DTS Catalogue DTS Catalogue

DTS Catalogue DTS Catalogue
Thomas and Betts manufacture and design a wide range of electrical equipment for hazardous
and hostile environments to ensure the safety of the personnel working in them.
The extensive range covers Kopex-Ex metallic and non metallic conduit and fittings and the
DTS range of lighting junction and control boxes. These products are approved to a wide range
of hazardous area standards including ATEX, IECEx, UL, CSA, GOST and Inmetro.
Thomas & Betts | France / Belgium
T +33 (0) 1 64 40 27 26
E [email protected]
T
Thomas & Betts | Middle East
+971 (0) 4 609 1635
E [email protected]
T
T
Thomas & Betts | Germany / Austria
+49 (0) 62 51 669/0
E [email protected]
T
Thomas & Betts | Netherlands
+31 (0) 180 641 888
E [email protected]
T
Thomas & Betts | Italy
+39 039 65 79 028
T
Thomas & Betts | Spain
34 938 45 4570
E [email protected]
T
Thomas & Betts | UK
+44 (0) 1675 468 213
E [email protected]
Thomas & Betts | USA
901 252 5000
E [email protected]
LIT-140GBR 08/13 • Designed by www.uc4.co.uk
T
Thomas & Betts | Switzerland (PMA)
+41 44 905 61 11
E [email protected]
Product Catalogue
Lighting, Boxes, Cabinets,
Conduits, Fittings & Accessories for
Hazardous and Hostile Areas
The content of the Thomas & Betts catalogue has been carefully checked for accuracy at the time of print. However,
Thomas & Betts doesn’t give any warranty of any kind, express or implied, in this respect and shall not be liable for
any loss or damage that may result from any use or as a consequence of any inaccuracies in or any omissions from the
information which it may contain.
Copyright Thomas & Betts 2006. Copyright in these pages is owned by Thomas & Betts except where otherwise indicated.
No part of this publication may be reproduced, copied or transmitted in any form or by any means, without our prior
written permission. Images, trade marks, brands, designs and technology are also protected by other intellectual property
rights and may not be reproduced or appropriated in any manner without written permission of their respective owners.
Thomas & Betts reserves the right to change and improve any product specifications or other mentions in the catalogue
at its own discretion and at any time. These conditions of use are governed by the laws of the Netherlands and the courts
of Amsterdam shall have exclusive jurisdiction in any dispute.
Lighting, Boxes, Cabinets, Conduits, Fittings & Accessories for Hazardous and Hostile Areas
Thomas & Betts Sales Offices
A Member of the ABB Group
A Member of the ABB Group
Introduction
Thomas & Betts - Industrial Capabilities
Key of Symbols
Key of Symbols
Welcome
Thomas &toBetts Worldwide
Thomas
& Capabilities
Betts
Industrial
DTS & Kopex Ex Symbols
Market Segments
At Thomas & Betts, our focus is on improving your business
performance by providing practical, reliable electrical
products & services. To connect & protect for life. To solve
Utilities /
Power
everyday problems in the area’s of Wire & Cable Management,
Cable Protection, Power Connection & Control and Safety.
Food &
Beverage
Marine &
Shipbuilding
Chemical &
Pharmaceutical
Mining
Ex de
Ex tb
Ex t
Zone 20
Zone 21
Zone 22
Class II
Division 1
Division 2
Onshore &
Offshore
Product Characteristics
Our extensive engineering, supply chain management
and technical sales support teams are committed to
understanding everything that impacts your ability to
accomplish your business objectives by reducing your total
cost of ownership.
Ex e
Ex d
Ex n
Ex nA
Ex ia
Ex eia
Zone 0
Zone 1
Zone 2
Gas IIB
Gas IIC
Dust IIIC
Group I
Group II
Class I
54
56
Ex tc
Ex tD
IK 09
IK 10
Whether you are designing, installing, operating, maintaining
or owning an office building, off-shore platform, hospital,
T&B Headquarters
or a high speed train, power generating plant, machine
Thomas
Betts Corporation
equipment
or a &manufacturing
facility, Thomas & Betts
World Headquarters
engineered products fit and function in your application
while providing
superior
performance, sustainability, and
8155 T&B
Boulevard
Memphis, the
TN 38125
value throughout
project life cycle.
T 901.252.8000
Thomas & Betts
I www.tnb-europe.com
All our brands are built upon four product
& service Pte Ltd
Asia (Singapore)
Europe, Middle East, Asia
solution platforms. Platforms that address you or your
10 Ang Mo kio
Kopex International
customers’
electrical
& lighting needs
covering
the Techpoint
Street
65, #06-07
UK critical
Head Offi
ce
Singapore
569059
protection of data, energy, processes, assets
and personal
T +65 6720 8828
Station
Road,
Coleshill,
safety. Beyond hi-performance application characteristics,
F +65 6720 8780
Birmingham, B46 1HT
Thomas T&+44
Betts(0)
products,
information
and services
facilitate
E asia.inquiry
1675 468
213
@tnb.com
F +44
1675
468critical
280 assembly, installation or
and speed
up(0)
your
time
I www.kopex-ex.com
maintenance process.
DTS
International Call Centre
Thomas & Betts
Z.I. Parc d’Activités de la Gare
EMEA European Centre
19 à 21 avenue Henri Beaudelet
B.P. 27 - 77831 Ozoir Cedex
200 Chaussee de Waterloo
France
B-1640 Rhode-St-Genese
T +33 (0) 1 64 40 27 26
Belgium
F +33 (0) 1 64 40 20 11
T +32 (0) 2 359 82 00
E [email protected]
F +44 (0) 2 359 82 01
I www.dtselec.fr
E [email protected]
IP 54
IP 56
64
IP 64
66
IP 66
67
IP 67
Battery LED Signals
SATI
Thomas & Betts in Europe:
2
98
Healthy
(test OK)
www.tnb.com
Emergency or
Indicator
Lamp Fault
(must be
replaced)
Test in
Progress
(waiting end
of test)
Fault
(replace
battery)
Healthy
Emergency or
Indicator
Lamp Fault
Test in
Progress
Fault
www.tnb-hazardous.com
A Member of the ABB Group
A Member of the ABB Group
Contents
Contents
Oil & Gas - Upstream Applications
Oil & Gas - Midstream Applications
Oil & Gas - Downstream Applications
Food & Beverage Applications
Chemical & Pharmaceutical Applications
World Standards & What They Mean
Zone Definitions - Onshore Gases & Vapours
Zone Definitions - Offshore Gases & Vapours
Zone Definitions - Dust
DTS - Product Marking Guide
Kopex Ex - Product Marking Guide
Index of Ingress Protection
Photometry
4-5
6-7
8-9
10
11
12-13
14-15
16
17
18-19
20-21
22
23
Ex Lighting Fittings
Lighting Fittings - Selection Guide
Ex Lighting
XFF Range - Ex d
XFP Range - Ex de
XEL Range - Ex d
XEP Range - Ex de
XF Range - Ex de
XFB / XFL Range - Ex n
XDF Range - Ex nA
EVS Range - Ex de
EVN Range - Ex n
EVD Range - Ex t
ESB Range - Ex de
Ex Emergency and Self-contained Lighting
XFF-EM Range - Ex d
XFP-EM Range - Ex de
XEL-BAES Range - Self-contained Lighting - Ex d
XEL-BAES Range - Remote Control Units
EVS-EM Range - Ex de
EVS-EMA Range - Ex de
EVN-EM Range - Ex n
EVD-EM Range - Ex t
ESB-EM Range - Ex de
Industrial Lighting - Non-Hazardous Locations
FF Range
EL Range
SF / QF / HF Range
EVT Range
EST Range
FB / FL Range
HF Range
Industrial Emergency Lighting - Safe Area
FR-EM / FF-EM Range
EVT-EM Range
EST-EM Range
24-25
26-27
28-29
30-31
32-33
34-35
36-37
38-39
40-41
42-43
44-45
46-47
48-49
50-51
52-53
54-55
56-57
58-59
60-61
62-63
64-65
66-67
68-69
70-71
72-73
74-75
76-77
78-79
80-81
82-83
84-85
86-87
88-89
Lighting Accessories & Spare Parts
Lamps Guide
Wellglass
90-95
96-97
98-99
Ex Boxes & Enclosures
Boxes & Enclosures - Selection Guide
XBL Range - XB100 Junction Boxes - GRP
XBL Range - Junction Boxes - GRP
XBL Range - Instrumentation Boxes - GRP
XBL-A Range - Control Boxes - GRP
XB Range - Instrumentation Boxes - Aluminium
XB-A Range - Control Boxes - Aluminium
XBi Range - Instrumentation Boxes - Stainless Steel
XBi-A Range - Control Boxes - Stainless Steel
GUV Range - Junction Boxes - Aluminium
EFDC / SRC / XMC Range - Control Boxes - Aluminium
Custom Built Enclosures
EJB Range - Custom Built Panels - Aluminium
GUB Range - Custom Built Panels - Aluminium
EJB-V Range - Boxes with visible breaking - Aluminium
Box Accessories & Spare Parts
100-101
102-103
104-105
106-107
108-109
110-111
112-113
114-115
116-117
118-119
120-121
122-123
124-125
126-127
128-129
130-131
132-133
Conduit Systems
Conduit Fittings - Selection Guide
EXB / EXBB / XESX Range
EXBQM / EXPQA Range
NENV / NENZ Range
NEBV 90º Curved Elbow / NEWV 90º Elbow /
NEAV 45º Elbow Range / BESGR /
BEYR Y Piece / BETR T Piece Range
BEAVR / NEIR / HEAK / BENR-REM Range
EXLB / EXLT / EXLH / EXBBT / EXLHC Range
EXSB / EXST / EXSH / EXSBBT / EXSHC Range
G1 Gland / 90º Elbow Gland
Universal / Universal Swivel Gland
Group II Gland
XP Flex Range
Ex d Double Compression Cable Gland
Ex d Single Compression Cable Gland
Ex e Cable Gland
Nylon Cable Gland
Enlargers, Reducers & Thread Convertors
Ex d Stopping Plugs - Standard / Tamperproof
Ex e Stopping Plugs - Hex Head / Dome Head / Nylon
Accessories
134-135
136-137
138-139
140-141
142-143
144-145
146-147
148-149
150-151
152-154
155-157
158-159
160-161
162-163
164-165
166-167
168-169
170-173
174-175
176-177
178-179
INDEX
180-189
Thomas & Betts Worldwide Industrial Capabilities 190-191
Key of Symbols
192
3
www.tnb.com
A Member of the ABB Group
Oil & Gas - Upstream Applications
Industry Overview
Approvals / Characteristics
The oil and gas market is split into three sectors Upstream,
Midstream and Downstream. Upstream consists of Exploration
and production both these areas offer very distinct and unique
challenges to people and equipment working within them.
Firstly there are offshore applications such as the drilling rigs
and production platforms; these are always open to extreme
weather conditions so equipment used here needs to be able to
withstand a salty environment. This is achieved through either
Product Selection
manufacturing product from stainless steel as is the
case for the Kopex-Ex conduit glands, and DTS enclosures, or
by ensuring that the product is coated or painted to withstand
marine environments as in the DTS XFF fluorescent lighting.
Equipment in offshore applications also needs to be
hardwearing and easy to maintain as production downtime
can be extremely costly for example FPSO (Floating Production
Storage and Offloading) vessel can produce up to 200,000
barrels of crude oil per day at approx $80 to $90 per barrel.
4
A breakdown would result in the vessel producing a loss of
revenue of over $700,000 per hour.
www.tnb-hazardous.com
•
•
•
•
•
•
•
•
Salt water corrosion (offshore platforms)
Oil and chemical resistance (Drilling rig MUD)
Extreme ambient temperature
Protection level
Connectivity to other pieces of equipment
Consequence of down time
Approval level required (Ex e, Ex d, etc.)
Approval specification required ATEX, IECEx,
UL, GOST, etc.
• Where product will be positioned, e.g. Zone 1
or Zone 2
Oil & Gas - Upstream Applications
This has led to Kopex-Ex conduit systems being used in many
This brings with it a whole new series of challenges to be overcome.
offshore applications to protect critical data and power cables
Firstly the drilling rigs tend to be mobile with motors and pumps often
across these massive vessels, whether it is data cables from
mounted on skids for easy transportation. This can lead to issues of
a gas detector or the cable protection on a power transmission
connectivity for which Kopex-Ex have a range of thread converters
unit, Kopex-Ex offers a whole range of products that are
in a variety of materials and approvals ready to resolve the problem.
tested and approved to many of the world standards.
Secondly with so many rigs in network there is a massive
DTS lighting on the other hand offers easy maintenance
monitoring operation to be done to ensure that the flow of all
with removable gear trays allowing the maintenance to be
the rigs is ongoing and consistent. This is where the DTS range of
carried out quickly and safely. In fact on the XFF Exd luminaries
instrumentation boxes can offer great flexibility as they can be
the components such as ballasts and tubes are standard so
custom made to meet exact specifications.
the stocking and sourcing of spare parts is made easy. Again
essential to an offshore vessel.
The need to maintain flow also leads to the need for motors and
controls on the well heads themselves often referred to as “Christmas
Onshore applications can also be split into exploration and
Trees.” These are under high pressure and must be able to withstand
production. However onshore is more economically viable than
up to 1400 bar this is a critical area and has to be monitored closely
offshore with some wells only producing as few as a dozen
to ensure that pressure do not fluctuate this is done by the valves
barrels of oil a day. However, they can become extremely large
within the wellhead controlled by motors. DTS EJB enclosures can be
with wells being networked together to produce up to a
custom built to control these valves and at the same time monitor
million barrels of oil a day.
the pressures and relay it back to the central control point.
Related Products
5
EXL Conduit
154
Stopping Plugs 176
EJB Range
132
XFF Range
28
www.tnb.com
A Member of the ABB Group
Oil & Gas - Midstream Applications
Industry Overview
Approvals / Characteristics
Midstream relates to the transportation, storage and partial
processing of crude oil and gas from the wellheads to the refining
plants. This brings a different set of challenges to overcome.
This all relates to the fact that what is pumped out of the well
is not pure and often contains a mixture of oil, gas, water
and often sand which firstly need to be separated off from each
other before being shipped or piped to a storage facility.
This can be done in a variety of ways depending on the type of oil
Product Selection
or gas that the well is pumping and can often take up to 4 processes
before the commodity is separated out ready for piping or
• Salt water corrosion (Tankers)
shipping. These processes require energy and this energy is often
• Extreme ambient temperature
created from the commodity itself by the utilization of the gas.
• Protection level
• Consequence of down time
Once the separating has been completed, the commodity can
• Approval level required (Ex e, Ex d, etc.)
then be moved to storage. In the case of an offshore rig this
• Approval specification required ATEX, IECEx,
separating is often done on shore away from the rig then
pumped to the storage depots. In the case of the FPSO vessels
6
it is all done on board and the oil transferred to tankers at
sea for delivery to storage depots.
www.tnb-hazardous.com
UL, GOST etc
• Where product will be positioned, e.g. Zone 1
or Zone 2
Oil & Gas - Midstream Applications
This is also the point when all metering needs to take place
DTS also offers a wide range of standard and custom made
to calculate invoices and taxes today. This is done very
instrumentation boxes often used in the monitoring
accurately measuring not only the amount of oil produced but
equipment to relay signals from the sensors back to the central
also the density, viscosity, pressure and temperature, and in
control systems. As well as a range of standard configuration
the case of gas, the amount of water vapour.
for control boxes including “Emergency Stop” and “On - Off”
to control motors etc. All of these are available in GRP,
Oil is often pumped direct to the oil refinery which is where the
aluminum and Stainless steel 316 therefore meeting any
down stream operation starts but often needs to go through
environmental requirement.
a series of pumps to get the required pressure.
Kopex-Ex conduits are used in many applications including to
With DTS and the Kopex-Ex range of products, Thomas & Betts can
protect the critical data cables feeding the information from
offer a range of products and services to meet the demands of
sensors to the instrumentation boxes as well as being used
midstream oil and gas markets. The DTS range of lighting products
on the compressors protecting the wiring where temperatures
is manufactured to meet ATEX and IECEx standards. Designed
can reach over 100ºC.
to be robust to meet the vigors of the environment whether it is on
oil tankers where the XFF product is ideal. To storage depots
where the EVS range of fluorescents is often preferred. Added to
this all the fluorescent lighting has been designed with the
installer and maintenance people in mind with removable gear
trays for easy and safe installation and maintenance.
Related Products
7
EXL Conduit
148
Stopping Plugs 176
EFDC Range
122
EVS Range
42
www.tnb.com
A Member of the ABB Group
Oil & Gas - Downstream Applications
Industry Overview
Approvals / Characteristics
The term downstream relates to the processing and delivery of
finished carbon related product to the end-user. This covers a whole
range of applications from refining to petrol stations.
There are over 700 refineries globally all competing to supply
finished carbon based products to local and international markets.
The products refined are varied including:
• Transportation fuels
LPG, gasoline, jet fuel, diesel, gas oil and bunker fuel.
Product Selection
• Petrochemical feedstocks
LPG, naphtha and aromatics.
• Energy sources
LPG, kerosene, heating oil and fuel oil.
• Specialities
Lubricants, bitumen, coke, solvents and waxes.
• Petrochemical feedstocks
Synthetic fibres (nylon), plastics (polyethylene, PVC).
• Continual Movement (CCTV)
• Extreme ambient temperature
• Protection level
• Consequence of down time
• Approval level required (Ex e, Ex d, etc.)
• Approval specification required ATEX, IECEx,
UL, GOST, etc.
• Where product will be positioned, e.g. Zone 1
or Zone 2
8
www.tnb-hazardous.com
Oil & Gas - Downstream Applications
The refining process is in four stages, firstly distillation which
All the stages in the downstream operation have different
separates it into 5 product sectors LPG, Naphtha, Kerosine, Gas,
requirements to ensure safety of personnel and the quality of
Oil, and Atmospheric residue, this is done using high
the end product. DTS and Kopex-Ex products are both used in
temperature. The higher the temperature the higher the quality
this area whether it is the XF floodlight range or EVS
of the product.
fluorescent range. They are all designed for easy maintenance.
There is also a range of instrumentation boxes either with
The second stage is the upgrading or reforming. This stage
standard configurations or custom made to end-user
is used to change the product at a molecular level for
requirements, all of which are essential within a refinery where
example changing the low octane version of Naphtha to high
sensors play a key part on the process to ensure quality.
octane which can be blended into gasoline.
Kopex-Ex also plays a key part within the downstream market.
Stages three and four are about treating the product to
It is not just used to protect the sensor cables but also for
remove impurities such as sulphur and blending the refined
security on CCTV all the way through to the cable protection
product into distinct products for the market.
on rail tankers and tanker trucks.
The final stage of the downstream process is delivery to the
market which involves storage and transportation. For example
in the case of aviation fuel this can be shipped direct to
airports by road or rail where it is stored, before transferring
to tanker trunks for the refuelling of aircraft.
Related Products
9
EXL Conduit
148
Stopping Plugs 176
XF Range
36
EVS Range
42
www.tnb.com
A Member of the ABB Group
Food & Beverage Applications
Food Manufacture - Explosion Proof (Dust)
Food Industry
Beverage Industry
Thomas & Betts offer a range of products for the food
Thomas & Betts has a range of products designed for use
processing market, including products for use in areas
in all beverage production sectors in the malting,
where stainless steel is preferred as well as areas classed as
brewing, wine, spirits or soft drink business. DTS can supply
hazardous. Thomas & Betts can offer stainless steel
lighting products to suit the needs of hazardous areas
control stations for use on automated food processing and
where explosive gases may occur or in areas where
packaging machines as well as lighting specifically designed
cleanliness is required.
for use in dust filled atmospheres such as flour mills or
10
Beverage Manufacture - Explosion Proof (Vapour)
other places where the risk of explosion is considered to
be extremely high.
www.tnb-hazardous.com
Pharmaceutical Applications
Chemical & Pharmaceutical Applications
Chemical Engineering - Explosion Proof
Pharmaceutical Production - Explosion Proof
Chemical Industry
Pharmaceutical Industry
The chemical industry produces very diverse products,
The Thomas & Betts range of products and solutions are
everything from fertilizers to explosives such as
ideal for use in the pharmaceutical Industry. Whether
nitroglycerin. The processes used in this industry mean that
it is upstream in the primary production stage or
there are lots of applications for the DTS lighting and
downstream in the packing stage. Many of the processes
box ranges. DTS can offer standard or custom built products,
and applications used in these areas require approvals
whether it is for a process control station or for
to hazardous area standards making stainless steel junction
instrumentation boxes linking sensors back to central
and control boxes ideal.
control panels.
11
www.tnb.com
A Member of the ABB Group
World Standards
and what they mean
Standards and what they mean
Product Approvals
In this Section we will outline the different Standards used
throughout the world and what it means for products
specified for use in Hazardous Areas. Below is a map of the
world which illustrates the Standards that are generally used in
these regions.
UL
CSA
CLASS &
DIV
CLASS &
ZONES
IECEx
ATEX
GOST
INMETRO
GROUPS & ZONES
The ATEX Europe Directives 94/9/EC
ATEX marking on the product or on a certificate plate. The
ATEX requires employers to eliminate or control risks from
obligation is placed upon the manufacturer or supplier of the
dangerous substances and to classify areas where explosive
product and the intention is to facilitate free movement of
atmospheres may occur into zones, as laid down in regulations.
goods within the EU.
ATEX Directives are designed to protect employees, the public
and the environment from accidents owing to explosive
Declaration of Conformance
atmospheres and since July 1st 2006 all existing sites, as well as
This has to be issued by the supplier for every order which is
new sites, must be fully ATEX compliant.
to be installed in a hazardous area. This document has to
show that the equipment supplied complies with the latest
Directive ATEX100a applies to equipment suppliers and
manufacturers and ATEX137 applies to end users. These
directives compliment each other, but have different purposes.
ATEX100A covers both electrical and non-electrical products
intended for use in hazardous areas, including mechanical
equipment. The Directive came into existence in 2003 and
products sold within the European Union designed for use in
12
hazardous areas must have ATEX certification and bear the
www.tnb-hazardous.com
harmonized standard.
World Standards
IECEx (International Scheme)
Electrical materials for use in potentially explosive
The IECEx scheme is an international certificate of
atmospheres must conform to two major certification
conformance for products used in a hazardous area.
standards: IEC/CENELEC and NEC
The IEC (International Electrotechnical Commission) standards
This scheme provides:
are accepted in practically all countries. They are identical to
a) A single certification of conformity for manufacturers to
the European CENELEC standards.
comply that includes:
i) Testing and assessment of products to a standard
including a full test report.
The NEC (National Electrical Code) is mandatory in the
United States. The 1996 version, art. 505, takes up the IEC
ii) Ongoing surveillance of manufacturers premises.
designations for gas, temperature classes for materials and
b) A fast-track process for countries where regulations still
zone definition.
require the issuing of national Ex certificates or approvals.
Gases and vapours classification
This scheme is in the process of being adopted by all the
Gases are divided into four groups in the NEC (National
known standards across the world but are all working to
Electrical Code) and three groups for IEC/CENELEC. The groups
various time scales.
display the same hierachy of classification of gases and vapour.
(See table on page 20).
Temperature classification
The IEC and the NEC have also defined a temperature
UL (America) & CSA (Canada)
classificiation for material used in zones at risk of explosion.
The American and Canadian standards are the only ones to
(See table on page 21).
have different classifications and locations. ATEX & IECEx
work to Groups and Zones whereas the NEC & CEC works
to Classes and Divisions, there is no direct comparison
between the two. This means that it is imperative that the two
standards are not inter-changed within an area.
GOST (Russia)
GOST follows similar rules to that of IECEx as far as the
breakdown of the zones and other criteria are concerned.
However, the requirements for this country mean that
separate GOST markings are required on the product.
GOST is divided into GOST (R) which is the standard for Russian
Federation and GOST (K) that cover Kazakhstan.
13
www.tnb.com
A Member of the ABB Group
Zone Definitions
Onshore Gases & Vapours (as per ATEX 60079-10)
Zones for Onshore Gases & Vapours
FOR GASES & VAPOURS
ZONE 0
Permanent / Frequent
Place in which an explosive
atmosphere consisting of a mixture with air
of flammable substances in the form of gas,
vapour or mist is present continuously or for
long periods, or frequently.
14
www.tnb-hazardous.com
ZONE 1
Ocassional
Site where an atmosphere
consisting of a mixture of air and
inflammable substances in the form of gas,
vapour or mist is likely to arise occasionally
during normal operation.
Zones Explained
SAFETY ZONE
Low Explosion Risk
ZONE 2
Gas Irregular / Short Duration
Place in which an explosive
atmosphere consisting of a mixture with air
of flammable substances in the form of gas,
vapour or mist is not likely to occur in
normal operation but, if it does occur, will
persist for a short period only.
15
www.tnb.com
A Member of the ABB Group
Zone Definitions
Offshore Gases & Vapours (as per ATEX 60079-10)
Zones for Offshore Gases & Vapours
FOR GASES & VAPOURS
ZONE 0
Permanent / Frequent
Place in which an explosive
atmosphere consisting of a mixture with air
of flammable substances in the form of gas,
vapour or mist is present continuously or for
long periods, or frequently.
SAFETY ZONE
Low Explosion Risk
ZONE 1
Ocassional
Site where an atmosphere
consisting of a mixture of air and
inflammable substances in the form of gas,
vapour or mist is likely to arise occasionally
during normal operation.
ZONE 2
Gas Irregular / Short Duration
Place in which an explosive
atmosphere consisting of a mixture with air
of flammable substances in the form of gas,
vapour or mist is not likely to occur in normal
operation but, if it does occur, will persist for
a short period only.
16
www.tnb-hazardous.com
Zones Explained
Zone Definitions
Dust (as per ATEX 60079)
Zones for Dust
FOR DUST
ZONE 20
Permanent / Frequent
Area in which an explosive
atmosphere in the form of a cloud of
combustible dust in air is present continuously,
or for long periods, or frequently.
ZONE 21
Occasional
Area in which an explosive
atmosphere, in the form of a cloud
of combustible dust in air is likely to occur,
occasionally, in normal operation,
ocassionally.
ZONE 22
Dust Irregular / Short Duration
Area in which an explosive
atmosphere, in the form of a cloud of
combustible dust in air is not likely to occur
in normal operation but, if it does occur,
will persist for a short period only.
SAFETY ZONE
No Explosion Risk
17
www.tnb.com
A Member of the ABB Group
DTS - Classification of equipment
for use in potentially explosive atmospheres
Classification of hazardous areas
European/IEC or NEC classifications
Flammable Temporary behaviour of
substances flammable substances in
hazardous places
Gases
Vapours
Typical
zones
equipment
group
equipment
protection level
is present continuously or
for long periods or frequently
zone 0
II
Ga
is likely to occur in normal
operation occasionally
zone 1
II
Gb
zone 2
II
IIA
Gc
IIC
is present continuously or for
for long periods or frequently
zone 20
III
Da
is likely to occur in normal
operation occasionally
zone 21
III
Db
zone 22
III
Dc
-
mines
I
Ma
-
mines
I
Mb
Gases or vapours
ammonia
methane
ethane
propane
ethyl alcohol galsoline
cyclohexane n-hexane
n-butane
acetaldehyde
town gas,
acrylnitril
ethylene
ethylene
oxide
ethylene
glycol
ethyl-ether
hydrogen
ethine
(acetylene)
sulphide of
carbon
Dust
it is not likely to occur in normal
operation but, if it does occur,
will persist for a short period only
Methane
Dusts
Subdivision of gases and vapours
Apparatus may
be used in group
IIB
is not likely to occur in normal
opration but, if it does occur, will
persist for a short period only
Dusts
Required marking for installation
IIIA
IIIB
IIIC
Combustible Flyings
Non-Conductive Dust
Conductive Dust
Product stamp detail
19-21, avenue Henri Baudelet
77831 Ozoir-la-Ferriere (France)
12/0116422
XB10-SI
U=415V/50Hz
(Serial No.)
Ex II 2 G Exe IIC T6/ II 2 D Extb IIIC T85C IP66
0081
(Gas)
LCIE 11 ATEX 3050 X
(Certification Number)
18
www.tnb-hazardous.com
(Dust)
DTS Product Marking Guide
Restriction
for using apparatus
Protection technique
Requirements
Application
Type of protection
All applications
Marking
Equipment without
restriction
Equipment with
special condition
may be noted
Ex component,
which is not
intended to be
used alone
and requires
additional
certification before
being used in
hazardous area
-
Marking
EN/IEC standard
General requirements
-
60079-0
Control stations, motors, fuses,
switchgear, power electronics
Flameproof enclosure
Ex d
60079-1
Installation materials, motors, luminaries
Increased safety
Ex e
60079-7
Measurement and control, automation
technology, sensors, actuators
Intrinsic safety
Ex i
60079-11
Switch- and control cupboards,
analyse-apparatus, computers
Pressurisation
Ex p
60079-2
Coils of motors or relays, solenoid valves
Encapsulation
Ex m
60079-18
Transformers, relays, control stations,
magnetic contactors
Oil immersion
Ex o
60079-6
Capacitors, transformers
Powder filling
Ex q
60079-5
See at the top - only for zone 2
‘Non sparking’
Ex n
60079-15
For use in zone 0, 1, 2 / for use in zone 1, 2
Dust atmospheres
Ex t
60079-31
X
U
IIA T1 Acetone 735º
IIA T1 Ammonia 630º
IIB T1 Carbon Monoxide 605º
IIA T1 Bensene 560º
IIC T1 Hydrogen 560º
IIA T1 Methane 537º
IIA T1 Toluene 535º
IIA T1 Styrene 490º
IIA T1 Propane 470º
IIA T1 1-Butene 455º
IIB T1 Butadiene 430º
IIB T2 Ethylene 425º
IIA T2 Butane 372º
IIA T2 Ethanol 363º
IIA T2 Butylalcohol 359º
IIB T2 Dimetylether 350º
IIC T2 Acetylene 305º
IIA T3 Nafta 290º
IIA T3 Hydrogen Sulphide 270º
IIA T3 Cyclohexane 259º
IIA T3 Hexane 233º
IIA T3 Heptane 215º
IIA T3 Kerosene 210º
IIA T3 Dekane 201º
IIB T4 Diethyl Ether 160º
Temperature Class (T) / Ignition Temperature
Product use depending on
temperature class (T1 - T6).
750º
600º
450º
T1 > 450º
300º
T2 > 300º
200º
T3 > 200º
135º
T4 > 135º
100º
T5 > 100º
85º
T6 > 85º
19
IIC T6 Carbon Disulphide 95º
www.tnb.com
A Member of the ABB Group
Kopex-Ex - Classification of equipment
for use in potentially explosive atmospheres
Classification of hazardous areas
European/IEC or NEC classifications
Flammable Temporary behaviour of
substances flammable substances in
hazardous places
Gases
Vapours
Typical
zones
equipment
group
equipment
protection level
is present continuously or
for long periods or frequently
zone 0
II
Ga
is likely to occur in normal
operation occasionally
zone 1
II
Gb
zone 2
II
IIA
Gc
IIC
is present continuously or for
for long periods or frequently
zone 20
III
Da
is likely to occur in normal
operation occasionally
zone 21
III
Db
zone 22
III
Dc
-
mines
I
Ma
-
mines
I
Mb
Gases or vapours
ammonia
methane
ethane
propane
ethyl alcohol galsoline
cyclohexane n-hexane
n-butane
acetaldehyde
town gas,
acrylnitril
ethylene
ethylene
oxide
ethylene
glycol
ethyl-ether
hydrogen
ethine
(acetylene)
sulphide of
carbon
Dust
it is not likely to occur in normal
operation but, if it does occur,
will persist for a short period only
Methane
Dusts
Subdivision of gases and vapours
Apparatus may
be used in group
IIB
is not likely to occur in normal
opration but, if it does occur, will
persist for a short period only
Dusts
Required marking for installation
IIIA
IIIB
IIIC
Combustible Flyings
Non-Conductive Dust
Conductive Dust
Product stamp detail
CMPL
I M2/II 2GD Exde I Mb Exde IIC Gb Extb IIIC Db
(Product stamp detail)
CLI.Div1.ABCD .CLII.Div1.EFG.
(Class & Divisions)
20
CLI (Class I), Div1
CLII (Class II), Div1
Where ignitable concentrations of flammable gases, vapors or liquids
are present within the atmosphere under normal operation conditions.
Where ignitable concentrations of combustible dusts are present within
the atmosphere under normal operation conditions.
CLI (Class I), Div2
CLII (Class II), Div2
Where ignitable concentrations of flammable gases, vapors or liquids are
present within the atmosphere under abnormal operation conditions.
Where ignitable concentrations of combustible dusts are present
within the atmosphere under abnormal operation conditions.
Class I Areas
Class II Areas
Group A: Acetylene / Group B: Hydrogen /
Group C: Propane & Ethylene / Group D: Benzene, Butane & Propane.
Group E: Metal Dust / Group F: Carbon & Charcoal / Group G: Flour,
Starch, Wood & Plastic.
www.tnb-hazardous.com
Kopex-Ex Product Marking Guide
Restriction
for using apparatus
Protection technique
Requirements
Application
Type of protection
All applications
Marking
Equipment without
restriction
Equipment with
special condition
may be noted
Ex component,
which is not
intended to be
used alone
and requires
additional
certification before
being used in
hazardous area
-
Marking
EN/IEC standard
General requirements
-
60079-0
Control stations, motors, fuses,
switchgear, power electronics
Flameproof enclosure
Ex d
60079-1
Installation materials, motors, luminaries
Increased safety
Ex e
60079-7
Measurement and control, automation
technology, sensors, actuators
Intrinsic safety
Ex i
60079-11
Switch- and control cupboards,
analyse-apparatus, computers
Pressurisation
Ex p
60079-2
Coils of motors or relays, solenoid valves
Encapsulation
Ex m
60079-18
Transformers, relays, control stations,
magnetic contactors
Oil immersion
Ex o
60079-6
Capacitors, transformers
Powder filling
Ex q
60079-5
See at the top - only for zone 2
‘Non sparking’
Ex n
60079-15
For use in zone 0, 1, 2 / for use in zone 1, 2
Dust atmospheres
Ex t
60079-31
X
U
IECEx SIRA09.0103 X
(Certification Number)
IIA T1 Acetone 735º
IIA T1 Ammonia 630º
IIB T1 Carbon Monoxide 605º
IIA T1 Bensene 560º
IIC T1 Hydrogen 560º
IIA T1 Methane 537º
IIA T1 Toluene 535º
IIA T1 Styrene 490º
IIA T1 Propane 470º
IIA T1 1-Butene 455º
IIB T1 Butadiene 430º
IIB T2 Ethylene 425º
IIA T2 Butane 372º
IIA T2 Ethanol 363º
IIA T2 Butylalcohol 359º
IIB T2 Dimetylether 350º
IIC T2 Acetylene 305º
New Marking - EPL’s
(Explosion Protection Levels)
The introduction of the EPL’s and changes in the
EN 60079 series standard has introduced new
marking requirements.
IIA T3 Nafta 290º
IIA T3 Hydrogen Sulphide 270º
IIA T3 Cyclohexane 259º
IIA T3 Hexane 233º
IIA T3 Heptane 215º
IIA T3 Kerosene 210º
IIA T3 Dekane 201º
IIB T4 Diethyl Ether 160º
Temperature Class (T) / Ignition Temperature
Product use depending on
temperature class (T1 - T6).
750º
600º
450º
T1 > 450º
300º
T2 > 300º
200º
T3 > 200º
135º
T4 > 135º
100º
T5 > 100º
85º
T6 > 85º
21
IIC T6 Carbon Disulphide 95º
www.tnb.com
A Member of the ABB Group
Index of Ingress Protection
Index of
Ingress Protection
IPxx suitability ratings are a system for classifying the
IP Classification
The first digit stands for
protection against
solid bodies
degree of protection provided by enclosures of electrical
equipment. The higher the number, the greater the
degree of protection, in accordance with standards
IEC 60529 and EN 60529.
7
=
IP 6
7
The second digit
stands for protection
against water
Protection standrards
• Protection against solid bodies
• Protection against liquids
• Protection against impact a per EN 50102 standard
Protection against Solid Bodies
Protection against Liquids
0
No protection
0
No protection
1
Protected against solid bodies
of 50mm and greater, (e.g. accidental
contact with the hand)
1
Protected against vertically falling
drops of water (condensation)
2
Protected against solid bodies
of 12.5mm and greater, (e.g. accidental
touch by fingers)
2
Protected against drops of water
falling up to 15º from the vertical
3
0
Protected against solid bodies
of 2.5mm and greater, (e.g. tools
and wires)
3
Protected against drops of water
falling up to 60º from the vertical
4
0
Protected against solid bodies
of 1mm or greater, (e.g. thin tools
and fine wires)
4
Protected against splashing water
from all directions
0
5
Protected against dust - limited
ingress (no harmfull deposits)
5
Protection against jets of water from
all directions
6
Totally protected against dust
(Dust-tight)
6
Protection against powerful jets of
water from all directions
7
Protected against the effects of
temporary immersion in water
8
Protected against the continuous
effects of immersion in water having
regard to specific conditions
9
IP69k Automotive standard DIN40050
signifies resistance to high pressure
jets (up to 80bar) from any angle
22
www.tnb-hazardous.com
Hazlux Catalogue
Introducing the NEW Industrial and Hazardous
Location Lighting Catalogue from Hazlux
®
Thomas & Betts® is committed to delivering high quality
industrial lighting fixtures designed, tested and
certified for use in hazardous locations and adverse
environment conditions.
You can rely on Hazlux® to safely provide light where
you need it - even under the harshest indoor and outdoor
conditions. If safety, labour reduction, quality and
reliability are your priorities, consider Hazlux® lighting
products to reduce maintenance and prevent downtimes.
Specifically designed and approved to UL and
CSA for the American market.
Call now to order!
our NEW Industrial and Hazardous Location Lighting product catalogue on
tel +44 (0) 1675 468 213 or visit our website at www.tnb-hazardous.com
23
www.tnb.com
A Member of the ABB Group
Ex Lighting Fittings
24
26
www.tnb-hazardous.com
Ex Lighting Fittings
25
www.tnb.com
A Member of the ABB Group
Ex Lighting Fittings - Selection Guide
Ex Lighting Range
Zones
Dust
Gas
Groups Groups
Protection Type
XFF
Page 28
26
www.tnb-hazardous.com
XFP
Page 30
XEL
Page 32
XEP
Page 34
XF
Page 36
XDF
Page 40
EVS
Page 42
EVN
Page 44
EVD
Page 46
ESB
Page 48
Ex Lighting Fittings - Selection Guide
Ex Emergency & Escape Lighting Range
XFF-EM
Page 50
XFP-EM
Page 52
XEL-BAES
Page 54
EVS-EM
Page 58
EVS-EMA
Page 60
EVN-EM
Page 62
EVD-EM
Page 64
ESB-EM
Page 66
27
www.tnb.com
A Member of the ABB Group
XFF Range
Tubular fluorescent fitting
Approvals / Characteristics
Features
• Manufactured from marine grade aluminium
• Supplied with offshore grade paint
• All components mounted on sliding gear tray for
easy installation and maintenance
• Standard components used inside body allowing
reduced maintenance costs
• Available in polycarbonate (light, high impact resistant)
or in glass (specific chemical environment & paint shop)
• Including accessories (cable gland & fixing brackets)
Certification & Standards
Polycarbonate
Version
Glass
Version
28
Approved to: EN60079-0, 60079-1, 60079-31
EC TYPE Examination Certificate:
INERIS 11 ATEX 0051X
Ex II 2 G
Ex d IIC T6 Gb for ≤ -20ºC to ≤ +55ºC (All Polycarbonate tubes)
Ex d IIC T6 Gb for ≤ -20ºC to ≤ +55ºC (Glass tubes)
Ex d IIB T6 Gb for ≤ -20ºC to ≤ +55ºC (Glass versions - XFR140,
XFR165, XFF240 and XFF265)
Ex II 2 D
Ex tb IIIC T80°C Db IP66
Glow wire test: 960ºC EN60598-2-22
Safe operating temperature range: -20°C to +55ºC
The fixture is supplied with non-barrier cable glands. For installations in either
Zone 1 or in the presence of Group IIC gases, barrier glands are required.
Please refer to EN-60079-14.
www.tnb-hazardous.com
Ex lighting - XFF Range
Technical Specifications
Dimensions
165
Wiring
Configuration
Rating (W)
Nominal
Current (A)
Diffuser
XFR120-0G000
5 Wire
1 x 18
0.15
Polycarbonate
780
565
5.5
XFR136-0G000
5 Wire
1 x PL36
0.2
Polycarbonate
780
565
6
XFR140-0G000
5 Wire
1 x 36
0.2
Polycarbonate
1385
1170
9
XFR155-0G000**
5 Wire
1 x PL55
0.25
Polycarbonate
780
565
6
XFR165-0G000
5 Wire
1 x 58
0.35
Polycarbonate
1690
1475
11
XFF220-0G000
5 Wire
2 x 18
0.3
Polycarbonate
780
565
6.5
XFF236-0G000
5 Wire
2 x PL36
0.4
Polycarbonate
780
565
6.5
XFF240-0G000
5 Wire
2 x 36
0.4
Polycarbonate
1385
1170
10
XFF255-0G000**
5 Wire
2 x PL55
0.5
Polycarbonate
780
565
6.5
XFF265-0G000
5 Wire
2 x 58
0.5
Polycarbonate
1690
1475
12
XFR120V-0G000
5 Wire
1 x 18
0.15
Glass
780
565
7
XFR136V-0G000
5 Wire
1 x PL36
0.2
Glass
780
565
8
XFR140V-0G000
5 Wire
1 x 36
0.2
Glass
1385
1170
17
XFR155V-0G000**
5 Wire
1 x PL55
0.25
Glass
780
565
8
XFR165V-0G000
5 Wire
1 x 58
0.35
Glass
1690
1475
17
XFF220V-0G000
5 Wire
2 x 18
0.3
Glass
780
565
8.5
XFF236V-0G000
5 Wire
2 x PL36
0.4
Glass
780
565
8.5
XFF240V-0G000
5 Wire
2 x 36
0.4
Glass
1385
1170
18
XFF255V-0G000**
5 Wire
2 x PL55
0.5
Glass
780
565
8.5
XFF265V-0G000
5 Wire
2 x 58
0.5
Glass
1690
1475
20
Type
Dimensions (mm)
A
B
Weight (kg)
**T5 for gas or T95ºC for dust when supply is 240V AC
Enclosure
End caps according to standard:
EN1706:EN AC-AISi12(Fe) DF or
EN AC-AISi10Mg(a) DF marine grade aluminium
UV protected extruded polycarbonate tube,
thickness 2.5mm
Borosilicate glass, thickness 7mm
Fixing
Standard: D023 - 2 Zinc Plated Steel articulated
(brackets for ceiling mounting included)
Rated voltages
Electronic ballast:
AC/DC 110-260V, 50-60Hz
Power factor
Up to 0.98
Cable entries
Standard: Two entries 3/4” NPT included
One 3/4” Nickel Plated Brass plug (EXN/075/SP)
One cable gland (EXN05AMC3) - 3/4” NPT Nickel
Plated Brass for non-armoured cable, diameter 12-16mm
Terminal block (plug in terminal block)
Up to 10mm² (rigid wire), 6mm² (flexible wire)
Terminals supplied L1, L2, L3, N, PE (looping possible
with 1 additional cable gland)
Lamps (order separately)
T8 bi-pin G13 tube, Ø 26 - white industry 4000°K
G11 compact fluorescent PL lamp
Shock proof kit
See dimension column A
D036 - 1690mm
Spares
D035 - 1385mm
D034 - 780mm
Other options
Stainless steel shock proof kit 304L
Colour (standard)
XF****-0G000 - Yellow offshore, RAL 1003
Colour options
XF****-BG000 - Grey, RAL 7035
XF****-CG000 - Black, RAL 9004
XF****-DG000 - Hammered Blue, RAL 5015
XF****-FG000 - Red, RAL 3001
XF****-GG000 - Blue, RAL 5010
XF****- JG000 - Green, RAL 6032
XF****-MG000 - White, RAL 9010
•
•
•
•
•
•
•
& Fixings Accessories see pages 90-95
Related Products
29
EXL Conduit
148
Stopping Plugs 174
GUV Range
120
Ex d Cable
Gland
162
www.tnb.com
A Member of the ABB Group
XFP Range
Tubular fluorescent fitting with
automatic switch off
Approvals / Characteristics
Features
• Manufactured from marine grade aluminium
• Supplied with offshore grade paint
• All components mounted on sliding gear tray for
easy installation and maintenance
• Standard components used inside body allowing
reduced maintenance costs
• Available in polycarbonate (light, high impact resistant)
or in glass (specific chemical environment & paint shop)
• Including accessories (cable gland & fixing brackets)
Certification & Standards
Polycarbonate
Version
Glass
Version
30
www.tnb-hazardous.com
Approved to: EN60079-0, 60079-1, 60079-7
EC TYPE Examination Certificate:
INERIS 11 ATEX 0052X
Ex II 2 G
Ex de IIC T6 Gb for ≤ -20ºC to ≤ +55ºC (All Polycarbonate tubes)
Ex de IIC T6 Gb for ≤ -20ºC to ≤ +55ºC (Glass tubes)
Ex de IIB T6 Gb for ≤ -20ºC to ≤ +55ºC (Glass versions - XFP140V,
XFP165V, XFP240V and XFP265V)
Ex II 2 D
Ex tb IIIC T80°C Db IP66
Glow wire test: 960ºC EN60598-2-22
Safe operating temperature range: -20°C to +55ºC
Ex lighting - XFP Range
Technical Specifications
Dimensions
260
165
Wiring
Configuration
Rating (W)
Nominal
Current (A)
Diffuser
XFP120-0G000
3 Wire
1 x 18
0.15
Polycarbonate
780
565
5.5
XFP136-0G000
3 Wire
1 x PL36
0.2
Polycarbonate
780
565
6
XFP140-0G000
3 Wire
1 x 36
0.2
Polycarbonate
1385
1170
9
XFP155-0G000**
3 Wire
1 x PL55
0.25
Polycarbonate
780
565
6
XFP165-0G000
3 Wire
1 x 58
0.35
Polycarbonate
1690
1475
11
XFP220-0G000
3 Wire
2 x 18
0.3
Polycarbonate
780
565
6.5
XFP236-0G000
3 Wire
2 x PL36
0.4
Polycarbonate
780
565
6.5
XFP240-0G000
3 Wire
2 x 36
0.4
Polycarbonate
1385
1170
10
XFP255-0G000**
3 Wire
2 x PL55
0.5
Polycarbonate
780
565
12
XFP265-0G000
3 Wire
2 x 58
0.5
Polycarbonate
1690
1475
12
XFP120V-0G000
3 Wire
1 x 18
0.15
Glass
780
565
7
XFP136V-0G000
3 Wire
1 x PL36
0.2
Glass
780
565
8
XFP140V-0G000
3 Wire
1 x 36
0.2
Glass
1385
1170
17
XFP155V-0G000**
3 Wire
1 x PL55
0.25
Glass
780
565
8
XFP165V-0G000
3 Wire
1 x 58
0.35
Glass
1690
1475
17
Type
Dimensions (mm)
A
B
Weight (kg)
XFP220V-0G000
3 Wire
2 x 18
0.3
Glass
780
565
8.5
XFP236V-0G000
3 Wire
2 x PL36
0.4
Glass
780
565
8.5
XFP240V-0G000
3 Wire
2 x 36
0.4
Glass
1385
1170
18
XFP255V-0G000**
3 Wire
2 x PL55
0.5
Glass
780
565
18
XFP265V-0G000
3 Wire
2 x 58
0.5
Glass
1690
1475
20
**T5 for gas or T95ºC for dust when supply is 240V AC
Enclosure
End caps according to standard:
EN1706:EN AC-AISi12(Fe) DF or EN ACAISi10Mg(a) DF marine grade aluminium
UV protected extruded polycarbonate tube,
thickness 2.5mm
Borosilicate glass, thickness 7mm
Fixing
Standard: D023 - 2 Zinc Plated Steel articulated
(brackets for ceiling mounting included)
Rated voltages
Standard electronic ballast:
AC/DC 110-260V, 50-60Hz
Power factor
Up to 0.98
Cable entries
Standard: One entry M20
One cable gland (EXN04MMC2) - M20 Nickel
Plated Brass for non-armoured cable,
diameter 10-16mm
Terminal block (plug in terminal block)
Up to 6mm² (rigid wire), 4mm² (flexible wire)
Terminals supplied L, N, PE
Lamps (order separately)
T8 bi-pin G13 tube, Ø 26 - white industry 4000°K
G11 compact fluorescent PL lamp
Other options
Stainless steel shock proof kit 304L
Shock proof kit
See dimension column A
D036 - 1690mm
D035 - 1385mm
D034 - 780mm
Colour (standard)
XFP***-0G000 - Yellow offshore, RAL 1003
Colour options
XFP***-BG000 - Grey, RAL 7035
XFP***-CG000 - Black, RAL 9004
XFP***-DG000 - Hammered Blue, RAL 5015
XFP***-FG000 - Red, RAL 3001
XFP***-GG000 - Blue, RAL 5010
XFP***- JG000 - Green, RAL 6032
XFP***-MG000 - White, RAL 9010
•
•
•
•
•
•
•
Related Products
31
EXL Conduit
148
Stopping Plugs 174
GUV Range
120
Ex d Cable
Gland
162
www.tnb.com
A Member of the ABB Group
XEL Range
Miniature tubular fluorescent fitting
Approvals / Characteristics
Features
• Manufactured from marine grade aluminium
• Supplied with offshore grade paint
• All components mounted on the gear tray for easy
installation and maintenance
• Standard components used inside the body allowing
reduced maintenance costs
• Available in polycarbonate (light, high impact resistant)
or in glass (for specific chemical environment and paint
shop for easy cleaning)
• Including accessories (cable gland & fixing brackets)
Certification & Standards
Polycarbonate
Version
Glass
Version
32
Approved to: EN60079-0, 60079-1, 60079-7, 60079-31
EC TYPE Examination Certificate:
INERIS II ATEX 0051X
Ex II 2 G
Ex d IIC T6 Gb
Ex II 2 D
Ex tb IIIC T80°C Db IP66
Glow wire test: 960ºC EN60598-2-22
Safe operating temperature range: -20°C to +55ºC
The fixture is supplied with non-barrier cable glands. For installations in either
Zone 1 or in the presence of Group IIC gases, barrier glands are required.
