IndustrIal Control and General purpose enClosed transformers seCtIon 1

IndustrIal Control and General purpose enClosed transformers seCtIon 1
SECTION 1
Industrial Control and
General purpose enclosed
Transformers
HPS Imperator®, HPS Spartan®,
HPS Fusion™ and Q Series Transformers
Control Transformer Quick Selection Charts ...................................... 30
What Is A Control Transformer? ........................................................ 31
Overcurrent Protection ..................................................................... 32
HPS Imperator Machine Tool Industrial Control Transformers
Features and Benefits .......................................................................36
Selection Tables ............................................................................... 38
Optional Accessories ......................................................................... 45
Wiring Schematics ............................................................................ 64
HPS Spartan Industrial Open-Style Core & Coil Control Transformers
Features and Benefits ...................................................................... 47
Selection Tables ............................................................................... 48
Optional Accessories ........................................................................ 53
Wiring Schematics ........................................................................... 75
HPS Fusion General Purpose Enclosed Transformers
Features and Benefits ......................................................................
Selection Tables ...............................................................................
Optional Accessories ........................................................................
Wiring Schematics ...........................................................................
55
56
61
75
Q Series Enclosed Potted Control Transformers
Features and Benefits ........................................................................ 62
Selection Table ................................................................................... 63
Wiring Schematics ............................................................................. 277
SECTION 1
TRANSFORMER QUICK SELECTION CHARTS
HPS Imperator®
Pri. Volts
SECTION 1
Group
Part No.
Page
600, 575, 550
120 x 240, 115 x 230, 110 x 220
Sec. Volts
A
PH***AJ
38
600, 575, 550
12 x 24, 11.5 x 23, 11 x 22
B
PH***AR
38
240 x 480, 230 x 460, 220 x 440
120 x 240, 115 x 230, 110 x 220
C
PH***MQMJ
39
240 x 480, 230 x 460, 220 x 440
12 x 24, 11.5 x 23, 11 x 22
D
PH***QR
39
208 x 416, 200 x 400, 190 x 380
120 x 240, 115 x 230, 110 x 220
E
PH***SP
40
120 x 240, 115 x 230, 110 x 220
120 x 240, 115 x 230, 110 x 220
F
PH***PP
40
120 x 240, 115 x 230, 110 x 220
12 x 24, 11.5 x 23, 11 x 22
G
PH***PG
41
600/480/240, 575/460/230, 550/440/220
120/100, 115/95, 110/90
H
PH***MBMH
41
480/240, 460/230/208, 440/220/200
120/25, 115/24, 110/23
I
PH***MLI
42
415/400/380
110 x 220
J
PH***MEMX
42
380/277/208
120 x 240
K
PH***MGJ
43
Group
Part No.
Page
HPS Spartan®
Pri. Volts
Sec. Volts
600/480, 575/460, 550/440
120 x 240, 115 x 230, 110 x 220
A
SP***ACP
48
600, 575, 550
12 x 24, 11.5 x 23, 11 x 22
B
SP***AR
48
240 x 480, 230 x 460, 220 x 440
120 x 240, 115 x 230, 110 x 220
C
SP***MQMJ
49
240 x 480, 230 x 460, 220 x 440
12 x 24, 11.5 x 23, 11 x 22
D
SP***QR
49
347/380
120 x 240
E
SP***KHP
50
347/380
12 x 24
F
SP***KHR
50
277
120
G
SP***NJ
51
120 x 240, 115 x 230, 110 x 220
12 x 24, 11.5 x 23, 11 x 22
H
SP***PR
51
208 x 416, 200 x 400, 190 x 380
120 x 240, 115 x 230, 110 x 220
I
SP***SP
52
208 x 416, 200 x 400, 190 x 380
12 x 24, 11.5 x 23, 11 x 22
J
SP***SR
52
Group
Part No.
Page
A
FS***ACP
56
HPS Fusion™
Pri. Volts
600/480, 575/460, 550/440
Sec. Volts
120 x 240, 115 x 230, 110 x 220
600, 575, 550
12 x 24, 11.5 x 23, 11 x 22
B
FS***AR
56
240 x 480, 230 x 460, 220 x 440
120 x 240, 115 x 230, 110 x 220
C
FS***MQMJ
57
240 x 480, 230 x 460, 220 x 440
12 x 24, 11.5 x 23, 11 x 22
D
FS***QR
57
347/380
120 x 240
E
FS***KHP
58
347/380
12 x 24
F
FS***KHR
58
277
120
G
FS***NJ
59
120 x 240, 115 x 230, 110 x 220
12 x 24, 11.5 x 23, 11 x 22
H
FS***PR
59
208 x 416, 200 x 400, 190 x 380
120 x 240, 115 x 230, 110 x 220
I
FS***SP
60
208 x 416, 200 x 400, 190 x 380
12 x 24, 11.5 x 23, 11 x 22
J
FS***SR
60
Q Series
Pri. Volts
600
Sec. Volts
12/24
© Hammond Power Solutions Inc.
30
Part No.
Page
Q***PRC*
63
Data subject to change without notice.
SECTION 1
SECTION 9
Control Transformer
WHAT IS A CONTROL TRANSFORMER?
What is a Control Transformer?
When you calculate the VA requirement of a Transformer, do you use the Primary or
the Secondary Voltage?
When selecting the VA requirement, you use the Secondary Voltage.
Can you use a Control Transformer connected in reverse?
Yes, a control transformer can be connected in reverse. However, keep in mind the output voltage will be less than
its rating, due to the compensation factor of the windings.
Can a Control Transformer regulate the output voltage?
A control transformer will not regulate the voltage. Output voltage is a function of the coil’s turn ratio only, times
the input voltage.
What is the benefit of “Vacuum Impregnation” on a Transformer?
All HPS Control Transformers are vacuum impregnated with “VT Polyester Resin” and oven cured which seals
the surface and eliminates moisture. Impregnating the entire unit provides a strong mechanical bond and offers
protection from environmental conditions.
Explain the “VA” or “Volt Ampere Output” Rating?
The VA or volt ampere output rating designates the output which a transformer can deliver for a specified time at
its rated secondary voltage and rated frequency, without exceeding its specified temperature rise.
Insulating Materials; what are they made of and what is their purpose?
Hammond Power Solutions utilizes Mylar, Nomex and other high quality insulating materials. Insulation is used to
electrically insulate turn-to-turn windings, layer-to-layer windings, primary to secondary windings and ground.
What is the effect of “Overload”?
When a transformer is continually overloaded, excessive heat develops and the insulation system will begin to
breakdown. As a result, the life expectancy of the transformer is shortened due to the heat exceeding the rating
of the insulation system.
© Hammond Power Solutions Inc.
31
Data subject to change without notice.
SECTION 1
A control transformer is an isolation transformer designed to provide a high degree of secondary voltage stability
(regulation) during a brief period of overload condition (also referred to as “inrush current” ). Control transformers
are also known as Machine Tool Transformers, Industrial Control Transformers or Control Power Transformers.
SECTION 1
Control Transformers
Recommendations For Overcurrent Protection
SECTION 1
UL and CSA (North American) Standards
North American standards, including UL 508, National Electric Code 450 and the Canadian Electrical
Code Part I, require overcurrent protection on all control circuit transformers. There are two options for
overcurrent protection:
Option 1
Provide an overcurrent device in the primary circuit rated to the current of the transformer. The overcurrent limits are as follows:
Primary 9 amps or more:
no more than 125% of rated current.
Primary 2 to 9 amps:
no more than 167% of rated current.
Primary less than 2 amps:
no more than 300% of rated current for power circuits.
no more than 500% of rated current for control circuits.
This method is considered less desirable as start-up inrush to the transformer can frequently surpass the current rating of the device and result in nuisance interruptions.
Option 2
The second option is to install overcurrent devices in both the primary and secondary circuits of the transformer. In this option, the secondary device must be rated no more than 125% of rated current of the transformer and the primary no more than 250%. CEC permits 300% overcurrent on the primary for this option.
In both options listed, it is recommended that time delay fuses be considered to avoid unnecessary
interruptions.
Secondary
The overcurrent protection listed below, in amperes, is 125% of the rated current of the transformer. Choose
the next higher fuse rating if these numbers do not correspond with standard fuse selections.
Sec.
Voltage
VA Rating
25
50
75
12
2.7
5.3
7.9
24
1.4
2.7
4.0
100
150
200
250
300
350
500
750
1000
1500
2000
3000
5000
11
16
21
27
-
-
-
-
-
-
-
-
-
5.3
7.9
11
14
16
19
27
-
-
-
-
-
-
90
0.4
0.7
1.1
1.4
2.1
2.8
3.5
4.2
4.9
7.0
11
14
21
28
-
-
95
0.4
0.7
1.0
1.4
2.0
2.7
3.3
4.0
4.7
6.6
9.9
14
20
27
-
-
100
0.4
0.7
1.0
1.3
1.9
2.5
3.2
3.8
4.4
6.3
9.4
13
19
25
-
-
110
0.3
0.6
0.9
1.2
1.8
2.3
2.9
3.5
4.0
5.7
8.6
12
18
23
-
-
115
0.3
0.6
0.9
1.1
1.7
2.2
2.8
3.3
3.9
5.5
8.2
11
17
22
-
-
120
0.3
0.6
0.8
1.1
1.6
2.1
2.7
3.2
3.7
5.3
7.9
11
16
21
-
-
220
0.15
0.3
0.5
0.6
0.9
1.2
1.5
1.8
2.0
2.9
4.3
5.7
8.6
12
18
29
230
0.14
0.3
0.5
0.6
0.9
1.1
1.4
1.7
2.0
2.8
4.1
5.5
8.2
11
17
28
240
0.14
0.3
0.4
0.6
0.8
1.1
1.4
1.6
1.9
2.7
4.0
5.3
7.9
11
16
27
© Hammond Power Solutions Inc.
32
Data subject to change without notice.
SECTION 1
SECTION 9
Control
Control Transformers
Transformers
Recommendations for Overcurrent Protection
Primary (UL and CSA)
Pri.
VA Rating
Volt
25
50
75
100
150
200
250
300
350
500
750
1000
1500
2000
3000
5000
7500
115
0.6
1.25
1.8
2.5
3.5
5
4
5
5
8
10
15
20
25
-
-
-
1
2
3.2
4
6.25
8
120
0.6
1.25
1.8
2.25
3.5
5
4
5
5
8
10
15
15
20
-
-
-
1
2
3
4
6.25
8
200
0.3
0.75
1.125
1.5
2.25
3
3.5
4.5
5
4.5
7
9
15
15
20
-
-
0.6
1.25
1.8
2.5
3.5
5
6.25
7.5
8
0.3
0.6
1
1.4
2
2.8
3.5
4
5
4
6
8
12
15
20
30
-
0.6
1.125
1.8
2.25
3.5
4.5
6
7
8
0.3
0.6
1
1.25
2
2.5
3.2
4
4.5
4
6
8
12
15
20
30
-
0.5
1.125
1.6
2.25
3.2
4.5
5.6
6.25
7.5
4
6
8
10
15
20
30
-
3.5
5
7
10
15
15
30
-
5
5
6
9
12
15
25
-
6.25
5
7.5
10
15
20
30
5.6
4.5
6.25
9
15
20
25
4.5
6.25
9
12
15
20
4
6
8
12
15
20
4
6
8
12
15
20
3.5
6
8
12
15
20
3.5
5
7
10
15
20
5
4.5
6
9
15
15
5
4.5
6
9
15
15
5
4
6
9
15
15
208
220
230
240
0.3
0.6
0.8
1.25
1.8
2.5
3.2
3.5
4.5
0.5
1
1.6
2
3.2
4
5
6.25
7.5
0.3
0.6
0.8
1.25
1.8
2.25
3
3.5
4
0.5
1
1.5
2
3
4
5
6.25
7
277
0.25
0.5
0.8
1
1.6
2
2.5
3.2
3.5
0.4
0.8
1.25
1.8
1.5
3.5
4.5
5
6.25
9
347
0.25
0.5
0.8
1
1.6
2
2.5
3.2
3.5
5
0.4
0.8
1.25
1.8
2.5
3.5
4.5
5
6.25
9
380
0.1875
0.3
0.5
0.75
1.125
1.5
1.8
2.25
2.5
3.5
0.3
0.6
0.8
1.25
1.8
2.5
3.2
3.5
4.5
6.25
9
400
0.1875
0.3
0.5
0.75
1.125
1.5
1.8
2.25
2.5
3.5
5.6
0.3
0.6
0.8
1.25
1.8
2.5
3
3.5
4
6.25
9
416
0.15
0.3
0.5
0.6
1
1.4
1.8
2
2.5
3.5
5
0.3
0.6
0.8
1.125
1.8
2.25
3
3.5
4
6
9
440
0.15
0.3
0.5
0.6
1
1.25
1.6
2
2.25
3.2
5
0.25
0.5
0.8
1.125
1.6
2.25
2.8
3.2
3.5
5.6
8
460
480
550
575
600
0.15
0.3
0.4
0.6
0.8
1.25
1.6
1.8
2.25
3.2
4.5
0.25
0.5
0.8
1
1.6
2
2.5
3.2
3.5
5
8
0.15
0.3
0.4
0.6
0.8
1.25
1.5
1.8
2
3
4.5
0.25
0.5
0.75
1
1.5
2
2.5
3
3.5
5
7.5
0.125
0.25
0.4
0.5
0.8
1
1.25
1.6
1.8
2.5
4
0.2
0.4
0.6
0.8
1.25
1.8
2.25
2.5
3
4.5
6.25
0.125
0.25
0.3
0.5
0.75
1
1.25
1.5
1.8
2.5
3.5
0.2
0.4
0.6
0.8
1.25
1.6
2
2.5
3
4
6.25
0.125
0.2
0.3
0.5
0.75
0.8
1.25
1.5
1.6
2.25
3.5
0.2
0.4
0.6
0.8
1.25
1.6
2
2.5
2.8
4
6.25
References:
© Hammond Power Solutions Inc.
UL 508, 32.7
UL 845, 11.16 and 11.17
NEC 430-72 (c) exception #2
NEC 450-3 (b) 1 and 2
CEC Part I, 26-256
33
Data subject to change without notice.
SECTION 1
To assist in the selection of fuses, the following chart recommends the maximum primary fuse rating in amperes. The
first number shown is the maximum overcurrent protection when the primary current is less than 2 amps and the overcurrent
protection device is rated for 300%. The second number shown (italic) is recommended when the primary is less than 2 amps
and the overcurrent device is to be rated at 500% of rated current. Where only one number is indicated, the primary is 2 amps
or more and one rating of over current protection is shown as optimal. Choose the next higher fuse rating if these numbers do
not correspond with standard fuse selections.
SECTION 1
HPS IMPERATOR®
HPS Imperator® Machine Tool Industrial Control Transformer
SECTION 1
The Perfect Solution
The HPS Imperator line of machine tool industrial control transformers are specifically designed to meet the high
inrush industrial applications where electromagnetic components such as relays, solenoids etc. are used.
•
•
•
•
•
•
•
11 standard voltage groups
VA range from 50VA to 1500VA
Available with standard secondary and optional
primary fuse kits
Optional finger safe terminal covers
Patented unique terminal block design
Innovative fusing method
Lifetime warranty (limited)
The HPS Imperator provides the perfect solution for any applications.
Superior Quality and Value
The HPS Imperator design, utilizing superior insulation systems and being constructed with high quality silicon steel
laminations for optimum performance, will meet or exceed UL and CE standards.
Backed by an industry leading LIFETIME warranty, the HPS Imperator industrial control transformer line offers
superior performance, quality and value.
STANDARDS
HPS Imperator Series Control Transformers meet or exceed the standards established
by UL, IEC, and NEMA.
Standard
File #
UL (ANSI/UL 506)
E50394
VA Size
All
IEC 61558
All (excluding PH***AJ & PH***AR) NEMA (ST-1)
All
At HPS, we rate the VA capacity of our transformers at the output ..... where it counts.
Other transformer manufacturers rate their capacity on the input side of the transformer, which can result in a 5% to 20% lower actual VA at the output.
© Hammond Power Solutions Inc.
34
Data subject to change without notice.
SECTION 1
SECTION 9
Machine Tool Industrial Control
MACHINE TOOL INDUSTRIAL CONTROL TRANSFORMER SELECTION
(A) The total steady state
“sealed” VA is the amount of VA
that the transformer must supply
to the load circuit for an extended
length of time. Simply add the total
steady-state VA of all devices in your
control circuit. The operating VA data
of these components is available
from the manufacturers.
( B ) T h e t o t a l i n r u s h VA
is the amount of VA that the
transformer must supply for all
components in the control circuit
which are energized together.
Some consideration to the start-up
sequence may be required. Inrush VA
should be obtained from the device
manufacturer.
(C) The inrush load power factor is
difficult to determine without detailed
vector analysis of all the control
circuit components. Such information
is not generally available. Therefore,
HPS is recommending that a 40%
power factor be utilized. Although
some other control transformer
manufacturers still recommend a
power factor of only 20%, HPS,
through recent tests conducted on
many popular brands of control
devices, has determined that the
40% power factor value is more
accurate.
Once the above circuit variables
have been determined, transformer
selection is a six step process.
SIX EASY STEPS
1. Determine what your Primary
(supply) and Secondary (output)
voltage requirements are, as well
as your required frequency (i.e. 60
Hz)
2. Calculate the Total Sealed VA
of your circuit. (See Step A)
3. Calculate the Inrush VA
by adding the inrush VA of all
components being energized
together. Remember to add the
sealed VA of all components that do
not have inrush VA, (lamps, timers
etc.) as they present a load to the
transformer during maximum inrush.
If the inrush for the components in
your circuit are not known, assume
a 40% Inrush Power Factor.
4. Calculate the Total Inrush VA
using one of the two methods:
A. Total Inrush VA =
(VA sealed)2 + (VA inrush)2
OR
B. Total Inrush VA =
VA Sealed + VA Inrush
Note: method B will result in a slightly
larger transformer being selected.
For VA sealed definition please refer to 1 (A).
For VA inrush definition please refer to 1 (B).
© Hammond Power Solutions Inc.
