Astria_Residential_Wood_Burning_Fireplace

Astria_Residential_Wood_Burning_Fireplace
Installation and Operation Instructions
AstriaTM Residential Wood Burning Fireplace
P/N 126634-01 Rev. A 01/2014
PFS
C
Models
®
US
Plantation48M3
(Red Brick, Catalog
No. F0691)
Plantation48M3
(Ivory Brick, Catalog
No. F0692)
P126634-01
SAVE THIS BOOK
This book is valuable. In addition to instructing you on how to install and manintain your appliance, it also contains
information that will enable you to obtain replacement parts or accessory items when needed. Keep it with your other
important papers.
INSTALLER: Leave this manual with the appliance. Installateur : Laissez cette notice avec l’appareil.
CONSUMER: Retain this manual for future reference. Consommateur : Conservez cette notice pour consultation ultérieure.
This fireplace is approved for use as a wood furning fireplace or for use with a vented gas log approved to
ANSI Z21.60 or Z21.84 standards or for use with a vent-free gas log heater approved to ANSI Z21.11.2 standard.
FOR CANADA: The authority having jurisdiction POUR LE CANADA: L’autorité compétente (comme le
(such as the municipal building department, fire service municipal du bâtiment, les pompiers, etc.) doit
department, etc.) should be contacted before
être contacté avant l’installation afin de déterminer la
installation to determine the need to obtain a
nécessité d’obtenir un permis.
permit.
This appliance may be installed in an aftermarket permanently located, manufactured home (USA only)
or mobile home, where not prohibited by local codes. This appliance is only for use with the type of gas indicated
on the rating plate. This appliance is not convertible for use with other gases, unless a certified kit is used.
WARNING: If the information in these
AVERTISSEMENT : Assurez-vous de bien suivre les
instructions is not followed exactly, a fire or
instructions données dans cette notice pour réduire au
explosion may result causing property damage, minimum le risque d’incindie ou d’explosion ou pour éviter
personal injury or death.
tout dommage matériel, toute blessure ou la mort.
—— Do not store or use gasoline or other
—— Ne pas entreposer ni utilizer d’essence ni d’autres
flammable vapors and liquids in the vicinity
vapeurs ou liquides inflammables dans le voisinage
of this or any other appliance.
de cet appareil ou de tout autre appareil.
—— WHAT TO DO IF YOU SMELL GAS:
—— QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ :
• Do not try to light any appliance.
• Ne pas tenter d’allumer d’appareil.
• Do not touch any electrical switch; do not
• Ne touchez à aucan interrupteur. Ne pas vous
use any phone in your building.
servir des téléphones se trouvant dans le bâtiment
où vous trouvez.
• Immediately call your gas supplier from
a neighbor’s phone. Follow the gas
• Appelez immédiatement votre fournisseur de
supplier’s instructions.
gaz depuis un voisin. Suivez les instructions du
fournisseur.
• If you cannot reach your gas supplier, call
the fire department.
• Si vous ne pouvez rejoindre le fournisseur de gaz,
appelez le service des incindies.
—— Installation and service must be performed
by a qualified installer, service agency or the —— L’installation et l’entretien doivent être assurés par un
gas supplier.
installateur ou un service d’entretien qualifié ou par
le fournisseur de gaz.
WARNING: Improper installation, adjustment, alteration, service or maintenance can cause injury, property
damage or loss of life. Refer to this manual for assistance or additional information. Consult a qualified
installer or local distributor.
TABLE OF CONTENTS
Safety................................................................... 2
Specifications....................................................... 3
Installation............................................................ 4
Firebrick Wall Installation.....................................11
Optional Gas Line............................................... 14
Glass Door Installation....................................... 18
Operation and Maintenance............................... 16
Technical Service............................................... 17
Replacement Parts............................................. 17
Parts................................................................... 18
Accessories........................................................ 19
SAFETY
IMPORTANT: Check local codes
before installing this fireplace.
Before beginning the installation of the
fireplace, read these instructions through
completely.
• This INNOVATIVE HEARTH PRODUCTS
fireplace and its components are safe
when installed according to this installation
manual. Unless you use IHP components,
which have been designed and tested for
the fireplace system, you may cause a fire
hazard.
• The INNOVATIVE HEARTH PRODUCTS
warranty will be voided by and IHP disclaims any responsibility for the following
actions.
a. Modification of the fireplace, components, doors, air inlet system and
damper control.
b. Use of any component part not manufactured or approved by INNOVATIVE
HEARTH PRODUCTS in combination
with a IHP fireplace system.
Proper installation is the most important step
in ensuring safe and continuous operation
of the fireplace. Consult the local building
codes as to the particular requirements
concerned with the installation of all factory
built fireplaces.
WARNING: Do not install a
fireplace insert in this box unless
the manufacturer's instructions
with the insert specifically state
this fireplace has been tested for
use with this insert.
This fireplace is not intended to
be used as a substitute for a furnace to heat an entire home. Use
for supplemental heat only.
FOR YOUR SAFETY
• Do not store or use gasoline
or any other flammable vapors
or liquids in the vicinity of this
or any other appliance.
• Due to high temperatures, the
appliance should be located
out of traffic and away from
furniture and draperies.
• Do not place clothing or other
flammable materials on or near
the appliance.
• Never leave children unattended when a fire is burning
in the fireplace.
WARNING: Use solid wood
or processed solid fuel fire logs
only. When processed wood
fuel fire logs are used, do not
poke or stir the logs while they
are burning. Use only fire logs
that have been evaluated for
the application in fireplace and
refer to fire log warnings and
caution markings on packaging
prior to use.
SAFETY
Continued
WARNING: Always leave glass
doors fully opened or fully closed
when operating fireplace.
WARNING: If fireplace is
to be installed on combustible
material, a Hearth Spacer must
be used. See Replacement and
Accessory Parts on page 18.
SPECIFICATIONS
MODELS PLANTATION48M3 (RED AND IVORY BRICK MODELS)
SQUARE
CHASE-TOP
TERMINATION
ROUND TOP
TERMINATION
No Combustible
Material on Front
Face Except for
Mantel Applications
2" Chimney Airspace
Clearance to Combustible
Material
1.5" Airspace
Back and Sides
PLANTATION FIREPLACE
WITH HEARTH SPACER
(REQUIRED FOR
COMBUSTIBLE FLOORS)
Outside Air
Access Location
Gas Line
Access Location
18" Min. to
Perpendicular
Wall
Hearth
Extension
72" X 20"
Hearth Spacer
(Required for
Combustible Floor)
0" to Bottom
12" Min.