Please refer to EN-60079-14
www.tnb-hazardous.com
Ex lighting - XEL Range
Technical Specifications
Dimensions
A 455
B 240
165
Wiring
Configuration
Rating (W)
Nominal
Current (A)
Diffuser
XEL3008-0G000
5 Wire
1x8
0.1
Polycarbonate
455
240
5
XEL3009-0G000
5 Wire
1 x PL9
0.1
Polycarbonate
455
240
9
XEL30011-0G000
5 Wire
1 x PL11
0.1
Polycarbonate
455
240
5
XEL120-0G000
5 Wire
1 x PL18
0.3
Polycarbonate
455
240
4.5
XEL220-0G000
5 Wire
2 x PL18
0.5
Polycarbonate
455
240
5
XEL30028-0G000
5 Wire
2x8
0.1
Polycarbonate
455
240
5
XEL3008V-0G000
5 Wire
1x8
0.1
Glass
455
240
7
XEL3009V-0G000
5 Wire
1 x PL9
0.1
Glass
455
240
9
XEL30011V-0G000
5 Wire
1 x PL11
0.1
Glass
455
240
7
XEL120V-0G000
5 Wire
1 x PL18
0.3
Glass
455
240
6.5
XEL220V-0G000
5 Wire
2 x PL18
0.5
Glass
455
240
7
XEL30028V-0G000
5 Wire
2x8
0.1
Glass
455
240
7
Type
Enclosure
End caps according to standard:
EN1706:EN AC-AISi12(Fe) DF or
EN AC-AISi10Mg(a) DF marine grade aluminium
UV protected extruded polycarbonate tube,
thickness 2.5mm
Borosilicate glass, thickness 7mm
Fixing
Standard: D023 - 2 Zinc Plated Steel articulated
(brackets for ceiling mounting included)
Rated voltages
Standard electronic ballast:
AC/DC 220-240V, 50-60Hz
Power factor
Up to 0.98
Cable entries
XEL: Two entries 3/4” NPT included
One 3/4” Nickel Plated Brass plug (EXN/075/SP)
One cable gland (EXN05AMC3) - 3/4” NPT Nickel
Plated Brass for non-armoured cable,
diameter 12-16mm
Terminal block
Up to 10mm² (rigid wire), 6mm² (flexible wire)
Terminals supplied L1, L2, L3, N, PE (looping possible
with 1 additional cable gland)
Dimensions (mm)
A
B
Weight (kg)
Lamps (order separately)
T5 bi-pin G5 tubes, Ø 16 coolwhite 4000°K
Compact fluorescent PL lamp with G11 base (18W)
or G23 (7W, 9W, 11W)
Colour (standard)
XEL***-0G000 - Yellow offshore, RAL 1003
Colour options
XEL***-BG000 - Grey, RAL 7035
XEL***-CG000 - Black, RAL 9004
XEL***-DG000 - Hammered Blue, RAL 5015
XEL***-FG000 - Red, RAL 3001
XEL***-GG000 - Blue, RAL 5010
XEL***- JG000 - Green, RAL 6032
XEL***-MG000 - White, RAL 9010
•
•
•
•
•
•
•
Spares & Fixings Accessories see pages 90-95
Related Products
33
EXL Conduit
148
Stopping Plugs 174
GUV Range
120
Ex d Cable
Gland
162
www.tnb.com
A Member of the ABB Group
XEP Range
Miniature tubular fluorescent fitting
with automatic switch off
Approvals / Characteristics
Features
• Manufactured from marine grade aluminium
• Supplied with offshore grade paint
• Maintenance in hazardous area - quick and easy
isolation switch for safe maintenance in hazardous area
• All components mounted on the gear tray for easy
installation and maintenance
• Standard components used inside the body allowing
reduced maintenance costs
• Available in polycarbonate (light, high impact resistant)
or in glass (specific chemical environment & paint shop)
• Including accessories (cable gland & fixing brackets)
Certification & Standards
Polycarbonate
Version
Glass
Version
34
www.tnb-hazardous.com
Approved to: EN60079-0, 60079-1, 60079-7
EC TYPE Examination Certificate:
INERIS II ATEX 0052X
Ex II 2 G
Ex de IIC T6 Gb
Ex II 2 D
Ex tb IIIC T80°C Db IP66
Glow wire test: 960ºC EN60598-2-22
Safe operating temperature range: -20°C to +55ºC
Ex lighting - XEP Range
Technical Specifications
Dimensions
A 455
165
260
B 240
Wiring
Configuration
Rating (W)
Nominal
Current (A)
Diffuser
XEP3008-0G000
3 Wire
1x8
0.1
Polycarbonate
455
240
XEP3009-0G000
3 Wire
1 x PL9
0.1
Polycarbonate
455
240
5
XEP30011-0G000
3 Wire
1 x PL11
0.1
Polycarbonate
455
240
5
XEP120-0G000
3 Wire
1 x PL18
0.3
Polycarbonate
455
240
4.5
XEP220-0G000
3 Wire
2 x PL18
0.5
Polycarbonate
455
240
5
XEP30028-0G000
3 Wire
2x8
0.1
Polycarbonate
455
240
5
XEP3008V-0G000
3 Wire
1x8
0.1
Glass
455
240
7
XEP3009V-0G000
3 Wire
1 x PL9
0.1
Glass
455
240
7
XEP30011V-0G000
3 Wire
1 x PL11
0.1
Glass
455
240
7
XEP120V-0G000
3 Wire
1 x PL18
0.3
Glass
455
240
6.5
XEP220V-0G000
3 Wire
2 x PL18
0.5
Glass
455
240
7
XEP30028V-0G000
3 Wire
2x8
0.1
Glass
455
240
7
Type
Enclosure
End caps according to standard:
EN1706:EN AC-AlSi12(Fe) DF or
EN AC-AlSi10Mg(a) DF marine grade aluminium
UV protected extruded polycarbonate tube,
thickness 2.5mm
Borosilicate glass, thickness 7mm
Fixing
Standard: D023 - 2 Zinc Plated Steel articulated
(brackets for ceiling mounting included)
Rated voltages
Standard electronic ballast:
AC/DC 220-240V, 50-60Hz
Power factor
Up to 0.98
Cable entries
Standard: One M20 cable entry included
One cable gland (EXN04MMC2), Nickel Plated Brass
for non-armoured cable, diameter 10-16mm
Terminal block
Up to 6mm² (rigid wire), 4mm² (flexible wire)
Terminals supplied for L, N, PE
Dimensions (mm)
A
B
Weight (kg)
5
Lamps (order separately)
T5 bi-pin G5 tubes, Ø 16 coolwhite 4000°K
Compact fluorescent PL lamp with G11 base (18W)
or G23 (7W, 9W, 11W)
Colour (standard)
XEP***-0G000 - Yellow offshore, RAL 1003
Colour options
XEP***-BG000 - Grey, RAL 7035
XEP***-CG000 - Black, RAL 9004
XEP***-DG000 - Hammered Blue, RAL 5015
XEP***-FG000 - Red, RAL 3001
XEP***-GG000 - Blue, RAL 5010
XEP***- JG000 - Green, RAL 6032
XEP***-MG000 - White, RAL 9010
•
•
•
•
•
•
•
Spares & Fixings Accessories see pages 90-95
Related Products
35
EXL Conduit
148
Stopping Plugs 174
GUV Range
120
Ex d Cable
Gland
162
www.tnb.com
A Member of the ABB Group
XHM : Also available pre mounted
(see opposite for details)
XF Range
Floodlight fittings
Approvals / Characteristics
Features
• Compact, lightweight and robust
• Ex e integral juction box: easy connection
• Excellent photometric properties, wide or narrow beam
• Internationally recognised
• Supplied with lamp installed and cable gland
• Supplied with offshore grade paint
Certification & Standards
Approved to: EN60079-0, 60079-1, 60079-7
EC TYPE Examination Certificate:
LCIE 00 ATEX 6019X / IECEx LCI 11-0062X
Ex II 2 G
Ex de IIB T1 to T5 Gb for ≤ -20ºC to ≤ +60ºC
depending on model
IP test: IP66 IEC 60529 (2001)
36
www.tnb-hazardous.com
Ex lighting - XF Range
Technical Specifications
Dimensions
Standard Flat
Type*
Mounting
Pole Mounting
Nominal
Rating (W)
Nominal
Current (A)
-20ºC to +40ºC
Temperature Class
-20ºC to +60ºC
Weight (kg)
XSF70P-00000
Flat
1 x 70W HP Sodium
0.4
T4
T3
17
XSF70G-00000
Pole
1 x 70W HP Sodium
0.4
T4
T3
17
XSF150P-00000
Flat
1 x 150W HP Sodium
0.8
T4
T3
17
XSF150G-00000
Pole
1 x 150W HP Sodium
0.8
T4
T3
17
XSF250P-00000
Flat
1 x 250W HP Sodium
1.3
T3
T3
18
XSF250G-00000
Pole
1 x 250W HP Sodium
1.3
T3
T3
18
XSF400P-00000
Flat
1 x 400W HP Sodium
2.1
T3
T2
20
XSF400G-00000
Pole
1 x 400W HP Sodium
2.1
T3
T2
20
XQF250P-00000
Flat
1 x 250W Metal Halide
1.3
T3
T2
20
XQF250G-00000
Pole
1 x 250W Metal Halide
1.3
T3
T3
18
XQF400P-00000
Flat
1 x 400W Metal Halide
2.1
T3
T3
18
XQF400G-00000
Pole
1 x 400W Metal Halide
2.1
T3
T2
20
XEF110P-00000
Flat
2 x 55W Halogen (12V)
9.2
T5
T5
13
XEF110G-00000
Pole
2 x 55W Halogen (12V)
9.2
T5
T5
13
XEF140P-00000
Flat
2 x 70W Halogen (24V)
5.8
T5
T5
13
XEF140G-00000
Pole
2 x 70W Halogen (24V)
5.8
T5
T5
13
*X... F... -0A000 (to complete with nominal rating & mounting) - Narrow beam, for example XQF400P-0A000
Enclosure
Marine grade aluminium alloy type according to
EN1706:EN AC-AlSi7 Mg 0,6 T6
Cataphoretically treated
12mm toughened glass
Rated voltages
Version HPS/metal halide:
Standard: 230V 50Hz ferromagnetic ballast,
with capacitor
Option: ferromagnetic ballast
- 220V 60Hz
- 120V 60Hz on few models
Power factor
Up to 0.85 for version with compensated ballast
(Sodium HP and metal halide)
Cable entries
Standard: Two entries M20 included
One plug (EXN/M20/HSP) and one cable gland
(EXN04MMC2) - Nickel Plated Brass ISO M20 for
non-armoured cable, diameter 10-16mm
Terminal block
Up to 6mm² (rigid wire), 4mm² (flexible wire)
Terminal supplies for L, N, PE
Lamps (Installed)
Polished aluminium reflector
Standard: wide beam
Option: narrow beam
Fixing
Standard:galvanised steel flat mounting bracket,
yellow polyester paint RAL1003
Pole mounted: Ø 40 to 60mm
Other options
Sling (SC100 ELINGUE)
FC 108 (CLAMP FOR BEAM MOUNTING)
SC100 (SAFETY HARNESS)
SA 103 (Jobsite option)
Galvanised steel support with base plate (SA103)
XHM... Pre wired masthead floodlighting systems:
Full system with 2 or 4 floodlights
For example XHM 4400 (4 x 400 W HPS)
(to complete with nominal rating)
Colour (standard)
X*****-00000 - Yellow offshore, RAL 1003
Colour option
X*****-B0000 - Grey, RAL 7035
X*****-C0000 - Black, RAL 9004
X*****-D0000 - Hammered Blue, RAL 5015
X*****-F0000 - Red, RAL 3001
X*****-G0000 - Blue, RAL 5010
X*****- J0000 - Green, RAL 6032
X*****-M0000 - White, RAL 9010
•
•
•
•
•
•
•
Spares & Fixings Accessories see pages 90-95
Related Products
37
EXL Conduit
148
Stopping Plugs 176
GUV Range
120
Ex e Cable
Gland
166
www.tnb.com
A Member of the ABB Group
XFB / XFL Range
Warning lights and beacons
Approvals / Characteristics
Features
• Lightweight and robust for easy installation
• Static or flashing versions available for use in a
variety of applications
• Choice of 5 colours of globe
• 2 or 3 light versions available for traffic signals
• Supplied with single cable gland and lamps installed
• Including accessories (cable gland, plug & lampstand)
Certification & Standards
Approved to: EN60079-0, 60079-15, 60079-31
EC TYPE Examination Certificate:
Ex II 3 G / D
Ex nA IIC T5 Gc
Ex tc IIIC T100ºC Dc IP66 for ≤ -20ºC to ≤ +60ºC
38
www.tnb-hazardous.com
Ex lighting - XFB / XFL Range
Technical Specifications
8
Dimensions
Type
Rating (W)
Lamp
Globe Colour*
Version
Rated Voltages
Weight (kg)
XFB30-00000
1 x 28
E27
Red
Halogen
AC 230V 50/60Hz
3.5
XFB70-00000
1x8
E27
Red
LED
AC 100-240V 50/60Hz
3.5
XFL30P-00000
30 Joules
Picots
Red
Xenon flash
AC 230V 50/60Hz
4
XFL30P-0C000
30 Joules
Picots
Red
Xenon flash
AC 100V 50/60Hz
4
XFL30P-0D000
30 Joules
Picots
Red
Xenon flash
DC 24V
4
XFL30P-0E000
30 Joules
Picots
Red
Xenon flash
DC 48V
4
XFL30P-0F000
30 Joules
Picots
Red
Xenon flash
DC 110V
4
XFB230-00000
2 x 28
E27
Red / Green
Halogen
AC 230V 50/60Hz
7
XFB270-00000
2x8
E27
Red / Green
LED
AC 100-240V 50/60Hz
7
XFL230-00000
2 x 30 Joules
Picots
Red / Green
Xenon Flash
AC 230V 50/60Hz
8
XFL230-0C000
2 x 30 Joules
Picots
Red / Green
Xenon Flash
AC 100V 50/60Hz
8
XFL230-0D000
2 x 30 Joules
Picots
Red / Green
Xenon Flash
DC 24V 50/60Hz
8
XFL230-0E000
2 x 30 Joules
Picots
Red / Green
Xenon Flash
DC 48V 50/60Hz
8
XFL230-0F000
2 x 30 Joules
Picots
Red / Green
Xenon Flash
DC 110V 50/60Hz
8
XFB330-00000
3 x 28
E27
Red / Yellow / Green
Halogen
AC 230V 50/60Hz
10.5
XFB370-00000
3x8
E27
Red / Yellow / Green
LED
AC 100-240V 50/60Hz
10.5
XFL330-00000
3 x 30 Joules
Picots
Red / Yellow / Green
Xenon Flash
AC 230V 50/60Hz
12
XFL330-0C000
3 x 30 Joules
Picots
Red / Yellow / Green
Xenon Flash
AC 100V 50/60Hz
12
XFL330-0D000
3 x 30 Joules
Picots
Red / Yellow / Green
Xenon Flash
DC 24V
12
XFL330-0E000
3 x 30 Joules
Picots
Red / Yellow / Green
Xenon Flash
DC 48V
12
XFL330-0F000
3 x 30 Joules
Picots
Red / Yellow / Green
Xenon Flash
DC 110V
12
*Choice of globe colours: XF...-00000 - Red, XF...-000A0 - Transparent globe, XF...-000B0 - Green globe, XF...-000C0 - Orange globe, XF...-000D0 - Blue globe
**Colour combination: please contact Sales for more information
Enclosure
Marine grade aluminium alloy type
EN1706 AC-43100KF-AlSi 10Mg
Aluminium reflector
Temperature
Ambient temperature: -20°C to +60°C
Cable entries
Standard: Two entries M20 included
One Nickel Plated Brass plug (EXN/M20/HSP ) and
one cable gland (EXN04MMC2) - Nickel Plated Brass
ISO M20 for non-armoured cable, diameter 10-16mm
Terminal block
Up to 6mm2
Terminals supplied for L, N, PE
Lamps (supplied)
For xenon flash versions
Flashing rate: 45 to 60 - per minute
Globe
Polycarbonate, thickness 3mm
Colour (standard)
XF****-00000 - Yellow offshore, RAL 1003
Colour options
XF****-B0000 - Grey, RAL 7035
XF****-C0000 - Black, RAL 9004
XF****-D0000 - Hammered Blue, RAL 5015
XF****-F0000 - Red, RAL 3001
XF****-G0000 - Blue, RAL 5010
XF****- J0000 - Green, RAL 6032
XF****-M0000 - White, RAL 9010
•
•
•
•
•
•
•
Spares & Fixings Accessories see pages 90-95
Related Products
39
EXL Conduit
148
Stopping Plugs 176
GUV Range
120
Thread
Convertors
170
www.tnb.com
A Member of the ABB Group
XDF Range
Drilling fluorescent fitting
Approvals / Characteristics
Features
•
•
•
•
•
•
•
Vibration resistant lighting system
Plug in system for fast installation
Designed to minimise heat build up and overheating
Corrosion resistant ideal for marine applications
Hazardous and safe area versions available
Including accessories (socket, plug, fixation & cable)
Supplied with offshore grade paint
Certification & Standards
X
40
www.tnb-hazardous.com
Approved to: EN60079-0, 60079-15
EC TYPE Examination Certificate:
Ex II 3 G / D
Ex nA IIC T4 Gc
Ex tc IIIC T135ºC Dc IP6X
Temperature range: -20ºC to +60ºC
Ex lighting - XDF Range
Technical Specifications
Dimensions
B
A
264
80
11
145
155
145
108
220
108
Rated Voltage
Rating (W)
Nominal
Current (A)
Diffuser
A
B
Weight (kg)
XDF140-00000
230V 50Hz
1 x 36
0.20
Polycarbonate
1173
1540
8.5
XDF165-00000
230V 50Hz
1 x 58
0.35
Polycarbonate
1474
1841
9
XDF140-0D000
220V 60Hz
1 x 36
0.20
Polycarbonate
1173
1540
8.5
XDF165-0D000
220V 60Hz
1 x 58
0.35
Polycarbonate
1474
1841
9
Type
Enclosure
End caps according to standard:
EN1706:EN AC-AISi12(Fe) DF or
EN AC-AISi10Mg(a) DF marine grade aluminium
Including offshore option
Yellow offshore polyurethane paint RAL 1003
UV protected extruded polycarbonate tube,
thickness 2.5mm
Wiring Diagram
Rated voltages
Ferromagnetic ballast
Cable entries
Standard: Two M20 cable entries
Supplied with:
One plug entry: male - 2 poles & earth 10Amp - 250VAC
One socket entry: female - 2 poles & earth 10 Amp - 250VAC
One extendable cable with male plug and female
socket (Helical cable) expandable to 5 metre max
Terminal block (plug in terminal block)
Up to 6mm²
Terminals supplied L, N, PE
Lamps (order separately)
T8 bi-pin G13 tube, Ø 26 - white industry 4000°K
Fixing (included)
2 Brackets for beam clamp fixing
Other options
Other voltage ratings: on request
Power
Supply
Upto 8
Upto 8
XDF
XDF
XDF
XDF
Upto 8
Must be used with XD104R - Junction box
For 3 x 8 = 24 light fitting
Contact Sales for further details
Spares & Fixings Accessories see pages 90-95
XDF
XDF
Related Products
41
EXL Conduit
148
Stopping Plugs 176
GUV Range
120
www.tnb.com
A Member of the ABB Group
EVS Range
Fluorescent fitting with easy disconnect
Approvals / Characteristics
Features
•
•
•
•
•
•
Easy disconnector for safer maintenance out of zones
Double central locking for ingress protection
Main body constructed of a GRP for high impact strength
Polycarbonate diffuser to resist harsh environments
Automatic switch off upon opening for safe maintenance
All components mounted on hinged and removable gear
tray which gives easy access for maintenance
• Including accessories (cable gland & fixing brackets)
Certification & Standards
Approved to: EN60079-0, 60079-1, 60079-5, 60079-7, 60079-31
EC TYPE Examination Certificate:
LCIE 11 ATEX 3065X
IEC Ex LCI 11.0053X
Ex II 2 G
Ex de IIC T4 Gb for ≤ -40ºC to ≤ +60ºC
Ex de IIC T5 Gb for ≤ -40ºC to ≤ +35ºC
Ex II 2 D
Ex tb IIIC T85°C Db IP6X
Glow wire test: 960ºC EN60598-2-22
Safe operating temperature range: -20°C to +50ºC
IP test: IP66 IEC 60529 (2001)
42
www.tnb-hazardous.com
Ex lighting - EVS Range
Technical Specifications
Dimensions
2 M8 holes
Depth 20
170
137
Wiring
Configuration
Rating (W)
Nominal
Current (A)
A
Dimensions (mm)
B
C
EVS120-0000
5 Wire Loop
1 x 18
0.09
785
432
400
5.5
EVS120-D000
5 Wire & Continuity plate
1 x 18
0.09
785
432
400
5.5
EVS140-0000
5 Wire Loop
1 x 36
0.17
1370
900
700
7.5
EVS140-D000
5 Wire & Continuity plate
1 x 36
0.17
1370
900
700
7.5
EVS165-0000
5 Wire Loop
1 x 58
0.26
1670
900
700
9
EVS165-D000
5 Wire & Continuity plate
1 x 58
0.26
1670
900
700
9
EVS220-0000
5 Wire Loop
2 x 18
0.17
785
432
400
6.5
EVS220-D000
5 Wire & Continuity plate
2 x 18
0.17
785
432
400
6.5
EVS240-0000
5 Wire Loop
2 x 36
0.33
1370
900
700
8.5
EVS240-D000
5 Wire & Continuity plate
2 x 36
0.33
1370
900
700
8.5
EVS265-0000
5 Wire Loop
2 x 58
0.5
1670
900
700
10
EVS265-D000
5 Wire & Continuity plate
2 x 58
0.5
1670
900
700
10
Type*
Weight (kg)
*(Through options) Define type rating: EVS...-B000 5 wires through (to complete with nominal rating),
EVS...-E000 5 wires through & 2 continuity plates (to complete with nominal rating)
Enclosure
Fiberglass reinforced polyester body
Polycarbonate diffuser, treated against UV
Fixing
Standard: V015 - 2 Zinc Plated Steel brackets for
ceiling mounting
Rated voltages
Standard: electronic ballast
AC/DC 220-240V, 50/60Hz
Contact Sales Office for other voltage options
Power factor
Up to 0.98
Cable entries
Standard: Three M20 entries included
Two M20 Nylon plugs (EX-M20)
One cable gland (EXCGM20S) - ISO M20 Nylon for
non-armoured cable, diameter 6-12mm
For armoured cable - continuity plate option:
Nickel Plated Brass cable gland (EXN04MMC1),
diameter 6-12 / 8.5-16mm (1 or 2 according to
number of plates)
Terminal block
Up to 4mm² (rigid wire), 2.5mm² (flexible wire)
Wiring L1, L2, L3, N, PE (5 wires)
5 wires through option: I max = 16 A max.
Lamps (order separately)
Tube G13 bi-pin T8 Ø 26 coolwhite 4000°k
Spares & Fixings Accessories see pages 90-95
Related Products
43
EXB Conduit 138
Nylon Stopping
Plugs
176
XB100 Range 104
Exe Nylon Gland 168
www.tnb.com
A Member of the ABB Group
EVN Range
Fluorescent fitting with diffuser
Approvals / Characteristics
Features
• Double central locking for ingress protection
• Main body constructed of a GRP for high impact strength
• Polycarbonate diffuser to resist harsh and
corrosive environments
• All components mounted on hinged and removable
gear tray which gives easy access for installation
and maintenenace
• Including accessories (cable gland & fixing brackets)
• Option: automatic switch off on opening
Certification & Standards
Approved to: EN60079-0, 60079-15, EN60079-31
EC TYPE Examination Certificate: Under new 94/9/EC self certified
Ex II 3 G
Ex nr IIC T4 Gb for ≤ -40ºC to ≤ +60ºC
Ex nr IIC T5 Gb for ≤ -40ºC to ≤ +35ºC
Ex II 3 D
Ex tc IIIC T85ºC Db IP66
Glow wire test: 960ºC EN60598-2-22
Safe operating temperature range: -20°C to +50ºC
IP test: IP66 IEC 60529 (2001)
44
www.tnb-hazardous.com
Ex lighting - EVN Range
Technical Specifications
Dimensions
2 M8 holes
Depth 20
170
137
Wiring
Configuration
Rating (W)
Nominal
Current (A)
A
EVN120-0000
5 Wire Loop
1 x 18
0.17
785
432
400
4.2
EVN120-D000
5 Wire & Continuity plate
1 x 18
0.17
785
432
400
4.2
EVN140-0000
5 Wire Loop
1 x 36
0.17
1370
900
700
6.5
EVN140-D000
5 Wire & Continuity plate
1 x 36
0.17
1370
900
700
6.5
EVN165-0000
5 Wire Loop
1 x 58
0.26
1670
900
700
8
EVN165-D000
5 Wire & Continuity plate
1 x 58
0.26
1670
900
700
8
EVN220-0000
5 Wire Loop
2 x 18
0.17
785
432
400
4.5
EVN220-D000
5 Wire & Continuity plate
2 x 18
0.17
785
432
400
4.5
EVN240-0000
5 Wire Loop
2 x 36
0.33
1370
900
700
6.8
6.8
Type*
Dimensions (mm)
B
C
Weight (kg)
EVN240-D000
5 Wire & Continuity plate
2 x 36
0.33
1370
900
700
EVN265-0000
5 Wire Loop
2 x 58
0.5
1670
900
700
8.5
EVN265-D000
5 Wire & Continuity plate
2 x 58
0.5
1670
900
700
8.5
*(Through options) Define type rating: EVN...-B000 5 wires through (to complete with nominal rating),
EVN...-E000 5 wires through & 2 continuity plates (to complete with nominal rating)
Enclosure
Fiberglass reinforced polyester body
Polycarbonate diffuser, treated against UV
Fixing
Standard: V015 - 2 Zinc Plated Steel brackets for
ceiling mounting
Rated voltages
Standard: electronic ballast
AC/DC 110-260V, 50-60Hz
Contact Sales Office for other voltage options
Power factor
Up to 0.98
Cable entries
Standard: Three M20 entries included
Two M20 Nylon plugs (EX-M20)
One cable gland (EXCGM20S) - ISO M20 Nylon for
non-armoured cable, diameter 6-12mm
For armoured cable - continuity plate option:
Nickel Plated Brass cable gland (EXN04MMC1),
diameter 6-12 / 8.5-16mm (1 or 2 according to
number of plates)
Terminal block
Up to 6mm² (rigid wire), 4mm² (flexible wire)
Wiring L1, L2, L3, N, PE (5 wires)
5 wire through option: I max 16 A
Lamps (order separately)
Tube G13 bi-pin T8 Ø 26 coolwhite 4000°k
Spares & Fixings Accessories see pages 90-95
Related Products
45
EXB Conduit 138
Nylon Stopping
Plugs
176
XB100 Range 104
Exe Nylon Gland 168
www.tnb.com
A Member of the ABB Group
EVD Range
Fluorescent fitting - developed
for dust environment
Approvals / Characteristics
Features
• Double central locking for ingress protection
• Main body constructed of a GRP for high impact strength
• Polycarbonate diffuser to resist harsh and
corrosive environments
• All components mounted on hinged and removable
gear tray which gives easy access for installation
and maintenance
• Including accessories (cable gland & fixing brackets)
• Option: automatic switch off on opening
Certification & Standards
Approved to: EN60079-0, 60079-31
EC TYPE Examination Certificate:
LCIE II ATEX 3092X
IECEx LCI 11.0064X
Ex II 2 D
Ex t IIIC T82ºC (≤ +60ºC) Db
Ex t IIIC T62ºC (≤ +40ºC) Db
Glow wire test: 960ºC EN60598-2-22
Safe operating temperature range: -20°C to +50ºC
IP test: IP66 IEC 60529 (2001)
46
www.tnb-hazardous.com
Ex lighting - EVD Range
Technical Specifications
Dimensions
2 M8 holes
Depth 20
170
137
Wiring
Configuration
Rating (W)
Nominal
Current (A)
A
Dimensions (mm)
B
C
EVD120-00J0
5 Wire Loop
1 x 18
0.09
785
432
400
4.2
EVD120-D0J0
5 Wire & Continuity plate
1 x 18
0.09
785
432
400
4.2
EVD140-00J0
5 Wire Loop
1 x 36
0.17
1370
900
700
6.5
EVD140-D0J0
5 Wire & Continuity plate
1 x 36
0.17
1370
900
700
6.5
EVD165-00J0
5 Wire Loop
1 x 58
0.26
1670
900
700
8
EVD165-D0J0
5 Wire & Continuity plate
1 x 58
0.26
1670
900
700
8
EVD220-00J0
5 Wire Loop
2 x 18
0.17
785
432
400
4.5
EVD220-D0J0
5 Wire & Continuity plate
2 x 18
0.17
785
432
400
4.5
EVD240-00J0
5 Wire Loop
2 x 36
0.33
1370
900
700
6.8
EVD240-D0J0
5 Wire & Continuity plate
2 x 36
0.33
1370
900
700
6.8
EVD265-00J0
5 Wire Loop
2 x 58
0.5
1670
900
700
8.5
EVD265-D0J0
5 Wire & Continuity plate
2 x 58
0.5
1670
900
700
8.5
Type*
Weight (kg)
*(Through options) EVD...-B0J0 - 5 Wires through (to complete with rating)
EVD...-E0J0 - 5 wires through & 2 continuity plates (to complete with rating)
EVD...-.0C0 - Automatic switch off on opening including electronic ballast (to complete with rating & wiring configuration)
Enclosure
Fiberglass reinforced polyester body
Polycarbonate diffuser, treated against UV
Fixing
Standard: V015 - 2 Zinc Plated Steel brackets for
ceiling mounting
Rated voltages
Standard: electronic ballast
AC/DC 110-260V, 50-60Hz
Contact Sales Office for other voltage options
Power factor
Up to 0.98
Cable entries
Standard: Three M20 cable entries included
Two M20 Nylon plugs and
One cable gland (EXCGM20S) - ISO M20 Nylon for
non-armoured cable, diameter 6-12mm
For armoured cable - continuity plate option:
Nickel Plated Brass cable gland (EXN04MMC1),
diameter 6-12 / 8.5-16m (1 or 2 according to
number of plates)
Terminal block
Up to 6mm² (rigid wire), 4mm² (flexible wire)
Terminals supplied for L1, L2, L3, N, PE
5 wires through option: I max 16 A
Lamps (order separately)
Tube G13 bi-pin T8 Ø 26 coolwhite 4000°k
Spares & Fixings Accessories see pages 90-95
Related Products
47
EXB Conduit 138
Nylon Stopping
Plugs
176
XB100 Range 104
Exe Nylon Gland 168
www.tnb.com
A Member of the ABB Group
ESB Range
Recessed fluorescent fitting
Approvals / Characteristics
Features
• Main body made from powder coated steel
• 6mm toughened glass making it perfect
for laboratories
• Automatic switch off upon opening
for safe maintenance
• Including accessories (cable gland)
Certification & Standards
Approved to: EN60079-0, 60079-1, 60079-7
EC TYPE Examination Certificate: Under 94/9/EC
INERIS II ATEX 0058X
Ex II 2 G
Ex de IIC T4 Gb for ≤ -20ºC to ≤ +40ºC
Glow wire test: 850°C EN60598-2-22
Safe operating temperature range: -20°C to +40ºC
IP test: IP64 IEC 60529 (2001)
48
www.tnb-hazardous.com
Ex lighting - ESB Range
Technical Specifications
Dimensions
Wiring
Configuration
Rating (W)
Nominal
Current (A)
Glass
ESB220-0000
5 Wire
2 x 18
0.17
Toughened
753
702
105
400 x 240
12.5
ESB220-A000
5 Wire
2 x 18
0.17
Frosted
753
702
105
400 x 240
12.5
ESB240-0000
5 Wire
2 x 36
0.33
Toughened
1364
1312
105
1000 x 240
20
ESB240-A000
5 Wire
2 x 36
0.33
Frosted
1364
1312
105
1000 x 240
20
ESB265-0000
5 Wire
2 x 58
0.5
Toughened
1664
1612
105
1300 x 240
25
ESB265-A000
5 Wire
2 x 58
0.5
Frosted
1664
1612
105
1300 x 240
25
Type
Enclosure
Steel housing and body painted in white polyester
powderpaint RAL 9016
6mm clear toughened glass panel (optional frosted
low lumen output)
Neoprene gasket
Dimensions (mm)
A
B
C
Rated voltages
Standard: electronic ballast
AC/DC 220-240V, 50-60Hz
Contact sales office for other voltages
Power factor
Up to 0.98
Cable entries
Two M20 cable entries included
One M20 Nylon stopping plug and
One cable gland (EXCGM20S) - ISO M20 Nylon for
non-armoured cable, diameter 6-12mm
One M20 Nylon stopping plug (EX-M20)
F x F’
Weight (kg)
Terminal block
Up to 4mm² (rigid wire), 2.5mm² (flexible wire)
Terminals supplied for L1, L2, L3, N, PE
Lamps (order separately)
Tube G13 bi-pin T8 Ø 26 coolwhite 4000°k
Fixing
Fixing by 4 M6 threaded bolts (not supplied) joined
to the main body
Spares & Fixings Accessories see pages 90-95
Related Products
49
EXB Conduit 138
Nylon Stopping
Plugs
176
XB100 Range 104
Exe Nylon Gland 168
www.tnb.com
A Member of the ABB Group
XFF-EM Range
Emergency tubular fluorescent fitting
Approvals / Characteristics
Features
• Manufactured from marine grade aluminium
• Supplied with offshore grade paint
• All components mounted on the gear tray for easy
installation and maintenance
• Standard components used inside the body allowing
reduced maintenance costs
• Available in polycarbonate (light, high impact resistant)
or in glass (specific chemical environment & paint shop)
• Battery duration 2 hours
• Including accessories (cable gland & fixing brackets)
Certification & Standards
Polycarbonate
Version
Glass
Version
50
Approved to: EN60079-0, 60079-1, 60079-31
EC TYPE Examination Certificate:
INERIS 11 ATEX 0051X
Ex II 2 G
Ex d IIC T6 Gb for ≤ -20ºC to ≤ +55ºC (All Polycarbonate tubes)
Ex d IIC T6 Gb for ≤ -20ºC to ≤ +55ºC (Glass tubes)
Ex d IIB T6 Gb for ≤ -20ºC to ≤ +55ºC (Glass versions - XFR140EM
and XFF240EM)
Ex II 2 D
Ex tb IIIC T80°C Db IP66
Glow wire test: 960ºC EN60598-2-22
Safe operating temperature range: -10°C to +40ºC
The fixture is supplied with non-barrier cable glands. For installations in either
Zone 1 or in the presence of Group IIC gases, barrier glands are required.
