Mixed Flow Fans from Models QEI

Mixed Flow Fans from Models QEI
Mixed Flow Fans
Belt and Direct Drive
Models QEI-L, QEI, QEID
October
2013
Quiet & Efficient, Inline
Mixed Flow Fans
Model QEI-L – Belt Drive
Mixed flow inline fans can be used for supply, exhaust,
or return air installations. Our patented design excels
in commercial applications where low sound is critical.
In addition, Greenheck’s mixed flow fans are more
efficient than comparably sized tubular centrifugal
and vane axial fans, thus reducing the required motor
horsepower and lowering operating costs.
• 11 sizes available (12 thru 36)
• Volume Range: 700 - 30,000 cfm
(1190 - 50,970 m3/hr)
• Static Pressure: Up to 3 in. wg (747 Pa)
Greenheck’s mixed flow fans are the quietest tubular
inline fans in the industry!
• Performance as cataloged is assured. All sizes are
licensed to bear the AMCA Certified Sound (both
inlet and outlet) and Air Performance Seal.
UL/cUL Listed
QEI-L
QEI-I/II
QEID
705 - Electrical
9
9
9
9
9
9
Emergency Smoke Evacuation
762 - Restaurant Grease Exhaust
• All sizes are tested before they leave the factory to
ensure trouble-free operation at the jobsite.
• Compact size and a “Universal Mounting System”
make tight space considerations and last minute
mounting changes easy to handle at the jobsite.
Model QEI-I/II – Belt Drive
• 17 sizes available (9 thru 60)
• Two classes of construction
• Volume Range: 500 - 115,000 cfm
(850 - 195,386 m3/hr)
• Static Pressure
Up to 5 in. wg (1245 Pa) Class I
Up to 8.5 in. wg (2120 Pa) Class II
• The belt drive models use air handling quality
bearings that are 100% inspected for swivel torque,
noise levels, and bore tolerances.
• These products are subjected to extensive life cycle
testing, assuring many years of reliable performance.
Typical Mixed Flow Applications:
Recommended for any ventilation application that
requires low sound and high efficiency, such as office
buildings, parking garages, concert halls, libraries,
and educational facilities.
Greenheck Fan Corporation certifies
that the model QEI-L, QEI-I/II and
QEID shown herein are licensed to
bear the AMCA Seal. The ratings
shown are based on tests and
procedures performed in accordance
with AMCA Publication 211 and
AMCA Publication 311 and comply
with the requirements of the AMCA
Certified Ratings Program.
For QEID performance showing AMCA licensed data
for sound and air performance, please refer to the
QEID Sound and Air Performance Supplement found
on our website at www.greenheck.com.
See page 10 for details.
2
Model QEID – Direct Drive
• 15 sizes available (12 thru 54)
• 50 - 100% wheel widths
• Volume Range: 800 - 83,000 cfm
(1,360 - 141,000 m3/hr)
• Static Pressure: Up to 10.5 in. wg (2370 Pa)
Patented (QEI/QEID): USA Patent No. 7048499
China (P.R.) Patent No. CN1294361C
Mexico Patent No. 243465
Standard Construction
Housing
Slip-Fit Duct Connection (QEI-I/II & QEID)
Tubular housings are constructed of welded steel to
eliminate air leakage. Integral straightening vanes are
constructed from steel and welded into place.
Inlets and outlets are designed with extended collars
for slip-fit duct connections as standard. QEI-L is
flanged as standard. Companion flanges can be
ordered for slip fit connections.
Wheel – Mixed Flow
Adjustable Motor Bases (Belt Drive)
Fabricated wheels are constructed from steel. The
blade profiles are angled and contoured for the most
efficient and quiet performance.
Rigid, heavy-gauge steel motor bases are welded to
the fan housing and include heavy-duty adjustment
screws for belt tensioning.
Bearings (Belt Drive)
Extended Lube Lines
Standard bearings are premium air handling quality,
grease lubricated, self-aligning, ball or roller type.
Bearings are selected with a basic rating fatigue life
L10 per ABMA standards, in excess of 80,000 hours
(L50 at 400,000 hours) at the maximum operating
speed for the QEI-I/II and QEI-L in the horizontal
position. The QEI-L bearings are selected with a
basic rating fatigue life L10 in excess of 50,000 hours
(L50 at 250,000 hours) in vertical position.
Belt drive units have nylon lubrication lines with
grease fittings that allow bearing lubrication without
disassembling the fan. Grease fittings are mounted
on the outside of the fan housing. Direct drive
units have extended lubrication lines for the motor
bearings, if required. Smaller frame sized motors are
typically sealed and not lubricatable.
Permatector™ Coating
Bolted Access Door
Greenheck’s Permatector coating is a thermosetting
polyester urethane, electrostatically applied to
provide uniform thickness and a clean appearance.
Permatector coatings also provide excellent
corrosion characteristics for general applications,
both indoor and outdoor. For corrosive environments
(ie. coastal), see page 9 for information on our zincrich basecoat technology.
A bolted access door provides an opening through
the fan housing for cleaning or visual inspection of
the wheel. A hinged access door is available as an
accessory.
Belt Guard (Belt Drive)
A totally enclosed belt guard provides protection
from rotating pulleys and belts. Belt guards meet
OSHA Standards.
Model Number Nomenclature
The model number code provides a numbering system designed to identify the fan model,
size and horsepower.
QEI D* - 36 - I - 70 - A 30
D = Direct Drive
Fan Size
9, 12, 15, 16, 18, 20,
22, 24, 27, 30, 33, 36,
40, 44, 49, 54, 60
Belt Drive available in sizes 9 through 60
Direct Drive available in sizes 12 through 54
Construction
L = Low Pressure
I = Class I
II = Class II
Low Pressure available in sizes 12 through 36
Motor Horsepower
4
3
5
7
10
15
20
= ¼
= 3
= ½
= ¾
= 1
= 1½
= 2
30
50
75
100
150
200
250
= 3
= 5
= 7½
= 10
= 15
= 20
= 25
300
400
500
600
750
1000
1250
= 30
= 40
= 50
= 60
= 75
= 100
= 125
RPM
A = 1770
B = 1170
C = 870
F = 690
J = 1425
K = 950
M = 3600
R = 2900
Percent Wheel Width
50 through 100
* Blue text is specific to direct drive model QEID only
3
Value Added Features
Quality Assurance Test
Before shipment, all Greenheck mixed flow fans are tested at the design speed after final assembly.
QEI-L fans are checked for amp draw and the levels are recorded. QEI-I/II and QEID fans are
subjected to a complete vibration analysis. The maximum allowable vibration on a QEI-I/II at the fan
bearings is 0.15 in/sec. peak velocity for the specified RPM. QEID maximum vibration is 0.08 in/sec.
peak velocity on the fan housing for the specified RPM. A record
of the vibration test result is available upon request.
By performing the vibration test, we are able to provide more than
wheel balancing, it is also a diagnostic tool for finding potential
problems. A defective bearing or motor, bent shaft or misaligned
sheaves may cause excessive vibration. A
complete vibration test will uncover
these problems before the fan leaves
the factory.
Electrostatic Powder Coatings
Powder coatings offer a uniform, durable and high-quality finish.
Standard powder coating is a one-coat process applied over
a phosphatized surface that generally meets or exceeds the
corrosion resistance of a comparable wet paint.
Greenheck offers a number
of in-house coatings applied
via “electrostatic powder.” The
standard coating, Permatector™,
is excellent for indoor or outdoor
applications and is resistance to
many common chemicals. Consult
Greenheck’s Product Application
Guide, Performance Coatings for
Ventilation Products, for a complete
listing of coatings and a relative
resistance chart. For corrosive environments (i.e. coastal), see page 9
for information on our zinc-rich basecoat technology.
Maintenance / Serviceable Construction Advantages
The following value added features are incorporated into the design to allow for quick and
easy field service.
QEI-L and QEI service advantages:
• Bearing lubrication is performed through extended grease fittings located on the
outside of the fan housing.
• The entire shaft and bearing assembly can be removed as a single assembly from
the inlet end of the fan housing.
• An adjustable motor base is provided for tightening the fan belts.
QEID service advantages:
• Extended lubrication lines are provided for motor bearing requiring lubrication.
Smaller frame motors use sealed bearings and are permanently lubricated.
4
Inlet and Outlet Sound Power Levels
All Greenheck mixed flow fans have AMCA licensed sound power levels for both the
fan inlet and outlet.
Application and installation determines which sound power reading (inlet, outlet,
or both) is critical. The differences between the generated sound from the inlet and
outlet are important and noticeable. AMCA licensed inlet and outlet sound power
data provides complete sound information to select a fan based on the acoustical
requirements. For additional information on sound, refer to page 6.
Greenheck’s Sound Lab
Field Rotatable Housing / Compact Size
The QEI-L and QEI are designed to accommodate changing fan
mounting positions and motor orientation in the field. Mounting
fixtures are securely bolted to the fan casing and can be relocated
to reposition how the fan is installed or the position the motor is
oriented. Flexibility in a motor’s location is important for easier
access and can determine where the unit will fit. Last minute
design changes or unexpected obstacles during installation are
no longer a problem.
Greenheck’s mixed flow fans were designed for compact size.
Keeping size to a minimum is important when fitting into tight
spaces like mechanical rooms or air handlers.
Slip-Fit Duct Connections
The inlet and outlet ends of the QEI-I/II and QEID are designed to
accept “slip-fit” connections. Often companion flanges are bolted
to a fan’s inlet/outlet flange to provide a slip-fit connection for a
flexible sleeve, as with the QEI-L. This extra step is now eliminated
by directly attaching the flexible sleeve to the duct and fan. This
saves time and money in the installation process.
It is recommended to use a flexible sleeve connection instead of a
rigid duct connection.
Patented (QEI/Q
(QEI/QEID)
USA Patent No
No. 704849
7048499
China (P.R.) Patent No. CN1294361C
Mexico Patent No. 243465
The advantages of a flexible transition are:
• Decreased sound transmission in
the ductwork
• Flexible connections allow for minor
misalignment
• Accommodates the use of thrust
restraints to resist thrust loads
AutoCAD® and 3-D Revit® Models
Scaled AutoCAD® drawings and Revit® models
are available through Greenheck’s website
or from the Greenheck CAPS program
which retrieves drawings and places them
automatically into a job folder.
5
Design & Performance
Mixed Flow: Axial/Centrifugal Hybrid
Centrifugal
Static Pressure
A mixed flow wheel is a hybrid between an axial propeller and a
centrifugal wheel. The result is a design that combines the best axial
and centrifugal properties: highly efficient air movement, increased
pressure capabilities, extremely low sound levels, and a steep fan
performance curve. To further enhance the fan’s performance,
straightening vanes are incorporated in the housing. These serve
to convert swirling airflow into a straight axial flow with a resulting
static pressure rise and energy savings.
Mixed Flow
Axial
CFM
Airflow Profiles
Axial Fans: Straight through
nearly linear airflow.
Centrifugal Fans: Two 90°
deflections, before airflow
exits the fan.
Axial
Centrifugal
Mixed Flow
Mixed Flow Fans: Slight
airflow deflection from
straight through.
Sound and Efficiency
Sound power levels and fan efficiency are two very important factors when selecting a fan. There is a noticeable
difference between impeller types. The table and chart below compare the sound power (LwA) and the static
efficiency of the belt-driven mixed flow fan wheel versus tubular centrifugal and vane axial inline fans. Over a
wide range of operating points, the mixed flow fan provides the quietest and most efficient selection.
Mixed Flow
Fan Size
Performance
Sound Power (LwA)
Static Efficiency
(QEI-L, QEI-I/II)
Inline
Centrifugal
Vane Axial
Mixed Flow
(QEI-L, QEI-I/II)
Inline
Centrifugal
Vane Axial
Mixed Flow
15,000 cfm
@ 1.0 in. wg
24
90 dB
100 dB
103 dB
43%
17%
34%
25,000 cfm
@ 2.0 in. wg
36
86 dB
93 dB
102 dB
68%
45%
56%
50,000 cfm
@ 4.0 in. wg
49
92 dB
98 dB
111 dB
71%
60%
59%
Model comparisons based on similar outer tube diameters.
Lower Sound Power, Better Sound Quality
Sound power levels shown at each frequency:
Typical
Tubular Centrifugal
Typical
Vane Axial
QEI-L
QEI-I/II
Sound Power, dB
100
90
80
70
60
62
125
250
500
1000
Frequency Hz
6
2000
4000
8000
The sound quality of the belt-driven mixed flow fan line is
as beneficial to low sound design as is the reduced overall
sound power. The sound chart compares units of similar
outer tube diameters at an operating point of 20,000 cfm with
1.5 inches wg of static pressure (Ps). Tubular centrifugals
(green) have dominant tones in the 63 Hz through 250 Hz
octave bands, while vane axials (red) have more mid to high
frequency sound. The mixed flow fan (blue) does not have a
dominant tone. A bystander would hear a more bland sound
that is quieter than a tubular centrifugal or vane axial.
Wheel Characteristics
Belt Drive: Fan Class
Class I and II fans have different wheel designs with different performance characteristics.
Class I mixed flow wheels are optimized for performances involving low pressures and high volumes. Class II
wheels are designed for a steeper fan curve with higher pressure capabilities. This is illustrated in the graph
with the two different class wheels plotted at identical fan RPMs.
When selecting a mixed flow fan, it cannot be assumed that moving into a Class II fan will produce the same
results as a Class I mixed flow fans. Model QEI-L utilizes a Class I wheel.
Static Pressure
Class II
Class I
CFM
Direct Drive: Percent Wheel Width
Direct drive mixed flow fans are optimized for performance requirements by the use of partial width wheels. This
is necessary because the fan RPM is commonly fixed and identical to the motor RPM. A reduction in the width
of the wheel (or the air passage) results in reduced airflow capacity and a steeper fan curve. This is similar to
the effect of a reduced pitch in a direct drive vane axial fan. QEID wheels are available in 5% increments from
50 - 100% wheel width.
Static Pressure
QEID fans can be used in conjunction with variable frequency drives (VFD’s) for variable air volume (VAV)
systems. In these applications, the wheel width is optimized to ensure efficient operation and stable
performance throughout the turndown range. VFD’s are also used for final system balancing and to reduce the
airflow when building requirements are reduced. In this case, the fan and wheel width are selected using the
final design CFM and static pressure.
100%
Wheel
Width
50%
Wheel
Width
Intermediate
Wheel
Widths
50% Wheel Width
100% Wheel Width
CFM
Sound Power versus Sound Pressure
The sound values displayed on the performance pages are in terms of inlet sound power (LWi A) and outlet sound
power (LWo A). These values are the acoustic power radiating from the inlet and outlet of the fan, respectively.
Sound pressure, expressed as dBA, is the acoustic pressure at a point in space which can be measured with a
microphone or can be heard. To convert sound power (LwA) into sound pressure (dBA), the following corrections
are applied for a hemispherical free field.
Distance from Fan
3 ft. (0.9 m)
5 ft. (1.5 m)
10 ft. (3.0 m)
dBA = LwA - correction
Correction
7 db
11.5 db
17.5 db
Note: Refer to AMCA Publication 303, Application of Sound Power Level Ratings for additional information on calculating typical sound pressure levels for fan installation.
7
Optional Features
Sure-Aire™
The Sure-Aire™ flow monitoring system measures fan
flow within a 3% accuracy. Unlike traditional flow probes
mounted in the fan venturi that create a system effect
hindering fan performance, Sure-Aire™ does not interfere
with airflow and will not impact the fan’s air or sound
performance. This option is available on all mixed flow fan
models and ships completely assembled from our factory.
An electronics package with pressure transmitter and
digital read out is available with the Sure-Aire™ system. The
electronic kits are available for 50 or 60 Hz power supplies
upplies
and provide either a 4-20 mA or 2-10 VCD output that
at can
be tied into the building’s automation system.
Sound Sensitive Areas
Sound Vault Housing - Radiated Sound Enclosure
The sound vault housing is an excellent product for fans that will be positioned adjacent to an occupied work
space or in sound critical applications. It locks in radiated sound from the fan casing, motor and drives, and
minimizes vibration transmission. Standard construction includes an acoustically lined housing, integral spring
isolators, and internal flexible connections at the fan’s inlet and outlet to effectively isolate the fan from the
system. Vertical or horizontal mounting configurations are available.
Why use a Sound Vault?
• Sound power attenuation levels determined by
sound intensity tests on actual units
• Ships fully assembled with fan
• Internal isolation to limit breakout noise
• Access panels for inspection of fan and motor
• Bearing lubrication lines extended to outside of
enclosure
• Formed mounting rails with prepunched holes
for easy installation
• Available on both QEI-I and QEID through
size 27 fans
This table lists the radiated sound
reductions from total sound power
levels for each octave band with
the sound vault housing.
8
Center Frequencies [Hz] 63
Attenuation Value (dB)
13
125 250 500 1000 2000 4000 8000
20
25
31
34
35
36
36
Optional Two-coat
Paint System
In 1972, Greenheck took the lead as the first commercial and industrial fan manufacturer to introduce
electrostatic powder coatings. Today, Greenheck continues to lead by being the first to offer a superior zinc-rich
powder basecoat and powder coating finish.
This zinc-rich basecoat technology is used extensively outside the HVAC industry to protect bridge beams,
automotive components and other heavy-gauge steel products. Now, this advanced technology is available on
Greenheck welded steel products.
Greenheck’s coating process starts with a minimum of five wash stages to treat all components prior to
painting. Cleaner parts result in better coating adhesion and durability. We then use an advanced two-coat
powder application method that includes a basecoat of zinc-rich powder and a topcoat of Greenheck’s
Permatector™ or Hi-Pro Polyester. The combination of these two topcoats over the zinc-rich basecoat results
in the two-coatings, Perma-Z and Hi-Pro-Z. These oven-cured coatings provide superior corrosion resistance
along with a tough, uniform finish to combat the most extreme conditions.
Zinc Advantage
When compared to a traditional single coat
application, the benefits of the two-coat
system include:
One Coat Process
Topcoat
• An automatic powder coat application
that produces uniform coverage and
unmatched paint quality.
• A double coat thickness that provides
superior durability and protection from
air and water.
Standard
Surface Preparation
2-3 mils
Base Steel
Two-coat Process
Zinc-rich Primer
(70% zinc)
Topcoat
• A zinc-rich basecoat that includes
an epoxy component that provides
additional corrosion protection.
• A zinc-rich basecoat that provides
chemical protection of exposed steel
to prevent corrosion.
The protection offered by the zinc-rich basecoats in
Perma-Z and Hi-Pro-Z result in extraordinary corrosion
resistance. Test data demonstrates our two-coat paint
system offers three (Perma-Z) and four (Hi-Pro-Z) times
the corrosion resistance of other coatings commonly
available within the fan industry. See table for salt spray
life for various coatings.
Coating fans with Perma-Z or Hi-Pro-Z has reduced our
customers annual paint maintenance costs by three to
four times!
For more information, see Greenheck’s Coatings for
Extreme Applications catalog, available online at
www.greenheck.com
Advanced
Surface Preparation
4-6 mils Total
Base Steel
Salt Spray ASTM B117
Hours
1000
2000
3000
4000
Permatector™
Hi-Pro Poly
Perma-Z
Hi-Pro-Z
Baked Phenolic
Epoxy Phenolic
Fluorocarbon
Salt Spray ASTM B117 is a comparative test
that indicates the corrosion resistance of
powder paint coatings.
9
Certifications & Listings
Seismic Certification
The International Building Code (IBC) has been adopted at the state and local
level throughout the United States. With the adoption of this code, comes the
introduction of standards intended to improve the performance and design of
non-structural systems subject to seismic events.
QEI-I/II and QEID
• Meet the 2006 IBC, 2009 IBC
• California OSHPD requirements (horizontal mount only) OSP 0223-10
• Shake table tested at an independent test facility in accordance with
ICC-ES AC 156
Structural Finite Element Analysis
• All equipment certified to worst case scenario seismic conditions
Seismic Design Category F
- Importance factor of 1.5 (IP = 1.5)
- Occupancy Categories (I - IV)
- Site Classes (A - F)
- Seismic Design Categories (A - F)
Consult your Greenheck representative or visit greenheck.com/seismic for more details.
UL 705 Power Ventilator
QEI-L, QEI-I/II and QEID models are available with the UL/cUL 705 (Underwriters Laboratory) listing on a wide
variety of 50 and 60 Hz motors. This listing ensures the use of UL approved electrical components.
Motors are available as either IEC (IP55) or NEMA (TEAO or ODP) designs. IEC design
motors are adjustable speed drive (ASD) compatible, have class F insulation and are
capable of wye-delta starting when over 5.5 kW. NEMA motors use across the line
starting with options for ASD compatibility. Motor (IEC or NEMA) using 50 Hz power have
a 1.0 service factor, while 60 Hz power have 1.15
UL/cUL File E40001
UL/cUL Listed Power Ventilator service factor. Design and construction options
for motors include increased thermal insulation,
overload protection and extended motor leads.
UL Emergency Smoke Evacuation
QEI-I/II and QEID models were tested and
rated for design time and temperature used
in emergency heat and smoke exhaust
applications.
UL/cUL File MH17511
UL/cUL Power Ventilators for Smoke Control Systems
Model
Operating
Time
Temperature Duration
ºC
ºF
Hours
QEID
300
572
1
QEI-I/II
300
572
2
QEI-I/II
260
500
4
QEID
260
500
5
Comments
Per British Spec 7346
Per Industrial Risk
Insurers (North America)
Consult your Greenheck representative for time and temperature
combinations other than those listed.
UL 762 Restaurant Exhaust
Inline grease exhaust fans are an excellent alternative for
kitchen applications when roof or wall mounted ventilators
are not practical. A QEI-I/II with UL 762 grease option is
designed to withstand the demands of high temperature
kitchen grease exhaust and high-pressure duct washers.
A Tough Package to Beat
The QEI-I/II inline grease fan is tough to beat when
packaged with our full line of kitchen hoods and grease
extraction options. Take advantage of Greenheck’s
expertise in providing a total solution in kitchen ventilation
equipment.
10
Listed Power
Ventilation for
Restaurant
Exhaust
Appliances
13G3 Maximum
Operating
Temperature
400°F.
UL 762 is concerned with fans designed
for removal of smoke and grease laden
vapors with airstream temperatures up
to 400°F.
• Meets all UL 705 requirements
• UL/cUL File MH11745
UL/cUL Power Ventilators for
Restaurant Exhaust Appliances
• Bolted access door
• Drain connection
• Meets requirements of NFPA 96
Ventilation Control and Fire Protection
of Commercial Cooking Operations
Belt Drive versus Direct Drive
Belt Drive Advantages
• Lower sound levels
• Motor out of the airstream for easy access
• Motor size may be changed to accommodate
possible future air capacity requirements
• Final system balancing accomplished by
changing drives
Direct Drive Advantages
• Fewer wear components and less maintenance, no
shaft, bearings, pulleys, or belts
• More compact than equivalent belt drive size
• Motor in airstream for increased motor efficiency
and cooling
• Equal loading between mounting brackets
• Final system balancing accomplished by adjusting
the motor speed (ex. variable frequency drive use).
High Efficiencies = Lower Operating Costs
Example of Annual Operating Cost Savings
For a system performance requirement of 25,000 cfm at 2.5 inches of static pressure (wg) the corresponding
operating power requirements are 13.97 Bhp with a QEI-I size 36 and 19.8 Bhp for a size 36 tubular centrifugal fan.
Formulas:
- Kilowatt-Hours = (Operating Power (Bhp) x 0.746 x Hours of Operation) / Motor Efficiency
- Operating Cost = Kilowatt-Hours x Power Cost per kW hour
Assumptions:
- Cost of electricity is $0.09 per kilowatt hour
- 3,120 annual hours of operation (12 hours per day, five days a week, 52 weeks a year)
- 93.0% motor efficiency (equal to NEMA Premium minimum efficiency for 15 and 20 hp, ODP, 1725 rpm motor)
Tubular Centrifugal Fan
QEI-I - Mixed Flow Fan
kW-Hours = (19.8 Bhp x 0.746 x 3120) / 0.93 = 49,554
kW-Hours = (13.97 Bhp x 0.746 x 3120) / 0.93 = 34,963
Operating Cost = 49,554 x $0.09 = $4,460
Operating Cost = 34,963 x $0.09 = $3,147
Annual Operating Cost Savings = $4,460 - $3,147 = $1,313
11
Belt Drive Mounting
Configurations
QEI-I/II Sizes 9-27 and all QEI-L
Universal Mounting
Optional
Mounting
Rails
Fig. 1
Fig. 2
QEI-I/II models sizes 9-27 and all QEI-L models can be
mounted horizontally or vertically. For ease of installation,
eight mounting brackets are welded on each fan. These
eight brackets along with standard mounting supports
provide for Greenheck’s Universal Mounting System.
Motor positions are viewed from the discharge end.
Fig. 1
Horizontal Base Mount
Each fan is shipped as standard in this arrangement.
Motor at “A” position (12 o’clock) is standard.
Fig. 2
Horizontal Base Mount with motor at “C” or “G”
position (3 or 9 o’clock). A set of optional mounting
rails are recommended for this installation.
Fig. 3
Horizontal Ceiling Hung
In this installation the supports can be positioned for
mounting the motor at “A” or “E” (12 or 6 o’clock).
Fig. 4
Horizontal Ceiling Hung with motor at “C” or “G” (3
or 9 o’clock). A set of optional mounting rails are
recommended for this installation.
Fig. 5
Vertical Mount
Universal QEI fans can be mounted vertically (ceiling
hung or base mount) for either upward or downward
airflow. Optional mounting rails are suggested for
any vertical installation.
Optional
Mounting
Rails
Fig. 4
Fig. 3
Vertical Ceiling Hung
Optional
Mounting Rails
Vertical Base Mount
Fig. 5
A
H
QEI-I/II Sizes 30-60
QEI-I/II models 30-60 are available in horizontal and vertical mounting configurations.
Lifting lugs are provided on horizontal fans for ease of installation. Vertical units
should be lifted by the mounting brackets.
B
G
C
Horizontal Mounting
Horizontal mounting configurations, base mount or ceiling hung, are provided with an
identical support. The mounting configuration can be changed between base mount
or ceiling hung in the field. The motor position can also be field rotated to any of the
shown positions. Motor positions are viewed from the discharge end.
Base Mount: Rigid steel base provides stable mounting to floor for the housing.
Motor Positions: A, B, C, G and H
Horizontal - Base Mount
A
C
G
Ceiling Hung: Suspend the fan horizontally from the ceiling.
Motor Positions: A, C, D, E, F and G
Mounting rails are recommended for horizontal installations with B, C, D, F, G and H
motor positions.
F
D
E
Horizontal - Ceiling Hung
Vertical Mounting
Vertical mounting configurations, upblast or downblast, are provided with heavy duty steel brackets welded to
both ends. These brackets permit either floor or ceiling mounting on the same unit. Optional mounting rails are
suggested for any vertical installation for sizes 9-27.
12
Roof Upblast & Spark Resistant
Construction
Roof Upblast
Models QEI-I/II sizes 9 through 54 and model QEID
sizes 12 through 54, are available in roof upblast
configuration. The roof upblast configuration is ideal
for exhausting contaminants away from a building to
prevent roof damage and re-entrainment of exhaust
air. Both QEI-I/II roof upblast models have the high
temperature UL rating and can be used for emergency
smoke exhaust applications.
Standard construction includes a fully-welded heavygauge curb cap to eliminate leaks, a butterfly damper
section for backflow prevention, and a windband
section to protect the butterfly dampers from debris. A
complete line of roof curbs is available for mounting to
a roof deck.
Spark Resistant Construction
Greenheck mixed flow fans are available with spark
resistant designs suitable for applications that involve
flammable particles, fumes or vapors. Spark resistant
construction options adhere to guidelines defined
within AMCA Standard 99-0401-10.
QEI-I/II
QEI-I/II
QEI-L
Spark B
The fan wheel is constructed of a
nonferrous material (aluminum).
A non-ferrous (aluminum) bearing
cover surrounds the driven bearing,
shielding it from the airstream.
Spark C
The inlet cone is constructed of
non-ferrous material (aluminum).
A nonferrous (aluminum) bearing
cover surrounds the driven bearing
shielding it from the airstream.
13
Accessories
Availability
Motor Cover
Hinged Access Door
QEI-L
QEI-I
QEI-II
A weatherproof motor cover shields the motor components
from dust, dirt and moisture for indoor or outdoor
installations. Motor covers also serve as a personnel guards
and meet OSHA standards.
9
9
9
Hinged access doors provide an opening through the fan
housing for cleaning or visual inspection of the wheel. Bolted
access door is standard.
9
9
9
9
9
9
9
9
Std.
