0-10000 Notes 2 2 2 2 2 2 2 2 2 2 Address +14, +16, +18, +20, +22, +24, +26, +28, +30, +32, +34, +36, +38, +40, +42, +44, +46, +48, +50, +52, +54, +56, +58, +60, +62, 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 45 47 49 51 53 55 57 59 61 63 Point ID Description 0x6F87 0x6F88 0x6F89 0x6F8A 0x6F8B 0x6F8C 0x6F8D 0x6F8E 0x6F8F 0x6F90 0x6F91 0x6F92 0x6F93 0x6F94 0x6F95 0x6F96 0x6F97 0x6F98 0x6F99 0x6F9A 0x6F9B 0x6F9C 0x6F9D 0x6F9E 0x6F9F I4 THD V1 interharmonics THD V2 interharmonics THD V3 interharmonics THD V4 interharmonics THD I1 interharmonics THD I2 interharmonics THD I3 interharmonics THD I4 interharmonics THD I1 TDD I2 TDD I3 TDD I4 TDD I1 K-Factor I2 K-Factor I3 K-Factor I4 K-Factor V1 Crest Factor V2 Crest Factor V3 Crest Factor V4 Crest Factor I1 Crest Factor I2 Crest Factor I3 Crest Factor I4 Crest Factor Generic TOU Season Energy Registers Tariff #1 register Tariff #2 register … Tariff #16 register Generic TOU Season Maximum Demand Registers Tariff #1 register Tariff #2 register … Tariff #16 register Generic Data V1 voltage V2 voltage V3 voltage V4 voltage V12 voltage 0x7000 0x7001 0x700F 0x7100 0x7101 0x710F 0x7400 0x7401 0x7402 0x7403 0x7404 3 3 Units ×0.1% ×0.1% ×0.1% ×0.1% ×0.1% ×0.1% ×0.1% ×0.1% ×0.1% ×0.1% ×0.1% ×0.1% ×0.1% ×0.1 ×0.1 ×0.1 ×0.1 ×0.01 ×0.01 ×0.01 ×0.01 ×0.01 ×0.01 ×0.01 ×0.01 Type R/W UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 R R R R R R R R R R R R R R R R R R R R R R R R R -999,999,999-999,999,999 -999,999,999-999,999,999 1 kWh 1 kWh UINT32 UINT32 -999,999,999-999,999,999 1 kWh UINT32 Options/Range 0-9999 0-9999 0-9999 0-9999 0-9999 0-9999 0-9999 0-9999 0-9999 0-1000 0-1000 0-1000 0-1000 10-9999 10-9999 10-9999 10-9999 0-10000 0-10000 0-10000 0-10000 0-10000 0-10000 0-10000 0-10000 Notes 2 2 2 2 2 2 Point references Point references 0-Pmax 0-Pmax U3 U3 UINT32 UINT32 0-Pmax U3 UINT32 0-Vmax 0-Vmax 0-Vmax 0-V4max 0-Vmax U1 U1 U1 U4 U1 UINT32 UINT32 UINT32 UINT32 UINT32 Point references 1 1 1 69 Address 70 Point ID Description 0x7405 0x7406 0x7407 0x7408 0x7409 0x740A 0x740B 0x740C 0x740D 0x740E 0x740F 0x7410 0x7411 0x7412 0x7413 0x7414 0x7415 0x7416 0x7417 0x7418 0x7419 0x741A 0x741B 0x741C 0x741D 0x741E 0x741F 0x7420 0x7421 0x7422 0x7423 0x7424 0x7425 0x7426 0x7427 0x7428 0x7429 0x742A 0x742B 0x742C 0x742D 0x742E V23 voltage V31 voltage I1 current I2 current I3 current I4 current In current I1x current I2x current I3x current I4x current Inx current Zero-sequence voltage Zero-sequence current Ix Zero-sequence current Voltage unbalance Current unbalance Ix current unbalance DC voltage Frequency V1 THD V2 THD V3 THD V4 THD I1 THD I2 THD I3 THD I4 THD V1 interharmonics THD V2 interharmonics THD V3 interharmonics THD V4 interharmonics THD I1 interharmonics THD I2 interharmonics THD I3 interharmonics THD I4 interharmonics THD I1 TDD I2 TDD I3 TDD I4 TDD I1 K-Factor I2 K-Factor Options/Range 0-Vmax 0-Vmax 0-Imax 0-Imax 0-Imax 0-I4max 0-Imax 0-Ixmax 0-Ixmax 0-Ixmax 0-I4xmax 0-Ixmax 0-Vmax 0-Imax 0-Ixmax 0-3000 0-3000 0-3000 0-999900 0-10000 0-9999 0-9999 0-9999 0-9999 0-9999 0-9999 0-9999 0-9999 0-9999 0-9999 0-9999 0-9999 0-9999 0-9999 0-9999 0-9999 0-1000 0-1000 0-1000 0-1000 10-9999 10-9999 3 3 Units U1 U1 U2 U2 U2 U2 U2 U2 U2 U2 U2 U2 U1 U2 U2 ×0.1% ×0.1% ×0.1% ×0.01V ×0.01Hz ×0.1% ×0.1% ×0.1% ×0.1% ×0.1% ×0.1% ×0.1% ×0.1% ×0.1% ×0.1% ×0.1% ×0.1% ×0.1% ×0.1% ×0.1% ×0.1% ×0.1% ×0.1% ×0.1% ×0.1% ×0.1 ×0.1 Type UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 R/W Notes 2 2 2 2 2 2 Address Point ID Description 0x742F 0x7430 0x7431 0x7432 0x7433 0x7434 0x7435 0x7436 0x7437 0x7438 0x750F 0x7510 0x7511 0x7513 0x7514 0x7515 0x1900 0x1901 I3 K-Factor I4 K-Factor V1 Crest Factor V2 Crest Factor V3 Crest Factor V4 Crest Factor I1 Crest Factor I2 Crest Factor I3 Crest Factor I4 Crest Factor V1 impulsive voltage V2 impulsive voltage V3 impulsive voltage V12 impulsive voltage V23 impulsive voltage V31 impulsive voltage V1 H01 Harmonic voltage, %Un V1 H02 Harmonic voltage, %Un ... V1 H50 Harmonic voltage, %Un V2 H01 Harmonic voltage, %Un V2 H02 Harmonic voltage, %Un ... V2 H50 Harmonic voltage, %Un V3 H01 Harmonic voltage, %Un V3 H02 Harmonic voltage, %Un ... V3 H50 Harmonic voltage, %Un V1 Pst V2 Pst V3 Pst V1 Plt V2 Plt V3 Plt V1 Frq1 %Un, 1st signaling voltage magnitude V1 V1 Frq2 %Un, 2nd signaling voltage magnitude V1 V1 Frq3 %Un, 3rd signaling voltage magnitude V1 V1 Frq4 %Un, 4th signaling voltage magnitude V1 V2 Frq1 %Un, 1st signaling voltage magnitude V2 V2 Frq2 %Un, 2nd signaling voltage magnitude V2 V2 Frq3 %Un, 3rd signaling voltage magnitude V2 V2 Frq4 %Un, 4th signaling voltage magnitude V2 0x1931 0x1A00 0x1A01 0x1A31 0x1B00 0x1B01 0x1B31 0x2980 0x2981 0x2982 0x2983 0x2984 0x2985 0x6005 0x6006 0x6007 0x6008 0x600A 0x600B 0x600C 0x600D Options/Range 10-9999 10-9999 0-10000 0-10000 0-10000 0-10000 0-10000 0-10000 0-10000 0-10000 0-Vmax 0-Vmax 0-Vmax 0-Vmax 0-Vmax 0-Vmax 0-10000 0-10000 3 3 Type R/W Notes Units ×0.1 ×0.1 ×0.01 ×0.01 ×0.01 ×0.01 ×0.01 ×0.01 ×0.01 ×0.01 U1 U1 U1 U1 U1 U1 ×0.01% ×0.01% UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 0-10000 0-10000 0-10000 ×0.01% ×0.01% ×0.01% UINT32 UINT32 UINT32 2 0-10000 0-10000 0-10000 ×0.01% ×0.01% ×0.01% UINT32 UINT32 UINT32 2 0-10000 0-10000 0-10000 0-10000 0-10000 0-10000 0-10000 0-10000 0-10000 0-10000 0-10000 0-10000 0-10000 0-10000 0-10000 ×0.01% ×0.01 ×0.01 ×0.01 ×0.01 ×0.01 ×0.01 ×0.01% ×0.01% ×0.01% ×0.01% ×0.01% ×0.01% ×0.01% ×0.01% UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 71 Address Point ID Description 0x600F 0x6010 0x6011 0x6012 V3 V3 V3 V3 Frq1 Frq2 Frq3 Frq4 %Un, %Un, %Un, %Un, 1st signaling voltage magnitude V3 2nd signaling voltage magnitude V3 3rd signaling voltage magnitude V3 4th signaling voltage magnitude V3 Options/Range 0-10000 0-10000 0-10000 0-10000 3 3 Units ×0.01% ×0.01% ×0.01% ×0.01% Type R/W UINT32 UINT32 UINT32 UINT32 Notes 2 2 2 2 NOTES: 1 When the 4LN3, 4LL3, 3LN3, 3LL3, 3BLN3 or 3BLL3 wiring mode is selected, the voltages will be line-to-neutral; for any other wiring mode, they will be line-to-line. 2 When the 4LN3, 3LN3 or 3BLN3 wiring mode is selected, the voltages will be line-to-neutral; for any other wiring mode, they will be line-to-line voltages. 3 For volts, amps, power and frequency scales and units, refer to Section 4 ”Data Scales and Units”. 4 On a 0.2-s interval. 5 On a 3-s interval. 6 Digital input registers return the state of the level-sensitive digital inputs in a 32-bit packed format beginning from the nearest lower point number divisible by 32. For example, registers 12544-12545 and 12548-12549 report the same 32-bit value that contains the state of digital inputs DI1:DI32. Bits that reference non-existent points will contain zeros. 7 Pulse input registers contain the transition status of the edge sensitive digital inputs. A bit value is set to '1' if a pulse edge (either rising, falling, or any of them depending on the input polarity setting) has been detected on the input. Pulse inputs cannot be directly read but can be tested through the setpoints and/or linked to the pulse counters and Summary energy/TOU registers. 72 3.5 Minimum/Maximum Log Registers Address 35840-35983 +0, 1 +2, 3 +4, 5 +6, 7 +8, 9 +10, 11 +12, 13 +14, 15 +16, 17 +18, 19 +20, 21 +22, 23 +24, 25 +26, 27 +28, 29 +30, 31 +32, 33 +34, 35 +36, 37 +38, 39 +40, 41 +42, 43 +44, 45 +46, 47 +48, 49 +50, 51 +52, 53 +54, 55 +56, 57 +58, 59 +60, 61 +62, 63 +64, 65 +66, 67 +68, 69 +70, 71 +72, 73 +74, 75 +76, 77 Point ID 0x2C00 0x2C01 0x2C02 0x2C03 0x2C04 0x2C05 0x2C06 0x2C07 0x2C08 0x2C09 0x2C0A 0x2C0B 0x2C0C 0x2C0D 0x2C0E 0x2C0F 0x2C10 0x2C11 0x2C12 0x2C13 Description Minimum Phase Values Min. V1 voltage Timestamp Min. V2 voltage Timestamp Min. V3 voltage Timestamp Min. I1 current Timestamp Min. I2 current Timestamp Min. I3 current Timestamp Min. kW L1 Timestamp Min. kW L2 Timestamp Min. kW L3 Timestamp Min. kvar L1 Timestamp Min. kvar L2 Timestamp Min. kvar L3 Timestamp Min. kVA L1 Timestamp Min. kVA L2 Timestamp Min. kVA L3 Timestamp Min. Power factor L1 Timestamp Min. Power factor L2 Timestamp Min. Power factor L3 Timestamp Min. V1 voltage THD Timestamp Min. V2 voltage THD 3 3 Options/Range/Format Units Type R/W Notes 0-Vmax F1 0-Vmax F1 0-Vmax F1 0-Imax F1 0-Imax U1 sec U1 sec U1 sec U2 sec U2 sec U2 sec U3 sec U3 sec U3 sec U3 sec U3 sec U3 sec U3 sec U3 sec U3 sec ×0.001 sec ×0.001 sec ×0.001 sec ×0.1% sec ×0.1% UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 INT32 INT32 INT32 INT32 INT32 INT32 INT32 INT32 INT32 INT32 INT32 INT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R 1 0-Imax -Pmax-Pmax -Pmax-Pmax -Pmax-Pmax -Pmax-Pmax -Pmax-Pmax -Pmax-Pmax 0-Pmax 0-Pmax 0-Pmax 0-1000 0-1000 0-1000 0-9999 0-9999 1 1 Absolute value Absolute value Absolute value 2, 4 2, 4 73 Address +78, 79 +80, 81 +82, 83 +84, 85 +86, 87 +88, 89 +90, 91 +92, 93 +94, 95 +96, 97 +98, 99 +100, 101 +102, 103 +104, 105 +106, 107 +108, 109 +110, 111 +112, 113 +114, 115 +116, 117 +118, 119 +120, 121 +122, 123 +124, 125 +126, 127 +128, 129 +130, 131 +132, 133 +134, 135 +136, 137 +138, 139 +140, 141 +142, 143 36096-36119 +0, 1 +2, 3 +4, 5 +6, 7 +8, 9 +10, 11 +12, 13 +14, 15 +16, 17 +18, 19 74 Point ID 0x2C14 0x2C15 0x2C16 0x2C17 0x2C18 0x2C19 0x2C1A 0x2C1B 0x2C1C 0x2C1D 0x2C1E 0x2C1F 0x2C20 0x2C21 0x2C22 0x2C23 0x2D00 0x2D01 0x2D02 0x2D03 0x2D04 Description Timestamp Min. V3 voltage THD Timestamp Min. I1 current THD Timestamp Min. I2 current THD Timestamp Min. I3 current THD Timestamp Min. I1 K-Factor Timestamp Min. I2 K-Factor Timestamp Min. I3 K-Factor Timestamp Min. I1 current TDD Timestamp Min. I2 current TDD Timestamp Min. I3 current TDD Timestamp Min. V12 voltage Timestamp Min. V23 voltage Timestamp Min. V31 voltage Timestamp Min. I1x current Timestamp Min. I2x current Timestamp Min. I3x current Timestamp Minimum Total Values Min. Total kW Timestamp Min. Total kvar Timestamp Min. Total kVA Timestamp Min. Total PF Timestamp Min. Total PF lag Timestamp 3 Options/Range/Format 0-9999 0-9999 0-9999 0-9999 10-9999 10-9999 10-9999 0-1000 0-1000 0-1000 0-Vmax 0-Vmax 0-Vmax 0-Ixmax 0-Ixmax 0-Ixmax -Pmax-Pmax -Pmax-Pmax 0-Pmax -1000-1000 0-1000 3 Units sec ×0.1% sec ×0.1% sec ×0.1% sec ×0.1% sec ×0.1 sec ×0.1 sec ×0.1 sec ×0.1% sec ×0.1% sec ×0.1% sec U1 sec U1 sec U1 sec U2 sec U2 sec U2 sec Type R/W UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R U3 sec U3 sec U3 sec ×0.001 sec ×0.001 sec INT32 UINT32 INT32 UINT32 UINT32 UINT32 INT32 UINT32 UINT32 UINT32 R R R R R R R R R R Notes 2, 4 4 4 4 4 4 4 4 4 4 Address Point ID Description +20, 21 +22, 23 36352-36395 +0, 1 +2, 3 +4, 5 +6, 7 +8, 9 +10, 11 +12, 13 +14, 15 +16, 17 +18, 19 +20, 21 +22, 23 +24, 25 +26, 27 +28, 29 +30, 31 +32, 33 +34, 35 +36, 37 +38, 39 +40, 41 +42, 43 36608-36671 +0, 1 +2, 3 +4, 5 +6, 7 0x2D05 +60, 61 +62, 63 36864-37007 +0, 1 +2, 3 +4, 5 +6, 7 +8, 9 +10, 11 +12, 13 +14, 15 +16, 17 +18, 19 0x300F Min. Total PF lead Timestamp Minimum Auxiliary Values Min. I4 current Timestamp Min. In current Timestamp Min. Frequency Timestamp Min. Voltage unbalance Timestamp Min. Current unbalance Timestamp Min. DC voltage Timestamp Min. V4 voltage Timestamp Min. I4x current Timestamp Min. V4 THD Timestamp Min. I4x THD Timestamp Min. I4x TDD Timestamp Programmable Min/Max Minimum Values Min. Min/Max Register #1 Timestamp Min. Min/Max Register #2 Timestamp … Min. Min/Max Register #16 Timestamp Maximum Phase Values Max. V1 voltage Timestamp Max. V2 voltage Timestamp Max. V3 voltage Timestamp Max. I1 current Timestamp Max. I2 current Timestamp 0x2E00 0x2E01 0x2E02 0x2E03 0x2E04 0x2E05 0x2E06 0x2E07 0x2E08 0x2E09 0x2E0A 0x3000 0x3001 0x3400 0x3401 0x3402 0x3403 0x3404 3 3 Options/Range/Format 0-1000 Units ×0.001 sec Type R/W UINT32 UINT32 R R 0-Imax U2 sec U2 sec ×0.01Hz sec ×0.1% sec ×0.1% sec ×0.01V sec U4 sec U2 sec ×0.1% sec ×0.1% sec ×0.1% sec UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 R R R R R R R R R R R R R R R R R R R R R R UINT32 UINT32 UINT32 UINT32 R R R R UINT32 UINT32 R R UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 R R R R R R R R R R 0-Imax 0-10000 0-3000 0-3000 0-999900 0-V4max 0-Ixmax 0-9999 0-9999 0-1000 0-Vmax 0-Vmax 0-Vmax 0-Imax 0-Imax U1 sec U1 sec U1 sec U2 sec U2 sec Notes 4 4 4 1 1 1 75 Address +20, 21 +22, 23 +24, 25 +26, 27 +28, 29 +30, 31 +32, 33 +34, 35 +36, 37 +38, 39 +40, 41 +42, 43 +44, 45 +46, 47 +48, 49 +50, 51 +52, 53 +54, 55 +56, 57 +58, 59 +60, 61 +62, 63 +64, 65 +66, 67 +68, 69 +70, 71 +72, 73 +74, 75 +76, 77 +78, 79 +80, 81 +82, 83 +84, 85 +86, 87 +88, 89 +90, 91 +92, 93 +94, 95 +96, 97 +98, 99 +100, 101 +102, 103 +104, 105 +106, 107 76 Point ID Description 0x3405 Max. I3 current Timestamp Max. kW L1 Timestamp Max. kW L2 Timestamp Max. kW L3 Timestamp Max. kvar L1 Timestamp Max. kvar L2 Timestamp Max. kvar L3 Timestamp Max. kVA L1 Timestamp Max. kVA L2 Timestamp Max. kVA L3 Timestamp Max. Power factor L1 Timestamp Max. Power factor L2 Timestamp Max. Power factor L3 Timestamp Max. V1 voltage THD Timestamp Max. V2 voltage THD Timestamp Max. V3 voltage THD Timestamp Max. I1 current THD Timestamp Max. I2 current THD Timestamp Max. I3 current THD Timestamp Max. I1 K-Factor Timestamp Max. I2 K-Factor Timestamp Max. I3 K-Factor Timestamp 0x3406 0x3407 0x3408 0x3409 0x340A 0x340B 0x340C 0x340D 0x340E 0x340F 0x3410 0x3411 0x3412 0x3413 0x3414 0x3415 0x3416 0x3417 0x3418 0x3419 0x341A 3 Options/Range/Format 0-Imax -Pmax-Pmax -Pmax-Pmax -Pmax-Pmax -Pmax-Pmax -Pmax-Pmax -Pmax-Pmax 0-Pmax 0-Pmax 0-Pmax 0-1000 0-1000 0-1000 0-9999 0-9999 0-9999 0-9999 0-9999 0-9999 10-9999 10-9999 10-9999 3 Units U2 sec U3 sec U3 sec U3 sec U3 sec U3 sec U3 sec U3 sec U3 sec U3 sec ×0.001 sec ×0.001 sec ×0.001 sec ×0.1% sec ×0.1% sec ×0.1% sec ×0.1% sec ×0.1% sec ×0.1% sec ×0.1 sec ×0.1 sec ×0.1 sec Type R/W UINT32 UINT32 INT32 INT32 INT32 INT32 INT32 INT32 INT32 INT32 INT32 INT32 INT32 INT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R Notes Absolute value Absolute value Absolute value 2, 4 2, 4 2, 4 4 4 4 4 4 4 Address +108, 109 +110, 111 +112, 113 +114, 115 +116, 117 +118, 119 +120, 121 +122, 123 +124, 125 +126, 127 +128, 129 +130, 131 +132, 133 +134, 135 +136, 137 +138, 139 +140, 141 +142, 143 37120-37143 +0, 1 +2, 3 +4, 5 +6, 7 +8, 9 +10, 11 +12, 13 +14, 15 +16, 17 +18, 19 +20, 21 +22, 23 37376-37419 +0, 1 +2, 3 +4, 5 +6, 7 +8, 9 +10, 11 +12, 13 +14, 15 +16, 17 +18, 19 +20, 21 +22, 23 Point ID Description 0x341B Max. I1 current TDD Timestamp Max. I2 current TDD Timestamp Max. I3 current TDD Timestamp Max. V12 voltage Timestamp Max. V23 voltage Timestamp Max. V31 voltage Timestamp Max. I1x current Timestamp Max. I2x current Timestamp Max. I3x current Timestamp Maximum Total Values Max. Total kW Timestamp Max. Total kvar Timestamp Max. Total kVA Timestamp Max. Total PF Timestamp Max. Total PF lag Timestamp Max. Total PF lead Timestamp Maximum Auxiliary Values Max. I4 current Timestamp Max. In current Timestamp Max. Frequency Timestamp Max. Voltage unbalance Timestamp Max. Current unbalance Timestamp Max. DC voltage Timestamp 0x341C 0x341D 0x341E 0x341F 0x3420 0x3421 0x3422 0x3423 0x3500 0x3501 0x3502 0x3503 0x3504 0x3505 0x3600 0x3601 0x3602 0x3603 0x3604 0x3605 3 Options/Range/Format 0-1000 0-1000 0-1000 0-Vmax 0-Vmax 0-Vmax 0-Ixmax 0-Ixmax 0-Ixmax -Pmax-Pmax -Pmax-Pmax 0-Pmax -1000-1000 0-1000 0-1000 0-Imax 0-Imax 