Please refer to EN-60079-14
www.tnb-hazardous.com
Ex Emergency lighting - XFF-EM Range
Technical Specifications
Dimensions
165
Wiring
Configuration
Rating (W)
Battery
Diffuser
XFR120EM-0G000
3 Wire
1 x 18
2h
Polycarbonate
780
565
7.5
XFR140EM-0G000
3 Wire
1 x 36
2h
Polycarbonate
1385
1170
9.5
XFF220EM-0G000
3 Wire
2 x 18
2h
Polycarbonate
780
565
7.5
XFF240EM-0G000
3 Wire
2 x 36
2h
Polycarbonate
1385
1170
9.5
XFR120VEM-0G000
3 Wire
1 x 18
2h
Glass
780
565
9.5
XFR140VEM-0G000
3 Wire
1 x 36
2h
Glass
1385
1170
9.5
XFF220VEM-0G000
3 Wire
2 x 18
2h
Glass
780
565
9.5
XFF240VEM-0G000
3 Wire
2 x 36
2h
Glass
1385
1170
9.5
Type
Enclosure
End caps and cover in marine grade aluminium
alloy type EN 1706 EN AC-AlSi12(Fe) DF or
EN AC-AlSi10 Mg(a) DF
Yellow offshore polyurethane paint RAL 1003
UV protected extruded polycarbonate tube,
thickness 2.5mm
Borosilicate glass, thickness 7mm
Fixing
Standard: D023 - 2 Zinc Plated Steel articulated
brackets for ceiling mounting
For wiring, please refer to the instruction
manual (drawings)
Technical assistance on request
Rated voltages
Electronic ballast:
XFF/XFR: AC/DC 220-240V, 50-60Hz
Power factor
Up to 0.98
Cable entries
Standard: Two entries 3/4” NPT included
One 3/4” Nickel Plated Brass plug (EXN/075/SP)
One cable gland (EXN05AMC3)- 3/4” NPT Nickel
Plated Brass for non-armoured cable,
diameter 12-16mm
Battery
Lumen output in emergency mode (1 tube lit)
40% for 18W
33% for 40W
Terminal block (plug in terminal block)
Up to 10mm² (rigid wire), 6mm² (flexible wire)
Supplied L1, 2, N, PE Terminals
Looping possible with additional cable gland
Select function: Lighting in maintained mode or
lighting in non-maintained mode
Dimensions (mm)
A
B
Weight (kg)
Lamps (order separately)
T8 bi-pin G13 tube, Ø 26 - white industry 4000°K
(order separately)
T5 bi-pin 65 supplied with XEL
Other options
Stainless steel shockproof kit 304L
Colour (standard)
X*****-0G000 - Yellow offshore, RAL 1003
Colour options
X*****-BG000 - Grey, RAL 7035
X*****-CG000 - Black, RAL 9004
X*****-DG000 - Hammered Blue, RAL 5015
X*****-FG000 - Red, RAL 3001
X*****-GG000 - Blue, RAL 5010
X*****- JG000 - Green, RAL 6032
X*****-MG000 - White, RAL 9010
•
•
•
•
•
•
•
Spares & Fixings Accessories see pages 90-95
Related Products
51
EXL Conduit
148
Stopping Plugs 174
GUV Range
120
Ex d Cable
Gland
162
www.tnb.com
A Member of the ABB Group
XFP-EM Range
Emergency tubular fluorescent fitting
with automatic switch off
Approvals / Characteristics
Features
• Manufactured from marine grade aluminium
• Supplied with offshore grade paint
• Maintenance in hazardous area is quick and easy with
isolation switch for safe maintenance
• All components mounted on the gear tray for easy
installation and maintenance
• Standard components used inside the body allowing
reduced maintenance costs
• Available in polycarbonate (light, high impact resistant)
or in glass (specific chemical environment & paint shop)
• Battery duration 2 hours
• Including accessories (cable gland & fixing brackets)
Certification & Standards
Polycarbonate
Version
Glass
Version
52
www.tnb-hazardous.com
Approved to: EN60079-0, 60079-1, 60079-7, 60079-31
EC TYPE Examination Certificate:
INERIS 11 ATEX 0052X
Ex II 2 G
Ex de IIC T6 Gb for ≤ -20ºC to ≤ +55ºC (All Polycarbonate tubes)
Ex de IIC T6 Gb for ≤ -20ºC to ≤ +55ºC (Glass tubes)
Ex de IIB T6 Gb for ≤ -20ºC to ≤ +55ºC (Glass versions - XFP140EM
and XFP240EM)
Ex II 2 D
Ex tb IIIC T80°C Db IP66
Glow wire test: 960ºC EN60598-2-22
Safe operating temperature range: -10°C to +40ºC
Ex Emergency lighting - XFP-EM Range
Technical Specifications
Dimensions
260
165
Wiring
Configuration
Rating (W)
Battery
Diffuser
XFP120EM-0G000
3 Wire
1 x 18
2h
Polycarbonate
780
565
7.5
XFP140EM-0G000
3 Wire
1 x 36
2h
Polycarbonate
1385
1170
9.5
XFP220EM-0G000
3 Wire
2 x 18
2h
Polycarbonate
780
565
7.5
XFP240EM-0G000
3 Wire
2 x 36
2h
Polycarbonate
1385
1170
9.5
XFP120VEM-0G000
3 Wire
1 x 18
2h
Glass
780
565
9.5
XFP140VEM-0G000
3 Wire
1 x 36
2h
Glass
1385
1170
11
XFP220VEM-0G000
3 Wire
2 x 18
2h
Glass
780
565
9.5
XFP240VEM-0G000
3 Wire
2 x 36
2h
Glass
1385
1170
11
Type
Enclosure
End caps and cover in marine grade aluminium
alloy type EN1706:EN AC-AlSi12(Fe) DF or
EN AC-AlSi10 Mg(a) DF
UV protected extruded polycarbonate tube,
thickness 2.5mm
Borosilicate glass, thickness 7mm
Fixing
Standard: D023 - 2 Zinc Plated Steel articulated
brackets for ceiling mounting
For wiring, please refer to the instruction
manual (drawings)
Technical assistance on request
Rated voltages
Standard: electronic ballast:
AC/DC 220-240V, 50-60Hz
Power factor
Up to 0.98
Cable entries
Standard M20 cable entry included
One cable gland (EXN04MMC2) - Nickel Plated
Brass M20 for non-armoured cable,
diameter 10-16mm
Battery
Lumen output in emergency mode (1 tube lit)
40% for 18W
33% for 33W
Monitored by one LED
Dimensions (mm)
A
B
Weight (kg)
Terminal block (plug in terminal block)
Up to 6mm² (rigid wire), 4mm² (flexible wire)
Supplied L1, 2, N, PE Terminals
Select function: Lighting in maintained mode or
lighting in non-maintained mode
Lamps (order separately)
T8 bi-pin G13 tube, Ø 26 - white industry 4000°K
Other options
Stainless steel shockproof kit 304L
Colour (standard)
XFP***-0G000 - Yellow offshore, RAL 1003
Colour options
XFP***-BG000 - Grey, RAL 7035
XFP***-CG000 - Black, RAL 9004
XFP***-DG000 - Hammered Blue, RAL 5015
XFP***-FG000 - Red, RAL 3001
XFP***-GG000 - Blue, RAL 5010
XFP***- JG000 - Green, RAL 6032
XFP***-MG000 - White, RAL 9010
•
•
•
•
•
•
•
Spares & Fixings Accessories see pages 90-95
Related Products
53
EFDC Range
122
Stopping Plugs 174
GUV Range
120
Ex e Cable
Gland
164
www.tnb.com
A Member of the ABB Group
Part No. B019T
XEL-BAES Range
Self-contained emergency lighting fitting
Approvals / Characteristics
Features
• Manufactured from marine grade aluminium
• Supplied with offshore grade paint
• All components mounted on the gear tray for easy
installation and maintenance
• Self contained luminaires with built in automatic
facility to give local indication of result, test or
control monitoring
• Available in polycarbonate (light, high impact resistant)
or in glass (specific chemical environment & paint shop)
• Battery duration 2 hours
• Including accessories (cable gland & fixing brackets)
Certification & Standards
Polycarbonate
Version
Glass
Version
54
Approved to: EN60079-0, 60079-1, 60079-7, 60079-31, 60598-2-22
EC TYPE Examination Certificate:
Models SI & AI
Models A & AK
INERIS II ATEX 0052X
INERIS II ATEX 0051X
Ex II 2 G
Ex II 2 G
Ex de IIC T6 Gb
Ex d IIC T6 Gb
Ex II 2 D
Ex II 2 D
Ex tb IIIC T80ºC IP66 Db
Ex tb IIIC T80ºC IP66 Db
Glow wire test: 960ºC EN60598-2-22
Safe operating temperature range: -20°C to +55ºC
The fixture is supplied with non-barrier cable glands. For installations in either
Zone 1 or in the presence of Group IIC gases, barrier glands are required.
Please refer to EN-60079-14
www.tnb-hazardous.com
Ex Emergency lighting - XEL-BAES Range
Technical Specifications
Dimensions
455
455
240
165
165
260
240
SI & AI
A & AK
Testing Type
Switch Type (see diagrams)
Manual Automatic Addressable Unswitched Switch Off Combined Weight (kg)
Type
Function Rating (W) Diffuser
XEL3001-00000
Large area
1x8
Polycarbonate
●
–
–
●
–
–
XEL3002-00000*
Large area
2x8
Polycarbonate
●
–
–
●
–
–
5
Escape route
1x6
Polycarbonate
–
●
–
●
–
–
4.7
XEL80A-00000
5
XEL80AK-00000
Escape route
1x6
Polycarbonate
–
●
–
–
●
–
4.7
XEL80AI-00000
Escape route
1x6
Polycarbonate
–
●
–
–
–
●
5.5
XEL80SI-00000
Escape route
1x6
Polycarbonate
–
–
●
–
–
●
5.5
XEL300A-00000
Large area
1x8
Polycarbonate
–
●
–
●
–
–
5
XEL300AK-00000
Large area
1x8
Polycarbonate
–
●
–
–
●
–
5
XEL300AI-00000
Large area
1x8
Polycarbonate
–
●
–
–
–
●
5.5
XEL300SI-00000
Large area
1x8
Polycarbonate
–
–
●
–
–
●
5.5
XEL3001V-00000
Large area
1x8
Glass
●
–
–
●
–
–
7
XEL3002V-00000*
Large area
2x8
Glass
●
–
–
●
–
–
7
Escape route
1x6
Glass
–
●
–
●
–
–
6.5
XEL80VA-00000
XEL80VAK-00000
Escape route
1x6
Glass
–
●
–
–
●
–
6.5
XEL80VAI-00000
Escape route
1x6
Glass
–
●
–
–
–
●
7.3
XEL80VSI-00000
Escape route
1x6
Glass
–
–
●
–
–
●
7.3
XEL300VA-00000
Large area
1x8
Glass
–
●
–
●
–
–
7
XEL300VAK-00000
Large area
1x8
Glass
–
●
–
–
●
–
7
XEL300VAI-00000
Large area
1x8
Glass
●
–
–
–
●
7.5
XEL300VSI-00000
Large area
1x8
Glass
–
●
–
–
●
7.5
–
*Light always on
Enclosure
End caps and cover in marine grade aluminium
alloy type AS10GY30. Yellow offshore
polyurethane paint RAL 1003
UV protected extruded polycarbonate tube,
thickness 2.5mm
Borosilicate glass, thickness 7mm
Rated voltages and emergency function
Electronic ballast: AC/DC 230V, 50Hz
Power factor
Up to 0.98
Cable entries
Model SI & AI: One M20 cable entry included
One cable gland (EXN04MMC2) - Nickel Plated Brass
ISO M20 for non-armoured cable, diameter 10-16mm
Model A & AK: Two entries 3/4” NPT included
One 3/4” Nickel Plated Brass plug (EXN/075/SP)
One cable gland (EXN05AMC3) - 3/4” NPT Nickel Plated
Brass for non-armoured cable, diameter 12-16mm
Self test SATI
Safety lighting with automatic built in systems test
the lamps every 7 days and the battery pack every 12
weeks. Results of the test are displayed by yellow
and green diodes.
Healthy
Emergency or
Indicator
Lamp Fault
Test in
Progress
Battery
XEL80: Lumen output for 1 hour = 70lm,
XEL300: Lumen output for 1 hour = 280lm
Model XEL 3001 and XEL 3002 - 3 hour models
available for markets outside of France and are not
NFC approved
Terminal block
Terminals supplied for L, N, PE
Model A & AK: Up to 10mm² (rigid wire),
6mm² (flexible wire)
Terminals supplied for L, N, PE (looping possible with
additional cable glands)
Lamps (supplied installed)
XEL 80: emergency lamp: 1 x 6W tube with G5
lampholder (70 lumen), 2 charge lamp using LEDs
UNSWITCHED enclosure
Compulsary power socket
Fitting has to be removed
Maintenance must be done in
safe area
XEL 300: emergency lamp: 1 x 8W tube with G5
lampholder (280 lumen), 2 charge lamp using LEDs
Fixing
Standard: D023 - 2 Zinc Plated Steel articulated
brackets for ceiling mounting
Colour (standard)
XEL***-00000 - Yellow offshore, RAL 1003
Colour options
XEL***-B0000 - Grey, RAL 7035
XEL***-C0000 - Black, RAL 9004
XEL***-D0000 - Hammered Blue, RAL 5015
XEL***-F0000 - Red, RAL 3001
XEL***-G0000 - Blue, RAL 5010
XEL***- J0000 - Green, RAL 6032
XEL***-M0000 - White, RAL 9010
•
•
•
•
•
•
•
Enclosure with battery
SWITCH OFF
No power socket
External cut-out required
Maintenance done in
hazardous area
Enclosure with COMBINED
battery and supply switch off
No power socket
No external cut-out
Maintenance done in hazardous area
55
Fault
A Member of the ABB Group
XEL-BAES Range
Remote control units for emergency lighting
Provided by our
sister company
Regulations
Article EC 12 paragrah 6
Self-contained emergency lighting installations must
possess one or several devices allowing centralised control.
The devices most be located close to the master control
unit or one sub-division control units.
Technical Specifications
Type
Power Supply
Main Feature
Testing Type
Size (mm)
BT5F 621500
230V - 50-60Hz
Multi-brand compatibility ON / OFF offset
Unswitched - Switch off - combined
82 x 70 x 70
BT12V 621201
230V - 50-60Hz
Standard ON / OFF
Unswitched - Switch off - combined
82 x 70 x 70
56
www.tnb-hazardous.com
Remote Control Units - XEL-BAES Range
Standard Remote Control installation (BAES)
LINE IN
230V - 50Hz
Main
disconnect
Block 1
Block 2
Block 3
Remote Control installation with integrated self testing capabilities (SATI)
LINE IN
230V - 50Hz
Remote
control
Main
disconnect
Normally open contact,
close for SATI report
Sub disconnect
57
www.tnb.com
A Member of the ABB Group
EVS-EM Range
Emergency fluorescent fitting with easy disconnect
Approvals / Characteristics
Features
•
•
•
•
•
Easy disconnector for safer maintenance out of zones
Double central locking for ingress protection
Main body constructed of a GRP for high impact strength
Battery duration 2 hours
All components mounted on hinged and removable gear tray
which gives easy access for installation and maintenance
• Automatic switch off on opening for safe maintenance
• Including accessories (cable gland & fixing brackets)
Certification & Standards
Approved to: EN60079-0, 60079-1, 60079-5, 60079-7, EN61241-1
EC TYPE Examination Certificate:
LCIE 11 ATEX 3065X
IEC Ex LCI 11.0053X
Ex II 2 G
Ex de IIC T4 Gb for ≤ -40ºC to ≤ +60ºC
Ex de IIC T5 Gb for ≤ -40ºC to ≤ +35ºC
Ex II 2 D
Ex tb IIIC T85ºC Db IP6X
Glow wire test: 960ºC EN60598-2-22
Safe operating temperature range: -10°C to +40ºC
IP test: IP66 IEC 60529 (2001)
58
www.tnb-hazardous.com
Ex Emergency lighting - EVS-EM Range
Technical Specifications
Dimensions
2 M8 holes
Depth 20
170
137
Wiring
Configuration
Rating (W)
Battery
Nominal
Current (A)
A
EVS120EME-0000*
3 Wire
1 x 18
2h
0.09
785
432
400
7.5
EVS120EME-C000*
3 Wire & Continuity plate
1 x 18
2h
0.09
785
432
400
7.5
Type
Dimensions (mm)
B
C
Weight (kg)
EVS140EM-0000
3 Wire
1 x 36
2h
0.17
1370
900
700
9.5
EVS140EM-C000
3 Wire & Continuity plate
1 x 36
2h
0.17
1370
900
700
9.5
EVS220EME-0000*
3 Wire
2 x 18
2h
0.17
785
432
400
8.5
EVS220EME-C000*
3 Wire & Continuity plate
2 x 18
2h
0.17
785
432
400
8.5
EVS240EM-0000
3 Wire
2 x 36
2h
0.33
1370
900
700
10.5
EVS240EM-C000
3 Wire & Continuity plate
2 x 36
2h
0.33
1370
900
700
10.5
*Easy disconnect not available
Enclosure
Fiberglass reinforced polyester body
Polycarbonate diffuser, treated against UV
Standard: V015 - 2 Zinc Plated Steel brackets for
ceiling mounting
For wiring, please refer to the instruction
manual (drawings)
Technical assistance on request
Rated voltages
Standard: electronic ballast
AC/DC 220-240V, 50-60Hz
For other voltages contact Sales
Battery
Ni-Cd 7.2V 4Ah battery in flameproof case
Auto cut out of defective light
Lumen output in emergency mode (1 tube lit):
40% at 18W, 33% at 36W
Battery duration: 18W = 2 hours, 36W = 2hours
Monitored by one LED
Operating in maintained mode (when the main
supply is connected: the tubes are lit, the battery
charges / when the main supply is off: the emergency
tube is lit and the battery does not recharge), or in
non-maintained mode (when the main supply is
connected: the tubes are not lit, the battery charges /
when the main supply is off: the emergency tube is
lit and the battery does not recharge)
Power factor
Up to 0.98
Cable entries
Standard: Three M20 cable entries included
Two M20 Nylon plugs (EX-M20)
One cable gland (EXCGM20S) - M20 Nylon for
non-armoured cable, diameter 6-12mm
For armoured cable - continuity plate option:
Nickel Plated Brass cable gland (EXN04MMC1),
diameter 6-12 / 8.5-16mm (1 or 2 according to
number of plates)
Terminal block
Up to 4mm² (rigid wire), 2.5mm² (flexible wire)
Select function: Lighting in maintained mode or
lighting in non-maintained mode
Supplied L1, N, PE, 1, 2 Terminals
Lamps (order separately)
Tube G13 bi-pin T8 Ø 26 coolwhite 4000°k
Spares & Fixings Accessories see pages 90-95
Related Products
59
EXB Conduit 138
Nylon Stopping
Plugs
176
XB100 Range 104
Exe Nylon Gland 168
www.tnb.com
A Member of the ABB Group
EVS-EMA Range
Emergency fluorescent fitting with
automatic test, and “BlackStart” capabilities
Approvals / Characteristics
Features
• Double central locking for ingress protection
• Main body constructed of a GRP for high impact strength
• Polycarbonate diffuser to resist harsh and
corrosive environments
• All components mounted on hinged and removable gear tray
• Battery duration 3 hours
• Automatic testing for preventive maintenance
• Clear LED for visual inspection
• Automatic switch off on opening for safe maintenance
• Possibility using the emergency inhibit mode
• Including accessories (cable gland & fixing brackets)
Certification & Standards
Approved to: EN60079-0, 60079-1, 60079-5, 60079-7, EN60079-31
EC TYPE Examination Certificate:
LCIE 11 ATEX 3065X
IEC Ex LCI 11.0053X
Ex II 2 G
Ex de IIC T4 Gb for ≤ -40ºC to ≤ +60ºC
Ex de IIC T5 Gb for ≤ -40ºC to ≤ +35ºC
Ex II 2 D
Ex tb IIIC T85ºC Db IP6X
Glow wire test: 960°C EN605988-2-22
Safe operating temperature range: -10°C to +40ºC
IP test: IP66 IEC 60529 (2001)
60
www.tnb-hazardous.com
Ex Emergency lighting - EVS-EMA Range
Technical Specifications
Dimensions
2 M8 holes
Depth 20
170
137
Wiring
Configuration
Rating (W)
Battery
Nominal
Current (A)
A
EVS120EMA-0000
3 / 5 Wire Loop
1 x 18
3h
0.09
785
432
400
7.5
EVS120EMA-D000
3 / 5 Wire & Continuity plate
1 x 18
3h
0.09
785
432
400
7.5
EVS140EMA-0000
3 / 5 Wire Loop
1 x 36
3h
0.17
1370
900
700
9.5
EVS140EMA-D000
3 / 5 Wire & Continuity plate
1 x 36
3h
0.17
1370
900
700
9.5
EVS220EMA-0000
3 / 5 Wire Loop
2 x 18
3h
0.17
785
432
400
8.5
EVS220EMA-D000
3 / 5 Wire & Continuity plate
2 x 18
3h
0.17
785
432
400
8.5
EVS240EMA-0000
3 / 5 Wire Loop
2 x 36
3h
0.33
1370
900
700
10.5
EVS240EMA-D000
3 / 5 Wire & Continuity plate
2 x 36
3h
0.33
1370
900
700
10.5
Type*
Dimensions (mm)
B
C
Weight (kg)
*Note: terminal blocks accept either 3 or 5 wire configurations (see instruction manual)
Enclosure
Fiberglass reinforced polyester body
Polycarbonate diffuser, treated against UV
Cable entries
Standard: Three M20 cable entries included
Two M20 Nylon plugs (EX-M20)
One cable gland (EXCGM20S) - ISO M20 Nylon for
non-armoured cable, diameter 6-12mm
For armoured cable - continuity plate option:
Nickel Plated Steel cable gland (EXN04MMC1),
diameter 6-12 / 8.5-16mm (1 or 2 according to
number of plates)
Fixing
Standard: V015 - 2 Zinc Plated Steel brackets for
ceiling mounting
Rated voltages
Standard: electronic ballast
AC/DC 220-240V, 50-60Hz
For other voltages contact Sales
Power factor
Up to 0.98
For wiring please refer to the instruction
manual (drawings)
Downloads available at tnb-hazardous.com
Battery
Ni-Cd 6V 4Ah for 18W /
Ni-Cd 6V 7Ah for 36W battery in flameproof case
Auto cut out of defective light
Lumen output in emergency mode (1 tube lit): 40%
at 18W, 33% at 36W
Battery duration: 3h max 36W
Operating in maintained mode (when the main
supply is connected: the tubes are lit, the battery
charges / when the main supply is off: the
emergency tube is lit and the battery does not
recharge), or in non-maintained mode (when the
main supply is connected: the tubes are not lit,
the battery charges / when the main supply is off:
the emergency tube is lit and the battery does
not recharge)
BlackStart
It is possible to wire the EVS-EMA in order to open
the fixture in ATEX zones in a completely powered
down mode (battery disconnected)
Normal mode: If main power is off, battery powers
emergency tube, main tubes are not lit
Disabled mode (terminals B S not connected,
usually via switch): Power off, battery is
disconnected, and neither main, nor emergency
tubes are lit
Preventive maintenance - Self test
- Battery charge - daily
- Emergency lamp during 1min - weekly
- Battery charge capacity during 1hr - quaterly
- Clear system test display
Battery charge monitored by 2 LED
Healthy
(test OK)
Emergency or
Test in
Indicator
Progress
Lamp Fault (waiting end
(must be
of test)
replaced)
Fault
(replace
battery)
Terminal block
Up to 4mm² (rigid wire), 2.5mm² (flexible wire)
Terminals supplied L1, L2, L3, LS, N, PE
Lamps (order separately)
Command must be supplied with switch on line
Tube G13 bi-pin T8 Ø 26 coolwhite 4000°k
Spares & Fixings Accessories see pages 90-95
Related Products
61
EXB Conduit 138
Nylon Stopping
Plugs
176
XB100 Range 104
Exe Nylon Gland 168
www.tnb.com
A Member of the ABB Group
EVN-EM Range
Emergency fluorescent fitting
Approvals / Characteristics
Features
•
•
•
•
Double central locking for ingress protection
Main body constructed of a GRP for high impact strength
Battery duration 2 hours
All components mounted on hinged and removable
gear tray which gives easy access for maintenance
• Including accessories (cable gland & fixing brackets)
• Option: automatic switch off on opening
Certification & Standards
Approved to: EN60079-0, 60079-15
EC TYPE Examination Certificate:
Ex II 3 G
Ex nR IIC T4 Gb for ≤ -40ºC to ≤ +60ºC
Ex nR IIC T6 Gb for ≤ -40ºC to ≤ +35ºC
Ex II 3 D
Ex tc IIIC T85°C Dc IP6X
Glow wire test: 960°C EN60598-2-22
Safe operating temperature range: -10°C to +40ºC
IP test: IP66 IEC 60529 (2001)
62
www.tnb-hazardous.com
Ex Emergency lighting - EVN-EM Range
Technical Specifications
Dimensions
2 M8 holes
Depth 20
170
137
Wiring
Configuration
Rating (W)
Battery
Nominal
Current (A)
A
5 Wire Loop
1 x 18
2h
0.09
785
432
400
EVN120EM-D000 5 Wire Loop & Continuity plate
1 x 18
2h
0.09
785
432
400
6.5
EVN140EM-0000
1 x 36
2h
0.17
1370
900
700
8.5
Type
EVN120EM-0000
5 Wire Loop
Dimensions (mm)
B
C
Weight (kg)
6.5
EVN140EM-D000 5 Wire Loop & Continuity plate
1 x 36
2h
0.17
1370
900
700
8.5
EVN220EM-0000
2 x 18
2h
0.17
785
432
400
7.5
5 Wire Loop
EVN220EM-D000 5 Wire Loop & Continuity plate
2 x 18
2h
0.17
785
432
400
7.5
EVN240EM-0000
2 x 36
2h
0.33
1370
900
700
10.5
2 x 36
2h
0.33
1370
900
700
10.5
5 Wire Loop
EVN240EM-D000 5 Wire Loop & Continuity plate
*EVN...EM-.0C0 Automatic switch off on opening (to complete with wiring configuration)
Enclosure
Fibreglass reinforced polyester body
Polycarbonate diffuser, treated against UV
Fixing
Standard: V015 - 2 Zinc Plated Steel brackets for
ceiling mounting
For wiring, please refer to the instruction
manual (drawings)
Technical assistance on request
Rated voltages
Standard: electronic ballast
AC/DC 220-220V, 50-60Hz
Battery
Ni-Cd 7.2V 4Ah battery
Lumen output in emergency mode (1 tube lit)
40% at 18W, 33% at 36W
Monitored by one LED:
1. operating in maintained mode;
- when the main supply is connected: the tubes
are lit, the battery charges
- when the main supply is off : the emergency
tube is lit and the battery does not recharge
2. Operating in non maintained mode;
- when the main supply is conneted : the tubes
are not lit, the battery charges
- when the main supply is off: the emergency
tube is lit and the battery does not recharge
Power factor
Up to 0.98
Cable entries
Standard: Three M20 cable entries included
Two M20 Nylon plugs (EX-M20)
One cable gland (EXCGM20S) - ISO M20 Nylon for
non-armoured cable, diameter 6-12mm
For armoured cable - continuity plate option:
Nickel Plated Brass cable gland (EXN04MMC1),
diameter 6-12 / 8.5-16mm
Terminal block
Up to 4mm² (rigid wire), 2.5mm² (flexible wire)
Select function: Lighting in maintained mode or
lighting in non-maintained mode
Terminal block supplied: N, PE, L1, L2, L3, LS
(Looping possible with additional cable gland)
Lamps (order separately)
Tube G13 bi-pin T8 Ø 26 coolwhite 4000°k
EMA version available upon request
(with automatic test) - similar to EVS-EMA
Spares & Fixings Accessories see pages 90-95
Related Products
63
EXB Conduit 138
Nylon Stopping
Plugs
176
XB100 Range 104
Exe Nylon Gland 168
www.tnb.com
A Member of the ABB Group
EVD-EM Range
Emergency fluorescent fitting
Approvals / Characteristics
Features
• Double central locking for ingress protection
• Main body constructed of a GRP for high impact strength
• Polycarbonate diffuser to resist harsh and
corrosive environments
• All components mounted on hinged and removable gear tray
which gives easy access for installation and maintenance
• Battery duration 2 hours
• Including accessories (cable gland & fixing brackets)
• Option: automatic switch off on opening
Certification & Standards
4
64
www.tnb-hazardous.com
Approved to: EN60079-0, 60079-31
EC TYPE Examination Certificate: Under new 94/9/EC self certified
LCIE II ATEX 3092X
IECEx LCI 11.0064X
Ex t IIIC T82ºC (≤ +60ºC) Db
Ex t IIIC T62ºC (≤ +40ºC) Db
Glow wire test: 960°C EN60598-2-22
Safe operating temperature range: -10°C to +40ºC
IP test: IP66 IEC 60529 (2001)
Ex Emergency lighting - EVD-EM Range
Technical Specifications
Dimensions
2 M8 holes
Depth 20
170
137
Wiring
Configuration
Rating (W)
Battery
Nominal
Current (A)
A
5 Wire Loop
1 x 18
2h
0.09
785
432
400
EVD120EM-D0J0 5 Wire Loop & Continuity plate 1 x 18
2h
0.09
785
432
400
6.5
EVD140EM-00J0
1 x 36
2h
0.17
1370
900
700
8.5
EVD140EM-D0J0 5 Wire Loop & Continuity plate 1 x 36
2h
0.17
1370
900
700
8.5
EVD220EM-00J0
2 x 18
2h
0.17
785
432
400
7.5
EVD220EM-D0J0 5 Wire Loop & Continuity plate 2 x 18
2h
0.17
785
432
400
7.5
EVD240EM-00J0
2 x 36
2h
0.33
1370
900
700
10.5
EVD240EM-D0J0 5 Wire Loop & Continuity plate 2 x 36
2h
0.33
1370
900
700
10.5
Type
EVD120EM-00J0
5 Wire Loop
5 Wire Loop
5 Wire Loop
Dimensions (mm)
B
C
Weight (kg)
6.5
*EVD...EM-.0C0 Automatic switch off on opening (to complete with wiring configuration)
Enclosure
Fiberglass reinforced polyester body
Polycarbonate diffuser, treated against UV
Fixing
Standard: V015 - 2 Zinc Plated Steel brackets for
ceiling mounting
For wiring, please refer to the instruction
manual (drawings)
Technical assistance on request
Rated voltages
Standard: dual tube electronic ballast
AC/DC 220-240V, 50-60Hz
Battery
Ni-Cd 7.2V 4Ah
Lumen level in emergency mode (1 tube lit):
40% at 18W, 33% at 36W
Battery duration in emenrgency mode: 2 hours
Battery charge monitored by one LED
Operating in maintained mode (when the main
supply is connected: the tubes are lit, the battery
charges / when the main supply is off: the emergency
tube is lit and the battery does not recharge), or in
non-maintained mode (when the main supply is
connected: the tubes are not lit, the battery charges /
when the main supply is off: the emergency tube is
lit and the battery does not recharge)
Power factor
Up to 0.98
Cable entries
Standard: Three M20 cable entries included
Two M20 Nylon plugs (EX-M20)
One cable gland (EXCGM20S) - M20 Nylon for
non-armoured cable, diameter 6-12mm
For armoured cable - continuity plate option:
Nickel Plated Brass cable gland (EXN04MMC1),
diameter 6-12 / 8.5-16mm
Terminal block
Up to 4mm² (rigid wire), 2.5mm² (flexible wire)
Terminals supplied for N, PE, L1, L2, L3, LS
Select function: Lighting in maintained mode or
lighting in non-maintained mode
Lamps (order separately)
Tube G13 bi-pin T8 Ø 26 coolwhite 4000°k
EMA version available upon request
(with automatic test) - similar to EVS-EMA
Spares & Fixings Accessories see pages 90-95
Related Products
65
EXB Conduit 138
Nylon Stopping
Plugs
176
XB100 Range 104
Exe Nylon Gland 168
www.tnb.com
A Member of the ABB Group
ESB-EM Range
Recessed emergency fluorescent fitting
Approvals / Characteristics
Features
• Main body made from powder coated steel
• 6mm toughened glass making it perfect
for laboratories
• Automatic switch off upon opening
for safe maintenance
• Battery duration 2 hours
• Including accessories (cable gland)
Certification & Standards
Approved to: EN60079-0, 60079-1, 60079-7
EC TYPE Examination Certificate: Under 94/9/EC
INERIS II ATEX 0058X
Ex II 2 G
Ex de IIC T4 Gb for ≤ -40ºC to ≤ +60ºC
Glow wire test: 850°C EN60598-2-22
Safe operating temperature range: -10°C to +40ºC
IP test: IP66 IEC 60529 (2001)
66
www.tnb-hazardous.com
Ex Emergency lighting - ESB-EM Range
Technical Specifications
Dimensions
240
240
Wiring
Configuration
Rating (W)
Battery
Nominal
Current (A)
Glass
A
ESB240EM-0000
5 Wire Loop
2 x 36
2h
0.33
Toughened
1364
1312
105
22
ESB240EM-A000
5 Wire Loop
2 x 36
2h
0.33
Frosted
1364
1312
105
22
Type
Enclosure
Steel housing and body painted in white polyester
powderpaint RAL 9016
6mm clear toughened glass panel (optional frosted
low lumen output)
Neoprene gasket
For wiring, please refer to the instruction
manual (drawings)
Technical assistance on request
Rated voltages
Standard: electronic ballast:
AC/DC 220-240V, 50-60Hz
Battery
Ni-Cd 7.2V 4Ah battery in flameproof case
Lumen level in emergency mode (1 tube lit): 33%
Emergency load duration: 2 hours
Battery change monitored by LED
Operating in maintained mode (when the main
supply is connected: the tubes are lit, the battery
charges / when the main supply is off: the emergency
tube is lit and the battery does not recharge), or in
non-maintained mode (when the main supply is
connected: the tubes are not lit, the battery charges /
when the main supply is off: the emergency tube is
lit and the battery does not recharge)
Power factor
Up to 0.98
Cable entries
Standard: Two M20 cable entries included
One M20 Nylon plug (EX-M20)
One cable gland (EXCGM20S) - M20 Nylon for
non-armoured cable, diameter 6-12mm
Dimensions (mm)
B
C
Weight (kg)
Terminal block
Up to 4mm² (rigid wire), 2.5mm² (flexible wire)
Terminals supplied N, PE, L1, 1, 2
Select function: Lighting in maintained mode or
lighting in non-maintained mode
Lamps (order separately)
Tube G13 bi-pin T8 Ø 26 coolwhite 4000°k
Fixing
Fixing by 4 M6 threaded bolts (not supplied) joined
to the main body
Spares & Fixings Accessories see pages 90-95
Related Products
67
EXB Conduit 138
Nylon Stopping
Plugs
176
XB100 Range 104
Exe Nylon Gland 168
www.tnb.com
A Member of the ABB Group
Industrial Lighting Non-Hazardous locations
68
26
www.tnb-hazardous.com
Industrial Lighting - Non-Hazardous Locations
69
www.tnb.com
A Member of the ABB Group
FF Range
Weatherproof tubular fluorescent fitting
Approvals / Characteristics
Features
• Ingress protection IP66 ideal for wash down areas
• All components mounted on a removable gear tray which
gives easy access for installation and maintenance
• Tubular shape to avoid waste accumulation
• Including accessories (cable gland & fixing brackets)
Technical Data
Glow wire test: 960°C EN60598-2-22
Safe operating temperature range: -20°C to +50ºC
IP test: IP66 IEC 60529 (2001)
70
www.tnb-hazardous.com
Industrial Lighting - FF Range
Technical Specifications
Dimensions
Wiring
Configuration
Diffuser
Nominal
Rating (W)
Current (A)
FR120-0G000
5 Wire
Polycarbonate
1 x 18
0.15
780
565
4
FR136-0G000
5 Wire
Polycarbonate
2 x PL36
0.2
780
565
4.5
FR140-0G000
5 Wire
Polycarbonate
1 x 36
0.2
1385
1170
7
FR155-0G000
5 Wire
Polycarbonate
1 x PL55
0.35
780
565
4.5
FR165-0G000
5 Wire
Polycarbonate
1 x 58
0.35
1690
1475
8
FF220-0G000
5 Wire
Polycarbonate
2 x 18
0.3
780
565
4.5
FF236-0G000
5 Wire
Polycarbonate
2 x PL36
0.4
780
565
5
FF240-0G000
5 Wire
Polycarbonate
2 x 36
0.4
1385
1170
7
FF255-0G000
5 Wire
Polycarbonate
2 x PL55
0.7
780
565
5
FF265-0G000
5 Wire
Polycarbonate
2 x 58
0.7
1690
1475
9
Type
Enclosure
Reinforced black polycarbonate end caps
UV protected extruded polycarbonate tube,
thickness 2.5mm
Temperature
Ambient temperature: -20°C to +50°C
Fixing
Standard: D023 - 2 Zinc Plated Steel articulated
brackets for ceiling mounting
Rated voltages
Electronic ballast: AC/DC 110-260V, 50-60Hz
Power factor
Up to 0.98
Cable entries
Standard: Two M20 entries included
One plug (EX-M20)
One cable gland (EXCGM20S) - M20 Nylon for
non-armoured cable, diameter 6-12mm
Dimensions (mm)
A
B
Weight (kg)
Terminal block (plug in terminal block)
Up to 10mm2 (rigid wire), 6mm2 (flexible wire)
Standard: terminals supplied for L1, L2, L3, N, PE
Looping possible with additional cable gland
Lamps (order separately)
T8 bi-pin G13 tube, Ø 26 - white industry 4000°K
G11 compact fluorescent PL lamp
Spares & Fixings Accessories see pages 90-95
Related Products
71
EXB Conduit 138
Nylon Stopping
Plugs
176
XB100 Range 104
Exe Nylon Gland 168
www.tnb.com
A Member of the ABB Group
EL Range
Weatherproof miniature tubular fluorescent fitting
Approvals / Characteristics
Features
• Small and compact for confined spaces
• Ingress protection IP66 ideal for wash down areas
• All components mounted on a removable gear tray which
gives easy access for installation and maintenance
• Tubular shape to avoid waste accumulation
• Including accessories (cable gland & fixing brackets)
Technical Data
Glow wire test: 960°C EN60598-2-22
Safe operating temperature range: -20°C to +50ºC
IP test: IP66 IEC 60529 (2001)
72
www.tnb-hazardous.com
Industrial Lighting - EL Range
Technical Specifications
Dimensions
Wiring
Configuration
Diffuser
Nominal
Rating (W)
Current (A)
EL3008-0G000
5 Wire
Polycarbonate
1x8
0.1
455
240
EL3009-0G000
5 Wire
Polycarbonate
1 x PL9
0.1
455
240
3
EL30011-0G000
5 Wire
Polycarbonate
1 x PL11
0.1
455
240
3.5
3.5
Type
Dimensions (mm)
A
B
Weight (kg)
3
EL120-0G000
5 Wire
Polycarbonate
1 x PL18
0.3
455
240
EL220-0G000
5 Wire
Polycarbonate
2 x PL18
0.5
455
240
4
EL30028-0G000
5 Wire
Polycarbonate
2x8
0.1
455
240
3.5
Enclosure
Reinforced black polycarbonate end caps
LEXAN 2034 UV protected extruded polycarbonate
tube, thickness 2.5mm
Neoprene gasket
Temperature
Ambient temperature: -20°C to +50°C
Fixing
Standard: D023 - 2 Zinc Plated Steel articulated
brackets for ceiling mounting
Rated voltages
Standard:
Electronic ballast: AC/DC 220-240V, 50/60Hz
Power factor
Up to 0.98
Cable entries
Standard: Two M20 entries included
One plug (EX-M20)
One cable gland (EXCGM20S) - M20 Nylon for
non-armoured cable, diameter 6-12mm
Terminal block (plug in terminal block)
Up to 10mm2 (rigid wire), 6mm2 (flexible wire)
Standard terminals supplied for L1,L2,L3, N, PE
Looping possible with additional cable glands
Lamps (order separately)
T8 bi-pin G13 tube, Ø 26 - white industry 4000°K
G11 compact fluorescent PL lamp
Lamp with G11 base (18W)
or G23 (7W, 9W, 11W)
Spares & Fixings Accessories see pages 90-95
Related Products
73
EXB Conduit 138
Nylon Stopping
Plugs
176
XB100 Range 104
Exe Nylon Gland 168
www.tnb.com
A Member of the ABB Group
SF / QF / EF Range
Weatherproof floodlight fitting
Approvals / Characteristics
Features
• Compact, lightweight and robust ideal for lighting
large areas
• Integral junction box: rapid installation
• Excellent photometric properties, wide or narrow beam
• Including accessories (cable gland & lamps installed)
• Supplied with offshore grade paint
Technical Data
IP test: IP66 IEC 60529 (2001)
74
www.tnb-hazardous.com
Industrial Lighting - SF / QF / EF Range
Technical Specifications
Dimensions
Standard Flat
Pole Mounting
Nominal
Rating (W)
Current (A)
Mounting
Weight (kg)
SF70P-00000
1 x 70 HP Sodium
0.4
Flat
17
SF70G-00000
1 x 70 HP Sodium
0.4
Pole
17
SF150P-00000
1 x 150 HP Sodium
0.8
Flat
17
SF150G-00000
1 x 150 HP Sodium
0.8
Pole
17
SF250P-00000
1 x 250 HP Sodium
1.3
Flat
18
SF250G-00000
1 x 250 HP Sodium
1.3
Pole
18
SF400P-00000
1 x 400 HP Sodium
2.1
Flat
20
SF400G-00000
1 x 400 HP Sodium
2.1
Pole
20
QF250P-00000
1 x 250 Metal Halide
1.3
Flat
18
QF250G-00000
1 x 250 Metal Halide
1.3
Pole
18
QF400P-00000
1 x 400 Metal Halide
2.1
Flat
20
QF400G-00000
1 x 400 Metal Halide
2.1
Pole
20
EF110P-00000
2 x 55 Halogen 12V
9.2
Flat
13
EF110G-00000
2 x 55 Halogen 12V
9.2
Pole
13
EF140P-00000
2 x 70 Halogen 24V
5.8
Flat
13
EF140G-00000
2 x 70 Halogen 24V
5.8
Pole
13
Type*
*Option: ...F... -0A000 (to complete with nominal rating & mounting) - Narrow beam, for example: SF400P-0A000
Enclosure
Marine grade aluminium alloy type according to
EN1706:EN AC-AlSi7 Mg 0,6 T6
Cataphoretically treated
12mm toughened glass
Stainless steel screws
Temperature
Ambient temperature: -20°C to +60°C
Rated voltages
Standard: 230V 50Hz ferromagnetic ballast,
with capacitor
Option: 220V 60Hz ferromagnetic ballast
or 120V 60Hz on few models, ferromagnetic
ballast
Power factor
Up to 0.85 for version with compensated ballast
(Sodium HP and metal halide)
Cable entries
Standard: Two M20 entries included
One M20 Nickel Plated Brass plug (EXN/M20/SP)
One cable gland (EXN04MMC2) - Nickel Plated
Brass M20 for non-armoured cable,
diameter 10-16mm
Lamps (Installed)
Polished aluminium reflector
Standard: wide beam
Option: narrow beam
Other options
Sling (SC100 ELINGUE)
Galvanised steel support with base plate (SA103)
Pre wired masthead floodlighting systems: Full system
with 2 or 4 floodlights (to complete with nominal
rating), for example HM 4400 (4 x 400 W HPS)
(See photo on XF Range)
Terminal block
Up to 6mm² (rigid wire), 4mm² (flexible wire)
Terminals supplied: L, N, PE
Fixing
Standard:galvanised steel flat mounting bracket,
Pole mounted: Ø 40 to 60mm
Colour (standard)
SF/QF/EF***-00000 - Yellow offshore, RAL 1003
Colour options
SF/QF/EF***-B0000 - Grey, RAL 7035
SF/QF/EF***-C0000 - Black, RAL 9004
SF/QF/EF***-D0000 - Hammered Blue, RAL 5015
SF/QF/EF***-F0000 - Red, RAL 3001
SF/QF/EF***-G0000 - Blue, RAL 5010
SF/QF/EF***-J0000 - Green, RAL 6032
SF/QF/EF***-M0000 - White, RAL 9010
•
•
•
•
•
•
•
Spares & Fixings Accessories see pages 90-95
Related Products
75
EXB Conduit 138
Stopping Plugs 174
XB100 Range 104
Ex e Cable
Gland
166
www.tnb.com
A Member of the ABB Group
EVT Range