9
9
9
9
9
9
9
9
9
9
9
Extended Life
Bearings
Air handling quality, flange mounted bearings meet a basic
rating fatigue life L10 per ABMA standards, in excess of
200,000 hours (L50 at 1,000,000) at maximum operating
speed.
Copper Lube Lines
(Belt Drive)
Copper lube lines can be used as a replacement for
standard nylon lube lines.
Flanges
Inlet and outlet flanges with prepunched holes, welded to
the housing, provide an easy means for bolted connection
to ductwork. Matching bolt-on companion flanges are also
available.
Disconnect Switches
Toggle-type and heavy-duty disconnect switches are
available for positive electrical shut-off and safety when
servicing fans. The following switches are available to
meet individual electrical requirements and can be factory
mounted or shipped loose for field mounting.
• NEMA-1
General purpose
• NEMA-3R
Rainproof
• NEMA-4
Watertight
• NEMA-7 & 9* Class 1 and 2 hazardous locations
QEID
9
*Greenheck will not factory mount NEMA-7 & 9 disconnect switches.
Inlet and Outlet
Guards
Removable inlet and outlet guards provide protection
for personnel and equipment in ducted or non-ducted
installations.
Extended Wiring
Electric leads from the motor junction box are brought out to
exterior of unit. This provides an easy means of connecting
the motor to the electrical system.
9
Belt Tube
A totally enclosed belt tube isolates the belts and drives
from the airstream.
Sound Vault Housing
See page 8 for more details on sound vault housing.
Mounting Rails
Mounting rails are recommended for vertically mounted fans
or horizontal mounting when the motor is to be located in the
C or G (3 or 9 o’clock) position.
9
9
9
Isolators
Both base mount and hanging isolators are available in
either neoprene or spring mounts.
9
9
9
9
Special Coatings
Special coatings are available for protective purposes.
Consult Greenheck’s Product Application Guide,
Performance Coatings for Ventilation Products, for a
complete list of coatings available and their chemical
resistance. Available online at www.greenheck.com.
9
9
9
9
Sure-Aire provides real-time flow measurement for use in
building automation systems. For additional information,
see page 8 or our Sure-Aire Flow Monitoring System catalog
available at www.greenheck.com.
9
9
9
9
Sure Aire™ Flow
Measurement
14
9
9
9
9
9
Exploded View
Motor Cover
Companion Flange
Slip Fit Connection
(Standard on QEI-I/II)
Inlet Guard
Outlet Flange
(Standard on QEI-L)
Outlet Guard
Bolted Access Door
(Standard)
Spring Base Isolator
Neoprene Base Isolator
Inlet Flange
(Standard on QEI-L)
Companion Flange
Spring Hanging Isolator
Mounting
Rails
15
Direct Drive Selection Charts
The quick select charts below and on the following page are a convenient method for sizing the fan required for a
specific performance. Colored bands for a given size in each chart represent the entire operating range available
for that size and speed.
For QEID performance pages showing AMCA Licensed data for sound and air performance please refer to the
Model QEID Sound and Air Performance Supplement found at www.greenheck.com
12
10
1770 RPM
(60 Hz)
Static
Pressure
(in. wg)
Model QEID
12—33
8
6
4
2
12
0
15
16
1
18 20 22
5
24 27 30 33
10
50
100
Volume (cfm x 1000)
12
10
1170 RPM
(60 Hz)
Static
Pressure
(in. wg)
Model QEID
15—49
8
6
4
2
15
0
1
16
18
20
5
22
24 27 30 33 36 40 44 49
10
Volume (cfm x 1000)
16
16
50
100
QEID Dimensional Data
8
6
870 RPM
(60 Hz)
Static
Pressure
4
(in. wg)
Model QEID
36—54
2
36
0
10
40
20
30
44
40
49
54
50
100
Volume (cfm x 1000)
Size
Slip Fit
O.D.
Length
* Length varies with motor frame size.
Refer to Length table shown.
** Weight is for unit only and does not
include motor.
12
15
16
18
20
22
24
27
30
33
36
40
44
49
54
Slip Fit O.D.
inches
mm
17.13
435
20.88
530
23.00
584
25.38
645
27.81
706
30.88
784
34.00
864
37.44
951
41.63
1057
45.75
1162
50.56
1284
55.75
1416
61.63
1565
67.75
1721
75.00
1905
Length*
inches
mm
25.0
635
25.0
635
26.0
660
29.0
737
34.0
864
35.5
902
41.5
1054
45.0
1143
Length — inches (millimeters)
284/6 T
324/6 T
364/5 T
Refer to
table below.
Size
254/6 T
30
45.5 (1156)
50.0 (1156)
50.0 (1156)
33
46.5 (1181)
54.0 (1372)
54.0 (1372)
54.0 (1372)
36
50.5 (1283)
58.0 (1473)
58.0 (1372)
58.0 (1372)
56.5 (1435)
61.0 (1549)
61.0 (1549)
64.0 (1626)
64.0 (1626)
70.0 (1778)
49
74.5 (1892)
74.5 (1892)
80.5 (2045)
54
77.0 (1956)
77.0 (1956)
83.0 (2108)
40
44
404/5 T
Weight**
lbs.
kg.
100
45
140
65
170
80
200
95
250
115
370
170
480
220
570
260
860
390
1140
520
1360
620
1650
750
2190
995
2700
1225
3130
1420
444/5 T
17
QEI Dimensional Data
QEI-L
QEI
Airflow
Airflow
Height
Slip Fit
O.D.
Height
Length
Length
QEI-L
Slip-Fit O.D.
Length
QEI Class I
Height
Slip-Fit O.D.
Length
Height
QEI Class II
Length
Height
Size
inches (mm)
18
inches (mm)
inches (mm)
inches (mm)
inches (mm)
9
NA
NA
NA
17.13 (435)
NA
NA
28.5 (724)
36.5 (927)
12
17.5 (445)
26.5 (673)
37.5 (953)
17.13 (435)
28.5 (724)
36.5 (927)
30.5 (775)
36.5 (927)
15
21.13 (537)
29.0 (737)
41.5 (1054)
20.88 (530)
31.0 (787)
41.0 (1041)
34.0 (864)
41.0 (1041)
16
23.31 (592)
31.0 (787)
44.0 (1118)
23.00 (584)
33.0 (838)
44.0 (1118)
34.0 (864)
44.0 (1118)
18
25.63 (651)
33.0 (838)
46.5 (1181)
25.38 (645)
35.0 (889)
46.5 (1181)
39.5 (1003)
47.5 (1207)
20
28.06 (713)
35.5 (902)
50.5 (1283)
27.81 (706)
37.5 (953)
50.5 (1283)
41.5 (1054)
50.5 (1283)
22
31.13 (791)
39.0 (991)
53.5 (1359)
30.88 (784)
41.0 (1041)
53.5 (1359)
44.0 (1118)
53.5 (1359)
24
34.25 (870)
42.5 (1080)
55.5 (1410)
34.00 (864)
44.5 (1130)
57.5 (1461)
49.0 (1245)
59.5 (1511)
27
37.69 (957)
45.0 (1143)
61.0 (1549)
37.44 (951)
47.0 (1194)
61.0 (1549)
53.0 (1346)
63.0 (1600)
30
42.00 (1067)
52.0 (1321)
64.5 (1638)
41.62 (1057)
54.0 (1372)
65.0 (1651)
60.5 (1537)
72.0 (1829)
33
46.13 (1172)
56.5 (1435)
68.0 (1727)
45.75 (1162)
58.5 (1486)
69.0 (1753)
65.0 (1651)
76.5 (1943)
36
51.06 (1297)
62.0 (1575)
75.0 (1905)
50.56 (1284)
64.0 (1626)
75.0 (1905)
69.0 (1753)
82.5 (2096)
40
NA
NA
NA
55.75 (1416)
68.5 (1740)
83.0 (2108)
75.5 (1918)
90.5 (2299)
44
NA
NA
NA
61.62 (1565)
74.0 (1880)
89.5 (2273)
80.5 (2045)
97.0 (2464)
49
NA
NA
NA
67.75 (1721)
80.5 (2045)
96.5 (2451)
86.5 (2197) 104.0 (2642)
54
NA
NA
NA
75.00 (1905)
87.0 (2210) 105.0 (2667) 93.5 (2375) 111.0 (2819)
60
NA
NA
NA
82.88 (2105)
91.5 (2324) 113.0 (2870) 102.5 (2604) 119.0 (3023)
QEI-9 Class II
10
Performance Data
5
50% WOV
RPM
BHP
% WOV
3
Density 0.075 lb/ft
3
Density 1.2 kg/m
3
4000
Specification Data
8
184T
Minimum Motor
Starting hp
1/3 hp
.25 kW
Wheel Diameter
15 in.
381 mm
Approximate Weight
(Less Motor & Drives)
77 kg.
170 lbs.
70% WOV
2
15
10
Static Pressure (in. wg)
Static Pressure (Pa x 100)
20
Maximum Motor
Frame Size
TH
EL
EF
TO
FT
HIS
SY
ST
EM
CU
RV
E
Maximum Fan RPM
60% WOV
6
1½
1
4
¾
28
5
2
3
SE
LE
CT
Maximum Bhp = (Fan RPM / 2671)
TO
½
3
Outlet Velocity (FPM) = CFM / 1.56
Tip Speed (FPM) = Fan RPM x 3.93
DO
0
% WOV = (CFM x 100) / (Fan RPM x 0.73)
16
T
NO
22
40
34
00
80% WOV
00
00
90% WOV
00
00
0
0
5
10
15
Volume (cfm x 100)
Imperial data — Metric data
0
1
2
20
25
3
30
4
5
3
Volume (m /hr x 1000)
Performance Data
STATIC PRESSURE (inches wg)
CFM
OV
0.25
0.5
1
1.5
2
2.5
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
850
541
1325
0.09
1463
0.14
1709
0.25
1937
0.38
2148
0.52
2341
0.67
1000
636
1511
0.13
1633
0.18
1854
0.31
2056
0.44
2252
0.59
2432
1150
732
1700
0.17
1811
0.23
2013
0.37
2198
0.52
2371
0.68
2542
1300
828
1893
0.23
1994
0.29
2177
0.44
2349
0.61
2511
0.78
1450
923
2088
0.31
2181
0.37
2351
0.53
2510
0.71
2658
1600
1019
2285
0.40
2371
0.47
2530
0.63
2674
0.82
2818
1750
1114
2483
0.50
2563
0.58
2711
0.75
2849
0.95
1900
1210
2682
0.63
2757
0.72
2897
0.89
3027
1.10
2050
1305
2883
0.77
2952
0.87
3084
1.06
3207
2200
1401
3083
0.94
3149
1.04
3274
1.25
3390
2350
1496
3285
1.13
3347
1.24
3465
1.46
2500
1592
3487
1.34
3545
1.46
3657
1.69
1600
2200
2800
3400
4000
% WOV
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
1
69
71
70
72
74
72
73
75
77
77
78
78
78
78
80
80
78
79
82
82
2
71
69
70
70
75
71
72
73
78
78
79
79
80
81
82
82
82
83
85
84
3
74
72
71
71
78
73
74
74
82
77
78
79
84
81
81
82
85
84
84
85
4
70
68
66
65
75
72
70
70
78
74
74
75
80
77
77
79
82
81
80
83
5
71
68
63
63
75
72
69
69
80
75
74
74
83
79
78
78
87
83
82
82
6
67
66
65
65
74
71
70
70
79
75
74
74
83
79
78
78
87
83
81
82
7
65
62
61
61
71
66
66
66
75
71
70
70
79
75
74
74
83
79
78
78
3.5
4
RPM
BHP
RPM
BHP
0.75
2606
0.93
2767
1.11
0.85
2700
1.03
2858
2661
0.96
2817
1.15
2961
0.89
2804
1.08
2940
1.28
1.02
2951
1.23
3083
1.44
2981
1.16
3109
1.38
3230
3149
1.32
3271
1.56
3387
1.26
3324
1.50
3435
1.75
1.45
3502
1.70
3609
1.96
3576
1.68
3683
1.92
3785
2.19
3764
1.93
3865
2.16
3964
2.44
Inlet Sound Power, LWi [dB ref 10-12 watts]
RPM
3
RPM
BHP
1.22
3007
1.42
1.35
3098
1.56
3079
1.49
3212
1.71
3207
1.66
3331
1.88
1.61
3351
1.84
3466
2.08
1.80
3498
2.04
3611
2.29
3549
2.00
3656
2.26
3758
2.53
3713
2.22
3818
2.50
3918
2.78
3883
2.47
3981
2.76
Outlet Sound Power, LWo [dB ref 10-12 watts]
8
57
56
55
55
65
60
60
61
74
66
65
65
79
71
70
70
83
76
76
75
LWiA
75
73
71
71
80
77
76
76
85
81
80
80
89
84
84
84
92
88
87
88
RPM
1600
2200
2800
3400
4000
% WOV
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
1
76
77
80
82
86
86
87
88
88
87
91
92
88
90
94
94
88
94
95
95
2
78
80
78
78
86
85
85
86
85
88
85
86
88
88
87
88
93
86
89
90
3
78
77
76
77
84
84
82
82
87
85
86
86
91
89
89
89
96
92
92
92
4
70
67
66
66
77
73
73
74
81
77
78
79
84
80
82
83
87
82
85
86
5
71
68
66
66
78
74
73
73
83
79
78
79
87
83
83
84
91
87
86
88
6
65
63
62
62
74
70
69
69
80
76
75
75
85
81
80
81
90
86
85
85
7
63
58
58
58
69
65
65
65
75
71
70
70
80
76
76
76
85
81
81
81
8
56
56
56
56
64
61
61
61
72
66
67
67
78
71
72
72
83
75
76
77
LWoA
76
74
73
73
82
80
79
79
87
84
84
84
92
88
88
89
96
92
92
92
Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not
include the effects of appurtenances (accessories).
The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA Standard 301. Values shown are for inlet LWi , LWi A and outlet LWo ,
LWo A sound power levels for installation type B: Free inlet, Ducted outlet. Ratings for inlet sound do not include the effects of duct end correction. Ratings for outlet
sound include the effects of duct end correction. The A-weighted sound power ratings shown have been calculated per AMCA Standard 301. The AMCA Certified
Ratings Seal applies to LWi A and LWo A values only.
19
QEI-12 Class I & QEI-L
10
Performance Data
QEI-L
QEI
5
7½
50% WOV
RPM
BHP
% WOV
Density 0.075 lb/ft3
3
Density 1.2 kg/m
60% WOV
2564
3800
20
Specification Data
8
70% WOV
Maximum
QEI-L
184T
Motor
QEI
184T
Frame Size
Minimum Motor
1/3 hp
.25 kW
Starting hp
Wheel Diameter
15 in.
381 mm
Approximate Weight QEI-L 120 lbs. 55 kg.
(Less Motor & Drives) QEI 160 lbs. 73 kg.
Maximum Bhp = (Fan RPM / 2301)3
Outlet Velocity (FPM) = CFM / 1.56
Tip Speed (FPM) = Fan RPM x 3.93
% WOV = (CFM x 100) / (Fan RPM x 1.34)
Imperial data — Metric data
15
10
80% WOV
TH
EL
EF
TO
FT
HIS
SY
ST
EM
CU
RVE
Static Pressure (Pa x 100)
3
Static Pressure (in. wg)
6
2
1½
4
1
¾
38
00
32
00
90% WOV
25
5
2
64
½
TO
Maximum
Fan RPM
EC
T
3
DO
0
0
T
NO
L
SE
200
0
1400
1
2
3
Volume (cfm x 1000)
0
2
4
4
6
5
6
8
10
3
Volume (m /hr x 1000)
Performance Data
STATIC PRESSURE (inches wg)
CFM
OV
0.25
0.5
1
1.5
2
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
2.5
3
RPM
BHP
RPM
BHP
3.5
4
RPM
BHP
RPM
BHP
RPM
BHP
1200
764
1070
0.09
1241
0.15
1549
0.30
1823
0.49
1500
955
1257
0.13
1399
0.20
1661
0.37
1907
0.57
2137
0.79
2341
1.03
1800
1146
1461
0.19
1575
0.27
1807
0.46
2020
0.67
2228
0.91
2423
1.16
2607
1.43
2776
1.72
2100
1337
1669
0.27
1763
0.36
1967
0.56
2162
0.80
2341
1.04
2523
1.31
2690
1.60
2858
1.90
3016
2.22
2400
1528
1881
0.38
1966
0.48
2139
0.69
2317
0.94
2484
1.21
2640
1.49
2801
1.79
2954
2.11
3099
2.44
2700
1719
2095
0.51
2172
0.62
2323
0.85
2479
1.11
2636
1.40
2785
1.71
2926
2.02
3067
2.35
3208
2.70
3000
1910
2310
0.68
2382
0.79
2514
1.04
2657
1.31
2799
1.62
2938
1.94
3072
2.28
3201
2.63
3322
2.98
3300
2101
2527
0.88
2593
1.00
2716
1.26
2840
1.55
2969
1.86
3100
2.21
3226
2.57
3348
2.94
3467
3.32
3600
2292
2745
1.11
2806
1.25
2922
1.53
3029
1.82
3150
2.16
3265
2.50
3387
2.88
3503
3.28
3615
3.68
3900
2484
2964
1.39
3021
1.54
3129
1.84
3231
2.15
3335
2.49
3446
2.86
3551
3.23
3665
3.65
3772
4.08
4200
2675
3184
1.71
3237
1.87
3338
2.19
3435
2.53
3527
2.87
3630
3.25
3731
3.65
4500
2866
3404
2.08
3453
2.25
3549
2.59
3641
2.95
3729
3.31
Inlet Sound Power, LWi [dB ref 10-12 watts]
RPM
1400
2000
2600
3200
3800
% WOV
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
1
77
77
78
78
78
74
74
76
83
80
79
81
85
82
83
83
86
80
85
84
2
78
78
78
77
78
77
76
77
82
82
81
81
85
85
85
84
87
87
88
87
3
71
69
68
68
78
76
75
75
80
81
79
79
82
83
82
82
85
83
85
84
4
73
68
65
64
79
75
71
70
80
78
76
75
82
81
81
81
86
83
85
86
5
67
65
62
62
75
71
68
67
78
75
73
72
81
79
77
77
86
82
80
81
6
68
64
61
60
75
72
68
67
77
76
74
73
80
78
77
77
84
80
79
80
7
61
60
60
60
73
66
64
63
83
74
70
69
87
79
74
74
88
80
77
78
Outlet Sound Power, LWo [dB ref 10-12 watts]
8
52
52
52
52
59
58
58
58
68
65
65
65
79
70
70
70
91
74
74
74
LWiA
75
72
70
69
82
78
75
74
86
82
80
79
90
86
84
84
95
88
87
88
RPM
1400
2000
2600
3200
3800
% WOV
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
1
87
87
88
89
84
84
85
87
90
92
90
91
93
94
93
95
93
93
96
97
2
83
81
82
81
84
84
84
84
93
90
89
90
95
92
92
93
94
92
93
94
3
75
74
74
73
80
77
76
76
83
81
81
81
88
85
85
86
93
89
89
90
4
74
71
70
70
80
77
75
75
82
79
79
78
85
82
82
81
90
85
85
85
5
72
70
68
67
80
77
74
73
83
82
79
78
86
85
83
83
90
87
87
87
6
71
68
67
66
77
75
71
70
80
79
77
76
83
82
81
80
88
84
84
84
7
63
62
62
62
75
69
67
66
82
75
73
71
86
80
77
76
87
83
81
81
8
59
58
59
59
64
64
64
64
72
69
69
70
81
74
74
74
92
77
77
77
LWoA
78
76
75
74
84
81
79
79
89
86
84
84
92
89
88
88
97
92
91
92
Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not
include the effects of appurtenances (accessories).
The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA Standard 301. Values shown are for inlet LWi , LWi A and outlet LWo ,
LWo A sound power levels for installation type B: Free inlet, Ducted outlet. Ratings for inlet sound do not include the effects of duct end correction. Ratings for outlet
sound include the effects of duct end correction. The A-weighted sound power ratings shown have been calculated per AMCA Standard 301. The AMCA Certified
Ratings Seal applies to LWi A and LWo A values only.
20
QEI-12 Class II
12
Performance Data
4000
60% WOV
25
Wheel Diameter
Approximate Weight
(Less Motor & Drives)
.25 kW
15 in.
381 mm
180 lbs.
82 kg.
15
10
3
6
2
1½
4
1
¾
Maximum Bhp = (Fan RPM / 2345)3
5
Outlet Velocity (FPM) = CFM / 1.56
½
2
Tip Speed (FPM) = Fan RPM x 3.93
DO
0
% WOV = (CFM x 100) / (Fan RPM x 1.16)
0
70% WOV
LE
FT
OF
TH
IS
SY
ST
EM
CU
RVE
1/3 hp
8
T
NO
0
40
80% WOV
00
34
00
28
00
TO
Minimum Motor
Starting hp
20
TH
E
184T
10
Static Pressure (in. wg)
Maximum Motor
Frame Size
Static Pressure (Pa x 100)
Specification Data
LE
CT
Maximum Fan RPM
RPM
BHP
% WOV
Density 0.075 lb/ft3
Density 1.2 kg/m3
50% WOV
7½
5
90% WOV
220
0
SE
160
0
1
2
3
Volume (cfm x 1000)
Imperial data — Metric data
0
2
4
4
5
6
8
3
Volume (m /hr x 1000)
Performance Data
STATIC PRESSURE (inches wg)
CFM
OV
0
0.5
1
2
3
4
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
5
RPM
BHP
6
RPM
BHP
7
RPM
BHP
RPM
BHP
1400
891
1203
0.08
1460
0.21
1696
0.37
2131
0.75
2510
1.21
1600
1019
1375
0.12
1604
0.26
1812
0.43
2213
0.84
2574
1.31
2894
1.84
1800
1146
1547
0.17
1752
0.33
1943
0.51
2301
0.93
2641
1.43
2957
1.98
3239
2.59
2000
1273
1719
0.24
1906
0.41
2080
0.60
2410
1.05
2728
1.56
3021
2.13
3302
2.76
3557
3.43
2200
1401
1891
0.32
2062
0.50
2223
0.71
2522
1.17
2817
1.71
3102
2.30
3366
2.95
3620
3.64
3854
4.37
2400
1528
2062
0.41
2221
0.61
2370
0.83
2653
1.32
2924
1.88
3190
2.49
3443
3.15
3684
3.86
3917
4.62
2600
1656
2234
0.52
2381
0.74
2519
0.97
2785
1.48
3035
2.06
3283
2.70
3530
3.38
3759
4.11
3981
4.88
2800
1783
2406
0.65
2543
0.88
2673
1.13
2921
1.66
3157
2.27
3393
2.92
3618
3.63
3846
4.38
3000
1910
2578
0.80
2706
1.05
2829
1.31
3064
1.87
3289
2.49
3504
3.17
3722
3.90
3934
4.67
3200
2038
2750
0.98
2871
1.24
2987
1.51
3209
2.10
3421
2.74
3624
3.44
3831
4.19
3400
2165
2922
1.17
3036
1.45
3145
1.74
3356
2.35
3556
3.01
3755
3.74
3943
4.50
3600
2292
3094
1.39
3202
1.68
3305
1.99
3504
2.62
3699
3.32
3887
4.06
Shaded values show where Class I fan selections are more efficient than Class II.
Inlet Sound Power, LWi [dB ref 10-12 watts]
RPM
1600
2200
2800
3400
4000
% WOV
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
1
72
74
73
74
76
76
76
77
83
86
85
86
83
87
87
87
80
82
84
84
2
77
79
80
80
77
78
79
79
82
86
91
89
86
86
90
89
89
83
82
83
3
77
75
75
76
78
76
75
75
83
81
79
80
85
83
82
83
86
83
85
85
4
74
69
66
65
78
74
71
71
80
77
76
76
83
80
79
80
86
81
81
83
5
70
66
64
63
76
72
70
69
80
76
75
74
83
80
79
78
87
83
82
82
6
69
67
64
63
75
72
70
68
78
75
75
74
82
79
78
78
86
82
81
81
7
69
61
58
57
76
68
66
64
78
73
72
70
80
76
76
75
84
79
79
79
Outlet Sound Power, LWo [dB ref 10-12 watts]
8
56
55
55
54
67
63
62
62
79
68
67
67
85
72
71
71
89
76
75
75
LWiA
77
73
72
72
82
78
76
76
86
82
82
81
90
85
85
85
93
88
87
88
RPM
1600
2200
2800
3400
4000
% WOV
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
1
87
84
85
87
89
87
88
89
97
91
91
93
98
93
93
95
95
94
94
94
2
83
85
84
84
85
84
82
83
89
90
87
88
91
90
89
89
90
88
89
89
3
78
73
73
73
80
77
77
77
86
83
83
83
88
86
86
86
90
87
89
88
4
75
70
68
68
80
76
74
74
83
80
79
79
86
83
83
83
89
85
85
86
5
74
71
68
68
80
77
74
74
84
82
80
79
88
85
84
83
91
88
88
87
6
71
69
66
65
77
74
72
71
81
79
77
76
85
82
81
81
89
86
85
84
7
69
63
61
60
75
70
67
67
78
75
73
73
81
79
78
77
85
82
82
82
8
58
58
58
59
67
66
66
66
78
71
71
70
84
75
75
74
87
78
78
78
LWoA
79
76
75
74
84
81
79
79
89
86
85
84
92
89
89
88
96
92
92
91
Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not
include the effects of appurtenances (accessories).
The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA Standard 301. Values shown are for inlet LWi , LWi A and outlet LWo ,
LWo A sound power levels for installation type B: Free inlet, Ducted outlet. Ratings for inlet sound do not include the effects of duct end correction. Ratings for outlet
sound include the effects of duct end correction. The A-weighted sound power ratings shown have been calculated per AMCA Standard 301. The AMCA Certified
Ratings Seal applies to LWi A and LWo A values only.
21
QEI-15 Class I & QEI-L
7
Performance Data
50% WOV
5
QEI-L
QEI
2090
2721
RPM
BHP
% WOV
Density 0.075 lb/ft3
Density 1.2 kg/m3
60% WOV
6
14
Specification Data
10
8
6
70% WOV
2
4
3
1
2
4
D
0
80% WOV
00
20
90
90% WOV
0
C
T
1
0
21
25
150
TO
½
2
27
CU
RV
E
12
LE
FT
OF
TH
IS
SY
ST
EM
Maximum
QEI-L
184T
Motor
QEI
213T
Frame Size
Minimum Motor
1/3 hp
.25 kW
Starting hp
Wheel Diameter
18.25 in.
464 mm
Approximate Weight QEI-L 140 lbs. 64 kg.
(Less Motor & Drives) QEI 190 lbs. 82 kg.