35
5. If the nominal supply voltage
does not fluctuate more than 5%,
then reference the 90% secondary
voltage column in the Regulation
Data Table for the correct VA
rating.
If the supply voltage varies upwards
of 10%, the 95% secondary voltage
column should be used to size the
transformer.
Current standards require
electromagnetic devices to operate
reliably at a minimum of 85%
of their rated voltage. However,
contact life may be affected with
continuous start-ups at that voltage
level. Therefore, the minimum 85%
secondary voltage column should
only be used as a reference.
6. Using the regulation data tables
below, select the appropriate VA
rated transformer:
A) With a continuous VA rating that
is equal to or greater than the value
in Step 2.
B) With a maximum inrush VA equal to or greater than the value
obtained in Step 4.
To determine the correct HPS
Transformer and its Catalog Number,
just refer to the tables in this catalog
for the voltage ratings, frequency
and corresponding VA required.
HPS IMPERATOR® TRANSFORMERS
REGULATION DATA TABLE
Continuous VA
Inrush VA @ 40% Power Factor
Transformer
85%
90%
95%
Nameplate
Secondary Secondary Secondary
Rating
Voltage
Voltage
Voltage
50
75
100
150
250
350
500
750
1000
1500
330
350
620
895
1596
2464
3939
6422
9842
12797
259
258
467
699
1229
1889
2854
4778
7102
9018
192
170
321
512
880
1345
1819
3228
4530
5489
It is recommended that a Control Transformer be
sized at a 40% Power Factor. Some components
in a circuit, such as electromagnetic devices,
typically operate at that level due to their
inherently lower power factor. Selecting a
transformer at 40% Power Factor will more than
adequately size the unit for all the various loads
in the circuit.
Data subject to change without notice.
SECTION 1
Selecting a Control Transformer
requires that you have first hand
knowledge of the application for the
transformer and that you understand
some basic terms related to the
selection process. By using the
following information, you will be sure
to select the HPS Imperator® Control
Transformer which best meets your
application.
The HPS Imperator Series
machine tool control transformers
are specifically designed for high
inrush applications requiring reliable
output voltage stability. Designed to
meet industrial applications where
electromagnetic devices such as
relays, solenoids, etc. are used, the
HPS Imperator series transformers
maximize inrush capability and
output voltage regulation when
electromagnetic devices are initially
energized.
To select the proper transformer,
three characteristics of the load
circuit must first be determined.
They are total steady-state (sealed)
VA, total inrush VA, and inrush load
power factor.
SECTION 1
HPS IMPERATOR®
•
•
•
•
•
•
•
•
•
600V class, machine tool rated industrial control transformers
11 standard multi primary and secondary voltage groups available1
50/60 Hertz (60Hz on PH***AJ & PH***AR)
VA range from 50 to 15001
Superior insulation system
• 50-150VA, temperature rise 55°C, insulation class 105°C
• 250-1500VA, temperature rise 80°C, insulation class 130°C
Constructed with high quality silicon steel laminations that provide optimum
performance and reliability
Encapsulated copper wound coils encased in a custom injection molded
cover, protects coils and terminations from moisture, dirt and other industrial
airborne contaminants
Mounting Feet: made of heavy steel and welded or bolted to the core, these
mounting feet provide superior strength in a compact design.
Termination: combination slot/Phillips #6 screw, complete with SEMS washer
(suitable for 18 AWG to 14 AWG solid or 14 AWG stranded wire)
•
•
•
•
•
•
•
•
•
1
2
Standard SEMS washers - supplied on all units2
Standard secondary fuse kits - utilizing 13/32” x 1 1/2” midget/type CC fuse
clips
Optional primary fuse kits available utilizing 13/32” x 1 1/2” midget/type CC
fuse clips
Optional finger safe terminal covers available on all units
Seismically certified in accordance with 2009 IBC for SDS <= 2.00g, z/h = 1.0
and IP = 1.5
UL Listed (approved for U.S. and Canada)
CE Mark standard on all units (excluding PH*AR and PH*AJ)
LIFETIME Warranty (Limited)
RoHS Compliant
special voltages and VA sizes available upon request
excluding PH750PG, PH1000PG, PH750MLI, PH1000MLI
Warranty
SECTION 1
Features & Benefits
Lifetime
© Hammond Power Solutions Inc.
36
Data subject to change without notice.
SECTION 1
SECTION 9
Machine Tool Industrial Control
Features & Benefits Continued
SEMS washer allows for easy connection
of supply or load wires with or without
terminal connectors.
Standard secondary and optional
primary fuse kits utilizing 13/32” x 1 1/2”
midget/type CC fuse clips provide an
economical solution to your fusing
requirements (fuses not available).
Innovative terminal block
design provides for easy
hook-up and installation of
fuse clips.
Optional removable finger safe
terminal covers available on all
units.
Custom injection molded coil
cover with its unique “fin shaped”
design combines superior cooling
properties with a clean, bold look.
© Hammond Power Solutions Inc.
37
Made of heavy steel and
welded or bolted to the
core, these mounting feet
provide superior strength
in a compact design.
Data subject to change without notice.
SECTION 1
Terminal connection numbers molded into the
terminal block and correspond to the nameplate
and wiring diagrams, make
connecting the HPS Imperator
quick and simple.
SECTION 1
HPS IMPERATOR®
B
B
C
SECTION 1
GxH
C
GxH
A
D
E
A
E
D
FIGURE B
FIGURE A
Group A
Primary Voltage: Secondary Voltage: VA
Rating
50
Catalog
Number
Mtg.
Fig.
600
575
120 X 240 115 X 230
Output
Amps
Overall
Dimensions
Mounting
Centers
550
110 X 220
Mounting
Slot
A
B
C
D
E
GXH
Height
with
Finger
Guard
60 Hertz
Depth
with
Finger
Guard
Approx.
Ship
Weight
Lbs.
Optional
Primary
Fuse
Kit P/N
Optional
Unfused and
Fused Finger
Guard Kit P/N
PH50AJ
A
0.42/0.21
3.00
3.81
3.19
2.50
2.25
0.22 x 0.44
4.00
5.25
2.70
PFK1
FG1*/FGF1
75
PH75AJ
A
0.63/0.31
3.25
3.69
3.56
2.63
2.50
0.22 x 0.44
4.37
5.13
2.80
PFK1
FG2*/FGF2
100
PH100AJ
A
0.83/0.42
3.25
4.06
3.63
2.63
2.63
0.22 x 0.44
4.44
5.50
4.10
PFK1
FG2*/FGF2
150
PH150AJ
B
1.25/0.63
4.00
4.63
3.81
3.38
2.75
0.22 x 0.75
4.50
6.13
4.90
PFK2
FG3
250
PH250AJ
B
2.08/1.04
4.50
5.25
3.81
3.75
3.13
0.22 x 0.75
4.50
6.75
6.97
PFK2
FG3
350
PH350AJ
B
2.92/1.46
4.50
4.88
4.44
3.75
3.75
0.22 x 0.75
4.94
6.38
8.30
PFK3
FG4
500
PH500AJ
B
4.17/2.08
4.75
5.56
4.31
4.06
3.44
0.31 x 0.94
4.81
7.06
11.6
PFK3
FG4
750
PH750AJ
B
6.25/3.13
5.13
6.38
4.31
4.38
4.00
0.31 x 0.81
4.81
7.88
16.6
PFK3
FG4
1000
PH1000AJ
B
8.33/4.17
5.25
6.50
4.94
4.50
4.09
0.31 x 0.81
5.56
8.00
21.0
PFK3
FG5
1500
PH1500AJ
B
12.5/6.25
5.25
7.56
4.94
4.50
5.44
0.38 x 1.00
5.56
9.06
30.0
PFK3
FG5
All dimensions in inches
Secondary fuse clips, fuse clip mounting screws and primary and secondary voltage links/jumpers supplied standard with transformers.
*Note: Unfused finger guard kits are marked with an asterisk, for more information refer to page 45.
Refer to page 64 for wiring schematic drawing. Custom voltage and VA sizes available upon request.
Group B
Primary Voltage: Secondary Voltage: VA
Rating
Catalog
Number
Mtg.
Fig.
575
11.5 X 23
600
12 X 24
Output
Amps
Overall
Dimensions
A
B
C
Mounting
Centers
D
550
11 X 22
Mounting
Slot
E
GXH
60 Hertz
Height
with
Finger
Guard
Depth
with
Finger
Guard
Approx.
Ship
Weight
Lbs.
Optional
Primary
Fuse
Kit P/N
Optional
Unfused and
Fused Finger
Guard Kit P/N
50
PH50AR
A
4.17/2.08
3.00
3.81
3.19
2.50
2.25
0.22 x 0.44
4.00
5.25
2.70
PFK1
FG1*/FGF1
75
PH75AR
A
6.25/3.13
3.25
3.69
3.56
2.63
2.50
0.22 x 0.44
4.37
5.13
2.80
PFK1
FG2*/FGF2
100
PH100AR
A
8.33/4.17
3.25
4.19
3.63
2.63
2.63
0.22 x 0.44
4.44
5.63
4.50
PFK1
FG2*/FGF2
150
PH150AR
B
12.5/6.25
4.00
4.94
3.81
3.38
2.75
0.22 x 0.75
4.50
6.44
5.70
PFK2
FG3
250
PH250AR
B
20.8/10.4
4.50
5.44
3.81
3.75
3.13
0.22 x 0.75
4.50
6.94
7.50
PFK2
FG3
350
PH350AR
B
29.2/14.6
4.50
4.88
4.44
3.75
3.75
0.22 x 0.75
4.94
6.38
8.30
PFK3
FG4
500
PH500AR
B
41.7/20.8
4.75
5.56
4.31
4.06
3.44
0.31 x 0.94
4.81
7.06
11.6
PFK3
FG4
Secondary fuse clips, fuse clip mounting screws and primary and secondary voltage links/jumpers supplied with transformers.
*Note: Unfused finger guard kits are marked with an asterisk, for more information refer to page 45.
Refer to page 65 for wiring schematic drawing. Custom voltages and VA sizes available upon request.
© Hammond Power Solutions Inc.
38
All dimensions in inches
Data subject to change without notice.
SECTION 1
SECTION 9
Machine Tool Industrial Control
B
B
C
GxH
C
GxH
E
A
SECTION 1
D
A
E
D
FIGURE B
FIGURE A
Group C
Primary Voltage: Secondary Voltage: VA
Rating
50
Catalog
Number
Mtg.
Fig.
240 X 480
120 X 240
Output
Amps
230 X 460
115 X 230
Overall
Dimensions
Mounting
Centers
220 X 440
110 X 220
Mounting
Slot
A
B
C
D
E
GXH
Height
with
Finger
Guard
50/60 Hertz
Depth
with
Finger
Guard
Approx.
Ship
Weight
Lbs.
Optional
Primary
Fuse
Kit P/N
Optional
Unfused and
Fused Finger
Guard Kit P/N
PH50MQMJ
A
0.42/0.21
3.00
4.38
3.19
2.50
2.25
0.22 x 0.44
4.00
5.82
3.50
PFK1
FG1*/FGF1
75
PH75MQMJ
A
0.63/0.31
3.25
3.88
3.56
2.63
2.50
0.22 x 0.44
4.37
5.32
3.54
PFK1
FG2*/FGF2
100
PH100MQMJ
A
0.83/0.42
3.25
4.19
3.63
2.63
2.63
0.22 x 0.44
4.44
5.63
4.50
PFK1
FG2*/FGF2
150
PH150MQMJ
B
1.25/0.63
4.00
4.94
3.81
3.38
2.75
0.22 x 0.75
4.50
6.44
5.70
PFK2
FG3
250
PH250MQMJ
B
2.08/1.04
4.50
5.44
3.81
3.75
3.13
0.22 x 0.75
4.50
6.94
7.50
PFK2
FG3
350
PH350MQMJ
B
2.92/1.46
4.50
5.19
4.44
3.75
3.75
0.22 x 0.75
4.94
6.69
10.1
PFK3
FG4
500
PH500MQMJ
B
4.17/2.08
4.75
5.94
4.31
4.06
3.81
0.31 x 0.94
4.81
7.44
14.2
PFK3
FG4
750
PH750MQMJ
B
6.25/3.13
5.13
6.69
4.31
4.38
4.31
0.31 x 0.81
4.81
8.19
16.6
PFK3
FG4
1000
PH1000MQMJ
B
8.33/4.17
5.25
6.81
4.94
4.50
4.44
0.31 x 0.81
5.56
8.31
23.6
PFK3
FG5
1500
PH1500MQMJ
B
12.5/6.25
5.25
8.19
4.94
4.50
6.06
0.38 x 1.00
5.56
9.69
32.0
PFK3
FG5
All dimensions in inches
Secondary fuse clips, fuse clip mounting screws and primary and secondary voltage links/jumpers supplied standard with transformers.
*Note: Unfused finger guard kits are marked with an asterisk, for more information refer to page 45.
Refer to page 66 for wiring schematic drawing. Custom voltages and VA sizes available upon request.
*** Available with FACTORY INSTALLED Primary and Secondary Fuse Kits up to 1500VA. To order, add the suffix “-FK” to the above part number. Refer to page 44 for details. ***
Group D
Primary Voltage: Secondary Voltage: VA
Rating
Catalog
Number
Mtg.
Fig.
240 X 480
12 X 24
Output
Amps
230 X 460
11.5 X 23
Overall
Dimensions
Mounting
Centers
220 X 440
11 X 22
Mounting
Slot
A
B
C
D
E
GXH
Height
with
Finger
Guard
50/60 Hertz
Depth
with
Finger
Guard
Approx.
Ship
Weight
Lbs.
Optional
Primary
Fuse
Kit P/N
Optional
Unfused and
Fused Finger
Guard Kit P/N
50
PH50QR
A
4.17/2.08
3.00
4.38
3.19
2.50
2.25
0.22 x 0.44
4.00
5.82
3.50
PFK1
FG1*/FGF1
75
PH75QR
A
6.25/3.13
3.25
3.88
3.56
2.63
2.50
0.22 x 0.44
4.37
5.32
3.54
PFK1
FG2*/FGF2
100
PH100QR
A
8.33/4.17
3.25
4.19
3.63
2.63
2.63
0.22 x 0.44
4.44
5.63
4.50
PFK1
FG2*/FGF2
150
PH150QR
B
12.5/6.25
4.00
4.94
3.81
3.38
2.75
0.22 x 0.75
4.50
6.44
5.70
PFK2
FG3
250
PH250QR
B
20.8/10.4
4.50
5.44
3.81
3.75
3.13
0.22 x 0.75
4.50
6.94
7.50
PFK2
FG3
350
PH350QR
B
29.2/14.6
4.50
5.19
4.44
3.75
3.75
0.22 x 0.75
4.94
6.69
10.1
PFK3
FG4
500
PH500QR
B
41.7/20.8
4.75
5.94
4.31
4.06
3.81
0.31 x 0.94
4.81
7.44
14.2
PFK3
FG4
Secondary fuse clips, fuse clip mounting screws and primary and secondary voltage links/jumpers supplied standard with transformers.
*Note: Unfused finger guard kits are marked with an asterisk, for more information refer to page 45.
Refer to page 67 for wiring schematic drawing. Custom voltages and VA sizes available upon request.
© Hammond Power Solutions Inc.
39
All dimensions in inches
Data subject to change without notice.
SECTION 1
HPS IMPERATOR®
B
B
C
SECTION 1
GxH
C
GxH
A
D
E
E
D
A
FIGURE B
FIGURE A
Group E
Primary Voltage: Secondary Voltage: VA
Rating
50
Catalog
Number
Mtg.
Fig.
208 X 416
120 X 240
Output
Amps
200 X 400
115 X 230
Overall
Dimensions
190 X 380
110 X 220
Mounting
Centers
Mounting
Slot
A
B
C
D
E
GXH
Height
with
Finger
Guard
50/60 Hertz
Depth
with
Finger
Guard
Approx.
Ship
Weight
Lbs.
Optional
Primary
Fuse
Kit P/N
Optional
Unfused and
Fused Finger
Guard Kit P/N
PH50SP
A
0.42/0.21
3.00
4.38
3.19
2.50
2.25
0.22 x 0.44
4.00
5.82
3.50
PFK1
FG1*/FGF1
75
PH75SP
A
0.63/0.31
3.25
3.88
3.56
2.63
2.50
0.22 x 0.44
4.37
5.32
3.54
PFK1
FG2*/FGF2
100
PH100SP
A
0.83/0.42
3.25
4.19
3.63
2.63
2.63
0.22 x 0.44
4.44
5.63
4.50
PFK1
FG2*/FGF2
150
PH150SP
B
1.25/0.63
4.00
4.94
3.81
3.38
2.75
0.22 x 0.75
4.50
6.44
5.70
PFK2
FG3
250
PH250SP
B
2.08/1.04
4.50
5.44
3.81
3.75
3.13
0.22 x 0.75
4.50
6.94
7.50
PFK2
FG3
350
PH350SP
B
2.92/1.46
4.50
5.19
4.44
3.75
3.75
0.22 x 0.75
4.94
6.69
10.1
PFK3
FG4
500
PH500SP
B
4.17/2.08
4.75
5.94
4.31
4.06
3.81
0.31 x 0.94
4.81
7.44
14.2
PFK3
FG4
750
PH750SP
B
6.25/3.13
5.13
6.69
4.31
4.38
4.31
0.31 x 0.81
4.81
8.19
16.6
PFK3
FG4
1000
PH1000SP
B
8.33/4.17
5.25
6.81
4.94
4.50
4.44
0.31 x 0.81
5.56
8.31
23.6
PFK3
FG5
All dimensions in inches
Secondary fuse clips, fuse clip mounting screws and primary and secondary voltage links/jumpers supplied standard with transformers.
*Note: Unfused finger guard kits are marked with an asterisk, for more information refer to page 45.
Refer to page 68 for wiring schematic drawing. Custom voltages and VA sizes available upon request.
Group F
Primary Voltage: Secondary Voltage: VA
Rating
Catalog
Number
Mtg.
Fig.