0-10000 0-3000 0-3000 0-999900 3 Units ×0.1% sec ×0.1% sec ×0.1% sec U1 sec U1 sec U1 sec U2 sec U2 sec U2 sec Type R/W Notes UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 R R R R R R R R R R R R R R R R R R 4 U3 sec U3 sec U3 sec ×0.001 sec ×0.001 sec ×0.001 sec INT32 UINT32 INT32 UINT32 UINT32 UINT32 INT32 UINT32 UINT32 UINT32 UINT32 UINT32 R R R R R R R R R R R R U2 sec U2 sec ×0.01Hz sec ×0.1% sec ×0.1% sec x0.01V sec UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 R R R R R R R R R R R R 4 4 77 Address 78 Point ID Description +24, 25 +26, 27 +28, 29 +30, 31 +32, 33 +34, 35 +36, 37 +38, 39 +40, 41 +42, 43 37504-37567 +0, 1 +2, 3 +4, 5 +6, 7 0x3606 +60, 61 +62, 63 37632-37719 +0, 1 +2, 3 +4, 5 +6, 7 +8, 9 +10, 11 +12, 13 +14, 15 +16, 17 +18, 19 +20, 21 +22, 23 +24, 25 +26, 27 +28, 29 +30, 31 +32, 33 +34, 35 +36, 37 +38, 39 +40, 41 +42, 43 +44, 45 +46, 47 +48, 49 0x4783 Max. V4 voltage Timestamp Max. I4x current Timestamp Max. V4 THD Timestamp Max. I4x THD Timestamp Max. I4x TDD Timestamp Summary Energy Maximum Demands Summary register #1 Maximum Demand Timestamp Summary register #2 Maximum Demand Timestamp … Summary register #16 Maximum Demand Timestamp Maximum Demands V1 Maximum volt demand Timestamp V2 Maximum volt demand Timestamp V3 Maximum volt demand Timestamp I1 Maximum ampere demand Timestamp I2 Maximum ampere demand Timestamp I3 Maximum ampere demand Timestamp Not used Timestamp Not used Timestamp Not used Timestamp Maximum kW import sliding window demand Timestamp Maximum kvar import sliding window demand Timestamp Maximum kVA sliding window demand Timestamp Not used 0x3607 0x3608 0x3609 0x360A 0x4780 0x4781 0x3700 0x3701 0x3702 0x3703 0x3704 0x3705 0x3706 0x3707 0x3708 0x3709 0x370A 0x370B 0x3737 3 3 Units U4 sec U2 sec ×0.1% sec ×0.1% sec ×0.1% sec Type R/W UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 R R R R R R R R R R 0-Pmax U3 UINT32 R 0-Pmax U3 UINT32 R 0-Pmax U3 UINT32 R 0-Vmax U1 sec U1 sec U1 sec U2 sec U2 sec U2 sec UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 R R R R R R R R R R R R R R R R R R R R R R R R R Options/Range/Format 0-V4max 0-Ixmax 0-9999 0-9999 0-1000 0-Vmax 0-Vmax 0-Imax 0-Imax 0-Imax 0 0 0 0-Pmax 0-Pmax 0-Pmax 0 U3 sec U3 sec U3 sec Notes 4 4 4 2 2 2 Address +50, 51 +52, 53 +54, 55 +56, 57 +58, 59 +60, 61 +62, 63 +64, 65 +66, 67 +68, 69 +70, 71 +72, 73 +74, 75 +76, 77 +78, 79 +80, 81 +82, 83 +84, 85 +86, 87 37888-37951 +0, 1 +2, 3 +4, 5 +6, 7 +60, 61 +62, 63 38016-38063 +0, 1 +2, 3 +4, 5 +6, 7 +8, 9 +10, 11 +12, 13 +14, 15 +16, 17 +18, 19 +20, 21 +22, 23 +24, 25 +26, 27 +28, 29 +30, 31 Point ID 0x370D 0x370E 0x370F 0x3710 0x3737 0x3712 0x3713 0x3714 0x3715 0x3800 0x3801 0x380F 0x3880 0x3881 0x3882 0x3883 0x3884 0x3885 0x3886 0x3887 Description Timestamp Not used Timestamp Not used Timestamp Maximum kW export sliding window demand Timestamp Maximum kvar export sliding window demand Timestamp Not used Timestamp Not used Timestamp V4 Maximum volt demand Timestamp I4 Maximum ampere demand Timestamp In Maximum ampere demand Timestamp Programmable Min/Max Maximum Values Max. Min/Max Register #1 Timestamp Max. Min/Max Register #2 Timestamp … Max. Min/Max Register #16 Timestamp Maximum Harmonic Demands V1 THD demand Timestamp V2 THD demand Timestamp V3 THD demand Timestamp V4 THD demand Timestamp I1 THD demand Timestamp I2 THD demand Timestamp I3 THD demand Timestamp I4 THD demand Timestamp 3 Options/Range/Format 3 Units 0 0 0-Pmax 0-Pmax U3 sec U3 sec 0 0 0-Vmax 0-I4max 0-Imax 0-9999 0-9999 0-9999 0-9999 0-9999 0-9999 0-9999 0-9999 U4 sec U2 sec U2 sec ×0.1% sec ×0.1% sec ×0.1% sec ×0.1% sec ×0.1% sec ×0.1% sec ×0.1% sec ×0.1% sec Type R/W UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 R R R R R R R R R R R R R R R R R R R UINT32 UINT32 UINT32 UINT32 R R R R UINT32 UINT32 R R UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 R R R R R R R R R R R R R R R R Notes 2 2 2 79 Address +32, 33 +34, 35 +36, 37 +38, 39 +40, 41 +42, 43 +44, 45 +46, 47 38144-38207 +0, 1 +2, 3 +4, 5 +6, 7 Point ID Description 0x3888 I1 TDD demand Timestamp I2 TDD demand Timestamp I3 TDD demand Timestamp I4 TDD demand Timestamp TOU Maximum Demand Register #1 Tariff #1 register Timestamp Tariff #2 register Timestamp … Tariff #16 register Timestamp TOU Maximum Demand Register #4 Tariff #1 register Timestamp Tariff #2 register Timestamp … Tariff #16 register Timestamp TOU Maximum Demand Register #2 Tariff #1 register Timestamp Tariff #2 register Timestamp … Tariff #16 register Timestamp TOU Maximum Demand Register #5 Tariff #1 register Timestamp Tariff #2 register Timestamp … Tariff #16 register Timestamp TOU Maximum Demand Register #3 Tariff #1 register 0x3889 0x388A 0x388B 0x4800 0x4801 +60, 61 0x480F +62, 63 38272-38335 +0, 1 0x4880 +2, 3 +4, 5 0x4881 +6, 7 +60, 61 0x488F +62, 63 38400-38463 +0, 1 0x4900 +2, 3 +4, 5 0x4901 +6, 7 +60, 61 0x490F +62, 63 38528-38591 +0, 1 0x4980 +2, 3 +4, 5 0x4981 +6, 7 +60, 61 0x498F +62, 63 38656-38719 +0, 1 0x4A00 80 3 3 Units ×0.1% sec ×0.1% sec ×0.1% sec ×0.1% sec Type R/W UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 R R R R R R R R U3 sec U3 sec UINT32 UINT32 UINT32 UINT32 0-Pmax U3 sec UINT32 UINT32 R R R R R R R 0-Pmax U3 sec U3 sec UINT32 UINT32 UINT32 UINT32 0-Pmax U3 sec UINT32 UINT32 0-Pmax U3 sec U3 sec UINT32 UINT32 UINT32 UINT32 0-Pmax U3 sec UINT32 UINT32 0-Pmax U3 sec U3 sec UINT32 UINT32 UINT32 UINT32 0-Pmax U3 sec UINT32 UINT32 R R R R R R R 0-Pmax U3 UINT32 R Options/Range/Format 0-1000 0-1000 0-1000 0-1000 0-Pmax 0-Pmax 0-Pmax 0-Pmax 0-Pmax R R R R R R R R R R R R R R Notes Address Point ID +2, 3 +4, 5 0x4A01 +6, 7 +60, 61 0x4A0F +62, 63 38784-38847 +0, 1 0x4A80 +2, 3 +4, 5 0x4A81 +6, 7 +60, 61 0x4A8F +62, 63 38912-38975 +0, 1 0x5300 +2, 3 +4, 5 0x5301 +6, 7 +60, 61 0x530F +62, 63 39040-39103 +0, 1 0x5380 +2, 3 +4, 5 0x5381 +6, 7 +60, 61 0x538F +62, 63 39168-39231 +0, 1 0x5400 +2, 3 +4, 5 0x5401 +6, 7 +60, 61 0x540F +62, 63 39296-39359 +0, 1 0x5480 +2, 3 +4, 5 0x5481 Description Timestamp Tariff #2 register Timestamp … Tariff #16 register Timestamp TOU Maximum Demand Register #6 Tariff #1 register Timestamp Tariff #2 register Timestamp … Tariff #16 register Timestamp TOU Maximum Demand Register #7 Tariff #1 register Timestamp Tariff #2 register Timestamp … Tariff #16 register Timestamp TOU Maximum Demand Register #8 Tariff #1 register Timestamp Tariff #2 register Timestamp … Tariff #16 register Timestamp TOU Maximum Demand Register #9 Tariff #1 register Timestamp Tariff #2 register Timestamp … Tariff #16 register Timestamp TOU Maximum Demand Register #10 Tariff #1 register Timestamp Tariff #2 register 3 3 Units sec U3 sec Type R/W UINT32 UINT32 UINT32 0-Pmax U3 sec UINT32 UINT32 R R R R R R 0-Pmax U3 sec U3 sec UINT32 UINT32 UINT32 UINT32 0-Pmax U3 sec UINT32 UINT32 0-Pmax U3 sec U3 sec UINT32 UINT32 UINT32 UINT32 0-Pmax U3 sec UINT32 UINT32 0-Pmax U3 sec U3 sec UINT32 UINT32 UINT32 UINT32 0-Pmax U3 sec UINT32 UINT32 0-Pmax U3 sec U3 sec UINT32 UINT32 UINT32 UINT32 0-Pmax U3 sec UINT32 UINT32 R R R R R R R 0-Pmax U3 sec U3 UINT32 UINT32 UINT32 R R R Options/Range/Format 0-Pmax 0-Pmax 0-Pmax 0-Pmax 0-Pmax 0-Pmax Notes R R R R R R R R R R R R R R R R R R R R R 81 Address Point ID +6, 7 +60, 61 0x548F +62, 63 39424-39487 +0, 1 0x5500 +2, 3 +4, 5 0x5501 +6, 7 +60, 61 0x550F +62, 63 39552-39615 +0, 1 0x5580 +2, 3 +4, 5 0x5581 +6, 7 +60, 61 0x558F +62, 63 39680-39743 +0, 1 0x5600 +2, 3 +4, 5 0x5601 +6, 7 +60, 61 0x560F +62, 63 39808-39871 +0, 1 0x5680 +2, 3 +4, 5 0x5681 +6, 7 +60, 61 0x568F +62, 63 39936-39999 +0, 1 0x5700 +2, 3 +4, 5 0x5701 +6, 7 82 Description Timestamp … Tariff #16 register Timestamp TOU Maximum Demand Register #11 Tariff #1 register Timestamp Tariff #2 register Timestamp … Tariff #16 register Timestamp TOU Maximum Demand Register #12 Tariff #1 register Timestamp Tariff #2 register Timestamp … Tariff #16 register Timestamp TOU Maximum Demand Register #13 Tariff #1 register Timestamp Tariff #2 register Timestamp … Tariff #16 register Timestamp TOU Maximum Demand Register #14 Tariff #1 register Timestamp Tariff #2 register Timestamp … Tariff #16 register Timestamp TOU Maximum Demand Register #15 Tariff #1 register Timestamp Tariff #2 register Timestamp … 3 3 Units sec Type R/W UINT32 0-Pmax U3 sec UINT32 UINT32 R R R R 0-Pmax U3 sec U3 sec UINT32 UINT32 UINT32 UINT32 0-Pmax U3 sec UINT32 UINT32 0-Pmax U3 sec U3 sec UINT32 UINT32 UINT32 UINT32 0-Pmax U3 sec UINT32 UINT32 0-Pmax U3 sec U3 sec UINT32 UINT32 UINT32 UINT32 0-Pmax U3 sec UINT32 UINT32 0-Pmax U3 sec U3 sec UINT32 UINT32 UINT32 UINT32 0-Pmax U3 sec UINT32 UINT32 0-Pmax U3 sec U3 sec UINT32 UINT32 UINT32 UINT32 Options/Range/Format 0-Pmax 0-Pmax 0-Pmax 0-Pmax 0-Pmax R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R Notes Address Point ID +60, 61 0x570F +62, 63 40064-40127 +0, 1 0x5780 +2, 3 +4, 5 0x5781 +6, 7 +60, 61 0x578F +62, 63 Description Tariff #16 register Timestamp TOU Maximum Demand Register #16 Tariff #1 register Timestamp Tariff #2 register Timestamp … Tariff #16 register Timestamp 3 3 Options/Range/Format 0-Pmax Units U3 sec Type R/W UINT32 UINT32 R R 0-Pmax U3 sec U3 sec UINT32 UINT32 UINT32 UINT32 U3 sec UINT32 UINT32 R R R R R R R 0-Pmax 0-Pmax Notes NOTES: 1 When the 4LN3, 4LL3, 3LN3, 3LL3, 3BLN3 or 3BLL3 wiring mode is selected, the voltages will be line-to-neutral; for any other wiring mode, they will be line-to-line. 2 When the 4LN3, 3LN3 or 3BLN3 wiring mode is selected, the voltages will be line-to-neutral; for any other wiring mode, they will be line-to-line voltages. 3 For volts, amps, power and frequency scales and units, refer to Section 4 ”Data Scales and Units”. 4 On a 0.2-s interval. 83 3.6 Device Control and Status Registers Address Point ID Description Event Flags Registers (bit map) 44032-44033 Event flags set register (0 = no effect, 1 = set) 44034-44035 Event flags clear register (0=clear, 1 = no effect) 44036-44037 Event flags status (0 = cleared, 1 = set) Remote Relay Control Registers (bit map) 44038-44045 Reserved 44046-44049 Force relay operate register: 0 = no effect, 1 = operate 44050-44053 Force relay release register: 0 = no effect, 1 = release 44054-44057 Locally latched relays status: 0 = unlatched, 1 = locally latched 44058-44061 Remote latched relays status: 0 = unlatched, 1 = remote latched 44062-44065 Relay access enabled status: 0 = local/remote access enabled, 1 = local/remote access disabled 44066-44069 Relay status: 0 = open, 1 = closed 44070-44073 Latch relays mode: 0 = unlatched mode, 1 = latched mode 44074-44077 Pulse relays mode: 0 = not pulse mode, 1 = pulse mode 44078-44081 KYZ relays mode: 0 = not KYZ mode, 1 = KYZ mode 44082-44085 Relay polarity mode: 0 = normal mode, 1 = inverting mode 44086-44089 Relay blocking mode: 0 = normal mode, 1 = blocked mode 44090-44093 Blocked relay status: 0 = relay unblocked, 1 = relay blocked 44094-44101 Reserved Reset/Clear Registers 44102 Clear energies 44103 Clear maximum demands 44104 84 Clear Summary and TOU energy registers Options/Range 0x00000000 - 0xFFFFFFF 0x00000000 - 0xFFFFFFF 0x00000000 - 0xFFFFFFF 0x00000000 0x00000000 0x00000000 0x00000000 0x00000000 0x00000000 0x00000000 0x00000000 0x00000000 0x00000000 - 0xFFFFFFFF 0xFFFFFFFF 0xFFFFFFFF 0xFFFFFFFF 0xFFFFFFFF 0xFFFFFFFF 0xFFFFFFFF 0xFFFFFFFF 0xFFFFFFFF 0xFFFFFFFF 0x00000000 0x00000000 0x00000000 0x00000000 0x00000000 0x00000000 0x00000000 0x00000000 0x00000000 0x00000000 0x00000000 0x00000000 0x00000000 0x00000000 - 0xFFFFFFFF 0xFFFFFFFF 0xFFFFFFFF 0xFFFFFFFF 0xFFFFFFFF 0xFFFFFFFF 0xFFFFFFFF 0xFFFFFFFF 0xFFFFFFFF 0xFFFFFFFF 0xFFFFFFFF 0xFFFFFFFF 0xFFFFFFFF 0xFFFFFFFF Units Type R/W Notes UINT32 UINT32 UINT32 W W R Read as 0 Read as 0 UINT32 UINT64 W Read as 0 UINT64 W Read as 0 UINT64 R UINT64 R UINT64 R UINT64 R UINT64 R UINT32 R UINT64 R UINT64 R UINT64 R UINT64 R UINT64 0 0= 1= 2= 3= 4= 5= 0 clear clear clear clear clear clear all maximum demands power demands volt and ampere demands volt demands ampere demands harmonic demands UINT16 UINT16 W W UINT16 W Access to a relay is disabled if a pulse source is linked to the relay Relay control commands are ignored if a relay is blocked Address Point ID 44105 44106 Description Clear Summary and TOU maximum demands Clear counters 44107 Clear Min/Max log 44108 Clear Statistics 44109-44133 Reserved Device Mode Control Registers 44134 Energy test mode 44135 Control setpoints operation 44136 PQ recorder 44137 Fault recorder 44138-44165 Reserved 44166-44261 Reserved Memory Status Registers 44262-44263 Memory size, bytes 44264-44265 Free memory, bytes 44266-44277 Reserved Log Notification Registers (bit map) 44278-44279 Files 0-31 (0 = no new logs, 1 = new record logged) 44280-44281 Files 32-63 (0 = no new logs, 1 = new record logged) 44282-44283 Files 64-95 (0 = no new logs, 1 = new record logged) 44284-44285 Files 96-127 (0 = no new logs, 1=new record logged) 44286-44293 Reserved Setpoint Status Registers (bit map) 44294-44295 Setpoints 1-32 status (0 = released, 1 = operated) 44296-44309 Reserved Setpoint Alarm Latch Registers (bit map) 44310-44311 Setpoints 1-32 alarm status. When read: 0 = no setpoint operations logged, 1 = setpoint has been operated at least once since the last alarm bit reset. When written: 0 = clear setpoint alarm bit, 1 = no effect. 44312-44325 Reserved Device Diagnostics Register (bit map) 44326-44327 Device self-diagnostics flags. When read: 0 = no faults logged, 1 = a fault bit has been set at least once since the last reset. When written: 0 = clear a fault bit, 1 = no effect. 44328-44341 Reserved Port Identification 44342 Active port number Options/Range 0 0 = clear all counters, 1-32 = clear counter #1-#32 0 0 = clear EN50160 statistics 0 0 0 0 = = = = disabled, disabled, disabled, disabled, 1 1 1 1 = = = = enabled enabled enabled enabled Units Type UINT16 UINT16 R/W W W UINT16 UINT16 UINT16 W W UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT32 UINT32 UINT32 R R R 0xFFFFFFFF 0xFFFFFFFF 0xFFFFFFFF 0xFFFFFFFF UINT32 UINT32 UINT32 UINT32 UINT32 R R R R R 0x00000000 - 0xFFFFFFFF UINT32 UINT32 R R 0x00000000 - 0xFFFFFFFF UINT32 R/W F23 UINT32 R/W 0-2 = serial port COM1-COM3, 3 = IR Port, 4 = Modem port, 5 = USB/Modbus port, 6-10 = Ethernet/TCP port UINT16 R 0x00000000 0x00000000 0x00000000 0x00000000 - Notes 85 Address Point ID Description Options/Range 44343-44345 Reserved Current Network Settings 44346-44377 +0, 1 Active device IP Address +2, 3 Active network subnet mask +4, 5 Active network default gateway 44352-44377 Reserved Device Authorization Register 44378-44379 When write: 8-digit password. When read: 0 = access 0 - 99999999 (write) permitted, -1 = authorization required. 