Each Side
42.375"
33.5"
15.625"
30"
24"
14.375"
30.31"
48"
60.625"
0.625"
22"
71.5"
65.75" 76.25"*
42"
43.75"
7.625"
7.625"
8.875"
17.5"
14.375"
48"
60.625"
*With Hearth Spacer
4.75"
1"
12.875"
Secure Fireplace
To Hearth Spacer
Using Straps
Provided
INSTALLATION
SELECTING FIREPLACE LOCATION
To determine the safest and most efficient
location for the fireplace, you must take into
consideration the following guidelines:
1. The location must allow for proper clearances (see Figures 1 and 2).
2. Consider a location where the fireplace
will not be affected by drafts, air conditioning ducts, windows or doors.
3. A location that avoids the cutting of
joists or roof rafters will make installation
easier.
4. An outside air kit is available with this
fireplace (see Optional Outside Air Kit on
page 5).
3.
4.
5.
MINIMUM CLEARANCE TO
COMBUSTIBLES
Back and sides of fireplace
Front of fireplace
Floor**
Perpendicular wall to opening
Top spacers
Mantel clearance
Chimney outer pipe surface
1 1/2" min.*
48" min.
0" min.
18" min.
0" min.
see Mantels,
page 5
2" min.
6.
on a hearth spacer designed for use with
this fireplace (see Replacement and Accessory Parts, page 18).
Set the fireplace directly in front of this
opening and slide the unit back until the
nailing flanges touch the side framing.
Check the level of the fireplace and shim
with sheet metal if necessary.
Before securing fireplace to prepared framing, the ember protector (provided) must be
placed between the hearth extension (not
supplied) and under the bottom front edge
of the fireplace to protect against glowing
embers falling through. If the fireplace is
to be installed on a raised platform, a Ztype ember protector (not supplied) must
be fabricated to fit your required platform
height. The ember protector should extend
under the fireplace a minimum of 1 1/2". The
ember protector should be made of galvanized sheet metal (28 gauge minimum to
prevent corrosion.
Using screws or nails, secure the fireplace
to the framing through flanges located on
the sides of the fireplace.
* Not required at nailing flanges
** See step 2 of Framing
71.5"
65.7"
76.375"*
WARNING: Do not pack required air spaces with insulation
or other materials.
60.875"
* With Hearth Spacer
31.625"
Secure Fireplace
To Hearth Spacer
Using Straps Provided
(Sides and Rear)
Figure 1 - Framing Dimensions
Maintain 1 1/2"
Clearance at Sides and
Back of Fireplace
.8
75
"
1 1/2" Clearance
Not Required at
Nailing Flanges
78
Minimum/Maximum Chimney Height
The minimum height of the chimney, measured from the base of the fireplace to the
flue gas outlet of the termination, is 16 feet for
straight flue or a flue with one elbow set. The
maximum distance between elbows is 6 feet.
For systems with two elbow sets, the minimum
height is 22 feet. The maximum height of any
system is 50 feet. This measurement includes
the fireplace, chimney sections and the height
of the termination assembly at the level of the
flue gas outlet (see Figure 15, page 9).
FRAMING
1. Frame the opening for the fireplace using
the dimensions shown in Figures 1 and 2.
2. If the fireplace is to be installed directly
on carpeting, tile (other than ceramic) or
any combustible material including wood
flooring, the fireplace must be installed
4
107.3"
Figure 2 - Corner Installation
www.Astria.US.com
126634-01A
INSTALLATION
Continued
HEARTH EXTENSION
A hearth extension projecting a minimum of
20" in front of and a minimum of 12" beyond
each side of the fireplace opening is required
to protect combustible floor construction
in front of the fireplace. Fabricate a hearth
extension using a material which meets the
following specifications: a layer of noncombustible, inorganic material having a thermal
conductivity of K=0.84 BTU IN/FT, HR. F (or
less) at 1" thick. For example, if the material
selected has a K factor of 0.25, such as glass
fiber, the following formula would apply:
0.25 x 1.0" = 0.30" thickness required
0.84
Thermal conductivity "K" of materials can be
obtained from the manufacturer or supplier of
the noncombustible material. If the hearth extension is to be covered, use noncombustible
material such as tile, slate, brick, concrete,
metal, glass, marble, stone, etc. Provide a
means to prevent the hearth extension from
shifting and seal gap between the fireplace
frame and hearth extension with a noncombustible material (see Figure 3).
WARNING: Hearth extension
is to be installed only as shown
in Figure 3.
Fireplace Front
Hearth
Extension
Seal Gap
Ember Protector
Figure 3 - Hearth Extension
126634-01A
12 1/4" Ref.
6"
Ref.
33°
3" Nom.
15" Min.
Combustible
Material
Safe
Zone for
Projection of
Combustible
Materials
11/2" Max.
12" Min.
Upper
Section of
Fireplace
Fireplace Opening
Figure 4 - Mantel Clearances to
Combustible Material
Fireplace Front
Raised Hearth
Fireplace Front
Elevated
A mantel may be installed if desired (see
Figure 4). Woodwork such as wood trims,
mantels or any other combustible material
projecting from the front face must not be
placed within 12" of the fireplace opening.
Combustible materials above 12" and projecting more than 1 1/2" from the fireplace
must not be placed less than 15" from the
top opening of the fireplace (NFPA STD 211,
Sec. 7-3.3.3).
Mantels or any other combustible material
also may come up to the side edge of the
black metal face of the fireplace just as long
as the projection from the front face fall within
the limit shown in Figure 4.
Seal Gap
Ember Protector
Ember Protector
MANTELS
OPTIONAL OUTSIDE AIR KIT
(MODEL AK4/AK4F)
Installation of an outside air kit should be performed during rough framing of fireplace due
to nature of it's location. Outside combustion
air is accessed through a vented crawl space
(AK4F) or through a sidewall (AK4). This fireplace is equipped with a barometric damper
which allow outside air to flow into fireplace
automatically when needed.
www.Astria.US.com
5
INSTALLATION
Continued
CAUTION: Combustion air
inlet ducts shall not terminate
in attic space.
The maximum height for the
air vent can not exceed 3 feet
below the flue gas outlet of the
termination.
Secure to Collars with Metal Tape, Screws
or Straps (Min. of 1/4" x 20" in size)
Air Inlet
Location
Must Allow
For Bushes
or Snow
PART NO.