120 X 240
120 X 240
Output
Amps
115 X 230
115 X 230
Overall
Dimensions
Mounting
Centers
110 X 220
110 X 220
Mounting
Slot
A
B
C
D
E
GXH
Height
with
Finger
Guard
50/60 Hertz
Depth
with
Finger
Guard
Approx.
Ship
Weight
Lbs.
Optional
Primary
Fuse
Kit P/N
Optional
Unfused and
Fused Finger
Guard Kit P/N
50
PH50PP
A
0.42/0.21
3.00
4.38
3.19
2.50
2.25
0.22 x 0.44
4.00
5.82
3.50
PFK1
FG1*/FGF1
75
PH75PP
A
0.63/0.31
3.25
3.88
3.56
2.63
2.50
0.22 x 0.44
4.37
5.32
3.54
PFK1
FG2*/FGF2
100
PH100PP
A
0.83/0.42
3.25
4.19
3.63
2.63
2.63
0.22 x 0.44
4.44
5.63
4.50
PFK1
FG2*/FGF2
150
PH150PP
B
1.25/0.63
4.00
4.94
3.81
3.38
2.75
0.22 x 0.75
4.50
6.44
5.70
PFK2
FG3
250
PH250PP
B
2.08/1.04
4.50
5.44
3.81
3.75
3.13
0.22 x 0.75
4.50
6.94
7.50
PFK2
FG3
350
PH350PP
B
2.92/1.46
4.50
5.19
4.44
3.75
3.75
0.22 x 0.75
4.94
6.69
10.1
PFK3
FG4
500
PH500PP
B
4.17/2.08
4.75
5.94
4.31
4.06
3.81
0.31 x 0.94
4.81
7.44
14.2
PFK3
FG4
750
PH750PP
B
6.25/3.13
5.13
6.69
4.31
4.38
4.31
0.31 x 0.81
4.81
8.19
16.6
PFK3
FG4
1000
PH1000PP
B
8.33/4.17
5.25
6.81
4.94
4.50
4.44
0.31 x 0.81
5.56
8.31
23.6
PFK3
FG5
1500
PH1500PP
B
12.5/6.25
5.25
8.19
4.94
4.50
6.06
0.38 x 1.0
5.56
9.69
32.0
PFK3
FG5
Secondary fuse clips, fuse clip mounting screws and primary and secondary voltage links/jumpers supplied standard with transformers.
*Note: Unfused finger guard kits are marked with an asterisk, for more information refer to page 45.
Refer to page 69 for wiring schematic drawing. Custom voltages and VA sizes available upon request.
© Hammond Power Solutions Inc.
40
All dimensions in inches
Data subject to change without notice.
SECTION 1
SECTION 9
Machine Tool Industrial Control
B
B
C
C
C
GxH
A
D
GxH
E
E
D
A
A
B
FIGURE C
FIGURE B
FIGURE A
E
D
SECTION 1
GxH
Group G
Primary Voltage: Secondary Voltage: VA
Rating
Catalog
Number
Mtg.
Fig.
120 X 240
12 X 24
Output
Amps
115 X 230
11.5 X 23
Overall
Dimensions
Mounting
Centers
110 X 220
11 X 22
Mounting
Slot
A
B
C
D
E
GXH
Height
with
Finger
Guard
50/60 Hertz
Depth
with
Finger
Guard
Approx.
Ship
Weight
Lbs.
Optional
Primary
Fuse
Kit P/N
Optional
Unfused and
Fused Finger
Guard Kit P/N
50
PH50PG
A
4.17/2.08
3.00
4.38
3.19
2.50
2.25
0.22 x 0.44
4.00
5.82
3.50
PFK1
FG1*/FGF1
75
PH75PG
A
6.25/3.13
3.25
3.88
3.56
2.63
2.50
0.22 x 0.44
4.37
5.32
3.54
PFK1
FG2*/FGF2
100
PH100PG
A
8.33/4.17
3.25
4.19
3.63
2.63
2.63
0.22 x 0.44
4.44
5.63
4.50
PFK1
FG2*/FGF2
150
PH150PG
B
12.5/6.25
4.00
4.94
3.81
3.38
2.75
0.22 x 0.75
4.50
6.44
5.70
PFK2
FG3
250
PH250PG
B
20.8/10.4
4.50
5.44
3.81
3.75
3.13
0.22 x 0.75
4.50
6.94
7.50
PFK2
FG3
350
PH350PG
B
29.2/14.6
4.50
5.19
4.44
3.75
3.75
0.22 x 0.75
4.94
6.69
10.1
PFK3
FG4
500
PH500PG
B
41.7/20.8
4.75
5.94
4.31
4.06
3.81
0.31 x 0.94
4.81
7.44
14.2
PFK3
FG4
750
PH750PG
C
62.5/31.3
5.13
6.69
4.31
4.38
4.31
0.31 x 0.81
4.81
8.19
16.6
PFK3
FG5
1000
PH1000PG
C
83.3/41.7
5.25
6.81
4.94
4.50
4.44
0.31 x 0.81
5.56
8.31
23.6
PFK3
FG5
All dimensions in inches
Secondary fuse clips and fuse clip mounting screws supplied standard with transformers up to and including 500VA. Primary and Secondary
voltage links/jumpers supplied standard with transformers.
*Note: Unfused finger guard kits are marked with an asterisk, for more information refer to page 45.
Refer to page 70 for wiring schematic drawing. Custom voltages and VA sizes available upon request.
*** Available with FACTORY INSTALLED Primary and Secondary Fuse Kits up to 1000VA. To order, add the suffix “-FK” to the above part number. Refer to page 44 for details. ***
Group H
Primary Voltage: Secondary Voltage:
VA
Rating
50
Catalog
Number
PH50MBMH
Mtg.
Fig.
600/480/240
120/100
Output
Amps
575/460/230
115/95
Overall
Dimensions
Mounting
Centers
550/440/220
110/90
Mounting
Slot
A
B
C
D
E
GXH
Height
with
Finger
Guard
50/60 Hertz
Depth
with
Finger
Guard
Approx.
Ship
Weight
Lbs.
Optional
Primary
Fuse
Kit P/N
Optional
Unfused and
Fused Finger
Guard Kit P/N
A
0.43
3.25
4.06
3.63
2.63
2.63
0.22 x 0.44
4.44
5.50
4.10
PFK5
FG2*/FGF2
75
PH75MBMH
A
0.65
3.25
4.19
3.63
2.63
2.63
0.22 x 0.44
4.44
5.63
4.50
PFK5
FG2*/FGF2
100
PH100MBMH
B
0.87
4.00
4.63
3.81
3.38
2.75
0.22 x 0.75
4.50
6.13
4.90
PFK6
FG3
150
PH150MBMH
B
1.30
4.00
5.44
3.81
3.38
2.75
0.22 x 0.75
4.50
6.94
7.60
PFK6
FG3
250
PH250MBMH
B
2.17
4.50
5.19
4.44
3.75
3.75
0.22 x 0.75
4.94
6.69
10.1
PFK6
FG4
350
PH350MBMH
B
3.04
4.50
5.56
4.44
3.75
3.75
0.22 x 0.75
4.94
7.06
11.0
PFK7
FG4
500
PH500MBMH
B
4.35
4.75
6.69
4.31
4.06
4.50
0.31 x 0.94
4.81
8.19
16.3
PFK7
FG4
750
PH750MBMH
B
6.52
5.25
6.81
4.94
4.50
4.44
0.31 x 0.81
5.56
8.31
23.6
PFK7
FG5
1000
PH1000MBMH
B
8.70
5.25
8.19
4.94
4.50
5.81
0.31 x 0.81
5.56
9.69
31.2
PFK7
FG5
1500
PH1500MBMH
B
13.0
5.25
8.19
4.94
4.50
6.06
0.38 x 1.0
5.56
9.69
32.0
PFK7
FG5
Secondary fuse clips, fuse clip mounting screws and primary and secondary voltage links/jumpers supplied standard with transformers.
*Note: Unfused finger guard kits are marked with an asterisk, for more information refer to page 45.
Refer to page 71 for wiring schematic drawing. Custom voltage and VA sizes available upon request.
© Hammond Power Solutions Inc.
41
All dimensions in inches
Data subject to change without notice.
SECTION 1
HPS IMPERATOR®
B
B
C
SECTION 1
C
GxH
C
GxH
A
D
GxH
E
A
E
D
A
B
FIGURE C
FIGURE B
FIGURE A
E
D
Group I
Primary Voltage: Secondary Voltage: VA
Rating
Catalog
Number
Mtg.
Fig.
480/240
120/25
460/230/208
115/24
Overall
Dimensions
Mounting
Centers
440/220/200
110/23
Mounting
Slot
A
B
C
D
E
GXH
Height
with
Finger
Guard
Output
Amps
50/60 Hertz
Depth
with
Finger
Guard
Approx.
Ship
Weight
Lbs.
Optional
Primary
Fuse
Kit P/N
Optional
Unfused and
Fused Finger
Guard Kit P/N
50
PH50MLI
A
0.43/2.08
3.25
4.06
3.56
2.63
2.50
0.22 x 0.44
4.37
5.50
4.00
PFK5
FG2*/FGF2
75
PH75MLI
A
0.65/3.13
3.25
4.25
3.56
2.63
2.50
0.22 x 0.44
4.37
5.69
4.60
PFK5
FG2*/FGF2
100
PH100MLI
A
0.87/4.17
3.25
4.69
3.63
2.63
2.63
0.22 x 0.44
4.44
6.13
5.20
PFK5
FG2*/FGF2
150
PH150MLI
B
1.30/6.25
4.00
5.44
3.81
3.38
2.75
0.22 x 0.75
4.50
6.94
7.60
PFK6
FG3
250
PH250MLI
B
2.17/10.42
4.50
5.19
4.44
3.75
3.75
0.22 x 0.75
4.94
6.69
10.1
PFK6
FG4
350
PH350MLI
B
3.04/14.58
4.50
5.56
4.44
3.75
3.75
0.22 x 0.75
4.94
7.06
11.0
PFK7
FG4
500
PH500MLI
B
4.35/20.83
4.75
6.69
4.31
4.06
4.50
0.31 x 0.94
4.81
8.19
16.3
PFK7
FG4
750
PH750MLI
C
6.52/31.25
5.25
6.50
4.94
4.50
4.13
0.31 x 0.81
5.56
8.00
21.0
PFK7
FG5
1000
PH1000MLI
C
8.70/41.67
5.25
8.19
4.94
4.50
5.81
0.31 x 0.81
5.56
9.69
31.2
PFK7
FG5
All dimensions in inches
Secondary fuse clips and fuse clip mounting screws supplied standard with transformers up to and including 500VA.
Primary and Secondary voltage links/jumpers supplied standard with transformers up to and including 1000VA.
*Note: Unfused finger guard kits are marked with an asterisk, for more information refer to page 45.
Refer to page 72 for wiring schematic drawing. Custom voltages and VA sizes available upon request.
*** Available with FACTORY INSTALLED Primary and Secondary Fuse Kits up to 1000VA. To order, add the suffix “-FK” to the above part number. Refer to page 44 for details. ***
Group J
Primary Voltage: Secondary Voltage: VA
Rating
50
Catalog
Number
Mtg.
Fig.
415/400/380
110 X 220
Output
Amps
50/60 Hertz
Overall
Dimensions
Mounting
Centers
Mounting
Slot
A
B
C
D
E
GXH
Height
with
Finger
Guard
Depth
with
Finger
Guard
Approx.
Ship
Weight
Lbs.
Optional
Primary
Fuse
Kit P/N
Optional
Unfused and
Fused Finger
Guard Kit P/N
PH50MEMX
A
0.45/0.23
3.00
4.38
3.19
2.50
2.25
0.22 x 0.44
4.00
5.82
3.50
PFK4
FG1*/FGF1
75
PH75MEMX
A
0.68/0.34
3.25
4.06
3.63
2.63
2.63
0.22 x 0.44
4.44
5.50
4.10
PFK5
FG2*/FGF2
100
PH100MEMX
A
0.91/0.45
3.25
4.19
3.63
2.63
2.63
0.22 x 0.44
4.44
5.63
4.50
PFK5
FG2*/FGF2
150
PH150MEMX
B
1.36/0.68
4.00
4.94
3.81
3.38
2.75
0.22 x 0.75
4.50
6.44
5.70
PFK6
FG3
250
PH250MEMX
B
2.27/1.14
4.50
5.44
3.81
3.75
3.13
0.22 x 0.75
4.50
6.94
7.50
PFK6
FG3
350
PH350MEMX
B
3.18/1.59
4.50
5.19
4.44
3.75
3.75
0.22 x 0.75
4.94
6.69
10.1
PFK7
FG4
500
PH500MEMX
B
4.55/2.27
4.75
5.94
4.31
4.06
3.81
0.31 x 0.94
4.81
7.44
14.2
PFK7
FG4
750
PH750MEMX
B
6.82/3.41
5.25
6.50
4.94
4.50
4.13
0.31 x 0.81
5.56
8.00
21.0
PFK7
FG5
1000
PH1000MEMX
B
9.09/4.55
5.25
6.81
4.94
4.50
4.44
0.31 x 0.81
5.56
8.31
23.6
PFK7
FG5
Secondary fuse clips, fuse clip mounting screws and primary and secondary voltage links/jumpers supplied standard with transformers.
*Note: Unfused finger guard kits are marked with an asterisk, for more information refer to page 45.
Refer to page 73 for wiring schematic drawing. Custom voltages and VA sizes available upon request.
© Hammond Power Solutions Inc.
42
All dimensions in inches
Data subject to change without notice.
SECTION 1
SECTION 9
Machine Tool Industrial Control
SECTION 1
B
B
C
GxH
C
GxH
A
D
E
A
FIGURE A
E
D
FIGURE B
Group K
Primary Voltage: Secondary Voltage: VA
Rating
Catalog
Number
Mtg.
Fig.
380/277/208
120 X 240
Output
Amps
50/60 Hertz
Overall
Dimensions
Mounting
Centers
Mounting
Slot
A
B
C
D
E
GXH
Height
with
Finger
Guard
Depth
with
Finger
Guard
Approx.
Ship
Weight
Lbs.
Optional
Primary
Fuse
Kit P/N
Optional
Unfused and
Fused Finger
Guard Kit P/N
50
PH50MGJ
A
0.42/0.21
3.25
3.88
3.56
2.63
2.50
0.22 x 0.44
4.37
5.32
3.54
PFK5
FG2*/FGF2
75
PH75MGJ
A
0.63/0.31
3.25
4.19
3.63
2.63
2.63
0.22 x 0.44
4.44
5.63
4.50
PFK5
FG2*/FGF2
100
PH100MGJ
A
0.83/0.42
3.25
4.69
3.63
2.63
2.63
0.22 x 0.44
4.44
6.13
5.20
PFK5
FG2*/FGF2
150
PH150MGJ
B
1.25/0.63
4.00
5.44
3.81
3.38
2.75
0.22 x 0.75
4.50
6.94
7.60
PFK6
FG3
250
PH250MGJ
B
2.08/1.04
4.50
4.88
4.44
3.75
3.75
0.22 x 0.75
4.94
6.38
8.30
PFK6
FG4
350
PH350MGJ
B
2.92/1.46
4.50
5.56
4.44
3.75
3.75
0.22 x 0.75
4.94
7.06
11.0
PFK7
FG4
500
PH500MGJ
B
4.17/2.08
4.75
6.69
4.31
4.06
4.50
0.31 x 0.94
4.81
8.19
16.3
PFK7
FG4
750
PH750MGJ
B
6.25/3.13
5.25
6.81
4.94
4.50
4.44
0.31 x 0.81
5.56
8.31
23.6
PFK7
FG5
1000
PH1000MGJ
B
8.33/4.17
5.25
7.25
4.94
4.50
4.83
0.31 x 0.81
5.44
8.75
25.5
PFK7
FG5
Secondary fuse clips, fuse clip mounting screws and primary and secondary voltage links/jumpers supplied standard with transformers.
*Note: Unfused finger guard kits are marked with an asterisk, for more information refer to page 45.
Refer to page 74 for wiring schematic drawings. Custom voltages and VA sizes available upon request.
© Hammond Power Solutions Inc.
43
All dimensions in inches
Data subject to change without notice.
SECTION 1
HPS IMPERATOR®
Field Installed Fuse Kits
SECTION 1
Standard Secondary Fuse Kits (Field Installed)
All HPS Imperator control transformers are supplied with standard secondary fuse kits which include:
13/32” x 1 1/2” midget/type CC fuse clips, fuse clip mounting screws, primary and secondary voltage
links and the PHAK1 instruction sheet (note: secondary fuse clips and fuse clip mounting screws are not supplied on the
PH750PG, PH1000PG, PH750MLI, and PH1000MLI).
Optional Primary Fuse Kits (Field Installed)
All HPS Imperator series machine tool industrial control transformers up to and including 1500VA are
available with the following optional primary fuse kits:
Kit Part
Number
Applicable Transformer
Part Number Suffix’s
Applicable
VA Sizes
Parts Included in Kit
PFK1
PFK2
PFK3
PFK4
PFK5
PFK5
PFK6
PFK6
PFK7
Refer to
Specification
Tables
on Pages
38 to 43 for
Optional Primary
Fuse Kit P/N
Refer to
Specification
Tables
on Pages
38 to 43 for
Optional Primary
Fuse Kit P/N
4 fuse clips, 4 mtg. screws, PHAK1 instruction sheet
4 fuse clips, 4 mtg. screws, PHAK1 instruction sheet
4 fuse clips, 4 mtg. screws, PHAK1 instruction sheet
4 fuse clips, 4 mtg. screws, 1 jumper, 1 finger guard, PHAK1 instruction sheet
4 fuse clips, 4 mtg. screws, 1 jumper, 1 finger guard, PHAK1 instruction sheet
4 fuse clips, 4 mtg. screws, 1 jumper, 1 finger guard, PHAK1 instruction sheet
4 fuse clips, 4 mtg. screws, 1 jumper wire, PHAK1 instruction sheet
4 fuse clips, 4 mtg. screws, 1 jumper wire, PHAK1 instruction sheet
4 fuse clips, 4 mtg. screws, 1 jumper wire, PHAK1 instruction sheet
Note: Maximum allowable current rating on all primary and secondary fuse kits is 30 amps.
