Installation TBLZ-1-55 Modular/terminal Adaptor

GOLD/COMPACT

GB.TBLZ55.130226

1. General

The adapter contains an 8-pin modular connection, internally connected to 8 screw connections.

2. Range of application

The adaptor is used for the preheating or Xzone function together with a standard Swegon electric air heater with control cable.

3. Function

The modular connection’s contact springs are connected to the relevant connection screw for an external cable.

The adaptor connects a modular connector on a cable to an electric air heater, with the relevant leads for connection to the IQnomic Plus module.

4. Installation

Secure the adaptor to an appropriate place. Use the screws or the plate with double-adhesive tape supplied with the adaptor.

If a higher tightness class is required, the adaptor must be placed in the TBLZ-1-61 junction box, see figure. Run the cables through the cable gland screw caps. Tighten the screw caps until they are fit tightly around the cables.

N.B.! The junction box must by mounted upright with the screw caps facing downward!

5. Technical Data

5.1 Adaptor

Enclosure class IP 20

Colour Beige

Material Thermoplastic.

Dimensions: 52x58x22 mm

Meets the provisions of the RoHS Directive.

5.2 TBLZ-1-61 Junction box, if required

Enclosure class IP 66

Colour Grey

Material

Dimensions:

Glass fibre reinforced polypropylene

85x85x51 mm

TBLZ-1-55

Adaptor

TBLZ-1-61 junction box

Cable gland screw caps

Registered design. The company reserves the right to make design changes without prior notice.

www.swegon.com 1

GB.TBLZ55.130226

6. Electrical Connections

The electrical connections are to be wired by a qualified electrician in accordance with local electrical safety regulations.

Adaptor for wall mounting, 8-pin, TBLZ-1-55

Electric air heater

Swegon

Standard with 8-pin control cable

BL

OR

BK

RD

WH

BR

YL

GR

Temp. sensor,** for preheated air

Jack for wall mounting, 019611

R1

RD

T1

GR

24 V AC*

(G)

(G0)

G0 0-10 V

Function selector switch in

Position 9 for the preheating function, or in Position A for the Xzone function

Communication cable to the control unit of the air handling unit, where it should be connected to one of the connections for Internal EIA-485.

13 14 15 16 17 18 19 20

– S – S

21 22 23 24

1 2

12

F0

DE

3 4567

ABC

3 4 5 6

L1

7 8

L2

9 10 11 12

* 24 V AC supply voltage is required for air heaters with a rated output of more than 20 kW/230 V

(Norway) and 34 kW/400 V.

24 V AC supply voltage can be supplied from the air handling unit control unit.

GOLD RX/PX/CX/SD: terminals 60 (G) and 61 (G0).

GOLD LP/COMPACT: terminals 9 (G) and 10 (G0).

** Digital temperature sensors require correct polarity. Be careful when you wire the conductors.

2 www.swegon.com

Registered design. The company reserves the right to make design changes without prior notice.

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals

Download PDF

advertisement