48" Plantation
12-12DM
12-12HT
18-12DM
18-12HT
24-12DM
24-12HT
36-12DM
36-12HT
48-12DM
48-12HT
RLT-12D
RLT-12HT
STL-12D
LINEAL GAIN
DESCRIPTION
GAIN (IN)
Fireplace
66 1/2"
Pipe Section
10 5/8"
Pipe Section
16 5/8"
Pipe Section
23 5/8"
Pipe Section
34 5/8"
Pipe Section
46 5/8"
Round
7 3/4"*
Termination
Square ChaseTop with Slip 7" to 15"*
Section
* The lineal gain for the terminations is measured to the flue gas outlet height.
15" Galvanized
Outer Pipe
Vented Crawl Space
(Check Local Codes
Before Installing in a
Vented Crawl Space)
Air Inlet
Eyebrow
Vent Hood
Required for
Wall Installation
Figure 5 - Outside Air Kit
CHIMNEY PIPE
INNOVATIVE HEARTH PRODUCTS chimney
system consists of 12", 18", 24", 36"' and 48"
snap-lock, double-wall pipe segments, planned
for maximum adaptability to individual site
requirements. Actual lengths gained after fitting overlaps must be taken into consideration
(lineal gain) and are given in lineal gain chart
(see Figure 6). Lineal gain is the actual measurable length of a part after two or more parts
are connected. For Canada, use chimney parts
designated "HT".
WARNING: The opening in the
collar around the chimney at the
top of the fireplace must not be
obstructed. Never use blown insulation to fill the chimney enclosure.
6
Hemmed
End
12 3/8"
Stainless
Inner Pipe
Figure 6 - Lineal Gain
ASSEMBLY AND INSTALLATION OF
DOUBLE WALL CHIMNEY SYSTEM
Each double wall chimney section consists of
a galvanized outer pipe, a stainless steel inner flue pipe and a wire spacer. Pipe sections
must be assembled independently as chimney
is installed. When connecting chimney directly
to fireplace, inner flue pipe section must be
installed first with lanced side up. Outer pipe
section can then be installed over flue pipe
section with hemmed end up. Press down
on each pipe section until lances securely
engage hem on fireplace starter. Wire will
assure proper spacing between inner and
outer pipe sections.
Continue to assemble chimney sections as
outlined above, making sure both inner and
outer pipe sections are locked together. When
installing double wall snap-lock chimney together, it is important to assure joint between
chimney sections is locked. Check by pulling
chimney upward after locking. Chimney will
not come apart if properly locked. It is not
necessary to add screws to keep chimney
together (exception, see Figure 9, page 8).
www.Astria.US.com
126634-01A
INSTALLATION
Continued
USING ELBOW OFFSETS (30E-12DM) 2. Chimney weight above offset rests on re1. To achieve desired offset, you may install
combinations of 12", 18", 24", 36" and 48"
length of double wall pipe (see offset chart
and Figure 7).
OFFSET
A
4 3/8"
9 3/4"
12 3/4"
15"
18"
21 1/4"
23 3/4"
27 3/4"
30"
33"
36"
38 1/4"
41 1/4"
45"
46 3/4"
51"
53 1/4"
56 1/4"
59 1/4"
61 3/4"
64 3/4"
68 1/4"
70"
74 1/4"
76 3/4"
79 3/4"
RISE
B
16 3/8"
25 1/2"
30 3/4"
34 3/4"
40"
46 1/4"
49 1/4"
56 3/4"
60 3/4"
66"
71"
75"
80 1/4"
86 3/4"
89 1/2"
97"
101"
106 1/4"
111 1/2"
115 1/2"
120 3/4"
127"
130"
137 1/2"
141 1/2"
146 3/4"
12"
1
CHIMNEY LENGTH
18" 24" 36" 48"
ELBOW SET ONLY
1
1
1
1
1
1
1
1
1
1
1
1
1
2
1
2
1
2
1
1
1
1
1
1
1
2
1
2
2
4
1
turn elbow. Straps must be securely nailed
to rafters or joists (see Figure 8, details A
and B).
3. Maximum length of pipe between supports
(return elbow or 12S-12DM) is 6' of angle
run. Maximum of two 6' angle run sections
per chimney system (see Figure 7).
4. All pipe connections between the offset
and return must be secured with two
screws on the outer pipe only (see Figure
9, page 8). Do not penetrate the inner
stainless.
See Detail A
1
2" Min.
1
1
Straps
Straps
Detail B
Angle Firestop
1
1
2
1
2
2
1
2
1
1
Straps
See Detail B
Straps
Detail A
Return Elbow
Figure 8 - Ceiling Support Pipe
12S-12DM
OFFSET CHART (22-50 FT. SYSTEM HEIGHT)
Return
Elbow
Offset
Elbow
Return
Elbow
Offset
Elbow
6' Max.
Return
Elbow
6' Max. Ceiling
Support Pipe
12S-12DM
Return
Elbow
6' Max.
Offset
Elbow
A
Offset
Elbow
Return
Elbow
Offset
6' Max. Elbow
B
6' Max.
6' Max.
C
Figure 7 - Typical Offset Terminations
126634-01A
www.Astria.US.com
7
INSTALLATION
Continued
PENETRATING ROOF
Screws
B
A
Figure 9 - Elbow Offset
FIRESTOP SPACERS (FS-10)
Firestop spacers are required at each point
where chimney penetrates a floor space.
Their purpose is to establish and maintain
required clearance between chimney and
combustible materials. When pipe passes
through a framed opening into a living space
above, firestop must be placed onto ceiling
from below as shown in Figure 10.
They also provide complete separation from
one floor space to another or attic space as
required by most codes. When the double wall
pipe passes through a framed opening into an
attic space, the firestop must be placed into
an attic floor as shown in Figure 11.
To maintain a 2" clearance to pipe on roof with
a pitch, a rectangular opening must be cut.
1. Determine center point through which pipe
will penetrate roof.
2. Determine center point of roof. Pitch is
the distance the roof drops over a given
span, usually 12".
3. Use roof opening chart (Figure 12) to
determine correct opening length and
flashing required.
4. Remove shingles around opening measured. Cut out this section.
5. Add next sections of pipe until end
penetrates roof line. Check to see that
proper clearances are maintained. Extend
chimney by adding sections of double wall
pipe until pipe is minimum of 30" above
highest point of roof cutout. Termination
and chimney must extend a minimum of
36" above highest point where it passes
through roof.
19.5" Min.
30" Min.
2" Min.
2" Min.
Existing
Ceiling
Frame
2" Min.