Factory Installed Fuse Kits
Factory Installed Primary and Secondary Fuse Kits
HPS now stocks some HPS Imperator series voltage groups with FACTORY INSTALLED primary and secondary
fuse clips. To order, just add the suffix “-FK” to the end of the standard part number.
Factory installed fusing only available on units up to 1500VA. The voltage groups that are stocked are:
Group C (p/n: PH***MQMJ-FK) | Group G (p/n: PH***PG-FK) | Group I (p/n: PH***MLI-FK)
On PH750PG-FK, PH1000PG-FK, PH750MLI-FK, and PH1000MLI-FK, only primary fuse clips are included on
factory installed units. Secondary fuse clips are not included or available on these units.
Other voltage groups available with factory installed fuse kits. Please contact your HPS sales or customer
service representative for details.
Note: All factory installed fuse kits are pre-wired at the transformers highest primary voltage and the lowest secondary voltage. To hook up at a different primary or secondary voltage, please refer to the wiring instruction sheet included with the transformer.
Sample Accessory Drawing
for Fuse Clips
(for 50, 75 and 100VA)
Sample Accessory Drawing
for Fuse Clips
Sample Assembly Drawing
for Secondary Fuse Clip
Installation
Sample Assembly Drawing
for Primary Fuse Clip
Installation
(for 150VA to 1500VA)
(For 150VA to 1500VA)
(For 150VA to 1500VA)
Note: HPS Imperator primary and secondary fuse kits are not suitable for branch circuit applications!
© Hammond Power Solutions Inc.
44
Data subject to change without notice.
SECTION 1
SECTION 9
Machine Tool Industrial Control
Optional Accessories
Finger Guards
Optional Unfused Finger Guard Kits
Kit Part
Number
Applicable Transformer
Part Number Suffixes
Applicable
VA Sizes
FG1
FG2
FG2
FG2
AJ, AR, MQMJ, MEMX, QR, SP, PG, PP
MBMH, MGJ, MLI
All
All (excluding PH100MBMH)
50
50
75
100
Refer to FG3, FG4 or FG5 below
150 to 1500
Note: Each finger guard kit supplies either the primary or secondary side.
Included in the kit: 1 finger guard (unfused) and PHAK1 instruction sheet
Optional Fused Finger Guard Kits
Kit Part
Number
Applicable Transformer
Part Number Suffixes
Applicable
VA Sizes
Parts Included in Kit
FGF1
FGF2
FGF2
FGF2
FG3
FG3
FG3
FG4
FG4
FG4
FG5
FG5
AJ, AR, MQMJ, MEMX, QR, SP, PG, PP
MBMH, MGJ, MLI
All
All (excluding PH100MBMH)
MBMH
All
AJ, AR, MQMJ, MEMX, QR, SP, PG, PP
MBMH, MGJ, MLI
All
AJ, AR, MQMJ, QR, SP, PP
MBMH, MEMX, MGJ, MLI, PG
All
50
50
75
100
100
150
250
250
350, 500
750
750
1000, 1500
1 finger guard (fused), PHAK1 instruction sheet
1 finger guard (fused), PHAK1 instruction sheet
1 finger guard (fused), PHAK1 instruction sheet
1 finger guard (fused), PHAK1 instruction sheet
1 finger guard, PHAK1 instruction sheet
1 finger guard, PHAK1 instruction sheet
1 finger guard, PHAK1 instruction sheet
1 finger guard, PHAK1 instruction sheet
1 finger guard, PHAK1 instruction sheet
1 finger guard, PHAK1 instruction sheet
1 finger guard, PHAK1 instruction sheet
1 finger guard, PHAK1 instruction sheet
Note: Each finger guard kit supplies either the primary or secondary side.
Sample Accessory Drawing
for Fused & Unfused
Finger Guards
(for 50, 75 and 100VA)
Sample Accessory Drawing
for Finger Guards
Sample Assembly Drawing
for Finger Guard Installation
(for 150VA and 1500VA)
© Hammond Power Solutions Inc.
(For 50, 75 and 100VA)
45
Sample Assembly Drawing
for Finger Guard Installation
(For 150VA to 1500VA)
Data subject to change without notice.
SECTION 1
The HPS Imperator line of machine tool industrial molded control transformers are available with the
following optional finger guard kits:
SECTION 1
HPS SPARTAN®
HPS Spartan® Industrial Open-Style Control Transformer
SECTION 1
The Economical Solution
The HPS Spartan® line of industrial control transformers are ideally suited for general purpose, industrial and
light duty loads. Designed for applications where high inrush or machine tool duty are not necessary, the HPS
Spartan industrial open-style control transformer offers an efficient and economical solution. These units are well
suited for HVAC applications, signal and alarm systems, motor control circuits, lighting and circuit isolation.
The HPS Spartan control transformer is an open style unit with molded terminal blocks up to 3000 VA or 30
amps. Optional Finger guards and a fuse block adapter kit are available upon request.
For an economical approach to control transformers, the HPS Spartan is the transformer of choice.
STANDARDS
The HPS Spartan Control Transformers meet or exceed the standards established by UL,
CSA, IEC and NEMA.
Standard
File #
UL (ANSI/UL506)
CSA
IEC 61558
NEMA (ST-1)
E50394
LR3902
© Hammond Power Solutions Inc.
VA Size
All
All All
All
46
Data subject to change without notice.
SECTION 1
SECTION 9
Industrial open-style control
Features and Benefits
•
•
•
•
•
•
•
•
•
•
•
•
1
Molded terminal blocks for primary and secondary connections1
Coil face termination over 3000VA or 30 amps
Vacuum Impregnated with Polyester Resin and oven cured
Bolted core construction
Bolt-on mounting brackets
All terminal blocks utilize a combination slot/Phillips #6 screw with a SEMS washer (suitable for 18 AWG
to 14 AWG for solid wire and 18 AWG to 12 AWG for stranded wire). Coil face terminations utilize a ¼ 20 UNC X 0.50” combination slot/Phillips screw and a spring lock washer
All units supplied with primary and secondary voltage links/jumpers
50/60 Hz (60 Hz on SP***ACP and SP***AR)
Copper wound coils with high dielectric strength insulation
Seismically certified in accordance with 2009 IBC for SDS <= 2.00g, z/h = 1.0 and IP = 1.5
CSA Certified, UL Listed, CE Marked and RoHS compliant
Meets NEMA standards
Superior insulating materials. The HPS Spartan series transformers offer the following insulation
systems:
Up to 1500 VA: 80°C rise, 130°C temperature class (B)
2000 VA to 5000 VA: 115°C rise, 180°C temperature class (F)
1
“Premium Packaging” which feature:
- Premium fluted cartons
- Custom molded foam inserts
- Easy removal and repacking
- Industry’s best box label
Supplied with trilingual installation and wiring instruction sheets
15 year warranty
Optional finger guards available1
Optional fuse block adapter kit available1
up to and including 3000VA or 30 amps
© Hammond Power Solutions Inc.
47
Data subject to change without notice.
SECTION 1
•
•
•
•
•
•
SECTION 1
HPS SPARTAN®
SECTION 1
B
C
GxH
A
B
B
D
C
GxH
E
A
FIGURE A
C
GxH
E
D
A
FIGURE B
E
D
B
FIGURE C
Group A
Primary Voltage:
600/480
Secondary Voltage: 120 X 240
VA
Rating
CE VA
Rating
Catalog
Number
Mtg.
Fig.
575/460
115 X 230
550/440
110 X 220
Overall
Dimensions
60 Hertz
Mounting
Centers
Mounting
Slot
A
B
C
D
E
GXH
Height
with
Finger
Guard
Output
Amps
Height
with
Fuse
Block
Adapter
Approx.
Ship
Weight
Lbs.
50
50
SP50ACP
A
0.42/0.21
2.60
3.82
2.60
2.13
2.64
0.22 x 0.44
2.98
2.79
2.2
100
100
SP100ACP
A
0.83/0.42
2.99
3.74
2.85
2.52
2.60
0.22 x 0.44
3.23
3.04
3.3
150
150
SP150ACP
A
1.25/0.63
2.99
4.29
2.85
2.52
3.15
0.22 x 0.44
3.23
3.04
4.4
250
160
SP250ACP
A
2.08/1.04
3.78
4.09
3.40
3.31
2.99
0.22 x 0.44
3.78
3.59
6.4
350
250
SP350ACP
A
2.92/1.46
3.78
4.49
3.40
3.31
3.39
0.22 x 0.44
3.78
3.59
7.5
500
300
SP500ACP
A
4.17/2.08
4.49
4.69
3.78
3.78
3.66
0.31 x 0.81
4.16
3.97
11
750
500
SP750ACP
A
6.25/3.13
5.25
5.081
4.37
4.50
4.06
0.31 x 0.81
4.75
4.56
18
1000
650
SP1000ACP
A
8.33/4.17
5.25
5.471
4.37
4.50
4.45
0.31 x 0.81
4.75
4.56
21
1500
1000
SP1500ACP
A
12.5/6.25
5.25
6.851
4.37
4.50
5.83
0.31 x 0.81
4.56
4.37
28
1
2000
1300
SP2000ACP
A
16.7/8.33
6.38
5.87
5.31
5.75
4.84
0.31 x 0.81
5.69
5.50
34
3000
2000
SP3000ACP
A
25.0/12.5
7.50
7.50
6.50
6.30
6.85
0.44 x 1.00
6.50
6.50
60
5000
3000
SP5000ACP
C
41.7/20.8
8.98
9.88
7.76
7.40
7.13
0.44 x 1.00
N/A
N/A
93
All dimensions in inches
Primary and Secondary voltage links/jumpers supplied standard with all transformers. Refer to page 75 for wiring schematic drawing.
Custom voltages and VA sizes available upon request.
1
Note: For 750 through 2000 VA units actual overall depth is 0.24” plus the value in column B.
Group B
Primary Voltage:
600
Secondary Voltage: 12 X 24
575
11.5 X 23
550
11 X 22
Overall
Dimensions
60 Hertz
Mounting
Centers
Mounting
Slot
A
B
C
D
E
GXH
Height
with
Finger
Guard
4.17/2.08
2.60
3.23
2.60
2.13
2.05
0.22 x 0.44
2.98
VA
Rating
CE VA
Rating
Catalog
Number
Mtg.
Fig.
Output
Amps
50
50
SP50AR
A
Height
with
Fuse
Block
Adapter
Approx.
Ship
Weight
Lbs.
2.79
1.5
100
100
SP100AR
A
8.33/4.17
2.99
3.74
2.85
2.52
2.60
0.22 x 0.44
3.23
3.04
3.3
150
150
SP150AR
A
12.5/6.25
2.99
4.09
2.85
2.52
2.95
0.22 x 0.44
3.23
3.04
3.9
250
160
SP250AR
A
20.8/10.4
3.78
3.70
3.40
3.31
2.60
0.22 x 0.44
3.78
3.59
5.2
350
250
SP350AR
A
29.2/14.6
3.78
4.29
3.40
3.31
3.19
0.22 x 0.44
3.78
3.59
7.1
500
300
SP500AR
B
41.7/20.8
4.49
5.08
3.78
3.78
3.27
0.31 x 0.81
4.16
3.97
9.9
Primary and Secondary voltage links/jumpers supplied standard with all transformers.
Refer to page 75 for wiring schematic drawing. Custom voltages and VA sizes available upon request.
© Hammond Power Solutions Inc.
48
All dimensions in inches
Data subject to change without notice.
SECTION 1
SECTION 9
Industrial open-style control
B
GxH
D
C
GxH
E
A
E
D
C
GxH
A
FIGURE B
FIGURE A
E
D
B
FIGURE C
Group C
Primary Voltage:
240 X 480
Secondary Voltage: 120 X 240
VA
Rating
CE VA
Rating
Catalog
Number
230 X 460
115 X 230
Mtg.
Fig.
Output
Amps
220 X 440
110 X 220
Overall
Dimensions
50/60 Hertz
Mounting
Centers
A
B
C
D
E
Mounting
Slot
GXH
Height
with
Finger
Guard
Height
with
Fuse
Block
Adapter
Approx.
Ship
Weight
Lbs.
50
50
SP50MQMJ
A
0.42/0.21
2.60
3.35
2.60
2.13
2.17
0.22 x 0.44
2.98
2.79
1.7
100
100
SP100MQMJ
A
0.83/0.42
2.99
3.74
2.85
2.52
2.60
0.22 x 0.44
3.23
3.04
3
150
150
SP150MQMJ
A
1.25/0.63
2.99
4.29
2.85
2.52
3.15
0.22 x 0.44
3.23
3.04
4.3
250
160
SP250MQMJ
A
2.08/1.04
3.78
4.09
3.40
3.31
2.99
0.22 x 0.44
3.78
3.59
6.5
350
250
SP350MQMJ
A
2.92/1.46
3.78
4.69
3.40
3.31
3.58
0.22 x 0.44
3.78
3.59
8.2
500
300
SP500MQMJ
A
4.17/2.08
4.49
4.69
3.78
3.78
3.66
0.31 x 0.81
4.16
3.97
11
1
750
500
SP750MQMJ
A
6.25/3.13
5.25
4.69
4.37
4.50
3.66
0.31 x 0.81
4.75
4.56
16
1000
650
SP1000MQMJ
A
8.33/4.17
5.25
5.471
4.37
4.50
4.45
0.31 x 0.81
4.75
4.56
21
1500
1000
SP1500MQMJ
A
12.5/6.25
5.25
6.851
4.37
4.50
5.83
0.31 x 0.81
4.75
4.56
28
1
2000
1300
SP2000MQMJ
A
16.7/8.33
6.38
5.87
5.31
5.75
4.84
0.31 x 0.81
5.50
5.31
35
3000
2000
SP3000MQMJ
A
25.0/12.5
7.50
7.50
6.50
6.30
7.28
0.44 x 1.00
6.50
6.50
64
5000
3000
SP5000MQMJ
C
41.7/20.8
8.98
9.88
7.76
7.40
7.28
0.44 x 1.00
N/A
N/A
97
All dimensions in inches
Primary and Secondary voltage links/jumpers supplied standard with all transformers.
Refer to page 76 for wiring schematic drawing. Custom voltages and VA sizes available upon request.
1
Note: For 750 through 2000 VA units actual overall depth is 0.24” plus the value in column B.
Group D
Primary Voltage:
240 X 480
Secondary Voltage: 12 X 24
230 X 460
11.5 X 23
VA
Rating
CE VA
Rating
Catalog
Number
Mtg.
Fig.
Output
Amps
50
50
SP50QR
A
4.17/2.08
220 X 440
11 X 22
Overall
Dimensions
50/60 Hertz
Mounting
Centers
Mounting
Slot
A
B
C
D
E
GXH
Height
with
Finger
Guard
2.60
3.35
2.60
2.13
2.17
0.22 x 0.44
2.98
Height
with
Fuse
Block
Adapter
Approx.
Ship
Weight
Lbs.
2.79
1.7
100
100
SP100QR
A
8.33/4.17
2.99
3.54
2.85
2.52
2.40
0.22 x 0.44
3.23
3.04
3
150
150
SP150QR
A
12.5/6.25
2.99
4.29
2.85
2.52
3.15
0.22 x 0.44
3.23
3.04
4.3
250
160
SP250QR
A
20.8/10.4
3.78
4.09
3.40
3.31
2.99
0.22 x 0.44
3.78
3.59
6.5
350
250
SP350QR
A
29.2/14.6
3.78
4.69
3.40
3.31
3.58
0.22 x 0.44
3.78
3.59
8.3
500
300
SP500QR
B
41.7/20.8
4.49
5.47
3.78
3.78
3.66
0.31 x 0.81
4.16
3.97
11
Primary and Secondary voltage links/jumpers supplied standard with all transformers.
Refer to page 76 for wiring schematic drawing. Custom voltages and VA sizes available upon request.
© Hammond Power Solutions Inc.
49
All dimensions in inches
Data subject to change without notice.
SECTION 1
C
A
B
B
SECTION 1
HPS SPARTAN®
SECTION 1
B
B
C
C
GxH
GxH
A
D
E
A
FIGURE A
E
D
FIGURE B
Group E
Primary Voltage: Secondary Voltage: VA
Rating
CE VA
Rating
380/347
120 X 240
Catalog
Number
Mtg.
Fig.
Output
Amps
50/60 Hertz
Overall
Dimensions
Mounting
Centers
A
B
C
D
E
Mounting
Slot
GXH
Height
with
Finger
Guard
Height
with
Fuse
Block
Adapter
Approx.
Ship
Weight
Lbs.
50
50
SP50KHP
A
0.42/0.21
2.60
3.35
2.60
2.13
2.17
0.22 x 0.44
2.98
2.79
1.7
100
100
SP100KHP
A
0.83/0.42
2.99
3.74
2.85
2.52
2.60
0.22 x 0.44
3.23
3.04
3.4
150
150
SP150KHP
A
1.25/0.63
2.99
4.29
2.85
2.52
3.15
0.22 x 0.44
3.23
3.04
4.4
250
160
SP250KHP
A
2.08/1.04
3.78
4.09
3.40
3.31
2.99
0.22 x 0.44
3.78
3.59
6.7
350
250
SP350KHP
A
2.92/1.46
3.78
4.69
3.40
3.31
3.58
0.22 x 0.44
3.78
3.59
8.4
500
300
SP500KHP
A
4.17/2.08
4.49
4.69
3.78
3.78
3.66
0.31 x 0.81
4.16
3.97
12
750
500
SP750KHP
A
6.25/3.13
5.25
4.691
4.37
4.50
3.66
0.31 x 0.81
4.75
4.56
17
1000
650
SP1000KHP
A
8.33/4.17
5.25
5.471
4.37
4.50
4.45
0.31 x 0.81
4.75
4.56
21
1500
1000
SP1500KHP
A
12.5/6.25
6.38
4.881
5.31
5.75
3.86
0.31 x 0.81
5.50
5.31
29
Primary and Secondary voltage links/jumpers supplied standard with all transformers.
Refer to page 77 for wiring schematic drawing. Custom voltages and VA sizes available upon request.
1
Note: For 750 through 1500 VA units actual overall depth is 0.24” plus the value in column B.