Maximum Bhp = (Fan RPM / 1617)3
Outlet Velocity (FPM) = CFM / 2.32
Tip Speed (FPM) = Fan RPM x 4.78
% WOV = (CFM x 100) / (Fan RPM x 2.55)
Imperial data — Metric data
TH
E
Static Pressure (Pa x 100)
3
5
Static Pressure (in. wg)
Maximum
Fan RPM
16
0
0
O
ON
T
LE
SE 10
00
1
2
2
3
4
Volume (cfm x 1000)
4
6
5
6
8
7
10
3
Volume (m /hr x 1000)
Performance Data
STATIC PRESSURE (inches wg)
CFM
OV
0.25
0.5
1
1.5
RPM
BHP
RPM
BHP
RPM
BHP
2
RPM
BHP
2.5
3
RPM
BHP
RPM
BHP
3.5
4
RPM
BHP
RPM
BHP
RPM
BHP
1700
732
823
0.12
965
0.21
1229
0.44
2100
905
952
0.17
1072
0.28
1301
0.52
1508
0.81
2500
1077
1088
0.24
1194
0.36
1391
0.62
1580
0.93
1753
1.27
1915
1.64
2900
1250
1231
0.33
1323
0.46
1495
0.75
1662
1.07
1827
1.43
1976
1.83
2122
2.24
2257
2.68
3300
1422
1376
0.44
1456
0.59
1615
0.92
1763
1.25
1907
1.62
2054
2.03
2188
2.47
2317
2.94
2443
3.42
3700
1594
1524
0.58
1597
0.74
1740
1.11
1875
1.47
2008
1.86
2135
2.27
2266
2.73
2390
3.22
2505
3.72
4100
1767
1674
0.75
1740
0.93
1870
1.31
1996
1.73
2114
2.13
2236
2.56
2350
3.02
2469
3.52
2583
4.05
4500
1939
1825
0.95
1885
1.14
2003
1.55
2121
2.01
2234
2.45
2339
2.90
2451
3.38
2556
3.88
2663
4.41
4900
2112
1977
1.19
2031
1.40
2141
1.83
2251
2.31
2356
2.82
2458
3.29
2553
3.77
2657
4.30
5300
2284
2130
1.47
2180
1.69
2282
2.16
2383
2.65
2483
3.20
2579
3.73
2672
4.24
5700
2456
2283
1.79
2330
2.03
2426
2.52
2517
3.04
2613
3.61
2704
4.20
6100
2629
2436
2.16
2481
2.41
2570
2.94
2657
3.48
Inlet Sound Power, LWi [dB ref 10-12 watts]
RPM
650
1000
1400
2000
2721
% WOV
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
1
63
62
60
60
65
63
63
66
69
68
67
68
73
68
75
81
79
80
78
80
2
61
59
59
59
66
63
63
64
77
76
70
71
73
76
77
80
78
73
75
79
3
59
59
57
56
68
65
63
63
73
70
68
70
82
76
77
77
86
83
78
80
4
56
53
52
52
65
62
60
59
72
68
66
65
81
78
76
76
88
85
81
81
5
57
54
54
53
60
58
57
57
69
66
65
64
78
74
72
72
86
81
79
78
6
52
51
51
51
63
56
55
55
67
63
62
61
74
72
70
71
83
79
77
76
7
48
48
47
47
52
51
50
50
69
58
57
56
77
67
67
67
80
74
73
74
Outlet Sound Power, LWo [dB ref 10-12 watts]
8
35
35
35
35
44
42
42
42
53
50
50
50
65
61
62
61
83
69
69
70
LWiA
60
59
58
58
68
64
63
62
75
71
69
69
84
80
78
78
91
86
84
83
RPM
650
1000
1400
2000
2721
% WOV
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
1
74
69
70
71
73
75
76
77
79
79
77
80
83
79
83
86
91
88
87
90
2
65
64
64
64
73
74
73
74
79
74
75
75
82
78
81
83
85
83
87
89
3
60
59
58
58
66
64
64
64
74
72
73
72
81
77
78
79
87
81
83
85
4
58
57
56
56
68
66
65
65
74
71
69
69
83
79
77
77
90
84
82
83
5
59
57
57
57
65
63
62
62
73
71
68
68
82
79
77
76
90
86
83
83
6
54
55
54
55
64
60
59
59
69
67
66
65
78
75
74
73
86
84
81
81
7
52
52
52
52
55
56
55
55
70
61
61
61
78
70
69
69
82
78
77
76
8
39
40
40
40
47
47
47
47
56
55
55
55
68
63
64
64
84
72
71
72
LWoA
63
62
61
61
70
68
68
68
78
74
73
73
86
82
81
81
94
90
88
88
Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not
include the effects of appurtenances (accessories).
The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA Standard 301. Values shown are for inlet LWi , LWi A and outlet LWo ,
LWo A sound power levels for installation type B: Free inlet, Ducted outlet. Ratings for inlet sound do not include the effects of duct end correction. Ratings for outlet
sound include the effects of duct end correction. The A-weighted sound power ratings shown have been calculated per AMCA Standard 301. The AMCA Certified
Ratings Seal applies to LWi A and LWo A values only.
22
QEI-15 Class II
10
Performance Data
Maximum Fan RPM
3445
RPM
BHP
% WOV
3
Density 0.075 lb/ft
Density 1.2 kg/m3
50% WOV
7½
60% WOV
9
10
5
18.25 in.
464 mm
Approximate Weight
(Less Motor & Drives)
100 kg.
220 lbs.
10
UR
VE
FT
HIS
SY
ST
EM
C
Wheel Diameter
6
3
5
2
4
3
5
DO
0
0
0
% WOV = (CFM x 100) / (Fan RPM x 2.20)
90% WOV
24
02
99
166
SE
1
Tip Speed (FPM) = Fan RPM x 4.78
47
20
LE
CT
2
Outlet Velocity (FPM) = CFM / 2.32
28
TO
1
Maximum Bhp = (Fan RPM / 1666)3
59
.25 kW
32
1/3 hp
80% WOV
45
34
Minimum Motor
Starting hp
15
7
EF
TO
215T
70% WOV
8
Static Pressure (in. wg)
Maximum Motor
Frame Size
Static Pressure (Pa x 100)
20
TH
EL
Specification Data
6
T
NO
1
2
3
4
5
6
7
8
Volume (cfm x 1000)
Imperial data — Metric data
0
2
4
6
8
10
12
3
Volume (m /hr x 1000)
Performance Data
STATIC PRESSURE (inches wg)
CFM
OV
0.5
1
2
3
4
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
2500
1077
1315
0.42
1471
0.64
1790
1.23
2082
1.91
2800
1206
1436
0.53
1575
0.77
1864
1.38
2131
3100
1336
1559
0.65
1687
0.92
1948
1.54
2201
3400
1465
1684
0.79
1805
1.10
2034
1.72
3700
1594
1810
0.96
1926
1.30
2137
1.95
4000
1724
1938
1.15
2047
1.52
2242
4300
1853
2067
1.37
2170
1.76
4600
1982
2197
1.61
2294
4900
2112
2328
1.89
2420
5200
2241
2460
2.20
5500
2370
2592
5800
2500
2724
5
RPM
BHP
2.09
2392
2.88
2.29
2435
2275
2.51
2358
2.75
2.21
2443
2353
2.50
2.04
2471
2.34
2590
2546
2.67
2.55
2673
2.93
2802
6
7
RPM
BHP
RPM
BHP
3.11
2670
3.99
2884
4.93
2500
3.36
2713
4.28
2926
2570
3.64
2771
4.59
2968
3.01
2647
3.94
2841
4.92
2538
3.31
2730
4.26
2913
2.84
2641
3.67
2816
4.61
3.22
2746
4.05
2908
5.01
2710
3.64
2856
4.49
3011
3.04
2831
4.07
2973
4.99
3.45
2953
4.53
3092
5.53
8
RPM
BHP
RPM
BHP
5.25
3122
6.28
5.59
3164
3023
5.96
3207
6.66
3347
7.76
7.05
3389
5.29
3093
6.36
8.20
3261
7.48
3431
8.65
2995
5.67
3164
3080
6.09
3243
6.78
3331
7.94
7.24
3402
5.47
3165
6.53
3326
7.72
8.43
3115
5.96
3259
7.04
3411
8.23
3221
6.50
3362
7.61
Shaded values show where Class I fan selections are more efficient than Class II.
Inlet Sound Power, LWi [dB ref 10-12 watts]
RPM
1000
1400
2000
2700
3445
% WOV
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
1
64
62
61
62
67
66
67
69
71
67
71
75
78
79
81
81
79
75
79
81
2
70
66
62
63
69
65
66
67
73
69
71
74
78
74
78
80
82
79
83
85
3
70
67
63
63
73
71
68
69
78
76
74
76
79
76
77
79
84
81
82
85
4
72
66
62
62
74
72
68
67
77
75
74
74
85
85
82
82
89
85
82
86
5
66
63
61
60
71
68
66
65
77
74
72
72
85
84
82
81
90
87
84
85
6
65
60
58
58
72
67
65
63
75
73
71
71
83
80
78
78
88
85
83
82
7
55
52
51
51
64
61
58
57
79
70
68
67
87
77
75
74
91
83
81
80
Outlet Sound Power, LWo [dB ref 10-12 watts]
8
48
43
42
41
56
53
51
52
66
62
61
61
77
71
70
70
87
78
77
77
LWiA
73
68
65
65
78
75
71
71
84
79
77
77
91
88
85
85
96
91
89
90
RPM
1000
1400
2000
2700
3445
% WOV
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
1
76
75
75
75
80
78
79
79
90
88
87
89
87
85
88
89
91
89
92
93
2
75
72
72
71
76
74
75
75
81
78
82
83
85
85
89
90
90
92
94
94
3
69
67
67
67
74
71
71
71
81
77
78
79
85
83
87
87
91
91
93
93
4
72
67
64
64
76
72
70
70
83
79
77
78
88
83
82
83
93
89
87
89
5
70
68
66
65
76
74
72
72
82
80
78
78
90
88
86
86
95
92
90
90
6
67
62
60
60
73
69
67
67
78
76
74
73
86
83
81
80
93
89
87
87
7
55
53
53
52
66
62
60
60
79
72
69
69
86
79
77
77
92
86
84
83
8
47
44
44
44
56
52
52
52
66
65
63
64
78
72
71
72
89
80
79
78
LWoA
74
71
69
68
80
77
75
75
87
84
82
82
94
90
89
89
100
96
94
94
Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not
include the effects of appurtenances (accessories).
The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA Standard 301. Values shown are for inlet LWi , LWi A and outlet LWo ,
LWo A sound power levels for installation type B: Free inlet, Ducted outlet. Ratings for inlet sound do not include the effects of duct end correction. Ratings for outlet
sound include the effects of duct end correction. The A-weighted sound power ratings shown have been calculated per AMCA Standard 301. The AMCA Certified
Ratings Seal applies to LWi A and LWo A values only.
23
QEI-16 Class I & QEI-L
Performance Data
7½
5
QEI-L
QEI
1895
2483
50% WOV
RPM
BHP
% WOV
3
Density 0.075 lb/ft
3
Density 1.2 kg/m
16
60% WOV
6
14
Specification Data
8
6
24
4
3
2
1½
¾
0
TO
3
0
0
0
71
20
DO
T
NO
90% WOV
15
87
0
LE
SE
1
00
95
126
CT
1
80% WOV
23
18
TH
E
4
2
83
CU
RV
E
10
3
YS
TE
M
12
HIS
S
Maximum
QEI-L
184T
Motor
QEI
213T
Frame Size
Minimum Motor
1/3 hp
.25 kW
Starting hp
Wheel Diameter
20 in.
508 mm
Approximate Weight QEI-L 160 lbs. 73 kg.
(Less Motor & Drives) QEI 220 lbs. 100 kg.
Maximum Bhp = (Fan RPM / 1387)3
Outlet Velocity (FPM) = CFM / 2.79
Tip Speed (FPM) = Fan RPM x 5.24
% WOV = (CFM x 100) / (Fan RPM x 3.36)
Imperial data — Metric data
LE
FT
OF
T
Static Pressure (Pa x 100)
70% WOV
5
Static Pressure (in. wg)
Maximum
Fan RPM
961
2
2
3
4
5
Volume (cfm x 1000)
4
6
6
8
10
7
8
12
9
14
3
Volume (m /hr x 1000)
Performance Data
STATIC PRESSURE (inches wg)
CFM
OV
0.25
0.5
1
1.5
2
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
2.5
RPM
BHP
3
3.5
RPM
BHP
RPM
BHP
4
RPM
BHP
RPM
BHP
2400
860
837
0.19
951
0.31
1169
0.59
1362
0.94
2800
1003
939
0.25
1039
0.39
1230
0.69
1411
1.05
1576
1.45
3200
1146
1046
0.33
1134
0.48
1307
0.81
1471
1.18
1625
1.60
1770
2.06
1904
2.54
3600
1290
1155
0.43
1235
0.59
1389
0.95
1538
1.33
1684
1.77
1820
2.25
1950
2.76
2073
3.29
2188
3.85
4000
1433
1266
0.55
1338
0.72
1479
1.11
1616
1.52
1747
1.96
1879
2.46
2002
2.99
2119
3.55
2233
4.13
4400
1577
1378
0.69
1445
0.88
1573
1.29
1700
1.73
1824
2.20
1940
2.69
2062
3.25
2174
3.83
2280
4.43
4800
1720
1492
0.85
1554
1.06
1673
1.50
1789
1.97
1901
2.46
2016
2.98
2121
3.52
2234
4.13
2338
4.76
5200
1863
1607
1.05
1664
1.27
1774
1.74
1880
2.24
1989
2.76
2093
3.30
2198
3.87
2294
4.46
2399
5.11
5600
2007
1722
1.27
1774
1.51
1878
2.01
1979
2.54
2078
3.09
2177
3.65
2274
4.25
2371
4.86
2461
5.49
6000
2150
1837
1.52
1886
1.77
1984
2.31
2080
2.87
2170
3.45
2265
4.04
2355
4.66
2447
5.29
6400
2293
1954
1.81
1999
2.08
2092
2.64
2181
3.23
2269
3.84
2355
4.47
2443
5.11
6800
2437
2070
2.14
2113
2.42
2201
3.01
2284
3.63
2369
4.27
2449
4.93
Inlet Sound Power, LWi [dB ref 10-12 watts]
RPM
600
900
1250
1750
2483
% WOV
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
1
65
64
62
62
65
64
63
66
71
69
68
69
73
69
75
80
80
80
78
81
2
62
61
60
60
67
64
63
65
78
78
71
73
75
76
77
80
80
75
77
80
3
60
59
57
57
68
65
63
63
73
70
68
69
81
76
77
77
88
84
80
82
4
57
55
53
53
65
62
60
60
72
68
66
65
80
77
75
75
88
85
82
81
5
57
55
54
54
61
58
57
57
69
65
65
64
77
73
71
71
86
81
79
78
6
52
52
52
52
62
56
55
55
67
62
61
60
75
71
70
70
83
79
77
77
7
47
47
47
47
51
50
49
49
67
57
57
55
75
66
66
66
81
74
74
74
Outlet Sound Power, LWo [dB ref 10-12 watts]
8
34
35
35
35
43
41
41
41
51
49
50
50
62
59
60
60
84
69
70
70
LWiA
61
59
59
58
68
64
63
62
75
71
69
69
83
79
77
77
92
87
84
84
RPM
600
900
1250
1750
2483
% WOV
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
1
75
70
71
72
74
76
76
77
80
78
77
79
82
79
83
86
91
88
88
90
2
66
65
64
64
73
73
72
73
80
75
75
76
82
78
80
82
86
84
88
89
3
60
60
59
59
67
65
64
65
74
72
72
72
81
77
77
79
88
82
85
86
4
59
58
57
57
68
66
65
65
74
71
69
69
83
79
77
77
90
85
83
84
5
60
58
58
57
65
63
62
62
72
70
68
68
81
78
76
75
90
87
84
84
6
55
55
55
55
63
60
59
59
70
66
65
65
78
74
73
72
87
84
81
81
7
51
51
51
51
55
55
54
54
68
61
60
60
76
69
68
68
83
78
77
77
8
39
39
40
40
46
46
46
46
54
54
55
55
65
62
62
63
85
72
72
72
LWoA
64
62
62
62
70
68
67
67
77
74
73
73
86
82
80
80
94
90
88
88
Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not
include the effects of appurtenances (accessories).
The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA Standard 301. Values shown are for inlet LWi , LWi A and outlet LWo ,
LWo A sound power levels for installation type B: Free inlet, Ducted outlet. Ratings for inlet sound do not include the effects of duct end correction. Ratings for outlet
sound include the effects of duct end correction. The A-weighted sound power ratings shown have been calculated per AMCA Standard 301. The AMCA Certified
Ratings Seal applies to LWi A and LWo A values only.
24
QEI-16 Class II
Performance Data
12
Maximum Fan RPM
11
3145
25
20 in.
508 mm
240 lbs.
109 kg.
10
CU
RVE
7
6
3
5
4
2
Maximum Bhp = (Fan RPM / 1430)
1
5
Outlet Velocity (FPM) = CFM / 2.79
2
1
Tip Speed (FPM) = Fan RPM x 5.24
DO
0
0
0
% WOV = (CFM x 100) / (Fan RPM x 2.89)
80% WOV
24
44
T
NO
62
18
01
S
14
30
10
9
8
7
6
5
4
3
2
1
90% WOV
20
TO
3
3
EL
EC
T
Approximate Weight
(Less Motor & Drives)
15
5
SY
ST
EM
Wheel Diameter
8
45
.25 kW
20
31
1/3 hp
70% WOV
9
97
27
Minimum Motor
Starting hp
7½
TH
EL
EF
TO
FT
H IS
215T
RPM
BHP
% WOV
3
Density 0.075 lb/ft
3
Density 1.2 kg/m
50% WOV
60% WOV
10
Static Pressure (in. wg)
Maximum Motor
Frame Size
Static Pressure (Pa x 100)
Specification Data
15
10
Volume (cfm x 1000)
Imperial data — Metric data
0
14
12
10
8
6
4
2
16
3
Volume (m /hr x 1000)
Performance Data
STATIC PRESSURE (inches wg)
CFM
OV
0.5
1
2
3
4
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
5
RPM
BHP
6
RPM
BHP
7
RPM
BHP
8
RPM
BHP
RPM
BHP
3000
1075
1199
0.50
1342
0.77
1633
1.48
1900
2.29
3300
1182
1291
0.61
1421
0.89
1688
1.62
1934
2.47
2176
3.41
3600
1290
1384
0.73
1503
1.03
1750
1.78
1987
2.66
2209
3.63
2424
4.68
3900
1397
1478
0.86
1592
1.20
1816
1.95
2041
2.88
2249
3.88
2456
4.96
2650
6.11
4200
1505
1574
1.01
1683
1.39
1887
2.16
2100
3.10
2302
4.14
2488
5.25
2682
6.44
2861
7.68
4500
1612
1670
1.18
1774
1.61
1965
2.39
2163
3.35
2356
4.42
2539
5.57
2715
6.78
2893
8.07
3060
9.40
4800
1720
1767
1.38
1867
1.83
2045
2.65
2229
3.61
2415
4.73
2592
5.91
2758
7.15
2926
8.46
3092
9.84
5100
1827
1865
1.59
1960
2.06
2128
2.94
2299
3.91
2478
5.05
2646
6.27
2811
7.55
2964
8.88
3124
10.3
5400
1935
1964
1.83
2054
2.33
2217
3.27
2377
4.26
2543
5.39
2707
6.65
2865
7.97
3017
9.34
5700
2043
2063
2.10
2149
2.62
2307
3.63
2457
4.63
2608
5.76
2770
7.05
2920
8.41
3071
9.82
6000
2150
2163
2.39
2245
2.93
2398
4.02
2537
5.03
2684
6.19
2835
7.48
2983
8.87
3125
10.3
6300
2258
2263
2.71
2341
3.27
2489
4.45
2623
5.48
2762
6.66
2900
7.93
3046
9.36
Shaded values show where Class I fan selections are more efficient than Class II.
Inlet Sound Power, LWi [dB ref 10-12 watts]
RPM
900
1250
1750
2475
3145
% WOV
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
1
66
63
62
63
68
66
67
69
71
67
71
74
79
80
82
82
81
77
81
83
2
71
67
63
64
70
67
66
68
74
70
72
74
79
75
79
81
84
80
84
86
3
71
67
63
63
73
71
68
69
78
77
74
76
81
78
78
80
85
81
83
86
4
72
66
63
62
74
72
68
67
77
74
73
74
86
86
83
83
91
86
83
87
5
66
63
61
60
71
69
66
65
77
73
72
71
86
84
82
82
91
88
85
85
6
64
59
57
57
71
67
64
63
76
72
70
70
84
80
78
78
89
85
83
83
7
54
51
50
50
63
60
57
57
77
68
66
65
86
77
75
74
92
83
81
80
Outlet Sound Power, LWo [dB ref 10-12 watts]
8
47
42
41
40
55
52
51
51
63
61
60
60
77
71
70
70
87
78
77
77
LWiA
72
68
65
65
77
74
71
70
83
79
77
77
92
88
86
86
97
92
90
90
RPM
900
1250
1750
2475
3145
% WOV
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
1
77
75
75
75
80
78
79
78
88
86
86
88
88
86
89
90
92
90
93
94
2
76
73
73
72
76
74
74
75
81
78
81
82
86
86
90
91
91
93
95
95
3
70
67
67
67
75
71
71
71
82
77
78
79
86
84
87
87
92
91
93
94
4
72
67
65
64
77
73
71
70
83
79
77
78
89
84
83
84
94
90
88
90
5
70
67
65
65
76
73
72
71
81
79
77
77
91
88
86
86
96
93
91
91
6
66
61
60
59
72
68
66
66
78
75
73
72
87
83
81
81
93
90
88
87
7
55
52
52
52
64
60
59
59
76
70
68
68
86
79
77
77
93
86
84
83
8
47
43
43
43
54
51
51
51
63
63
62
62
78
72
71
72
90
80
79
79
LWoA
74
71
69
68
79
76
75
75
86
83
81
81
95
91
90
89
100
97
95
95
Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not
include the effects of appurtenances (accessories).
The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA Standard 301. Values shown are for inlet LWi , LWi A and outlet LWo ,
LWo A sound power levels for installation type B: Free inlet, Ducted outlet. Ratings for inlet sound do not include the effects of duct end correction. Ratings for outlet
sound include the effects of duct end correction. The A-weighted sound power ratings shown have been calculated per AMCA Standard 301. The AMCA Certified
Ratings Seal applies to LWi A and LWo A values only.
25
QEI-18 Class I & QEI-L
7
Performance Data
QEI-L
QEI
Maximum
Fan RPM
7
50% WOV
16
1723
2232
RPM
BHP
% WOV
Density 0.075 lb/ft3
Density 1.2 kg/m3
60% WOV
5
6
70% WOV
14
8
6
80% WOV
CU
RVE
10
5
3
4
22
32
20
SY
STE
M
12
3
TH
EL
EF
TO
FT
HIS
Maximum
QEI-L
215T
Motor
QEI
215T
Frame Size
Minimum Motor
1/3 hp
.25 kW
Starting hp
Wheel Diameter
22.5 in.
565 mm
Approximate Weight QEI-L 190 lbs. 87 kg.
(Less Motor & Drives) QEI 260 lbs. 118 kg.
Maximum Bhp = (Fan RPM / 1199)3
Outlet Velocity (FPM) = CFM / 3.45
Tip Speed (FPM) = Fan RPM x 5.83
% WOV = (CFM x 100) / (Fan RPM x 4.50)
Imperial data — Metric data
Static Pressure (in. wg)
Static Pressure (Pa x 100)
Specification Data
1½
2
¾
17
23
90% WOV
13
72
TO
4
50
0
0
108
LE
CT
1
2
3
DO
T
NO
0
0
SE
9
831
2
2
4
6
Volume (cfm x 1000)
4
6
8
10
8
12
14
10
16
12
18
20
3
Volume (m /hr x 1000)
Performance Data
STATIC PRESSURE (inches wg)
CFM
OV
0.25
0.5
1
1.5
RPM
BHP
RPM
BHP
RPM
BHP
2
2.5
RPM
BHP
RPM
BHP
3
RPM
BHP
3.5
4
RPM
BHP
RPM
BHP
RPM
BHP
2600
753
697
0.17
814
0.30
1026
0.62
3100
898
788
0.23
889
0.37
1080
0.72
1250
1.12
1407
1.57
3600
1043
886
0.31
972
0.46
1142
0.84
1300
1.26
1445
1.73
1583
2.24
4100
1188
986
0.42
1062
0.58
1213
0.97
1358
1.43
1494
1.92
1622
2.45
1746
3.03
1861
3.63
4600
1333
1088
0.54
1156
0.72
1293
1.13
1425
1.61
1552
2.14
1672
2.70
1785
3.28
1899
3.91
2006
4.57
5100
1478
1192
0.69
1254
0.89
1376
1.32
1498
1.81
1616
2.37
1730
2.96
1839
3.58
1940
4.22
2044
4.91
5600
1623
1298
0.87
1355
1.09
1466
1.55
1578
2.06
1686
2.62
1793
3.25
1897
3.91
1997
4.58
2090
5.28
6100
1768
1405
1.08
1456
1.32
1558
1.81
1660
2.33
1763
2.92
1862
3.56
1959
4.25
2055
4.96
2148
5.69
6600
1913
1513
1.33
1558
1.58
1653
2.11
1748
2.66
1843
3.26
1936
3.91
2029
4.62
2118
5.37
2206
6.14
7100
2057
1620
1.62
1662
1.88
1752
2.44
1840
3.02
1926
3.63
2016
4.31
2100
5.02
2187
5.79
7600
2202
1729
1.94
1768
2.23
1851
2.82
1932
3.43
2015
4.07
2097
4.75
2180
5.49
8100
2347
1837
2.31
1875
2.61
1952
3.24
2028
3.88
2106
4.56
2182
5.25
Inlet Sound Power, LWi [dB ref 10-12 watts]
RPM
550
800
1100
1600
2232
% WOV
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
1
65
61
60
62
66
62
61
64
70
64
66
69
77
76
78
79
80
74
80
83
2
68
67
67
67
70
66
64
64
78
78
73
73
80
75
77
78
83
78
79
82
3
68
68
68
67
69
68
66
66
73
73
70
70
87
80
83
82
92
87
82
83
4
64
64
64
64
64
62
60
59
72
69
67
66
82
78
75
76
89
85
82
82
5
57
56
56
56
59
58
55
55
67
64
62
61
78
74
71
70
87
85
82
81
6
52
52
52
51
61
56
55
54
68
62
61
61
75
72
70
69
84
81
78
77
7
49
48
48
48
49
49
49
48
66
57
57
56
77
67
66
66
81
76
74
74
Outlet Sound Power, LWo [dB ref 10-12 watts]
8
41
40
39
39
41
40
40
40
53
51
52
52
64
61
62
62
83
71
70
71
LWiA
65
65
65
64
67
65
63
63
75
71
69
69
85
80
79
78
92
89
86
85
RPM
550
800
1100
1600
2232
% WOV
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
1
74
72
69
69
74
71
72
72
77
73
75
77
82
78
82
86
88
83
88
93
2
74
73
72
72
75
73
70
70
84
80
77
77
83
83
82
84
87
83
89
92
3
67
68
67
67
68
66
66
65
75
70
69
70
84
80
77
78
91
85
83
85
4
66
68
67
67
67
65
63
63
74
71
69
69
84
80
78
78
93
89
87
86
5
63
62
62
62
64
63
62
61
72
69
67
66
83
80
77
76
92
90
88
87
6
55
56
56
56
62
58
57
57
68
64
63
62
77
75
74
73
87
85
82
81
7
53
56
56
57
54
54
54
54
65
59
58
58
75
70
69
69
82
79
77
76
8
45
50
51
52
43
43
43
43
51
50
50
51
64
64
64
64
82
72
71
72
LWoA
68
68
68
68
70
68
66
66
77
74
72
71
87
83
81
81
95
93
91
90
Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not
include the effects of appurtenances (accessories).
The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA Standard 301. Values shown are for inlet LWi , LWi A and outlet LWo ,
LWo A sound power levels for installation type B: Free inlet, Ducted outlet. Ratings for inlet sound do not include the effects of duct end correction. Ratings for outlet
sound include the effects of duct end correction. The A-weighted sound power ratings shown have been calculated per AMCA Standard 301. The AMCA Certified
Ratings Seal applies to LWi A and LWo A values only.
26
QEI-18 Class II
Performance Data
12
Maximum Fan RPM
11
15
10
2777
RPM
BHP
% WOV
3
Density 0.075 lb/ft
3
Density 1.2 kg/m
50% WOV
60% WOV
25
Specification Data
10
141 kg.
UR
VE
YS
TE
MC
310 lbs.
10
HIS
S
Approximate Weight
(Less Motor & Drives)
15
6
5
3
4
2
Maximum Bhp = (Fan RPM / 1219)
1
5
Outlet Velocity (FPM) = CFM / 3.45
2
1
Tip Speed (FPM) = Fan RPM x 5.83
0
0
0
% WOV = (CFM x 100) / (Fan RPM x 3.80)
20
83
DO
1
90% WOV
17
SE
LE
CT
3
3
80% WOV
TH
EL
EF
TO
FT
565 mm
TO
22.25 in.
5
24
Wheel Diameter
7
26
.25 kW
8
77
1/3 hp
20
70% WOV
27
Minimum Motor
Starting hp
Static Pressure (in. wg)
254T
9
85
23
Static Pressure (Pa x 100)
7½
Maximum Motor
Frame Size
57
15
35
T
NO
121
9
2
3
10
9
8
7
6
5
4
11
Volume (cfm x 1000)
Imperial data — Metric data
15
10
5
0
3
Volume (m /hr x 1000)
Performance Data
STATIC PRESSURE (inches wg)
CFM
OV
0.5
1
2
3
4
5
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
6
7
RPM
BHP
RPM
BHP
8
RPM
BHP
RPM
BHP
3800
1101
1124
0.64
1239
0.97
1467
1.74
1690
2.65
1900
3.67
4200
1217
1219
0.79
1326
1.14
1538
1.98
1738
2.88
1934
3.94
2120
5.09
2290
6.31
4600
1333
1315
0.96
1414
1.34
1609
2.25
1787
3.15
1977
4.24
2154
5.42
2323
6.69
2478
8.02
5000
1449
1413
1.16
1503
1.56
1682
2.50
1858
3.50
2024
4.56
2193
5.78
2356
7.09
2511
8.47
2656
9.91
5400
1565
1511
1.40
1595
1.82
1758
2.77
1929
3.89
2079
4.94
2241
6.18
2394
7.51
2545
8.93
2689
10.4
5800
1681
1611
1.66
1690
2.11
1844
3.11
2001
4.29
2150
5.42
2289
6.60
2441
7.98
2582
9.42
2723
10.9
6200
1797
1711
1.96
1786
2.44
1932
3.48
2075
4.66
2221
5.94
2354
7.14
2489
8.48
2629
9.97
2760
11.5
6600
1913
1812
2.29
1883
2.81
2020
3.89
2150
5.07
2293
6.50
2424
7.76
2544
9.06
2676
10.5
7000
2028
1913
2.66
1981
3.21
2110
4.34
2236
5.57
2366
6.98
2495
8.42
2615
9.77
2726
11.2
7400
2144
2015
3.07
2079
3.66
2200
4.83
2323
6.12
2440
7.49
2568
9.11
2686
10.5
7800
2260
2117
3.53
2178
4.16
2295
5.38
2411
6.70
2521
8.10
2641
9.71
2757
11.3
8200
2376
2219
4.03
2277
4.70
2390
5.98
2500
7.34
2608
8.78
2715
10.4
Shaded values show where Class I fan selections are more efficient than Class II.