Firestop
Spacer
Screws or
Staples
(Min. of 8)
Figure 10 - Firestop Spacer with Living
Space Above Ceiling
Firestop
Spacer
Screws or Staples
(Min. of 8)
Existing
Ceiling
Frame
Figure 11 - Firestop Spacer with Attic
Space Above Ceiling
8
Opening "A"
Pitch
Slope
Flat
0-6/12
6/12-12/12
0°
26.6°
45.0°
Opening
"A" Max.
19.5"
22'
27"
Used Flashing
Model No.
V6F-10DM
V6F-10DM
V12F-10DM
Figure 12 - Roof Opening Measurements
CAUTION: THE STRUCTURAL
INTEGRITY OF THE MANUFACTURED
HOME FLOOR, WALL, AND CEILING/
ROOF MUST BE MAINTAINED.
WARNING: DO NOT INSTALL IN SLEEPING
ROOM OF MOBILE HOMES.
www.Astria.US.com
126634-01A
INSTALLATION
Continued
FLASHING INSTALLATION (V6F-10DM Terminations/Spark Arrestor
Fireplace system must be terminated with
OR V12F-10DM)
Determine flashing to be used with roof opening chart. Slide flashing over pipe until base is
flat against roof. Replace as many shingles as
needed to cover exposed area and flashing
base. Secure in position by nailing through
shingles (see Figure 13). DO NOT NAIL
THROUGH FLASHING CONE.
Storm
Collar
Flashing
Cone
Nail Only
Outer
Perimeter
of Flashing
Overlap
Shingles Top
and Sides Only
listed round top or chase terminations. In any
case, refer to installation instructions supplied
with termination.
CAUTION: Do not seal openings on the rooftop flashing.
Follow installation instructions
provided with termination being
used.
Stainless
Inner Flue
Pipe
Secure
Termination
to Outer
Pipe with 3
Screws
Underlap
Shingles
at Bottom
RLT-12D
(Shown)
Level of
Flue Gas
Outlet
Waterproof
Caulking
Storm
Collar
Flashing
Figure 13 - Flashing Installation
Installing Flashing on a Metal Roof
When installing the flashing on a metal roof,
it is required that putty tape be used between
the flashing and the roof. The flashing must be
secured to the roof using #8 x 3/4" screws and
then sealed with roof coating to prevent leakage through the screw holes. A roof coating
must also be applied around the perimeter of
the flashing to provide a proper seal.
Overlap
Shingles (Top
and Sides of
Flashing Base)
Underlap
Shingles
Figure 15 - Termination
CHASE INSTALLATIONS
Instructions for chase installations are included with the chase style termination chosen.
Storm Collar Installation (SC2-1)
In a multiple chase installation, be sure to
Place storm collar over pipe and slide down provide adequate distance between termiuntil it is snug against open edge of flashing nations to prevent smoke spillage from one
(see Figure 14). Apply waterproof caulk around termination to another. Terminations must be
perimeter of collar to provide a proper seal.
separated a minimum of 24" center to center
and stacked at a minimum vertical height difChimney
Waterproof
ference of 18" (see Figure 16, page 10).
Pipe
Caulk
Note: If a decorative shroud is to be installed,
Storm
contact the manufacturer for specifications.
Flashing
Collar
Figure 14 - Storm Collar
126634-01A
www.Astria.US.com
9
INSTALLATION
Continued
18"
Min.
Typ.
24" Min.
24" Min.
Figure 16 - Multiple Chase Installation
10 FOOT RULE
All flue gas outlet chimney terminations must
extend a minimum of 3 feet in height above
highest point where it passes through the roof
and must be at least 2 feet above highest point
of the roof that is within a horizontal distance
of 10 feet (see Figure 17).
Level of
Flue Gas
Outlet
10'
10'
2' Min.
3' Min.
2' Min.
3' Min.
Figure 17 - 10 Foot Rule
FINISHING FIREPLACE
Combustible materials, such as wallboard,
gypsum board, sheet rock, drywall, plywood,
etc. may make direct contact with sides and
top around the fireplace face. It is important
that combustible materials do not overlap face
itself. Brick, glass, tile or other noncombustible
materials may overlap front face provided they
do not obstruct essential openings like louvered
slots or any other opening. When overlapping
with a noncombustible facing material, use only
noncombustible mortar or adhesive.
10
CAUTION: All gas piping
and connections must be tested
for leaks after the installation
is completed. After ensuring
that the gas valve is on, apply
soap and water solution to all
connections and joints. Bubbles
forming show a leak. Correct
all leaks at once. DO NOT USE
AN OPEN FLAME FOR LEAK
TESTING AND DO NOT OPERATE ANY APPLIANCE IF A LEAK
IS DETECTED. LEAK TESTING
SHOULD BE DONE BY A QUALIFIED SERVICE PERSON.
WARNING: Do not operate an
unvented gas log set in this fireplace with the chimney removed.
If you install a decorative gas appliance
(vented gas log), the decorative gas appliance
must comply with the Standard for Decorative
Gas Appliance for Installation in Solid Fuel
Burning Fireplaces, ANS Z21.60 or Z21.84
and shall also be installed in accordance with
the National Fuel Gas Code, ANSI Z223.1/
NFPA 54 latest edition.
WARNING: If fireplace has
been used for wood burning,
firebox and chimney must be
cleaned of soot, creosote and
ashes by a qualified chimney
cleaner. Creosote will ignite if
heavily heated.
WARNING: When using
a decorative vented gas log,
damper must be removed or
permanently locked in the fully
open position and glass doors
must be in fully open position.
www.Astria.US.com
126634-01A
FIREBRICK WALL INSTALLATION
IMPORTANT: Installation of brick
should be done after the fireplace is placed in a permanent
location.
1. The fireplace is shipped with the hearth
preinstalled. It is held in place for shipping with 3 shipping brackets (Figure 19).
Remove these brackets before installing
any of the other firebrick walls.
3. Secure the firebrick wall using two of the
side retaining brackets provided. The
bracket will slip underneath the metal lip
on the top of the wall and screw into the
inner dome of the fireplace (Figure 21).
Right Wall
Retaining
Bracket
Leading
Bricks
Figure 21 - Installing Side Walls
Shipping
Brackets
Figure 19 - Removing Shipping Brackets
2. Install the left and right firebrick walls.
There is a bracket with 2 tabs on the
bottom of each firebrick wall. Angle the
wall into the fireplace opening and into
the slots on the side of the hearth (Figure
20), then tilt the top of the panel toward
the firebox surround.
Slot
Top
Bracket
Right Face
Hearth
Figure 20 - Slots for Firebrick Walls
126634-01A
4. Install the bottom rear firebrick wall. Place
the wall face side down on the hearth with
the bottom of the wall toward the rear of
the firebox and the top toward the front
of the fireplace. Tilt the wall up toward
the back of the firebox. Secure bracket at
top of the firebrick wall to the rear firebox
surround (Figure 22).