All dimensions in inches
Group F
Primary Voltage: Secondary Voltage: VA
Rating
CE VA
Rating
Catalog
Number
380/347
12 X 24
Mtg.
Fig.
50/60 Hertz
Overall
Dimensions
Output
Amps
A
B
Mounting
Centers
C
D
E
Mounting
Slot
GXH
Height
with
Finger
Guard
Height
with
Fuse
Block
Adapter
Approx.
Ship
Weight
Lbs.
50
50
SP50KHR
A
4.17/2.08
2.60
3.35
2.60
2.13
2.17
0.22 x 0.44
2.98
2.79
1.7
100
100
SP100KHR
A
8.33/4.17
2.99
3.74
2.85
2.52
2.60
0.22 x 0.44
3.23
3.04
3.3
150
150
SP150KHR
A
12.5/6.25
2.99
4.29
2.85
2.52
3.15
0.22 x 0.44
3.23
3.04
4.4
250
160
SP250KHR
A
20.8/10.4
3.78
4.09
3.40
3.31
2.99
0.22 x 0.44
3.78
3.59
6.4
350
250
SP350KHR
A
29.2/14.6
3.78
4.69
3.40
3.31
3.58
0.22 x 0.44
3.78
3.59
8.1
500
300
SP500KHR
B
41.7/20.8
4.49
5.47
3.78
3.78
3.66
0.31 x 0.81
4.16
3.97
11
Primary and Secondary voltage links/jumpers supplied standard with all transformers.
Refer to page 77 for wiring schematic drawing. Custom voltages and VA sizes available upon request.
© Hammond Power Solutions Inc.
50
All dimensions in inches
Data subject to change without notice.
SECTION 1
SECTION 9
Industrial open-style control
B
B
SECTION 1
C
C
GxH
GxH
A
D
E
A
E
D
FIGURE A
FIGURE B
Group G
Primary Voltage: Secondary Voltage: 277
120
50/60 Hertz
Overall
Dimensions
Mounting
Centers
Mounting
Slot
Height
with
Fuse
Block
Adapter
Approx.
Ship
Weight
Lbs.
A
B
C
D
E
GXH
Height
with
Finger
Guard
0.42
2.60
3.35
2.60
2.13
2.17
0.22 x 0.44
2.98
2.79
1.6
A
0.83
2.99
3.54
2.85
2.52
2.40
0.22 x 0.44
3.23
3.04
3.2
A
1.25
2.99
4.29
2.85
2.52
3.15
0.22 x 0.44
3.23
3.04
4.3
SP250NJ
A
2.08
3.78
4.09
3.40
3.31
2.99
0.22 x 0.44
3.78
3.59
6.4
SP350NJ
A
2.92
3.78
4.69
3.40
3.31
3.58
0.22 x 0.44
3.78
3.59
8.1
VA
Rating
CE VA
Rating
Catalog
Number
Mtg.
Fig.
Output
Amps
50
50
SP50NJ
A
100
100
SP100NJ
150
150
SP150NJ
250
160
350
250
500
300
SP500NJ
A
4.17
4.49
4.69
3.78
3.78
3.66
0.31 x 0.81
4.16
3.97
11
750
500
SP750NJ
A
6.25
5.25
5.081
4.37
4.50
4.06
0.31 x 0.81
4.75
4.56
18
1000
650
SP1000NJ
A
8.33
5.25
5.471
4.37
4.50
4.45
0.31 x 0.81
4.75
4.56
20
5.25
1
4.37
4.50
5.83
0.31 x 0.81
4.75
4.56
29
1500
1000
SP1500NJ
A
12.50
6.85
All dimensions in inches
Primary and Secondary voltage links/jumpers supplied standard with all transformers.
Refer to page 78 for wiring schematic drawing. Custom voltages and VA sizes available upon request.
1
Note: For 750 through 1500 VA units actual overall depth is 0.24” plus the value in column B.
Group H
Primary Voltage:
120 X 240
Secondary Voltage: 12 X 24
VA
Rating
CE VA
Rating
115 X 230
11.5 X 23
Catalog
Number
Mtg.
Fig.
Output
Amps
110 X 220
11 X 22
Overall
Dimensions
50/60 Hertz
Mounting
Centers
Mounting
Slot
A
B
C
D
E
GXH
Height
with
Finger
Guard
Height
with
Fuse
Block
Adapter
Approx.
Ship
Weight
Lbs.
50
50
SP50PR
A
4.17/2.08
2.60
3.35
2.60
2.13
2.17
0.22 x 0.44
2.98
2.79
1.7
100
100
SP100PR
A
8.33/4.17
2.99
3.74
2.85
2.52
2.60
0.22 x 0.44
3.23
3.04
3
150
150
SP150PR
A
12.5/6.25
2.99
4.29
2.85
2.52
3.15
0.22 x 0.44
3.23
3.04
4.3
250
160
SP250PR
A
20.8/10.4
3.78
3.90
3.40
3.31
2.80
0.22 x 0.44
3.78
3.59
5.9
350
250
SP350PR
A
29.2/14.6
3.78
4.69
3.40
3.31
3.58
0.22 x 0.44
3.78
3.59
8.2
500
300
SP500PR
B
41.7/20.8
4.49
5.47
3.78
3.78
3.66
0.31 x 0.81
4.16
3.97
11
Primary and Secondary voltage links/jumpers supplied standard with all transformers.
Refer to page 78 for wiring schematic drawing. Custom voltages and VA sizes available upon request.
© Hammond Power Solutions Inc.
51
All dimensions in inches
Data subject to change without notice.
SECTION 1
HPS SPARTAN®
B
SECTION 1
B
C
C
GxH
GxH
A
D
E
A
FIGURE A
E
D
FIGURE B
Group I
Primary Voltage:
208 X 416 200 X 400
Secondary Voltage: 120 X 240 115 X 230
VA
Rating
CE VA
Rating
Catalog
Number
Mtg.
Fig.
190 X 380
110 X 220
Overall
Dimensions
Output
Amps
50/60 Hertz
Mounting
Centers
A
B
C
D
Mounting
Slot
E
GXH
Height
with
Finger
Guard
Height
with
Fuse
Block
Adapter
Approx.
Ship
Weight
Lbs.
50
50
SP50SP
A
0.42/0.21
2.60
3.35
2.60
2.13
2.17
0.22 x 0.44
1.6
2.60
1.6
100
100
SP100SP
A
0.83/0.42
2.99
3.54
2.85
2.52
2.40
0.22 x 0.44
3
2.85
3
150
150
SP150SP
A
1.25/0.63
2.99
4.29
2.85
2.52
3.15
0.22 x 0.44
4.3
2.85
4.3
250
160
SP250SP
A
2.08/1.04
3.78
4.09
3.40
3.31
2.99
0.22 x 0.44
6.5
3.40
6.5
350
250
SP350SP
A
2.92/1.46
3.78
4.69
3.40
3.31
3.58
0.22 x 0.44
8.3
3.40
8.3
500
300
SP500SP
A
4.17/2.08
4.49
4.69
3.78
3.78
3.66
0.31 x 0.81
11
3.78
11
1
4.50
3.66
0.31 x 0.81
16
4.75
16
750
500
SP750SP
A
6.25/3.13
5.25
4.69
4.37
1000
650
SP1000SP
A
8.33/4.17
5.25
5.471
4.37
4.50
4.45
0.31 x 0.81
20
4.75
20
1500
1000
SP1500SP
A
12.5/6.25
6.38
4.881
5.31
5.75
3.86
0.31 x 0.81
27
5.69
27
All dimensions in inches
Primary and Secondary voltage links/jumpers supplied standard with all transformers.
Refer to page 79 for wiring schematic drawing. Custom voltages and VA sizes available upon request.
1
Note: For 750 through 1500 VA units actual overall depth is 0.24” plus the value in column B.
Group J
Primary Voltage:
208 X 416 200 X 400
Secondary Voltage: 12 X 24
11.5 X 23
VA
Rating
CE VA
Rating
Catalog
Number
Mtg.
Fig.
Output
Amps
190 X 380
11 X 22
Overall
Dimensions
50/60 Hertz
Mounting
Centers
Mounting
Slot
A
B
C
D
E
GXH
Height
with
Finger
Guard
Height
with
Fuse
Block
Adapter
Approx.
Ship
Weight
Lbs.
50
50
SP50SR
A
4.17/2.08
2.60
3.35
2.60
2.13
2.17
0.22 x 0.44
2.98
2.79
1.6
100
100
SP100SR
A
8.33/4.17
2.99
3.54
2.85
2.52
2.40
0.22 x 0.44
3.23
3.04
3.1
150
150
SP150SR
A
12.5/6.25
2.99
4.29
2.85
2.52
3.15
0.22 x 0.44
3.23
3.04
4.3
250
160
SP250SR
A
20.8/10.4
3.78
4.09
3.40
3.31
2.99
0.22 x 0.44
3.78
3.59
6.5
350
250
SP350SR
A
29.2/14.6
3.78
4.69
3.40
3.31
3.58
0.22 x 0.44
3.78
3.59
8.3
500
300
SP500SR
B
41.7/20.8
4.49
5.47
3.78
3.78
3.66
0.31 x 0.81
4.16
3.97
11
Primary and Secondary voltage links/jumpers supplied standard with all transformers.
Refer to page 79 for wiring schematic drawing. Custom voltages and VA sizes available upon request.
© Hammond Power Solutions Inc.
52
All dimensions in inches
Data subject to change without notice.
SECTION 1
SECTION 9
Industrial open-style control
Optional Accessories
Finger Guards
HPS Spartan industrial control transformers up to and including 3000VA or 30 amps are available with
optional finger guards.
Applicable Transformer
Part Number Suffixes
SPFG1
AR, QR, PR, KHR, SR
50 to 500
SPFG1
KHP, SP, NJ
50 to 1500
SPFG1
ACP, MQMJ
50 to 3000
SECTION 1
Part
Number
Applicable
VA Sizes
Note: Each finger guard supplies either the primary or secondary side. Finger guard option not
available on SP5000ACP and SP5000MQMJ standard units. Add 0.38” per finger guard to overall
depth (column B) on units from 50 VA to 500 VA and 0.31” to units from 750 VA to 2000 VA when finger
guard has been installed. For custom units, optional finger guards are only available on units up to
3000VA or 30 amps.
Sample Assembly Drawing for
Optional Finger Guard Installation
Finger Guard
(Only available for units supplied with either a primary
or secondary molded terminal block)
(Optional)
Fuse Block Adapter Kit
HPS Spartan industrial control transformers up to and including 3000VA or 30 amps are available with
optional fuse block adapter kits. The Fuse Block Adapter Kit is designed to allow for the installation
of any third party after market fuse block assembly onto the industrial control transformer. The
transformer must be a unit that incorporates a molded terminal block on either the primary or secondary
side.
Note: HPS does not provide any jumpers or appropriate fuses for any after market fuse block you install on the HPS Spartan
industrial control transformer. The HPS fuse block adapter kit provides only the mechanical means of attaching a third party after
market fuse block. HPS does not recommend any specific fuse block or fuse supplier. For a recommended size of fuse, please see
page # 32.
Kit Part
Number
Applicable Transformer
Part Number Suffixes
Applicable
VA Sizes
SPFBAK1
AR, QR, PR, KHR, SR
50 to 500
SPFBAK1
KHP, SP, NJ
50 to 1500
SPFBAK1
ACP, MQMJ
50 to 3000
Note: Only 1 fuse block adapter kit is required per transformer. Fuse block adapter kit not available
on SP5000ACP and SP5000MQMJ standard units. Add 0.38” per fuse block adapter to overall depth
(column B) on units from 750 VA to 3000 VA when optional fuse block adapter is installed. For custom
units, optional fuse block adapter kit is only available on units up to 3000VA or 30 amps.
Sample Assembly Drawing for
Optional Fuse Block Adapter Installation
Fuse Block Adapter Kit
(Optional)
For detailed installation instructions of HPS Spartan transformers or the optional finger guards and fuse block adapter kits, please visit our
website under Products and Services - Literature & Resources - Instruction Sheets - Control Transformers.
Or go to the following link: http://www.hammondpowersolutions.com/products/product_literature/instruction_sheets/control_transformers.php
© Hammond Power Solutions Inc.
53
Data subject to change without notice.
SECTION 1
HPS FUSION™
HPS Fusion™ General Purpose Enclosed Transformer
SECTION 1
The Ideal Solution
The HPS Fusion™ line of single phase, general purpose enclosed transformers are ideally suited for general
purpose, industrial and light duty loads. They have been designed for indoor applications and offer an efficient
and economical solution. These units are well suited for HVAC applications, signal and alarm systems, motor
control circuits, lighting and circuit isolation.
The HPS Fusion control transformer is an enclosed style unit with either molded terminal blocks (on units up
to 3000 VA or 30 amps) or coil face termination. Optional Finger guards and a fuse block adapter kit are available
upon request.
For an economical approach to general purpose loads, the HPS Fusion is the transformer of choice.
STANDARDS
The HPS Fusion Control Transformers meet or exceed the standards established by UL,
CSA, IEC and NEMA.
Standard
File #
UL (ANSI/UL506)
CSA
IEC 61558
NEMA (ST-1)
E50394
LR3902
VA Size
All
All All
All
54
© Hammond Power Solutions Inc.
Data subject to change without notice.
SECTION 1
SECTION 9
General Purpose Enclosed
Features and Benefits
•
•
•
•
Molded terminal blocks for primary and secondary connections up to 3000 VA or 30 amps; coil face
termination over 3000VA or 30 amps
All terminal blocks utilize a combination slot/Phillips #6 screw with a SEMS washer (suitable for 18 AWG
to 14 AWG for solid wire and 18 AWG to 12 AWG for stranded wire). Coil face terminations utilize a
¼ - 20 UNC X 0.50” combination slot/Phillips screw and a spring lock washer
Vacuum Impregnated with Polyester Resin and oven cured
Bolted core construction
Bolt-on mounting brackets
Coils with high dielectric strength insulation
Seismically certified in accordance with 2009 IBC for SDS <= 2.00g, z/h = 1.0 and IP = 1.5
CSA Certified, UL Listed, CE Marked and RoHS compliant
Meets NEMA standards
Superior insulating materials. The HPS Fusion series transformers offer the following insulation
systems:
Up to 1500 VA: 95°C temperature rise, 130°C insulation class (B)
2000 VA to 5000 VA: 130°C temperature rise, 180°C insulation class (F)
(Note: Temperature rise based on 25°C ambient)
50/60 Hz (60 Hz on FS***ACP and FS***AR)
Rugged NEMA 1 enclosure
Finish - forest green powder coat
Primary and secondary ground screw
•
•
•
•
•
Four (0.88”) wiring knockouts and four (0.50”) accessory knockouts
Optional panel mount fuse holder available
Easy mounting and installation via four mounting slots and two keyhole slots
Easy access to primary and secondary wiring compartments through removable covers
15 year warranty
•
•
•
•
•
•
•
•
•
55
© Hammond Power Solutions Inc.
Data subject to change without notice.
SECTION 1
•
SECTION 1
HPS FUSION™
E
A
SECTION 1
D
C
B
GxH
Group A
Primary Voltage:
600/480
Secondary Voltage: 120 X 240
VA
Rating
CE VA
Rating
Catalog
Number
575/460
115 X 230
550/440
110 X 220
Overall
Dimensions
Output
Amps
A
60 Hertz
Mounting
Centers
B
C
D
E
Mounting
Slot
GXH
Approx.
Ship
Weight
Lbs.
50
50
FS50ACP
0.42/0.21
2.7
6.4
3.33
1.66
4.16
0.22 x 0.44
3.0
100
100
FS100ACP
0.83/0.42
3.09
6.3
3.6
2.05
3.5
0.22 x 0.44
4.2
150
150
FS150ACP
1.25/0.63
3.09
6.9
3.6
2.05
4.1
0.22 x 0.44
5.3
250
160
FS250ACP
2.08/1.04
3.9
6.6
4.3
2.52
3.9
0.22 x 0.44
7.6
350
250
FS350ACP
2.92/1.46
3.9
7
4.3
2.52
4.3
0.22 x 0.44
8.7
500
300
FS500ACP
4.17/2.08
4.6
7.2
4.6
3.3
4.5
0.31 x 0.81
13.3
750
500
FS750ACP
6.25/3.13
5.6
7.6
5.1
4
4.9
0.31 x 0.81
20.3
1000
650
FS1000ACP
8.33/4.17
5.6
8
5.1
4
5.3
0.31 x 0.81
22.9
1500
1000
FS1500ACP
12.5/6.25
5.6
9.4
5.1
4
6.7
0.31 x 0.81
30.3
2000
1300
FS2000ACP
16.7/8.33
6.6
9.1
6
5.1
5.7
0.31 x 0.81
37.1
3000
2000
FS3000ACP
25.0/12.5
7.8
11.3
6.7
6.3
6.9
0.31 x 0.81
64.0
5000
3000
FS5000ACP
41.7/20.8
9.3
14.9
8
7.1
7.3
0.31 x 0.81
99.7
All dimensions in inches
Primary and Secondary voltage links/jumpers supplied standard with all transformers.
Refer to page 75 for wiring schematic drawing. Custom voltages and VA sizes available upon request.
Group B
Primary Voltage:
600
Secondary Voltage: 12 X 24
VA
Rating
CE VA
Rating
575
11.5 X 23
Catalog
Number
Output
Amps
550
11 X 22
60 Hertz
Overall
Dimensions
Mounting
Centers
Mounting
Slot
A
B
C
D
E
GXH
Approx.
Ship
Weight
Lbs.
50
50
FS50AR
4.17/2.08
2.7
5.8
3.33
1.66
3.58
0.22 x 0.44
2.3
100
100
FS100AR
8.33/4.17
3.09
6.3
3.6
2.05
3.5
0.22 x 0.44
4.2
150
150
FS150AR
12.5/6.25
3.09
6.7
3.6
2.05
3.9
0.22 x 0.44
4.8
250
160
FS250AR
20.8/10.4
3.9
6.2
4.3
2.52
3.5
0.22 x 0.44
6.4
350
250
FS350AR
29.2/14.6
3.9
6.8
4.3
2.52
4.1
0.22 x 0.44
8.3
500
300
FS500AR
41.7/20.8
4.6
6.8
4.1
3.3
4.5
0.31 x 0.81
11.8
Primary and Secondary voltage links/jumpers supplied standard with all transformers.