0/-1 (read) 44380-44385 Reserved 44386-45951 Reserved Factory Diagnostic Registers 45952-46079 Factory diagnostic registers 86 Units Type R/W Notes UINT32 UINT32 UINT32 R R R Network byte order Network byte order Network byte order INT32 R/W UINT32 R 3.7 Device Setup Registers Address Point ID Device Identification 46080-46111 +0,1 +2,3 +4-11 +12-13 +14-19 +20 +21 +22 +23 +24 +25 +26-31 Factory Device Settings 46112-46207 +0 +1 +2 +3 +4 +5 +6 +7 +8 +9 +10 +11 +12 +13 +14-63 +64 +65 +66 +67-95 Basic Setup 46208-46271 +0 +1 +2 Description Options/Range Device serial number Device model ID Device model name Device options (bitmap) Reserved Device firmware version number Device firmware build number DSP firmware version number DSP firmware build number Boot loader version number Boot loader build number Reserved 1-999999 310, 320, 330 “SA310”, “SA320”, “SA330” V1-V3 input range V1-V3 input overload V4 input range V4 input overload I1-I3 input range I1-I3 input overload I4 input range I4 input overload I1x-I3x input range I1x-I3x input overload I4x input range I4x input overload VDC input range VDC input overload Reserved Ethernet MAC address 0-1 Ethernet MAC address 2-3 Ethernet MAC address 4-5 Reserved 690 120 690 120 1, 5 400 (ANSI), 200 (IEC) 1, 5 400 (ANSI), 200 (IEC) 1, 5 3000 1, 5 3000 300 100 Wiring mode PT ratio (primary to secondary ratio) PT secondary (Line-to-Line) F26 10-65000 10-690 Units V % V % A % A % A % A % V % 0x0500 0x00F0 0x0000-0xFFFF ×0.1 V Type R/W UINT32 UINT32 CHAR16 UINT32 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 R R R R R R R R R R R R UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 R R R R R R R R R R R R R R R R R R R UINT16 UINT16 UINT16 R/W R/W R/W Notes Null-terminated string 87 Address Point ID +3 +4 +5 +6 +7 +8 +9 +10 +11 +12 +13-15 +16 +17 +18 +19-23 +24 +25 +26 +27 +28-31 Demands Setup 46240-46255 +0 +1 +2 Description V4 PT ratio (primary to secondary ratio) V4 PT secondary voltage CT primary current CT secondary current I4 CT primary current I4 CT secondary current Ix CT primary current Ix CT secondary current I4x CT primary current I4x CT secondary current Reserved VDC nominal voltage Nominal line frequency Phase order Reserved I maximum demand load current I4 maximum demand load current Ix maximum demand load current I4x maximum demand load current Reserved Options/Range 10-65000 10-690 1-10000 1, 5 1-10000 1, 5 1-10000 1, 5 1-10000 1-10000 Units ×0.1 V A A A A A A A A 10-300 50, 60 0 = ABC, 1 = CBA V Hz 0-10000 0-10000 0-10000 0-10000 A A A A Power demand period (block interval) Number of demand periods in a sliding window Demand synchronization source input 1, 2, 5, 10, 15, 30, 60 1-15 0 = device clock, 1-96 = DI1-DI96 min +3-7 +8 +9 +10 +11-15 Device Options Setup 46256-46399 +0 Reserved Volt demand period Ampere demand period Harmonic demand period Reserved 0-9000 0-9000 0-9000 sec sec sec +1 +2-7 +8 88 Power calculation mode Energy roll value Reserved “kWh”/”kvarh” LED pulse rate, Wh/varh per pulse (in 0 = using reactive power: S = f(P,Q), 1 = using non-active power: Q = f(S,P) 0 = 1×104, 1 = 1×105, 2 = 1×106, 3 = 1×107, 4 = 1×108, 5 = 1×109 1 - 10000 ×0.01Wh Type UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W UINT16 UINT16 UINT16 R/W R/W R/W UINT16 UINT16 UINT16 UINT16 UINT16 R/W R/W R/W R/W R/W UINT16 R/W UINT16 R/W UINT16 UINT16 R/W R/W Notes A DI input is considered a pulse or KYZ input. The pulse edge restarts the power demand accumulation interval. Address Point ID Description secondary units) “VDC MEASURE LOW” LED alarm threshold, % Reserved Options/Range Units Type R/W 10 - 1000 ×0.1% UINT16 UINT16 R/W R/W Local time offset, min 0-+/-720 INT16 R/W +1 Daylight savings time (DST) option UINT16 R/W +2 +3 DST start month DST start week of the month UINT16 UINT16 R/W R/W +4 +5 +6 DST start weekday DST end month DST end week of the month UINT16 UINT16 UINT16 R/W R/W R/W +7 +8 DST end weekday Clock synchronization source 0 = DST disabled (standard time only), 1 = DST enabled 1 - 12 1 - 4 = 1st, 2nd, 3rd and 4th week, 5 = the last week of the month 1-7 (1= Sun, 7 = Sat) 1 – 12 1 - 4 = 1st, 2nd, 3rd and 4th week, 5 = the last week of the month 1-7 (1= Sun, 7 = Sat) 0 = GPS IRIG-B master clock, 0x0001-0x0060 = DI1-DI96 1PPM, 0x1001-0x1060 = DI1-DI96 1PPS, 0xfffe = SNTP, 0xffff = none UINT16 UINT16 R/W R/W UINT16 R/W UINT32 UINT32 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 R/W R/W R/W R/W R/W R/W R/W R/W R/W R R UINT16 R +9 +12-143 Time/Date Setup 46400-46415 +0 +9-15 Clock Setup and Status 46416-46447 +0,1 +2,3 +4 +5 +6 +7 +8 +9 +10 +11 +12 +13 Reserved Local time, in seconds, since Jan 1, 1970 Fractional seconds, µsec Fractional seconds, milliseconds Seconds Minutes Hour Day of month Month Year (calendar year minus 2000) Weekday Daylight savings time status IRIG-B status +14-31 Reserved Communication Ports Setup 46448-46575 F1 0-999 0-59 0-59 0-23 1-31 1-12 0-99 1-7 (Sun = 1, Sat = 7) 0 = standard time, 1 = daylight savings time is active 0, 1 = no signal, 2 = time unlocked, 3 = time locked sec µsec Notes Offset in minutes from UTC (Universal Coordinated or Greenwich Mean time) A DI input is considered a pulse or KYZ input. The pulse edge aligns the clock at the nearest whole minute. UINT16 89 Address +0 Point ID Description Communication protocol +1 Interface +2 +3 Device address Baud rate +4 Data format +5 CTS mode +6 RTS mode +7 +8 +9-15 46448-46463 46464-46479 46480-46495 46496-46511 46512-46527 46528-46575 Network Setup 46576-46703 +0,1 +2,3 +4,5 +6,7 +8,9 Minimum delay before sending data Inter-character time-out Reserved COM1 Setup COM2 Setup COM3 Setup COM4 Setup COM5 Setup Reserved +10-127 Password Setup 46704-46707 +0,1 +2 +3 46708-46767 Reserved 46768-51893 90 Device IP Address Network subnet mask Network default gateway Use DHCP TCP service port Communications password (8 digits) Password protection enabled Reserved Reserved Reserved Options/Range Units 0 = Modbus RTU, 1 = Modbus ASCII, 2 = DNP3.0 0 = RS-232, 1 = RS-422, 2 = RS485, 3 = Infrared, 4 = Modem 1-247 1 = 300 bps, 2 = 600 bps, 3 = 1200 bps, 4 = 2400 bps, 5 = 4800 bps, 6 = 9600 bps, 7 = 19200 bps, 8 = 38400 bps, 9 = 57600 bps, 10 = 115200 bps 0 = 7 bits/even parity, 1 = 8 bits/no parity, 2 = 8 bits/even parity 0 = not used, 1 = wait for CTS before sending data 0 = not used, 1 = RTS is asserted during the transmission 0-1000 (default = 5) ms 0-1000 (default = 4-character time) ms Type UINT16 R/W R/W UINT16 R/W UINT16 UINT16 R/W R/W UINT16 R/W UINT16 R/W UINT16 R/W UINT16 UINT16 R/W R/W 0x01000000-0xFFFFFFFF 0x00000001-0xFFFFFFFF 0x00000000-0xFFFFFFFF 0 = NO, 1 = YES 502 = Modbus/TCP, 20000 = DNP3.0/TCP UINT32 UINT32 UINT32 UINT32 UINT32 R/W R/W R/W R/W R/W Notes N/A for COM2-COM5 (read as 65535) N/A for COM2-COM5 (read as 65535) Network byte order Network byte order Network byte order Only for firmware versions older than 10.2.16 R/W 0 - 99999999 0 = disabled, 1 = enabled UINT32 UINT16 UINT16 R/W R/W R/W Read as 0 Address Point ID Description Expert Power Service Setup 46768-46783 +0,1 Expert Power server IP Address +2,3 Expert Power server TCP service port +4,5 Expert Power client enabled +6,7 Time to next session Time to next session +8,9 +10-15 Reserved Internet Service Provider (ISP) accounts 46784-46879 +0-15 ISP telephone number +16-31 Login name +32-47 Login password 46784-46831 Account No.1 46832-46879 Account No.2 SNTP Client Setup 46880-46895 +0,1 SNTP client enabled +2,3 Polling interval +4-7 Reserved +8,9 Primary SNTP server IP address +10,11 Secondary SNTP server IP address +12-15 Reserved EN50160 PQ Recorder Triggers Setup (EN50160 voltage characteristics) 50134-50453 +0 Threshold, % +1 Hysteresis, % of threshold +2 Log options, bitmap +3 +4 +5 +6 +7 +8 +9 +10 +11 Waveform log number Data/RMS plot option Data log number (factory preset) 1/2-cycle RMS plot, cycles before event 1/2-cycle RMS plot, cycles after event 1/2-cycle RMS plot duration, cycles 0.2-sec envelope RMS plot duration, seconds 3-sec envelope RMS plot duration, minutes 10-min envelope RMS plot duration, hours Options/Range 0x01000000-0xFFFFFFFF 0-65535 0 = client disabled, 1 = client enabled 1-99999 1-99999 0 = disabled, 1 = enabled 60-86400 0 0x01000000-0xFFFFFFFF 0x01000000-0xFFFFFFFF Units min min s 0 - 2000 ×0.1% 0 - 500 ×0.1% Bit 0 – waveform log on event start: 0 = disabled, 1 = enabled; Bit 1 – waveform log on event end: 0 = disabled, 1 = enabled; Bit 2 – PQ log: 0 = enabled, 1 = disabled. 0 - 7 = log #1 - #7 0 = disabled, 1 = enabled 13 = log #14 0 - 20 cycle 0 - 20 cycle 0 - 10000 cycle 0 - 10000 sec 0 - 10000 min 0 - 10000 hours Type R/W Notes UINT32 UINT32 UINT32 R/W R/W R/W Default = 207.232.60.18 Default = 5001 UINT32 UINT32 R/W R CHAR32 CHAR32 CHAR32 R/W R/W R/W UINT32 UINT32 UINT32 UINT32 UINT32 R/W R/W R/W R/W R/W UINT16 UINT16 UINT16 R/W R/W R/W UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 R/W R/W R/W R/W R/W R/W R/W R/W R/W Same as previous Default = 600 s Default = 192.36.143.151 Default = 130.149.17.21 91 Address Point ID Description +12-15 Reserved 50134-50149 Power frequency, dF/Fn 50150-50165 Voltage variations, dV/Un 50166-50181 Rapid voltage changes, dV/Un 50182-50197 Flicker severity, Plt 50198-50213 Voltage dips, %Un 50214-50229 Voltage interruptions, %Un 50230-50245 Temporary overvoltages, %Un 50246-50261 Transient overvoltages, %Un 50262-50277 Voltage unbalance, % 50278-50293 Harmonic THD, % 50294-50309 Harmonic voltage, %Un 50310-50325 Interharmonic THD, % 50326-50341 Interharmonic voltage, %Un 50342-50357 Mains signaling voltage, %Un 50358-50453 Reserved Advanced EN50160 Setup 50838-50865 EN50160 Compliance Statistics +0 Evaluation +1 Evaluation period +2 First day of the week +3 Reserved EN50160 Harmonics Survey +4 Evaluation +5 Evaluation period +6-7 Reserved Rapid Voltage Changes +8 Repetition rate, per hour, maximum +9 Reserved Flicker +10 Pst period +11 Reserved Harmonic Voltage +12 THD, up to order +13 Harmonics, up to order +14-15 Reserved Interharmonic Voltage +16 Evaluation +17 THD, up to order +18 Interharmonics, up to order +19 Reserved Mains Signaling Voltage 92 Options/Range 0 Type UINT16 R/W R/W 0=disabled, 1=enabled 0=daily, 1=weekly 1=Sunday, 7=Saturday 0 UINT16 UINT16 UINT16 UINT16 R/W R/W R/W R/W 0=disabled, 1=enabled 0=daily, 1=weekly 0 UINT16 UINT16 UINT16 R/W R/W R/W 1-10 0 UINT16 UINT16 R/W R/W UINT16 UINT16 R/W R/W 25-50 25-50 0 UINT16 UINT16 UINT16 R/W R/W R/W 0=disabled, 1=enabled 25-50 25-50 0 UINT16 UINT16 UINT16 UINT16 R/W R/W R/W R/W 1-10 0 Units min Notes Address Point ID +20 +21 +22 +23 +24 +25 Description Evaluation 1st signaling frequency 2nd signaling frequency 3rd signaling frequency 4th signaling frequency Transient Overvoltage Transient detection and classification method +26-27 Reserved 50866-50901 Reserved EN50160 Harmonic Voltage Limits 50902-50965 +0 H02 limit +1 H03 limit +2 H04 limit … +48 H50 limit +49-63 Reserved EN50160 Interharmonic Voltage Limits 50966-51029 +0 H02 limit +1 H03 limit +2 H04 limit … +48 H50 limit +49-63 Reserved DNP Options Setup 51158-51183 +0 Default Binary Input Static object variation +1 Binary Input Change object variation +2 Default Binary Counter object variation +3 Frozen Binary Counter object variation +4 Reserved +5 Binary Counter Change Event object variation +6 Default Analog Input object variation +7 Reserved +8 Reserved +9 Analog Input Change Event object variation +10 Re-mapping static point indices for event objects +11 16-bit BC scaling +12 16-bit AI scaling Options/Range 0=disabled, 1=enabled 1100-30000 1100-30000 1100-30000 1100-30000 Units ×0.1Hz ×0.1Hz ×0.1Hz ×0.1Hz 0=peak voltage, 1=impulsive voltage 0 0 Type UINT16 UINT16 UINT16 UINT16 UINT16 R/W R/W R/W R/W R/W R/W UINT16 R/W UINT16 UINT16 R/W R/W 1-10000 1-10000 1-10000 ×0.01% ×0.01% ×0.01% UINT16 UINT16 UINT16 R/W R/W R/W 1-10000 ×0.01% UINT16 R/W 1-10000 1-10000 1-10000 ×0.01% ×0.01% ×0.01% UINT16 UINT16 UINT16 R/W R/W R/W 1-10000 ×0.01% UINT16 R/W UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W UINT16 R/W F24 (default 0) F24 (default 1) F24 (default 3) F24 (default 4) F24 (default 2) F24 (default 3) F24 (default 2) 0=disabled (default), 1=enabled 0=×1 (default), 1=×10, 2=×100, 3=×1000 0=disabled, 1=enabled Notes 93 Address Point ID +13 +14 +15 +16 +17 +18-21 +22,23 +24 +25 51184-51189 DNP Events Setup 51190-51445 +0,1 Description Number of Analog Input change event points Number of Binary Input change event points Number of Binary Counter change event points Options/Range 0 to 43 (default 43) 0 to 32 (default 21) 0 to 16 (default 0) Select/Operate Timeout Multi Fragment Interval Reserved Time Sync Period 2 to 30 seconds (default 10 sec) 50 to 500 ms (default 50 ms) Read as 65535 1 to 86400 seconds (default 86400 sec), 0=disable time requests 60 to 828V (default 828V) 10 to 200 (default CT secondary × CT overload) Voltage scale, secondary volts Current scale, secondary amps Units ×0.1A Type UINT16 UINT16 UINT16 R/W R/W R/W R/W UINT16 UINT16 UINT16 UINT32 R/W R/W R/W R/W UINT16 UINT16 R/W R/W Reserved Threshold/Deadband See Section 3.5 for point value limits. UINT32 R/W +2 DNP point number UINT16 R/W +3 Event scan control field (bitmap) DNP point number available for the selected object Bits 0-1 - DNP Object: 0=none, 1=AI, 2=BI, 3=BC Bit 2 – Object change event scan: 0= disabled, 1=enabled Bits 5-6 - DNP event poll class: 0=Class 1, 1=Class 2, 2=Class 3 Bit 7 – unused Bits 8-9 – Threshold/Deadband relation: 0=Delta, 1=more than (over threshold), 2=less than (under threshold) UINT16 R/W F25 Start point number for the selected object 0-128 UINT16 UINT16 R/W R/W UINT16 R/W 51190-51193 51194-51197 DNP Event #1 DNP Event #2 … 51442-51445 DNP Event #64 51446-51701 Reserved DNP Class 0 Point Assignment 51702-51797 +0 DNP object and variation +1 Start point number +2 94 Notes Number of the points in a range A hysteresis for the point return threshold is 0.05Hz for frequency and 2% of the operating threshold for other points If Event log is enabled, the source of a DNP event will be recorded to the device Event log file as a general Setpoint #17. Address Point ID 51702-51704 51705-51707 51795-51797 51798-51893 SOE Log Labels 51894-52043 +0 Description DNP Class 0 Points Range 1 Options/Range Units Type R/W Notes 0=Setpoints, 2=Faults, 3=DI, 4=RO UINT16 R/W Write the event type and point number before reading following registers 0-47 UINT16 CHAR32 CHAR32 CHAR96 UINT16 UINT16 CHAR32 CHAR96 UINT16 UINT16 R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 R/W R/W R/W R/W R/W R/W R/W DNP Class 0 Points Range 2 … DNP Class 0 Points Range 32 Reserved Event type +1 Point number +2-17 Point ID +18-33 Status ON label +34-81 Status ON description +82 Status ON color +83 Reserved +84-99 Status OFF label +100-147 Status OFF description +148 Status OFF color +149 Reserved Reserved 52044-52149 Fault Log Triggers Setup 52150-52277 +0 Trigger 1: Threshold, % +1 Trigger 1: Hysteresis, % of threshold +2 Trigger 1: Trigger enabled +3 Trigger 2: Threshold, % +4 Trigger 2: Hysteresis, % of threshold +5 Trigger 2: Trigger enabled +6-7 Reserved 52150-52157 External trigger 52158-52165 Zero-sequence current 52166-52173 Zero-sequence voltage 52174-52181 Current unbalance 52182-52189 Voltage unbalance 52190-52197 Overcurrent and Undervoltage 52198-52205 Undervoltage 52206-52213 I4 (neutral) current 52214-52277 Reserved Fault Log Recording Setup 52278-52341 +0 Log options, bitmap 0-15 0 0-15 0 0 0 0 0 0 0 - 2000 - 500 = disabled, 1 = enabled - 2000 - 500 = disabled, 1 = enabled x 0.1% x 0.1% x 0.1% x 0.1% Enabled by default Bit 0 – waveform log on event start: UINT16 R/W UINT16 R/W 95 Address Point ID Description +1 Waveform log number +2 Data/RMS plot option +3 Data log number (factory preset) +4 1/2-cycle RMS plot, cycles before event +5 1/2-cycle RMS plot, cycles after event +6 1/2-cycle RMS plot duration, cycles +7-63 Reserved IEEE 1159 PQ Log Triggers Setup (IEEE 1159 disturbance categories) 52342-52597 +0 Threshold, % +1 Hysteresis, % of threshold +2 Log options, bitmap +3 +4 +5 +6 +7 +8 +9 +10 +11 +12-15 52342-52357 52358-52373 52374-52389 52390-52405 52406-52421 52422-52437 52438-52453 52454-52469 52470-52597 File Setup 52598-53877 +0 +1 96 Waveform log number Data/RMS plot option Data log number (factory preset) 1/2-cycle RMS plot, cycles before event 1/2-cycle RMS plot, cycles after event 1/2-cycle RMS plot duration, cycles 0.2-sec envelope RMS plot duration, seconds 3-sec envelope RMS plot duration, minutes 10-min envelope RMS plot duration, hours Reserved Impulsive Sag Swell Interruption Volt Unbalance Frequency variation Harmonics Interharmonics Reserved File type File attributes (bitmap) Options/Range 0 = disabled, 1 = enabled; Bit 1 – waveform log on event end: 0 = disabled, 1 = enabled; Bit 2 – recording to PQ log: 0 = enabled, 1 = disabled. 