Figure 22 - Installing Bottom Rear Wall
www.Astria.US.com
11
FIREBRICK WALL INSTALLATION
Continued
GROUTING INSTRUCTIONS
5. Install the rear top firebrick wall. Lift the
panel up with the front of the firebrick wall
facing toward the front of the fireplace.
The bottom of the panel has two tabs
that slide into the bracket on the top of
the bottom rear panel (Figure 23). Secure
the top of the firebrick wall with the rear
retaining bracket provided. The bracket
will slip underneath the metal lip on the
top of the firebrick wall and screw into the
inner dome of the fireplace (Figure 24).
Tab
Bottom
Rear
Top
Rear
Slot
Figure 23 - Installing Top Rear Wall
Retaining
Bracket
Figure 24 - Installing Top Rear Wall
6. It is recommended that the joints between
all firebrick walls be grouted for a more
finished look. For grouting instructions.
For more information and to watch a how
to video go to www.IHP.US.com and select
Technical Support.
12
Material provided:
Bag of cement
Bag of sand
Material required:
Piping bag
Joints striker
Heavy duty mixing bucket
Sponge or Wet Cloth
1. Moisten brick surface with damp sponge
or spray bottle just prior to application.
When bricks are wet, any excess grout
mixture on bricks will easily wipe off.
2. In a heavy duty mixing bucket, add equal
parts cement and sand. Add enough water
and mix together well using a power drill
with mixing wand attachment to a yogurt
like consistency. Not adding enough water
can lead to grout falling out after burning.
3. The overall length of piping bag should be
about 16". If the bag is longer than 16",
cut it down to size by removing end with
larger opening. This will make the bag
easier to handle.
4. Put grout mixture into piping bag making
sure the smaller opening is downward and
over a moist towel to avoid spilling. Place
a wet towel over the bucket making sure it
is directly on the surface of grout mixture.
This will keep the mixture moist and it will
not dry out before use.
5. Grout all joints where two firebrick walls
come together.
6. Using a trowel, remove excess grout mixture by moving trowel in the direction of
the joint. Grout mixture in the joint should
now be flush with brick surface. If not
enough grout is applied into each space,
grout may fall out after burning.
7. Using a joint striker, smooth out grout line.
Allow 72 hours before
operating fireplace.
www.Astria.US.com
126634-01A
INSTALLATION
Continued
INSTALLING SCREEN
1. Slide round end of screen rod into rings at
top of screen. Attach one push-on nut to end
of rod before attaching last ring of screen.
2. Insert the round end screen rod into hole
on the left and right side of smoke shelf
(Figure 25).
3. Mount flat end of screen rod with #10 x 5/8"
to center of smoke shelf.
4. Install other screen rod in same manner.
Rating
Plate
WARNING: Risk of fire! Replace grate with INNOVATIVE
HEARTH PRODUCTS grate only
(see Parts, page 23). This grate
has been designed to keep the
operation of your fireplace safe
and efficient.
Hole for Screen
Rod
Leading Bricks
Figure 25 - Installing Fireplace Screen
INSTALLING GRATE RETAINERS
1. Place the provided grate retainers on the
hearth as shown in Figure 26. The back
of the retainer will be flush with the rear
firebrick wall. Mark the center of the hole
on the hearth with a marker.
2. Drill two holes in the hearth in the marked
locations using a masonry 3/16" drill bit.
3. Secure grate retainer with masonry screws
provided.
126634-01A
Figure 26 - Installing Grate Retainers
www.Astria.US.com
13
OPTIONAL GAS LINE INSTALLATION
Gas line hook up should be done by your
supplier or a qualified service person.
Note: Before you proceed, make sure your
gas supply is turned off.
Use only a 1/2" black iron pipe and appropriate fittings.
1. Remove knockout indentation on refractory or firebrick wall located above refractory hearth floor. Knockout indentation
must be firmly tapped with any solid object
such as a 1/2" dowel until it is released.
Remove fragmented portions of refractory
(see Figure 27).
2. Remove gas line cover plate located on
either side of fireplace and pull out insulation from gas line conduit sleeve. Save
insulation for reuse. Replace screws.
3. Run a 1/2" black iron gas line into fireplace
through the rear at gas line conduit sleeve (if
using a raised platform, add height). Provide
sufficient gas line into fireplace chamber for
fitting connection (see Figure 28).
Note: Secure incoming gas line to wood
framing to provide rigidity for threaded end.
4. Repack insulation around gas line and into
sleeve opening. Seal any gaps between
gas line and refractory knockout hole with
refractory cement or commercial furnace
cement, Install the gas appliance or cap-off
gas line if desired.
CAUTION: All gas piping
and connections must be tested
for leaks after the installation
is completed. After ensuring
that the gas valve is on, apply
soap and water solution to all
connections and joints. Bubbles
forming show a leak. Correct
all leaks at once. DO NOT USE
AN OPEN FLAME FOR LEAK
TESTING AND DO NOT OPERATE ANY APPLIANCE IF A LEAK
IS DETECTED. LEAK TESTING
SHOULD BE DONE BY A QUALIFIED SERVICE PERSON.
WARNING: Do not operate an
unvented gas log set in this fireplace with the chimney removed.
14
If you install a decorative gas appliance
(vented gas log), the decorative gas appliance
must comply with the Standard for Decorative
Gas Appliance for Installation in Solid Fuel
Burning Fireplaces, ANS Z21.60 or Z21.84
and shall also be installed in accordance with
the National Fuel Gas Code, ANSI 7223NFPA
54 latest edition.
WARNING: If the fireplace
has been used for wood burning,
the firebox and chimney must be
cleaned of soot, creosote and
ashes be a qualified chimney
cleaner. Creosote will ignite if
heavily heated.
WARNING: When using a
decorative vented gas log, the
damper must be removed or
permanently locked in the fully
open position and the glass doors
must be in the fully open position.
Outside of
Fireplace
Gas Line
Conduit
Insulation
Remove
Knockout
Side
Firebrick
Finished
Side
1/2" Dowel
Gas
Conduit
Cover
Brick with
Access
Hole
Figure 27 - Gas Line Access
Side
Outside of
Firebrick
Fireplace
Finished
Incoming
Side
1/2" Black
Gas Line
Iron Pipe
Conduit
Repack
Insulation
Seal
Opening
with
Refractory
Cement
Provide Enough
Threaded
End for Fitting
Connection
Figure 28 - Gas Line Installation
www.Astria.US.com
126634-01A
GLASS DOOR INSTALLATION
IMPORTANT: Install top and bottom rails and hardware before
installing glass door panels.