Refer to page 75 for wiring schematic drawing. Custom voltages and VA sizes available upon request.
All dimensions in inches
56
© Hammond Power Solutions Inc.
Data subject to change without notice.
SECTION 1
SECTION 9
General Purpose Enclosed
E
A
SECTION 1
D
C
B
GxH
Group C
Primary Voltage:
240 X 480
Secondary Voltage: 120 X 240
VA
Rating
CE VA
Rating
230 X 460
115 X 230
Catalog
Number
Output
Amps
220 X 440
110 X 220
Overall
Dimensions
50/60 Hertz
Mounting
Centers
A
B
C
D
E
Mounting
Slot
GXH
Approx.
Ship
Weight
Lbs.
50
50
FS50MQMJ
0.42/0.21
2.7
5.9
3.33
1.66
3.69
0.22 x 0.44
2.5
100
100
FS100MQMJ
0.83/0.42
3.09
6.3
3.6
2.05
3.5
0.22 x 0.44
3.9
150
150
FS150MQMJ
1.25/0.63
3.09
6.9
3.6
2.05
4.1
0.22 x 0.44
5.2
250
160
FS250MQMJ
2.08/1.04
3.9
6.6
4.3
2.52
3.9
0.22 x 0.44
7.7
350
250
FS350MQMJ
2.92/1.46
3.9
7.2
4.3
2.52
4.9
0.22 x 0.44
9.4
500
300
FS500MQMJ
4.17/2.08
4.6
7.2
4.6
3.3
4.5
0.31 x 0.81
13.2
750
500
FS750MQMJ
6.25/3.13
5.6
7.2
5.1
4
4.5
0.31 x 0.81
18.0
1000
650
FS1000MQMJ
8.33/4.17
5.6
8
5.1
4
5.3
0.31 x 0.81
22.8
1500
1000
FS1500MQMJ
12.5/6.25
6.6
8.5
6
5.1
5.1
0.31 x 0.81
31.1
2000
1300
FS2000MQMJ
16.7/8.33
6.6
9.1
6
5.1
5.7
0.31 x 0.81
38.1
3000
2000
FS3000MQMJ
25.0/12.5
7.8
11.7
6.7
6.3
7.3
0.31 x 0.81
68.5
5000
3000
FS5000MQMJ
41.7/20.8
9.3
15.1
8
7.4
7.3
0.31 x 0.81
104.2
All dimensions in inches
Primary and Secondary voltage links/jumpers supplied standard with all transformers.
Refer to page 76 for wiring schematic drawing. Custom voltages and VA sizes available upon request.
Group D
Primary Voltage:
240 X 480
Secondary Voltage: 12 X 24
VA
Rating
CE VA
Rating
230 X 460
11.5 X 23
Catalog
Number
Output
Amps
220 X 440
11 X 22
Overall
Dimensions
A
50/60 Hertz
Mounting
Centers
B
C
D
E
Mounting
Slot
GXH
Approx.
Ship
Weight
Lbs.
50
50
FS50QR
4.17/2.08
2.7
5.9
3.33
1.66
3.69
0.22 x 0.44
2.5
100
100
FS100QR
8.33/4.17
3.09
6.1
3.6
2.05
3.35
0.22 x 0.44
3.9
150
150
FS150QR
12.5/6.25
3.09
6.9
3.6
2.05
4.1
0.22 x 0.44
5.2
250
160
FS250QR
20.8/10.4
3.9
6.6
4.3
2.52
3.9
0.22 x 0.44
7.7
350
250
FS350QR
29.2/14.6
3.9
7.2
4.3
2.52
4.9
0.22 x 0.44
9.5
500
300
FS500QR
41.7/20.8
4.6
7.2
4.6
3.3
4.5
0.31 x 0.81
13.4
Primary and Secondary voltage links/jumpers supplied standard with all transformers.
Refer to page 76 for wiring schematic drawing. Custom voltages and VA sizes available upon request.
All dimensions in inches
57
© Hammond Power Solutions Inc.
Data subject to change without notice.
SECTION 1
HPS FUSION™
E
A
SECTION 1
D
C
B
GxH
Group E
Primary Voltage:
380/347
Secondary Voltage: 120 X 240
VA
Rating
CE VA
Rating
50/60 Hertz
Catalog
Number
Output
Amps
Overall
Dimensions
A
Mounting
Centers
B
C
D
E
Mounting
Slot
GXH
Approx.
Ship
Weight
Lbs.
50
50
FS50KHP
0.42/0.21
2.7
5.9
3.33
1.66
3.69
0.22 x 0.44
2.5
100
100
FS100KHP
0.83/0.42
3.09
6.3
3.6
2.05
3.5
0.22 x 0.44
4.3
150
150
FS150KHP
1.25/0.63
3.09
6.9
3.6
2.05
4.1
0.22 x 0.44
5.3
250
160
FS250KHP
2.08/1.04
3.9
6.6
4.3
2.52
3.9
0.22 x 0.44
7.9
350
250
FS350KHP
2.92/1.46
3.9
7.2
4.3
2.52
4.9
0.22 x 0.44
9.6
500
300
FS500KHP
4.17/2.08
4.6
7.2
4.6
3.3
4.5
0.31 x 0.81
13.6
750
500
FS750KHP
6.25/3.13
5.6
7.2
5.1
4
4.5
0.31 x 0.81
19
1000
650
FS1000KHP
8.33/4.17
5.6
8
5.1
4
5.3
0.31 x 0.81
23.5
1500
1000
FS1500KHP
12.5/6.25
6.6
8.5
6
5.1
5.1
0.31 x 0.81
Primary and Secondary voltage links/jumpers supplied standard with all transformers.
Refer to page 77 for wiring schematic drawing. Custom voltages and VA sizes available upon request.
31.6
All dimensions in inches
Group F
Primary Voltage:
380/347
Secondary Voltage: 12 X 24
VA
Rating
CE VA
Rating
Catalog
Number
50/60 Hertz
Overall
Dimensions
Output
Amps
Mounting
Centers
A
B
C
D
E
Mounting
Slot
GXH
Approx.
Ship
Weight
Lbs.
50
50
FS50KHR
4.17/2.08
2.7
5.9
3.33
1.66
3.69
0.22 x 0.44
2.5
100
100
FS100KHR
8.33/4.17
3.09
6.3
3.6
2.05
3.5
0.22 x 0.44
4.2
150
150
FS150KHR
12.5/6.25
3.09
6.9
3.6
2.05
4.1
0.22 x 0.44
5.3
250
160
FS250KHR
20.8/10.4
3.9
6.6
4.3
2.52
3.9
0.22 x 0.44
7.6
350
250
FS350KHR
29.2/14.6
3.9
7.2
4.3
2.52
4.9
0.22 x 0.44
9.3
500
300
FS500KHR
41.7/20.8
4.6
7.2
4.6
3.3
4.5
0.31 x 0.81
13.2
Primary and Secondary voltage links/jumpers supplied standard with all transformers.
Refer to page 77 for wiring schematic drawing. Custom voltages and VA sizes available upon request.
All dimensions in inches
58
© Hammond Power Solutions Inc.
Data subject to change without notice.
SECTION 1
SECTION 9
General Purpose Enclosed
E
A
SECTION 1
D
C
B
GxH
Group G
Primary Voltage:
277
Secondary Voltage: 120
50/60 Hertz
Overall
Dimensions
Mounting
Centers
Mounting
Slot
A
B
C
D
E
GXH
Approx.
Ship
Weight
Lbs.
0.42
2.7
5.9
3.33
1.66
3.69
0.22 x 0.44
2.4
FS100NJ
0.83
3.09
6.1
3.6
2.05
3.35
0.22 x 0.44
4.1
FS150NJ
1.25
3.09
6.9
3.6
2.05
4.1
0.22 x 0.44
5.2
160
FS250NJ
2.08
3.9
6.6
4.3
2.52
3.9
0.22 x 0.44
7.6
250
FS350NJ
2.92
3.9
7.2
4.3
2.52
4.9
0.22 x 0.44
9.3
VA
Rating
CE VA
Rating
Catalog
Number
Output
Amps
50
50
FS50NJ
100
100
150
150
250
350
500
300
FS500NJ
4.17
4.6
7.2
4.6
3.3
4.5
0.31 x 0.81
13.3
750
500
FS750NJ
6.25
5.6
7.6
5.1
4
4.9
0.31 x 0.81
20.1
1000
650
FS1000NJ
8.33
5.6
8
5.1
4
5.3
0.31 x 0.81
22.8
1500
1000
FS1500NJ
12.50
5.6
9.4
5.1
4
6.7
0.31 x 0.81
31.1
All dimensions in inches
Primary and Secondary voltage links/jumpers supplied standard with all transformers.
Refer to page 78 for wiring schematic drawing. Custom voltages and VA sizes available upon request.
Group H
Primary Voltage:
120 X 240
Secondary Voltage: 12 X 24
VA
Rating
CE VA
Rating
115 X 230
11.5 X 23
Catalog
Number
Output
Amps
110 X 220
11 X 22
Overall
Dimensions
A
50/60 Hertz
Mounting
Centers
B
C
D
E
Mounting
Slot
GXH
Approx.
Ship
Weight
Lbs.
50
50
FS50PR
4.17/2.08
2.7
5.9
3.33
1.66
3.69
0.22 x 0.44
2.5
100
100
FS100PR
8.33/4.17
3.09
6.1
3.6
2.05
3.35
0.22 x 0.44
3.9
150
150
FS150PR
12.5/6.25
3.09
6.9
3.6
2.05
4.1
0.22 x 0.44
5.2
250
160
FS250PR
20.8/10.4
3.9
6.4
4.3
2.52
3.7
0.22 x 0.44
7.1
350
250
FS350PR
29.2/14.6
3.9
7.2
4.3
2.52
4.9
0.22 x 0.44
9.4
500
300
FS500PR
41.7/20.8
4.6
7.2
4.6
3.3
4.5
0.31 x 0.81
13.2
Primary and Secondary voltage links/jumpers supplied standard with all transformers.
Refer to page 78 for wiring schematic drawing. Custom voltages and VA sizes available upon request.
All dimensions in inches
59
© Hammond Power Solutions Inc.
Data subject to change without notice.
SECTION 1
HPS FUSION™
E
A
SECTION 1
D
C
B
GxH
Group I
Primary Voltage:
208 X 416
Secondary Voltage: 120 X 240
VA
Rating
CE VA
Rating
Catalog
Number
200 X 400
115 X 230
190 X 380
110 X 220
Overall
Dimensions
50/60 Hertz
Mounting
Centers
Mounting
Slot
A
B
C
D
E
GXH
Approx.
Ship
Weight
Lbs.
0.22 x 0.44
2.4
Output
Amps
50
50
FS50SP
0.42/0.21
2.7
5.9
3.33
1.66
3.69
100
100
FS100SP
0.83/0.42
3.09
6.1
3.6
2.05
3.35
0.22 x 0.44
3.9
150
150
FS150SP
1.25/0.63
3.09
6.9
3.6
2.05
4.1
0.22 x 0.44
5.2
250
160
FS250SP
2.08/1.04
3.9
6.6
4.3
2.52
3.9
0.22 x 0.44
7.7
350
250
FS350SP
2.92/1.46
3.9
7.2
4.3
2.52
4.9
0.22 x 0.44
9.5
500
300
FS500SP
4.17/2.08
4.6
7.2
4.6
3.3
4.5
0.31 x 0.81
13.3
750
500
FS750SP
6.25/3.13
5.6
7.2
5.1
4
4.5
0.31 x 0.81
18.2
1000
650
FS1000SP
8.33/4.17
5.6
8
5.1
4
5.3
0.31 x 0.81
22.5
1500
1000
FS1500SP
12.5/6.25
6.6
8.5
6
5.1
5.1
0.31 x 0.81
30.1
Primary and Secondary voltage links/jumpers supplied standard with all transformers.
Refer to page 79 for wiring schematic drawing. Custom voltages and VA sizes available upon request.
All dimensions in inches
Group J
Primary Voltage:
208 X 416
Secondary Voltage: 12 X 24
VA
Rating
CE VA
Rating
Catalog
Number
200 X 400
11.5 X 23
Output
Amps
190 X 380
11 X 22
Overall
Dimensions
A
50/60 Hertz
Mounting
Centers
B
C
D
Mounting
Slot
E
GXH
Approx.
Ship
Weight
Lbs.
50
50
FS50SR
4.17/2.08
2.7
5.9
3.33
1.66
3.69
0.22 x 0.44
2.4
100
100
FS100SR
8.33/4.17
3.09
6.1
3.6
2.05
3.35
0.22 x 0.44
4
150
150
FS150SR
12.5/6.25
3.09
6.9
3.6
2.05
4.1
0.22 x 0.44
5.2
250
160
FS250SR
20.8/10.4
3.9
6.6
4.3
2.52
3.9
0.22 x 0.44
7.7
350
250
FS350SR
29.2/14.6
3.9
7.2
4.3
2.52
4.9
0.22 x 0.44
9.5
500
300
FS500SR
41.7/20.8
4.6
7.2
4.6
3.3
4.5
0.31 x 0.81
13.3
Primary and Secondary voltage links/jumpers supplied standard with all transformers.
Refer to page 79 for wiring schematic drawing. Custom voltages and VA sizes available upon request.
All dimensions in inches
60
© Hammond Power Solutions Inc.
Data subject to change without notice.
SECTION 1
SECTION 9
General Purpose Enclosed
Optional Accessories
Fuse Holder Kit
Part
Number
Applicable Transformer
Part Number Suffixes
Applicable
Specifications
FSFH1
All
Up to 20 amps and 250V
Sample Assembly Drawing for
Optional Fuse Kit Installation
Fuse Kit
(Only available for units supplied with either a primary
or secondary molded terminal block)
(Optional)
For detailed installation instructions of HPS Fusion transformers or the optional fuse kits, please
visit our website under Products and Services - Literature & Resources - Instruction Sheets - Control
Transformers.
Or go to the following link: http://www.hammondpowersolutions.com/products/product_literature/
instruction_sheets/control_transformers.php
61
© Hammond Power Solutions Inc.
Data subject to change without notice.
SECTION 1
This general purpose enclosed transformer optional secondary fuse holder kit is specifically designed to
provide circuit protection up to a maximum of 20 amps and up to 250V. The fuse holder kit is supplied
with leads for easy hook-up and is easy to install. Fuses are NOT supplied with this kit. Fuses should
be selected in accordance with CSA, UL and local electrical codes.
SECTION 1
Q SERIES
SECTION 1
SINGLE PHASE ENCLOSED Encapsulated
CONTROL TRANSFORMER FEATURES
For applications where a cost effective approach to general purpose loads indoor or outdoor is required,
consider the ‘Q’ series, single phase encapsulated control transformer. These units are specifically designed for
the following applications;
 General purpose enclosed control applications used to adjust a supply voltage to match a load
requirement.
 Supplying machine tool circuits.
 Actuating relays, bells, signal and alarm systems.
 Operating small motors, valves and dampers.
 Industrial lighting and circuit isolation.
50 to 5000VA
SINGLE PHASE ENCLOSED Encapsulated CONTROL STANDARD SPECIFICATIONS
50 to 5000VA
Benefits
UL Listed
File: E50394
CSA Certified
File: LR3902
Frequency
60 Hertz
Insulation System
Up to 1kVA; Class B, 80°C temperature rise.
1.5 to 5kVA; Class F, 115°C temperature rise.
Assures long life and reliable performance.
Standard Design
Single Phase, all welded core construction made
with high quality, high permeability silicon steel
laminations.
Computer designed coils, accurately wound with
optimum mean turns made from high quality
magnetic wire with insulation film.
Rugged one-piece assembly with low noise
provides optimum performance and reliability.
Encapsulation
All units from 50VA to 5kVA are encapsulated with
electrical grade silica sand and resin compounds.
Completely encloses the core and coil to
seal out moisture, airborne contaminants and
eliminates corrosion & insulation deterioration.
Enclosure Type
Heavy Duty NEMA Type 3R (conduit knockouts
on sides and rear)
Meets the heavy industrial trade requirements
for indoor/outdoor enclosed transformers.
Termination
Front accessible wiring compartment with high
and low voltage copper lead wires or tabs.
Ample space for transformer connection for
primary and secondary terminations.
Mounting
Designed for vertical or horizontal mounting.
Facilitates any installation requirement.
© Hammond Power Solutions Inc.
62
Provides enhanced voltage regulation, excellent
thermal characteristics and compliments
modern winding techniques.
Data subject to change without notice.
SECTION 1
SECTION 9
Enclosed encapsulated
(potted) Control
SINGLE PHASE, NEMA 3R STYLE ENCLOSURE
VA
Rating
50
12/24 Secondary Volts Approx. Dimensions
(Inches)
Case
Style
60 Hz
Wiring
Diagram
(Page 262)
Width
Depth
Height
Approx.
Weight
(Lbs.)
QC05PRCB
NQ0
3.75
5.25
7.25
6
W
SCD 4
Catalog
Number
Mtg Type
W - Wall
(Page 277)
100
QC10PRCB
NQ0
3.75
5.25
7.25
7
W
SCD 4
150
QC15PRCB
NQ0
3.75
5.25
7.25
8
W
SCD 4
200
QC20PRCB
NQ1
4.50
5.75
7.25
11
W
SCD 4
250
QC25PRCB
NQ1
4.50
5.75
7.25
13
W
SCD 4
350
QC35PRCB
NQ1
4.50
5.75
7.25
14
W
SCD 4
500
QC50PRCB
NQ2
5.00
4.75
9.25
15
W
SCD 4
750
QC75PRCB
NQ2
5.00
4.75
9.25
18
W
SCD 4
1000
Q1C0PRCB
NQ3
5.88
5.50
10.50
25
W
SCD 4
1500
Q1C5PRCF
NQ4
7.00
6.50
11.75
36
W
SCD 4
2000
Q002PRCF
NQ4
7.00
6.50
11.75
46
W
SCD 4
3000
Q003PRCF
NQ4
7.00
6.50
11.75
65
W
SCD 4
5000
Q005PRCF
NQ5
10.00
7.75
17.25
105
W
SCD 4
©
Power Solutions
Solutions Inc.