Inlet Sound Power, LWi [dB ref 10-12 watts]
RPM
800
1100
1600
2200
2777
% WOV
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
1
66
63
62
77
70
62
63
66
78
71
73
77
81
75
79
83
85
80
84
87
2
75
71
69
73
78
73
72
72
79
76
76
77
84
78
81
83
88
83
86
89
3
67
64
63
69
72
68
66
67
82
77
74
76
89
83
84
84
89
85
85
89
4
66
63
61
65
72
67
66
65
80
75
73
73
88
83
81
81
93
89
88
88
5
63
62
62
62
68
66
65
64
78
74
72
72
87
82
79
78
93
90
87
86
6
65
62
63
62
72
66
66
65
76
73
72
71
84
80
78
77
90
87
85
84
7
51
51
53
50
60
57
57
56
80
67
67
66
87
76
75
74
91
82
80
80
Outlet Sound Power, LWo [dB ref 10-12 watts]
8
43
41
42
41
51
48
49
49
64
60
61
61
78
69
71
70
87
76
76
76
LWiA
70
67
67
68
76
71
71
70
85
79
77
77
93
87
85
85
98
93
91
91
RPM
800
1100
1600
2200
2777
% WOV
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
1
73
70
70
70
78
73
75
77
87
84
85
86
89
85
89
91
93
88
94
96
2
79
76
74
75
83
77
75
77
86
80
80
82
89
86
88
89
94
91
94
95
3
66
63
63
63
74
69
68
70
83
77
77
78
91
85
86
88
93
89
92
92
4
69
67
65
65
76
73
71
71
85
81
79
79
92
88
86
87
96
92
89
91
5
68
66
66
65
74
72
71
70
84
80
78
77
91
89
87
86
97
94
92
92
6
66
63
63
62
72
68
68
68
78
75
74
74
86
83
82
81
93
90
88
88
7
54
53
53
53
63
60
60
60
79
70
70
69
86
79
78
77
91
86
84
84
8
45
46
46
47
53
50
52
53
64
61
62
62
80
73
73
73
88
79
79
79
LWoA
72
70
70
69
79
76
74
75
88
84
82
82
96
92
90
90
101
97
95
96
Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not
include the effects of appurtenances (accessories).
The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA Standard 301. Values shown are for inlet LWi , LWi A and outlet LWo ,
LWo A sound power levels for installation type B: Free inlet, Ducted outlet. Ratings for inlet sound do not include the effects of duct end correction. Ratings for outlet
sound include the effects of duct end correction. The A-weighted sound power ratings shown have been calculated per AMCA Standard 301. The AMCA Certified
Ratings Seal applies to LWi A and LWo A values only.
27
QEI-20 Class I & QEI-L
7
Performance Data
7½
QEI-L
QEI
1571
2027
10
RPM
BHP
% WOV
3
Density 0.075 lb/ft
Density 1.2 kg/m3
50% WOV
60% WOV
6
14
Specification Data
70% WOV
8
6
80% WOV
4
3
2
3
2
1
1
0
TO
4
2
20
UR
VE
10
5
FT
HIS
SY
ST
EM
C
12
TH
EL
EF
TO
Maximum
QEI-L
215T
Motor
QEI
215T
Frame Size
Minimum Motor
1/3 hp
.25 kW
Starting hp
Wheel Diameter
24.5 in.
622 mm
Approximate Weight QEI-L 230 lbs. 105 kg.
(Less Motor & Drives) QEI 310 lbs. 141 kg.
Maximum Bhp = (Fan RPM / 1021)3
Outlet Velocity (FPM) = CFM / 4.14
Tip Speed (FPM) = Fan RPM x 6.41
% WOV = (CFM x 100) / (Fan RPM x 6.01)
Imperial data — Metric data
Static Pressure (in. wg)
Static Pressure (Pa x 100)
5
½
0
0
LE
CT
Maximum
Fan RPM
16
DO
N
OT
17
46
15
71
14
90% WOV
73
12
87
102
1
SE
818
2
4
0
27
6
8
Volume (cfm x 1000)
5
10
10
12
15
14
20
3
Volume (m /hr x 1000)
Performance Data
STATIC PRESSURE (inches wg)
CFM
OV
0.25
0.5
1
1.5
RPM
BHP
RPM
BHP
RPM
BHP
2
RPM
BHP
2.5
3
RPM
BHP
RPM
BHP
3.5
4
RPM
BHP
RPM
BHP
RPM
BHP
3000
724
613
0.19
724
0.35
923
0.73
3700
893
708
0.27
801
0.44
975
0.86
1132
1.34
4400
1062
810
0.39
887
0.57
1040
1.02
1183
1.54
1314
2.11
1440
2.73
5100
1231
915
0.53
982
0.74
1116
1.21
1245
1.78
1368
2.38
1480
3.03
1593
3.73
1697
4.47
5800
1400
1023
0.72
1082
0.95
1201
1.45
1317
2.03
1428
2.70
1538
3.38
1637
4.11
1738
4.88
1835
5.69
6500
1570
1133
0.95
1187
1.20
1292
1.74
1398
2.34
1501
3.03
1599
3.78
1697
4.54
1789
5.34
1875
6.17
7200
1739
1245
1.23
1292
1.50
1388
2.09
1483
2.71
1577
3.41
1671
4.19
1759
5.02
1849
5.86
1934
6.74
7900
1908
1357
1.56
1400
1.86
1486
2.49
1574
3.15
1662
3.88
1746
4.66
1832
5.52
1913
6.42
1994
7.35
8600
2077
1470
1.96
1508
2.28
1590
2.95
1669
3.66
1748
4.40
1830
5.22
1907
6.07
1985
7.02
9300
2246
1584
2.41
1619
2.76
1694
3.48
1766
4.23
1842
5.01
1915
5.84
1990
6.74
10000
2415
1698
2.94
1731
3.32
1800
4.08
1868
4.88
1937
5.71
2005
6.56
10700
2584
1812
3.55
1843
3.95
1907
4.76
1972
5.60
Inlet Sound Power, LWi [dB ref 10-12 watts]
RPM
500
700
1000
1450
2027
% WOV
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
1
66
63
62
64
66
62
61
63
72
67
68
71
79
77
79
80
82
76
81
84
2
69
69
69
68
70
67
65
65
79
79
74
74
82
77
79
80
85
80
81
83
3
68
68
68
68
68
67
65
65
74
73
70
70
87
81
82
82
93
88
83
84
4
64
64
64
64
63
62
59
59
72
69
67
66
82
78
76
76
90
86
83
83
5
57
56
56
56
60
57
55
55
68
65
63
62
78
75
71
71
88
85
82
81
6
53
52
52
52
59
55
54
53
69
62
61
61
76
72
70
69
84
81
78
77
7
49
48
48
48
48
48
47
47
65
57
57
57
76
67
66
66
82
76
74
74
Outlet Sound Power, LWo [dB ref 10-12 watts]
8
40
40
39
39
40
38
39
38
52
51
52
52
63
61
63
63
84
71
71
71
LWiA
65
65
65
65
66
64
62
62
75
72
70
69
85
80
79
79
93
89
86
86
RPM
500
700
1000
1450
2027
% WOV
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
1
75
73
71
70
74
72
71
71
79
75
76
78
83
79
83
86
89
84
89
93
2
74
73
72
72
74
72
69
69
84
80
77
77
84
82
81
83
89
84
89
92
3
68
68
68
68
68
66
65
65
75
71
70
70
85
81
78
79
92
86
85
86
4
67
68
68
67
66
64
63
62
75
72
70
69
85
81
79
79
93
90
88
87
5
62
62
62
62
64
62
61
61
72
70
67
67
83
80
78
76
92
90
88
87
6
56
56
57
57
60
58
57
56
68
64
63
63
77
75
74
73
87
85
82
81
7
53
56
56
57
52
52
52
52
64
58
58
58
74
69
69
69
83
79
77
76
8
45
50
51
52
41
41
41
41
50
50
50
51
63
63
64
64
83
72
72
72
LWoA
68
69
68
68
69
67
66
65
77
74
72
72
87
84
82
81
96
93
91
90
Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not
include the effects of appurtenances (accessories).
The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA Standard 301. Values shown are for inlet LWi , LWi A and outlet LWo ,
LWo A sound power levels for installation type B: Free inlet, Ducted outlet. Ratings for inlet sound do not include the effects of duct end correction. Ratings for outlet
sound include the effects of duct end correction. The A-weighted sound power ratings shown have been calculated per AMCA Standard 301. The AMCA Certified
Ratings Seal applies to LWi A and LWo A values only.
28
QEI-20 Class II
10
Performance Data
15
10
Maximum Fan RPM
2517
RPM
BHP
% WOV
3
Density 0.075 lb/ft
3
Density 1.2 kg/m
50% WOV
9
60% WOV
7½
Approximate Weight
(Less Motor & Drives)
163 kg.
360 lbs.
10
YST
EM
CU
RVE
622 mm
5
6
5
3
4
3
1½
5
SE
LE
CT
TO
3
Maximum Bhp = (Fan RPM / 1038)
2
Outlet Velocity (FPM) = CFM / 4.14
1
Tip Speed (FPM) = Fan RPM x 6.41
DO
0
0
0
% WOV = (CFM x 100) / (Fan RPM x 5.07)
80% WOV
HIS
S
24.5 in.
Static Pressure (in. wg)
Wheel Diameter
15
35
.25 kW
1
30
20
1/3 hp
22
Minimum Motor
Starting hp
70% WOV
7
17
254T
8
25
Maximum Motor
Frame Size
Static Pressure (Pa x 100)
20
TH
EL
EF
TO
FT
Specification Data
17
74
90% WOV
14
97
118
8
T
NO
7
6
5
4
3
2
9
8
10
12
11
13
Volume (cfm x 1000)
Imperial data — Metric data
20
15
10
5
0
3
Volume (m /hr x 1000)
Performance Data
STATIC PRESSURE (inches wg)
CFM
OV
0.5
1
2
3
4
5
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
6
RPM
BHP
7
8
RPM
BHP
RPM
BHP
RPM
BHP
4500
1076
1002
0.74
1110
1.14
1319
2.05
1526
3.15
1719
4.38
5000
1196
1090
0.92
1189
1.34
1384
2.34
1570
3.44
1750
4.71
1920
6.10
5500
1315
1181
1.13
1271
1.58
1451
2.67
1615
3.75
1788
5.08
1951
6.51
2105
8.04
2246
9.65
6000
1435
1272
1.38
1355
1.86
1519
2.99
1679
4.19
1833
5.48
1986
6.95
2136
8.53
2277
10.2
2408
11.9
6500
1555
1364
1.66
1440
2.18
1589
3.32
1745
4.67
1882
5.94
2031
7.44
2170
9.05
2308
10.8
2439
12.6
7000
1674
1457
1.99
1529
2.54
1670
3.74
1813
5.18
1948
6.53
2075
7.96
2214
9.64
2342
11.4
2471
13.2
7500
1794
1551
2.36
1619
2.95
1751
4.20
1882
5.64
2015
7.18
2135
8.64
2258
10.3
2386
12.1
2505
13.9
8000
1913
1645
2.77
1710
3.40
1834
4.72
1953
6.14
2082
7.88
2201
9.40
2310
11.0
2430
12.8
8500
2033
1740
3.24
1801
3.91
1918
5.28
2033
6.77
2151
8.48
2268
10.2
2376
11.9
2477
13.5
9000
2153
1835
3.75
1893
4.48
2003
5.90
2115
7.45
2220
9.12
2336
11.1
2443
12.8
9500
2272
1930
4.33
1986
5.10
2092
6.59
2197
8.20
2297
9.89
2404
11.8
2510
13.8
10000
2392
2026
4.96
2079
5.78
2181
7.34
2280
9.00
2378
10.7
2474
12.6
Shaded values show where Class I fan selections are more efficient than Class II.
Inlet Sound Power, LWi [dB ref 10-12 watts]
RPM
700
1000
1450
2000
2517
% WOV
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
1
68
65
64
76
72
64
65
68
79
73
75
78
82
76
81
84
88
82
86
89
2
74
70
68
72
80
75
74
74
80
77
77
78
86
80
83
84
89
85
87
90
3
67
64
62
68
73
69
67
68
82
77
75
77
91
85
85
85
90
86
85
90
4
66
63
61
65
72
68
67
66
81
76
73
74
89
84
81
82
94
90
89
89
5
64
62
62
62
70
67
66
65
79
75
72
72
87
83
80
79
94
91
87
87
6
62
60
61
60
71
65
65
65
77
73
72
71
85
80
78
78
90
87
85
85
7
49
49
51
48
60
56
57
56
79
67
67
67
87
76
75
75
92
82
80
80
Outlet Sound Power, LWo [dB ref 10-12 watts]
8
42
39
40
40
51
48
49
49
63
59
61
61
78
69
71
71
87
76
76
77
LWiA
69
66
66
68
76
72
71
71
85
79
78
78
93
87
86
85
99
94
92
92
RPM
700
1000
1450
2000
2517
% WOV
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
1
74
71
71
71
80
75
76
78
88
84
85
86
90
86
90
92
95
90
95
97
2
76
73
72
72
85
78
77
79
86
81
80
82
90
87
88
90
94
92
94
96
3
66
64
63
64
75
70
69
71
84
78
78
79
92
87
87
89
93
89
92
93
4
69
67
65
65
76
74
71
71
86
82
80
79
93
89
87
87
97
93
90
92
5
67
66
65
65
75
72
71
71
83
81
79
78
91
89
87
86
98
96
93
93
6
63
61
61
61
72
68
68
68
79
75
74
74
87
83
82
82
93
90
88
88
7
52
52
52
52
63
60
60
60
77
70
69
69
86
79
78
78
92
86
85
84
8
43
44
45
46
52
50
52
52
63
61
62
62
80
73
73
73
89
79
79
79
LWoA
71
70
69
69
79
76
75
75
88
84
83
82
96
92
90
90
102
98
96
96
Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not
include the effects of appurtenances (accessories).
The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA Standard 301. Values shown are for inlet LWi , LWi A and outlet LWo ,
LWo A sound power levels for installation type B: Free inlet, Ducted outlet. Ratings for inlet sound do not include the effects of duct end correction. Ratings for outlet
sound include the effects of duct end correction. The A-weighted sound power ratings shown have been calculated per AMCA Standard 301. The AMCA Certified
Ratings Seal applies to LWi A and LWo A values only.
29
QEI-22 Class I & QEI-L
7
Performance Data
10
QEI-L
QEI
Maximum
Fan RPM
16
1425
1839
RPM
BHP
% WOV
3
Density 0.075 lb/ft
Density 1.2 kg/m3
50% WOV
7½
6
60% WOV
14
Specification Data
6
18
39
CU
RV
E
4
3
3
2
2
4
0
TO
1
2
½
0
0
77
14
25
D
CT
LE
SE
T
O
ON
2
36
90% WOV
80
857
680
4
0
12
10
TH
E
1
80% WOV
16
SY
ST
EM
8
5
FT
HI
S
10
5
LE
FT
O
12
Static Pressure (in. wg)
Static Pressure (Pa x 100)
70% WOV
Maximum
QEI-L
215T
Motor
QEI
254T
Frame Size
Minimum Motor
1/3 hp
.25 kW
Starting hp
Wheel Diameter
27 in.
686 mm
Approximate Weight QEI-L 270 lbs. 123 kg.
(Less Motor & Drives) QEI 370 lbs. 168 kg.
Maximum Bhp = (Fan RPM / 857)3
Outlet Velocity (FPM) = CFM / 5.12
Tip Speed (FPM) = Fan RPM x 7.07
% WOV = (CFM x 100) / (Fan RPM x 8.60)
Imperial data — Metric data
5
6
8
10
Volume (cfm x 1000)
10
12
15
14
20
16
25
3
Volume (m /hr x 1000)
Performance Data
STATIC PRESSURE (inches wg)
CFM
OV
0.25
0.5
1
1.5
RPM
BHP
RPM
BHP
RPM
BHP
2
RPM
BHP
2.5
3
RPM
BHP
RPM
BHP
3.5
RPM
BHP
4
RPM
BHP
RPM
BHP
3900
762
564
0.25
662
0.44
837
0.93
4700
918
641
0.34
725
0.55
883
1.07
1023
1.68
5500
1075
723
0.45
796
0.69
935
1.25
1066
1.90
1184
2.61
1301
3.38
6300
1231
806
0.60
872
0.87
997
1.46
1116
2.14
1228
2.90
1329
3.72
1434
4.58
7100
1388
892
0.79
953
1.08
1065
1.72
1173
2.43
1277
3.22
1376
4.08
1466
4.99
1560
5.94
1650
6.93
7900
1544
979
1.02
1035
1.33
1137
2.01
1236
2.77
1332
3.60
1425
4.49
1515
5.44
1598
6.44
1678
7.47
8700
1700
1068
1.29
1118
1.62
1213
2.35
1305
3.15
1394
4.02
1480
4.94
1564
5.93
1646
6.97
1723
8.05
9500
1857
1156
1.61
1204
1.97
1293
2.75
1377
3.59
1458
4.49
1541
5.46
1619
6.48
1696
7.54
1772
8.67
10300
2013
1246
1.98
1290
2.37
1374
3.20
1451
4.08
1529
5.03
1603
6.03
1680
7.09
1751
8.19
1822
9.34
11100
2170
1335
2.41
1377
2.83
1456
3.70
1530
4.64
1602
5.63
1673
6.67
1742
7.76
1813
8.91
11900
2326
1426
2.90
1465
3.35
1539
4.27
1610
5.26
1676
6.29
1745
7.38
1809
8.51
12700
2482
1516
3.46
1554
3.94
1624
4.91
1691
5.95
1755
7.03
1818
8.16
Inlet Sound Power, LWi [dB ref 10-12 watts]
RPM
450
650
900
1300
1839
% WOV
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
1
68
67
66
67
70
67
67
68
73
69
70
72
76
72
74
78
81
79
80
84
2
69
68
67
68
75
75
74
73
79
76
73
74
89
91
83
83
86
82
82
84
3
64
62
60
60
70
68
65
65
78
77
74
74
85
83
79
79
99
95
87
86
4
60
59
58
58
67
64
62
62
74
71
68
67
83
79
76
75
94
92
87
86
5
59
57
56
55
64
61
59
58
71
68
66
65
81
78
74
73
91
87
84
82
6
59
59
58
58
65
61
60
60
72
66
63
62
78
75
71
69
88
84
81
79
7
52
52
52
52
54
54
53
53
61
58
56
55
79
69
65
64
88
80
76
75
Outlet Sound Power, LWo [dB ref 10-12 watts]
8
38
38
38
38
43
41
41
41
53
50
50
49
65
61
61
62
77
72
71
71
LWiA
65
64
63
63
70
68
66
66
78
74
72
71
87
83
79
78
97
93
89
87
RPM
450
650
900
1300
1839
% WOV
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
1
71
71
69
72
78
76
75
75
77
73
74
77
83
81
84
88
87
86
91
94
2
71
70
69
70
75
74
74
74
83
80
78
79
84
82
81
83
89
84
89
91
3
65
63
62
61
70
70
69
69
77
74
72
72
84
80
78
79
91
90
87
88
4
64
63
62
61
69
69
67
65
78
76
72
71
86
83
79
78
96
92
89
88
5
65
64
64
64
67
67
66
65
75
73
71
70
85
82
77
76
93
90
87
85
6
62
62
62
62
66
65
65
65
73
69
67
66
81
77
72
71
90
87
83
81
7
56
57
57
57
57
58
58
58
64
62
60
60
79
71
66
65
88
82
78
76
8
44
44
44
45
47
47
48
48
53
51
51
51
64
60
59
60
79
72
71
71
LWoA
69
68
68
68
72
72
71
71
80
78
75
74
89
85
81
81
98
94
91
90
Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not
include the effects of appurtenances (accessories).
The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA Standard 301. Values shown are for inlet LWi , LWi A and outlet LWo ,
LWo A sound power levels for installation type B: Free inlet, Ducted outlet. Ratings for inlet sound do not include the effects of duct end correction. Ratings for outlet
sound include the effects of duct end correction. The A-weighted sound power ratings shown have been calculated per AMCA Standard 301. The AMCA Certified
Ratings Seal applies to LWi A and LWo A values only.
30
QEI-22 Class II
10
Performance Data
15
Maximum Fan RPM
2265
20
10
60% WOV
70% WOV
420 lbs.
191 kg.
10
CU
RVE
EF
TO
FT
HIS
SY
STE
M
686 mm
4
2
17
00
5
SE
LE
CT
Maximum Bhp = (Fan RPM / 869)3
2
85
10
95
T
Outlet Velocity (FPM) = CFM / 5.12
90% WOV
14
TO
27 in.
Approximate Weight
(Less Motor & Drives)
5
41
Wheel Diameter
6
21
.25 kW
80% WOV
65
1/3 hp
15
71
18
Minimum Motor
Starting hp
7½
Static Pressure (in. wg)
256T
8
22
Maximum Motor
Frame Size
Static Pressure (Pa x 100)
20
TH
EL
Specification Data
RPM
BHP
% WOV
3
Density 0.075 lb/ft
3
Density 1.2 kg/m
Tip Speed (FPM) = Fan RPM x 7.07
DO
0
0
0
% WOV = (CFM x 100) / (Fan RPM x 7.17)
NO
12
10
8
6
4
2
18
16
14
Volume (cfm x 1000)
Imperial data — Metric data
0
30
25
20
15
10
5
3
Volume (m /hr x 1000)
Performance Data
STATIC PRESSURE (inches wg)
CFM
OV
0.5
1
2
3
4
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
5
RPM
BHP
6
RPM
BHP
7
RPM
BHP
8
RPM
BHP
RPM
BHP
5600
1093
882
0.81
982
1.29
1174
2.43
1360
3.80
6200
1210
956
1.00
1045
1.51
1222
2.69
1395
4.11
1564
5.70
6800
1328
1032
1.22
1115
1.75
1273
2.97
1434
4.43
1588
6.07
1746
7.86
7400
1445
1109
1.47
1185
2.03
1335
3.32
1480
4.81
1626
6.49
1762
8.32
1912
10.3
8000
1562
1187
1.76
1257
2.34
1396
3.71
1531
5.22
1666
6.94
1801
8.83
1925
10.8
2065
13.0
2195
15.2
8600
1679
1265
2.09
1331
2.71
1459
4.13
1588
5.69
1714
7.45
1840
9.37
1962
11.4
2078
13.6
2209
15.9
9200
1796
1345
2.46
1407
3.12
1528
4.60
1649
6.23
1764
8.00
1882
9.96
2001
12.1
2113
14.3
2222
16.6
9800
1914
1425
2.87
1483
3.58
1598
5.11
1711
6.81
1820
8.61
1932
10.6
2040
12.8
2152
15.0
2257
17.4
10400
2031
1505
3.33
1560
4.10
1668
5.68
1773
7.45
1881
9.32
1982
11.3
2088
13.5
2192
15.8
11000
2148
1586
3.84
1637
4.66
1740
6.29
1841
8.13
1942
10.1
2039
12.1
2138
14.3
2237
16.7
11600
2265
1667
4.40
1715
5.28
1813
6.96
1910
8.87
2005
10.9
2100
13.0
2189
15.2
12200
2382
1749
5.02
1794
5.96
1888
7.72
1980
9.66
2068
11.8
2161
13.9
2249
16.2
Shaded values show where Class I fan selections are more efficient than Class II.
Inlet Sound Power, LWi [dB ref 10-12 watts]
RPM
650
900
1300
1800
2265
% WOV
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
1
66
64
64
67
70
68
70
73
75
71
75
79
81
76
82
85
85
79
85
87
2
75
72
70
72
79
73
71
75
80
76
76
83
85
79
82
87
88
82
87
92
3
70
67
65
66
73
69
69
70
89
85
80
86
93
90
87
90
94
89
88
93
4
65
62
60
61
71
68
66
66
82
79
76
76
89
85
83
83
95
91
88
89
5
63
62
60
60
69
66
65
65
79
76
74
73
88
85
82
81
94
91
87
87
6
64
59
59
59
73
66
65
65
76
73
71
71
84
81
78
78
91
87
84
83
7
51
51
51
52
60
59
59
59
79
68
66
66
87
77
74
74
91
83
80
80
Outlet Sound Power, LWo [dB ref 10-12 watts]
8
43
41
41
41
52
49
50
50
63
60
61
61
78
69
70
70
89
76
77
77
LWiA
70
67
65
66
77
72
71
71
86
82
79
81
94
89
87
87
99
95
91
92
RPM
650
900
1300
1800
2265
% WOV
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
1
74
73
73
75
77
73
74
81
82
79
81
82
87
82
86
88
92
87
92
93
2
79
78
77
78
80
76
76
79
84
79
82
84
89
86
90
91
94
88
93
94
3
68
66
65
66
74
70
70
71
85
80
80
80
92
88
89
90
96
92
92
93
4
69
67
65
65
75
73
71
71
86
84
81
81
92
92
88
88
98
93
92
92
5
66
65
64
64
72
71
69
70
82
80
78
77
91
89
86
86
96
92
91
91
6
64
64
63
63
72
68
68
68
77
75
74
74
86
84
81
81
92
89
87
87
7
55
59
59
58
64
63
63
64
78
71
70
70
86
80
79
79
91
85
83
83
8
45
49
48
47
54
52
53
54
67
65
65
65
80
71
72
72
90
78
77
78
LWoA
72
71
70
70
78
76
74
75
88
85
83
83
95
93
91
91
101
96
95
95
Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not
include the effects of appurtenances (accessories).
The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA Standard 301. Values shown are for inlet LWi , LWi A and outlet LWo ,
LWo A sound power levels for installation type B: Free inlet, Ducted outlet. Ratings for inlet sound do not include the effects of duct end correction. Ratings for outlet
sound include the effects of duct end correction. The A-weighted sound power ratings shown have been calculated per AMCA Standard 301. The AMCA Certified
Ratings Seal applies to LWi A and LWo A values only.
31
QEI-24 Class I & QEI-L
7
Performance Data
15
10
1283
1655
60% WOV
6
14
3
CUR
VE
3
2
1½
1
2
T
¾
07
83
DO
0
90% WOV
10
37
82
3
653
T
NO
0
0
0
14
12
TO
4
80% WOV
SY
STE
M
5
TH
EL
EF
TO
FT
HE
6
4
49
8
Static Pressure (in. wg)
10
15
Static Pressure (Pa x 100)
12
5
55
16
Maximum
QEI-L
215T
Motor
QEI
254T
Frame Size
Minimum Motor
1/3 hp
.25 kW
Starting hp
Wheel Diameter
30 in.
762 mm
Approximate Weight QEI-L 400 lbs. 182 kg.
(Less Motor & Drives) QEI 470 lbs. 213 kg.
