July 25 ~ Monday Morning Minutes:
Plumbing Topic: Domestic Water Recirculation Systems Part 2
Last week we left you hanging without the answer to an example problem:
Example: suppose you have a 4 story commercial building. Let’s assume the domestic hot water supply is a
total length of 1000 ft. That is the entire pipe on all of the floors. Let’s also assume an average of 15 BTU/hr/ft
of loss through the supply pipe insulation. Now let’s assume the recirc piping is 300 ft total at an average of 10
BTU/hr/ft of loss. What flow rate is required for a 10 degree ΔT? What flow rate is required for a 5 ΔT?
Answer: If I have 1000 feet of supply pipe at 15 BTU/hr./ft. loss and 300 feet of recirc pipe at 10 BTU/hr./ft.;
my total loss is (1000 X 15) + (300 X 10) = 18,000 BTUH. If I assume a 10° ΔT, my flow rate is 3.6 GPM. If I
assume a 5° ΔT, the flow is twice that or 7.2 GPM. We would round these off to the nearest unit so the answer
is 4 GPM or 8 GPM.
The total flow would really be calculated by floor and circuit so we can balance the
correct flow for each floor and circuit. Gil Carlson, past Bell and Gossett engineer and
author of many of the engineering design manuals, used to say, “A difference to be a
difference has to make a difference”. If the piping on the floors is relatively the same
then we could just divide the total by the number of floors and balance to that
number.
Each circuit should have a combination balance valve/flow meter like the Bell and
Gossett LEAD FREE circuit setters. RL Deppmann recommends a minimum flow in any
circuit of ½ GPM. Anything smaller than that is difficult to balance.
Why would we use 5° ΔT or 10° ΔT or even 20° ΔT? The lower the temperature at the fixture, the more water
and time will be wasted waiting for hot water. The American Society of Plumbing engineers (ASPE) suggests a
5° ΔT with 120° supply. If the supply temperature is 140°, we believe a 10° ΔT will do just fine. Of course
always check for local codes before deciding which temperature drop to choose.
Next Week, We look at the pressure drop
Click here to request the latest specification for LEAD FREE balancing devices.
Disclaimer: R. L. Deppmann and it’s affiliates can not be held liable for issues caused by use of the information on this page. While the information comes from many
years of experience and can be a valuable tool, it may not take into account special circumstances in your system and we therefore can not take responsibility for actions
that result from this information. Please feel free to contact us if you do have any questions.
20929 Bridge Street, Southfield, MI 48033
4121 Brockton Drive SE, Grand Rapids, MI 49512
6200 Baron Drive, Bridgeport, MI 48722
6910 Treeline Drive, Suite A, Brecksville, OH 44141
Serving the industry since 1927
Phone: (800) 589-6120 - Fax: (248) 354-3710
www.deppmann.com
Disclaimer: R. L. Deppmann and it’s affiliates can not be held liable for issues caused by use of the information on this page. While the information comes from many
years of experience and can be a valuable tool, it may not take into account special circumstances in your system and we therefore can not take responsibility for actions
that result from this information. Please feel free to contact us if you do have any questions.
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertisement