PRODUCT SPECIFICATION
714 and 715 -8 or -16 Zone Expanders
8 and 16 Point Zone
Expanders
Description
The DMP 714-8, 714-16, 715-8, and 715-16 Zone Expanders
allow you to increase the number of protection zones
available on DMP Command Processor™ Panels. Each
expander provides addressable protection zones for
connecting a variety of fire or burglary devices. Individual
zones on the expanders can be programmed with separate
zone types.
The expander is housed in a Model 340 metal enclosure
with lock and is suitable for mounting in a remote location.
Each expander provides screw terminal strips for zone
inputs and data bus connections, a two position jumper to
designate connection to the Keypad bus or the LX-Bus, and
a transmit data LED for panel communication. Separate
zone end-of-line resistors are included with each expander.
714-8 and 714-16 Zone Expanders
The 714 expander contains eight or sixteen Class B zones
and is suitable for use with normally open and normally
closed burglary and fire devices. Individual zones are
supervised with an end-of-line resistor and can be
programmed with any zone type.
715-8 and 715-16 Zone Expanders
The 715 expander contains eight or sixteen Class B powered
zones and is suitable for use with 12 VDC, 2-wire devices
such as smoke detectors and non-powered fire or burglary
devices. Individual zones are supervised with an
end-of-line resistor and can be programmed with any zone
type.
Features
• Powered from panel or auxiliary power supply
• 8 or 16 protection zones on each expander
• Connects to 4-wire LX-Bus™ or Keypad bus from panel
•
•
•
•
Status LED indicates good communication with panel
Individual zone programming
Individual zone annunciation
Individual zone expander addressing
• Durable metal enclosure housing with lock and key
• Individual screw terminals accommodate 14 to 22
gauge wire for easy connection
• Suitable for mounting in a remote location
Specifications
Model
714-8
714-16
Operating Voltage
8-15 VDC
8-15 VDC
715-8
715-16
9.9-15 VDC 9.9-15 VDC
Operating Current
20mA
20mA
20mA
20mA
Per Zone Current
1.6mA
1.6mA
4mA*
4mA*
*
Add 30mA per smoke detector in alarm
Add 58mA per zone short alarm (pull stations, heat detectors, and other
shorting devices)
Wiring and Addressing
Each zone expander connects to the 4-wire LX-Bus or
Keypad bus of the panel. The 715 can be connected to the
switched smoke terminal of the panel to provide reset
capability when used with latching type devices such as
two-wire smoke detectors.
Each zone expander contains two easy-to-use rotary
switches for assigning the expanders address.
All expansion zones are programmable for plain English
annunciation at Security Command™ keypads connected
to the panel. Each zone can also be individually programmed
to report alarms, troubles, and restorals to remote DMP
SCS-1 Security Receivers.
Enclosure
20 GA. Cold rolled steel
Dimensions
12.5" W x 9.5" H x 2.75" D
Color
Gray
Listings and Approvals
• Underwriters Laboratories
UL
R
LISTED