Weatherproof fluorescent fitting with diffuser
Approvals / Characteristics
Features
• Double central locking for ingress protection
• Including accessories (cable gland & fixing brackets)
• Option: automatic switch off on opening
Technical Data
Glow wire test: 960°C EN60598-2-22
Safe operating temperature range: -20°C to +50ºC
IP test: IP66 IEC 60529 (2001)
76
www.tnb-hazardous.com
Industrial Lighting - EVT Range
Technical Specifications
Dimensions
2 M8 holes
Depth 20
170
137
Wiring
Configuration
Rating (W)
Nominal
Current (A)
A
EVT120-A0J0
5 Wire Loop
1 x 18
0.09
785
432
400
4.2
EVT120-D0J0
5 Wire Loop & Continuity plate
1 x 18
0.09
785
432
400
4.2
EVT140-A0J0
5 Wire Loop
1 x 36
0.17
1370
900
700
6.5
EVT140-D0J0
5 Wire Loop & Continuity plate
1 x 36
0.17
1370
900
700
6.5
EVT165-A0J0
5 Wire Loop
1 x 58
0.26
1670
900
700
8
EVT165-D0J0
5 Wire Loop & Continuity plate
1 x 58
0.26
1670
900
700
8
EVT220-A0J0
5 Wire Loop
2 x 18
0.17
785
432
400
4.5
EVT220-D0J0
5 Wire Loop & Continuity plate
2 x 18
0.17
785
432
400
4.5
EVT240-A0J0
5 Wire Loop
2 x 36
0.33
1370
900
700
6
EVT240-D0J0
5 Wire Loop & Continuity plate
2 x 36
0.33
1370
900
700
6
EVT265-A0J0
5 Wire Loop
2 x 58
0.5
1670
900
700
8.5
EVT265-D0J0
5 Wire Loop & Continuity plate
2 x 58
0.5
1670
900
700
8.5
Type*
Dimensions (mm)
B
C
Weight (kg)
*(Through options) Define type rating (to complete with rating): EVT...-B0J0 5 Wires through, EVT...-E0J0 with two continuity plates,
EVT...-.0C0 Automatic switch off on opening (to complete with wire configuration)
Enclosure
Fiberglass reinforced polyester body
Polycarbonate diffuser, treated against UV
Temperature
Ambient temperature: -20ºC to +50ºC
Fixing
Standard: V015 - 2 Zinc Plated Steel brackets for
ceiling mounting
Rated voltages
Standard electronic ballast:
AC/DC 110-260V , 50-60Hz
Power factor
Up to 0.98
Cable entries
Standard: Three M20 cable entries included
Two M20 Nylon plug (EX-M20)
One cable gland (EXCGM20S) - M20 Nylon for
non-armoured cable, diameter 6-12mm
For armoured cable - continuity plate option:
Nickel Plated Brass cable gland (EXN04MMC1),
diameter 6-12 / 8.5-16mm (1 or 2 according to
number of plates)
Terminal block
Up to 6mm² (rigid wire), 4mm² (flexible wire)
Standard: Terminals supplied for L1, L2, L3, N, PE
Looping possible with additional cable glands
5 wire through option I MAX =16A max
Lamps (order separately)
T8 bi-pin G13 tube, Ø 26 - cool white 4000°K
Spares & Fixings Accessories see pages 90-95
Related Products
77
EXB Conduit 138
Nylon Stopping
Plugs
176
XB100 Range 104
Exe Nylon Gland 168
www.tnb.com
A Member of the ABB Group
EST Range
Weatherproof recessed fluorescent fitting
Approvals / Characteristics
Features
• Fitting combines photometric qualities, strength
and design
• Including accessories (cable gland)
Technical Data
Glow wire test: 960°C EN60598-2-22
Safe operating temperature range: -20°C to +50ºC
IP test: IP64 IEC 60529 (2001)
78
www.tnb-hazardous.com
Industrial Lighting - EST Range
Technical Specifications
Dimensions
240
240
Wiring
Configuration
Rating (W)
Glass
Nominal
Current (A)
A
EST220-00J0
5 Wire Loop
2 x 18
Toughened
0.17
753
702
105
12.5
EST220-A0J0
5 Wire Loop
2 x 18
Frosted
0.17
753
702
105
12.5
EST240-00J0
5 Wire Loop
2 x 36
Toughened
0.33
1364
1312
105
20
EST240-A0J0
5 Wire Loop
2 x 36
Frosted
0.33
1364
1312
105
20
EST265-00J0
5 Wire Loop
2 x 58
Toughened
0.5
1664
1612
105
25
EST265-A0J0
5 Wire Loop
2 x 58
Frosted
0.5
1664
1612
105
25
Type
Enclosure
Steel housing and body painted in white polyester
powder paint RAL 9016 (stainless steel 304L on
request)
6mm clear toughened glass panel (optional frosted
low lumen output)
Temperature
Operating temperature range: -20°C to +40°C
Rated voltages
Standard: electronic ballast
AC/DC 110-260V, 50-60Hz
Power factor
Up to 0.98
Cable entries
Standard: Two M20 cable entries included
One M20 Nylon plug (EX-M20)
One cable gland (EXCGM20S) - ISO M20 Nylon for
non-armoured cable, diameter 6-12mm
Dimensions (mm)
B
C
Weight (kg)
Terminal block
Up to 4mm² (rigid wire), 2.5mm² (flexible wire)
Terminals supplied L1, L2, L3, N, PE
Lamps (order separately)
Tube G13 bi-pin T8 Ø 26 coolwhite 4000°k
Fixing
Fixing by 4 M6 threaded bolts (not supplied) joined
to the main body
Spares & Fixings Accessories see pages 90-95
Related Products
79
EXB Conduit 138
Nylon Stopping
Plugs
176
XB100 Range 104
Exe Nylon Gland 168
www.tnb.com
A Member of the ABB Group
FB / FL Range
Weatherproof warning lights and beacons
Approvals / Characteristics
Features
• Lightweight and robust for easy installation
• Static or flashing versions available for use in a
variety of applications
• Choice of 5 colours of globe
• 2 or 3 light versions available for traffic signals
• Including accessories (cable gland, plug & lamp installed)
Technical Data
IP test: IP66 IEC 60529 (2001)
80
www.tnb-hazardous.com
Industrial Lighting - FB / FL Range
Technical Specifications
8
Dimensions
Contact Sales for Mounting Options
Type
Rating (W)
Lamp
Standard Globe*
Version
Rated Voltages
FB30-00000
1 x 28
E27
Red
Halogen
AC 230V 50/60Hz
Weight (kg)
3.5
FB70-00000
1x8
E27
Red
LED
AC 100-240V 50/60Hz
3.5
FL30P-00000
30 Joules
Picots
Red
Xenon flash
AC 230V 50/60Hz
4
FL30P-0C000
30 Joules
Picots
Red
Xenon flash
AC 100V 50/60Hz
4
FL30P-0D000
30 Joules
Picots
Red
Xenon flash
DC 24V
4
FL30P-0E000
30 Joules
Picots
Red
Xenon flash
DC 48V
4
FL30P-0F000
30 Joules
Picots
Red
Xenon flash
DC 110V
4
*Choice of globe colours: XF...-00000 - Red, XF...-000A0 - Transparent globe, XF...-000B0 - Green globe, XF...-000C0 - Orange globe, XF...-000D0 - Blue globe
**For colour combinations: Colour combination: please contact Sales for more information
Enclosure
Marine grade aluminium alloy type
EN1706 AC-43100KF-AlSi 10Mg
Aluminium reflector
Temperature
Ambient temperature: -20°C to +60°C
Cable entries
Standard: Two entries M20 included
One M20 nickel plated brass plug (EXN/M20/SP) and
one cable gland (EXN04MMC2) - Nickel Plated Brass
ISO M20 for non-armoured cable, diameter 10-16mm
Terminal block
Up to 6mm2
Terminals supplied for L, N, PE
Lamps (supplied)
For xenon flash versions
Flashing rate: 45 to 60 - per minute
Globe
Polycarbonate, thickness 3mm
Colour (standard)
FB/FL***-00000 - Yellow offshore, RAL 1003
•Colour
options
- Grey, RAL 7035
• FB/FL***-B0000
- Black, RAL 9004
• FB/FL***-C0000
- Hammered Blue, RAL 5015
• FB/FL***-D0000
FB/FL***-F0000
RAL 3001
• FB/FL***-G0000 -- Red,
RAL 5010
• FB/FL***-J0000 - Blue,
RAL 6032
• FB/FL***-M0000 - Green,
White, RAL 9010
Spares & Fixings Accessories see pages 90-95
Related Products
81
EXB Conduit 138
Stopping Plugs 176
XB100 Range 104
Ex e Cable
Gland
166
www.tnb.com
A Member of the ABB Group
HF Range
Portable floodlight
Approvals / Characteristics
Features
• Lightweight and robust
• Free standing on base plate for stable use
in high winds
• Fully portable with carrying handle
• Including accessories (cable gland & lamp installed)
Technical Data
IP test: IP66 IEC 60529 (2001)
82
www.tnb-hazardous.com
Industrial Lighting - HF Range
Technical Specifications
Dimensions
Rating (W)
Lamp
Power Supply (V)
Nominal
Current (A)
Weight (kg)
HF55P-00000
55
Halogen H3
12
4.6
6
HF70P-00000
70
Halogen H3
24
2.9
6
Type
Enclosure
Marine grade aluminium alloy
Globe: 3mm thick transparent polycarbonate
Temperature
Ambient temperature: -20°C to +60°C
Cable entries
One M20 entry included
One cable gland (EXN04MMC2) - ISO M20 Nickel
Plated Brass for non-armoured cable,
diameter 10-16mm
Terminal block
Up to 6mm2
Terminals supplied L, N, PE
Lamps (supplied)
70W - 24V iodine lamp - H3 lampholder
55W - 12V iodine lamp - H3 lampholder
Fixing (including)
Galvanised steel support with base plate ref. SA103
Spares & Fixings Accessories see pages 90-95
Related Products
83
EXL Conduit 148
Stopping Plugs 176
GUV Range
120
Ex e Cable
Gland
166
www.tnb.com
A Member of the ABB Group
FR-EM / FF-EM Range
Emergency weatherproof tubular fluorescent fitting
Approvals / Characteristics
Features
• Ingress protection IP66 ideal for wash down areas
• All components mounted on removable gear tray which
gives easy access for installation and maintenance
• Battery 2h duration
• Tubular shape to avoid waste accumulation
• Including accessories, cable gland & fixing brackets
Technical Data
Glow wire test: 960°C EN60598-2-22
Safe operating temperature range: -20°C to +40ºC
84
www.tnb-hazardous.com
Industrial Emergency Lighting - FR-EM / FF-EM Range
Technical Specifications
Dimensions
Wiring
Configuration
Diffuser
Rating (W)
Nominal
Current (A)
Battery
FR120EM-0G000
3 Wire
Polycarbonate
1 x 18
0.15
2h
780
565
FR140EM-0G000
3 Wire
Polycarbonate
1 x 36
0.2
2h
1385
1170
8
FF220EM-0G000
3 Wire
Polycarbonate
2 x 18
0.2
2h
780
565
5.5
FF240EM-0G000
3 Wire
Polycarbonate
2 x 36
0.35
2h
1385
1170
8
Type
Enclosure
Reinforced black polycarbonate end caps
UV protected extruded polycarbonate tube,
thickness 2.5mm
Temperature
Ambient temperature: -10°C to +40°C
Fixing
Standard: D023 - 2 Zinc Plated Steel articulated
brackets for ceiling mounting
For wiring, please refer to the instruction
manual (drawings)
Technical assistance on request
Power Factor
Up to 0.98
Rated voltages
Electronic ballast: AC/DC 220-240V, 50-60Hz
Battery
Ni-Cd battery 7.2V, 4Ah
Lumen output in emergency mode (1 tube lit):
40% for 8W, 33% for 36W
Battery duration in emergency mode: 2 hours
Monitored by one LED
Operating in maintained mode (when the main
supply is connected: the tubes are lit, the battery
charges / when the main supply is off: the emergency
tube is lit and the battery does not recharge), or in
non-maintained mode (when the main supply is
connected: the tubes are not lit, the battery charges /
when the main supply is off: the emergency tube is
lit and the battery does not recharge)
Cable entries
Standard: Two M20 entries included
One cable gland (EXCGM20S) - ISO M20 Nylon for
non-armoured cable, diameter 6-12mm
One Nylon plug (EXM20)
Dimensions (mm)
A
B
Weight (kg)
5
Terminal block (plug in terminal block)
Terminals supplied: L1,2,N, PE
Up to 10mm2 (rigid wire), 6mm2 (flexible wire)
Standard: terminals supplied for L1, 2, N, PE
Looping possible with additional cable gland
Lamps (order separately)
T8 bi-pin G13 tube, Ø 26 - white industry 4000°K
Spares & Fixings Accessories see pages 90-95
Related Products
85
EXB Conduit 138
Nylon Stopping
Plugs
176
XB100 Range 104
Exe Nylon Gland 168
www.tnb.com
A Member of the ABB Group
EVT-EM Range
Emergency weatherproof fluorescent fitting with diffuser
Approvals / Characteristics
Features
• Double central locking for ingress protection
• Battery duration 2 hours
• Included accessories (cable gland & fixing brackets)
• Option: automatic switch off on opening
Technical Data
Glow wire test: 960°C EN60598-2-22
Safe operating temperature range: -10°C to +40ºC
IP test: IP66 IEC 60529 (2001)
86
www.tnb-hazardous.com
Industrial Emergency Lighting - EVT-EM Range
Technical Specifications
Dimensions
2 M8 holes
Depth 20
170
137
Wiring
Configuration
Rating (W)
Battery
Nominal
Current (A)
A
EVT120EM-00J0
5 Wire
1 x 18
2h
0.09
785
432
400
6.5
EVT120EM-D0J0
5 Wire & Continuity plate
1 x 18
2h
0.09
785
432
400
6.5
EVT140EM-00J0
5 Wire
1 x 36
2h
0.17
1370
900
700
8.5
EVT140EM-D0J0
5 Wire & Continuity plate
1 x 36
2h
0.17
1370
900
700
8.5
EVT220EM-00J0
5 Wire
2 x 18
2h
0.17
785
432
400
7.5
EVT220EM-D0J0
5 Wire & Continuity plate
2 x 18
2h
0.17
785
432
400
7.5
EVT240EM-00J0
5 Wire
2 x 36
2h
0.33
1370
900
700
10.5
EVT240EM-D0J0
5 Wire & Continuity plate
2 x 36
2h
0.33
1370
900
700
10.5
Type*
Dimensions (mm)
B
C
Weight (kg)
*(Through options) EVT...-.0C0 Automatic switch off on opening (to complete with wire configuration)
Enclosure
Fiberglass reinforced polyester body
Polycarbonate diffuser, treated against UV
Temperature
Ambient temperature: -10ºC to +40ºC
Fixing
Standard: V015 - 2 Zinc Plated Steel brackets for
ceiling mounting
For wiring, please refer to the instruction
manual (drawings)
Technical assistance on request
Rated voltages
Electronic ballast: AC/DC 220-240V, 50-60Hz
Battery
Ni-Cd 7.2V 4Ah
Lumen level in emergency mode (1 tube lit):
40% for 18W, 33% for 36W
Battery duration in emergency mode:
2 hours
Battery charge monitored by LED
Operating in maintained mode (when the main
supply is connected: the tubes are lit, the battery
charges / when the main supply is off: the emergency
tube is lit and the battery does not recharge), or in
non-maintained mode (when the main supply is
connected: the tubes are not lit, the battery charges /
when the main supply is off: the emergency tube is
lit and the battery does not recharge)
Power factor
Up to 0.98 with electronic ballast
Cable entries
Standard: Three M20 cable entries included
Two M20 Nylon plugs (EX-M20)
One cable gland (EXCGM20S) - M20 Nylon for
non-armoured cable, diameter 6-12mm
For armoured cable - continuity plate option:
Nickel Plated Brass cable gland (EXN04MMC1),
diameter 6-12 / 8.5-16mm (1 or 2 according to
number of plates)
Terminal block (plug in terminal block)
Up to 6mm² (rigid wire), 4mm² (flexible wire)
Terminals supplied : L1, L2, L3, N, PE, LS
Select function: Lighting in maintained mode or
lighting in non-maintained mode
Lamps (order separately)
T8 bi-pin G13 tube, Ø 26 - cool white 4000°K
EMA version available upon request
(with automatic test) - similar to EVS-EMA
Spares & Fixings Accessories see pages 90-95
Related Products
87
EXB Conduit 138
Ex d Cable
Gland
162
XB100 Range 104
Exe Nylon Gland 168
www.tnb.com
A Member of the ABB Group
EST-EM Range
Emergency weatherproof recessed fluorescent fitting
Approvals / Characteristics
Features
• Fitting combines photometric qualities, strength
and design
• Battery duration 2 hours
• Included accessories (cable gland)
Technical Data
Glow wire test: 850°C EN60598-2-22
Safe operating temperature range: -10°C to +40ºC
IP test: IP66 IEC 60529 (2001)
88
www.tnb-hazardous.com
Industrial Emergency Lighting - EST-EM Range
Technical Specifications
Dimensions
240
240
Wiring
Configuration
Rating (W)
Battery
Nominal
Current (A)
Glass
A
EST240EM-00J0
5 Wire
2 x 36
2h
0.33
Toughened
1364
1312
105
22
EST240EM-A0J0
5 Wire
2 x 36
2h
0.33
Frosted
1364
1312
105
22
Type
Enclosure
Steel housing and body painted in white polyester
powder paint RAL 9016
6mm clear toughened glass panel (optional frosted
low lumen output)
Temperature
Operating temperature range:
-10°C to +40°C
For wiring, please refer to the instruction
manual (drawings)
Technical assistance on request
Rated voltages
Electronic ballast:
Standard: AC/DC 220-240V, 50-60Hz
Battery
Ni-Cd 7.2V 4Ah
Lumen level in emergency mode (1 tube lit): 33%
Emergency load duration: 2 hours
Battery charge monitored by LED
Operating in maintained mode (when the main
supply is connected: the tubes are lit, the battery
charges / when the main supply is off: the emergency
tube is lit and the battery does not recharge), or in
non-maintained mode (when the main supply is
connected: the tubes are not lit, the battery charges /
when the main supply is off: the emergency tube is
lit and the battery does not recharge)
Power factor
Up to 0.98
Cable entries
Standard: Two M20 cable entries included
One M20 Nylon plug and
One cable gland (EXCGM20S) - ISO M20 Nylon for
non-armoured cable, diameter 6-12mm
One Nylon plug (EX-M20)
Dimensions (mm)
B
C
Weight (kg)
Terminal block
Up to 4mm² (rigid wire), 2.5mm² (flexible wire)
Terminals for L, N, PE terminal 1 and terminal 2
Select function: Lighting in maintained mode or
lighting in non-maintained mode
Lamps (order separately)
Tube G13 bi-pin T8 Ø 26 coolwhite 4000°k
Spares & Fixings Accessories see pages 90-95
Related Products
89
EXB Conduit 138
Nylon Stopping
Plugs
176
XB100 Range 104
Exe Nylon Gland 168
www.tnb.com
A Member of the ABB Group
Fixing Accessories
Fixing Accessories for DTS lighting fittings
Fixing Accessories for EV Fluorescent Light Fitting Range
100
fl 36
fl 20
2
25
41
ø9
fl 9
2 x fl 9
20
M8
18
100
70
30
60¡
maxi
α
M8
~70
30
Hinged bracket
V023: plastic coated
Hook
V024: zinc plated steel
Fixing bracket and flange for
ø 1”1/4 and 1”1/2
V018: zinc plated steel (V019 - 2”)
V021: stainless steel 316L (V022 - 2”)
2 oblong holes
18x9
ø9
25
160
200
60
,
2 Ø 8.5
25
Brackets
Standard V015: zinc plated steel
V016: stainless steel 316L
Mounting bracket clip
V014: stainless steel
55
R
Fixing Accessories for Tubular Fitting: XFF / XFR / XFP / XEL / XEP / XFF-EM / XFP-EM / FF / FR / EL / FF-EM Range
Ø8
Ø 11
35
35
35
U-bolt for pole mounting
for 1”1/4
D025: zinc plated steel
(D026 - 1”1/2)
(D027 - 2”)
90
www.tnb-hazardous.com
2 Ø 11
3
35
3
Bracket
Standard D023: zinc plated steel
D024: stainless steel 304L
Accessories & Spare Parts
Spare Parts
Spare Parts for DTS lighting fittings
Spare Parts for EVS / EVN / EVD / EVN / EVT Fluorescent Light Fitting Range
V001
V005
V004
V008
EVS-EM/EMA Range
EVN / EVD / EVT-EM/EMA Range
Type
Specifications
Type
V001
Transparent diffuser (included gasket)*
V001
Transparent diffuser (included gasket)*
V004
Complete gear tray*
V004
Complete gear tray*
V005S
Connection Pack: Switch,
Connector, Terminal
V005E
Switch*
V008N
Bi-pin Lampholder
V008
Bi-pin Lampholder
V011
Battery pack*
002
Specifications
*Define type, rating and operating voltage
Spare Parts for ES Recessed Fluorescent Light Fitting Range
ESB / ESB-EM Range
Type
Specifications
Z001
Tranparent frame*
Z007
Electronic Ballast*
V008
Lampholder
V011
Battery Pack*
EST / EST-EM Range
Type
Specifications
Z001
Tranparent frame*
Z007N
Electronic Ballast*
V008N
Lampholder
Z007
V008
Z001
91
*Define type, rating and operating voltage
www.tnb.com
A Member of the ABB Group
Spare Parts
Spare Parts for DTS lighting fittings
Spare Parts for XFF / XFR Tubular Light Fitting Range
D001
D005
D002
D010
D010
XFF / XFR Range
Type
Specifications
D001
Sealed tube, cover, gasket, chain and slides*
D002
Cover, chain, gasket
D005
Complete gear tray* (included FF/FR Range)
D010
Bi-pin Lampholder
4GRA00002S
Grease for tubular model
*Define type, rating and operating voltage
Spare Parts for XFP Tubular Light Fitting Range
D021C
D005
D002
D010
D010
XFP Range
92
Type
Specifications
D001
Sealed tube, cover, gasket, chain and slides*
D002
Cover, chain, gasket
D005
Complete gear tray*
D010
Bi-pin Lampholder
D021C
Cover, gasket, screw, terminals, switch of junction boxes
D022
Interlock
4GRA00002S
Grease for tubular model
*Define type, rating and operating voltage
www.tnb-hazardous.com
D022
D001
Accessories & Spare Parts
Spare Parts
Spare Parts for DTS lighting fittings
Spare Parts for XEL / XEP Miniature Tubular Light Fitting Range
B002
B001
XEP
M005
D002
D002
XEL
D021C
D010
XEL Range
XEP Range
Type
Specifications
Type
Specifications
B001
Sealed tube, cover, gasket, chain and slides*
B002
Sealed tube, cover, gasket, chain and slides*
D002
Cover, chain, gasket
D002
Cover, chain, gasket
M005
Complete gear tray* (included EL Range)
M005
Complete gear tray*
D010
Bi-pin Lampholder*
D010
Bi-pin Lampholder*
4GRA00002S
Grease for tubular model
D021C
Cover, gasket, screw, terminals, switch and
interlock of junction boxes
D022
Interlock
4GRA00002S
Grease for tubular model
*Define type, rating and operating voltage
Spare Parts for XSF / XQF / XEF / EF / SF / QF Floodlight Range
SC100ELINGUE
P008
P009
XSF / XQF / XEF / SF / QF / EF Range
P006
P002 P004
P001
P012
P017
P007
P030
E007
E008C
P030C
Type
Specifications
P001
Closing Screw (12)
P002
Sealed front glass*
P004
Gasket*
P006
Lamp*
P007
Lampholder
P008
Reflector*
P009
Ferromagnetic Ballast*
P010
Ferromagnetic Ballast 120V 60Hz (400W)
P012
Ignitor
P017FC
Fixing (including screws)
P030C
Boxes Accessories: terminal 2* 6mm²
+ earthing terminal, + cover gasket, + cover, screw
P030
Ex trough connector
E007
Iodine Lamp*
E008C
Gear tray support, + fixing for optic, + optic for XEF
4GRA00001S
Grease for model XSF, XQF,XEF
93
*Define type, rating and operating voltage
www.tnb.com
A Member of the ABB Group
Spare Parts
Spare Parts for DTS lighting fittings
Spare Parts for XFF-EM / XFP-EM Tubular Light Fitting Range
D001
D005
D002EM
XFF-EM
D001
D021C
D016
D010
D022
D010
XFP-EM
XFF-EM Range
XFP-EM Range
Type
Specifications
Type
Specifications
D001
Sealed tube, cover, gasket, chain and slides*
D001
Sealed tube, cover, gasket, chain and slides*
D002EM
Cover, chain, gasket
D002EM
Cover, chain, gasket
D005
Complete gear tray*
D005
Complete gear tray*
D010
Bi-pin Lampholder
D010
Bi-pin Lampholder
D016
Battery pack
D016
Battery pack
4GRA00002S
Grease for tubular model
D021C
Cover, gasket, screw, terminals, switch an
interlock of junction boxes
D022
Interlock
4GRA00002S
Grease for tubular model
*Define type, rating and operating voltage
Spare Parts for XEL-BAES Range - XEL / XEP
B002
B001
XEP
B008
B009
B004
D002EM
D002
D021C
XEL
B00”
B01”
XEL- A / AK / AI / SI Range
B010B
Gear tray - 230V 50Hz - XEL 80AK / XEL80AI
Type
Specifications
B013K
Gear tray - 230V 50Hz - XEL 300AK / XEL300AI
B001
Sealed tube, cover, gasket, chain and slides*
B013
Gear tray - 230V 50Hz - XEL 300A
D002EM
Cover, chain, gasket
B014B
Gear tray - 230V 50Hz - XEL 80SI
B004
Slide for gear tray - XEL / XEP / XEL-BAES
B015
Gear tray - 230V 50Hz - XEL 300SI
B008B
Battery XEL 80A
4GRA00002S
Grease for tubular model
B008C
Battery + XIN05 XEL80AK / XEL80AI / XEL80SI
B009A
Battery + XIN05 XEL300AK / XEL300AI / XEL300SI
XEL - AI / SI Range (ONLY)
B009
Battery XEL3001 / XEL300A
Type
B005B
Gear tray - 230V 50Hz - XEL 80A
B002
Sealed tube, cover, gasket, chain and slides*
B006L
Gear tray - 230V 50/60Hz - XEL 3001
D021C
B007
Gear tray - 230V 50/60Hz - XEL 3002
Cover, gasket, screw, terminals, switch and
interlock of junction boxes
D022
Interlock
94
*Define type, rating and operating voltage
www.tnb-hazardous.com
Specifications
Accessories & Spare Parts
Spare Parts
Spare Parts for DTS lighting fittings
Spare Parts for XFB / XFL / FB / FL Beacons Range
L002A
L003A
L002A
L003A
L003A
L021
XFB / FB Range
L023
L021
L022
Type
Specifications
L00*
Globe (included gasket L023)
L021
Lamp*
L013
Lampholder
XFL / FL Range
L021
Type
Specifications
L00*
Globe (included gasket L023)
L021
Lamp*
L022110VCC
Gear tray - 110V DC - for XFL30P / XFL230P / XFL330P / FL30P / FL230P / FL330P
L022110VAC
Gear tray - 110V AC - for XFL30P / XFL230P / XFL330P / FL30P / FL230P / FL330P
L022220VAC
Gear tray - 220 - 230VAC 50-60Hz - for XFL30P / XFL230P / XFL330P / FL30P / FL230P / FL330P
L02224VCC
Gear tray - 24V DC - for XFL30P / XFL230P / XFL330P / FL30P / FL230P / FL330P
L02248VCC
Gear tray - 48V DC - for XFL30P / XFL230P / XFL330P / FL30P / FL230P / FL330P
*Define type, rating and operating voltage
Spare Parts for XDF Range
FF013
FF015C
FF019C
FF026
XFF012
FF02
FF013
FC108
XFF012
FF012
FF005C
XDF Range
Type
SC100ELINGUE
Specifications
FF013
Enclosure (included tube, cover, gasket, screws)*
XFF012
Bi-pin Lampholder
FF005C
Lampholder and starter
FF012
Ferromagnetic ballast*
FF023D
Plug (2P + E) - 10Amp - 250V AC
FF024D
Socket (2P + E) - 10Amp - 250V AC
FF019C
Connecting and earthing terminals
FF015C
Beam clamp with screws and steel brackets
FF026
Extendable cable with socket and plug - (helical cable) expandable to 5 metre max
95
*Define type, rating and operating voltage
www.tnb.com
A Member of the ABB Group
Lamps Guide
Guide to Lamps for use in DTS lighting fittings
Bi-pin T8/T12 fluorescent tubes
Specifications:
Type
G13 - ø 26mm or ø 38mm
TL18W
Power (W) Flux (lm) Cap
18
1250
G13
Fluorescent
Lighting equipment Reference
EVS...
CRI: > 80 - Lm/W: 65 > 93
TL36W
36
3350
G13
Fluorescent
XFR / XFF / XFP...
Colour temperature:
TL58W
58
5200
G13
Fluorescent
EVN...
2700K > 6500K
Fluorescent
EVD...
Average life: 6,000 > 10,000 hours
Weatherproof fluorescent EVT... FR/FF
Standard or electronic ballast
Miniature T5 fluorescent tubes
Specifications:
Type
G5 - ø 15mm
TL8W
Power (W) Flux (lm) Cap
8
430
G5
Lighting equipment Reference
Miniature
XEL / XEP...
CRI: 60 > 85 - Lm/W: 51 > 59
Weatherproof miniature
EL...
Colour temperature:
BAES range
XEL BAES...
2700K > 4100K
Average life: 6,000 hours
Electronic ballast or inverter
Compact fluorescent lamps
Specifications:
Type Power (W) Flux (lm) Cap
Lighting equipment Reference
G23 or G11
PL7W
7
400
G23
Miniature
CRI: 85 > 90 - Lm/W: 57 > 87
PL9W
9
600
G23
Weatherproof miniature
EL...
Colour temperature:
PL11W
11
900
G23
Fluorescent
XFR / XFF / XFP
2700K > 4000K
PL18W
18
1200
2 G11
Average life: 20,000 hours
PL36W
36
2900
2 G11
Standard or electronic ballast,
PL55W
55
4800
2 G11
XEL / XEP...
inverter
LED lamps
Power (W)
Flux (lm)
Cap
Lighting equipment Reference
E27
Specifications:
8
345
E27
Beacon
XFB
CRI: 80 - Lm/W: 55
12
806
E27
Weatherproof beacon
FB
Power (W)
Flux (lm)
Cap
Lighting equipment Reference
CRI: 100 - Lm/W: 10 > 17
28
345
E27
Beacon
Colour temperature:
70
1200
E27
Wellglass
EVX / EVH
2700K
140
3000
E27
Weatherproof beacon
FB
Colour temperature: 3000K
Average life: 25,000 hours
Integral electronic ballast
For lamp type - Contact Sales
Halogen lamps
Specifications:
Average life: 1,000 hours
For lamp type - Contact Sales
96
www.tnb-hazardous.com
XFB
Lamps Guide
Guide to Lamps for use in DTS lighting fittings
High pressure sodium tubular lamps
Specifications:
Type
CRI: NS - Lm/W: 100 > 120
E007
Power (W) Flux (lm) Cap
70
6000
E40
Lighting equipment Reference
Ex d floodlight
XSF...