0 - 7 = log #1 - #8 0 = disabled, 1 = enabled 12 = log #13 0 - 20 0 - 20 0 - 10000 0 Units Type R/W UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 R/W R/W R/W R/W R/W R/W R/W 0 - 2000 x 0.1% 0 - 500 x 0.1% Bit 0 – waveform log on event start: 0 = disabled, 1 = enabled; Bit 1 – waveform log on event end: 0 = disabled, 1 = enabled. 0 - 7 = log #1 - #7 0 = disabled, 1 = enabled 13 = log #14 0 - 20 cycle 0 - 20 cycle 0 - 10000 cycle 0 - 10000 sec 0 - 10000 min 0 - 10000 hours 0 UINT16 UINT16 UINT16 R/W R/W R/W UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W 0 F3 UINT16 UINT16 R/W R/W cycle cycle cycle Notes Address Point ID Description +2 Number of records in the file +3 Number of sections/channels in the file +4 Number of parameters per section record +5 Not used +6 Section record size, bytes (for info only) +7 File record size, bytes (for info only) +8,9 Allocated file size, bytes (for info only) 52598-52607 Event Log Setup 52608-52617 Data Log #1 Setup 52618-52627 Data Log #2 Setup 52628-52637 Data Log #3 Setup 52638-52647 Data Log #4 Setup 52648-52657 Data Log #5 Setup 52658-52667 Data Log #6 Setup 52668-52677 Data Log #7 Setup 52678-52687 Data Log #8 Setup 52688-52697 Data Log #9 Setup 52698-52707 Data Log #10 Setup 52708-52717 Data Log #11 Setup 52718-52727 Data Log #12 Setup 52728-52737 Data Log #13 Setup 52738-52747 Data Log #14 Setup 52748-52757 Data Log #15 Setup 52758-52767 Data Log #16 Setup 52768-52777 Waveform Log #1 Setup 52778-52787 Waveform Log #2 Setup 52788-52797 Waveform Log #3 Setup 52798-52807 Waveform Log #4 Setup 52808-52817 Waveform Log #5 Setup 52818-52827 Waveform Log #6 Setup 52828-52837 Waveform Log #7 Setup 52838-52847 Waveform Log #8 Setup 52848-52857 SOE Log Setup 52858-52867 PQ Log Setup 52868-52877 Fault Log Setup 52878-53877 Reserved Waveform Log Recorder Setup 53878-53949 +0 Sampling rate, samples per cycle +1 Number of cycles per series +3 Not used Options/Range 0-65535 (0 = delete file) 0-32 1-16 0 32, 64, 128 16-10848 (32 samples/cycle), 8-5424 (64 samples/cycle), 4-2712 (128 samples/cycle) 0 Units Type UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT32 R/W R/W R/W R/W R/W R R R UINT16 UINT16 R/W R/W UINT16 R/W Notes 0 = non-partitioned file 97 Address Point ID +4 +4,5 +6,7 53878-53885 53886-53893 53894-53901 53902-53909 53910-53917 53918-53925 53926-53933 53934-53941 53942-53949 Data Log Setup 54006-55541 +0 +1 +2 +3 +4 +5 +6 +7 +8 +9 +10 +11 +12 +13 +14 +15 +16-31 54006-54037 54038-54069 54070-54101 54102-54133 54134-54165 54166-54197 54198-54229 54230-54261 54262-54293 54294-54325 98 Description Number of cycles before trigger File channel mask (channels 1-32), bitmap File channel mask (channels 33-64), bitmap Waveform Log #1 Setup Waveform Log #2 Setup Waveform Log #3 Setup Waveform Log #4 Setup Waveform Log #5 Setup Waveform Log #6 Setup Waveform Log #7 Setup Waveform Log #8 Setup Reserved Options/Range 1-20 F9 F9 Data log parameter #1 ID Data log parameter #2 ID Data log parameter #3 ID Data log parameter #4 ID Data log parameter #5 ID Data log parameter #6 ID Data log parameter #7 ID Data log parameter #8 ID Data log parameter #9 ID Data log parameter #10 ID Data log parameter #11 ID Data log parameter #12 ID Data log parameter #13 ID Data log parameter #14 ID Data log parameter #15 ID Data log parameter #16 ID Reserved Data log #1 Setup Data log #2 Setup Data log #3 Setup Data log #4 Setup Data log #5 Setup Data log #6 Setup Data log #7 Setup Data log #8 Setup Data log #9 Setup 0x0000-0xFFFF 0x0000-0xFFFF 0x0000-0xFFFF 0x0000-0xFFFF 0x0000-0xFFFF 0x0000-0xFFFF 0x0000-0xFFFF 0x0000-0xFFFF 0x0000-0xFFFF 0x0000-0xFFFF 0x0000-0xFFFF 0x0000-0xFFFF 0x0000-0xFFFF 0x0000-0xFFFF 0x0000-0xFFFF 0x0000-0xFFFF Data log #10 Setup Units Type UINT16 UINT32 UINT32 R/W R/W R/W R/W UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W Notes Read as NONE for EN50160 Statistics log Read as NONE for EN50160 Harmonics Survey log Address Point ID Description 54326-54357 Data log #11 Setup 54358-54389 Data log #12 Setup 54390-54421 Data log #13 Setup 54422-54453 Data log #14 Setup 54454-54485 Data log #15 Setup 54486-54517 Data log #16 Setup 54518-55541 Reserved Programmable Min/Max Log Setup 55542-55573 55542 Min/Max log parameter 55543 Min/Max log parameter 55544 Min/Max log parameter 55545 Min/Max log parameter 55546 Min/Max log parameter 55547 Min/Max log parameter 55548 Min/Max log parameter 55549 Min/Max log parameter 55550 Min/Max log parameter 55551 Min/Max log parameter 55552 Min/Max log parameter 55553 Min/Max log parameter 55554 Min/Max log parameter 55555 Min/Max log parameter 55556 Min/Max log parameter 55557 Min/Max log parameter 55558-55573 Reserved TOU Daily Profile Setup 55574-55701 +0 1st tariff change +1 2nd tariff change +2 3rd tariff change +3 4th tariff change +4 5th tariff change +5 6th tariff change +6 7th tariff change +7 8th tariff change 55574-55581 TOU daily profile #1 55582-55589 TOU daily profile #2 55590-55597 TOU daily profile #3 55598-55605 TOU daily profile #4 55606-55613 TOU daily profile #5 55614-55621 TOU daily profile #6 55622-55629 TOU daily profile #7 Options/Range #1 ID #2 ID #3 ID #4 ID #5 ID #6 ID #7 ID #8 ID #9 ID #10 ID #11 ID #12 ID #13 ID #14 ID #15 ID #16 ID Units Type R/W UINT16 R/W 0x0000-0xFFFF 0x0000-0xFFFF 0x0000-0xFFFF 0x0000-0xFFFF 0x0000-0xFFFF 0x0000-0xFFFF 0x0000-0xFFFF 0x0000-0xFFFF 0x0000-0xFFFF 0x0000-0xFFFF 0x0000-0xFFFF 0x0000-0xFFFF 0x0000-0xFFFF 0x0000-0xFFFF 0x0000-0xFFFF 0x0000-0xFFFF UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W F10 F10 F10 F10 F10 F10 F10 F10 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 R/W R/W R/W R/W R/W R/W R/W R/W Notes 99 Address Point ID Description 55630-55637 TOU daily profile #8 55638-55645 TOU daily profile #9 55646-55653 TOU daily profile #10 55654-55661 TOU daily profile #11 55662-55669 TOU daily profile #12 55670-55677 TOU daily profile #13 55678-55685 TOU daily profile #14 55686-55693 TOU daily profile #15 55694-55701 TOU daily profile #16 TOU Calendar Years Setup 55702-55711 55702 Calendar #1 year 55703 Calendar #2 year 55704 Calendar #3 year 55705 Calendar #4 year 55706 Calendar #5 year 55707 Calendar #6 year 55708 Calendar #7 year 55709 Calendar #8 year 55710 Calendar #9 year 55711 Calendar #10 year TOU Calendar Setup 55712-56671 +0-7 January +0 1-4 January day profiles +1 5-7 January day profiles +2 8-12 January day profiles +3 13-16 January day profiles +4 17-20 January day profiles +5 21-24 January day profiles +6 25-28 January day profiles +7 29-31 January day profiles +8-15 February +0 1-4 February day profiles +1 5-7 February day profiles +2 8-12 February day profiles +3 13-16 February day profiles +4 17-20 February day profiles +5 21-24 February day profiles +6 25-28 February day profiles +7 29 February day profile +16-23 March +0 1-4 March day profiles 100 Options/Range 0-99 0-99 0-99 0-99 0-99 0-99 0-99 0-99 0-99 0-99 Units Type R/W UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W UINT16 R/W Notes Address +1 +2 +3 +4 +5 +6 +7 +24-31 +0 +1 +2 +3 +4 +5 +6 +7 +32-39 +0 +1 +2 +3 +4 +5 +6 +7 +40-23 +0 +1 +2 +3 +4 +5 +6 +7 +48-55 +0 +1 +2 +3 +4 +5 +6 +7 Point ID Description 5-7 March day profiles 8-12 March day profiles 13-16 March day profiles 17-20 March day profiles 21-24 March day profiles 25-28 March day profiles 29-31 March day profile April 1-4 April day profiles 5-7 April day profiles 8-12 April day profiles 13-16 April day profiles 17-20 April day profiles 21-24 April day profiles 25-28 April day profiles 29-30 April day profile May 1-4 May day profiles 5-7 May day profiles 8-12 May day profiles 13-16 May day profiles 17-20 May day profiles 21-24 May day profiles 25-28 May day profiles 29-31 May day profile June 1-4 June day profiles 5-7 June day profiles 8-12 June day profiles 13-16 June day profiles 17-20 June day profiles 21-24 June day profiles 25-28 June day profiles 29-30 June day profile July 1-4 July day profiles 5-7 July day profiles 8-12 July day profiles 13-16 July day profiles 17-20 July day profiles 21-24 July day profiles 25-28 July day profiles 29-31 July day profile Options/Range Units Type UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W Notes 101 Address Point ID +56-63 +0 +1 +2 +3 +4 +5 +6 +7 +64-71 +0 +1 +2 +3 +4 +5 +6 +7 +72-79 +0 +1 +2 +3 +4 +5 +6 +7 +80-87 +0 +1 +2 +3 +4 +5 +6 +7 +88-95 +0 +1 +2 +3 +4 +5 102 Description August 1-4 August day profiles 5-7 August day profiles 8-12 August day profiles 13-16 August day profiles 17-20 August day profiles 21-24 August day profiles 25-28 August day profiles 29-31 August day profile September 1-4 September day profiles 5-7 September day profiles 8-12 September day profiles 13-16 September day profiles 17-20 September day profiles 21-24 September day profiles 25-28 September day profiles 29-30 September day profile October 1-4 October day profiles 5-7 October day profiles 8-12 October day profiles 13-16 October day profiles 17-20 October day profiles 21-24 October day profiles 25-28 October day profiles 29-31 October day profile November 1-4 November day profiles 5-7 November day profiles 8-12 November day profiles 13-16 November day profiles 17-20 November day profiles 21-24 November day profiles 25-28 November day profiles 29-30 November day profile December 1-4 December day profiles 5-7 December day profiles 8-12 December day profiles 13-16 December day profiles 17-20 December day profiles 21-24 December day profiles Options/Range Units Type UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W Notes Address Point ID Description +6 25-28 December day profiles +7 29-31 December day profile 55712-55807 TOU Calendar #1 Setup 55808-55903 TOU Calendar #2 Setup 55904-55999 TOU Calendar #3 Setup 56000-56095 TOU Calendar #4 Setup 56096-56191 TOU Calendar #5 Setup 56192-56287 TOU Calendar #6 Setup 56288-56383 TOU Calendar #7 Setup 56384-56479 TOU Calendar #8 Setup 56480-56575 TOU Calendar #9 Setup 56576-56671 TOU Calendar #10 Setup Summary Energy/TOU Registers Setup 56672-56927 +0,1 Roll over value +2 TOU register enabled +3 Setpoint gate 56672-56675 Register #1 Setup 56676-56679 Register #2 Setup 56680-56683 Register #3 Setup ... 56796-56799 Register #32 Setup 56800-56927 Reserved Summary Energy/TOU Registers Source Setup 56928-57183 +0 Energy source ID +1 Target summary energy register number +2,3 Multiplier 56928-56931 Energy Source #1 56932-56935 Energy Source #2 56936-56939 Energy Source #3 ... 57180-57183 Energy Source #64 Control Setpoints Setup 57184-61023 +0 Condition #1: Trigger parameter ID +1 Condition #2: Trigger parameter ID +2 Condition #3: Trigger parameter ID +3 Condition #4: Trigger parameter ID +4 Condition #1: Logical operator +5 Condition #2: Logical operator +6 Condition #3: Logical operator +7 Condition #4: Logical operator Options/Range Type UINT16 UINT16 R/W R/W R/W 1-1,000,000,000 0 = disabled, 1 = enabled 0 = disabled, 1-32 = setpoint No UINT32 UINT16 UINT16 R/W R/W R/W F11 0-31 +/-1-10000 UINT16 UINT16 INT32 R/W R/W R/W F12 F12 F12 F12 0= 0= 0= 0= UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 R/W R/W R/W R/W R/W R/W R/W R/W OR, OR, OR, OR, 1 1 1 1 = = = = AND AND AND AND Units Notes 103 Address Point ID +8 +9 +10 +11 +12,13 +14,15 +16,17 +18,19 +20,21 +22,23 +24,25 +26,27 +28 +29 +30 +31 +32,33 +34,35 +36,37 +38,39 +40,41 +42,43 +44-59 57184-57243 57244-57303 59044-59103 59104-61023 Periodic Timers Setup 61024-61087 +0,1 61024-61025 61026-61027 61040-61041 61042-61043 61044-61045 61046-61047 61048-61049 61050-61051 61052-61053 61054-61055 61056-61087 104 Description Condition #1: Relational operator Condition #2: Relational operator Condition #3: Relational operator Condition #4: Relational operator Condition #1: Operate limit Condition #2: Operate limit Condition #3: Operate limit Condition #4: Operate limit Condition #1: Release limit Condition #2: Release limit Condition #3: Release limit Condition #4: Release limit Action #1: Action ID Action #2: Action ID Action #3: Action ID Action #4: Action ID Action #1: Parameter value Action #2: Parameter value Action #3: Parameter value Action #4: Parameter value Operate delay Release delay Not used Setpoint #1 Setpoint #2 ... Setpoint #32 Reserved Options/Range F13 F13 F13 F13 Units Type UINT16 UINT16 UINT16 UINT16 INT32 INT32 INT32 INT32 INT32 INT32 INT32 INT32 UINT16 UINT16 UINT16 UINT16 INT32 INT32 INT32 INT32 UINT32 UINT32 UINT16 R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W R/W 0-10000000 0-10000000 0.001 s 0.001 s Time interval (positive in seconds, negative in cycles) Timer #1 Setup Timer #2 Setup ... Timer #9 Setup Timer #10 Setup (factory preset) Timer #11 Setup (factory preset) Timer #12 Setup (factory preset) Timer #13 Setup (factory preset) Timer #14 Setup (factory preset) Timer #15 Setup (factory preset) Timer #16 Setup (factory preset) Reserved -100000000 -100000000 0.001 s/c 0.001 s/c 0.001 s/c UINT32 UINT32 UINT32 R/W R/W R/W 0.001s/c 0.001cyc 0.001cyc 0.001 s 0.001 s 0.001 s 0.001 s 0.001 s UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 R/W R R R R R R R F14 F14 F14 F14 -500 (half-cycle) -1000 (one cycle) 200 (200 ms = 10/12 cycles) 3000 (3 sec = 150/180 cycles) 10000 (10 sec) 600000 (10 min) 7200000 (2 hours) Notes Address Point ID Description Energy Pulse Source Setup 61088-61215 +0 Energy pulse source ID +1 Not used +2,3 Units per pulse 61088-61091 Pulse Source #1 61092-61095 Pulse Source #2 ... 61212-61215 Pulse Source #32 Counters Setup 61216-61471 +0,1 Roll over value +2,3 Reset value 61216-61219 Counter #1 Setup 61220-61223 Counter #2 Setup ... 61340-61343 Counter #32 Setup 61344-61471 Reserved Counter Source Setup 61472-61727 +0 Pulse source ID +1 Target counter number +2,3 Multiplier 61472-61475 Counter Source #1 61476-61479 Counter Source #2 ... 61724-61727 Counter Source #64 Digital Inputs Setup DI1-DI64 61728-61983 +0 Pulse mode +1 Polarity +2 De-bounce time, ms +3 Flags Options/Range Units Type R/W F15 0 1-10000 UINT16 UINT16 UINT32 R/W R/W R/W 1-1,000,000,000 0 - +/-999,999,999 UINT32 INT32 R/W R/W F16 0-31 +/-1-10000 UINT16 UINT16 INT32 R/W R/W R/W 0 = pulse, 1 = KYZ 0 = normal, 1 = inverting 1-1000 Bit 0 – SOE Log: 0 = disabled, 1 = enabled; Bit 1 – Fault Log: 0 = disabled, 1 = enabled; UINT16 UINT16 UINT16 UINT16 R/W R/W R/W R/W Notes Note 3 61728-61731 61732-61735 DI1 Setup DI2 Setup ... 