Rail installation
1. Remove screws securing top face to
firebox (see Figure 29).
2. Align holes on rail to be installed at top
and replace screws. Note: Door rails are
identical until spring clips are in place.
3. Using remaining door rail as a template,
place along front row of bricks at bottom
making sure rail front surface is flush with
fireplace bottom face surface. Mark hole
centers and remove rail (see Figure 29).
4. Drill 9 - 5/32" diameter holes about 1"
deep directly into bricks using a 5/32"
concrete drill bit (not provided).
5. Place rail back on bricks and align holes.
Secure using 9 concrete screws provided
with glass door kit.
6. Secure retaining clips to top and bottom
rails (see Figure 30).
Installing Glass Doors
After spring clips have been installed some
adjustments may be needed. Install the doors
using the following steps:
Top Rail
Remove Screws
then Replace to
Secure Top Rail
Top Rail
Retaining
Clip
Bottom Rail
Figure 30 - Mounting Door Retaining
Clips
1. With bi-fold doors completely folded, insert
bottom pivot pin into bottom retaining clip
located at far left and far right side of bottom rail. Swing door to vertical position
making sure top pins slide into top door rail.
Door is installed when top door pin snaps
into spring clip (see Figure 31).
2. Repeat step 1 for remaining door.
If you find the doors do not close properly or
do not appear level or straight, proceed with
section on door adjustment.
Slide Top
Pin Into Top
Retaining Clip
Spring
Clip
Bottom Rail
(Use as a
Template before
Drilling)
Drill Holes
into Bricks
Concrete
Screws
Figure 29 - Securing Door Rails to
Fireplace
126634-01A
Bottom
Retaining
Clip
Figure 31 - Installing Doors
www.Astria.US.com
15
GLASS DOOR INSTALLATION
Continued
DOOR ADJUSTMENT
Remove doors and slightly loosen upper spring
clips. Replace and fully close doors. Use 1/8"
shims (any material) to level doors. Once proper
setting is achieved, carefully open doors enough
to access top retaining clips with a phillips
screwdriver. Tighten screws. See Figure 32.
WARNING: Do not slam or
strike doors. Damage can result
in a hazardous condition.
Side Front
Face
Spring Clip
Partially
Opened
Door
Figure 32 - Adjusting Bi-Fold Doors
OPERATION AND MAINTENANCE
GLASS DOORS
Glass doors are optional with fireplace. When
fireplace is in operation, doors must be fully
opened or fully closed position only or a fire
hazard may be created (see Figure 33).
A fireplace equipped with glass doors operates much differently than a fireplace with an
open front. A fireplace with glass doors has a
limited amount of air for combustion.
Excessive heat within the fireplace can result if
too large a fire is built or if combustion air gate is
not completely open. The following tips should
be followed to assure that both the fireplace
and glass door retain their beauty and function properly. Both the flue damper and glass
doors must be fully opened before starting fire.
This will provide sufficient combustion air and
maintain safe temperatures in firebox.
Doors Fully Closed
Fireplace Front
Fireplace Front
Doors
Fully Opened
Figure 33 - Bi-Fold Glass Doors
16
IMPORTANT: The glass must be allowed to
warm slowly and evenly. Such materials as
pitch/wax laden logs, very dry mill end lumber
and large amounts of paper or cardboard
boxes can create an excessively hot fire and
should not be burned in this fireplace. Always
keep the fire well back from the doors and
never allow flames to contact the glass.
WARNING: Fireplaces
equipped with glass doors
should be operated only with
doors fully opened or doors fully
closed. Doors, if left partly open,
may draw gas and flame out of
the fireplace opening creating
risks of both fire and smoke.
Cleaning Glass
Clean glass with any commercial glass
cleaner or soap and water. Do not use any
abrasive material to clean glass. Do not clean
glass with any cool water if glass is still hot
from the fire and smoke.
A gas line or gas log lighter may be installed
for the purpose of installing a vented or ventfree decorative gas appliance incorporating an
automatic shutoff device and complying with
the Standard for Decorative Gas Appliances for
Installation in Vented Fireplaces, ANSI Z21.60
or American Gas Association draft requirements
for Gas Fired Log Lighters for Wood Burning
Fireplaces, Draft NO. 4 dated August, 1993.
If you wish to install an unvented (vent-free)
www.Astria.US.com
126634-01A
OPERATION AND MAINTENANCE
Continued
gas log set, only unvented gas log sets which
have been found to comply with the standard
for unvented room heaters, ANSI Z21.11.2 are
to be installed in this fireplace.
FULLY CLOSED POSITION
Retaining
Bracket
(Holds
Damper
Door
Closed)
DAMPER HANDLE OPERATION
The damper handle opens and closes the
damper blade and is located in the upper rear
side of fireplace just above rear bricks. Rotate
handle counterclockwise slightly to disengage
from retaining bracket. Swing slowly toward
opening of fireplace. Engage handle to secondary bracket located at front of fireplace
inner wall (see Figure 34).
CAUTION: When operating
damper door, please be aware of
sharp edges and corners. Open
and close damper door slowly to
avoid injury.
WARNING: Risk of fire! Replace grate with INNOVATIVE
HEARTH PRODUCTS model
109496-01 grate only. This grate
has been designed to keep the
operation of your fireplace safe
and efficient.
Damper
Handle
Swing Door Down to Open
FULLY OPEN POSITION
Secondary
Retaining
Bracket
(Holds
Damper
Door
Open)
Swing Door
Up to Close
Figure 34 - Operating Damper Handle
TECHNICAL SERVICE
Yo u m a y h a v e f u r t h e r q u e s t i o n s
about installation, operation, or troubleshooting. If so, contact INNOVATIVE
HEARTH PRODUCTS PRODUCTS, at
1-800-655-2008. When calling please have
your model and serial numbers of your heater
ready.
You can also visit our web site at
www.IHP.US.com.
REPLACEMENT PARTS
If this product is missing a part or has a broken
component, please do not return it to the store.
Call INNOVATIVE HEARTH PRODUCTS at
1-800-655-2008 to answer questions and
replace parts under warranty.
WARNING: Discontinue use of the
appliance immediately if doors
are damaged and contact a qualified installer for repair. Only doors
certified with the appliance shall
be used.
126634-01A
Note: Use only original replacement parts.
This will protect your warranty coverage for
parts replaced under warranty.
When calling or writing, please have your
model and serial numbers of your fireplace
ready.