Colour temperature: 2100K
P006150SHP
150
15000
E40
Weatherproof floodlight
SF...
Average life: 15,000 > 20,000 hours
P006250SHP
250
28000
E40
Mimimum starting temperature: -30ºC
P006400SHP
400
48000
E40
Time to full power: 1 > 10mm
With control gear and ignitor
Metal halide tubular lamps
Specifications:
Type
CRI: 65 - Lm/W: 68 > 76
P006250IM
Power (W) Flux (lm) Cap
250
20000
E40
Lighting equipment Reference
Ex d floodlight
XQF...
Colour temperature:
P006400IM
400
42000
E40
Weatherproof floodlight
QF...
4300K > 4600K
Average life: 3,000 > 6,000 hours
Mimimum starting temperature: -25ºC
Time to full power: 5 > 10mm
With control gear and ignitor
Halogen lamps
Specifications:
Type
H3
S00755W
Power (W) Flux (lm) Cap
55
1350
H3
Lighting equipment Reference
Ex d floodlight
CRI: 100 - Lm/W: 25
S00770W
70
1770
H3
Weatherproof floodlight EF / HF...
XEF / XHF...
Colour temperature:
3000K
Average life: 1,000 hours
Metal halide elliptical lamps
Specifications:
Power (W)
Flux (lm)
Cap
Lighting equipment Reference
CRI: 33 > 49 - Lm/W: 50 > 60
250
12700
E40
Ex d wellglass
Colour temperature:
400
22000
E40
3900K > 4300K
250
12700
E40
Average life: 15,000 > 20,000 hours
400
22000
E40
EVX
Mimimum starting temperature: -25ºC
Time to full power: 5 > 10mm
With control gear
For lamp type - Contact Sales
High pressure sodium elliptical lamps
Power (W)
Flux (lm)
Cap
Lighting equipment Reference
CRI: NS - Lm/W: 80 > 125
Specifications:
70
6300
E27
Ex d wellglass
Colour temperature:
150
17000
E40
2000K > 2200K
250
31100
E40
Average life:
400
55500
E40
EVX / EVH Na...
34,000 hours
Mimimum starting temperature: -25ºC
Time to full power: 1 > 10mm
With control gear and ignitor
For lamp type - Contact Sales
97
www.tnb.com
A Member of the ABB Group
Wellglass
EV Range
EVX / EVH Range
EVH 100 (Halogen)
EVX 100 (Halogen)
EVX Range - Halogen
Type
Dimensions (mm)
Tº Class
Rating (W)
Lamps
Nominal (A)
A/A’
B
EVX100-00000
70
E27 Halogen
0.45
250/283
150
T4
Weight in (kg)
2.9
EVX200-00000
140
E27 Halogen
0.90
313/346
170
T3
3.5
EVX300-00000
250
E27 Mixed light
1.30
410/463
220
T3
7.2
*Suspension ring mounted version, remove X and add the H, e.g. EVH100-00000
EC TYPE Examination Certificate:
IECEx CES 07.0004
CESI 12 ATEX 006
GOST R
II 2 GD
Ex d IIC T...ºC Gb
Ex tb IIIC T...ºC Db IP66
Enclosure
Body in marine grade aluminium alloy
(CU<0.05%) Yellow polyurethane paint RAL1003
Borosilicate glass globe
Galvanised steel protection grill
Ingress rating: IP65 (EN60529), neoprene ingress gasket
Stainless steel screws
Temperature
Ambient temperature range:-20°C to +60°C
Surface temperature classification: T4 to T3 (gas)
98
www.tnb-hazardous.com
Power factor
Up to 0.85 (HP Sodium and metal halide)
Cable entries
EVH: four 3/4” NPT entries - fitted 2 plugs
EVX: four 3/4” NPT entries - fitted 2 plugs
Terminal block
Up to 6mm² (rigid wire), 4mm² (flexible wire)
Lamps
Not supplied (order separately)
Fixing
Ceiling screw M8 (EVX)
Suspension ring (EVH)
Spare part: 30º angle wall mounting arm (R018)
Wellglass
EV Range
EVXNa / EVXlm / EVHNa / EVHlm Range
EVX Na (HP Sodium)
EVH Im (Metal Halide)
Rating (W)
Lamps
Nominal (A)
Dimensions (mm)
A/A’
B
EVXNa20-00000
70
E27 Elliptical
0.40
470/500
200
T4
6.5
EVXNa30-00000
150
E40 Elliptical
0.80
600/633
220
T3
9.7
EVH Na (HP Sodium)
EVXNa Range - HP Sodium
Type
EVX Im (Metal Halide)
TºC Class
Weight in (kg)
EVXNa40-00000
250
E40 Elliptical
1.30
600/633
220
T3
9.7
EVXNa50-00000
400
E40 Elliptical
2.10
630/670
270
T3
12
*Suspension ring mounted version, remove X and add H, e.g. EVHNa20-00000
EVXlm Range - Metal Halide
Type
Dimensions (mm)
B
TºC Class
Rating (W)
Lamps
Nominal (A)
A/A’
EVXlm40-00000
250
E40 Elliptical
1.30
600/633
220
T3
Weight in (kg)
9.7
EVXlm50-00000
400
E40 Elliptical
2.10
630/670
270
T3
12
*Suspension ring mounted version, remove X and add H, e.g. EVHlm40-00000
EC TYPE Examination Certificate:
IECEx CES 07.0004
CESI 12 ATEX 006
GOST R
II 2 GD
Ex d IIC T...ºC Gb
Ex tb IIIC T...ºC Db IP66
Enclosure
Body in marine grade aluminium alloy
(CU<0.05%) Yellow polyurethane paint RAL1003
Borosilicate glass globe
Galvanised steel protection grill
Ingress rating: IP65 (EN60529), neoprene ingress gasket
Stainless steel screws
Temperature
Ambient temperature range:-20°C to +60°C
Surface temperature classification: T4 to T3 (gas)
Rated voltages
HP Sodium metal halide
Standard: 230V 50Hz compensated,
wirewound ballast
Power factor
Up to 0.85 (HP Sodium and metal halide)
Cable entries
EVH: four 3/4” NPT entries - fitted 2 plugs
EVX: four 3/4” NPT entries - fitted 2 plugs
Variants: Other options available on request
Terminal block
Up to 6mm² (rigid wire), 4mm² (flexible wire)
Lamps
Not supplied (order separately)
Fixing
Ceiling screw M8 (EVX)
Suspension ring (EVH)
Spare part: 30º angle wall mounting arm (R018)
99
www.tnb.com
A Member of the ABB Group
Ex Boxes & Enclosures
100
26
www.tnb-hazardous.com
Ex Boxes & Enclosures
101
www.tnb.com
A Member of the ABB Group
Ex Boxes & Enclosures - Selection Guide
Ex Boxes & Enclosures Range
Zones
Dust
Gas
Group Groups
Protection Type
XBL
Junction
Boxes
Page 104
102
www.tnb-hazardous.com
XBL
Instrument
Boxes
Page 108
XBL-A
Control
Boxes
Page 110
XB
Instrument
Boxes
Page 112
XB-A
Control
Boxes
Page 114
XBi
Instrument
Boxes
Page 116
XBi-A
Control
Boxes
Page 118
Ex Boxes & Enclosures - Selection Guide
GUV
Junction
Boxes
Page 120
EFDC
Control
Boxes
Page 122
SRC
Control
Boxes
Page 122
XMC
Control
Boxes
Page 122
EJB
Custom
Built Panel
Page 124
GUB
Custom
Built Panel
Page 128
EJB-V
Boxes with
visible breaking
Page 130
103
www.tnb.com
A Member of the ABB Group
XBL Range
XB100 Junction boxes
Approvals / Characteristics
Features
• External mounting points allow for junction boxes
to be mounted without removing the lid
• Robust design
• Manufactured from anti static GRP so eliminating any
chance of static build up
• Supplied complete with terminals and glands so all
on site combinations are covered
Certification & Standards
Approved to: EN60079-0, 60079-7, 60079-11, 60079-31
EC TYPE Examination Certificate: Under 94/9/EC
LCIE 11 ATEX 3049X / IECEx LCI 11.0045X
Ex II 2 G / II 2 D
Ex e II T6 to T4 Gb
Ex tb IIIC T85ºC to T135ºC Db IP66
T6: -20ºC to 40ºC
T5: -20ºC to 55ºC
T4: -20ºC to 90ºC
Glow wire test: 960ºC EN60598-2-22
104
www.tnb-hazardous.com
Ex Boxes & Enclosures - XBL Range
Technical Specifications
Dimensions
75.5
100
121
121
AVERTISSEMENT
- NE PAS OUVRIR SOUS TENSION
WARNING
- DO NOT OPEN WHILE ENERGIZED
R3
.2
100
No. of
Entries Material
Type
XB100-6BV
4
32
Glands
Plug
No. of
Gland Size Thread Size Provided Connectors Type
Poly
M20
6-12mm
1 x M20
6
4
XB100-10BV
XB100A-6BV
Poly
4
Poly
4 Nickel Plated Brass
M20
6-12mm
1 x M20
3 x M20
6-12mm
1 x M20
1 x M32
15-21mm
M20*
6-12mm Int.
6
6
Screw/Screw
6mm2 bridge x2
Screw/Screw
–
4 x Grey
4mm2 bridge
Spring/Spring
–
2x
4mm2 bridge
Spring/Spring
–
4 x Grey 10mm2 bridge x2 Screw/Screw
–
2x
1 x M20
6
8.5-16mm Ext.
XB100A-6BR
4 Nickel Plated Brass
M20*
6-12mm Int.
6
8.5-16mm Ext.
XB100A-10BV
4 Nickel Plated Brass
3 x M20*
6-12mm Int.
Screw/Screw
6mm2 bridge x2
Screw/Screw
4 x Grey 4mm2 bridge x2 Spring/Spring
2x
1 x M20
6
10mm2 bridge x2 Screw/Screw
4 x Grey 6mm2 bridge x2
2x
1 x M20
Plate Bonding
Connection Conductors
4 x Grey 6mm2 bridge x2
2x
XB100-6BR
Terminal
Section
–
–
Yes
Yes
4mm2 bridge x2 Spring/Spring
4 x Grey 10mm2 bridge x2 Screw/Screw
Yes
8.5-16mm Ext.
1 x M32*
12-20mm Int.
2x
10mm2 bridge x2 Screw/Screw
16-26mm Ext.
*for armoured cable
Gland Size
Gland Type
M20
EXCGM20S
M32
EXCGM32S
M20*
EX04MMC1
M32*
EXN06MSC1
Related Products
105
XFF Range
28
Nylon Stopping
Plugs
176
EVS Range
42
Exe Nylon Gland 168
www.tnb.com
A Member of the ABB Group
XBL Range
Junction boxes
Approvals / Characteristics
Features
• Robust design
• Manufactured from anti static GRP to eliminate
static build up
• Supplied complete with terminals and glands so all
on site combinations are covered
Certification & Standards
Approved to: EN60079-0, 60079-7, 60079-11, 60079-31
EC TYPE Examination Certificate: Under 94/9/EC
LCIE 11 ATEX 3049X / IECEx LCI 11.0045X
Ex II 2 G / II 2 D
Ex e II T6 to T4 Gb
Ex ia IIC T6
Ex tb IIIC T85ºC to T135ºC Db IP66
T6: -20ºC to 40ºC
T5: -20ºC to 55ºC
T4: -20ºC to 90ºC
Glow wire test: 960ºC EN60598-2-22
106
www.tnb-hazardous.com
Ex Boxes & Enclosures - XBL Range
Technical Specifications
Dimensions
75.5
75
110
AVERTISSEMENT
- NE PAS OUVRIR SOUS TENSION
WARNING
- DO NOT OPEN WHILE ENERGIZED
25
Glands
Plug
No. of
No. of Entries Material Gland Size Thread Size Provided Connectors
Type
Terminal
Plate Bonding
Section
Connection Conductors
XBL28-25BR
6
Poly
M20
6-12mm
1 x M20
3
8 x 2, 5mm2 deck Spring/Spring
–
XBL26-25R
4
Poly
M20
6-12mm
1 x M20
3
4 x 2, 5mm2 deck Spring/Spring
–
Gland Size
Gland Type
M20
EXCGM20S
XB10-SI Boxes for connecting SI Sensors (for Instrumentation Box Zone 0 Products)
75.5
81
81
Dimensions
R6.5
25
No. of
Glands
Plug
No. of
Entries Material Gland Size Thread Size Provided Connectors Colour
Type
XB10-SI
3
XB10A-SI
Poly (Blue)
3
M16
Poly (Blue)
M16
Nickel Plated Brass
M20*
4.5-10mm
1 x M16
4.5-10mm
6
1 x M16
6
6-12mm Int.
Terminal
Section
Plate Bonding
Connection Conductors
4 x Blue
2.5mm2
Screw/Screw
2 x V/J
2.5mm2
Screw/Screw
–
4 x Blue
2.5mm2
Screw/Screw
Yes
2 x V/J
2.5mm2
Screw/Screw
–
8.5-16mm Ext.
*For armoured cable
Type
Connection
Nominal Section
Maximum Intensity
Rigid
0.5 - 6mm2
21A
Semi Rigid
0.5 - 4mm2
Flexible
0.5 - 4mm2
Flexible Tip
0.5 - 2.5mm2
XB10-SI
XB10A-SI
Gland Size
Gland Type
M16
EXCGM16S
M20
EXCGM20S
M20*
EXC03MMC1
21A
Related Products
107
XFF Range
28
Nylon Stopping
Plugs
176
EVS Range
42
Exe Nylon Gland 168
www.tnb.com
A Member of the ABB Group
XBL Range
Instrumentation boxes
Approvals / Characteristics
Features
• Robust design
• Manufactured from anti static GRP to eliminate
static build up
• Can be supplied complete with terminals and glands so
all on site combinations are covered
Certification & Standards
Approved to: EN60079-0, 60079-1, 60079-7, 60079-11, 60079-31
EC TYPE Examination Certificate: Under 94/9/EC
LCIE 11 ATEX 3049X / IECEx LCI 11.0045X
Ex II 2 G / D
Ex e or ia or eia IIC T6, T5 or T4 Gb
Ex tb IIIC T85ºC to T135ºC Db IP66
T4: ≤ -20ºC to ≤ +90ºC
T5: ≤ -20ºC to ≤ +55ºC
T6: ≤ -20ºC to ≤ +40ºC
LCIE 11 ATEX 3035 U / IECEx LCI 11.0028U
Ex e IIC Gb
Ex tb IIIC Db IP66
Glow wire test: 960°C EN60598-2-22
108
www.tnb-hazardous.com
Ex Boxes & Enclosures - XBL Range
Technical Specifications
Dimensions
For mounting ø 06.5
Type Material
Dimensions (mm)
A
B
C
D
E
2.5/21
4/28
13
11
XBL15
Poly
122
120
91
106
82
XBL20
Poly
110
75
75
98
45
XBL25
Poly
220
120
91
204
82
XBL35
Poly
360
160
91
340
110
60
XBL40
Poly
405
400
121
380
355
204
XBL45
Poly
400
250
121
380
200
136
XBL55
Poly
400
250
161
380
200
XBL65
Poly
600
250
121
580
XBL75
Poly
405
605
252
370
Enclosure
Fiberglass reinforced polyester with graphite finish
(R<1G Ohm)
Stainless steel unlosable screws
Optional hinges
Maximum number of terminals
size (in mm2) / In Max (in A)
Weight in
6/36 10/50 16/66 35/109 70/167 70/95/100 120/234 185/307 240/350 (kg)
8
6
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
0.4
21
16
–
–
–
–
–
–
–
1.1
50
38
30
25
–
–
–
–
–
–
2.2
171
129
68
58
21
–
–
–
–
–
5.6
114
86
34
29
21
–
–
–
–
–
3.7
136
114
86
34
29
21
17
–
–
–
–
4.8
200
216
180
136
54
45
34
–
–
–
–
–
5.2
570
312
261
130
104
86
32
25
19
6
5
5
7.2
11 (Min) 9 (Min)
33
28
Rated voltages
Depending on the components fitted in the box
(eg:with terminal block: Un max = 500V)
Cable entries
ISO entries and threads
Nylon cable glands for non-armoured cable
Nickel Plated Brass cable glands for armoured and
non-armoured cable require brass continuity plate
on XBL
0.8
Terminal block
Can be supplied with Exe or Exia terminal blocks
The maximum number of terminal blocks per box is
dependent on the certification
Stainless steel external earth
Other options available upon request
For full details and design service contact Sales
Related Products
109
XFF Range
28
Nylon Stopping
Plugs
176
EVS Range
42
Exe Nylon Gland 168
www.tnb.com
A Member of the ABB Group
XBL-A Range
Standard control boxes
Approvals / Characteristics
Features
• Wide variety of sizes and functions available as
standard products for speed of supply and custom
built to meet the end users exact requirements
• All manufactured with approved components
• Manufactured from anti static GRP to eliminate
static build up
Certification & Standards
Approved to: EN60079-0, 60079-1, 60079-7, 60079-11, 60079-31
EC TYPE Examination Certificate: Under 94/9/EC
LCIE 11 ATEX 3049X / IECEx LCI 11.0045X
Ex II 2 G / D
Ex de or e or ia or eia IIC T6, T5 or T4 Gb
Ex tb IIIC T85ºC to T135ºC Db IP66
T4: ≤ -20ºC to ≤ +90ºC
T5: ≤ -20ºC to ≤ +55ºC
T6: ≤ -20ºC to ≤ +40ºC
Glow wire test: 960ºC EN60598-2-22
110
www.tnb-hazardous.com
Ex Boxes & Enclosures - XBL-A Range
Technical Specifications
Dimensions
Standard Configurations
M6
M20 x 1,5
M20 x 1,5
ø22.5
*
M6
M20 x 1,5
M6
*Second cable
gland impossible
Visu 50x50
80
Visu 50x50
104
214
80
214
80
XB300 / XBL15
*Second cable
gland impossible
80
3 x ø22.5
104
*
M6
M20 x 1,5
XB300 / XBL15
with ammeter
XB400 / XBL25
3x ø22.5
XB400 / XBL25
with ammeter
XBL: 122 x 120 x 91 (mm)
XBL: 220 x 120 x 91 (mm)
1 Function
2 Functions Ammeter
3 Functions
4 Functions Ammeter
21A 21FA 21VA 215A 215VA 22A 23A
AMP
26A 38A 41A
43A
22AMP 38AMP
Type
Green Push Button 1 NO
●
–
–
–
–
●
●
–
●
●
●
●
●
Emergency Stop PB Push/Pull 1 NC
–
●
–
–
–
–
–
–
●
–
–
–
–
●
–
Emergency Stop PB Push/Pull 1 NC with Key 455
–
–
●
–
–
–
–
–
–
–
–
–
–
–
Switch 0-1, 2NO
–
–
–
●
–
–
–
–
–
●
–
–
–
●
Switch with Key 0-1, 1 NO
–
–
–
–
●
–
–
–
–
–
–
–
–
–
Red Push Button 1 NC
–
–
–
–
–
●
–
–
–
●
●
●
●
●
Green Indicator Lamp
–
–
–
–
–
–
●
–
●
–
●
●
–
–
Red Indicator Lamp
–
–
–
–
–
–
–
–
–
–
–
●
–
–
Ammeter TC/IA Graduate
Scale 0-In-3In dilo IN= to be indicated
–
–
–
–
–
–
–
●
–
–
–
–
●
●
Front Plug
–
–
–
–
–
–
–
–
–
–
–
–
●
–
*Add function to complete part number, e.g. XBL21A
Enclosure
XBL-A: Fiberglass reinforced polyester with graphite
finish (R< 1 Gohm)
Stainless steel unlosable screws
Optional hinges
Protection class: I
Technical Characteristics
AC: U = 415V max. I = 1,75A or U = 240V, I = 3A or
U = 120V, I = 6A
DC: U = 415V max. I = 0,165A or U = 250V,
I = 0,27A or U = 125V, I = 0,55A
Cable entries
ISO entries and threads
Nylon cable glands for non-armoured cable
Nickel Plated Brass cable glands for
non- armoured cable (order separetely)
Nickel Plated Brass cable glands for armoured and
non-armoured cable require brass contimuity
plate on XBL (order separetely)
Components
Drilling on request
Full range indicator lamp with LED Voltage of use
24V-254V AC/DC
Push button (green, red, black, yellow or blue) 1
contact (3 contacts maximum)
Emergency stop 1 contact (3 contacts maximum)
Rotary switch 2 or 3 positions (2 contacts maximum)
Anmeter Ex e: direct 1A or with CT/1Amp. max.
For Accessories see page 132
Related Products
111
XFF Range
28
Stopping Plugs 176
EVS Range
42
Exe Nylon Gland 168
www.tnb.com
A Member of the ABB Group
XB Range
Instrumentation boxes
Approvals / Characteristics
Features
• Robust design and paint finish ideal for marine applications
• Can be supplied complete with terminals and glands
so all on site combinations are covered
Certification & Standards
Approved to: EN60079-0, 60079-1, 60079-7, 60079-11, 60079-31
EC TYPE Examination Certificate: Under 94/9/EC
LCIE 11 ATEX 3051X / IECEx LCI 11.0046X
Ex II 2 G / D
Ex e or ia or eia IIC T6, T5 or T4 Gb
Ex tb IIIC T85ºC to T135ºC Db IP66
T4: ≤ -20ºC to ≤ +90ºC
T5: ≤ -20ºC to ≤ +55ºC
T6: ≤ -20ºC to ≤ +40ºC
LCIE 11 ATEX 3046 U / IECEx LCI 11.0043U
Ex e IIC Gb
Ex tb IIIC Db IP66
112
www.tnb-hazardous.com
Ex Boxes & Enclosures - XB Range
Technical Specifications
Dimensions
For mounting ø 06.5
Type Material
Dimensions (mm)
A
B
C
D
E
Maximum number of terminals
size (in mm2) / In Max (in A)
Weight in
6/36 10/50 16/66 35/109 70/167 70/95/100 120/234 185/307 240/350 (kg)
2.5/21
4/28
XB300
Alu
122
120
91
106
82
13
11
8
6
–
–
–
–
–
–
–
XB400
Alu
220
120
91
204
82
33
27
21
16
–
–
–
–
–
–
–
1.4
XB510
Alu
160
160
91
140
110
20
17
13
10
–
–
–
–
–
–
–
1.5
XB520
Alu
260
160
91
240
110
40
33
25
20
–
–
–
–
–
–
–
2.0
XB570
Alu
202
232
111
180
180
56
46
36
14
11
9
–
–
–
–
–
2.4
XB700
Alu
360
160
91
340
110
61
50
38
30
–
–
–
–
–
–
–
2.5
XB710
Alu
330
230
111
310
180
108
90
68
54
22
17
15
–
–
–
–
3.4
XB750
Alu
403
312
141
382
262
204
171
129
51
42
21
16
–
–
–
–
6.7
XB950
Alu
600
230
111
580
260
216
180
134
54
45
33
–
19
6
5
5
7.0
XB960
Alu
600
600
202
555
525
432
360
204
162
135
132
39
20
11
9
9
26.0
Enclosure
Aluminium ALSi 12, yellow polyurethane paint
RAL 1003 (other colours available on request)
Stainless steel unlosable screws
Optional hinges
Rated voltages
Depending on the components fitted in the box
(eg:with terminal block: Un max = 500V)
Cable entries
ISO entries and threads
Nylon cable glands for non-armoured cable
Nickel Plated Brass cable glands for
armoured cable (order separetely)
1.0
Terminal block
Can be supplied with Exe or Exia terminal blocks
The maximum number of terminal blocks per box is
dependent on the certification
Stainless steel external earth
Other options available upon request
For full details and design service contact Sales
Related Products
113
EJB Range
126
Stopping Plugs 176
EVS Range
42
ExeNylonGland 168
www.tnb.com
A Member of the ABB Group
XB-A Range
Standard control boxes
Approvals / Characteristics
Features
• Wide variety of sizes and functions available as
standard products for speed of supply and custom
built to meet the end users exact requirements
• All manufactured with approved components
• Manufactured from aluminium ideal for
marine applications
Certification & Standards
Approved to: EN60079-0, 60079-1, 60079-7, 60079-11, 60079-31
EC TYPE Examination Certificate: Under 94/9/EC
LCIE 11 ATEX 3051X / IECEx LCI 11.0046X
Ex II 2 G / D
Ex de or e or ia or eia IIC T6, T5 or T4 Gb
Ex tb IIIC T85ºC to T135ºC Db IP66
T4: ≤ -20ºC to ≤ +90ºC
T5: ≤ -20ºC to ≤ +55ºC
T6: ≤ -20ºC to ≤ +40ºC
114
www.tnb-hazardous.com
Ex Boxes & Enclosures - XB-A Range
Technical Specifications
Dimensions
Standard Configurations
M6
M20 x 1,5
M20 x 1,5
ø22.5
*
M6
M20 x 1,5
M6
*Second cable
gland impossible
Visu 50x50
80
Visu 50x50
104
214
80
214
80
XB300 / XBL15
*Second cable
gland impossible
80
3 x ø22.5
104
*
M6
M20 x 1,5
XB300 / XBL15
with ammeter
XB400 / XBL25
3x ø22.5
XB400 / XBL25
with ammeter
XB: 122 x 120 x 91 (mm)
XB: 220 x 120 x 91 (mm)
1 Function
2 Functions Ammeter
3 Functions
4 Functions Ammeter
21A 21FA 21VA 215A 215VA 22A 23A
AMP
26A 38A 41A
43A
22AMP 38AMP
Type
Green Push Button 1 NO
●
–
–
–
–
●
●
–
●
●
●
●
●
Emergency Stop PB Push/Pull 1 NC
–
●
–
–
–
–
–
–
●
–
–
–
–
●
–
Emergency Stop PB Push/Pull 1 NC with Key 455 –
–
●
–
–
–
–
–
–
–
–
–
–
–
Switch 0-1, 2NO
–
–
–
●
–
–
–
–
–
●
–
–
–
●
Switch with Key 0-1, 1NO
–
–
–
–
●
–
–
–
–
–
–
–
–
–
Red Push Button 1 NC
–
–
–
–
–
●
–
–
–
●
●
●
●
●
Green Indicator Lamp
–
–
–
–
–
–
●
–
●
–
●
●
–
–
Red Indicator Lamp
–
–
–
–
–
–
–
–
–
–
–
●
–
–
Ammeter TC/IA Graduate
Scale 0-In-3In dilo IN= to be indicated
–
–
–
–
–
–
–
●
–
–
–
–
●
●
Front Plug
–
–
–
–
–
–
–
–
–
–
–
–
●
–
*Add function to complete part number, e.g. XB21A
Enclosure
XB-A: Aluminium ALSi 12, yellow polyurethane
paint RAL1003 (other colours on request)
Stainless steel unlosable screws
Protection class: I
Technical Characteristics
AC: U = 415V max. I = 1,75A or U = 240V, I = 3A or
U = 120V, I = 6A
DC: U = 415V max. I = 0,165A or U = 250V,
I = 0,27A or U = 125V, I = 0,55A
Cable entries
ISO entries and threads
Nylon cable glands for non-armoured cable
Nickel Plated Brass cable glands for
armoured cable (order separetely)
Components
Indicator lamp with LED Voltage of use 24V-254V
AC/DC
Push button (green, red) 1 contact
Emergency stop 1 contact
Rotary switch 2 positions (2 contacts maximum)
Anmeter Ex e: direct 1A or with CT/1Amp. max.