61980-61983 DI64 Setup Digital Inputs Setup DI65-DI96 62752-62879 105 Address Point ID 62752-62575 62756-62759 62876-62879 62880-63007 Relay Outputs Setup 61984-62367 +0 +1 +2 +3 +4 +5 61984-61989 61990-61995 62362-62367 Analog Inputs Setup 62368-62559 +0 +1 +2,3 +4,5 62368-62373 62374-62379 62458-62463 62464-62559 Analog Outputs Setup 62560-62751 +0 +1 +2,3 +4,5 62560-62565 62566-62571 62650-62655 62656-62751 106 Description DI64 Setup DI65 Setup ... DI96 Setup Reserved Options/Range Operation Mode Type R/W 0 = unlatched, 1 = latched, 2 = pulse, 3 = KYZ Bit 0 – polarity: 0 = normal, 1 = inverting Bit 2 – blocking: 0 = unblocked relay, 1= blocked relay 1-1000 F17 0 = disabled, 1 = enabled 0 = disabled, 1 = enabled UINT16 R/W UINT16 R/W UINT16 UINT16 UINT16 UINT16 R/W R/W R/W R/W Input parameter ID Not used Zero scale value (0/4 mA, 0V) Full scale value (1/20/50 mA, 10V) AI1 Setup AI2 Setup … AI16 Setup Reserved 0 = input not assigned 0 UINT16 UINT16 INT32 INT32 R/W R/W R/W R/W Output parameter ID Not used Zero scale value (0/4 mA) Full scale value (20/1 mA) AO1 Setup AO2 Setup … AO16 Setup Reserved F18 0 UINT16 UINT16 INT32 INT32 R/W R/W R/W R/W Flags Pulse width, ms Pulse source ID Retentive mode SOE log on output change enabled RO1 Setup RO2 Setup … RO64 Setup Units Notes A blocked relay can only be unblocked by the “unblock relay” setpoint command 107 3.8 Expansion I/O Slots Configuration Address Point ID Description Expansion I/O Slots Configuration Info Expansion I/O Slots Configuration Info 63008-63055 Options/Range +0 I/O module type +1 Number of I/Os on the slot +2 First I/O number on the slot +3 Last I/O number on the slot 63008-63011 I/O Slot #1 Configuration 63012-63015 I/O Slot #2 Configuration 63016-63019 I/O Slot #3 Configuration 63020-63023 I/O Slot #4 Configuration 63024-63027 I/O Slot #5 Configuration 63028-63055 Reserved Expansion I/O Modules Type Info Expansion I/O Modules Type Info 63056-63119 +0 +1 +2 +3 63056-63059 63060-63063 63064-63067 63068-63071 63072-63075 63076-63119 Number of I/O modules of this type Total number of I/O's of this type Not used Not used DI Module Type Info RO Module Type Info AI Module Type Info AO Module Type Info XM Module Type Info Reserved Type R/W Notes Bitmap 0-32 0-79 0-95 UINT16 UINT16 UINT16 UINT16 R R R R Note 2 0-5 0-96 UINT16 UINT16 UINT16 UINT16 R R R R 0 Units Note 1 Note 1 NOTES: 1. I/O numbers of expansion I/O modules are automatically assigned in the order of connection. The connection order is counted for each I/O module type separately. If the I/O module position is changed but its order in the chain of the modules of the same type is preserved, then all I/Os on the module will retain their I/O numbers. 108 2. The type of a module in the corresponding slot position, number of I/Os on the module and their I/O numbers can be read through the I/O Slots Configuration Info registers. I/O module type register contains bit-mapped information on the module type and its options in bits D7:D0 as shown in the Table below. I/O Module Type Module DI (16DI) DI (16DI) DI (16DI) DI (16DI) DI (32DI) DI (32DI) DI (32DI) DI (32DI) DI (32DI) RO (8RO) RO (16RO) RO (8RO) AI (4AI/4AO) AI (4AI/4AO) AI (4AI/4AO) AI (4AI/4AO) AI (8AI) AI (8AI) AO (4AI/4AO) AO (4AI/4AO) AO (4AI/4AO) AO (4AI/4AO) XM XM Empty slot Option DRY WET 24V WET 48V WET 125V DRY WET 24V WET 48V WET 125V WET 250V ±1 mA 0-20 mA 4-20 mA 0-1 mA 0-50 mA ±10 V ±1 mA 0-20 mA 4-20 mA 0-1 mA 64MB 128MB D7 0 0 0 0 0 0 0 0 0 0 1 1 0 0 0 0 0 0 0 0 0 0 1 1 1 D6 0 0 0 0 0 0 0 0 0 0 0 0 1 1 1 1 1 1 1 1 1 1 0 0 1 D5 0 0 0 0 0 0 0 0 0 1 1 1 0 0 0 0 0 0 0 0 0 0 0 0 1 D4 0 0 0 0 1 1 1 1 1 0 0 1 0 0 0 0 1 1 0 0 0 0 0 0 1 D3 0 0 0 0 0 0 0 0 0 0 0 0 × × × × 0 0 0 0 1 1 0 0 1 D2 0 0 0 0 0 0 0 0 1 0 0 0 × × × × 1 1 0 1 0 1 0 0 1 D1 0 0 1 1 0 0 1 1 0 0 0 0 0 0 1 1 0 0 × × × × 0 0 1 D0 0 1 0 1 0 1 0 1 0 0 0 0 0 1 0 1 0 1 × × × × 0 1 1 × = don’t care 3. The same de-bounce time is used for each group of eight adjacent digital inputs. To assign de-bounce time for a group, write the desired value into the setup register for the first DI in the group, e.g., DI1, DI9, DI17 and so on. The device will assign this value to the following seven inputs automatically. Any attempt to change de-bounce time for an input that is not the first in the group will be ignored. No error will occur. 109 3.9 File Transfer Blocks Address Point ID Description File Transfer Control Blocks 63120-63151 File Request Block +0 File function +1 +2 +3 +4 +5 +6 +7 +8, 9 +10, 11 +12, 13 +14, 15 +16-31 63152-64943 64944-64951 +0 +1 +2 +3 +4 +5 +6-7 64952-65151 110 Options/Range Type R/W Notes 1 = ACK - acknowledgement 3 = set file position 5 = reset file position 7 = find 11 = read file 127 = erase file UINT16 R/W 1 - clears the file transfer block 3 - changes the file position 5 - sets the file position at the first (oldest) record 7 - finds a record matching an event or/and time (see Note 3) 11 - opens the file for reading from the present file position File ID Section number (functions 3, 5, 11) Section channel ID (functions 3, 5, 11) Record sequence number (functions 3, 11) F2 0-31, 0xFFFF = use channel ID F6, F7 0-65535 UINT16 UINT16 UINT16 UINT16 R/W R/W R/W R/W Request variation (function 11) Find key: Event type Find key: Event number Find key: Start time, seconds since 1/1/1970 Find key: Start time, fractional seconds in µsec Find key: End time, seconds since 1/1/1970 Find key: End time, fractional seconds in µsec Reserved File Response Block Data transfer area [0 – 1791] File Info Request Block File function File ID Section number Section channel ID Not used Request variation Reserved File Info Response Block Data transfer area [0 - 199] 0, 4 F22 1 - 65535 F1 UINT16 UINT16 UINT16 UINT32 UINT32 UINT32 UINT32 UINT16 R/W R/W R/W R/W R/W R/W R/W R/W UINT16 R UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 R/W R/W R/W R/W R/W R/W R/W UINT16 R F1 9 = read file info F2 0-31, 0xFFFF = use channel ID F6, F7 0 0, 1, 2 Units sec µsec sec µsec The record sequence number with function 11 does not change the file position (see Note 2). See file response headings Note 3 Note 3 Note 3 Note 3 Note 3 Note 3 NOTES: 1. File sections for partitioned (multi-section) files, such as TOU profile log files and waveform log files, can be requested either by a section number, or by a section channel ID. If a section number is set to 0xFFFF, the section channel ID will be used to identify the section. The section number will be returned in the response block. If a section number is written, then the corresponding channel ID will be returned in the file response block. 2. The record sequence number with function 11 (Read-File) does not change the file position and is used only as a reference to track the order of records. The file transfer block will continue to hold the same data until it is acknowledged, or until the file position is explicitly moved to another record. For multi-section Waveform files that use a single read pointer for all file sections, the Read-File request, which addresses a different file section, will refill the transfer block with data of the record from the requested file section with the identical sequence number. After acknowledgment, the file position will be moved to the next record. 3. Function 7 (Find) puts into the file request block the sequence number of the first record in the file that matches the event or/and the time. If the file ID is set to 0xFFFF, the device will search for the desired record in the waveform file that is preset by default for the fault and power quality recorders or a setpoint, depending on the event type. The file ID where a record is found is returned in the file response block header. Any one of the find keys can be omitted by setting it to 0. If one or a number of find keys are omitted, the device will use the remaining keys to locate the matching record. If the record could not be found, the device responds to the write request with the exception code 3 (illegal data). The status of the operation can be read through the file status word in the file info block. File Response Blocks Address Point ID Description File Info Response Block (Variation 0 – File info) 64952-64959 Block Heading +0 File function +1 File ID +2 Section number +3 Section channel ID +4 Number of records in the block +5 Record size, words +6 Request variation +7 Reserved 64960-64997 File Info +0 File type +1 File attributes +2 File (section) status +3 Number of sections in the file +4, 5 File channel mask (channels 1-32), bitmap +6, 7 File channel mask (channels 33-64), bitmap +8 Number of records in the file +9 Number of records until the end of the file +10 Current record (read position) sequence number +11 Current write position sequence number +12 First (oldest) record sequence number +13 Last (newest) record sequence number +14, 15 Last record time, seconds since 1/1/1970 +16, 17 Last record time, fractional seconds +18, 19 First record time, seconds since 1/1/1970 Options/Range Type R/W 9 F2 0-31 F6, F7 1 36 0 0 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 R R R R R R R R 0 F3 F4 0-32 F8, F9 F8, F9 0-65535 0-65535 0-65535 0-65535 0-65535 0-65535 F1 UINT16 UINT16 UNT16 UINT16 UINT32 UINT32 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT32 UINT32 UINT32 R R R R R R R R R R R R R R R F1 Units sec µsec sec Notes 0 = non-partitioned file 111 Address Point ID Description +20, 21 First record time, fractional seconds +22, 23 Creation time, seconds since 1/1/1970 +24, 25 Creation time, fractional seconds +26, 27 Reset time, seconds since 1/1/1970 +28, 29 Reset time, fractional seconds +30 Maximum number of records +31 Number of parameters per data section record +32 Section record size, bytes +33 File record size, bytes +34, 35 Allocated file size, bytes File Info Response Block (Variation 1 – Current record info) 64952-64959 Block Heading +0 File function +1 File ID +2 Section number +3 Section channel ID +4 Number of records in the block +5 Record size, words +6 Request variation +7 Reserved 64960-64997 File Info +0 File (section) status +1 Number of records in the file +2 Number of records until the end of the file +3 Current record (read position) sequence number +4, 5 Current record time, seconds since 1/1/1970 +6, 7 Current record time, fractional seconds File Info Response Block (Variation 2 – Data log record structure) 64952-64959 Block Heading +0 File function +1 File ID +2 Section number +3 Section channel ID +4 Number of records in the block +5 Record size, words +6 Request variation +7 Reserved 64960-64997 File Info +0 Not used +1 Number of fields in a data record +2 +3 112 Field 1 parameter ID Field 2 parameter ID Options/Range Type UINT32 UINT32 UINT32 UINT32 UINT32 UINT16 UINT16 UINT16 UINT16 UINT32 R/W R R R R R R R R R R 9 F2 0-31 F6, F7 1 8 1 0 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 R R R R R R R R F4 0-65535 0-65535 0-65535 F1 UNT16 UINT16 UINT16 UINT16 UINT32 UINT32 R R R R R R 9 1-16 0-15 F6, F7 1 2 + Number of parameters 2 0 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 R R R R R R R R 0 1-16 (34 for EN50160 Statistics log, 52 for EN50160 Harmonics Survey) 0-0xFFFF 0-0xFFFF UINT16 UINT16 R R UINT16 UINT16 R R F1 F1 Units µsec sec µsec sec µsec 0-65535 0-52 Byte Byte Byte sec µsec Notes Address Point ID Description … … Event Log Response Block 63152-63159 Block Heading +0 Last file function +1 File ID +2 Section number +3 Section channel ID +4 Number of records in the block +5 Record size, words +6 Request variation +7 Reserved 63160-63543 Event Log Records +0 Record status +1 Record sequence number +2, 3 Trigger time, seconds since 1/1/1970 +4, 5 Trigger time, fractional seconds in µsec +6 Event number +7 Event point/source ID +8 Event effect +9 Reserved +10, 11 Value triggered 63160-63171 Record #1 ... 63532-63543 Record #32 Data Log Response Block 63152-63159 Block Heading +0 Last file function +1 File ID +2 Section number +3 Section channel ID +4 Number of records in the block +5 Record size, words +6 Request variation +7 63160-64439 +0 +1 +2, 3 +4, 5 +6 +7 +8, 9 Reserved Data Log Records Record status Record sequence number Record time, seconds since 1/1/1970 Record time, fractional seconds in µsec Trigger event type Trigger event number Log value #1 Options/Range Units Type R/W 1, 3, 5, 11 0 0 0 1-32 12 0 0 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 R R R R R R R R F5 0-65535 F1 INT16 UINT16 UINT32 UINT32 UINT16 UINT16 UINT16 UINT16 INT32 R R R R R R R R R 1, 3, 5, 11 1-16 (F2) 0-31 F6 1-32 8 + 2×Number of parameters 0 = regular log, 4 = EN50160 online statistics (with file ID = 9, 10) 0 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 R R R R R R R UINT16 R F5 0-65535 F1 INT16 UINT16 UINT32 UINT32 INT16 UINT16 INT32 R R R R R R R sec µsec 1-65535 F19 F20 0 F22 1-65535 sec µsec Notes 113 Address Point ID +10, 11 … 63160-… Description Log value #2 … Record #1 (variable length) ... Record #32 (variable length) Waveform Log Response Block 63152-63159 Block Heading +0 Last file function +1 File ID +2 Section number +3 Section channel ID +4 Number of records in the block +5 Record size, words +6 Request variation +7 Reserved 63160-63799 Waveform Log Record +0 Record status +1 Record sequence number +2, 3 Start time, seconds since 1/1/1970 +4, 5 Start time, fractional seconds +6, 7 Trigger time, seconds since 1/1/1970 +8, 9 Trigger time, fractional seconds +10 Record series number +11 Record serial number in a series +12 Trigger event type +13 Trigger event number +14 Source point ID (generic) +15 Trigger reference sample index +16 Sampling rate, µsec/sample +17 Sampling rate, samples/cycle +18 Sampling frequency +19 Channel offset, sampling units +20, 21 Channel multiplier, primary units +22 Channel divisor, sampling units +23 Length of a sample series, data points +24-127 Not used +128 Sample Series +128-639 Sample data series points [0...511] Sequence of Events (SOE) Log Response Block 63152-63159 Block Heading +0 Last file function +1 File ID +2 Section number 114 Options/Range Type INT32 R/W R R 1, 3, 5, 11 17-24, 128 (F2) 0-9 (0-25 for V10.6.XX) F7 1 640 0 0 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 R R R R R R R R F5 0 - 65535 F1 INT16 UINT16 UINT32 UINT32 UINT32 UINT32 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 INT16 UINT32 UINT16 UINT16 UINT16 R R R R R R R R R R R R R R R R R R R R +/-8191 INT16 R 1, 3, 5, 11 25 0 UINT16 UINT16 UINT16 R R R F1 1-65535 0-65535 F22 1-65535 See Generic Data in Section 3.4 0-511 600-27000 16, 32, 64, 128 4500-6500 +/-32767 See Generic Data in Section 3.4 2147-8191 64-512 0 Units sec µsec sec µsec ×0.1µsec ×0.01Hz Notes For VDC channel, ×1µsec 1 Address Description Section channel ID Number of records in the block Record size, words Request variation Reserved SOE Log Records Record status Record sequence number Trigger time, seconds since 1/1/1970 Trigger time, fractional seconds in µsec Fault event type Fault event number Fault source point status GPS clock sync status Record #1 ... 