Inc.
© Hammond
Hammond Power
63
Data
Data subject
subject to
to change
change without
without notice.
notice.
SECTION 1
600 Primary Volts
SECTION 1
HPS IMPERATOR®
HPS Imperator - Wiring Schematic Drawings
Group A
PH***AJ Schematic for 50, 75 and 100VA Units
SECTION 1
HV
550V
575V
600V
1
2
3
7
6
5
8
1
4
4
4
High Voltage (HV) Install Supplied Jumpers/ Supply Lines
(Primary Volts)Links Between Terminals
Connect To
4
3
6
3 2
2
1
5
4
110V
115V
120V
1
3
2
220V
230V
240V
LV
600 575 550
600 575 550
Low Voltage (LV) (Secondary Volts)
1 120 115 110
240230220
120 115 110
240230220
None
None
1, 4
6, 7
Install Supplied Links Load Lines
Between Terminals Connect To
3-4, 1-2
2-3
3-4, 1-2
2-3
1, 4
1, 4
4, 6
4, 6
Install Fuse
Clips To
Unfused
1-5, 4-8
Install Fuse
Clips To
Unfused
Unfused
1-5
1-5
PH***AJ Schematic for 150VA to 1500VA Units
HV
550V
575V
600V
1 2
3
4
5
High Voltage (HV) Install Supplied Jumpers/ Supply Lines
(Primary Volts)Links Between Terminals Connect To
6
6
1
7
8
2
5
5
6 5 4
4 3
3 2 1
110V
115V
120V
LV
1
7
2
600 575 550
600 575 550
Low Voltage (LV) (Secondary Volts)
6 5 4 3 2 1 220V
230V
240V
None
None
Install Supplied Links Load Lines
Between Terminals
Connect To
120 115 110
240230220
120 115 110
240 230 220
© Hammond Power Solutions Inc.
2, 5
1, 6
4-5, 2-3
3-4
4-5, 2-3
3-4
64
2, 5
2, 5
1, 5
1, 5
Install Fuse
Clips To
Unfused
2-7, 5-8
Install Fuse
Clips To
Unfused
Unfused
2-7
2-7
Data subject to change without notice.
SECTION 1
SECTION 9
Machine Tool Industrial Control
HPS Imperator - Wiring Schematic Drawings continued
Group B
PH***AR Schematic for 50, 75 and 100VA Units
550V
575V
600V
1
2
3
7
6
5
8
1
4
4
4
High Voltage (HV) Install Supplied Jumpers/ Supply Lines
(Primary Volts)Links Between Terminals Connect To
4
3
6
3 2
2
1
5
4
11V
11.5V
12V
1
3
600 575 550
600 575 550
Low Voltage (LV) (Secondary Volts)
1 2
22V
23V
24V
LV
None
None
1, 4
6, 7
Install Supplied Links Load Lines
Between Terminals Connect To
12 11.5 11
242322
12 11.5 11
242322
3-4, 1-2
2-3
3-4, 1-2
2-3
1, 4
1, 4
4, 6
4, 6
Install Fuse
Clips To
Unfused
1-5, 4-8
Install Fuse
Clips To
Unfused
Unfused
1-5
1-5
PH***AR Schematic for 150VA to 500VA Units
HV
550V
575V
600V
1 2
3
4
5
High Voltage (HV) Install Supplied Jumpers/ Supply Lines
(Primary Volts)Links Between Terminals Connect To
6
6
1
7
8
2
5
5
6 5 4
4 3
3 2 1
11V
11.5V
12V
LV
1
7
2
600 575 550
600 575 550
Low Voltage (LV) (Secondary Volts)
6 5 4 3 2 1 22V
23V
24V
None
None
Install Supplied Links Load Lines
Between Terminals Connect To
12 11.5 11
242322
12 11.5 11
24 23 22
© Hammond Power Solutions Inc.
2, 5
1, 6
4-5, 2-3
3-4
4-5, 2-3
3-4
65
2, 5
2, 5
1, 5
1, 5
Install Fuse
Clips To
Unfused
2-7, 5-8
Install Fuse
Clips To
Unfused
Unfused
2-7
2-7
Data subject to change without notice.
SECTION 1
HV
SECTION 1
HPS IMPERATOR®
HPS Imperator - Wiring Schematic Drawings continued
SECTION 1
Group C
HV
220V
230V
240V
1
2
3
4
440V
460V
480V
1
2
3
High Voltage (HV) 4 (Primary Volts)
7
6
8
5
2
1
3
3
4
4
PH***MQMJ Schematic for 50, 75 and 100VA Units
3
2
2 65
1
4
110V
115V
120V
1 2 3
4 5 6
2
220V
230V
240V
HV
1
3
LV
220V
230V
240V
4
1 6
2
5
6 5 4
4
4
3 17
3 2 1
110V
115V
120V
8
3
5
2
6 5 4 3 2 1
LV
1-2, 3-4
2-3
1-2, 3-4
2-3
Low Voltage (LV) (Secondary Volts)
220V
230V
240V
1, 4
1, 4
6, 7
6, 7
Install Supplied Links Load Lines
Between Terminals Connect To
120 115 110
240230220
120 115 110
240230220
3-4, 1-2
2-3
3-4, 1-2
2-3
High Voltage (HV) 4 5 6 (Primary Volts)
1
7
240 230 220
480460440
240 230 220
480 460 440
1, 4
1, 4
4, 6
4, 6
Install Fuse
Clips To
Unfused
Unfused
1-5, 4-8
1-5, 4-8
Install Fuse
Clips To
Unfused
Unfused
1-5
1-5
PH***MQMJ Schematic for 150VA to 1500VA Units
440V
460V
480V
1 2 3
Install Supplied Links Supply Lines
Between Terminals Connect To
Install Supplied Links Supply Lines
Between Terminals Connect To
240 230 220
480460440
240 230 220
480 460 440
2-3, 4-5
3-4
2-3, 4-5
3-4
Low Voltage (LV) (Secondary Volts)
Install Supplied Links Load Lines
Between Terminals Connect To
120 115 110
240230220
120 115 110
240 230 220
© Hammond Power Solutions Inc.
2, 5
2, 5
1, 6
1, 6
4-5, 2-3
3-4
4-5, 2-3
3-4
66
2, 5
2, 5
1, 5
1, 5
Install Fuse
Clips To
Unfused
Unfused
2-7, 5-8
2-7, 5-8
Install Fuse
Clips To
Unfused
Unfused
2-7
2-7
Data subject to change without notice.
SECTION 1
SECTION 9
Machine Tool Industrial Control
HPS Imperator - Wiring Schematic Drawings continued
Group D
1
2
3
4
1
2
3
4
8
5
2
1
3
3
4
3
2
1
4
11V
11.5V
12V
2
1
22V
23V
24V
HV
4 5 6
1
3
LV
220V
230V
240V
1 2 3
4
2 65
1 2 3
2
5
6 5 4
4
3 17
3 2 1
11V
11.5V
12V
8
4
5
2
6 5 4 3 2 1
LV
1-2, 3-4
2-3
1-2, 3-4
2-3
Low Voltage (LV) (Secondary Volts)
22V
23V
24V
1, 4
1, 4
6, 7
6, 7
Install Supplied Links Load Lines
Between Terminals Connect To
12 11.5 11
242322
12 11.5 11
242322
3-4, 1-2
2-3
3-4, 1-2
2-3
1, 4
1, 4
4, 6
4, 6
Install Fuse
Clips To
Unfused
Unfused
1-5, 4-8
1-5, 4-8
Install Fuse
Clips To
Unfused
Unfused
1-5
1-5
PH***QR Schematic for 150VA to 500VA Units
High Voltage (HV) 4 5 6 (Primary Volts)
6
3
Install Supplied Links Supply Lines
Between Terminals Connect To
240 230 220
480460440
240 230 220
480 460 440
440V
460V
480V
1
7
High Voltage (HV) (Primary Volts)
7
6
4
PH***QR Schematic for 50, 75 and 100VA Units
440V
460V
480V
Install Supplied Links Supply Lines
Between Terminals Connect To
240 230 220
480460440
240 230 220
480 460 440
2-3, 4-5
3-4
2-3, 4-5
3-4
Low Voltage (LV) (Secondary Volts)
Install Supplied Links Load Lines
Between Terminals Connect To
12 11.5 11
242322
12 11.5 11
24 23 22
© Hammond Power Solutions Inc.
2, 5
2, 5
1, 6
1, 6
4-5, 2-3
3-4
4-5, 2-3
3-4
67
2, 5
2, 5
1, 5
1, 5
Install Fuse
Clips To
Unfused
Unfused
2-7, 5-8
2-7, 5-8
Install Fuse
Clips To
Unfused
Unfused
2-7
2-7
Data subject to change without notice.
SECTION 1
HV
220V
230V
240V
SECTION 1
HPS IMPERATOR®
HPS Imperator - Wiring Schematic Drawings continued
SECTION 1
Group E
HV
190V
200V
208V
1
2
3
4
380V
400V
416V
1
2
3
High Voltage (HV) 4 (Primary Volts)
7
6
8
5
2
1
3
3
4
4
PH***SP Schematic for 50, 75 and 100VA Units
3
2
2 65
1
4
110V
115V
120V
1 2 3
4 5 6
2
220V
230V
240V
HV
1
3
LV
190V
200V
208V
4
1 6
7
5
6 5 4
4
4
3 17
3 2 1
110V
115V
120V
8
3
5
2
6 5 4 3 2 1
LV
1-2, 3-4
2-3
1-2, 3-4
2-3
Low Voltage (LV) (Secondary Volts)
220V
230V
240V
1, 4
1, 4
6, 7
6, 7
Install Supplied Links Load Lines
Between Terminals Connect To
120 115 110
240230220
120 115 110
240230220
3-4, 1-2
2-3
3-4, 1-2
2-3
High Voltage (HV) 4 5 6 (Primary Volts)
1
2
208 200 190
416400380
208 200 190
416 400 380
1, 4
1, 4
4, 6
4, 6
Install Fuse
Clips To
Unfused
Unfused
1-5, 4-8
1-5, 4-8
Install Fuse
Clips To
Unfused
Unfused
1-5
1-5
PH***SP Schematic for 150VA to 1000VA Units
380V
400V
416V
1 2 3
Install Supplied Links Supply Lines
Between Terminals Connect To
Install Supplied Links Supply Lines
Between Terminals Connect To
208 200 190
416400380
208 200 190
416 400 380
2-3, 4-5
3-4
2-3, 4-5
3-4
Low Voltage (LV) (Secondary Volts)
Install Supplied Links Load Lines
Between Terminals Connect To
120 115 110
240230220
120 115 110
240 230 220
© Hammond Power Solutions Inc.
2, 5
2, 5
1, 6
1, 6
4-5, 2-3
3-4
4-5, 2-3
3-4
68
2, 5
2, 5
1, 5
1, 5
Install Fuse
Clips To
Unfused
Unfused
2-7, 5-8
2-7, 5-8
Install Fuse
Clips To
Unfused
Unfused
2-7
2-7
Data subject to change without notice.
SECTION 1
SECTION 9
Machine Tool Industrial Control
HPS Imperator - Wiring Schematic Drawings continued
Group F
1
2
3
4
1
2
3
4
8
5
2
1
3
3
4
3
2
1
4
110V
115V
120V
1 2 3
2
1
220V
230V
240V
HV
4 5 6
1
3
LV
110V
115V
120V
4
2 65
1 2 3
5
6 5 4
4
4
3 17
3 2 1
110V
115V
120V
8
3
5
2
6 5 4 3 2 1
LV
Install Supplied Links Supply Lines
Between Terminals Connect To
120 115 110
240230220
120 115 110
240 230 220
1-2, 3-4
2-3
1-2, 3-4
2-3
Low Voltage (LV) (Secondary Volts)
220V
230V
240V
1, 4
1, 4
6, 7
6, 7
Install Supplied Links Load Lines
Between Terminals Connect To
120 115 110
240230220
120 115 110
240230220
3-4, 1-2
2-3
3-4, 1-2
2-3
1, 4
1, 4
4, 6
4, 6
Install Fuse
Clips To
Unfused
Unfused
1-5, 4-8
1-5, 4-8
Install Fuse
Clips To
Unfused
Unfused
1-5
1-5
PH***PP Schematic for 150VA to 1500VA Units
High Voltage (HV) 4 5 6 (Primary Volts)
6
7
220V
230V
240V
1
2
High Voltage (HV) (Primary Volts)
7
6
4
PH***PP Schematic for 50, 75 and 100VA Units
220V
230V
240V
Install Supplied Links Supply Lines
Between Terminals Connect To
120 115 110
240230220
120 115 110
240 230 220
2-3, 4-5
3-4
2-3, 4-5
3-4
Low Voltage (LV) (Secondary Volts)
Install Supplied Links Load Lines
Between Terminals Connect To
120 115 110
240230220
120 115 110
240 230 220
© Hammond Power Solutions Inc.
2, 5
2, 5
1, 6
1, 6
4-5, 2-3
3-4
4-5, 2-3
3-4
69
2, 5
2, 5
1, 5
1, 5
Install Fuse
Clips To
Unfused
Unfused
2-7, 5-8
2-7, 5-8
Install Fuse
Clips To
Unfused
Unfused
2-7
2-7
Data subject to change without notice.
SECTION 1
HV
110V
115V
120V
SECTION 1
HPS IMPERATOR®
HPS Imperator - Wiring Schematic Drawings continued
Group G
HV
SECTION 1
110V
115V
120V
1
2
3
4
1
2
High Voltage (HV) 4 (Primary Volts)
3
7
6
8
5
2
1
3
3
4
4
PH***PG Schematic for 50, 75 and 100VA Units
220V
230V
240V
3
2
4
1
2
5
6 5 4
4
4
3 17
3 2 1
5
2
6 5 4
11V
11.5V
12V
LV
1 2 3 4
1
3
4
4 3
3
11V
11.5V
12V
120 115 110
240230220
120 115 110
240 230 220
2-3, 4-5
3-4
2-3, 4-5
3-4
Low Voltage (LV) (Secondary Volts)
1
4 3
LV
2, 5
2, 5
1, 6
1, 6
Install Supplied Links Load Lines
Between Terminals Connect To
12 11.5 11
242322
12 11.5 11
24 23 22
4-5, 2-3
3-4
4-5, 2-3
3-4
220V
230V
240V
2
2 1
1, 4
1, 4
4, 6
4, 6
Install Supplied Links Supply Lines
Between Terminals Connect To
High Voltage (HV) (Primary Volts)
1 2 3 4 5 6 120 115 110
6
240230220
8
120 115 110
4
5
240 230 220
5 6
2
3-4, 1-2
2-3
3-4, 1-2
2-3
Unfused
Unfused
1-5, 4-8
1-5, 4-8
Install Fuse
Clips To
Unfused
Unfused
1-5
1-5
2, 5
2, 5
1, 5
1, 5
Install Fuse
Clips To
Unfused
Unfused
2-7, 5-8
2-7, 5-8
Install Fuse
Clips To
Unfused
Unfused
2-7
2-7
PH***PG Schematic for 750VA and 1000VA Units
HV
7
12 11.5 11
242322
12 11.5 11
242322
3 2 1 22V
23V
24V
110V
115V
120V
1, 4
1, 4
6, 7
6, 7
Install Supplied Links Load Lines
Between Terminals Connect To
High Voltage (HV) (Primary Volts)
8
3
Low Voltage (LV) (Secondary Volts)
5 6 6
7
1-2, 3-4
2-3
1-2, 3-4
2-3
Install Fuse
Clips To
PH***PG Schematic for 150VA to 500VA Units
220V
230V
240V
1 2 3 4
120 115 110
240230220
120 115 110
240 230 220
1 2
22V
23V
24V
HV
5 6
1
3
LV
110V
115V
120V
1 2 3 4
2 65
1
11V
11.5V
12V
4
Install Supplied Links Supply Lines
Between Terminals Connect To
2 1
22V
23V
24V
Install Supplied Links Supply Lines
Between Terminals Connect To
2-3, 4-5
3-4
2-3, 4-5
3-4
Low Voltage (LV) (Secondary Volts)
Install Supplied Links Load Lines
Between Terminals Connect To
12 11.5 11
242322
© Hammond Power Solutions Inc.
2, 5
2, 5
1, 6
1, 6
3-4, 1-2
2-3
1, 4
1, 4
Install Fuse
Clips To
Unfused
Unfused
2-7, 5-8
2-7, 5-8
Install Fuse
Clips To
Unfused
Unfused
Note: secondary fuse clips not available on PH750PG or PH1000PG.
70
Data subject to change without notice.
SECTION 1
SECTION 9
Machine Tool Industrial Control
HPS Imperator - Wiring Schematic Drawings continued
Group H
PH***MBMH Schematic for 50 and 75VA Units
5
1
High Voltage (HV) (Primary Volts)
4
Dotted line represents
supplied jumper lead*
8
600V/575V/550V
480V/460V/440V
240V/230V/220V
3
7
2
100V/95V/90V
3
120V/115V/110V
4
6
LV
5
1
Install Supplied Jumpers Supply Lines
Between Terminals Connect To
600 575 550
None
480 460 440
None
240230220None
600 575 550
3-8
480 460 440
8-7
240 230 220
2-8
1, 3
1, 7
1, 2
6, 4
6, 4
6, 4
Low Voltage (LV) Install Supplied Jumpers/ Load Lines
(Secondary Volts)Links Between Terminals Connect To
120 115 110None
100 95 90None
120 115 110None
100 95 90None
1, 4
1, 3
4, 6
3, 6
Install Fuse
Clips To
Unfused
Unfused
Unfused
1-5, 4-8
1-5, 4-8
1-5, 4-8
Install Fuse
Clips To
Unfused
Unfused
1-5
1-5
*This primary fuse jumper is supplied with the primary fuse kit only.
