COUNTIS E5x Active energy meters three-phase - via CT up to 6000 A

COUNTIS E5x Active energy meters three-phase - via CT up to 6000 A
COUNTIS E5x
Single-circuit metering,
measurement &
analysis
Active energy meters
three-phase - via CT up to 6000 A
The solution for
count_196_b_1_cat
> Industry
> Infrastructure
> Data centres
COUNTIS E53 up to 6000 A via CT
Strong points
Function
> RS485 MODBUS
communication or pulse
output
> Large backlit LCD display
> Detection of connection errors
> Direct display of multimeasurement and metering
values
Principle diagram
CO
UN
TIS
E 50
count_197_b_1_x_cat
The COUNTIS E5x is a panel mounted active
and reactive electrical energy meter displaying
energy and multi-measurement values directly
on its large backlit LCD display. It is designed
for utilisation on three-phase or single-phase
networks with connection via CT and is
suitable for applications of up to 6000 A. The
CT ratio can be configured by the user via
the keypad and the display, or via RS485
MODBUS communication (E53).
Common characteristics
• Measurement accuracy: 0.5%.
• Large backlit LCD display.
• Direct access to multi-measurement
and metering values.
• Detects connection errors.
COUNTIS E50
CO
UN
TIS
E
50
Conformity to standards
> IEC 62053-23
class 2
> IEC 62053-22
class 0.5S
> IEC 61557-12
CO
UN
TIS
Advantages
COUNTIS E50
RS485 MODBUS communication
or pulse output
To enable the remote reporting of energy
consumption, COUNTIS E5x are provided
with either a pulse output (E50) or an RS485
MODBUS communication output (E53).
Remote configuration of the Countis E53 is
possible via RS485 MODBUS communication.
Detection of connection errors
The COUNTIS E5x is protected against
phase/neutral inversion and has an integrated
test function which can be utilised to detect
wiring errors. This function enables CT
installation errors to be corrected without
having to remake connections. This simplifies
the installation and commissioning, thereby
reducing associated costs, and ensures that
the device operates correctly.
Large backlit LCD display
Thanks to its large backlit LCD display and its
multiple viewing screens with direct pushbutton
access, COUNTIS E5x provide clear readings
and are easy to use.
48
E 50
models
Key characteristics
E50
Pulse output
E53
RS485 MODBUS communication
Catalogue 2015 - 2016
Management software
COUNTIS E50
They directly display a number of total/partial
metering and multi-measurement values :
+/- kWh, +/- kvarh, kVAh, I, U, V, S, PF, etc.
Direct display of multi-measurement and
metering values
Multi-measurement
• Currents: instantaneous: I1, I2, I3
• Voltages: instantaneous: V1, V2, V3, U12,
U23, U31
• Power:
- instantaneous: 3P, 3Q, 3S
- maximum average: 3P
• Power factor:
- instantaneous: 3PF
Metering
• Active energy: +/- kWh
• Reactive energy: +/- kvarh
• Apparent energy: kVAh
> To get the most effective
use from your Socomec
measurement and metering
devices, we offer a range of
dedicated software tools.
See page 142.
COUNTIS E5x
Active energy meters
three-phase - via CT up to 6000 A
Front panel
References
COUNTIS E50
Reference
Type
Pulse output
RS485 MODBUS communication (1)
Management software for COUNTIS
COUNTIS E53
Reference
1. Backlit LCD display
2. Energy display and test function key
3. Power and power factor display key
4. Current and voltage display key
5. Programming mode access key
4850 3010
4850 3011
See page 142
(1) 4 tariffs through RS485 communication.
three-phase on CT/5A up to 6000 A
< 0.6 VA
40 mA
50 mA(1)
250 mA(2)
5 A(3)
6A
50 A for 1 s
1
2
3
4
5
Case
0.8
92 +- 0.0
86 … 520 VAC
< 0.1 VA
800 VAC
count_194_c_1_x_cat
Current measurement
Type
Input consumption
Startup current (Ist)
Minimum current (Imin)
Transition current (Itr)
Reference current (Iref)
Permanent overload (Imax)
Intermittent overload
Voltage measurement
Range of measurement
Input consumption
Permanent overload
Energy accuracy
Reactive (according to IEC 62053-23)
Active (according to IEC 62053-22)
Power supply
Self-supplied
Auxiliary power supply Us
Frequency
Output (pulsed)
Number
Type
Max. number of operations
Operating conditions
Operating temperature
Storage temperature
Relative humidity
Communication
Link
Type
Protocol
MODBUS® speed
count_196x_b_2_cat
Electrical characteristics
Class 2
Class 0.5S
no
110 … 400 VAC / 125… 350 VDC +/-10 %
45 … 65 Hz
CO
U
96
NT
IS
0.8
92 +- 0.0
E5
3
60
20
96
1
100 VDC - 0.5 A - 10 VA
≤ 108
Type
Dimensions W x H x D
Case degree of protection
Front degree of protection
Display type
Voltage and current connection cross-section
Current connection cross-section
Weight
-10 … 55 °C
-20 … 85 °C
95 %
RS485
2 … 3 half duplex wires
MODBUS RTU
1400 … 38400 bauds
Panel mounting
96 x 96 x 80 mm
IP30
IP52
backlit LCD display
0.5 … 2.5 mm²
1.5 … 6 mm²
370 g
(1) I(min) ≤ 0.5 * Itr
(2) The accuracy class is guaranteed between Itr and Imax.
(3) I(ref) = I(b) (base current) = 10 * I(tr) for direct connection COUNTIS.
Connection
- When disconnecting the COUNTIS, the secondary of each current transformer
must be short-circuited. This operation can be carried out automatically by a
SOCOMEC PTI, an accessory which is included in this catalogue.
Please consult us.
Recommendation:
- For IT earthing systems, it is recommended that the CT secondary is not
connected to earth.
Low voltage balanced network
Low voltage unbalanced network
3/4 wires with 3 CTs
1
1
S2
1
S1 S2 S1 S2 S1 S2
V1 V2 V3 VN
I1
I2
I3
P1
S1
1
1
3 wires with 2 CTs
S2
P1
S1
diris_395_d_1_x_cat
diris_392_d_1_x_cat
P1
S1
N
L1
L2
L3
S2
N
L1
L2
L3
1
1
V1 V2 V3 VN
S1 S2 S1 S2 S1 S2
I1
I2
Use of 1 CT reduces by 0.5% the accuracy of the phases,
the current of which is worked out by vector calculation.
I3
diris_397_d_1_x_cat
3/4 wires with 1 CT
1
P1
S1
P1
S1
L1
L2
L3
S2
1
V1 V2 V3 VN
S1 S2 S1 S2 S1 S2
I1
I2
I3
Use of 2 CT reduces by 0.5% the accuracy of the phases,
the current of which is worked out by vector calculation.
Additional information
Communication via RS485 link
AC & DC auxiliary power supply
LIYCY-CY
0V -
+
ON
RS485
diris_400_h_1_x_cat
diris_398_c_1_x_cat
110 / 400 VAC (IEC)
120 / 350 VDC (IEC)
1
1
A U X
1. Fuses 0.5 A gG / 0.5 A class CC.
Catalogue 2015 - 2016
49