63470-63479 Record #32 Power Quality (PQ) Log Response Block 63152-63159 Block Heading +0 Last file function +1 File ID +2 Section number +3 Section channel ID +4 Number of records in the block +5 Record size, words +6 Request variation +7 Reserved 63160-63799 PQ Log Records +0 Record status +1 Record sequence number +2, 3 Start time, seconds since 1/1/1970 +4, 5 Start time, fractional seconds in µsec +6, 7 End time, seconds since 1/1/1970 +8, 9 End time, fractional seconds in µsec +10 PQ event type +11 PQ event number +12 Point ID (generic) +13 Reserved +14, 15 Value reference (base), primary units +16, 17 Value magnitude, primary units +3 +4 +5 +6 +7 63160-63479 +0 +1 +2, 3 +4, 5 +6 +7 +8 +9 63160-63169 Point ID Options/Range 0 1-32 10 0 0 Type UINT16 UINT16 UINT16 UINT16 UINT16 R/W R R R R R F22 1-65535 0 = Open/Off, 1 = Closed/On 0 = time unlocked, 1 = time locked INT16 UINT16 UINT32 UINT32 UINT16 UINT16 UINT16 UINT16 R R R R R R R R 1, 3, 5, 11 26 0 0 1 -32 18 0 0 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 R R R R R R R R F5 0-65535 F1 INT16 UINT16 UINT32 UINT32 UINT32 UINT32 UINT16 UINT16 UINT16 UINT16 INT32 INT32 R R R R R R R R R R R R F5 0-65535 F1 F1 F22 1-65535 See Generic Data in Section 3.4 0 See Generic Data in Section 3.4 See Generic Data in Section 3.4 Units sec µsec sec µsec sec µsec Notes 115 Address Point ID 63160-63179 Description Record #1 ... 63780-63799 Record #32 Fault Log Response Block 63152-63159 Block Heading +0 Last file function +1 File ID +2 Section number +3 Section channel ID +4 Number of records in the block +5 Record size, words +6 Request variation +7 Reserved 63160-64183 Fault Log Records +0 Record status +1 Record sequence number +2, 3 Start time, seconds since 1/1/1970 +4, 5 Start time, fractional seconds in µsec +6, 7 End time, seconds since 1/1/1970 +8, 9 End time, fractional seconds in µsec +10 Fault event type +11 Fault event number +12 Current phase point ID (generic) +13 Volts phase point ID (generic) +14, 15 Current reference (base), primary units +16, 17 Current magnitude, primary units +18, 19 Volts reference (base), primary units +20, 21 Volts magnitude, primary units 63160-63191 Record #1 ... 64152-64183 Record #32 1 Units Type R/W 1, 3, 5, 11 27 0 0 1-32 22 0 0 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 R R R R R R R R F5 0-65535 F1 INT16 UINT16 UINT32 UINT32 UINT32 UINT32 UINT16 UINT16 UINT16 UINT16 INT32 INT32 INT32 INT32 R R R R R R R R R R R R R R sec µsec sec µsec F1 F22 1-65535 0-65535 0-65535 See Generic See Generic See Generic See Generic Data Data Data Data in in in in Section Section Section Section 3.4 3.4 3.4 3.4 U2 U2 U1 U1 To restore the original sampled data in the channel units (e.g., Volts, Amps), the following conversion should be applied: Sampled Data [primary units ] = 116 Options/Range (Data Sample − Channel Offset) × Channel Multiplier Channel Divisor Notes File Response Block Alias Address Point ID Description File Response Block Alias 3072-3079 Block Heading +0 File function +1 File ID +2 Section number +3 Section channel ID +4 Number of records in the block +5 Record size, words +6 Request variation +7 Reserved 3080-3583 Last 1-10 file records Power Quality (PQ) Log Response Block Alias 3072-3079 Block Heading +0 File function +1 File ID +2 Section number +3 Section channel ID +4 Number of records in the block +5 Record size, words +6 Request variation +7 Reserved 3080-3259 PQ Log Records +0 Record status +1 Record sequence number +2, 3 Start time, seconds since 1/1/1970 +4, 5 Start time, fractional seconds in µsec +6, 7 End time, seconds since 1/1/1970 +8, 9 End time, fractional seconds in µsec +10 PQ event type +11 PQ event number +12 Point ID (generic) +13 Reserved +14, 15 Value reference (base), primary units +16, 17 Value magnitude, primary units 3080-3097 Record #1 ... 3242-3259 Record #10 Options/Range Type R/W 11 0, 25, 26, 27 0 0 1 - 10 18 0 0 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 R R/W R R R/W R R R 11 26 0 0 1 - 10 18 0 0 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 UINT16 R R/W R R R/W R R R F5 0 - 65535 F1 INT16 UINT16 UINT32 UINT32 UINT32 UINT32 UINT16 UINT16 UINT16 UINT16 INT32 INT32 R R R R R R R R R R R R F1 F22 1 - 65535 See Generic Data in Section 3.4 0 See Generic Data in Section 3.4 See Generic Data in Section 3.4 Units sec µsec sec µsec Notes Write: sets the block size Write: sets the block size The block of registers 3072-3583 is the alias for the common file response block. It is intended for continuous polling of the last 1 to 10 records of the event files (Event Log, SOE Log, PQ Log or Fault Log) from SCADA systems. The alias block is preset at factory to provide access to the last ten PQ Log records. You can change factory assignments to point to another log file or change the number of the records in the transfer block by re-writing of the corresponding registers in the block heading. To update records in the alias block, at least one of the block heading registers 3072-3079 must be read first. 117 NOTES: 1. Registers 3080-3259 share the same data transfer buffer as the common file transfer block registers 63152-64943. Reading data from the common transfer block within the same connection session can destroy data in the alias transfer block. To guarantee that the alias block contains correct data, always read block heading registers 3072-3079 before accessing data records in the alias block. 2. If you read the block through a TCP connection and change a file ID or the number of records in the block, your assignments for the transfer block will be effective only within the current connection socket. Since the device cannot guarantee that your next connection will be made through the same socket, you should not make any assumptions regarding the present block settings. When you open a new connection, always check the block heading before accessing data records. 118 3.10 EN 50160 Compliance Statistics Data Log File Record Section Field No. 0 1 2 3 4 5 6 7 8 1 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 2 1 2 3 4 5 6 7 3 1 2 3 Point Label Point ID Nnv N N1 N2 N1/N, % N2/N, % Freq Min Freq Max 0x5A00 0x5A01 0x5A02 0x5A03 0x5A04 0x5A05 0x5A06 0x5A07 Nnv N N1 N2 N1/N, % N2/N, % V1 N1 V1 Min V1 Max V2 N1 V2 Min V2 Max V3 N1 V3 Min V3 Max 0x5A80 0x5A81 0x5A82 0x5A83 0x5A84 0x5A85 0x5A86 0x5A87 0x5A88 0x5A89 0x5A8A 0x5A8B 0x5A8C 0x5A8D 0x5A8E N1 V1 N1 V1 dV% V2 N1 V2 dV% V3 N1 V3 dV% 0x5B00 0x5B01 0x5B02 0x5B03 0x5B04 0x5B05 0x5B06 Nnv N N1 0x5B80 0x5B81 0x5B82 1 Description Power Frequency Number of non-valid 10-sec intervals Number of valid 10-sec intervals Number of incidents ±1%, N1 Number of incidents +4%/-6%, N2 EN50160 compliance ratio, N1/N EN50160 compliance ratio, N2/N Minimum frequency Maximum frequency Supply Voltage Variations Number of non-valid 10-min intervals Number of valid 10-min intervals Number of polyphase incidents ±10%, N1 Number of polyphase incidents +10/-15%, N2 EN50160 compliance ratio, N1/N EN50160 compliance ratio, N2/N Number of incidents ±10% on phase V1 Minimum voltage on phase V1 Maximum voltage on phase V1 Number of incidents ±10% on phase V2 Minimum voltage on phase V2 Maximum voltage on phase V2 Number of incidents ±10% on phase V3 Minimum voltage on phase V3 Maximum voltage on phase V3 Rapid Voltage Changes Number of polyphase incidents Number of incidents on phase V1 Maximum voltage variation on phase V1, dV/Un% Number of incidents on phase V2 Maximum voltage variation on phase V2, dV/Un% Number of incidents on phase V3 Maximum voltage variation on phase V3, dV/Un% Flicker Number of non-valid 2-hour intervals Number of valid 2-hour intervals Number of polyphase incidents Plt >1%, N1 2 Range 2 Units 0.01% 0.01% 0.01Hz 0.01Hz 0.01% 0.01% U1 U1 U1 U1 U1 U1 0.01% 0.01% 0.01% Type Notes UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 119 File Record Section Field No. 4 5 6 7 8 9 10 4 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 120 Point Label N1/N, % V1 N1 V1 Plt Max V2 N1 V2 Plt Max V3 N1 V3 Plt Max Point ID 0x5B83 0x5B84 0x5B85 0x5B86 0x5B87 0x5B88 0x5B89 N11 90%/100ms N12 85%/100ms N13 70%/100ms N14 40%/100ms N11 90%/500ms N12 85%/500ms N13 70%/500ms N14 40%/500ms N11 90%/1s N12 85%/1s N13 70%/1s N14 40%/1s N11 90%/3s N12 85%/3s N13 70%/3s N14 40%/3s N11 90%/20s N12 85%/20s N13 70%/20s N14 40%/20s N11 90%/60s N12 85%/60s N13 70%/60s N14 40%/60s N11 90%/180s N12 85%/180s N13 70%/180s N14 40%/180s V1 N1 V1 Min V2 N1 V2 Min V3 N1 V3 Min 0x5C00 0x5C01 0x5C02 0x5C03 0x5C04 0x5C05 0x5C06 0x5C07 0x5C08 0x5C09 0x5C0A 0x5C0B 0x5C0C 0x5C0D 0x5C0E 0x5C0F 0x5C10 0x5C11 0x5C12 0x5C13 0x5C14 0x5C15 0x5C16 0x5C17 0x5C18 0x5C19 0x5C1A 0x5C1B 0x5C1C 0x5C1D 0x5C1E 0x5C1F 0x5C20 0x5C21 1 Description EN50160 compliance ratio, N1/N Number of incidents Plt > 1% on phase V1 Maximum Plt on phase V2 Number of incidents Plt > 1% on phase V2 Maximum Plt on phase V2 Number of incidents Plt > 1% on phase V3 Maximum Plt on phase V3 Voltage Dips (indicative statistics) Number of polyphase incidents u<90%/t<100ms Number of polyphase incidents u<85%/t<100ms Number of polyphase incidents u<70%/t<100ms Number of polyphase incidents u<40%/t<100ms Number of polyphase incidents u<90%/t<500ms Number of polyphase incidents u<85%/t<500ms Number of polyphase incidents u<70%/t<500ms Number of polyphase incidents u<40%/t<500ms Number of polyphase incidents u<90%/t<1s Number of polyphase incidents u<85%/t<1s Number of polyphase incidents u<70%/t<1s Number of polyphase incidents u<40%/t<1s Number of polyphase incidents u<90%/t<3s Number of polyphase incidents u<85%/t<3s Number of polyphase incidents u<70%/t<3s Number of polyphase incidents u<40%/t<3s Number of polyphase incidents u<90%/t<20s Number of polyphase incidents u<85%/t<20s Number of polyphase incidents u<70%/t<20s Number of polyphase incidents u<40%/t<20s Number of polyphase incidents u<90%/t<60s Number of polyphase incidents u<85%/t<60s Number of polyphase incidents u<70%/t<60s Number of polyphase incidents u<40%/t<60s Number of polyphase incidents u<90%/t<180s Number of polyphase incidents u<85%/t<180s Number of polyphase incidents u<70%/t<180s Number of polyphase incidents u<40%/t<180s Total number of incidents on phase V1 Minimum residual voltage on phase V1 Total number of incidents on phase V2 Minimum residual voltage on phase V2 Total number of incidents on phase V3 Minimum residual voltage on phase V3 2 Range 2 Units 0.01% 0.01 0.01 0.01 U1 U1 U1 Type UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 Notes File Record Section Field No. 5 1 2 3 4 5 6 6 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 7 1 2 3 4 5 6 7 8 9 10 11 12 Point Label Point ID N1 1s N2 180s N3 >180s V1 Min V2 Min V3 Min 0x5D00 0x5D01 0x5D02 0x5D03 0x5D04 0x5D05 N11 110%/1s N12 120%/1s N13 140%/1s N14 160%/1s N15 200%/1s N21 110%/60s N22 120%/60s N23 140%/60s N24 160%/60s N25 200%/60s N31 110%/>60s N32 120%/>60s N33 140%/>60s N34 160%/>60s N35 200%/>60s V1 N1 V1 Max V2 N1 V2 Max V3 N1 V3 Max 0x5D80 0x5D81 0x5D82 0x5D83 0x5D84 0x5D85 0x5D86 0x5D87 0x5D88 0x5D89 0x5D8A 0x5D8B 0x5D8C 0x5D8D 0x5D8E 0x5D8F 0x5D90 0x5D91 0x5D92 0x5D93 0x5D94 N1 110% N2 150% N3 200% N4 250% N5 300% V1 N1 110% V1 N2 150% V1 N3 200% V1 N4 250% V1 N5 300% V2 N1 110% V2 N2 150% 0x5E00 0x5E01 0x5E02 0x5E03 0x5E04 0x5E05 0x5E06 0x5E07 0x5E08 0x5E09 0x5E0A 0x5E0B 1 Description Voltage Interruptions (indicative statistics) Number of polyphase incidents <1s Number of polyphase incidents <180s Number of polyphase incidents >180s Minimum residual voltage on phase V1 Minimum residual voltage on phase V2 Minimum residual voltage on phase V3 Temporary Overvoltages (indicative statistics) Number of polyphase incidents u>110%/t<1s Number of polyphase incidents u>120%/t<1s Number of polyphase incidents u>140%/t<1s Number of polyphase incidents u>160%/t<1s Number of polyphase incidents u>200%/t<1s Number of polyphase incidents u>110%/t<60s Number of polyphase incidents u>120%/t<60s Number of polyphase incidents u>140%/t<60s Number of polyphase incidents u>160%/t<60s Number of polyphase incidents u>200%/t<60s Number of polyphase incidents u>110%/t>60s Number of polyphase incidents u>120%/t>60s Number of polyphase incidents u>140%/t>60s Number of polyphase incidents u>160%/t>60s Number of polyphase incidents u>200%/t>60s Total number of incidents on phase V1 Maximum voltage magnitude on phase V1 Total number of incidents on phase V2 Maximum voltage magnitude on phase V2 Total number of incidents on phase V3 Maximum voltage magnitude on phase V3 Transient Overvoltages (peak voltage, indicative statistics) Number of polyphase incidents u>120% Number of polyphase incidents u>150% Number of polyphase incidents u>200% Number of polyphase incidents u>250% Number of polyphase incidents u>300% Number of incidents u>120% on phase V1 Number of incidents u>150% on phase V1 Number of incidents u>200% on phase V1 Number of incidents u>250% on phase V1 Number of incidents u>300% on phase V1 Number of incidents u>120% on phase V2 Number of incidents u>150% on phase V2 2 Range 2 Units U1 U1 U1 U1 U1 U1 Type Notes UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 121 File Record Section Field No. 13 14 15 16 17 18 19 20 21 22 23 7 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 8 1 2 3 4 5 122 Point Label N3 200% N4 250% N5 300% N1 110% N2 150% N3 200% N4 250% N5 300% Peak Max Peak Max Peak Max Point ID 0x5E0C 0x5E0D 0x5E0E 0x5E0F 0x5E10 0x5E11 0x5E12 0x5E13 0x5E14 0x5E15 0x5E16 N1 110% N2 150% N3 200% N4 250% N5 300% V1 N1 110% V1 N2 150% V1 N3 200% V1 N4 250% V1 N5 300% V2 N1 110% V2 N2 150% V2 N3 200% V2 N4 250% V2 N5 300% V3 N1 110% V3 N2 150% V3 N3 200% V3 N4 250% V3 N5 300% V1 imp max V2 imp max V3 imp max 0x5E00 0x5E01 0x5E02 0x5E03 0x5E04 0x5E05 0x5E06 0x5E07 0x5E08 0x5E09 0x5E0A 0x5E0B 0x5E0C 0x5E0D 0x5E0E 0x5E0F 0x5E10 0x5E11 0x5E12 0x5E13 0x5E14 0x5E15 0x5E16 Nnv N N1 N1/N, % V Unb% Max 0x5E80 0x5E81 0x5E82 0x5E83 0x5E84 V2 V2 V2 V3 V3 V3 V3 V3 V1 V2 V3 1 Description Number of incidents u>200% on phase V2 Number of incidents u>250% on phase V2 Number of incidents u>300% on phase V2 Number of incidents u>120% on phase V3 Number of incidents u>150% on phase V3 Number of incidents u>200% on phase V3 Number of incidents u>250% on phase V3 Number of incidents u>300% on phase V3 Maximum peak voltage on phase V1 Maximum peak voltage on phase V2 Maximum peak voltage on phase V3 Transient Overvoltages (impulsive voltage, indicative statistics) Number of polyphase incidents u>120% Number of polyphase incidents u>150% Number of polyphase incidents u>200% Number of polyphase incidents u>250% Number of polyphase incidents u>300% Number of incidents u>120% on phase V1 Number of incidents u>150% on phase V1 Number of incidents u>200% on phase V1 Number of incidents u>250% on phase V1 Number of incidents u>300% on phase V1 Number of incidents u>120% on phase V2 Number of incidents u>150% on phase V2 Number of incidents u>200% on phase V2 Number of incidents u>250% on phase V2 Number of incidents u>300% on phase V2 Number of incidents u>120% on phase V3 Number of incidents u>150% on phase V3 Number of incidents u>200% on phase V3 Number of incidents u>250% on phase V3 Number of incidents u>300% on phase V3 Maximum impulsive voltage on phase V1 Maximum impulsive voltage on phase V2 Maximum impulsive voltage on phase V3 Supply Voltage Unbalance Number of non-valid 10-min intervals Number of valid 10-min intervals Number of incidents V Unb > 2%, N1 EN50160 compliance ratio, N1/N Maximum voltage unbalance 2 Range 2 Units Type U1 U1 U1 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 U1 U1 U1 