Maximum Bhp = (Fan RPM / 719)3
Outlet Velocity (FPM) = CFM / 6.21
Tip Speed (FPM) = Fan RPM x 7.85
% WOV = (CFM x 100) / (Fan RPM x 11.8)
Imperial data — Metric data
70% WOV
7½
Specification Data
RPM
BHP
% WOV
Density 0.075 lb/ft3
Density 1.2 kg/m3
50% WOV
SE
LE
C
QEI-L
QEI
Maximum
Fan RPM
16
5
5
10
15
Volume (cfm x 1000)
10
15
20
20
25
30
25
35
40
3
Volume (m /hr x 1000)
Performance Data
STATIC PRESSURE (inches wg)
CFM
OV
0.25
0.5
1
1.5
RPM
BHP
RPM
BHP
RPM
BHP
2
RPM
BHP
2.5
RPM
BHP
3
3.5
RPM
BHP
RPM
BHP
4
RPM
BHP
RPM
BHP
4600
740
494
0.28
584
0.52
748
1.11
5600
901
563
0.39
640
0.65
786
1.29
915
2.02
6600
1062
636
0.53
704
0.82
831
1.50
951
2.29
1060
3.16
7600
1223
712
0.71
772
1.03
888
1.76
996
2.59
1097
3.52
1191
4.51
1286
5.56
8600
1384
790
0.93
845
1.28
948
2.06
1047
2.94
1142
3.91
1231
4.96
1312
6.07
1400
7.24
1481
8.45
9600
1545
869
1.21
920
1.59
1013
2.42
1103
3.35
1190
4.36
1276
5.46
1357
6.63
1431
7.85
1507
9.12
10600
1706
949
1.54
996
1.95
1082
2.84
1165
3.82
1247
4.88
1324
6.02
1402
7.23
1475
8.51
1545
9.83
11600
1867
1030
1.93
1073
2.37
1154
3.33
1231
4.36
1304
5.46
1380
6.65
1450
7.90
1521
9.22
1589
10.6
12600
2028
1112
2.39
1152
2.86
1228
3.88
1298
4.96
1369
6.13
1436
7.35
1506
8.66
1570
10.0
1635
11.4
13600
2190
1193
2.91
1231
3.43
1303
4.50
1369
5.65
1435
6.87
1499
8.15
1562
9.49
1626
10.9
14600
2351
1275
3.52
1311
4.07
1378
5.21
1442
6.42
1502
7.69
1564
9.03
1623
10.4
15600
2512
1358
4.21
1392
4.80
1455
6.00
1516
7.27
1574
8.60
1631
9.99
Inlet Sound Power, LWi [dB ref 10-12 watts]
RPM
400
600
850
1150
1655
% WOV
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
1
69
68
66
67
72
70
69
71
76
72
72
74
79
76
76
79
83
80
81
85
2
69
68
67
67
76
75
75
74
81
79
75
77
91
92
85
84
89
85
84
85
3
64
62
60
60
71
69
66
66
80
79
76
76
85
83
79
79
100
95
88
87
4
61
59
58
58
68
65
63
63
76
73
69
68
83
80
76
75
95
92
88
86
5
60
58
57
56
65
62
60
60
73
70
67
66
81
78
74
73
91
88
84
82
6
58
58
58
58
65
61
61
61
73
67
65
63
79
74
70
69
89
85
81
79
7
50
50
50
50
55
54
53
53
62
59
57
57
77
68
65
64
87
80
76
75
Outlet Sound Power, LWo [dB ref 10-12 watts]
8
36
36
37
36
43
41
41
41
55
51
51
51
63
60
61
63
76
72
71
71
LWiA
65
64
63
63
71
69
67
67
79
76
73
73
87
83
79
78
97
94
89
88
RPM
400
600
850
1150
1655
% WOV
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
1
72
72
70
72
79
77
77
77
80
76
77
79
83
82
84
87
88
87
91
94
2
71
70
69
69
76
75
75
75
84
81
79
80
85
83
82
84
90
86
89
91
3
65
63
63
62
72
71
70
70
79
76
74
74
85
81
78
79
92
91
88
89
4
65
64
63
63
71
70
68
67
80
78
74
73
86
83
79
79
96
92
90
89
5
65
64
64
64
68
68
67
66
77
75
73
72
84
81
77
76
94
90
87
86
6
62
62
62
62
67
66
66
65
75
70
68
68
81
76
72
71
91
87
83
81
7
55
55
55
56
58
58
58
59
65
63
61
61
77
69
65
65
88
81
78
76
8
43
43
43
43
47
47
48
48
54
52
52
52
62
59
58
59
78
71
70
71
LWoA
69
68
68
68
73
73
72
72
82
79
77
76
89
85
81
81
98
94
91
90
Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not
include the effects of appurtenances (accessories).
The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA Standard 301. Values shown are for inlet LWi , LWi A and outlet LWo ,
LWo A sound power levels for installation type B: Free inlet, Ducted outlet. Ratings for inlet sound do not include the effects of duct end correction. Ratings for outlet
sound include the effects of duct end correction. The A-weighted sound power ratings shown have been calculated per AMCA Standard 301. The AMCA Certified
Ratings Seal applies to LWi A and LWo A values only.
32
QEI-24 Class II
10
Performance Data
20
15
2036
.55 kW
Wheel Diameter
30 in.
762 mm
550 lbs.
249 kg.
15
10
SY
ST
EM
CU
RV
E
3/4 hp
70% WOV
10
7
6
7½
5
5
4
3
5
2
Outlet Velocity (FPM) = CFM / 6.21
1
Tip Speed (FPM) = Fan RPM x 7.85
DO
0
0
0
% WOV = (CFM x 100) / (Fan RPM x 9.84)
15
69
T
NO
26
12
91
8
S
20
18
16
14
12
10
8
6
4
2
90% WOV
14
46
EL
EC
T
Maximum Bhp = (Fan RPM / 729)
17
96
TO
2
3
80% WOV
36
Minimum Motor
Starting hp
8
Static Pressure (in. wg)
284T
Approximate Weight
(Less Motor & Drives)
RPM
BHP
% WOV
3
Density 0.075 lb/ft
3
Density 1.2 kg/m
60% WOV
20
Static Pressure (Pa x 100)
20
Maximum Motor
Frame Size
OF
TH
IS
Specification Data
TH
EL
EF
T
Maximum Fan RPM
25
9
Volume (cfm x 1000)
Imperial data — Metric data
0
25
20
15
10
5
30
3
Volume (m /hr x 1000)
Performance Data
STATIC PRESSURE (inches wg)
CFM
OV
0.5
1
2
3
4
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
5
RPM
BHP
6
RPM
BHP
7
RPM
BHP
8
RPM
BHP
RPM
BHP
6800
1075
784
0.97
875
1.56
1051
2.96
1222
4.64
7500
1186
847
1.18
928
1.80
1090
3.25
1248
4.99
1405
6.94
8200
1297
911
1.43
987
2.08
1133
3.57
1281
5.36
1420
7.37
1568
9.57
8900
1408
976
1.71
1046
2.39
1184
3.96
1318
5.78
1453
7.85
1580
10.1
1717
12.5
9600
1518
1042
2.03
1107
2.74
1236
4.39
1360
6.25
1486
8.36
1607
10.7
1728
13.1
1854
15.7
10300
1629
1108
2.40
1169
3.15
1289
4.87
1405
6.76
1523
8.92
1641
11.3
1751
13.8
1865
16.5
1983
19.3
11000
1740
1176
2.81
1233
3.60
1345
5.39
1457
7.36
1566
9.54
1674
11.9
1784
14.5
1885
17.2
1994
20.1
11700
1851
1244
3.26
1298
4.11
1404
5.97
1509
8.02
1609
10.2
1714
12.7
1817
15.3
1918
18.1
2013
21.0
12400
1962
1312
3.76
1363
4.67
1464
6.59
1562
8.72
1660
11.0
1757
13.5
1853
16.1
1951
19.0
13100
2072
1380
4.32
1428
5.29
1524
7.27
1617
9.48
1712
11.8
1800
14.3
1895
17.0
1985
19.9
13800
2183
1449
4.94
1494
5.97
1585
8.00
1675
10.3
1765
12.7
1851
15.3
1938
18.0
2026
20.9
14500
2294
1518
5.61
1561
6.72
1648
8.82
1734
11.2
1818
13.7
1903
16.3
1982
19.0
Shaded values show where Class I fan selections are more efficient than Class II.
Inlet Sound Power, LWi [dB ref 10-12 watts]
RPM
600
850
1150
1650
2036
% WOV
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
1
69
67
66
69
73
71
72
76
76
72
76
80
83
78
84
86
86
80
87
89
2
76
73
71
73
81
76
74
78
82
78
77
84
87
82
84
89
89
84
88
94
3
71
68
66
67
75
71
71
72
88
85
80
85
95
92
89
91
96
91
89
94
4
66
64
61
62
73
70
68
68
82
79
76
76
90
86
84
84
96
92
89
89
5
65
63
61
62
71
68
67
67
79
76
74
73
89
86
83
82
95
92
88
87
6
64
59
59
60
74
67
67
67
77
73
71
71
86
82
79
78
91
88
84
84
7
52
51
51
52
61
60
61
60
77
67
66
66
87
77
75
75
92
83
80
80
Outlet Sound Power, LWo [dB ref 10-12 watts]
8
43
41
41
41
53
50
51
51
61
59
60
61
78
69
71
71
90
76
77
77
LWiA
71
68
66
67
78
74
73
73
86
82
79
81
95
91
88
88
100
95
92
93
RPM
600
850
1150
1650
2036
% WOV
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
1
76
76
75
76
79
75
76
83
83
80
81
83
88
84
88
89
94
88
93
94
2
79
78
77
78
82
78
79
81
84
80
82
83
90
87
91
92
95
89
94
95
3
70
68
67
67
76
73
72
73
86
81
81
81
94
90
91
91
97
93
93
94
4
70
68
67
66
77
75
73
73
86
83
81
81
94
93
89
89
99
94
93
93
5
67
67
66
65
74
73
71
71
82
80
78
77
92
90
87
87
97
93
91
91
6
65
65
64
64
74
70
69
69
78
75
74
74
87
84
82
82
93
89
87
87
7
56
59
59
59
65
64
65
65
77
71
70
70
87
80
79
80
92
85
83
83
8
45
49
49
47
55
53
54
55
65
64
65
65
81
72
72
73
91
77
77
78
LWoA
73
72
71
71
80
77
76
77
87
84
83
82
96
94
92
92
102
97
95
96
Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not
include the effects of appurtenances (accessories).
The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA Standard 301. Values shown are for inlet LWi , LWi A and outlet LWo ,
LWo A sound power levels for installation type B: Free inlet, Ducted outlet. Ratings for inlet sound do not include the effects of duct end correction. Ratings for outlet
sound include the effects of duct end correction. The A-weighted sound power ratings shown have been calculated per AMCA Standard 301. The AMCA Certified
Ratings Seal applies to LWi A and LWo A values only.
33
QEI-27 Class I & QEI-L
7
Performance Data
15
QEI-L
QEI
Maximum
Fan RPM
16
1164
1505
RPM
BHP
% WOV
3
Density 0.075 lb/ft
Density 1.2 kg/m3
50% WOV
6
10
60% WOV
14
Specification Data
10
8
6
5
7½
LE
FT
OF
TH
IS
SY
ST
EM
CU
RV
E
12
Static Pressure (in. wg)
4
5
3
3
2
4
0
EC
T
1
80% WOV
05
13
47
12
24
11
64
¾
0
0
0
DO
NO
T
69
90% WOV
90
2
TO
1½
2
15
10
TH
E
Static Pressure (Pa x 100)
70% WOV
Maximum
QEI-L
215T
Motor
QEI
256T
Frame Size
Minimum Motor
3/4 hp
.55 kW
Starting hp
Wheel Diameter
33 in.
838 mm
Approximate Weight QEI-L 470 lbs. 214 kg.
(Less Motor & Drives) QEI 540 lbs. 245 kg.
Maximum Bhp = (Fan RPM / 626)3
Outlet Velocity (FPM) = CFM / 7.54
Tip Speed (FPM) = Fan RPM x 8.64
% WOV = (CFM x 100) / (Fan RPM x 15.2)
Imperial data — Metric data
716
L
SE
568
5
5
10
15
Volume (cfm x 1000)
10
15
20
20
25
30
25
35
40
3
Volume (m /hr x 1000)
Performance Data
STATIC PRESSURE (inches wg)
CFM
OV
0.25
0.5
1
1.5
RPM
BHP
RPM
BHP
RPM
BHP
2
2.5
RPM
BHP
RPM
BHP
950
3.36
3
RPM
BHP
3.5
4
RPM
BHP
RPM
BHP
RPM
BHP
5700
755
459
0.35
541
0.63
690
1.32
6900
915
524
0.48
594
0.79
724
1.53
843
2.40
8100
1074
593
0.65
651
0.98
767
1.79
875
2.72
976
3.75
1070
4.85
9300
1233
664
0.87
716
1.24
819
2.10
916
3.08
1009
4.17
1097
5.34
1182
6.58
1260
7.88
10500
1392
737
1.14
783
1.54
875
2.46
964
3.51
1050
4.64
1131
5.87
1208
7.17
1287
8.55
1359
9.98
11700
1551
811
1.47
853
1.91
933
2.88
1017
3.99
1096
5.19
1172
6.46
1246
7.83
1314
9.26
1386
10.8
12900
1710
886
1.88
924
2.35
999
3.38
1073
4.54
1148
5.81
1218
7.14
1287
8.55
1355
10.0
1418
11.6
14100
1870
962
2.35
997
2.86
1065
3.96
1131
5.15
1202
6.50
1269
7.90
1332
9.36
1396
10.9
1459
12.5
15300
2029
1038
2.91
1070
3.46
1133
4.62
1196
5.88
1259
7.25
1322
8.74
1384
10.3
1442
11.9
1500
13.5
16500
2188
1114
3.55
1144
4.14
1203
5.37
1262
6.70
1318
8.10
1379
9.64
1436
11.3
1494
12.9
17700
2347
1191
4.29
1219
4.92
1275
6.23
1329
7.61
1383
9.08
1436
10.6
1492
12.3
18900
2506
1268
5.13
1294
5.80
1346
7.18
1397
8.62
1449
10.2
1497
11.8
Inlet Sound Power, LWi [dB ref 10-12 watts]
RPM
400
550
750
1100
1505
% WOV
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
1
70
65
65
67
73
70
69
74
84
82
79
79
77
73
75
79
80
78
81
85
2
71
68
67
68
72
70
69
70
83
80
77
78
86
84
84
82
89
87
90
89
3
64
62
62
61
70
67
64
64
75
73
71
71
86
83
79
82
92
88
88
89
4
59
58
59
58
65
63
61
61
73
70
68
67
84
80
76
76
93
90
86
86
5
61
57
57
57
65
61
60
60
70
69
67
66
80
77
75
74
89
86
83
82
6
58
58
58
58
67
61
60
60
76
66
64
63
78
74
72
71
85
83
80
80
7
52
52
52
53
54
54
55
54
62
60
59
59
82
70
67
66
90
79
77
76
Outlet Sound Power, LWo [dB ref 10-12 watts]
8
38
40
42
42
45
44
44
44
54
53
52
52
66
63
64
64
76
72
72
73
LWiA
65
64
63
64
71
67
66
66
79
74
72
71
88
83
80
80
95
91
89
88
RPM
400
550
750
1100
1505
% WOV
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
1
70
69
69
68
78
75
74
73
85
85
83
83
85
81
84
87
88
86
91
93
2
70
68
69
68
73
71
70
71
82
80
79
79
89
86
87
88
91
89
89
92
3
65
63
63
62
71
68
67
66
77
75
74
74
86
82
81
83
93
90
88
90
4
67
65
64
64
71
69
67
66
79
76
75
73
89
86
83
82
97
94
91
92
5
62
59
59
59
67
65
65
64
74
72
71
71
84
81
78
78
93
90
87
87
6
60
61
61
61
67
65
64
64
75
68
67
66
81
77
75
74
89
87
84
83
7
55
57
57
56
56
57
57
56
64
62
61
61
82
72
69
68
89
83
81
80
8
44
45
45
45
46
47
47
46
55
53
53
52
66
63
63
64
79
73
72
72
LWoA
68
67
67
66
73
71
70
70
81
78
76
75
90
86
84
84
99
95
92
93
Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not
include the effects of appurtenances (accessories).
The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA Standard 301. Values shown are for inlet LWi , LWi A and outlet LWo ,
LWo A sound power levels for installation type B: Free inlet, Ducted outlet. Ratings for inlet sound do not include the effects of duct end correction. Ratings for outlet
sound include the effects of duct end correction. The A-weighted sound power ratings shown have been calculated per AMCA Standard 301. The AMCA Certified
Ratings Seal applies to LWi A and LWo A values only.
34
QEI-27 Class II
10
Performance Data
1847
304 kg.
670 lbs.
10
CU
RVE
TEM
SY
S
7½
5
4
5
3
3
Maximum Bhp = (Fan RPM / 630)
5
2
2
Outlet Velocity (FPM) = CFM / 7.54
1
Tip Speed (FPM) = Fan RPM x 8.64
DO
0
0
0
% WOV = (CFM x 100) / (Fan RPM x 12.9)
80% WOV
LE
FT
OF
TH
IS
Approximate Weight
(Less Motor & Drives)
838 mm
6
47
33 in.
10
08
Wheel Diameter
1.1 kW
70% WOV
18
11⁄2 hp
7
17
Minimum Motor
Starting hp
15
15
15
52
13
56
TH
E
286T
60% WOV
8
Static Pressure (in. wg)
Maximum Motor
Frame Size
Static Pressure (Pa x 100)
20
2
T
NO
90% WOV
12
32
TO
Specification Data
EL
EC
T
Maximum Fan RPM
RPM
BHP
% WOV
3
Density 0.075 lb/ft
3
Density 1.2 kg/m
30
25
20
9
10
77
79
S
4
6
4
10
8
14
12
16
18
20
22
24
Volume (cfm x 1000)
Imperial data — Metric data
40
30
20
10
0
3
Volume (m /hr x 1000)
Performance Data
STATIC PRESSURE (inches wg)
CFM
OV
0.5
1
2
3
4
5
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
6
RPM
BHP
8300
1100
727
1.21
807
1.89
967
3.57
1119
5.59
1265
7.80
9100
1206
782
1.45
854
2.16
1002
3.91
1147
5.98
1281
8.29
1410
10.8
7
RPM
BHP
8
RPM
BHP
RPM
BHP
9900
1312
839
1.73
906
2.49
1038
4.28
1175
6.41
1303
8.81
1427
11.4
1543
14.1
10700
1419
896
2.05
959
2.87
1082
4.71
1207
6.89
1331
9.34
1444
12.0
1560
14.8
1667
17.8
11500
1525
953
2.41
1012
3.28
1128
5.19
1243
7.42
1359
9.91
1472
12.7
1576
15.6
1684
18.6
1783
21.8
12300
1631
1011
2.82
1067
3.75
1174
5.71
1280
7.99
1392
10.6
1500
13.4
1602
16.4
1700
19.5
1800
22.7
13100
1737
1070
3.28
1123
4.26
1223
6.30
1325
8.65
1428
11.3
1529
14.1
1630
17.2
1723
20.4
1816
23.8
13900
1843
1130
3.78
1179
4.82
1275
6.97
1371
9.36
1464
12.0
1563
14.9
1658
18.0
1752
21.3
1839
24.8
14700
1949
1189
4.35
1236
5.44
1327
7.69
1417
10.1
1506
12.8
1599
15.8
1688
18.9
1780
22.3
15500
2055
1249
4.97
1293
6.12
1380
8.48
1464
11.0
1551
13.8
1635
16.7
1724
20.0
1809
23.3
16300
2161
1309
5.65
1351
6.86
1434
9.33
1515
11.9
1597
14.7
1676
17.8
1760
21.0
1843
24.5
17100
2267
1370
6.39
1409
7.67
1488
10.2
1566
12.9
1644
15.8
1721
18.9
1797
22.2
Shaded values show where Class I fan selections are more efficient than Class II.
Inlet Sound Power, LWi [dB ref 10-12 watts]
RPM
550
750
1100
1500
1847
% WOV
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
1
81
79
76
74
73
65
67
68
78
74
74
78
83
78
80
83
85
82
89
89
2
72
71
68
68
80
73
70
71
90
89
84
83
86
80
80
83
90
83
86
89
3
67
64
62
63
75
71
70
69
84
80
76
77
95
91
87
86
97
91
90
91
4
64
62
61
61
72
68
65
65
83
79
75
74
91
87
83
83
97
92
89
89
5
68
62
62
62
71
68
67
67
81
78
77
76
89
85
82
81
96
92
89
88
6
62
58
59
59
77
62
62
62
83
73
72
71
86
80
79
78
92
87
85
84
7
50
50
51
51
58
56
56
56
78
67
67
67
89
76
75
75
94
84
82
81
Outlet Sound Power, LWo [dB ref 10-12 watts]
8
43
44
45
45
53
49
50
51
65
61
62
63
75
70
71
72
84
77
78
78
LWiA
71
67
66
66
79
72
71
70
88
82
80
80
95
89
87
86
101
96
93
92
RPM
550
750
1100
1500
1847
% WOV
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
1
83
82
79
79
79
76
75
77
85
81
83
84
90
85
89
91
96
91
97
97
2
74
72
69
70
81
76
73
75
92
84
82
84
91
86
88
90
95
90
94
96
3
4
70 71
67 70
65 68
65 67
78 79
75 77
72 74
71 73
88 89
84 86
81 83
81 82
96 96
91 94
88 91
90 90
100 101
98 98
94 95
96 95
5
68
66
65
65
74
72
71
70
84
82
79
79
92
89
87
86
99
96
93
92
6
64
62
62
62
75
67
66
66
84
77
75
74
89
85
82
82
94
91
88
88
7
55
56
56
56
62
61
61
61
78
69
68
68
90
79
77
77
94
86
83
83
8
45
45
45
45
55
53
52
53
67
62
63
64
77
72
72
73
86
79
79
79
LWoA
73
71
70
70
81
77
75
75
91
87
84
84
98
95
92
91
103
100
97
97
Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not
include the effects of appurtenances (accessories).
The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA Standard 301. Values shown are for inlet LWi , LWi A and outlet LWo ,
LWo A sound power levels for installation type B: Free inlet, Ducted outlet. Ratings for inlet sound do not include the effects of duct end correction. Ratings for outlet
sound include the effects of duct end correction. The A-weighted sound power ratings shown have been calculated per AMCA Standard 301. The AMCA Certified
Ratings Seal applies to LWi A and LWo A values only.
35
QEI-30 Class I & QEI-L
7
Performance Data
QEI-L
QEI
1051
1360
15
50% WOV
20
6
RPM
BHP
% WOV
3
Density 0.075 lb/ft
Density 1.2 kg/m3
60% WOV
14
70% WOV
Specification Data
10
8
6
MC
UR
VE
12
4
TH
EL
EF
TO
FT
HIS
SY
ST
E
Maximum
QEI-L
256T
Motor
QEI
284T
Frame Size
Minimum Motor
1 hp
.75 kW
Starting hp
Wheel Diameter
36.5 in.
927 mm
Approximate Weight QEI-L 630 lbs. 286 kg.
(Less Motor & Drives) QEI 850 lbs. 386 kg.
Maximum Bhp = (Fan RPM / 528)3
Outlet Velocity (FPM) = CFM / 9.31
Tip Speed (FPM) = Fan RPM x 9.56
% WOV = (CFM x 100) / (Fan RPM x 20.6)
Imperial data — Metric data
Static Pressure (in. wg)
Static Pressure (Pa x 100)
10
5
5
3
2
2
80% WOV
13
60
11
39
10
51
90% WOV
90
4
TO
4
1
2
EL
CT
Maximum
Fan RPM
16
1
DO
0
0
0
T
NO
L
SE
666
529
5
10
15
Volume (cfm x 1000)
0
10
20
20
30
25
30
40
50
3
Volume (m /hr x 1000)
Performance Data
STATIC PRESSURE (inches wg)
CFM
OV
0.25
0.5
1
1.5
RPM
BHP
RPM
BHP
RPM
BHP
2
2.5
RPM
BHP
RPM
BHP
6900
748
412
0.42
487
0.76
622
1.60
8400
910
472
0.58
536
0.96
654
1.87
761
2.93
858
4.10
3
RPM
BHP
3.5
4
RPM
BHP
RPM
BHP
RPM
BHP
9900
1073
536
0.79
588
1.20
693
2.19
791
3.32
882
4.58
968
5.93
11400
1235
602
1.07
648
1.52
742
2.58
829
3.77
912
5.10
992
6.54
1069
8.06
1140
9.65
12900
1398
669
1.41
710
1.9
793
3.03
874
4.31
950
5.70
1024
7.21
1093
8.80
1164
10.5
1230
12.2
14400
1561
737
1.83
775
2.37
847
3.55
923
4.92
993
6.39
1062
7.95
1128
9.63
1190
11.4
1254
13.2
15900
1723
806
2.34
841
2.92
908
4.19
975
5.61
1042
7.17
1104
8.80
1167
10.5
1228
12.4
1285
14.3
17400
1886
876
2.94
908
3.57
969
4.92
1028
6.39
1092
8.04
1152
9.77
1209
11.6
1266
13.4
1323
15.4
18900
2048
947
3.65
975
4.33
1032
5.76
1088
7.31
1145
8.99
1202
10.8
1257
12.7
1310
14.7
20400
2211
1018
4.47
1044
5.20
1097
6.72
1150
8.35
1200
10.1
1254
12.0
1306
14.0
1358
16.0
21900
2374
1088
5.41
1113
6.19
1163
7.81
1212
9.51
1260
11.3
1307
13.2
1358
15.3
23400
2536
1160
6.49
1183
7.32
1230
9.03
1275
10.8
1321
12.7
Inlet Sound Power, LWi [dB ref 10-12 watts]
RPM
350
500
700
950
1360
% WOV
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
1
70
66
66
67
74
71
70
74
87
84
81
81
78
75
77
79
83
80
84
87
2
70
67
66
67
73
71
70
71
84
81
78
79
86
84
83
82
91
89
91
91
3
63
61
61
61
70
68
65
65
77
74
72
73
85
82
78
81
93
90
89
89
4
60
58
58
58
66
64
62
62
74
72
69
68
83
79
76
76
93
90
86
86
5
61
57
57
57
66
62
61
61
73
70
68
67
79
77
74
73
89
86
84
83
6
57
57
57
57
67
61
60
60
76
67
65
64
79
73
71
70
87
83
81
80
7
49
50
51
51
54
54
54
54
62
61
60
60
79
68
67
66
88
79
77
76
Outlet Sound Power, LWo [dB ref 10-12 watts]
8
36
38
40
40
44
43
44
43
55
53
53
53
62
61
63
63
75
72
73
73
LWiA
65
63
63
63
72
68
67
66
80
75
73
73
86
82
79
79
96
92
89
89
RPM
350
500
700
950
1360
% WOV
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
1
70
69
69
68
78
76
75
74
87
87
85
85
86
82
84
87
89
87
92
94
2
69
68
68
67
74
71
71
71
83
81
80
80
89
85
86
87
92
90
91
93
3
66
64
63
63
72
69
68
67
79
76
75
75
86
83
82
83
95
91
89
91
4
66
64
63
63
72
70
68
67
80
78
76
75
88
85
82
81
97
94
91
92
5
62
60
59
59
68
66
66
65
75
73
72
72
84
80
77
77
93
90
87
87
6
59
60
60
60
67
65
64
64
76
69
68
67
81
76
73
72
90
87
85
84
7
53
55
55
54
56
56
56
56
64
63
62
61
79
70
68
67
89
82
81
80
8
42
43
43
43
46
46
46
46
55
54
53
53
63
61
62
63
78
72
72
71
LWoA
68
66
66
66
74
72
71
70
82
79
77
77
89
85
83
83
99
95
93
93
Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not
include the effects of appurtenances (accessories).
The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA Standard 301. Values shown are for inlet LWi , LWi A and outlet LWo ,
LWo A sound power levels for installation type B: Free inlet, Ducted outlet. Ratings for inlet sound do not include the effects of duct end correction. Ratings for outlet
sound include the effects of duct end correction. The A-weighted sound power ratings shown have been calculated per AMCA Standard 301. The AMCA Certified
Ratings Seal applies to LWi A and LWo A values only.
36
QEI-30 Class II
10
Performance Data
20
1670
454 kg.
1000 lbs.
10
5
CU
RVE
SY
STE
M
927 mm
7½
4
5
3
5
SE
LE
CT
2
Outlet Velocity (FPM) = CFM / 9.31
1
Tip Speed (FPM) = Fan RPM x 9.56
DO
0
0
0
% WOV = (CFM x 100) / (Fan RPM x 17.4)
13
13
90% WOV
11
47
10
43
TO
3
Maximum Bhp = (Fan RPM / 533)3
80% WOV
70
36.5 in.