PH***MBMH Schematic for 100VA to 1500VA Units
HV
1
7
2
High Voltage (HV) (Primary Volts)
5
Dotted line represents
supplied jumper lead*
8
600V/575V/550V
6
480V/460V/440V
240V/230V/220V
4
3
100V/95V/90V
3
120V/115V/110V
4
LV
1
7
2
Install Supplied Jumpers Supply Lines
Between Terminals Connect To
600 575 550
None
480460440None
240230220None
600 575 550
8-6
480 460 440
4-8
240 230 220
3-8
2, 6
2, 4
2, 3
1, 5
1, 5
1, 5
Low Voltage (LV) Install Supplied Jumpers/ Load Lines
(Secondary Volts)Links Between Terminals Connect To
120 115 110None
100 95 90None
120 115 110
None
100 95 90
None
2, 4
2, 3
1, 4
1, 3
Install Fuse
Clips To
Unfused
Unfused
Unfused
2-7, 5-8
2-7, 5-8
2-7, 5-8
Install Fuse
Clips To
Unfused
Unfused
2-7
2-7
*This primary fuse jumper is supplied with the primary fuse kit only.
© Hammond Power Solutions Inc.
71
Data subject to change without notice.
SECTION 1
HV
6
SECTION 1
HPS IMPERATOR®
HPS Imperator - Wiring Schematic Drawings continued
Group I
6
HV
5
1
SECTION 1
PH***MLI Schematic for 50, 75 and 100VA Units
4
Dotted line represents
supplied jumper lead*
8
480V/460V/440V
240V/230V/220V
3
7
208V/200V
2
120V/115V/110V
4
6
LV
5
1
Install Supplied Jumpers Supply Lines
Between Terminals Connect To
480460440None
240 230 220
None
208 200None
480 460 440
3-8
240 230 220
8-7
208 200
2-8
25V/24V/23V
3
High Voltage (HV) (Primary Volts)
Low Voltage (LV) (Secondary Volts)
1, 3
1, 7
1, 2
6, 4
6, 4
6, 4
Install Supplied Jumpers Load Lines
Between Terminals Connect To
120 115 110None
252423None
120 115 110None
252423None
1, 4
1, 3
4, 6
3, 6
Install Fuse
Clips To
Unfused
Unfused
Unfused
1-5, 4-8
1-5, 4-8
1-5, 4-8
Install Fuse
Clips To
Unfused
Unfused
1-5
1-5
*This primary fuse jumper is supplied with the primary fuse kit only.
HV
1
7
2
PH***MLI Schematic for 150VA to 500VA Units
5
Dotted line represents
supplied jumper lead*
8
480V/460V/440V
240V/230V/220V
208V/200V
6
4
3
120V/115V/110V
1
7
Low Voltage (LV) (Secondary Volts)
2
2, 6
2, 4
2, 3
1, 5
1, 5
1, 5
Install Supplied Jumpers Load Lines
Between Terminals Connect To
120 115 110None
252423None
120 115 110
None
25 24 23
None
4
LV
Install Supplied Jumpers Supply Lines
Between Terminals Connect To
480460440None
240230220None
208 200None
480 460 440
8-6
240 230 220
4-8
208 200
3-8
25V/24V/23V
3
High Voltage (HV) (Primary Volts)
2, 4
2, 3
1, 4
1, 3
Install Fuse
Clips To
Unfused
Unfused
Unfused
2-7, 5-8
2-7, 5-8
2-7, 5-8
Install Fuse
Clips To
Unfused
Unfused
2-7
2-7
*This primary fuse jumper is supplied with the primary fuse kit only.
HV
1
7
2
Dotted line represents
supplied jumper lead*
8
480V/460V/440V
240V/230V/220V
208V/200V
6
4
3
25V/24V/23V
2
High Voltage (HV) (Primary Volts)
120V/115V/110V
1
Install Supplied Jumpers Supply Lines
Between Terminals Connect To
480460440None
240230220None
208 200None
480 460 440
8-6
240 230 220
4-8
208 200
3-8
4
LV
PH***MLI Schematic for 750VA and 1000VA Units
5
Low Voltage (LV) (Secondary Volts)
2, 6
2, 4
2, 3
1, 5
1, 5
1, 5
Install Supplied Jumpers Load Lines
Between Terminals Connect To
120 115 110None
252423None
1, 4
1, 2
Install Fuse
Clips To
Unfused
Unfused
Unfused
2-7, 5-8
2-7, 5-8
2-7, 5-8
Install Fuse
Clips To
Unfused
Unfused
Note: secondary fuse clips for 24V tap not available on the PH750MLI or PH1000MLI units.
*This primary fuse jumper is supplied with the primary fuse kit only.
© Hammond Power Solutions Inc.
72
Data subject to change without notice.
SECTION 1
SECTION 9
Machine Tool Industrial Control
HPS Imperator - Wiring Schematic Drawings continued
Group J
PH***MEMX Schematic for 50, 75 and 100VA Units
5
1
Dotted line represents
supplied jumper lead*
8
415V
400V
380V
4
4
3
2
3
7
2
3
2 65
1
4
110V
High Voltage (HV) (Primary Volts)
4
3
2
Low Voltage (LV) (Secondary Volts)
1, 3
1, 7
1, 2
6, 4
6, 4
6, 4
Install Supplied Links Load Lines
Between Terminals
Connect To
1 110
220
110
220
220V
LV
415None
400
None
380None
415
3-8
400
8-7
380
2-8
1
Install Supplied Jumpers Supply Lines
Between Terminals Connect To
3-4, 1-2
2-3
3-4, 1-2
2-3
1, 4
1, 4
4, 6
4, 6
Install Fuse
Clips To
Unfused
Unfused
Unfused
1-5, 4-8
1-5, 4-8
1-5, 4-8
Install Fuse
Clips To
Unfused
Unfused
1-5
1-5
*This primary fuse jumper is supplied with the primary fuse kit only.
PH***MEMX Schematic for 150VA to 1000VA Units
HV
1
7
2
Dotted line represents
supplied jumper lead*
415V
400V
380V
4
5
6 5 4
110V
LV
8
6
4
3
3 17
3 2 1
High Voltage (HV) (Primary Volts)
5
2
6 5 4 3 2 1
220V
Install Supplied Jumpers Supply Lines
Between Terminals Connect To
415None
400None
380None
415
8-6
400
4-8
380
3-8
Low Voltage (LV) (Secondary Volts)
2, 6
2, 4
2, 3
1, 5
1, 5
1, 5
Install Supplied Links Load Lines
Between Terminals Connect To
110
220
110
220
4-5, 2-3
3-4
4-5, 2-3
3-4
2, 5
2, 5
1, 5
1, 5
Install Fuse
Clips To
Unfused
Unfused
Unfused
2-7, 5-8
2-7, 5-8
2-7, 5-8
Install Fuse
Clips To
Unfused
Unfused
2-7
2-7
*This primary fuse jumper is supplied with the primary fuse kit only.
© Hammond Power Solutions Inc.
73
Data subject to change without notice.
SECTION 1
HV
6
SECTION 1
SECTION
1
HPS IMPERATOR
HPS
IMPERATOR®®
HPS Imperator - Wiring Schematic Drawings continued
SECTION 1
Group K
PH***MGJ Schematic for 50, 75 and 100VA Units
HV
6
5
1
4 Dotted line represents
supplied jumper lead*
8
380V
277V
208V
4
2
3
4
3
2
2 65
1
120V
3
7
4
3
2
Low Voltage (LV) (Secondary Volts)
1, 3
1, 7
1, 2
6, 4
6, 4
6, 4
Install Supplied Links Load Lines
Between Terminals Connect To
1 120
240
120
240
240V
LV
Install Supplied Jumpers Supply Lines
Between Terminals Connect To
380None
277
None
208None
380
3-8
277
8-7
208
2-8
1
High Voltage (HV) (Primary Volts)
3-4, 1-2
2-3
3-4, 1-2
2-3
1, 4
1, 4
4, 6
4, 6
Install Fuse
Clips To
Unfused
Unfused
Unfused
1-5, 4-8
1-5, 4-8
1-5, 4-8
Install Fuse
Clips To
Unfused
Unfused
1-5
1-5
*This primary fuse jumper is supplied with the primary fuse kit only.
PH***MGJ Schematic for 150VA to 1000VA Units
HV
1
Dotted line represents
supplied jumper lead*
7
2
380V
277V
208V
6 5 4
3
3 17
3 2 1
120V
2
6 5 4 3 2 1
240V
LV
8
6
4
4
5
High Voltage (HV) (Primary Volts)
5
Install Supplied Jumpers Supply Lines
Between Terminals Connect To
380None
277
None
208None
380
8-6
277
4-8
208
3-8
Low Voltage (LV) (Secondary Volts)
2, 6
2, 4
2, 3
1, 5
1, 5
1, 5
Install Supplied Links Load Lines
Between Terminals Connect To
120
240
120
240
4-5, 2-3
3-4
4-5, 2-3
3-4
2, 5
2, 5
1, 5
1, 5
Install Fuse
Clips To
Unfused
Unfused
Unfused
2-7, 5-8
2-7, 5-8
2-7, 5-8
Install Fuse
Clips To
Unfused
Unfused
2-7
2-7
*This primary fuse jumper is supplied with the primary fuse kit only.
© Hammond Power Solutions Inc.
74
Data subject to change without notice.
SECTION 1
SECTION 9
Machine Tool Industrial Control
HPS Spartan and HPS Fusion - Wiring Schematic Drawings
Group A
SP***ACP Schematic Connections for 600/480 to 120 X 240
HV
H1
480V 460V 440V
X4
X4
H3
600V 575V 550V
X2
X3
X2 X3 X1
H2
X1
X4 X2 X3 X1
120V
115V
110V
240V
230V
220V
LV
Group B
High Voltage (HV)
(Primary Volts)
Install Supplied Jumpers
Between Terminals
Supply Lines
Connect To
600
575
550
None
H1, H3
480
460
440
None
H1, H2
Install Supplied Links
Between Terminals
Load Lines
Connect To
Low Voltage (LV)
(Secondary Volts)
120
115
110
X1-X3, X2-X4
X1, X4
240
230
220
X2-X3
X1, X4
SP***AR Schematic Connections for 600/480 to 12 X 24
FS***AR Schematic Connections for 600/480 to 12 X 24
HV
H1
X4
600V
575V
550V
H2
X2 X3
X1
Install Supplied Jumpers
Between Terminals
Supply Lines
Connect To
575
None
H1, H2
Install Supplied Links
Between Terminals
Load Lines
Connect To
600
X4 X2 X3 X1
X4 X2 X3 X1
12V
11.5V
11V
24V
23V
22V
LV
High Voltage (HV)
(Primary Volts)
550
Low Voltage (LV)
(Secondary Volts)
12
11.5
11
X1-X3, X2-X4
X1, X4
24
23
22
X2-X3
X1, X4
© Hammond Power Solutions Inc.
75
Data subject to change without notice.
SECTION 1
FS***ACP Schematic Connections for 600/480 to 120 X 240
SECTION 1
HPS SPARTAN® & HPS FUSION™
HPS Fusion and HPS Spartan - Wiring Schematic Drawings continued
SECTION 1
Group C
SP***MQMJ Schematic Connections for 240 X 480 to 120 X 240
FS***MQMJ Schematic Connections for 240 X 480 to 120 X 240
240V
230V
220V
480V
460V
440V
HV
H1 H3 H2 H4
H1 H3 H2 H4
H1
H3
H2
H4
X4
X2
X3
X1
X4 X2 X3 X1
X4 X2 X3 X1
120V
115V
110V
240V
230V
220V
LV
Group D
High Voltage (HV)
(Primary Volts)
Install Supplied Jumpers
Between Terminals
Supply Lines
Connect To
240
230
220
H1-H3, H2-H4
H1, H4
480
460
440
H2-H3
H1, H4
Install Supplied Links
Between Terminals
Load Lines
Connect To
Low Voltage (LV)
(Secondary Volts)
120
115
110
X1-X3, X2-X4
X1, X4
240
230
220
X2-X3
X1, X4
SP***QR Schematic Connections for 240 X 480 to 12 X 24
FS***QR Schematic Connections for 240 X 480 to 12 X 24
HV
240V
230V
220V
H1 H3 H2 H4
480V
460V
440V
H1 H3 H2 H4
High Voltage (HV)
(Primary Volts)
230
220
H1-H3, H2-H4
H1, H4
460
440
H2-H3
H1, H4
Install Supplied Links
Between Terminals
Load Lines
Connect To
H3
H2
H4
480
X4
X2
X3
X1
Low Voltage (LV)
(Secondary Volts)
X4 X2 X3 X1
12V
11.5V
11V
24V
23V
22V
LV
Supply Lines
Connect To
240
H1
X4 X2 X3 X1
Install Supplied Jumpers
Between Terminals
12
11.5
11
X1-X3, X2-X4
X1, X4
24
23
22
X2-X3
X1, X4
© Hammond Power Solutions Inc.
76
Data subject to change without notice.
Industrial open-style control
General Purpose Enclosed
SECTION 1
SECTION 9
HPS Fusion and HPS Spartan - Wiring Schematic Drawings continued
Group E
SP***KHP Schematic Connections for 380/347 to 120 X 240
HV
H1
H3
380V
347V
X4
X4
High Voltage (HV)
(Primary Volts)
Install Supplied Jumpers
Between Terminals
Supply Lines
Connect To
380
None
H1, H3
347
None
H1, H2
Low Voltage (LV)
(Secondary Volts)
Install Supplied Links
Between Terminals
Load Lines
Connect To
120
X1-X3, X2-X4
X1, X4
240
X2-X3
X1, X4
H2
X2
X3
X2 X3 X1
X1
X4 X2 X3 X1
120V
240V
LV
Group F
SP***KHR Schematic Connections for 380/347 to 12 X 24
FS***KHR Schematic Connections for 380/347 to 12 X 24
HV
H1
H3
380V
347V
X4
X4
Install Supplied Jumpers
Between Terminals
Supply Lines
Connect To
380
None
H1, H3
347
None
H1, H2
Low Voltage (LV)
(Secondary Volts)
Install Supplied Links
Between Terminals
Load Lines
Connect To
12
X1-X3, X2-X4
X1, X4
24
X2-X3
X1, X4
H2
X2
X3
X2 X3 X1
12V
High Voltage (HV)
(Primary Volts)
X1
X4 X2 X3 X1
LV
24V
© Hammond Power Solutions Inc.
77
Data subject to change without notice.
SECTION 1
FS***KHP Schematic Connections for 380/347 to 120 X 240
SECTION 1
HPS SPARTAN® & HPS FUSION™
HPS Spartan and HPS Fusion - Wiring Schematic Drawings continued
SECTION 1
Group G
SP***NJ Schematic Connections for 277 to 120
FS***NJ Schematic Connections for 277 to 120
HV
H1
H2
277V
120V
X2
X1
High Voltage (HV)
(Primary Volts)
Install Supplied Jumpers
Between Terminals
Supply Lines
Connect To
277
None
H1, H2
Low Voltage (LV)
(Secondary Volts)
Install Supplied Links
Between Terminals
Load Lines
Connect To
120
None
X1, X2
LV
Group H
SP***PR Schematic Connections for 120 X 240 to 12 X 24
FS***PR Schematic Connections for 120 X 240 to 12 X 24
HV
120V
115V
110V
H1 H3 H2 H4
H1
X4
240V
230V
220V
H1 H3 H2 H4
H3
H2
X2
X3
H4
X1
X4 X2 X3 X1
X4 X2 X3 X1
12V
11.5V
11V
24V
23V
22V
LV
High Voltage (HV)
(Primary Volts)
Install Supplied Jumpers
Between Terminals
Supply Lines
Connect To
120
115
110
H1-H3, H2-H4
H1, H4
240
230
220
H2-H3
H1, H4
Install Supplied Links
Between Terminals
Load Lines
Connect To
Low Voltage (LV)
(Secondary Volts)
12
11.5
11
X1-X3, X2-X4
X1, X4
24
23
22
X2-X3
X1, X4
© Hammond Power Solutions Inc.
78
Data subject to change without notice.
Industrial open-style control
General Purpose Enclosed
SECTION 1
SECTION 9
HPS Spartan and HPS Fusion - Wiring Schematic Drawings continued
Group I
SP***SP Schematic Connections for 208 X 416 to 120 X 240
HV
208V
200V
190V
H1 H3 H2 H4
H1
X4
416V
400V
380V
H1 H3 H2 H4
H3
H4
H2
X2
X3
X4 X2 X3 X1
120V
115V
110V
240V
230V
220V
Group J
H1 H3 H2 H4
H1
X4
Supply Lines
Connect To
208
200
190
H1-H3, H2-H4
H1, H4
416
400
380
H2-H3
H1, H4
Install Supplied Links
Between Terminals
Load Lines
Connect To
Low Voltage (LV)
(Secondary Volts)
120
115
110
X1-X3, X2-X4
X1, X4
240
230
220
X2-X3
X1, X4
SP***SR Schematic Connections for 208 X 416 to 12 X 24
FS***SR Schematic Connections for 208 X 416 to 12 X 24
HV
208V
200V
190V
Install Supplied Jumpers
Between Terminals
X1
X4 X2 X3 X1
LV
High Voltage (HV)
(Primary Volts)
416V
400V
380V
H1 H3 H2 H4
H3
H2
X2
X3
H4
X1
X4 X2 X3 X1
X4 X2 X3 X1
12V
11.5V
11V
24V
23V
22V
LV
High Voltage (HV)
(Primary Volts)
Install Supplied Jumpers
Between Terminals
Supply Lines
Connect To
208
200
190
H1-H3, H2-H4
H1, H4
416
400
380
H2-H3
H1, H4
Install Supplied Links
Between Terminals
Load Lines
Connect To
Low Voltage (LV)
(Secondary Volts)
12
11.5
11
X1-X3, X2-X4
X1, X4
24
23
22
X2-X3
X1, X4
© Hammond Power Solutions Inc.
79
Data subject to change without notice.
SECTION 1
FS***SP Schematic Connections for 208 X 416 to 120 X 240
HPS SPARTAN® & HPS FUSION™
SECTION 1
SECTION 1
© Hammond Power Solutions Inc.
80
Data subject to change without notice.