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 0.01% 0.1% UINT32 UINT32 UINT32 UINT32 UINT32 Notes File Record Section Field No. 9 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 10 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 Point Label Nnv N N1 N2 N1/N, % N2/N, % V1 N1 V1 HD% Max V1 H# V1 N2 V1 THD Max V2 N1 V2 HD% Max V2 H# V2 N2 V2 THD Max V3 N1 V3 HD% Max V3 H# V3 N2 V3 THD Max Nnv N N1 N2 N1/N, % N2/N, % V1 N1 V1 HD% Max V1 H# V1 N2 V1 THD Max V2 N1 V2 HD% Max V2 H# V2 N2 V2 THD Max V3 N1 V3 HD% Max V3 H# Point ID 1 Description Harmonic Voltage Number of non-valid 10-min intervals Number of valid 10-min intervals Number of polyphase harmonic voltage incidents, N1 Number of polyphase voltage THD incidents, N2 EN50160 harmonic voltage compliance ratio, N1/N EN50160 voltage THD compliance ratio, N2/N Number of harmonic voltage incidents on phase V1 Worst-case harmonic magnitude on phase V1, %Un Worst-case harmonic component number on phase V1 Number of voltage THD incidents on phase V1 Worst-case voltage THD on phase V1 Number of harmonic voltage incidents on phase V2 Worst-case harmonic magnitude on phase V2, %Un Worst-case harmonic component number on phase V2 Number of voltage THD incidents on phase V2 Worst-case voltage THD on phase V2 Number of harmonic voltage incidents on phase V3 Worst-case harmonic magnitude on phase V3, %Un Worst-case harmonic component number on phase V3 Number of voltage THD incidents on phase V3 Worst-case voltage THD on phase V3 Interharmonic Voltage 0x5F80 Number of non-valid 10-min intervals 0x5F81 Number of valid 10-min intervals 0x5F82 Number of polyphase interharmonic voltage incidents, N1 0x5F83 Number of polyphase interharmonic THD incidents, N2 0x5F84 EN50160 interharmonic voltage compliance ratio, N1/N 0x5F85 EN50160 interharmonic voltage THD compliance ratio, N2/N 0x5F86 Number of interharmonic voltage incidents on phase V1 0x5F87 Worst-case interharmonic magnitude on phase V1, %Un 0x5F88 Worst-case interharmonic component number on phase V1 0x5F89 Number of interharmonic voltage THD incidents on phase V1 0x5F8A Worst-case interharmonic voltage THD on phase V1 0x5F8B Number of interharmonic voltage incidents on phase V2 0x5F8C Worst-case interharmonic magnitude on phase V2, %Un 0x5F8D Worst-case interharmonic component number on phase V2 0x5F8E Number of interharmonic voltage THD incidents on phase V2 0x5F8F Worst-case interharmonic voltage THD on phase V2 0x5F90 Number of interharmonic voltage incidents on phase V3 0x5F91 Worst-case interharmonic magnitude on phase V3, %Un 0x5F92 Worst-case interharmonic component number on phase V3 0x5F00 0x5F01 0x5F02 0x5F03 0x5F04 0x5F05 0x5F06 0x5F07 0x5F08 0x5F09 0x5F0A 0x5F0B 0x5F0C 0x5F0D 0x5F0E 0x5F0F 0x5F10 0x5F11 0x5F12 0x5F13 0x5F14 2 Range 2 Units 0.01% 0.01% 0.01% 2-50 0.1% 0.01% 2-50 0.1% 0.01% 2-50 0.1% 0.01% 0.01% 0.01% 2-50 0.1% 0.01% 2-50 0.1% 0.01% 2-50 Type Notes UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 123 File Record Section Field No. 20 21 11 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 124 Point Label V3 N2 V3 THD Max Point ID 0x5F93 0x5F94 Nnv N N1 N1/N, % V1 N1 V1 Frq1 %Un V1 Frq2 %Un V1 Frq3 %Un V1 Frq4 %Un V2 N1 V2 Frq1 %Un V2 Frq2 %Un V2 Frq3 %Un V2 Frq4 %Un V3 N1 V3 Frq1 %Un V3 Frq2 %Un V3 Frq3 %Un V3 Frq4 %Un Frq1 Frq2 Frq3 Frq4 0x6000 0x6001 0x6002 0x6003 0x6004 0x6005 0x6006 0x6007 0x6008 0x6009 0x600A 0x600B 0x600C 0x600D 0x600E 0x600F 0x6010 0x6011 0x6012 0x6013 0x6014 0x6015 0x6016 1 Description Number of interharmonic voltage THD incidents on phase V3 Worst-case interharmonic THD on phase V3 Mains Signaling Voltage Number of non-valid 3-sec intervals Number of valid 3-sec intervals Number of polyphase incidents, N1 EN50160 compliance ratio, N1/N Number of incidents on phase V1 Maximum 1st signaling voltage magnitude on phase V1, %Un Maximum 2nd signaling voltage magnitude on phase V1, %Un Maximum 3rd signaling voltage magnitude on phase V1, %Un Maximum 4th signaling voltage magnitude on phase V1, %Un Number of incidents on phase V2 Maximum 1st signaling voltage magnitude on phase V2, %Un Maximum 2nd signaling voltage magnitude on phase V2, %Un Maximum 3rd signaling voltage magnitude on phase V2, %Un Maximum 4th signaling voltage magnitude on phase V2, %Un Number of incidents on phase V3 Maximum 1st signaling voltage magnitude on phase V3, %Un Maximum 2nd signaling voltage magnitude on phase V3, %Un Maximum 3rd signaling voltage magnitude on phase V3, %Un Maximum 4th signaling voltage magnitude on phase V3, %Un 1st signaling voltage frequency 2nd signaling voltage frequency 3rd signaling voltage frequency 4th signaling voltage frequency 2 Range 2 Units 0.1% 0.01% 0.01% 0.01% 0.01% 0.01% 0.01% 0.01% 0.01% 0.01% 0.01% 0.01% 0.01% 0.01% 0.01Hz 0.01Hz 0.01Hz 0.01Hz 1 When the 4LN3 or 3LN3 wiring mode is selected, the voltages will be line-to-neutral; for any other wiring mode, they will be line-to-line voltages. 2 For volts, amps, power and frequency scales and units, refer to Section 4 ”Data Scales and Units”. Type UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 Notes 3.11 EN 50160 Harmonics Survey Statistics Data Log File Record Section Field No. 0 1 2 3 4 5 Point Label Point ID THD MAX THDO MAX THDE MAX %HD02 MAX %HD03 MAX … 51 %HD50 MAX 0x8000 0x8001 0x8002 0x8003 0x8004 0x8032 THD MAX THDO MAX THDE MAX %HD02 MAX %HD03 MAX … 51 %HD50 MAX THD MAX THDO MAX THDE MAX %HD02 MAX %HD03 MAX … 51 %HD50 MAX 1 Units 0.1% 0.1% 0.1% 0.01% 0.01% 0.01% 0.01% 0x8000 0x8001 0x8002 0x8003 0x8004 Maximum HD50 harmonic voltage magnitude, %Un V3 Harmonic Voltage Maximum THD on phase Maximum odd harmonics THD Maximum even harmonics THD Maximum HD02 harmonic voltage magnitude, %Un Maximum HD03 harmonic voltage magnitude, %Un 0x8032 Maximum HD50 harmonic voltage magnitude, %Un 0.01% 0x8000 0x8001 0x8002 0x8003 0x8004 0x8032 2 1 2 3 4 5 V1 Harmonic Voltage Maximum THD on phase Maximum odd harmonics THD Maximum even harmonics THD Maximum HD02 harmonic voltage magnitude, %Un Maximum HD03 harmonic voltage magnitude, %Un Range Maximum HD50 harmonic voltage magnitude, %Un V2 Harmonic Voltage Maximum THD on phase Maximum odd harmonics THD Maximum even harmonics THD Maximum HD02 harmonic voltage magnitude, %Un Maximum HD03 harmonic voltage magnitude, %Un 1 1 2 3 4 5 1 Description 0.1% 0.1% 0.1% 0.01% 0.01% 0.1% 0.1% 0.1% 0.01% 0.01% Type Notes UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 When the 4LN3 or 3LN3 wiring mode is selected, the voltages will be line-to-neutral; for any other wiring mode, they will be line-to-line voltages. 125 3.12 Billing/TOU Daily and Monthly Profile Data Logs Record File Channel/ Field No. 2 1 Section 0/0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 … 15/15 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 16/16 1 2 126 Point Label Point ID TRF1 TRF2 TRF3 TRF4 TRF5 TRF6 TRF7 TRF8 TRF9 TRF10 TRF11 TRF12 TRF13 TRF14 TRF15 TRF16 0x7000 0x7001 0x7002 0x7003 0x7004 0x7005 0x7006 0x7007 0x7008 0x7009 0x700A 0x700B 0x700C 0x700D 0x700E 0x700F TRF1 TRF2 TRF3 TRF4 TRF5 TRF6 TRF7 TRF8 TRF9 TRF10 TRF11 TRF12 TRF13 TRF14 TRF15 TRF16 0x7000 0x7001 0x7002 0x7003 0x7004 0x7005 0x7006 0x7007 0x7008 0x7009 0x700A 0x700B 0x700C 0x700D 0x700E 0x700F TRF1 MD TRF2 MD 0x7100 0x7101 Description Energy Register #1 Tariff #1 energy reading Tariff #2 energy reading Tariff #3 energy reading Tariff #4 energy reading Tariff #5 energy reading Tariff #6 energy reading Tariff #7 energy reading Tariff #8 energy reading Tariff #9 energy reading Tariff #10 energy reading Tariff #11 energy reading Tariff #12 energy reading Tariff #13 energy reading Tariff #14 energy reading Tariff #15 energy reading Tariff #16 energy reading … Energy Register #16 Tariff #1 energy reading Tariff #2 energy reading Tariff #3 energy reading Tariff #4 energy reading Tariff #5 energy reading Tariff #6 energy reading Tariff #7 energy reading Tariff #8 energy reading Tariff #9 energy reading Tariff #10 energy reading Tariff #11 energy reading Tariff #12 energy reading Tariff #13 energy reading Tariff #14 energy reading Tariff #15 energy reading Tariff #16 energy reading Maximum Demand Register #1 Tariff #1 max. demand reading Tariff #2 max. demand reading Range Units 3 Type -999,999,999-999,999,999 -999,999,999-999,999,999 -999,999,999-999,999,999 -999,999,999-999,999,999 -999,999,999-999,999,999 -999,999,999-999,999,999 -999,999,999-999,999,999 -999,999,999-999,999,999 -999,999,999-999,999,999 -999,999,999-999,999,999 -999,999,999-999,999,999 -999,999,999-999,999,999 -999,999,999-999,999,999 -999,999,999-999,999,999 -999,999,999-999,999,999 -999,999,999-999,999,999 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 kWh kWh kWh kWh kWh kWh kWh kWh kWh kWh kWh kWh kWh kWh kWh kWh UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 -999,999,999-999,999,999 -999,999,999-999,999,999 -999,999,999-999,999,999 -999,999,999-999,999,999 -999,999,999-999,999,999 -999,999,999-999,999,999 -999,999,999-999,999,999 -999,999,999-999,999,999 -999,999,999-999,999,999 -999,999,999-999,999,999 -999,999,999-999,999,999 -999,999,999-999,999,999 -999,999,999-999,999,999 -999,999,999-999,999,999 -999,999,999-999,999,999 -999,999,999-999,999,999 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 kWh kWh kWh kWh kWh kWh kWh kWh kWh kWh kWh kWh kWh kWh kWh kWh UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 0-Pmax 0-Pmax U3 U3 UINT32 UINT32 Notes File Channel/ 1 Section Record 2 Field No. Point Label Point ID 3 4 5 6 7 8 9 10 11 12 13 14 15 16 TRF3 MD TRF4 MD TRF5 MD TRF6 MD TRF7 MD TRF8 MD TRF9 MD TRF10 MD TRF11 MD TRF12 MD TRF13 MD TRF14 MD TRF15 MD TRF16 MD 0x7102 0x7103 0x7104 0x7105 0x7106 0x7107 0x7108 0x7109 0x710A 0x710B 0x710C 0x710D 0x710E 0x710F 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 TRF1 MD TRF2 MD TRF3 MD TRF4 MD TRF5 MD TRF6 MD TRF7 MD TRF8 MD TRF9 MD TRF10 MD TRF11 MD TRF12 MD TRF13 MD TRF14 MD TRF15 MD TRF16 MD 0x7100 0x7101 0x7102 0x7103 0x7104 0x7105 0x7106 0x7107 0x7108 0x7109 0x710A 0x710B 0x710C 0x710D 0x710E 0x710F … 32/32 Description Tariff #3 max. demand reading Tariff #4 max. demand reading Tariff #5 max. demand reading Tariff #6 max. demand reading Tariff #7 max. demand reading Tariff #8 max. demand reading Tariff #9 max. demand reading Tariff #10 max. demand reading Tariff #11 max. demand reading Tariff #12 max. demand reading Tariff #13 max. demand reading Tariff #14 max. demand reading Tariff #15 max. demand reading Tariff #16 max. demand reading … Maximum Demand Register #16 Tariff #1 max. demand reading Tariff #2 max. demand reading Tariff #3 max. demand reading Tariff #4 max. demand reading Tariff #5 max. demand reading Tariff #6 max. demand reading Tariff #7 max. demand reading Tariff #8 max. demand reading Tariff #9 max. demand reading Tariff #10 max. demand reading Tariff #11 max. demand reading Tariff #12 max. demand reading Tariff #13 max. demand reading Tariff #14 max. demand reading Tariff #15 max. demand reading Tariff #16 max. demand reading Range Units 3 Type 0-Pmax 0-Pmax 0-Pmax 0-Pmax 0-Pmax 0-Pmax 0-Pmax 0-Pmax 0-Pmax 0-Pmax 0-Pmax 0-Pmax 0-Pmax 0-Pmax U3 U3 U3 U3 U3 U3 U3 U3 U3 U3 U3 U3 U3 U3 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 0-Pmax 0-Pmax 0-Pmax 0-Pmax 0-Pmax 0-Pmax 0-Pmax 0-Pmax 0-Pmax 0-Pmax 0-Pmax 0-Pmax 0-Pmax 0-Pmax 0-Pmax 0-Pmax U3 U3 U3 U3 U3 U3 U3 U3 U3 U3 U3 U3 U3 U3 U3 U3 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 UINT32 Notes 1 An energy use profile section and a maximum demand profile section are allocated for registers for which a source input is selected in the Summary/TOU Register setup and for which TOU profile is enabled. Not configured sections/channels are not available for download. Refer to the file channel mask in the file info for configured channels. 2 The number of parameters in a section is automatically configured depending on the number of actually used tariffs selected in the TOU Daily Profiles. 3 For power scale and units, refer to Section 4 ”Data Scales and Units”. 127 4 Data Scales and Units Code Data Scales Vmax V4max Imax I4max Ixmax I4xmax Pmax AImin AImax Condition 1A secondary 5A secondary 1A secondary 5A secondary PT Ratio = 1 PT Ratio > 1 +/-1mA 0-20mA 4-20mA 0-1mA 0-50mA +/-10V Data Units U1 U2 U3 U4 1 PT Ratio = 1 PT Ratio > 1 PT PT V4 V4 Ratio = 1 Ratio > 1 PT Ratio = 1 PT Ratio > 1 Value/Range Voltage Scale × PT Ratio, V Voltage Scale × V4 PT Ratio, V Current Scale × CT Ratio 1, A, Current Scale × I4 CT Ratio 1, A, 30 × CTx Ratio 1, A 150 × CTx Ratio 1, A 30 × I4x CTx Ratio 1, A 150 × I4x CTx Ratio 1, A Vmax × Imax × 2, W (Vmax × Imax × 2)/1000, kW AImin = -AI full scale × 2 AImax = AI full scale × 2 AImin = AI zero scale AImax = AI full scale AImin = AI zero scale AImax = AI full scale AImin = AI zero scale AImax = AI full scale AImin = AI zero scale AImax = AI full scale AImin = -AI full scale AImax = AI full scale Notes 2 2 3 3 4 0.1V 1V 0.01A 1W/Var/VA 1kW/kvar/kVA 0.1V 1V CT Ratio = CT primary current/CT secondary current 2 The default Voltage Scale is 828V. You can change it via the Modbus Setup registers (see Section 3.1) or via the Device Options setup in PAS. 3 The default Current Scale is 4 × CT secondary current for devices with a 400% overload (ANSI) or 2 × CT secondary current for devices with a 200% overload (IEC). You can change it via the Modbus Setup registers (see Section 3.1) or via the Device Options setup in PAS. 4 Pmax is rounded to whole kilowatts. If Pmax is greater than 9,999,000 W, it is truncated to 9,999,000 W. 128 5 Data Formats Format Code Timestamp F1 File ID F2 Value Description Notes Local time in a UNIX-style format. Represents the number of seconds since midnight (00:00:00), January 1, 1970. The time is valid after January 1, 2000. 