10
16
Wheel Diameter
6
45
1.1 kW
7
57
11⁄2 hp
15
70% WOV
15
14
Minimum Motor
Starting hp
Static Pressure (in. wg)
324T
8
15
Static Pressure (Pa x 100)
20
Approximate Weight
(Less Motor & Drives)
RPM
BHP
% WOV
3
Density 0.075 lb/ft
3
Density 1.2 kg/m
60% WOV
FT
HIS
Specification Data
Maximum Motor
Frame Size
30
25
9
TH
EL
EF
TO
Maximum Fan RPM
91
1
76
8
T
NO
30
25
20
15
10
5
Volume (cfm x 1000)
Imperial data — Metric data
50
40
30
20
10
0
3
Volume (m /hr x 1000)
Performance Data
STATIC PRESSURE (inches wg)
CFM
OV
0.5
1
2
3
4
5
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
6
RPM
BHP
7
RPM
BHP
8
RPM
BHP
RPM
BHP
10000
1084
650
1.43
723
2.26
870
4.31
1009
6.76
1141
9.50
11100
1203
706
1.76
771
2.63
905
4.77
1036
7.30
1158
10.1
1274
13.1
12200
1323
763
2.15
824
3.09
942
5.28
1065
7.89
1180
10.8
1291
14.0
1397
17.3
13300
1442
821
2.60
877
3.61
987
5.88
1098
8.56
1209
11.6
1311
14.9
1413
18.3
1510
21.9
14400
1561
880
3.11
931
4.20
1034
6.56
1135
9.31
1237
12.4
1339
15.8
1431
19.4
1527
23.1
1617
27.0
15500
1681
939
3.70
988
4.86
1082
7.31
1176
10.1
1273
13.3
1368
16.7
1460
20.5
1545
24.4
1634
28.4
16600
1800
999
4.37
1045
5.60
1133
8.18
1222
11.1
1310
14.3
1399
17.8
1489
21.6
1573
25.6
1652
29.8
17700
1919
1060
5.11
1103
6.43
1186
9.15
1269
12.1
1349
15.4
1436
19.0
1517
22.8
1602
26.9
18800
2039
1121
5.94
1161
7.34
1240
10.2
1317
13.2
1395
16.6
1473
20.3
1553
24.2
1631
28.3
19900
2158
1182
6.87
1219
8.35
1294
11.4
1367
14.5
1442
18.0
1513
21.7
1590
25.7
1665
29.9
21000
2277
1243
7.90
1278
9.46
1349
12.6
1420
15.9
1489
19.4
1559
23.2
1627
27.2
22100
2396
1304
9.03
1338
10.7
1406
14.0
1473
17.4
1537
20.9
1606
24.9
Shaded values show where Class I fan selections are more efficient than Class II.
Inlet Sound Power, LWi [dB ref 10-12 watts]
RPM
500
700
950
1350
1670
% WOV
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
1
83
81
78
76
75
68
69
70
80
76
76
79
84
79
81
84
87
84
91
91
2
72
71
68
68
81
74
72
72
91
90
85
84
88
82
82
85
91
84
86
90
3
68
65
63
63
77
72
71
70
83
79
76
77
95
91
87
87
99
93
92
92
4
66
63
62
62
74
70
67
67
82
78
76
75
92
87
84
83
97
93
90
89
5
68
63
62
62
73
69
68
68
81
77
76
75
89
85
82
82
97
93
90
89
6
61
58
59
59
76
63
63
63
82
71
71
70
87
80
79
79
92
87
85
85
7
50
50
51
51
59
56
57
57
75
66
66
66
88
76
75
75
95
84
82
82
Outlet Sound Power, LWo [dB ref 10-12 watts]
8
43
44
45
46
54
50
51
52
63
59
61
62
74
69
71
72
84
77
78
79
LWiA
71
67
66
66
80
73
72
71
87
82
80
79
95
90
87
87
102
96
94
93
RPM
500
700
950
1350
1670
% WOV
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
1
84
83
80
80
80
77
76
78
86
82
83
84
91
86
90
92
98
92
98
99
2
75
72
70
71
82
77
74
76
93
85
83
85
92
87
89
91
96
91
94
97
3
4
71 72
68 70
66 68
66 68
80 80
76 78
73 75
73 74
88 88
84 85
81 82
81 81
97 97
92 94
90 91
91 90
102 102
100 99
95 96
97 95
5
69
66
66
65
76
73
72
71
84
81
78
78
93
90
87
86
99
97
94
92
6
64
62
62
62
75
68
67
67
83
75
73
73
90
85
82
82
95
91
89
88
7
54
55
55
56
63
62
61
61
76
68
67
67
89
79
77
77
95
86
83
83
8
45
44
44
45
55
54
53
54
64
61
61
63
76
72
72
73
85
79
79
79
LWoA
73
72
70
70
82
79
76
76
90
86
83
83
98
95
92
91
104
101
98
97
Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not
include the effects of appurtenances (accessories).
The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA Standard 301. Values shown are for inlet LWi , LWi A and outlet LWo ,
LWo A sound power levels for installation type B: Free inlet, Ducted outlet. Ratings for inlet sound do not include the effects of duct end correction. Ratings for outlet
sound include the effects of duct end correction. The A-weighted sound power ratings shown have been calculated per AMCA Standard 301. The AMCA Certified
Ratings Seal applies to LWi A and LWo A values only.
37
QEI-33 Class I & QEI-L
Performance Data
8
QEI-L
QEI
25
20
964
1234
18
Specification Data
16
Maximum
QEI-L
256T
Motor
QEI
286T
Frame Size
Minimum Motor
1.1 kW
11⁄2 hp
Starting hp
Wheel Diameter
40.25 in.
1022 mm
Approximate Weight QEI-L 730 lbs. 332 kg.
(Less Motor & Drives) QEI 990 lbs. 449 kg.
Maximum Bhp = (Fan RPM / 450)3
Outlet Velocity (FPM) = CFM / 11.27
Tip Speed (FPM) = Fan RPM x 10.5
% WOV = (CFM x 100) / (Fan RPM x 26.7)
Imperial data — Metric data
14
15
6
CU
RV
E
FT
HI
SS
YS
TE
M
10
4
3
LE
FT
O
8
5
5
2
1
2
0
34
11
09
4
1
0
0
0
90% WOV
EL
EC
T
2
4
80% WOV
12
96
TH
E
10
70% WOV
TO
Static Pressure (Pa x 100)
6
12
RPM
BHP
% WOV
Density 0.075 lb/ft3
3
Density 1.2 kg/m
60% WOV
7
Static Pressure (in. wg)
Maximum
Fan RPM
DO
T
NO
769
S
567
450
5
10
10
15
20
Volume (cfm x 1000)
20
25
30
30
40
35
50
3
Volume (m /hr x 1000)
Performance Data
STATIC PRESSURE (inches wg)
CFM
OV
0.25
0.5
1
1.5
RPM
BHP
RPM
BHP
RPM
BHP
2
RPM
BHP
2.5
RPM
BHP
3
3.5
RPM
BHP
RPM
BHP
4
RPM
BHP
RPM
BHP
8400
745
379
0.52
444
0.93
562
1.93
10200
905
435
0.72
489
1.17
593
2.27
687
3.52
12000
1064
494
0.99
539
1.48
631
2.67
717
4.02
795
5.48
13800
1224
556
1.35
595
1.88
675
3.13
753
4.60
827
6.17
893
7.81
966
9.68
15600
1384
618
1.79
653
2.37
723
3.69
793
5.22
862
6.93
927
8.71
988
10.6
1050
12.6
1113
14.7
17400
1543
682
2.32
714
2.96
776
4.37
840
5.97
902
7.74
963
9.66
1022
11.6
1077
13.7
1129
15.8
19200
1703
747
2.97
775
3.67
832
5.17
888
6.83
947
8.67
1003
10.7
1058
12.8
1112
15.0
1163
17.2
21000
1863
812
3.74
837
4.50
889
6.08
940
7.83
994
9.75
1045
11.8
1098
14.0
1149
16.3
1198
18.7
22800
2023
878
4.64
900
5.46
948
7.16
996
8.99
1042
10.9
1093
13.1
1140
15.3
1189
17.8
24600
2182
944
5.69
965
6.56
1009
8.38
1053
10.3
1097
12.4
1141
14.5
1188
16.9
1231
19.3
26400
2342
1010
6.89
1029
7.83
1070
9.75
1111
11.8
1153
13.9
1192
16.2
28200
2502
1076
8.25
1094
9.25
1132
11.3
1171
13.4
1209
15.6
Inlet Sound Power, LWi [dB ref 10-12 watts]
RPM
300
450
600
850
1234
% WOV
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
1
68
66
62
65
74
71
69
69
83
79
78
78
84
82
81
81
88
86
86
86
2
68
66
65
66
76
75
72
72
81
80
79
79
93
92
90
88
98
96
95
95
3
62
60
59
60
71
68
66
66
78
75
73
73
88
85
80
80
95
93
88
88
4
60
60
60
60
70
70
70
70
74
72
70
70
83
80
76
75
94
91
87
87
5
61
60
60
60
70
66
65
65
73
72
71
71
79
78
75
75
90
88
84
84
6
48
49
49
49
59
58
59
58
74
66
66
66
84
74
73
73
88
84
82
82
7
39
40
39
39
50
51
52
52
59
60
60
60
70
67
68
68
90
78
77
77
Outlet Sound Power, LWo [dB ref 10-12 watts]
8
32
34
32
33
45
44
45
44
54
53
54
54
62
61
63
63
75
72
73
73
LWiA
64
62
62
62
73
70
70
70
79
76
75
75
88
84
81
81
97
93
90
90
RPM
300
450
600
850
1234
% WOV
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
1
71
68
67
68
80
77
77
78
88
86
85
84
85
84
84
86
91
89
92
94
2
67
68
68
69
76
76
76
76
82
82
82
82
90
90
88
89
95
95
93
94
3
64
63
62
62
73
70
68
69
79
77
75
75
87
84
82
82
97
94
92
92
4
64
63
63
63
72
71
70
70
80
78
75
75
88
85
83
82
99
96
93
93
5
64
63
63
64
71
68
67
68
76
75
73
73
83
80
78
78
94
91
88
88
6
52
52
52
53
62
61
60
60
74
68
67
67
83
76
75
75
91
87
85
85
7
45
45
46
46
54
54
54
54
61
61
61
61
74
70
69
69
91
82
80
80
8
38
38
39
40
46
46
46
46
54
53
53
54
65
62
64
64
78
74
74
75
LWoA
67
66
66
66
74
72
71
72
81
79
78
77
90
86
84
84
100
97
94
94
Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not
include the effects of appurtenances (accessories).
The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA Standard 301. Values shown are for inlet LWi , LWi A and outlet LWo ,
LWo A sound power levels for installation type B: Free inlet, Ducted outlet. Ratings for inlet sound do not include the effects of duct end correction. Ratings for outlet
sound include the effects of duct end correction. The A-weighted sound power ratings shown have been calculated per AMCA Standard 301. The AMCA Certified
Ratings Seal applies to LWi A and LWo A values only.
38
QEI-33 Class II
10
Performance Data
1522
20
544 kg.
1200 lbs.
10
SY
ST
EM
CU
RVE
HIS
FT
4
5
3
3
Maximum Bhp = (Fan RPM / 450)
3
5
DO
0
0
0
20
N
90% WOV
09
96
9
76
9
SE
1
Tip Speed (FPM) = Fan RPM x 10.5
12
11
LE
CT
2
Outlet Velocity (FPM) = CFM / 11.27
% WOV = (CFM x 100) / (Fan RPM x 23.5)
22
1022 mm
10
5
80% WOV
15
40.25 in.
Approximate Weight
(Less Motor & Drives)
6
14
Wheel Diameter
1.5 kW
70% WOV
15
13
2 hp
15
7
97
Minimum Motor
Starting hp
Static Pressure (in. wg)
324T
8
13
Static Pressure (Pa x 100)
20
TH
EL
EF
TO
Specification Data
Maximum Motor
Frame Size
RPM
BHP
% WOV
3
Density 0.075 lb/ft
3
Density 1.2 kg/m
50% WOV
60% WOV
TO
Maximum Fan RPM
40
30
25
9
64
9
OT
24
20
16
12
8
4
36
32
28
Volume (cfm x 1000)
Imperial data — Metric data
0
60
50
40
30
20
10
3
Volume (m /hr x 1000)
Performance Data
STATIC PRESSURE (inches wg)
CFM
OV
0.5
1
2
3
4
5
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
6
RPM
BHP
7
RPM
BHP
8
RPM
BHP
RPM
BHP
12500
1109
599
1.76
668
2.84
797
5.47
923
8.58
1043
11.9
13900
1233
652
2.17
714
3.32
833
6.06
948
9.29
1059
12.8
1165
16.6
15300
1357
707
2.64
762
3.87
872
6.71
975
10.0
1080
13.8
1181
17.8
1277
21.9
16700
1481
762
3.20
812
4.50
915
7.47
1011
10.9
1107
14.8
1200
18.9
1293
23.3
1381
27.8
18100
1606
818
3.84
862
5.22
958
8.30
1050
11.9
1136
15.8
1227
20.1
1311
24.7
1398
29.4
1480
34.3
19500
1730
874
4.57
916
6.03
1004
9.26
1092
12.9
1174
17.0
1254
21.4
1338
26.1
1415
31.1
1496
36.1
20900
1854
931
5.40
971
6.95
1053
10.3
1134
14.1
1212
18.3
1288
22.8
1365
27.6
1442
32.7
1514
38.0
22300
1978
988
6.34
1026
7.98
1101
11.5
1178
15.4
1253
19.7
1326
24.3
1395
29.2
1469
34.4
23700
2102
1046
7.38
1081
9.12
1151
12.8
1224
16.8
1296
21.2
1365
25.9
1433
31.0
1496
36.2
25100
2227
1103
8.55
1137
10.4
1201
14.2
1272
18.4
1340
22.9
1407
27.7
1471
32.9
26500
2351
1161
9.85
1193
11.8
1254
15.8
1320
20.1
1384
24.7
1450
29.7
1510
34.9
27900
2475
1219
11.3
1249
13.3
1308
17.5
1370
21.9
1432
26.7
1493
31.7
Shaded values show where Class I fan selections are more efficient than Class II.
Inlet Sound Power, LWi [dB ref 10-12 watts]
RPM
450
600
850
1200
1522
% WOV
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
1
83
80
78
75
83
79
76
76
79
75
74
79
85
79
81
83
90
85
87
90
2
74
72
70
69
83
80
77
77
93
90
87
88
92
89
86
87
94
89
88
91
3
4
69 67
66 66
63 64
62 64
77 75
73 72
70 70
70 69
84 85
82 82
77 79
78 77
97 94
94 91
91 87
89 86
101 100
97 98
93 94
93 93
5
71
67
66
66
74
73
72
72
81
79
77
76
90
87
85
84
96
94
90
90
6
61
58
57
56
78
65
64
63
87
75
74
72
89
83
81
81
94
90
87
87
7
50
48
48
48
59
56
56
55
73
67
67
65
92
79
77
76
98
87
84
83
Outlet Sound Power, LWo [dB ref 10-12 watts]
8
44
40
40
40
53
49
49
49
65
60
61
61
76
70
70
71
86
79
78
79
LWiA
73
69
69
68
81
76
75
74
90
84
82
81
98
93
90
89
104
99
96
95
RPM
450
600
850
1200
1522
% WOV
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
1
87
85
84
83
82
82
82
82
85
82
82
85
89
87
88
91
94
92
94
96
2
77
77
76
77
82
82
81
83
89
87
85
87
92
89
89
92
96
93
95
97
3
4
73 73
71 72
69 70
68 68
79 80
77 79
75 76
74 75
88 90
85 88
82 84
82 83
95 99
93 97
90 94
92 93
102 104
98 102
95 99
98 99
5
74
72
72
72
76
75
75
74
83
81
79
79
93
91
88
87
99
97
94
94
6
64
61
60
59
76
68
67
65
86
77
75
74
90
87
84
83
96
93
90
90
7
54
52
52
52
62
60
59
58
75
70
68
67
92
82
79
78
98
89
86
85
8
47
45
45
45
54
51
52
52
66
61
62
62
78
73
72
73
87
81
79
80
LWoA
76
75
74
74
82
80
78
77
91
88
85
84
100
97
94
93
106
103
100
100
Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not
include the effects of appurtenances (accessories).
The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA Standard 301. Values shown are for inlet LWi , LWi A and outlet LWo ,
LWo A sound power levels for installation type B: Free inlet, Ducted outlet. Ratings for inlet sound do not include the effects of duct end correction. Ratings for outlet
sound include the effects of duct end correction. The A-weighted sound power ratings shown have been calculated per AMCA Standard 301. The AMCA Certified
Ratings Seal applies to LWi A and LWo A values only.
39
QEI-36 Class I & QEI-L
8
Performance Data
25
QEI-L
QEI
872
1116
30
RPM
BHP
% WOV
Density 0.075 lb/ft3
3
Density 1.2 kg/m
60% WOV
18
7
20
16
70% WOV
Specification Data
8
6
4
80% WOV
CU
RV
E
10
15
5
10
3
5
2
1
2
0
1½
0
0
0
N
DO
S
OT
T
EC
EL
5
T
93
9
87
2
90% WOV
820
1
549
436
10
10
16
33
65
O
4
3
11
10
TH
IS
SY
ST
EM
12
OF
14
LE
FT
Maximum
QEI-L
256T
Motor
QEI
286T
Frame Size
Minimum Motor
1.1 kW
11⁄2 hp
Starting hp
Wheel Diameter
44.5 in.
1130 mm
Approximate Weight QEI-L 900 lbs. 409 kg.
(Less Motor & Drives) QEI 1200 lbs. 544 kg.
Maximum Bhp = (Fan RPM / 380)3
Outlet Velocity (FPM) = CFM / 13.79
Tip Speed (FPM) = Fan RPM x 11.7
% WOV = (CFM x 100) / (Fan RPM x 36.1)
Imperial data — Metric data
Static Pressure (in. wg)
Static Pressure (Pa x 100)
6
TH
E
Maximum
Fan RPM
15
20
25
Volume (cfm x 1000)
20
30
40
30
50
35
40
60
45
70
3
Volume (m /hr x 1000)
Performance Data
STATIC PRESSURE (inches wg)
CFM
OV
0.25
0.5
1
1.5
RPM
BHP
RPM
BHP
RPM
BHP
2
RPM
BHP
2.5
RPM
BHP
3
3.5
RPM
BHP
RPM
BHP
4
RPM
BHP
RPM
BHP
10300
746
343
0.63
402
1.14
508
2.36
12500
906
394
0.88
443
1.44
537
2.79
622
4.31
14700
1065
448
1.22
488
1.82
571
3.27
649
4.93
720
6.71
16900
1225
503
1.65
539
2.31
611
3.83
681
5.63
748
7.55
808
9.57
874
11.8
19100
1385
560
2.19
592
2.90
654
4.52
718
6.39
780
8.49
839
10.7
894
12.9
950
15.4
1007
18.0
21300
1544
618
2.85
646
3.63
702
5.35
760
7.31
817
9.48
872
11.8
925
14.3
975
16.7
1022
19.3
23500
1704
677
3.64
702
4.50
753
6.33
803
8.36
857
10.6
908
13.1
958
15.7
1006
18.3
1052
21.0
25700
1863
736
4.59
758
5.51
805
7.45
851
9.59
899
11.9
946
14.4
994
17.1
1040
20.0
1084
22.9
27900
2023
795
5.69
815
6.69
859
8.76
902
11.0
943
13.4
989
16.0
1032
18.8
1076
21.7
30100
2182
854
6.97
873
8.05
913
10.3
953
12.6
993
15.1
1033
17.8
1075
20.7
1114
23.6
32300
2342
914
8.44
932
9.59
969
12.0
1005
14.4
1043
17.0
1079
19.8
34500
2501
974
10.1
991
11.3
1024
13.8
1060
16.4
1094
19.1
Inlet Sound Power, LWi [dB ref 10-12 watts]
RPM
275
400
550
800
1116
% WOV
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
1
70
68
64
66
75
72
70
70
85
81
80
80
87
85
84
84
91
89
88
88
2
68
67
65
66
76
74
72
71
82
80
80
80
95
93
91
89
100
98
96
96
3
63
61
60
61
71
69
67
67
79
76
74
74
89
86
82
81
96
94
89
89
4
62
61
61
61
70
70
70
69
75
73
72
72
84
81
77
77
94
91
87
87
5
61
59
60
59
69
65
65
65
75
72
72
72
81
79
77
77
91
88
84
84
6
48
49
49
49
58
57
58
58
73
66
66
66
84
75
74
74
89
84
82
82
7
39
40
39
39
49
50
51
51
60
60
61
61
71
68
69
69
89
78
78
78
Outlet Sound Power, LWo [dB ref 10-12 watts]
8
32
34
32
33
45
43
44
43
54
53
54
55
63
62
64
64
74
72
73
73
LWiA
64
63
63
63
72
70
70
70
79
76
76
75
89
85
82
82
97
93
90
90
RPM
275
400
550
800
1116
% WOV
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
1
72
69
69
69
80
78
77
78
90
88
86
86
88
86
86
88
92
91
93
95
2
68
69
69
69
76
75
75
75
83
82
82
82
91
91
89
90
97
96
94
95
3
65
64
63
63
73
71
69
70
80
78
76
76
89
86
84
84
98
95
93
93
4
65
65
64
64
72
71
70
70
80
79
76
76
90
87
84
83
99
97
93
93
5
64
63
63
64
70
67
67
67
77
75
74
74
85
82
80
80
95
92
89
89
6
53
53
53
53
61
60
60
59
74
68
68
67
84
77
76
76
92
87
85
85
7
45
45
46
47
53
53
53
53
62
61
61
61
75
71
71
71
90
82
80
80
8
38
38
40
40
45
45
46
45
54
53
53
54
66
64
65
65
77
74
74
75
LWoA
67
66
66
66
74
72
71
71
82
80
78
78
91
87
85
85
100
97
94
94
Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not
include the effects of appurtenances (accessories).
The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA Standard 301. Values shown are for inlet LWi , LWi A and outlet LWo ,
LWo A sound power levels for installation type B: Free inlet, Ducted outlet. Ratings for inlet sound do not include the effects of duct end correction. Ratings for outlet
sound include the effects of duct end correction. The A-weighted sound power ratings shown have been calculated per AMCA Standard 301. The AMCA Certified
Ratings Seal applies to LWi A and LWo A values only.
40
QEI-36 Class II
10
Performance Data
Maximum Bhp = (Fan RPM / 381)3
CU
RVE
SY
STE
M
EF
TO
FT
HIS
635 kg.
1400 lbs.
10
4
3
5
5
2
Outlet Velocity (FPM) = CFM / 13.79
1
Tip Speed (FPM) = Fan RPM x 11.7
DO
0
0
0
% WOV = (CFM x 100) / (Fan RPM x 31.7)
80% WOV
10
TH
EL
Approximate Weight
(Less Motor & Drives)
10
5
NO
33
93
90% WOV
9
TO
1130 mm
15
77
44.5 in.
6
13
Wheel Diameter
7
83
2.2 kW
15
70% WOV
01
3 hp
20
13
Minimum Motor
Starting hp
8
Static Pressure (in. wg)
326T
60% WOV
11
Static Pressure (Pa x 100)
20
RPM
BHP
% WOV
3
Density 0.075 lb/ft
3
Density 1.2 kg/m
50% WOV
9
Specification Data
Maximum Motor
Frame Size
50
40
30
1377
82
0
SE
LE
CT
Maximum Fan RPM
65
1
T
30
25
20
15
10
5
45
40
35
Volume (cfm x 1000)
Imperial data — Metric data
60
40
20
0
3
Volume (m /hr x 1000)
Performance Data
STATIC PRESSURE (inches wg)
CFM
OV
0.5
1
2
3
4
5
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
6
RPM
BHP
7
RPM
BHP
8
RPM
BHP
RPM
BHP
15000
1088
534
2.08
598
3.39
716
6.58
832
10.3
941
14.4
16600
1204
579
2.53
636
3.91
745
7.23
852
11.2
955
15.4
1050
20.0
18200
1320
625
3.05
677
4.52
778
7.96
875
12.0
970
16.5
1064
21.3
1151
26.3
19800
1436
671
3.66
718
5.21
814
8.78
902
13.0
993
17.6
1078
22.6
1165
27.8
1244
33.3
21400
1552
718
4.35
760
5.99
850
9.71
935
14.0
1016
18.8
1099
24.0
1178
29.4
1258
35.1
1332
41.0
23000
1669
766
5.14
805
6.87
888
10.7
968
15.1
1045
20.1
1122
25.4
1198
31.0
1272
37.0
1346
43.0
24600
1785
814
6.02
851
7.86
928
11.9
1005
16.4
1077
21.5
1146
26.9
1221
32.7
1291
38.8
1360
45.2
26200
1901
862
7.02
897
8.96
969
13.8
1041
17.8
1110
22.9
1178
28.5
1244
34.5
1314
40.8
27800
2017
910
8.13
943
10.2
1010
14.6
1078
19.3
1146
24.6
1210
30.3
1272
36.4
1337
42.8
29400
2133
959
9.37
990
11.5
1052
16.1
1118
21.0
1182
26.4
1243
32.2
1305
38.4
1362
44.9
31000
2249
1008
10.7
1038
13.0
1095
17.7
1159
22.9
1219
28.4
1280
34.3
1337
40.6
32600
2365
1057
12.2
1085
14.6
1140
19.5
1200
24.8
1257
30.4
1316
36.5
1371
42.9
Shaded values show where Class I fan selections are more efficient than Class II.
Inlet Sound Power, LWi [dB ref 10-12 watts]
RPM
400
550
800
1100
1377
% WOV
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
1
84
81
78
76
85
82
78
79
82
79
78
82
87
82
83
85
92
87
89
92
2
73
71
69
68
84
80
77
78
94
92
89
90
94
91
88
88
95
90
89
91
3
4
69 69
67 66
64 65
63 65
78 76
74 73
71 71
71 71
86 86
84 84
79 80
80 79
98 95
95 92
91 88
90 87
103 101
98 98
94 95
94 94
5
70
66
65
65
76
73
72
72
83
80
78
78
91
88
85
84
97
94
91
90
6
60
57
56
55
77
65
64
63
87
76
75
73
91
84
82
81
94
90
88
87
7
50
47
47
47
60
57
56
55
74
68
68
67
91
79
77
77
100
88
84
84
Outlet Sound Power, LWo [dB ref 10-12 watts]
8
43
39
39
40
54
49
50
50
66
61
62
62
75
71
71
72
84
79
78
79
LWiA
73
69
68
67
81
76
75
74
91
86
83
82
98
94
91
90
105
100
96
96
RPM
400
550
800
1100
1377
% WOV
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
1
87
85
84
84
84
84
83
84
87
84
84
87
91
88
90
93
96
93
96
98
2
76
77
76
76
83
83
82
83
91
89
86
89
94
91
90
93
97
93
96
98
3
73
72
69
68
80
78
76
75
90
87
84
84
97
94
91
93
103
100
97
99
4
74
72
71
70
81
80
77
76
91
89
86
85
99
98
94
94
105
104
100
100
5
73
71
71
70
77
75
75
74
85
83
81
80
94
91
89
88
99
97
94
94
6
62
60
59
58
76
68
67
66
86
78
76
75
92
87
85
84
96
93
91
90
7
53
52
51
51
62
60
59
59
76
71
69
68
92
82
79
78
100
89
86
85
8
47
44
44
45
55
52
52
53
67
62
63
63
77
73
73
73
86
80
79
80
LWoA
76
74
73
73
83
80
79
78
92
89
86
86
100
98
94
94
107
104
100
100
Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not
include the effects of appurtenances (accessories).
The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA Standard 301. Values shown are for inlet LWi , LWi A and outlet LWo ,
LWo A sound power levels for installation type B: Free inlet, Ducted outlet. Ratings for inlet sound do not include the effects of duct end correction. Ratings for outlet
sound include the effects of duct end correction. The A-weighted sound power ratings shown have been calculated per AMCA Standard 301. The AMCA Certified
Ratings Seal applies to LWi A and LWo A values only.
41
QEI-40 Class I
Performance Data
6
5
49 in.
1245 mm
1500 lbs.
680 kg.