Model and serial number information are in the
fireplace's rating plate located on the fireplace
smoke shelf.
www.Astria.US.com
17
PARTS
9
6
8
4
8
8
7
8
5
2
1 124652-01
124652-03
2 124652-02
124652-04
3 125634-01
125634-02
4 124646-01
124646-02
5 124648-01
124648-02
6 124650 01
124650-02
7 124644-01
124644-02
8 124134-07
9 125553-01
18
Right Leading Brick Red
Right Leading Brick Ivory
Left Leading Brick Red
Left Leading Brick Ivory
Hearth Red
Hearth Ivory
Rear Top Red
Rear Top Ivory
Right Red
Right Ivory
Left Red
Left Ivory
Rear Bottom Red
Rear Bottom Ivory
Side Retaining Brackets
Rear Retaining Brackets
www.Astria.US.com
•
•
•
•
•
•
Ivor
DESCRIPTION
Red
KEY
NO. PART NO.
1
Bric
k
y Br
ick
3
•
•
•
•
•
•
QTY.
1
1
1
1
1
1
1
1
1
1
1
1
4
1
126634-01A
PARTS
Continued
GRATE
109496-01 (for F48 Series)
EMBER PROTECTOR - 20093
SCREEN - 118115-01
ROD - 110146-02
PUSH-ON NUT - 11418
ACCESSORIES
BI-FOLD GLASS MASONRY DOOR
OPTIONAL OUTSIDE AIR KIT FOR
FLOOR INSTALLATION - AK4F
BDMO48E - 48" Ebony
BDMO48G - 48" Pewter
BDMO48C - 48" Oiled Bronze
DOUBLE WALL PIPE - 12-12DM,
18-12DM, 24-12DM, 36-12DM, 48-12DM,
12-12HT, 18-12HT, 24-12HT, 36-12HT and
48-12HT
OPTIONAL OUTSIDE AIR KIT FOR
SIDEWALL INSTALLATION - AK4
STORM COLLAR - SC2-1
30° OFFSET AND RETURN
30E-12DM and 30E-12HT
126634-01A
www.Astria.US.com
19
ACCESSORIES
Continued
SQUARE CHASE-TOP
TERMINATION - STL-12D
OPTIONAL HEARTH SPACER
HS48
ROUND TOP TERMINATIONS
RLT-12D AND RLT-12HT
24" ROUND WOODNOOK - DHR-24
ROOF FLASHING
V6F-10DM - 0 to 6/12 Pitch
V12F-10DM - 6/12 to 12/12 Pitch
20
FIRESTOP SPACER - FS-10
www.Astria.US.com
126634-01A
Canadian code CAN/ULC-S610-M87 and
other pertinent codes require stainless steel
chimney for the installation of this fireplace.
A Cold Air Climate Kit is also required in
Canada and is recommended for cooler
regions in the United Stated. Below, find a
list of approved stainless steel parts.
Chimney Parts List for Canada
Model No.
8" Hi-Temp
Woodburning Chimney
12-8HT
12" Section Double Wall Pipe
18-8HT
18" Section Double Wall Pipe
24-8HT
24" Section Double Wall Pipe
36-8HT
36" Section Double Wall Pipe
48-8HT
48" Section Double Wall Pipe
30E-8HT
30" Offset and Return
12S-8HT
Chimney Support
RT-8HT
Round Top w/ Mesh Screen
RTT-8HT*
Round Top w/ Slip Section
& Mesh
RLT-8HT
Round Top w/ Louvers
RLTT-8HT*
Round Top w/ Slip Section
& Louvers
ET-8HT*
Square Top
ETL-8HT*
Square Top w/ Slip Section
AP-8HT
Anchor Plate/Collar Assembly
(Masonry Fireplaces)
CAK-8
Cold Air Collar Kit
IMPORTANT NOTICE
A manufactured shroud which
has been approved by a national
testing agency for use with this
fireplace may be used if installed
in accordance with the instructions by its manufacturer. A
locally fabricated shroud may be
used with IHP Shroud Leg Spacer
Kit (SLK) in accordance with
instructions provided with the
shroud.
IMPORTANT NOTICE
When penetrating a ceiling
into an attic, a firestop thimble
(38FST or FST30) is required
to avoid intrusion by insulation
and recommended to negotiate a
joist.
Thimble 38FST
or FST 30
*When ordered alone, this part cannot ship
via parcel delivery services.
Firestop
NOTICE: The firebox canopy (hood)
must not be modified or replaced with
a canopy that may be provided with
the unvented decorative room heater.
CAUTION: THE STRUCTURAL INTEGRITY OF
THE MANUFACTURED HOME FLOOR, WALL,
AND CEILING/ROOF MUST BE MAINTAINED.
WARNING: DO NOT INSTALL IN SLEEPING
ROOM OF MOBILE HOMES.
WARNING: Discontinue use of the
appliance immediately if doors
are damaged and contact a qualified installer for repair. Only doors
certified with the appliance shall
be used.
WARNING: Do not slam or strike
doors. Damage can result in a hazardous condition.
Innovative Hearth Products
Astria™ Brand Wood-Burning Fireplace
20 Year Limited Warranty
THE WARRANTY
Innovative Hearth Products ("IHP") 20 Year Limited Warranty warrants your Astria™ brand wood burning fireplace ("Product") to be free from defects in materials and
workmanship at the time of manufacture. The Product body, firebox and ceramic glass carry the 20 Year Limited Warranty. Ceramic glass carries the 20 Year Limited Warranty against thermal breakage only. After installation, if covered components manufactured by IHP are found to be defective in materials or workmanship during the 20
Year Limited Warranty period and while the Product remains at the site of the original installation, IHP will, at its option, repair or replace the covered components. If repair
or replacement is not commercially practical, IHP will, at its option, refund the purchase price or wholesale price of the IHP product, whichever is applicable. IHP will also
pay IHP prevailing labor rates, as determined in its sole discretion, incurred in repairing or replacing such components for up to five years. THERE ARE EXCLUSIONS AND
LIMITATIONS to this 20 Year Limited Warranty as described herein.
COVERAGE COMMENCEMENT DATE
Warranty coverage begins on the date of installation. In the case of new home construction, warranty coverage begins on the date of first occupancy of the dwelling or six
months after the sale of the Product by an independent IHP dealer/distributor, whichever occurs earlier. The warranty shall commence no later than 24 months following the
date of product shipment from IHP, regardless of the installation or occupancy date.
EXCLUSIONS AND LIMITATIONS
This 20 Year Limited Warranty applies only if the Product is installed in the United States or Canada and only if operated and maintained in accordance with the printed
instructions accompanying the Product and in compliance with all applicable installation and building codes and good trade practices.