0 1-16 17-24 25 26 27 128 File Attributes F3 Bit 0 = 0 Bit 0 = 1 Bit 1 = 1 Bits 4:6 = 0 1 2 3 4 File Status Word (bitmap) F4 Bit 0 = 1 Bit 8 = 1 Bit 9 = 1 Bit 10 = 1 Bit 11 = 1 Bit 12 = 1 Bit 13 = 1 Bit 14 = 1 Bit 15 = 1 File Record Status Word (bitmap) F5 Bit 0 = 1 Bit 8 = 1 Bit 9 = 1 Bit 10 = 1 Bit 11 = 1 Bit 12 = 1 Bit 13 = 1 Bit 14 = 1 Bit 15 = 1 TOU Profile Log Channel ID F6 0-15 16-31 Waveform Log Channel ID F7 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 Event log Data log #1-#16 Waveform log #1-#8 Sequence-of-events (SOE) log Power quality (PQ) log Fault log Real time waveform capture Non-wrap file (stop when full) Wrap-around (circular) file Fixed (non-changeable) file attributes Multi-section data log file attributes: Regular file TOU monthly profile log TOU daily profile log EN50160 Compliance Statistics EN50160 Survey Statistics - Voltage Harmonics Multi-section Multi-section Multi-section Multi-section file file file file The last record of the file is being read File is empty Reading after EOF Corrupted record (CRC error) No file section found for the requested channel Reading after the end of a data block File is not accessible Record not found Generic read error (with one of the bits 8-14) The last record of the file is being read File is empty Reading after EOF Corrupted record (CRC error) No file section found for the requested channel Reading after the end of a data block File is not accessible Record not found Generic read error (with one of the bits 8-14) TOU energy registers #1-#16 TOU maximum demand registers #1-#16 V1 V2 V3 V4 I1 I2 I3 I4 I1x I2x I3x I4x VDC DI1-16 DI17-32 DI33-48 AI1 AI2 1 1 1 V10.3.20 and higher V10.3.20 and higher V10.6.XX 129 Format Code Value 18 19 20 21 22 23 24 25 26 27 28 29 30 31 TOU Profile Log Channel Mask (bitmap) F8 Bit 0:15 = 1 Bit 16:31 = 1 Waveform Log Channel Mask (bitmap) F9 Bit 0 Bit 1 Bit 2 Bit 3 Bit 4 Bit 5 Bit 6 Bit 7 Bit 8 Bit 9 Bit 10 Bit 11 Bit 12 Bit 13 Bit 14 Bit 15 Bit 16 Bit 17 Bit 18 Bit 19 Bit 20 Bit 21 Bit 22 Bit 23 Bit 24 Bit 25 Bit 26 Bit 27 Bit 28 Bit 29 Bit 30 Bit 31 TOU Tariff Change Time F10 Bits 8:15 = 0-15 Bits 2:7 = 0-23 Bits 0:1 = 0-3 Summary Energy Register Source ID F11 0x0000 0x0700-0x072F 0x1700 0x1701 0x1702 0x1703 0x1704 0x1705 0x1706 0x1707 0x1708 0x1780-0x178F 130 Description Notes AI3 AI4 AI5 AI6 AI7 AI8 AI9 AI10 AI11 AI12 AI13 AI14 AI15 AI16 TOU energy registers #1-#16 TOU maximum demand registers #1-#16 Channel V1 Channel V2 Channel V3 Channel V4 Channel I1 Channel I2 Channel I3 Channel I4 Channel I1x Channel I2x Channel I3x Channel I4x Channel VDC Channels DI1-16 Channels DI17-32 Channels DI33-48 Channel AI1 Channel AI2 Channel AI3 Channel AI4 Channel AI5 Channel AI6 Channel AI7 Channel AI8 Channel AI9 Channel AI10 Channel AI11 Channel AI12 Channel AI13 Channel AI14 Channel AI15 Channel AI16 Tariff number #1-#16 Tariff start hour Tariff start quarter of an hour None Pulse input DI1-DI48 kWh import kWh export kWh net kWh total kvarh import kvarh export kvarh net kvarh total kVAh total Summary energy register #1-#16 1 1 1 V10.3.20 and higher V10.3.20 and higher V10.6.XX Format Code Value Setpoint Trigger Parameters ID F12 0x0000-0xFFFF 0x1200-0x120F Setpoint Relational Operator F13 0 = NONE 1 = GREATER OR EQUAL 2 = LESS OR EQUAL 3 = EQUAL 4 = NOT EQUAL 5 = ON 6 = OFF 7 = NEW 8 = Delta Description Any data point ID excluding energy counters External trigger #1-#16 (UDP broadcast trigger message) Notes See Section 3.4 No relation (used with pulsed events) Analog value or counter is over the operate limit Analog value or counter is under the operate limit Analog value or counter is equal to the operate limit Analog value or counter is not equal to the operate limit Binary status is 1/ON Binary status is 0/OFF New Min/Max value logged for the point The absolute value of the difference between the last reported value and the current value exceeds the specified threshold Setpoint Action ID F14 0x0000 No action 0x2000-0x200F Set user event flag #1-#16 0x2100-0x210F Clear user event flag #1-#16 0x3000-0x303F Operate relay RO1-RO64 0x3100-0x313F Release latched relay RO1-RO64 0x3700-0x373F Unblock relay RO1-RO64 0x4000-0x401F Increment counter #1-#32 0x4100-0x411F Decrement counter #1-#32 0x4200-0x421F Clear counter #1-#32 0x6000 Reset total energy registers 0x6100 Reset total maximum demand registers 0x6200 Reset summary and TOU energy 0x6300 Reset summary and TOU maximum demands 0x6400 Clear all counters 0x6500 Clear Min/Max log registers 0x7000 Event log on setpoint operated 0x7001 Event log on setpoint released 0x7002 Event log on any setpoint transition 0x7100-0x710F Data log 1-16 0x7200-0x7207 Waveform Log 1-8 0x7400 SOE (Sequence of Events) Log 0x8000-0x800F External trigger #1-#16 (UDP broadcast trigger message) Energy Pulse Source ID F15 0x0000 None 0x0400 kWh Import pulse 0x0401 kWh Export pulse 0x0402 kWh Total pulse 0x0403 kvarh Import pulse 0x0404 kvarh Export pulse 0x0405 kvarh Total pulse 0x0406 kVAh pulse Counter Source ID F16 0x0000 None 0x0700-0x072F Pulse input DI1-DI48 Relay Output Pulse Source ID F17 0x0000 None 0x0400 kWh Import pulse 0x0401 kWh Export pulse 0x0402 kWh Total pulse 0x0403 kvarh Import pulse 0x0404 kvarh Export pulse 0x0405 kvarh Total pulse 0x0406 kVAh pulse 0x0407 Start of power demand interval pulse 0x0408 Start of tariff interval pulse AO Parameters ID (see Section 3.4 for data scales) F18 0x0000 None (output disabled) 1-Cycle Phase Values 0x0C00 V1 Voltage 0x0C01 V2 Voltage 0x0C02 V3 Voltage 2 131 Format Code Value 0x0C03 0x0C04 0x0C05 0x0C12 0x0C13 0x0C14 0x0C15 0x0C16 0x0C17 0x0C18 0x0C19 0x0C1A 0x0C1B 0x0C1C 0x0C1D 0x0C1E 0x0C1F 0x0C20 0x0F00 0x0F01 0x0F02 0x0F03 0x0F04 0x0F05 0x1000 0x1001 0x1002 0x1005 0x1100 0x1101 0x1102 0x1103 0x1104 0x1105 0x111E 0x111F 0x1120 0x1400 0x1401 0x1402 0x1403 0x1404 0x1405 0x140A 0x140B 0x140C 0x1500 0x1501 0x1502 0x160F 0x1610 0x1611 0x161A 0x161B Event Source/Point ID F19 0x0000-0x59FF 0x6400-0xFFFF 0x5A00-0x5A1F 132 Description I1 Current I2 Current I3 Current V1 Voltage THD V2 Voltage THD V3 Voltage THD I1 Current THD I2 Current THD I3 Current THD I1 K-Factor I2 K-Factor I3 K-Factor I1 Current TDD I2 Current TDD I3 Current TDD V12 Voltage V23 Voltage V31 Voltage 1-Cycle Total Value Total kW Total kvar Total kVA Total PF Total PF Lag Total PF Lead 1-Cycle Auxiliary Values I4 Current In Current Frequency DC voltage 1-Sec Phase Values V1 Voltage V2 Voltage V3 Voltage I1 Current I2 Current I3 Current V12 Voltage V23 Voltage V31 Voltage 1-Sec Total Values Total kW Total kvar Total kVA Total PF Total PF Lag Total PF Lead 3-phase average L-N voltage 3-phase average L-L voltage 3-phase average current 1-Sec Auxiliary Values I4 Current In Current Frequency Present Demands Accumulated kW import demand Accumulated kvar import demand Accumulated kVA demand Accumulated kW export demand Accumulated kvar export demand Setpoint Operation Events Trigger parameter ID Trigger parameter ID Setpoint Action Events Setpoint #1-#32 Communications Events Notes Format Code Value 0x5B00-0x5BFF 0x5D00-0x5DFF 0x5E08 0x6014 0x6015 0x6016 0x6201 0x6202 0x6203 0x6204 0x6205 0x6206 0x6207 0x620E 0x620F 0x6210 0x6211 0x6300 0x6308 0x6309 0x6318 0x6319 0x631A 0x6320 0x6321 Event Effect ID F20 0x0000 0x6000 0x6100 0x6101 0x6102 0x6103 0x6104 0x6105 0x6200 0x6300 0x6400 0x6401-0x641F 0x6500 0x6A00-0x6A1B 0x6B00 0xF100-0xF11F 0xF200 0xF300 0xF400 0xF500 0xF600 0xF700 0xF800 0xF900 0xE100-0xE11F 0xE200-0xE21F See F14 Data/Function Point ID F21 0x03 0x04 0x05 0x06 Description Data/Function point ID (low byte, see F21) Self-Check Diagnostics Events Data/Function point ID (low byte, see F21) Self-Update Events RTC DST/Standard time update Run-time Error Library error RTOS Kernel error Task error Hardware Diagnostics Events Permanent fault RAM/Data error CPU watchdog reset DSP/Sampling fault CPU exception Reserved Software watchdog reset Expanded memory fault (Event effect = File ID + 1) CPU EEPROM fault AC board EEPROM fault I/O board EEPROM fault External Events Power down Power up External reset IRIG-B signal lost IRIG-B time unlocked IRIG-B time locked SNTP server failed SNTP server reconnected Communications/Self-check/Self-update Events None Total energy registers cleared All total maximum demands cleared Power maximum demands cleared Volt/Ampere maximum demands cleared Volt maximum demands cleared Ampere maximum demands cleared Harmonic maximum demands cleared TOU energy registers cleared TOU demand registers cleared All counters cleared Counter cleared (low byte = counter ID) Min/Max log cleared Log file cleared (low byte = File ID) EN50160 statistics cleared Setpoint cleared (low byte = setpoint ID) Setup/Data cleared Setup reset (set by default) Setup changed RTC set Device function/option enabled Device function/option disabled Device function restarted Device function stopped Setpoint Operation Events Setpoint operated (low byte = setpoint ID) Setpoint released (low byte = setpoint ID) Setpoint Action Events Setpoint action ID Notes 3 4 4 3 Data Location Data memory Factory setup Access/Password setup Basic setup 133 Format Code Value 0x07 0x08 0x09 0x0A 0x0B 0x0E 0x10 0x11 0x12 0x13 0x14 0x15 0x16 0x18 0x19 0x1A 0x1D 0x1C 0x1F 0x20 0x21 0x22 0x23 0x24 0x25 0x26 0x27 0x28 0x29 0x2A 0x2B-0x3F 0x40 0x41 0x42 0x43 0x44 0x80 0x81 Event Type ID F22 0x0000 0x0001-0x0020 0x0100 0x0102 0x010C 0x010D 0x010F 0x0110 0x0111 0x0113 0x0114 0x0115 0x0117 0x0118 0x0119 0x011A 0x011D 0x011E 0x0121 0x0122 0x0200 0x0201 0x0202 134 Description Communications setup Real-time clock Digital inputs setup Pulse counters setup AO setup Timers setup Event/alarm setpoints Pulsing setup User assignable register map Programmable Min/Max log setup Data log setup File/Memory setup TOU energy registers setup TOU daily profiles TOU calendar TOU calendar years RO Setup User selectable options DNP 3.0 class 0 map DNP 3.0 options setup DNP 3.0 events setup DNP 3.0 event setpoints Calibration registers Date/Time Setup Net setup AI setup Waveform log setup PQ log setup Fault log setup Device mode control Reserved Device Mode/Option General device operations Energy test mode Setpoints mode PQ recorder Fault recorder Device Diagnostics Device diagnostics Critical error Setpoint Events SP: Generic setpoint event SP1-SP32: Setpoint #1-#32 event IEEE 1159 PQ Events (IEEE 1159 categories) PQE: Generic IEEE1159 PQ event PQE11: Impulsive transient PQE211: Sag, instantaneous PQE212: Swell, instantaneous PQE221: Interruption, momentary PQE222: Sag, momentary PQE223: Swell, momentary PQE231: Interruption, temporary PQE232: Sag, temporary PQE233: Swell, temporary PQE31: Interruption, sustained PQE32: Undervoltage PQE33: Overvoltage PQE4: Voltage imbalance PQE52: Harmonics PQE53: Interharmonics PQE6: Voltage fluctuations (flicker) PQE7: Frequency variation Fault Events FE: Generic fault event FE1: Zero-sequence current FE2: Zero-sequence voltage Notes Format Code Value 0x0203 0x0204 0x0205 0x0206 0x0207 0x0300 0x0301-0x0360 0x0400 0x0401-0x0440 0x0500 0x0501 0x0502 0x0503 0x0504 0x0505 0x0506 0x0507 0x0508 0x0509 0x050A 0x050B 0x050C Device Diagnostics (bitmap) F23 Bit 0 = 1 Bit 1 = 1 Bit 2 = 1 Bit 3 = 1 Bit 4 = 1 Bit 5 = 1 Bit 6 Bit 7 = 1 Bit 8 = 1 Bit 9 = 1 Bit 10 = 1 Bit 11 = 1 Bit 12 = 1 Bit 13 Bit 14 = 1 Bit 15 = 1 Bit 16 = 1 Bit 17 = 1 Bit 18 Bit 19 Bit 20 = 1 Bit 21 = 1 Bit 22 = 1 Bit 23 Bit 24 = 1 Bit 25 = 1 DNP Object Types F24 0 1 0 1 0 1 2 3 0 1 Description FE3: Current unbalance FE4: Voltage unbalance FE5: Overcurrent and undervoltage FE6: Undervoltage FE7: Neutral current (I4) DI Events DI: Generic DI event DI1-DI96: DI1-DI96 event RO Events RO: Generic RO event RO1-RO64: RO1-RO64 event EN 50160 PQ Events (EN 50160 categories) PQE: Generic EN50160 PQ event PQE1: Frequency variations PQE2: Voltage variations PQE3: Rapid voltage changes PQE4: Flicker PQE5: Voltage dips PQE6: Voltage interruptions PQE7: Temporary overvoltages PQE8: Transient overvoltages PQE9: Voltage unbalance PQE10: Harmonic voltage PQE11: Interharmonic voltage PQE12: Mains signaling voltage Notes Critical error - device operations stop Permanent fault (critical error) RAM/Data error CPU watchdog reset DSP/Sampling fault CPU exception Reserved Software watchdog reset Power down Device reset Configuration reset RTC fault (critical error) Configuration fault (critical error) Reserved Expanded memory fault CPU EEPROM fault AC board EEPROM fault I/O board EEPROM fault Reserved Reserved C Library error RTOS Kernel error Task error Reserved IRIG-B signal lost IRIG-B time unlocked Binary Input Static Object Single-Bit Binary Input Binary Input With Status Binary Input Change Event Object Binary Input Change Without Time Binary Input Change With Time Binary Counter 32-bit Binary Counter 32-bit Binary Counter Without Flag 16-bit Binary Counter 16-bit Binary Counter Without Flag Binary Counter Change Event 32-bit Counter Change Event Without Time 32-bit Counter Change Event With Time 135 Format Code Value 2 3 0 1 2 3 4 5 0 1 2 3 0 1 2 3 DNP Class 0 Objects F25 0x1E01 0x1E02 0x1E03 0x1E04 0x2801 0x2802 0x0101 0x0102 0x1401 0x1402 0x1405 0x1406 0x1501 0x1502 0x1505 0x1506 0x1509 0x150A Wiring Mode F26 0 1 2 3 4 5 6 8 9 Description 16-bit Counter Change Event Without Time 16-bit Counter Change Event With Time Frozen Binary Counter 32-bit Frozen Counter 32-bit Frozen Counter Without Flag 32-bit Frozen Counter With Time of Freeze 16-bit Frozen Counter 16-bit Frozen Counter Without Flag 16-bit Frozen Counter With Time of Freeze Analog Input 32-bit Analog Input 32-bit Analog Input Without Flag 16-bit Analog Input 16-bit Analog Input Without Flag Analog Input Change Event 32-bit Analog Change Event Without Time 32-bit Analog Change Event With Time 16-bit Analog Change Event Without Time 16-bit Analog Change Event With Time Notes Analog Input 30:01 Analog Input 30:02 Analog Input 30:03 Analog Input 30:04 Analog Output 40:01 Analog Output 40:02 Binary Input 01:01 Binary Input 01:02 Binary Counter 20:01 Binary Counter 20:02 Binary Counter 20:05 Binary Counter 20:06 Frozen Counter 21:01 Frozen Counter 21:02 Frozen Counter 21:05 Frozen Counter 21:06 Frozen Counter 21:09 Frozen Counter 21:10 3OP2 - 3-wire open delta using 2 CTs (2 element) 4LN3 - 4-wire WYE using 3 PTs (3 element), line-toneutral voltage readings 3DIR2 - 3-wire direct connection using 2 CTs (2 element) 4LL3 - 4-wire WYE using 3 PTs (3 element), line-to-line voltage readings 3OP3 - 3-wire open delta using 3 CTs (2 1/2 element) 3LN3 - 4-wire WYE using 2 PTs (2 1/2 element), line-toneutral voltage readings 3LL3 - 4-wire WYE using 2 PTs (2 1/2 element), line-toline voltage readings 3BLN3 - 3-wire broken delta using 2 PTs (2 1/2 element), line-to-neutral voltage readings 3BLL3 - 3-wire broken delta using 2 PTs (2 1/2 element), line-to-line voltage readings NOTES: 1 When the 4LN3 or 3LN3 wiring mode is selected, the voltages will be line-to-neutral; for any other wiring mode, they will be line-to-line voltages. 2 1) For bi-directional analog output (±1 mA), the zero scale setup corresponds to the center (0 mA) of the scale range, and the direction of the current matches the sign of the output parameter. Unsigned parameters are output within the current range 0 to +1 mA and can be scaled as in the case of single-ended analog output (0-1 mA). For signed values, such as powers and signed power factor, the scale is always symmetrical with regard to 0 mA, and the full scale corresponds to +1 mA output for positive readings and to -1 mA output for negative readings. The zero scale (0 mA output) is permanently set in the instrument to zero for all parameters except the signed power factor for which it is set to 1.000 (see Note 2). In write requests, the zero scale is ignored. 136 2) Except for the signed power factor, the setup scale is continuous within the entire value range. For signed power factor, the setup scale is broken at +1.000 in order to provide continuous output current when the power factor changes close to ±1.000. The setup scale is symmetrical in the range of -0 to +0 with a center at 1.000 (-1.000 is assumed to be equal to +1.000). Negative power factor is output as -1.000 minus measured value, and non-negative power factor is output as +1.000 minus measured value. To set the entire range for power factor from-0 to +0, the scales would be specified as -0 to 0. Because of the fact that negative zero may not be transmitted through communications, the value of -0.001 is used to specify the scale of -0, and both +0.001 and 0.000 are used to specify the scale of +0. 3 The event value field shows the present device time in the F1 format (starting with V10.4.12). 4 The event value field shows the server IP address in a network byte order. 137
* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project
Related manuals
Download PDF
advertisement