Approximate Weight
(Less Motor & Drives)
6
CU
RV
E
3
5
2
80% WOV
79
9
90% WOV
TH
E
Wheel Diameter
8
10
8
3.7 kW
4
94
5 hp
10
13
Minimum Motor
Starting hp
Static Pressure (in. wg)
324T
70% WOV
15
10
Static Pressure (Pa x 100)
12
Maximum Motor
Frame Size
60% WOV
SY
ST
EM
Specification Data
RPM
BHP
% WOV
3
Density 0.075 lb/ft
Density 1.2 kg/m3
40
30
25
FT
HIS
1013
LE
FT
O
Maximum Fan RPM
14
8
TO
4
69
Maximum Bhp = (Fan RPM / 324)
1
Outlet Velocity (FPM) = CFM / 16.77
EL
EC
T
3
2
2
N
Tip Speed (FPM) = Fan RPM x 12.8
OT
55
4
S
40
8
DO
0
0
0
% WOV = (CFM x 100) / (Fan RPM x 48.1)
5
10
15
20
25
30
35
40
45
50
Volume (cfm x 1000)
Imperial data — Metric data
0
10
20
30
40
50
60
70
80
3
Volume (m /hr x 1000)
Performance Data
STATIC PRESSURE (inches wg)
CFM
OV
0.25
0.5
1
1.5
RPM
BHP
RPM
BHP
RPM
BHP
2
RPM
BHP
2.5
RPM
BHP
3
3.5
RPM
BHP
RPM
BHP
4
RPM
BHP
RPM
BHP
12500
745
312
0.77
365
1.39
462
2.86
15200
906
359
1.08
403
1.75
488
3.39
565
5.23
17900
1067
408
1.49
445
2.22
520
3.98
590
6.00
654
8.16
20600
1228
459
2.03
491
2.82
557
4.68
620
6.86
681
9.20
735
11.7
795
14.4
23300
1389
511
2.70
540
3.56
596
5.53
654
7.81
710
10.4
764
13.0
813
15.7
863
18.7
915
21.9
26000
1550
565
3.51
590
4.47
641
6.56
693
8.94
744
11.6
794
14.4
842
17.4
887
20.4
930
23.5
28700
1711
619
4.50
641
5.54
687
7.77
733
10.2
781
13.0
827
16.0
872
19.1
916
22.4
958
25.7
31400
1872
673
5.67
693
6.81
735
9.17
777
11.8
820
14.6
864
17.7
906
21.0
947
24.4
986
28.0
34100
2033
727
7.05
746
8.27
785
10.8
824
13.5
861
16.4
903
19.7
941
23.0
981
26.6
36800
2194
782
8.64
799
9.96
835
12.7
871
15.5
907
18.6
942
21.8
981
25.3
39500
2355
837
10.5
853
11.9
886
14.8
919
17.7
953
21.0
986
24.3
42200
2516
892
12.6
907
14.1
937
17.1
969
20.3
1000
23.6
Inlet Sound Power, LWi [dB ref 10-12 watts]
RPM
250
350
500
700
1013
% WOV
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
1
71
69
65
68
76
73
71
71
86
82
81
81
90
88
86
86
94
91
90
90
2
68
67
66
66
75
73
71
70
82
81
80
80
94
92
89
88
101
99
97
97
3
64
62
61
62
71
69
68
68
79
76
75
74
88
85
81
80
96
94
90
90
4
63
62
62
62
70
69
69
69
76
74
73
73
84
81
77
77
94
92
88
88
5
60
59
59
59
66
63
64
63
76
72
72
72
82
78
76
76
91
88
85
85
6
48
49
48
48
56
56
57
57
72
66
66
66
82
74
73
73
90
84
82
82
7
39
40
39
39
49
49
50
50
60
60
61
61
69
67
68
68
87
78
78
78
Outlet Sound Power, LWo [dB ref 10-12 watts]
8
32
34
32
33
44
42
42
42
54
53
54
55
62
61
63
63
72
72
73
73
LWiA
64
63
63
63
71
69
69
69
80
77
76
76
88
84
82
81
97
94
91
91
RPM
250
350
500
700
1013
% WOV
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
1
72
70
70
70
79
77
77
78
90
88
87
86
89
88
87
88
94
92
94
95
2
69
69
69
69
76
74
74
74
83
82
82
82
91
90
88
89
98
97
95
96
3
66
65
64
64
73
71
69
70
81
79
77
77
89
86
84
84
99
96
94
94
4
66
65
65
65
72
70
69
70
81
79
77
76
89
86
83
83
99
97
93
93
5
63
62
63
63
68
66
65
65
77
75
74
73
85
81
79
79
95
92
89
89
6
52
53
53
53
60
59
59
58
73
68
68
67
82
76
75
75
93
87
85
85
7
45
45
46
46
51
51
52
51
61
61
61
61
73
69
69
70
89
81
80
80
8
38
38
40
40
44
44
44
44
54
53
53
54
65
62
64
64
76
73
74
75
LWoA
67
66
66
67
73
71
70
71
82
80
78
78
90
87
85
84
101
97
94
95
Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not
include the effects of appurtenances (accessories).
The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA Standard 301. Values shown are for inlet LWi , LWi A and outlet LWo ,
LWo A sound power levels for installation type B: Free inlet, Ducted outlet. Ratings for inlet sound do not include the effects of duct end correction. Ratings for outlet
sound include the effects of duct end correction. The A-weighted sound power ratings shown have been calculated per AMCA Standard 301. The AMCA Certified
Ratings Seal applies to LWi A and LWo A values only.
42
QEI-40 Class II
10
Performance Data
1251
862 kg.
1900 lbs.
10
YS
TEM
CU
RVE
5
4
10
3
Maximum Bhp = (Fan RPM / 324)
5
2
Outlet Velocity (FPM) = CFM / 16.77
1
Tip Speed (FPM) = Fan RPM x 12.8
DO
0
0
0
% WOV = (CFM x 100) / (Fan RPM x 42.4)
10
06
90% WOV
87
9
TO
5
3
69
SE
LE
CT
Approximate Weight
(Less Motor & Drives)
51
1245 mm
12
49 in.
80% WOV
07
Wheel Diameter
20
6
11
5.5 kW
70% WOV
92
71⁄2 hp
15
7
11
Minimum Motor
Starting hp
60% WOV
FT
HIS
S
364T
30
8
Static Pressure (in. wg)
Maximum Motor
Frame Size
Static Pressure (Pa x 100)
20
EF
TO
Specification Data
RPM
BHP
% WOV
3
Density 0.075 lb/ft
3
Density 1.2 kg/m
50% WOV
TH
EL
Maximum Fan RPM
60
50
40
9
5
8
55
4
T
NO
15
10
30
25
20
50
45
40
35
55
Volume (cfm x 1000)
Imperial data — Metric data
80
60
40
20
0
3
Volume (m /hr x 1000)
Performance Data
STATIC PRESSURE (inches wg)
CFM
OV
0.5
1
2
3
4
5
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
6
RPM
BHP
7
RPM
BHP
8
RPM
BHP
RPM
BHP
18000
1077
481
2.48
540
4.06
649
7.91
754
12.4
853
17.3
20000
1197
523
3.03
575
4.70
675
8.71
772
13.5
866
18.6
953
24.1
22000
1317
566
3.68
613
5.45
705
9.61
794
14.5
880
20.0
966
25.7
1045
31.8
24000
1437
609
4.43
652
6.31
739
10.7
819
15.7
902
21.3
979
27.4
1058
33.7
1130
40.4
26000
1556
653
5.30
691
7.29
773
11.8
849
17.0
923
22.8
999
29.1
1071
35.7
1143
42.6
1210
49.8
28000
1676
698
6.29
733
8.40
808
13.1
881
18.4
950
24.4
1021
30.9
1089
37.8
1156
44.9
1223
52.3
30000
1796
743
7.41
776
9.65
846
14.6
915
20.1
981
26.2
1043
32.7
1111
39.8
1174
47.3
1236
55.0
32000
1916
788
8.67
820
11.0
884
16.2
949
21.8
1011
28.1
1073
34.9
1132
42.0
1195
49.7
34000
2035
833
10.1
863
12.6
923
17.9
984
23.7
1046
30.2
1104
37.1
1160
44.5
1217
52.2
36000
2155
879
11.7
907
14.3
963
19.8
1022
25.9
1080
32.5
1135
39.5
1190
47.1
1242
55.0
38000
2275
925
13.4
951
16.2
1003
21.9
1060
28.2
1114
34.9
1169
42.2
1221
49.8
40000
2395
971
15.3
996
18.2
1046
24.2
1099
30.7
1150
37.6
1203
45.0
Shaded values show where Class I fan selections are more efficient than Class II.
Inlet Sound Power, LWi [dB ref 10-12 watts]
RPM
350
500
700
1000
1251
% WOV
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
1
82
79
77
75
87
83
80
81
85
82
80
84
89
85
85
87
93
89
90
93
2
73
70
68
67
84
80
77
77
93
90
87
88
96
93
90
89
97
92
91
93
3
4
69 69
67 67
64 66
63 65
78 77
75 74
72 73
72 72
86 85
84 83
80 80
80 79
98 95
95 92
92 89
90 88
104 101
99 99
95 95
95 94
5
68
64
63
63
77
73
72
72
84
80
78
77
92
88
86
85
97
94
91
90
6
58
55
54
54
75
65
64
63
85
75
74
72
92
84
82
81
96
90
88
88
7
49
46
46
46
60
56
56
55
73
67
67
66
90
79
77
77
99
87
84
84
Outlet Sound Power, LWo [dB ref 10-12 watts]
8
42
38
38
38
54
49
50
50
64
60
61
62
74
70
71
72
83
78
78
79
LWiA
72
68
67
66
81
76
75
75
90
85
82
82
99
94
91
90
105
100
97
96
RPM
350
500
700
1000
1251
% WOV
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
1
85
83
83
82
85
85
85
85
88
85
85
87
92
89
91
94
97
94
97
99
2
76
75
74
74
84
83
82
82
91
89
86
88
95
92
91
93
99
95
97
99
3
73
72
70
68
81
80
77
76
90
87
84
84
98
96
93
94
104
101
98
100
4
5
74 71
72 68
71 68
70 68
81 78
80 75
78 75
77 74
90 86
88 82
85 80
84 79
99 94
98 92
94 89
94 88
105 100
104 97
100 94
100 94
6
61
58
57
57
75
68
67
66
84
77
75
74
93
88
85
84
97
94
91
90
7
52
50
50
50
62
60
59
59
74
69
68
67
91
81
79
78
99
89
86
85
8
46
42
43
43
54
51
52
53
65
61
62
62
76
73
73
74
85
80
79
80
LWoA
75
73
72
72
83
81
79
78
92
88
85
85
101
98
95
94
107
104
101
100
Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not
include the effects of appurtenances (accessories).
The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA Standard 301. Values shown are for inlet LWi , LWi A and outlet LWo ,
LWo A sound power levels for installation type B: Free inlet, Ducted outlet. Ratings for inlet sound do not include the effects of duct end correction. Ratings for outlet
sound include the effects of duct end correction. The A-weighted sound power ratings shown have been calculated per AMCA Standard 301. The AMCA Certified
Ratings Seal applies to LWi A and LWo A values only.
43
QEI-44 Class I
Performance Data
6
5
6
CU
RV
E
907 kg.
10
2
5
YS
TE
M
2000 lbs.
3
OF
Approximate Weight
(Less Motor & Drives)
8
90% WOV
TH
4
3
0
1378 mm
5
54.25 in.
58
9
TO
Maximum Bhp = (Fan RPM / 273)
2
2
T
NO
DO
Tip Speed (FPM) = Fan RPM x 14.2
0
0
0
% WOV = (CFM x 100) / (Fan RPM x 65.3)
46
LE
CT
1
Outlet Velocity (FPM) = CFM / 20.49
80% WOV
91
Wheel Diameter
4
3
5.5 kW
10
85
71⁄2 hp
70% WOV
74
Minimum Motor
Starting hp
20
E
326T
Static Pressure (in. wg)
Maximum Motor
Frame Size
Static Pressure (Pa x 100)
12
60% WOV
TH
IS
S
Specification Data
RPM
BHP
% WOV
3
Density 0.075 lb/ft
Density 1.2 kg/m3
40
30
FT
915
LE
Maximum Fan RPM
14
5
8
SE
34
5
10
15
20
25
30
35
40
45
50
55
60
Volume (cfm x 1000)
Imperial data — Metric data
0
10
20
30
40
50
60
70
80
90
100
3
Volume (m /hr x 1000)
Performance Data
STATIC PRESSURE (inches wg)
CFM
OV
0.25
0.5
1
1.5
RPM
BHP
RPM
BHP
RPM
BHP
2
RPM
BHP
2.5
RPM
BHP
3
3.5
RPM
BHP
RPM
BHP
4
RPM
BHP
RPM
BHP
15200
741
280
0.93
329
1.69
417
3.49
18500
902
322
1.30
362
2.12
440
4.12
510
6.39
21800
1063
367
1.81
400
2.69
468
4.84
532
7.31
590
9.96
25100
1224
413
2.45
442
3.42
501
5.70
559
8.36
613
11.2
663
14.2
717
17.6
28400
1386
459
3.26
485
4.32
537
6.72
589
9.51
640
12.6
689
15.9
733
19.2
779
22.8
826
26.8
31700
1547
507
4.25
531
5.42
577
7.97
624
10.9
670
14.1
715
17.6
759
21.2
800
24.9
838
28.7
35000
1708
556
5.44
577
6.72
619
9.44
660
12.5
704
15.8
745
19.5
786
23.3
826
27.3
864
31.3
38300
1869
605
6.86
623
8.25
661
11.1
700
14.3
739
17.8
777
21.5
816
25.6
853
29.8
889
34.1
41600
2030
654
8.53
670
10.0
706
13.1
741
16.5
775
20.0
813
23.9
847
28.0
884
32.4
44900
2191
703
10.5
719
12.1
751
15.4
784
18.9
816
22.6
849
26.6
883
30.9
48200
2352
753
12.7
767
14.4
797
17.9
827
21.6
858
25.5
888
29.6
51500
2513
802
15.2
816
17.0
843
20.8
872
24.6
901
28.7
Inlet Sound Power, LWi [dB ref 10-12 watts]
RPM
225
325
450
650
915
% WOV
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
1
71
70
66
68
77
75
73
73
86
83
82
82
92
91
89
88
96
94
93
93
2
68
67
65
66
76
74
72
71
83
81
80
79
95
93
90
88
101
99
96
96
3
64
63
62
63
72
71
70
70
79
77
75
75
89
86
82
81
97
95
90
90
4
64
63
63
63
72
70
70
70
77
75
74
74
85
82
79
79
95
92
88
88
5
59
58
58
58
67
64
64
64
76
72
72
72
84
79
78
78
92
88
86
86
6
47
48
48
47
56
57
58
57
71
66
66
66
82
74
74
74
91
84
82
82
7
39
40
39
39
50
49
51
50
60
60
60
61
70
68
69
69
86
78
78
78
Outlet Sound Power, LWo [dB ref 10-12 watts]
8
32
34
32
33
45
42
43
42
54
53
54
54
63
62
64
64
71
71
74
74
LWiA
64
63
63
63
72
70
70
70
80
77
76
76
89
85
83
82
98
94
91
91
RPM
225
325
450
650
915
% WOV
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
1
72
71
71
71
80
79
78
79
90
88
87
87
91
90
89
90
95
94
95
96
2
69
69
68
69
77
75
74
75
84
83
82
82
92
91
89
90
99
98
96
97
3
4
67 67
66 66
65 66
65 66
74 74
73 71
71 71
71 71
82 81
80 80
78 77
77 77
91 90
88 87
86 84
85 84
100 100
97 97
95 93
95 93
5
62
62
62
62
69
66
66
66
78
75
74
73
86
82
80
80
95
92
89
89
6
52
52
53
53
60
59
59
59
72
68
68
67
83
77
76
76
93
88
85
85
7
45
45
46
46
52
52
52
52
61
60
61
61
74
70
70
71
88
81
80
80
8
38
38
39
40
45
44
45
45
53
52
53
54
65
63
65
65
75
73
74
75
LWoA
67
67
66
67
74
72
71
72
82
80
79
78
91
88
86
86
101
98
95
95
Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not
include the effects of appurtenances (accessories).
The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA Standard 301. Values shown are for inlet LWi , LWi A and outlet LWo ,
LWo A sound power levels for installation type B: Free inlet, Ducted outlet. Ratings for inlet sound do not include the effects of duct end correction. Ratings for outlet
sound include the effects of duct end correction. The A-weighted sound power ratings shown have been calculated per AMCA Standard 301. The AMCA Certified
Ratings Seal applies to LWi A and LWo A values only.
44
QEI-44 Class II
10
Performance Data
1129
9
10
UR
VE
TEM
C
4
10
3
3
Maximum Bhp = (Fan RPM / 274)
HIS
SY
S
1043 kg.
FT
2300 lbs.
5
TH
EL
EF
TO
Approximate Weight
(Less Motor & Drives)
5
2
5
1
Tip Speed (FPM) = Fan RPM x 14.2
DO
0
0
0
85
0
5
90% WOV
74
3
59
0
SE
L
Outlet Velocity (FPM) = CFM / 20.49
% WOV = (CFM x 100) / (Fan RPM x 57.5)
80% WOV
TO
1378 mm
20
71
54.25 in.
6
29
Wheel Diameter
15
11
7.5 kW
70% WOV
6
10 hp
30
7
10
Minimum Motor
Starting hp
8
Static Pressure (in. wg)
365T
60% WOV
93
Static Pressure (Pa x 100)
20
Maximum Motor
Frame Size
40
EC
T
Specification Data
RPM
BHP
% WOV
3
Density 0.075 lb/ft
3
Density 1.2 kg/m
75
60
Maximum Fan RPM
46
T
NO
8
15
10
20
30
25
35
50
45
40
60
55
65
Volume (cfm x 1000)
Imperial data — Metric data
0
100
80
60
40
20
3
Volume (m /hr x 1000)
Performance Data
STATIC PRESSURE (inches wg)
CFM
OV
0.5
1
2
3
4
5
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
6
RPM
BHP
7
RPM
BHP
8
RPM
BHP
RPM
BHP
22000
1074
434
3.02
487
4.95
585
9.67
681
15.2
770
21.2
24500
1196
472
3.71
519
5.75
609
10.7
698
16.5
782
22.8
861
29.6
27000
1319
512
4.52
554
6.70
637
11.8
717
17.8
795
24.5
873
31.6
944
39.0
29500
1441
552
5.46
590
7.78
668
13.1
741
19.3
815
26.2
885
33.7
956
41.4
1021
49.6
32000
1563
592
6.55
626
9.00
700
14.5
769
20.9
835
28.0
903
35.8
968
44.0
1033
52.4
1094
61.1
34500
1685
633
7.80
665
10.4
732
16.2
798
22.8
860
30.1
923
38.0
985
46.5
1045
55.3
1106
64.4
37000
1807
675
9.21
705
12.0
767
18.0
829
24.8
888
32.3
945
40.4
1005
49.1
1062
58.2
1118
67.7
39500
1929
716
10.8
745
13.7
803
20.0
861
27.0
917
34.7
972
43.0
1025
51.8
1082
61.3
42000
2051
758
12.6
785
15.7
839
22.3
894
29.4
949
37.4
1000
45.8
1051
54.9
1102
64.4
44500
2173
800
14.6
825
17.8
875
24.7
928
32.2
980
40.2
1029
48.9
1079
58.2
1126
67.9
47000
2296
842
16.8
866
20.2
913
27.4
963
35.1
1012
43.3
1061
52.3
1107
61.7
49500
2418
885
19.2
907
22.8
952
30.3
999
38.3
1046
46.7
1093
55.8
Shaded values show where Class I fan selections are more efficient than Class II.
Inlet Sound Power, LWi [dB ref 10-12 watts]
RPM
325
450
650
900
1129
% WOV
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
1
82
79
77
75
89
85
82
82
88
85
83
86
91
87
86
88
95
90
91
94
2
74
71
69
68
83
80
77
77
93
91
87
88
98
95
91
90
99
95
92
94
3
4
70 71
68 68
66 67
65 67
79 78
75 75
73 74
72 73
88 86
85 84
81 81
81 80
99 95
96 92
92 89
91 88
104 102
100 99
96 95
96 95
5
69
64
64
63
78
72
72
71
86
81
79
78
92
88
86
85
98
95
92
91
6
58
55
55
54
73
64
64
62
85
75
74
73
94
84
82
82
97
91
88
88
7
49
46
46
46
60
56
56
55
73
68
68
67
88
78
77
77
97
87
84
84
Outlet Sound Power, LWo [dB ref 10-12 watts]
8
43
38
38
39
53
49
50
50
65
61
62
63
72
70
71
72
82
78
78
80
LWiA
73
69
68
67
82
77
75
75
91
86
83
83
99
94
91
91
105
100
97
97
RPM
325
450
650
900
1129
% WOV
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
1
85
84
83
83
87
86
86
86
90
87
86
89
93
90
92
94
98
95
98
99
2
77
76
75
75
84
83
81
82
92
90
87
89
96
93
91
93
101
97
98
100
3
75
73
71
70
82
81
78
77
92
89
86
86
100
98
94
95
105
103
99
101
4
5
75 71
74 69
73 68
72 68
81 79
80 75
79 74
77 73
91 87
89 83
86 81
85 80
99 95
97 92
94 89
94 89
105 100
104 98
100 95
100 94
6
61
59
58
58
73
67
66
65
85
78
76
74
94
88
85
84
99
94
91
90
7
53
51
51
51
62
59
59
59
75
70
69
68
89
81
79
79
98
88
86
85
8
46
43
44
44
54
51
52
52
66
61
62
63
75
72
73
74
84
80
79
80
LWoA
76
74
73
73
83
81
79
78
93
89
86
86
101
98
95
95
107
104
101
101
Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not
include the effects of appurtenances (accessories).
The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA Standard 301. Values shown are for inlet LWi , LWi A and outlet LWo ,
LWo A sound power levels for installation type B: Free inlet, Ducted outlet. Ratings for inlet sound do not include the effects of duct end correction. Ratings for outlet
sound include the effects of duct end correction. The A-weighted sound power ratings shown have been calculated per AMCA Standard 301. The AMCA Certified
Ratings Seal applies to LWi A and LWo A values only.
45
QEI-49 Class I
Performance Data
6
1524 mm
Approximate Weight
(Less Motor & Drives)
1089 kg.
2400 lbs.
8
6
3
2
7½
Maximum Bhp = (Fan RPM / 231)
SE
LE
CT
3
1
2
Tip Speed (FPM) = Fan RPM x 15.7
DO
0
0
0
% WOV = (CFM x 100) / (Fan RPM x 88.4)
6
90% WOV
57
0
TO
4
3
Outlet Velocity (FPM) = CFM / 24.85
80% WOV
67
TH
E
60 in.
Static Pressure (in. wg)
Wheel Diameter
15
1
7.5 kW
4
79
10 hp
10
8
Minimum Motor
Starting hp
70% WOV
82
Static Pressure (Pa x 100)
364T
25
CU
RVE
5
12
Maximum Motor
Frame Size
60% WOV
SY
STE
M
Specification Data
RPM
BHP
% WOV
3
Density 0.075 lb/ft
Density 1.2 kg/m3
50
40
FT
HIS
828
LE
FT
O
Maximum Fan RPM
14
T
NO
45
3
33
4
10
20
30
40
50
60
70
80
Volume (cfm x 1000)
Imperial data — Metric data
0
20
40
60
80
100
120
3
Volume (m /hr x 1000)
Performance Data
STATIC PRESSURE (inches wg)
CFM
OV
0.25
0.5
1
1.5
RPM
BHP
RPM
BHP
RPM
BHP
2
RPM
BHP
2.5
RPM
BHP
3
3.5
RPM
BHP
RPM
BHP
4
RPM
BHP
RPM
BHP
18000
724
248
1.08
293
2.00
375
4.18
22000
885
285
1.52
323
2.51
394
4.91
459
7.67
26000
1046
325
2.10
356
3.16
418
5.77
477
8.73
532
12.0
30000
1207
366
2.85
393
4.02
448
6.77
500
10.0
551
13.4
597
17.1
647
21.2
34000
1368
407
3.79
432
5.06
479
7.98
527
11.4
574
15.1
618
19.0
659
23.1
703
27.6
38000
1529
450
4.95
472
6.35
514
9.43
558
13.0
601
16.9
641
21.1
682
25.5
719
29.9
755
34.6
42000
1690
494
6.34
513
7.88
552
11.2
590
14.8
629
18.9
668
23.3
705
28.0
742
32.8
776
37.7
46000
1851
538
8.01
554
9.67
590
13.2
625
17.0
661
21.3
696
25.8
732
30.7
766
35.8
799
41.0
50000
2012
582
9.96
597
11.8
630
15.5
662
19.5
694
23.9
728
28.6
759
33.6
793
38.9
824
44.4
54000
2173
626
12.2
640
14.2
670
18.1
700
22.4
730
26.9
760
31.7
792
36.9
820
42.3
58000
2334
670
14.8
683
16.9
711
21.1
739
25.5
767
30.3
794
35.2
823
40.6
62000
2494
714
17.8
727
20.0
752
24.5
779
29.2
805
34.1
Inlet Sound Power, LWi [dB ref 10-12 watts]
RPM
200
300
425
575
828
% WOV
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
1
72
70
67
69
79
77
75
74
88
85
84
84
94
93
91
90
98
96
95
95
2
68
66
65
66
76
74
72
72
84
82
81
81
94
92
88
87
101
99
96
96
3
64
63
63
63
73
73
72
71
81
78
76
76
89
86
81
81
98
96
91
91
4
64
63
63
63
73
71
71
70
79
77
76
76
84
82
79
79
95
93
89
89
5
57
57
57
56
67
65
65
65
78
74
73
73
85
79
78
77
92
89
86
86
6
46
47
47
46
57
57
58
58
71
67
68
68
80
74
74
73
93
84
83
83
7
38
40
38
39
50
50
51
51
61
61
62
62
69
67
68
68
85
78
78
78
Outlet Sound Power, LWo [dB ref 10-12 watts]
8
31
34
31
33
46
43
44
43
55
54
55
56
62
61
63
64
70
71
74
74
LWiA
64
63
63
63
73
71
71
71
82
78
78
78
89
85
82
82
99
94
91
91
RPM
200
300
425
575
828
% WOV
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
1
72
72
71
71
81
80
79
80
91
89
89
88
92
92
90
91
97
96
96
97
2
3
4
69 67 67
69 67 67
68 66 67
68 66 67
78 76 75
76 74 72
75 72 72
75 73 72
85 84 82
84 82 81
83 80 79
83 79 79
92 91 89
90 88 86
88 86 84
89 86 83
100 102 100
98 99 97
96 96 94
97 96 94
5
60
60
60
61
69
67
67
67
80
76
75
75
87
82
80
80
96
92
90
90
6
51
52
52
52
61
60
60
60
73
69
69
69
81
76
76
75
94
88
86
85
7
44
44
45
46
53
52
53
53
62
61
62
62
73
69
70
70
87
81
80
81
8
37
37
39
39
45
45
45
45
55
53
54
55
64
62
64
65
74
73
74
75
LWoA
67
67
66
67
75
73
72
73
84
82
80
80
91
87
86
85
102
98
95
95
Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not
include the effects of appurtenances (accessories).
The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA Standard 301. Values shown are for inlet LWi , LWi A and outlet LWo ,
LWo A sound power levels for installation type B: Free inlet, Ducted outlet. Ratings for inlet sound do not include the effects of duct end correction. Ratings for outlet
sound include the effects of duct end correction. The A-weighted sound power ratings shown have been calculated per AMCA Standard 301. The AMCA Certified
Ratings Seal applies to LWi A and LWo A values only.
46
QEI-49 Class II
10
Performance Data
1020
10
CU
RVE
TH
IS
SY
ST
EM
1406 kg.
20
OF
3100 lbs.
Approximate Weight
(Less Motor & Drives)
5
4
3
10
3
5
LE
CT
2
Outlet Velocity (FPM) = CFM / 24.85
1
Tip Speed (FPM) = Fan RPM x 15.7
DO
0
0
0
% WOV = (CFM x 100) / (Fan RPM x 77.8)
9
71
N
90% WOV
7
62
6
49
7
SE
Maximum Bhp = (Fan RPM / 231)
78
EF
T
1524 mm
3
60 in.
80% WOV
97
Wheel Diameter
30
6
20
11 kW
70% WOV
7
10
15 hp
15
50% WOV
40
0
Minimum Motor
Starting hp
Static Pressure (in. wg)
405T
8
85
Static Pressure (Pa x 100)
20
TH
EL
Specification Data
Maximum Motor
Frame Size
60% WOV
TO
Maximum Fan RPM
RPM
BHP
% WOV
3
Density 0.075 lb/ft
3
Density 1.2 kg/m
100
75
50
9
OT
60
50
40
30
20
10
80
70
Volume (cfm x 1000)
Imperial data — Metric data
0
100
80
60
40
20
120
3
Volume (m /hr x 1000)
Performance Data
STATIC PRESSURE (inches wg)
CFM
OV
0.5
1
2
3
4
5
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
6
RPM
BHP
7
RPM
BHP
8
RPM
BHP
RPM
BHP
27000
1078
393
3.72
441
6.09
530
11.9
616
18.7
697
26.0
30000
1198
427
4.55
470
7.05
551
13.1
631
20.2
707
28.0
778
36.2
33000
1317
462
5.52
501
8.18
576
14.4
648
21.8
719
30.0
789
38.6
853
47.7
36000
1437
498
6.65
533
9.48
604
16.0
669
23.5
736
32.0
800
41.1
864
50.6
923
60.5
39000
1557
534
7.95
565
10.9
631
17.7
694
25.5
754
34.2
816
43.6
874
53.6
933
63.9
988
74.6
42000
1677
570
9.43
599
12.6
660
19.6
719
27.7
776
36.6
834
46.3
890
56.6
944
67.4
999
78.5
45000
1797
607
11.1
634
14.5
691
21.8
748
30.1
801
39.2
852
49.1
907
59.7
959
70.9
1010
82.5
48000
1916
644
13.0
670
16.6
722
24.2
775
32.7
826
42.1
876
52.3
925
63.0
976
74.5
51000
2036
681
15.1
705
18.9
754
26.9
804
35.6
854
45.3
901
55.6
947
66.7
994
78.3
54000
2156
718
17.5
741
21.4
786
29.8
835
38.8
882
48.7
927
59.2
972
70.6
1014
82.4
57000
2276
755
20.1
777
24.2
820
32.9
866
42.3
910
52.3
955
63.2
997
74.7
60000
2396
793
23.0
814
27.3
854
36.4
898
46.1
940
56.4
983
67.5
Shaded values show where Class I fan selections are more efficient than Class II.