This warranty is non-transferable and extends to the original owner only. The Product must be purchased through a listed supplier of IHP and proof of purchase must be
provided. The Product body and firebox carry the 20 Year Limited Warranty from the date of installation. Vent components, trim components, paint and applied stains are
excluded from this 20 Year Limited Warranty. The following do not carry a 20 Year Limited Warranty but are warranted as follows:
Air tubes, baffles and brick retainers – Repair or replacement for one year from the date of installation
Cast iron parts – Replacement for one year from date of installation
Electrical components – Repair or replacement for one year from the date of installation
Fireplace screens, refractory and side shields (metal or refractory) – Repair or replacement for two years from date of installation. Excludes hairline cracks.
Fuel grates –These parts are considered consumable accessories and therefore are not warranted, with the exception of defects in material or workmanship which
are covered for 90 days from the date of installation
Gaskets – Replacement for one year from date of installation
Gold & nickel plating – Replacement for two years from date of installation. Excludes tarnishing
Optional glass doors – Repair or replacement for 90 days from the date of installation
Labor coverage – Prevailing IHP labor rates apply for the warranty period of the component.
Parts not otherwise listed carry a 90 day warranty from the date of installation.
Whenever practicable, IHP will provide replacement parts, if available, for a period of 10 years from the last date of manufacture of the Product.
IHP will not be responsible for: (a) damages caused by normal wear and tear, accident, riot, fire, flood or acts of God; (b) damages caused by abuse, negligence, misuse, or
unauthorized alteration or repair of the Product affecting its stability or performance. (The Product must be subject to normal use with approved fuels listed in the Operation
Manual provided with the product. This includes burning such fireplace fuels as wood and natural or propane gas. Fuel products with abnormal burning characteristics,
including but not limited to fuel such as driftwood, coal or plywood and wood products using a binder may burn at excessive temperatures and may cause damage to the
Product or may cause it to function improperly.); (c) damages caused by failing to provide proper maintenance and service in accordance with the instructions provided with
the Product; (d) damages, repairs or inefficiency resulting from faulty installation or application of the Product.
Coverage of this 20 Year Limited Warranty is conditional upon use of an adequate fuel grate on factory-built fireplaces only, when applicable.
IHP is not responsible for inadequate fireplace system draft caused by air conditioning and heating systems, mechanical ventilation systems, or general construction conditions which may generate negative air pressure in the room in which the appliance is installed. Additionally IHP assumes no responsibility for smoking conditions caused by
inadequate chimney height, adjoining trees or buildings, adverse wind conditions or unusual environmental factors and conditions. Certain IHP Products are listed for use with
Security Chimneys International, Ltd. or IHP chimney systems only. Use of chimney components other than that specified in the Product manual will void the Product warranty.
This 20 Year Limited Warranty covers only parts and labor as provided herein. In no case shall IHP be responsible for materials, components or construction which are
not manufactured or supplied by IHP or for the labor necessary to install, repair or remove such materials, components or construction. Additional utility bills incurred due
to any malfunction or defect in equipment are not covered by this 20 Year Limited Warranty. All replacement or repair components will be shipped F.O.B. from the nearest
stocking IHP factory.
LIMITATION ON LIABILITY
It is expressly agreed and understood that IHP’s sole obligation and the purchaser’s exclusive remedy under this warranty, under any other warranty, expressed or implied,
or in contract, tort or otherwise, shall be limited to replacement, repair, or refund, as specified herein.
In no event shall IHP be liable for any incidental or consequential damages caused by defects in the Product, whether such damage occurs or is discovered before or after
replacement or repair, and whether such damage is caused by IHP’s negligence. IHP has not made and does not make any representation or warranty of fitness for a particular
use or purpose, and there is no implied condition of fitness for a particular use or purpose.
IHP makes no expressed warranties except as stated in this 20 Year Limited Warranty. The duration of any implied warranty is limited to the duration of this expressed warranty.
No one is authorized to change this 20 Year Limited Warranty or to create for IHP any other obligation or liability in connection with the Product. Some states and provinces
do not allow the exclusion or limitation of incidental or consequential damages, so the above limitations or exclusions may not apply to you. The provisions of this 20 Year
Limited Warranty are in addition to and not a modification of or subtraction from any statutory warranties and other rights and remedies provided by law.
INVESTIGATION OF CLAIMS AGAINST WARRANTY
IHP reserves the right to investigate any and all claims against this 20 Year Limited Warranty and to decide, in its sole discretion, upon the method of settlement.
To receive the benefits and advantages described in this 20 Year Limited Warranty, the appliance must be installed and repaired by a licensed contractor approved by IHP.
Contact IHP at the address provided herein to obtain a listing of approved dealers/distributors. IHP shall in no event be responsible for any warranty work done by a
contractor that is not approved without first obtaining IHP's prior written consent.
HOW TO REGISTER A CLAIM AGAINST WARRANTY
In order for any claim under this warranty to be valid, you must contact the IHP dealer/distributor from which you purchased the product. If you cannot locate the dealer/
distributor, then you must notify IHP in writing. IHP must be notified of the claimed defect in writing within 90 days of the date of failure. Notices should be directed to the
IHP Warranty Department at 1508 Elm Hill Pike, Suite 108; Nashville, TN 37210 or visit our website at WWW.ASTRIA.US.COM.
Printed in U.S.A. © 2013 Innovative Hearth Products LLC
P/N 900202-00, Rev. NC 12/2013
Innovative Hearth Products
1508 Elm Hill Pike, Suite 108 • Nashville, TN 37210
NOTES
_____________________________________________________
______________________________________________________
______________________________________________________
______________________________________________________
______________________________________________________
______________________________________________________
______________________________________________________
______________________________________________________
______________________________________________________
______________________________________________________
______________________________________________________
______________________________________________________
______________________________________________________
_____________________________________________________
______________________________________________________
______________________________________________________
______________________________________________________
______________________________________________________
______________________________________________________
______________________________________________________
______________________________________________________
______________________________________________________
______________________________________________________
______________________________________________________
______________________________________________________
______________________________________________________
_____________________________________________________
______________________________________________________
______________________________________________________
______________________________________________________
______________________________________________________
______________________________________________________
______________________________________________________
______________________________________________________
______________________________________________________
126634-01A
www.Astria.US.com
23
1508 Elm Hill Pike, Suite 108
Nashville, TN 37210
1-800-655-2008
P126634-01
www.IHP.US.com
126634-01
Rev. A
1/14