Inlet Sound Power, LWi [dB ref 10-12 watts]
RPM
300
425
575
825
1020
% WOV
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
1
82
79
77
76
91
87
84
84
91
88
86
88
93
89
88
90
96
91
92
94
2
3
4
75 72 73
72 69 70
69 67 69
68 66 68
85 81 79
81 77 77
78 75 76
78 74 75
92 88 86
89 86 84
86 82 81
87 81 80
100 99 96
97 97 93
93 93 90
92 92 89
102 105 102
97 101 99
94 97 96
95 97 95
5
69
65
64
63
81
74
73
72
88
80
79
77
93
89
87
86
98
95
92
91
6
58
56
55
55
73
65
65
63
83
74
74
72
95
85
83
82
99
91
89
88
7
50
47
47
47
61
57
57
57
72
67
67
66
87
78
77
78
96
86
84
84
Outlet Sound Power, LWo [dB ref 10-12 watts]
8
44
39
39
39
55
50
51
51
64
60
61
62
71
70
71
73
80
77
78
80
LWiA
73
70
69
68
83
78
77
76
91
86
83
82
100
95
92
91
105
101
97
97
RPM
300
425
575
825
1020
% WOV
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
1
2
3
4
5
6
85 78 76 77 71 61
84 77 75 75 69 59
83 75 73 75 68 59
83 75 71 74 68 58
89 85 84 83 81 74
88 84 83 82 76 69
88 83 80 80 75 68
88 83 79 79 74 67
91 93 93 90 88 83
89 90 90 88 83 77
87 87 87 85 81 75
90 88 86 84 80 74
95 98 101 99 95 96
92 95 99 98 93 88
93 92 96 95 90 85
96 94 97 94 89 84
99 103 106 105 101 100
99 104 104 98 94
96
98 99 101 100 95 91
100 101 102 100 95 90
7
53
51
51
51
63
60
60
60
74
69
68
68
89
81
79
79
97
88
86
85
8
47
44
44
45
55
52
53
54
64
60
62
63
74
72
73
74
83
79
79
80
LWoA
77
75
74
74
85
82
81
80
93
89
86
86
102
99
96
95
107
104
101
101
Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not
include the effects of appurtenances (accessories).
The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA Standard 301. Values shown are for inlet LWi , LWi A and outlet LWo ,
LWo A sound power levels for installation type B: Free inlet, Ducted outlet. Ratings for inlet sound do not include the effects of duct end correction. Ratings for outlet
sound include the effects of duct end correction. The A-weighted sound power ratings shown have been calculated per AMCA Standard 301. The AMCA Certified
Ratings Seal applies to LWi A and LWo A values only.
47
QEI-54 Class I
Performance Data
6
752
5
1315 kg.
2900 lbs.
6
CU
RV
E
M
SY
ST
E
3
TH
IS
1676 mm
10
2
4
LE
CT
Maximum Bhp = (Fan RPM / 197)
1
2
Tip Speed (FPM) = Fan RPM x 17.3
DO
0
0
0
% WOV = (CFM x 100) / (Fan RPM x 118)
61
3
T
NO
6
42
5
33
SE
10
90% WOV
53
TO
5
3
Outlet Velocity (FPM) = CFM / 30.46
80% WOV
OF
66 in.
LE
FT
Wheel Diameter
8
20
2
7.5 kW
4
5
10 hp
10
75
Minimum Motor
Starting hp
70% WOV
Static Pressure (in. wg)
365T
30
67
Static Pressure (Pa x 100)
12
Approximate Weight
(Less Motor & Drives)
RPM
70
BHP
% WOV
Density 0.075 lb/ft3
3
Density 1.2 kg/m
60
60% WOV
Specification Data
Maximum Motor
Frame Size
50
40
TH
E
Maximum Fan RPM
14
7
20
30
40
50
60
70
80
90
Volume (cfm x 1000)
Imperial data — Metric data
0
2
4
6
8
10
12
14
3
Volume (m /hr x 1000)
Performance Data
STATIC PRESSURE (inches wg)
CFM
OV
0.25
0.5
1
1.5
RPM
BHP
RPM
BHP
RPM
BHP
2
RPM
BHP
2.5
3
RPM
BHP
RPM
BHP
3.5
RPM
BHP
4
RPM
BHP
RPM
BHP
23000
755
234
1.43
272
2.56
343
5.24
27800
912
268
1.99
300
3.21
363
6.20
420
9.54
32600
1070
304
2.73
331
4.05
386
7.25
439
10.9
486
14.8
536
19.4
37400
1227
341
3.68
365
5.13
414
8.50
460
12.5
505
16.7
546
21.2
590
26.2
42200
1385
379
4.87
400
6.44
442
10.0
485
14.1
527
18.8
567
23.6
603
28.5
641
33.9
679
39.7
47000
1543
418
6.32
437
8.05
475
11.8
514
16.2
551
20.9
588
26.1
624
31.5
658
36.9
689
42.6
51800
1700
457
8.06
474
9.94
508
14.0
542
18.4
578
23.4
612
28.8
646
34.5
679
40.4
710
46.4
56600
1858
497
10.1
511
12.2
543
16.4
574
21.1
607
26.3
638
31.8
670
37.8
701
44.0
730
50.4
61400
2015
536
12.5
550
14.7
579
19.3
608
24.2
636
29.5
667
35.3
695
41.3
725
47.8
66200
2173
576
15.3
589
17.7
616
22.6
643
27.7
669
33.2
696
39.1
725
45.4
751
52.0
71000
2330
616
18.5
628
21.1
653
26.2
678
31.6
703
37.4
727
43.4
75800
2488
656
22.2
667
24.9
690
30.4
714
36.0
737
42.0
Inlet Sound Power, LWi [dB ref 10-12 watts]
RPM
200
275
375
525
752
% WOV
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
1
2
75 71
73 69
71 68
72 69
80 77
78 74
76 72
76 72
87 84
85 82
84 80
84 80
96 94
95 92
93 88
91 87
100 101
98 99
97 95
97 95
3
67
66
66
66
74
74
73
73
80
78
76
76
89
86
82
81
98
96
92
92
4
67
66
66
66
74
71
71
71
79
77
76
76
85
83
80
80
96
93
89
89
5
60
60
60
59
66
65
65
65
79
73
73
72
87
79
78
78
93
89
87
87
6
49
50
49
49
57
57
58
58
69
66
67
67
79
74
74
74
94
84
83
83
7
41
43
41
42
51
50
51
51
60
60
61
61
69
67
69
69
84
78
79
79
Outlet Sound Power, LWo [dB ref 10-12 watts]
8
34
37
34
36
47
43
44
43
55
53
54
55
62
61
64
64
69
71
74
74
LWiA
67
66
66
66
74
72
71
71
81
78
77
77
90
85
83
83
99
95
92
92
RPM
200
275
375
525
752
% WOV
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
1
75
74
74
74
82
81
80
81
90
88
88
88
94
93
91
93
98
98
97
98
2
3
4
72 70 70
71 69 70
71 69 70
71 69 70
78 77 75
76 75 73
75 74 72
75 74 73
85 84 82
83 83 81
82 80 79
82 80 79
93 92 89
91 89 87
88 87 84
89 86 84
101 103 100
99 100 97
97 97 94
98 97 94
5
63
63
63
64
69
67
67
67
80
75
74
74
88
82
81
80
96
93
90
90
6
54
54
55
55
61
60
60
60
70
68
68
68
81
76
76
76
95
88
86
86
7
47
47
48
49
53
52
53
53
61
60
61
61
72
69
70
70
86
81
80
81
8
40
40
42
42
45
45
45
45
53
52
53
54
64
62
64
65
73
73
74
75
LWoA
70
69
69
70
76
73
73
73
84
81
80
79
92
88
86
86
102
98
96
96
Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not
include the effects of appurtenances (accessories).
The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA Standard 301. Values shown are for inlet LWi , LWi A and outlet LWo ,
LWo A sound power levels for installation type B: Free inlet, Ducted outlet. Ratings for inlet sound do not include the effects of duct end correction. Ratings for outlet
sound include the effects of duct end correction. The A-weighted sound power ratings shown have been calculated per AMCA Standard 301. The AMCA Certified
Ratings Seal applies to LWi A and LWo A values only.
48
QEI-54 Class II
10
Performance Data
100
75
929
66 in.
1676 mm
Approximate Weight
(Less Motor & Drives)
1633 kg.
3600 lbs.
10
UR
VE
SY
ST E
MC
Wheel Diameter
6
30
20
4
Maximum Bhp = (Fan RPM / 197)
5
SE
LE
CT
TO
10
3
2
DO
0
0
0
% WOV = (CFM x 100) / (Fan RPM x 104)
72
5
90% WOV
61
1
53
4
42
4
T
Outlet Velocity (FPM) = CFM / 30.46
Tip Speed (FPM) = Fan RPM x 17.3
NO
40
20
140
120
100
80
60
100
90
80
70
60
50
40
Volume (cfm x 1000)
30
20
10
Imperial data — Metric data
0
80% WOV
9
11 kW
70% WOV
0
15 hp
15
50
92
Minimum Motor
Starting hp
Static Pressure (in. wg)
405T
8
83
Static Pressure (Pa x 100)
20
Maximum Motor
Frame Size
RPM
BHP
% WOV
3
Density 0.075 lb/ft
3
Density 1.2 kg/m
60% WOV
FT
HIS
Specification Data
TH
EL
EF
TO
Maximum Fan RPM
125
50% WOV
160
3
Volume (m /hr x 1000)
Performance Data
STATIC PRESSURE (inches wg)
CFM
OV
0.5
1
2
3
4
5
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
6
RPM
BHP
7
RPM
BHP
8
RPM
BHP
RPM
BHP
33500
1105
364
4.71
407
7.61
485
14.7
562
23.0
636
32.0
37000
1221
394
5.71
433
8.78
505
16.1
577
24.8
645
34.3
710
44.4
40500
1336
425
6.88
460
10.1
527
17.7
592
26.7
656
36.6
719
47.2
777
58.3
44000
1452
457
8.22
488
11.7
552
19.6
611
28.8
671
39.0
728
50.1
786
61.7
840
73.7
47500
1567
488
9.76
516
13.4
576
21.6
632
31.1
687
41.6
743
53.1
796
65.2
849
77.7
899
90.7
51000
1683
520
11.5
546
15.4
602
23.9
655
33.6
707
44.4
759
56.2
810
68.7
859
81.8
909
95.2
54500
1798
552
13.5
577
17.6
629
26.5
680
36.5
728
47.5
775
59.5
825
72.3
872
85.9
918
99.9
58000
1914
584
15.7
608
20.0
656
29.3
704
39.5
750
50.8
796
63.2
840
76.2
887
90.1
61500
2029
617
18.1
639
22.7
684
32.3
729
42.9
775
54.5
818
67.1
860
80.4
903
94.5
65000
2145
650
20.9
671
25.6
712
35.7
756
46.6
800
58.5
840
71.2
881
85.0
920
99.3
68500
2260
682
23.9
702
28.9
741
39.3
784
50.7
824
62.8
865
75.9
903
89.7
72000
2376
715
27.2
734
32.4
771
43.3
811
55.0
850
67.4
889
80.8
926
94.9
Shaded values show where Class I fan selections are more efficient than Class II.
Inlet Sound Power, LWi [dB ref 10-12 watts]
RPM
275
375
525
750
929
% WOV
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
1
81
79
77
76
90
87
83
84
93
91
88
90
95
91
90
91
97
92
93
95
2
3
4
75 72 75
72 70 71
70 68 70
69 68 70
84 80 79
80 77 77
77 75 76
77 74 76
92 89 87
89 87 85
85 83 82
86 82 81
101 100 96
98 97 94
95 93 90
93 92 89
104 105 102
99 102 100
96 98 96
96 97 95
5
69
65
64
63
81
72
72
70
89
81
79
78
94
89
87
86
99
95
92
92
6
58
55
55
55
70
64
63
62
82
74
74
72
97
85
83
82
101
92
89
89
7
50
47
47
47
60
56
56
56
72
67
67
67
86
78
77
78
95
86
84
85
Outlet Sound Power, LWo [dB ref 10-12 watts]
8
44
38
39
39
54
49
50
50
63
60
61
63
70
70
71
73
79
77
79
80
LWiA
74
71
70
69
83
78
77
76
92
86
84
83
101
95
93
92
106
101
98
97
RPM
275
375
525
750
929
% WOV
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
1
2
3
4
5
6
84 78 77 78 71 61
84 77 76 76 68 59
83 75 74 76 68 59
83 75 73 76 67 58
88 85 85 82 81 71
88 84 83 81 75 67
88 82 81 80 74 66
88 81 79 79 73 65
93 93 94 90 89 83
90 90 91 88 83 77
88 87 88 85 81 75
91 88 87 85 80 74
96 99 103 99 96 97
93 96 101 98 93 88
94 94 97 95 90 86
97 96 98 94 90 84
100 104 108 105 101 102
97 101 105 104 98 94
99 99 102 100 96 91
101 102 103 100 95 91
7
54
51
51
51
61
59
59
59
73
69
68
68
87
81
79
79
96
88
86
85
8
47
44
44
45
54
51
52
53
64
60
62
63
73
72
73
74
82
79
79
80
LWoA
78
76
75
75
84
82
80
79
93
89
87
86
103
99
96
96
108
105
101
101
Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not
include the effects of appurtenances (accessories).
The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA Standard 301. Values shown are for inlet LWi , LWi A and outlet LWo ,
LWo A sound power levels for installation type B: Free inlet, Ducted outlet. Ratings for inlet sound do not include the effects of duct end correction. Ratings for outlet
sound include the effects of duct end correction. The A-weighted sound power ratings shown have been calculated per AMCA Standard 301. The AMCA Certified
Ratings Seal applies to LWi A and LWo A values only.
49
QEI-60 Class I
8
Performance Data
RPM
BHP
% WOV
Density 0.075 lb/ft3
3
Density 1.2 kg/m
75
Maximum Fan RPM
60% WOV
680
18
Specification Data
7
60
73 in.
Approximate Weight
(Less Motor & Drives)
1854 mm
1588 kg.
3500 lbs.
10
8
6
Maximum Bhp = (Fan RPM / 167)
CU
RV
E
30
4
25
20
3
15
10
2
3
LE
FT
OF
TH
IS
SY
ST
EM
Wheel Diameter
11 kW
40
5
4
Outlet Velocity (FPM) = CFM / 37.23
1
2
DO
Tip Speed (FPM) = Fan RPM x 19.1
0
% WOV = (CFM x 100) / (Fan RPM x 159)
50
TH
E
15 hp
12
70% WOV
40
EC
T
Minimum Motor
Starting hp
50
6
14
0
0
T
NO
L
SE
35
68
60
0
0
90% WOV
0
20
20
40
0
0
40
Imperial data — Metric data
0
80% WOV
TO
405T
Static Pressure (in. wg)
Maximum Motor
Frame Size
Static Pressure (Pa x 100)
16
60
60
Volume (cfm x 1000)
80
100
80
120
140
100
160
120
180
200
3
Volume (m /hr x 1000)
Performance Data
STATIC PRESSURE (inches wg)
CFM
OV
0.25
0.5
1
1.5
2
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
2.5
3
RPM
BHP
RPM
BHP
3.5
RPM
BHP
4
RPM
BHP
RPM
BHP
34000
912
242
2.43
271
3.92
328
7.58
380
11.7
40000
1073
276
3.36
300
4.98
349
8.89
397
13.4
439
18.2
484
23.7
46000
1234
310
4.56
331
6.33
374
10.5
417
15.3
458
20.5
494
26.0
534
32.1
52000
1395
345
6.06
364
8.00
402
12.4
440
17.4
477
23.1
514
29.0
547
35.1
580
41.6
615
48.8
58000
1556
381
7.89
398
10.0
432
14.7
465
20.0
500
25.8
533
32.2
566
38.8
596
45.5
625
52.5
64000
1717
417
10.1
432
12.4
463
17.4
493
22.9
525
29.0
556
35.6
586
42.6
616
49.9
644
57.2
70000
1878
454
12.7
467
15.3
495
20.5
523
26.3
551
32.6
580
39.4
609
46.7
636
54.4
663
62.3
76000
2039
490
15.8
502
18.5
529
24.2
555
30.3
579
36.7
606
43.8
632
51.3
659
59.2
82000
2200
527
19.4
538
22.3
562
28.3
586
34.7
610
41.5
634
48.7
659
56.5
88000
2361
564
23.5
575
26.6
597
33.0
619
39.7
642
46.8
663
54.3
94000
2522
601
28.2
611
31.5
631
38.3
652
45.3
673
52.7
100000
2683
638
33.5
647
37.0
666
44.2
Inlet Sound Power, LWi [dB ref 10-12 watts]
RPM
300
400
500
600
680
% WOV
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
1
85
83
82
81
92
91
89
89
99
97
95
94
101
99
98
96
103
101
99
99
2
81
79
77
77
89
86
84
83
96
93
89
88
101
99
96
95
105
104
101
99
3
78
77
76
76
84
82
79
79
90
87
83
83
95
93
88
88
99
97
92
92
4
78
75
75
75
82
80
79
79
87
85
82
82
91
89
86
86
95
92
89
89
5
73
69
69
69
83
76
76
75
89
81
80
80
92
86
84
84
94
90
88
88
6
63
62
63
63
72
70
70
70
79
75
75
75
87
80
80
80
92
85
84
84
7
56
55
56
56
64
63
65
65
70
69
70
70
76
74
75
75
81
78
79
79
Outlet Sound Power, LWo [dB ref 10-12 watts]
8
51
49
49
49
58
57
59
59
63
63
65
65
69
68
70
70
73
72
74
74
LWiA
78
76
75
75
86
82
81
81
92
87
85
85
96
92
89
89
100
96
93
93
RPM
300
400
500
600
680
% WOV
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
1
2
3
4
86 82 82 80
85 81 80 78
85 79 78 77
85 79 78 77
92 89 89 86
92 87 87 84
91 85 84 82
91 85 84 82
96 94 94 91
95 92 91 88
93 90 89 86
95 90 88 86
98 99 98 96
98 97 95 93
96 95 93 91
98 96 92 90
100 102 101 100
99 101 98 97
98 99 95 95
100 100 95 94
5
75
71
71
71
84
78
77
77
90
83
82
82
93
88
87
87
96
92
91
90
6
65
64
65
64
75
72
72
72
82
78
77
77
88
83
82
82
93
87
87
86
7
57
57
57
57
66
64
65
65
73
70
71
72
79
76
77
77
84
81
81
81
8
50
49
49
50
58
56
58
59
65
63
65
67
71
69
71
72
76
73
75
76
LWoA
80
78
77
77
88
85
83
83
94
90
88
88
98
94
93
92
102
98
96
96
Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not
include the effects of appurtenances (accessories).
The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA Standard 301. Values shown are for inlet LWi , LWi A and outlet LWo ,
LWo A sound power levels for installation type B: Free inlet, Ducted outlet. Ratings for inlet sound do not include the effects of duct end correction. Ratings for outlet
sound include the effects of duct end correction. The A-weighted sound power ratings shown have been calculated per AMCA Standard 301. The AMCA Certified
Ratings Seal applies to LWi A and LWo A values only.
50
QEI-60 Class II
12
Performance Data
Maximum Fan RPM
50% WOV
150
125
100
840
RPM
BHP
% WOV
3
Density 0.075 lb/ft
3
Density 1.2 kg/m
60% WOV
25
Specification Data
10
75
Wheel Diameter
73 in.
1854 mm
4200 lbs.
1905 kg.
Approximate Weight
(Less Motor & Drives)
15
10
3
Maximum Bhp = (Fan RPM / 167)
60
50
40
6
30
25
4
DO
0
0
% WOV = (CFM x 100) / (Fan RPM x 140)
0
0
80% WOV
75
0
0
2
Tip Speed (FPM) = Fan RPM x 19.1
84
60
20
15
5
Outlet Velocity (FPM) = CFM / 37.23
TH
EL
EF
TO
FT
HIS
SY
ST
EM
CU
RV
E
11 kW
8
70% WOV
90% WOV
TO
15 hp
20
EL
EC
T
Minimum Motor
Starting hp
Static Pressure (Pa x 100)
405T
Static Pressure (in. wg)
Maximum Motor
Frame Size
T
NO
S
45
0
350
20
40
60
Volume (cfm x 1000)
Imperial data — Metric data
0
50
80
100
100
120
150
200
3
Volume (m /hr x 1000)
Performance Data
STATIC PRESSURE (inches wg)
CFM
OV
0.5
1
2
3
4
5
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
6
RPM
BHP
7
RPM
BHP
8
RPM
BHP
91.5
RPM
BHP
40000
1073
323
5.51
362
9.20
436
17.6
507
27.6
573
38.5
45000
1207
355
6.91
390
10.6
455
19.6
520
30.2
583
41.8
641
54.1
50000
1341
388
8.58
418
12.6
479
21.9
537
32.9
595
45.1
651
58.1
704
71.7
55000
1476
421
10.6
448
14.8
504
24.6
557
35.9
611
48.6
662
62.3
713
76.6
762
60000
1610
454
12.9
479
17.4
531
27.6
580
39.3
628
52.4
678
66.6
724
81.7
772
97.2
817
113.4
65000
1744
488
15.5
511
20.4
559
31.1
605
43.2
651
56.6
694
71.1
740
86.7
783
103.1
827
119.9
70000
1878
522
18.6
543
23.8
588
35.0
631
47.5
674
61.3
715
76.2
757
92.1
799
109.1
839
126.7
75000
2012
556
22.0
576
27.5
617
39.3
658
52.2
699
66.5
738
81.8
776
98.1
815
115.3
80000
2147
591
25.9
610
31.8
647
44.1
687
57.6
724
72.2
762
87.8
799
104.6
834
122.1
85000
2281
625
30.3
643
36.5
678
49.4
715
63.4
751
78.3
787
94.5
822
111.5
90000
2415
660
35.2
677
41.7
710
55.3
745
69.8
779
85.1
813
101.7
95000
2549
695
40.7
711
47.5
742
61.7
774
76.7
808
92.6
840
109.3
Shaded values show where Class I fan selections are more efficient than Class II.
Inlet Sound Power, LWi [dB ref 10-12 watts]
RPM
300
450
600
750
840
% WOV
1
2
100
86 80
80
83 77
60
81 74
50
80 73
100
95 90
80
93 87
60
90 83
50
91 84
100
96 98
80
94 95
60
91 91
50
92 91
100
98 103
80
95 101
60
93 97
50
94 97
100
100 105
80
96 102
60
95 99
50
97 100
3
4
5
6
77 78 76 64
75 75 69 60
73 75 68 59
72 74 67 59
88 86 89 79
86 84 79 72
82 82 78 72
81 81 77 70
96 93 93 91
94 91 86 81
90 88 84 79
89 87 83 78
103 99 97 99
100 96 92 88
96 93 90 86
95 92 89 85
106 102 100 101
103 100 95 91
99 96 93 89
98 95 92 89
7
56
52
52
52
70
65
65
65
80
73
73
74
89
81
80
81
94
85
84
84
Outlet Sound Power, LWo [dB ref 10-12 watts]
8
49
44
45
45
61
58
59
61
66
66
67
69
73
72
74
76
78
76
78
79
LWiA
79
75
74
74
91
85
83
82
98
92
90
89
104
98
95
95
107
101
99
98
RPM
300
450
600
750
840
% WOV
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
100
80
60
50
1
87
86
86
86
93
91
90
92
96
93
93
95
99
96
97
99
101
98
99
102
2
82
81
79
78
92
89
87
87
98
95
93
94
102
99
98
100
104
101
101
104
3
82
81
78
77
93
91
88
87
100
98
95
95
105
104
100
100
107
105
102
103
4
5
6
81 77 66
80 72 64
80 71 63
79 70 62
89 89 80
87 82 75
85 80 73
84 79 72
96 94 92
94 89 84
91 87 81
91 86 80
103 99 99
101 96 91
98 93 88
97 92 87
106 102 102
104 99 95
101 96 92
101 96 91
7
58
55
56
56
71
66
66
67
81
76
75
75
90
83
82
82
95
88
86
86
8
51
48
49
49
62
58
60
61
69
67
69
70
76
75
76
77
81
79
79
81
LWoA
82
80
79
78
92
88
86
85
99
96
93
92
105
102
99
99
108
105
102
102
Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings do not
include the effects of appurtenances (accessories).
The sound power level ratings shown are in decibels, referred to 10-12 watts, calculated per AMCA Standard 301. Values shown are for inlet LWi , LWi A and outlet LWo ,
LWo A sound power levels for installation type B: Free inlet, Ducted outlet. Ratings for inlet sound do not include the effects of duct end correction. Ratings for outlet
sound include the effects of duct end correction. The A-weighted sound power ratings shown have been calculated per AMCA Standard 301. The AMCA Certified
Ratings Seal applies to LWi A and LWo A values only.
51
Specifications
Model QEI-L, QEI-I/II and QEID
Supply, exhaust, or return air fans shall be
of the inline mixed flow type.
The housing shall be constructed of welded
heavy-gauge steel to assure no air leakage.
Housing shall have inlet and outlet collars
for slip-fit duct connections. The housing
and bearing and/or motor supports shall be
constructed of heavy-gauge steel members
to prevent vibration and rigidly support the
shaft and bearings. Welded steel vanes
shall straighten the flow of air from the fan
discharge.
All QEI-L and QEI-I/II units up through size
27 shall incorporate a universal mounting
system that allows the fan to be mounted in
either vertical or horizontal configurations
and field rotation of the motor position in
90 degree increments. Bearing life shall not
be reduced below specified level in different
configurations. QEI-I/II units size 30 and
larger shall allow for field rotation of motor
positions. Units shall accommodate base
mount or ceiling hung mounting without
structural modifications to the fan.
The wheel shall be of the mixed flow type.
Wheels shall have a wheel cone, spherical
back plate and single thickness cambered
blades. Wheels shall be statically and
dynamically balanced to balance grade
G6.3 per ANSI S2.19. The wheel cone and
fan inlet cone shall be carefully matched
and shall have precise running tolerances
for maximum performance and operating
efficiency.
Each assembled fan shall be test run at
the factory at the specified fan RPM. The
maximum allowable fan vibration shall be
0.15 in/sec. peak velocity, filter-in for
QEI-I/II with signatures taken on each
bearing in three planes; horizontal, vertical,
and axial. Maximum vibration of 0.08 in/sec.
peak velocity, filter-in for QEID in a single
plane on the fan housing. This report shall
be provided at no charge to the customer
upon request.
Inlet and outlet sound power levels shall be
provided for each of the eight octave bands
at the point of operation.
Fans shall be licensed to bear the AMCA
Seal for Sound and Air Performance.
Mixed flow fans shall be Model QEI-L,
QEI-I/II or QEID as manufactured by
Greenheck Fan Corporation, Schofield,
Wisconsin, USA and shall be supplied as
shown on the plans and in the fan schedule.
Additional Belt Drive Specification
Turned, precision ground and polished steel
shafts shall be sized so the first critical
speed is at least 25% over the maximum
operating speed. Close tolerances shall be
maintained where the shaft makes contact
with the bearings.
Bearings shall be heavy-duty, grease
lubricated, self-aligning ball or roller type
with extended lubrication lines.
QEI-I/II and QEI-L (horizontal mount)
bearings shall be selected for a minimum
life L10 of 80,000 (L50 of 400,000) hours at
maximum operating speed. QEI-L (vertical
mount) bearings shall be selected for a
minimum life, L10 of 50,000 (L50 of 250,000)
hours at maximum operating speed.
Our Commitment
As a result of our commitment to continuous improvement, Greenheck reserves the right to change
specifications without notice.
Specific Greenheck product warranties are located on greenheck.com within the product
area tabs and in the Library under Warranties.
P.O. Box 410 • Schofield, WI 54476-0410 • Phone (715) 359-6171 • greenheck.com