For Accessories see page 132
Related Products
115
EJB Range
126
Stopping Plugs 176
EVS Range
42
ExeNylonGland 168
www.tnb.com
A Member of the ABB Group
XBi Range
Instrumentation boxes
Approvals / Characteristics
Features
• Robust design
• Manufactured from stainless steel 316 so ideal for
offshore applications
• Can be supplied complete with terminals and glands
so all on site combinations are covered
Certification & Standards
Approved to: EN60079-0, 60079-1, 60079-7, 60079-11, 60079-31
EC TYPE Examination Certificate: Under 94/9/EC
LCIE 11 ATEX 3050X / IECEx LCI 11.0044X
Ex II 2 G / D
Ex e or ia or eia IIC T6, T5 or T4 Gb
Ex tb IIIC T85ºC to T135ºC Db IP66
T4: ≤ -20ºC to ≤ +90ºC
T5: ≤ -20ºC to ≤ +55ºC
T6: ≤ -20ºC to ≤ +40ºC
LCIE 11 ATEX 3045 U / IECEx LCI 11.0041U
Ex e IIC Gb
Ex tb IIIC Db IP66
116
www.tnb-hazardous.com
Ex Boxes & Enclosures - XBi Range
Technical Specifications
Dimensions
A
EB
C
D
Maximum number of terminals
size (in mm2) / In Max (in A)
Weight in
6/36 10/50 16/66 35/109 70/167 70/95/100 120/234 185/307 240/350 (kg)
Dimensions (mm)
Type Material A
B
C
D
E
2.5/21
XBi100 316L S/S 100
100
61
60
60
9 (Min) 8 (Min)
XBi150 316L S/S 150
150
81
110
110
XBi200 316L S/S 200
100
61
160
110
XBi300 316L S/S 300
200
81
260
160
98
80
XBi400 316L S/S 400
300
161
360
260
138
116
XBi500 316L S/S 500
400
161
460
360
356
296
XBi600 316L S/S 600
200
121
560
360
218
182
136
Enclosure
316L stainless steel,1.25mm thick
Stainless steel unlosable screws
Optional hinges
19
4/28
16
29 (Min) 24 (Min)
–
–
–
–
–
–
–
–
–
0.8
12
10
–
–
–
–
–
–
–
0.4
–
–
–
–
–
–
–
–
–
1.1
60
25
–
–
–
–
–
–
–
2.2
86
70
56
21
17
–
–
–
–
5.6
224
135
87
46
14
11
–
–
–
3.7
55
45
34
–
–
–
–
–
4.8
Rated voltages
Depending on the components fitted in the box
(eg:with terminal block: Un max = 500V)
Cable entries
ISO entries and threads
Nylon cable glands for non-armoured cable
Nickel Plated Brass cable glands for
non-armoured cable (order separately)
Terminal block
Can be supplied with either Exe or
Exia Terminal blocks
The maximum number of terminal blocks per box is
dependent on the certification
Stainless steel external earth
Other options available upon request
For full details and design service contact Sales
Related Products
117
EJB Range
126
Stopping Plugs 176
EVS Range
42
ExeNylonGland 168
www.tnb.com
A Member of the ABB Group
XBi-A Range
Standard control boxes
Approvals / Characteristics
Features
• Robust design
• Manufactured from stainless steel 316 so ideal
for offshore applications
Certification & Standards
Approved to: EN60079-0, 60079-1, 60079-7, 60079-11, 60079-31
EC TYPE Examination Certificate: Under 94/9/EC
LCIE 11 ATEX 3050 / IECEx LCI 11.0044
Ex II 2 G / D
Ex de or e or ia or eia IIC T6, T5 or T4 Gb
Ex tb IIIC T85ºC to T135ºC DB IP66
Ex de IIC T6, T5 or T4 IP66
T4: ≤ -20ºC to ≤ +90ºC
T5: ≤ -20ºC to ≤ +55ºC
T6: ≤ -20ºC to ≤ +40ºC
Glow wire test: 960°C EN60598-2-22
118
www.tnb-hazardous.com
Ex Boxes & Enclosures - XBi-A Range
Technical Specifications
Dimensions
Standard Configurations
60
Label
ø22.5
60
4x
ø20.5
ø20.5
3x ø22.5
160
60
XBi100
Type
XBi200
21A
XBi: 100 x 100 x 61 (mm)
1 Function
2 Functions
21FA 21VA 215A 215VA
22A 23A
XBi: 200 x 100 x 61 (mm)
3 Functions
4 Functions
26A 38A 41A
43A
Green Push Button 1 NO
●
–
–
–
–
●
●
●
●
●
Emergency Stop PB Push/Pull 1NC
–
●
–
–
–
–
–
●
–
–
●
–
Emergency Stop PB Push/Pull 1NC with Key 455
–
–
●
–
–
–
–
–
–
–
–
Switch 0-1, 2NO
–
–
–
●
–
–
–
–
●
–
–
Switch with Key 0-1, 1NO
–
–
–
–
●
–
–
–
–
–
–
Red Push Button 1 NC
–
–
–
–
–
●
–
–
●
●
●
Green Indicator Lamp
–
–
–
–
–
–
●
●
–
●
●
Red Indicator Lamp
–
–
–
–
–
–
–
–
–
–
●
Ammeter TC/IA Graduate
Scale 0-In-3In dilo IN= to be indicated
–
–
–
–
–
–
–
–
–
–
–
Front Plug
–
–
–
–
–
–
–
–
–
–
–
*Add function to complete part number, e.g. XBi21A
Enclosure
XBi-A: 316L stainless steel,
1.25mm thick
Stainless steel unlosable screws
Protection class: I
Technical Characteristics
AC: U = 415V max. I = 1,75A or U = 240V, I = 3A or
U = 120V, I = 6A
DC: U = 415V max. I = 0,165A or U = 250V,
I = 0,27A or U = 125V, I = 0,55A
Cable entries
ISO entries and threads
Nylon cable glands for non-armoured cable
Nickel Plated Brass cable glands for
armoured cable (order seperately)
Components
Full range indicator lamp with LED Voltage of use
24V-254V AC/DC
Push button (green, red, black, yellow or blue) 1
contact (2 contacts maximum)
Emergency stop 1 contact (2 contacts maximum)
Rotary switch 2 or 3 positions (2 contacts maximum)
Anmeter Ex e: direct 1A or with CT/1Amp. max.
For Accessories see page 132
Related Products
119
EJB Range
126
Stopping Plugs 176
EVS Range
42
Exe Nylon Gland 168
www.tnb.com
A Member of the ABB Group
GUV Range
Aluminium junction boxes
Approvals / Characteristics
Features
• External mounting points allow junction boxes
to be mounted without removing the lid
• Robust design in cast aluminium
• Bright yellow paint (RAL-1003) for high visibility
Certification & Standards
Approved to: EN60079-0, 60079-1
EC TYPE Examination Certificate:
LCIE 00 ATEX 6022 / IECEx in progress
Ex II 2 G
Ex d IIC T6 to T4
LCIE 00 ATEX 6022
T6: ≤ -20°C to ≤ +40°C
T5: ≤ -20°C to ≤ +55°C
T4: ≤ -20°C to ≤ +60°C
120
www.tnb-hazardous.com
Ex Boxes & Enclosures - GUV Range
Technical Specifications
Dimensions
Type
Number of entries
Number of terminals (optional)
Weight (Kg)
GUVC26-00000
2 -c-
4 x 2.5 to 6mm2
0.6
GUVC36-00000
2 -c-
Max 8 x 25mm2 or 6 x 35mm2
1.6
GUVL26-00000
2 i-
4 x 2.5 to 6mm2
0.6
GUVL36-00000
2 i-
Max 8 x 25mm2 or 6 x 35mm2
1.6
GUVT26-00000
3T
4 x 2.5 to 6mm2
0.6
GUVT36-00000
3T
Max 8 x 25mm2 or 6 x 35mm2
1.7
GUVX26-00000
4X
4 x 2.5 to 6mm2
0.7
GUVX36-00000
4X
Max 8 x 25mm2 or 6 x 35mm2
1.8
Enclosure
Aluminium alloy body EN 1706 AC - 43100KF AISI 10Mg
Yellow polyurethane paint RAL1003
Stainless steel screws
Cable entries
Standard: Two to four 3/4” NPT entries
Cable glands and plugs can be ordered seperately
Terminals
GUV26:
4 terminals up to 6mm2 (order separately)
4 interconnected earthing terminals with one 4mm
clamping screws per each terminal
GUV36:
Terminals (order separately)
Maximum number 8 x 25mm2 terminals
or 6 x 35mm2 terminals
Other options (order separately)
Terminal 4 x 6mm2 (G03)
Terminal 6 x 4mm2 (G005)
Terminal 10 x 4mm2 (G006)
Terminal 4 x 10mm2 (G009)
Terminal 5 x 10mm2 (G0010)
Terminal 4 x 16mm2 (G0011)
Terminal 8 x 16mm2 (G0015)
Related Products
121
EXL Conduit
148
Stopping Plugs 176
XFF Range
28
Ex d Cable
Gland
162
www.tnb.com
A Member of the ABB Group
EFDC / SRC / XMC Range
Control stations
Approvals / Characteristics
Features
• Ex d approved for hazardous locations
• Manufactured from cast aluminium and machined
with a cylindrical spigot joint flame path
Certification & Standards
Approved to: EN60079-0, 60079-1
EC TYPE Examination Certificate:
LCIE 00 ATEX 6022 / IECEx in progress
Ex II 2 G
Ex d IIC T6 to T4
Type (without light): EFDC, SRC
T6: ≤ -20°C to ≤ +40°C
T5: ≤ -20°C to ≤ +55°C
T4: ≤ -20°C to ≤ +60°C
Type (with light): EFDC, SRC
T6: ≤ -20°C to ≤ +40°C
122
www.tnb-hazardous.com
Ex Boxes & Enclosures - EFDC / SRC / XMC Range
Technical Specifications
Dimensions
112
3/4
124
58
137
ø7
150
105
140
195
ø6.5
M6
M6
3/4 23
166
65
3/4
3/4
3/4
34
SRC / EFDC
(enclosure size 1)
XMC 36
(enclosure size 3)
SRC / EFDC
(enclosure size 2)
Type EFDC
21
25
41
43 44
22
40 42
38
23 21F 21V 21G 21P 24 23A 39
Green Push Button NO+NC
●
–
●
●
●
●
●
–
●
●
–
–
–
–
–
–
–
–
–
2 x Green Push button NO+NC
–
–
–
–
–
–
–
●
–
–
–
–
–
–
–
–
–
–
–
Push/Pull Emergency Button NO+NF
–
●
–
–
–
–
–
–
–
–
●
–
–
–
–
–
–
–
–
Emergency Key Operated Push Button 455 NO+NF
–
–
–
–
–
–
–
–
–
–
–
●
–
–
–
–
–
–
–
Break Glass Automatic Cut-off NO+NC
–
–
–
–
–
–
–
–
–
–
–
–
●
–
–
–
–
–
–
Potentiometer Driver
–
–
–
–
–
–
–
–
–
–
–
–
–
●
–
–
–
–
–
Green Indicator Lamp 230V
–
●
●
●
●
–
–
–
–
●
–
–
–
–
●
●
●
●
–
Red Push Button NO+NC
–
–
●
●
●
●
●
–
●
–
–
–
–
–
–
–
–
–
–
2 x Red Push Button NO+NC
–
–
–
–
–
–
–
●
–
–
–
–
–
–
–
–
–
–
–
Red Indicator Lamp 230V
–
–
–
●
–
–
–
–
–
–
–
–
–
–
–
●
●
–
–
Push Button Black NO+NC
–
–
–
–
●
–
●
–
–
–
–
–
–
–
–
–
–
–
–
Rotary Switch Unit 16A 2 NO
–
–
–
–
–
–
–
–
●
–
–
–
–
–
–
–
●
●
–
2 x Rotary Switch Unit 16A 2 NO
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
●
Type SRC Rotary Switch Unit
215
415
330
340
215V
16A 2NO
●
–
–
–
●
32A 3NO Lockable
–
–
●
–
–
40A 3NO Lockable
–
–
–
●
–
With Key 455
–
–
–
–
●
16A 4 NO
–
●
–
–
–
37
36
Type XMC
XMC36
1 display diameter 80 with base plate - no equipment
*Add function to complete part number, e.g. EDFC21, SRC215, XMC36
Enclosure
Body in marine grade aluminium alloy
EN1706 AC - 43100KF - AISI 10Mg
Polyurethane paint: yellow RAL1003 except
EFDC21G (red paint RAL3001)
Stainless steel screws
Volume < 2 dm3
Power supply
Maximum operating power: 400 Vac max for the
indicator lamps
6 A max for the push buttons
40 A max for the rotary switches
For indicator and potentiometer: please enquire
Cable entries
Standard: Two 3/4”NPT one being equipped with
one Nickel Plated Brass plug
Cable glands ordered separately
Terminal blocks
Directly connected to the accesory / component,
as required.
Recommendation:
For proper selection of cable glands in
hazardous locations, refer to EN60079-14
For Accessories see page 132
Related Products
123
EXL Conduit
148
Stopping Plugs 176
XFF Range
28
www.tnb.com
A Member of the ABB Group
Custom Built Enclosures
124
26
www.tnb-hazardous.com
Custom Built Enclosures
Custom built Ex d enclosures & panels
DTS Ex d control panels are constructed & tested according to ATEX protection type Ex d.
Available with a wide variety of components such as switches, contactors and relays, which can be mounted into explosionproof
enclosures constructed to keep internal explosions from igniting the surrounding atmosphere.
125
Ex d control panels are usually custom-built in cooperation with the customer to suit their specific application requirements.
www.tnb.com
A Member of the ABB Group
EJB Range
Custom built panels
Approvals / Characteristics
Features
• Robust construction
• Wide variety of sizes
• Large choice of electrical components
• Customised to user’s specification
Certification & Standards
Approved to: EN60079-0, 60079-1
EC TYPE Examination Certificate:
INERIS 11 ATEX 0050X
Ex II 2 G
Ex d IIB T5 or T6 Gb
Ex II 2 (1) G
Ex d (ia IIC Ga, or ib, or ib IIC, or ia Ga) IIB T6 Gb
Safe operating temperature range: -20ºC to +40ºC
126
For installations in either Zone 1 or in the presence of Group IIC gases, barrier
glands are required. Please refer to EN-60079-14
www.tnb-hazardous.com
Ex Boxes & Enclosures - EJB Range
Technical Specifications
Dimensions
GxH
A
External
B
C
D
Internal
E
F
EJB0
200
145
130
145
90
90
140
85
EJB1
302
190
170
225
115
130
200
EJB2
295
230
165
225
165
132
EJB4
410
300
167
340
220
EJB5
475
295
220
390
EJB8
625
360
250
525
EJB11
595
505
275
EJB12
805
435
EJB13
832
612
Type
Internal Plate
(mm)
Weight (kg)
M6
138 x 85
4
100
M6
215 x 110
8
185
130
M6
220 x 160
9
127
290
190
M8
320 x 210
16
207
179
335
178
M8
380 x 200
18
260
195
480
210
M8
510 x 250
33
485
395
207
436
335
M10
470 x 380
55
315
690
345
246
605
262
M12
675 x 325
75
323
720
435
252
628
405
M12
790 x 470
92
Enclosure
Marine grade aluminium alloy type EN 1706 AC 43100KF - AISI 10Mg
Stainless steel external earth
Stainless steel screws
Hinged door if command buttons are on the panel
(except EJB0)
Cable entries
NPT or ISO entries and threads as requested:
Nickel Plated Brass, or Stainless Steel cable
glands can be supplied (order separately) for either
armoured, or non-armoured cables
Fixing / Mounting
G
H
L
Switches and Indicators
On request Rotary switches: 1 to X positions two-way,
spring return, layout on request (eg : 3NO + 1NC, 1
NO / Position...)
Push buttons: Colours: green, red, black, yellow, blue
Mechanical reactivation
Contacts: maximum 6 contacts as specified, NO
or NC Indicator lamps: Colours: green, red, white,
yellow, blue, power supply not exceeding 400V
LEDs
Potentiometer: please advise: value in Ohms, power
in W, Number of turns, linear or logarithmic
For all components: legends as requested
Isolating switch/circuit-breaker: up to 800A
Meters behind visual display: ammeter, voltmeter or
others upon request
Fixing
4 threaded holes on the back plate (see table)
Frame or supporting feet on request
Colour (standard)
EJB - Yellow offshore, RAL 1003
Colour options
EJB - Grey, RAL 7035
EJB - Black, RAL 9004
EJB - Hammered Blue, RAL 5015
EJB - Red, RAL 3001
EJB - Blue, RAL 5010
EJB - Green, RAL 6032
EJB - White, RAL 9010
•
•
•
•
•
•
•
Recommendation
For installations in either Zone 1 or in the
presence of Group IIC gases, barrier glands
are required. Please refer to EN-60079-14
(except EJB0/< 2 dm3)
For Accessories see page 132
Related Products
127
EXL Conduit
148
Stopping Plugs 176
GUV Range
120
www.tnb.com
A Member of the ABB Group
GUB Range
Custom built panels
Approvals / Characteristics
Features
• IIC boxes
• Anti-corrosion and marine protection
• Large internal volume
• Quick and easy opening and closing
Certification & Standards
Approved to: EN 60079-0,60079-1, 61241-0, 61241-1
EC TYPE Examination Certificate:
CESI 01 ATEX 036
Ex II 2 G / D
Ex d IIC T6 to T5
Ex tD A21 IP66 T 85°C to T 100°C
T6: -20ºC to +40ºC
T5: -20ºC to +55ºC
128
For installations in either Zone 1 or in the presence of Group IIC gases, barrier
glands are required. Please refer to EN-60079-14
www.tnb-hazardous.com
Ex Boxes & Enclosures - GUB Range
Technical Specifications
Dimensions
A
D
A
D
A
B
C
D
A
2 1/2”
B C
Type
A
GUB0AS
3
2
1
3
2
1
1
2
1
–
–
1
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
GUB0BS
3
3
2
3
3
3
2
3
2
2
1
2
2
1
1
2
1
1
1
1
–
–
–
–
–
–
–
–
GUB01CS
5
4
3
5
4
4
3
4
3
2
2
3
2
1
1
2
2
1
1
2
1
1
1
1
–
–
–
–
GUB02DS
7
6
6
7
7
6
6
7
5
4
4
2
3
2
2
3
2
2
2
2
2
1
1
2
1
1
1
1
GUB03ES
15
15 15
15
15
14
13
15
8
8
7
8
8
7
6
8
5
4
4
5
3
2
2
3
2
2
1
2
GUB04FS
26
26 26
26
20
19
19
20 14
13
13
14
10
9
9
10
10
9
9
10
8
7
7
8
5
4
4
5
Type
External Dimensions (mm)
A
B
C
D
D
3/4”
B
C
Cable Glands and Plugs Per Side
1”
1/4”
1 1’2”
B C D A B C D A B C
1/2”
B C
Internal Dimensions (mm)
F
G
H
I
Fixing
J
D
Kø
Weight (kg)
GUB0AS
120
120
116
166
96
96
54
75
100
145
9
2
GUB0BS
150
150
130
205
126
126
68
115
126
174
10
3
GUB01CS
174
174
140
218
146
146
75
115
150
195
10
4
GUB02DS
230
230
165
302
204
204
85
175
196
267
14
7
GUB03ES
276
276
217
346
274
256
134
220
236
316
14
12
GUB04FS
430
430
290
522
398
398
155
360
390
480
14
30
Enclosure
Marine aluminium alloy body (CU<0.05%)
Ingress rating IP66 (EN60529)
Neoprene gasket
Stainless steel screws
Protection class: I
E
2”
Cable entries
NPT or ISO threaded entries according to specification
The fixture is supplied with non-barrier cable glands.
For installations in either Zone 1, or in the presence
of Group IIC gases, barrier glands are required.
Please refer to EN-60079-14.
Fixing
By fixing lugs incorporated to the box
Colour (standard)
GUB***-00000 - Yellow offshore, RAL 1003
•Colour
options
- Grey, RAL 7035
• GUB***-B0000
GUB***-C0000
RAL 9004
• GUB***-D0000 - Black,
Blue, RAL 5015
• GUB***-F0000 - Hammered
Red,
RAL
3001
• GUB***-G0000 - Blue, RAL 5010
• GUB***-J0000 - Green, RAL 6032
• GUB***-M0000 - White, RAL 9010
For Accessories see page 132
Related Products
129
EXL Conduit
148
Stopping Plugs 176
GUV Range
120
www.tnb.com
A Member of the ABB Group
EJB-V Range
Boxes with visible breaking
Approvals / Characteristics
Features
• Boxes provided with load-break switch
• Visible breaking
• Switch off and on under load and provide safety cut off
• IIB control panels
Certification & Standards
Approved to: EN60079-0, 60079-1
EC TYPE Examination Certificate:
INERIS 11 ATEX 0050X
Ex II 2 G
Ex d IIB T5 or T6 Gb
Ex II 2 (1) G
Ex d IIB T6 Gb
Safe operating temperature range: -20ºC to +40ºC
130
For installations in either Zone 1 or in the presence of Group IIC gases,
barrier glands are required. Please refer to EN-60079-14
www.tnb-hazardous.com
Ex Boxes & Enclosures - EJB-V Range
Technical Specifications
Dimensions
Type
A
Dimensions (mm)
B
C
G
H
L
Display Size (mm)
Switching
Gland
Number
Plugs
Weight
(kg)
EJB2-V1
295
230
165
132
185
M6
100 x 100
3 x 50A
2 x 3/4”
1 x 3/4”
9
EJB2-V2
295
230
165
132
185
M6
100 x 100
4 x 50A
2 x 3/4”
1 x 3/4”
9
EJB2-V3
295
230
165
132
185
M6
100 x 100
3 x 80A
2 x 3/4”
1 x 3/4”
9
EJB2-V4
295
230
165
132
185
M6
100 x 100
4 x 80A
2 x 3/4”
1 x 3/4”
9
EJB4-V1
410
300
167
190
290
M8
100 x 100
3 x 125A
2 x 1”
1 x 3/4”
18
EJB4-V2
410
300
167
190
290
M8
100 x 100
4 x 125A
2 x 1”
1 x 3/4”
18
EJB4-V3
410
300
167
190
290
M8
50 x 200
6 x 50A
4 x 3/4”
1 x 3/4”
18
EJB4-V4
410
300
167
190
290
M8
50 x 200
8 x 50A
4 x 3/4”
1 x 3/4”
18
EJB4-V5
410
300
167
190
290
M8
50 x 200
6 x 80A
4 x 3/4”
1 x 3/4”
18
EJB4-V6
410
300
167
190
290
M8
50 x 200
8 x 80A
4 x 3/4”
1 x 3/4”
18
EJB8-V1
625
360
250
210
480
M8
50 x 200
6 x 125A
4 x 1”
1 x 3/4”
35
EJB8-V2
625
360
250
210
480
M8
50 x 200
8 x 125A
4 x 1”
1 x 3/4”
35
EJB8-V3
625
360
250
210
480
M8
100 x 100
3 x 200A
2 x 1”
1 x 3/4”
55
EJB11-V1
595
505
275
355
436
M10
50 x 200
3 x 400A
2 x 2”
1 x 3/4”
55
EJB11-V2
595
505
275
355
436
M10
50 x 200
4 x 400A
2 x 2”
1 x 3/4”
55
EJB13-V1
825
605
320
405
628
M12
50 x 200
3 x 400A
2 x 2”
1 x 3/4”
95
EJB13-V2
825
605
320
405
628
M12
50 x 200
4” 4 x 400A
2 x 2”
1 x 3/4”
95
Enclosure
Marine grade aluminium alloy type AS10GY30
Toughened glass display
Stainless steel external earth stud
Stainless steel screws
Hinged door standard on EJB versions of
EJB8-11-12-13, (optional on other EJB versions)
Protection class: I
Cut-out equipment
“Sider” load-breaker, 50A to 400A,
3 or 4-poles visible breaking
(up to 800A on request)
Padlockable handle
Options: security key, auxiliary contacts
mechanical indicator
Cable entries
NPT or ISO entries and threads as requested
Brass, Nickel Plated Brass, or Stainless Steel cable
glands can be supplied (order separately) for either
armoured, or non-armoured cables.
Fixing
4 threaded holes on the back plate (see table)
Colour (standard)
EJB-V*-00000 - Yellow offshore, RAL 1003
Colour options
EJB-V*-B0000 - Grey, RAL 7035
EJB-V*-C0000 - Black, RAL 9004
EJB-V*-D0000 - Hammered Blue, RAL 5015
EJB-V*-F0000 - Red, RAL 3001
EJB-V*-G0000 - Blue, RAL 5010
EJB-V*-J0000 - Green, RAL 6032
EJB-V*-M0000 - White, RAL 9010
•
•
•
•
•
•
•
For Accessories see page 132
Related Products
131
EXL Conduit
148
Stopping Plugs 176
GUV Range
120
www.tnb.com
A Member of the ABB Group
Box Accessories
Spare Components for Control Panels & Enclosures
Components for Control Station
Complete Units
for DTS control stations and boxes
Spare Parts
for the complete units
(SRC - EFDC Mod 1 & 2, XBL, XB, XBi, EJB)
Type
Function
(EFDC / SRC or EJB as specified)
Type
Function
BPN10
Push button Black NO+NC
PB01
Contacts NO+NC for push button switches
BPR10
Push button Red NO+NC
PR01
Rotary switch unit 2x16A 0-1 2NO
BPV10
Push button green NO+NC
PR02
Rotary switch unit 2x16A 1-2 NO+NC
REA20
Reset button (customised for EJB ranges)
PR03
Rotary switch unit 2x16A 1-0-2 NO-0-NC
BCP30
Simple emergency stop push button NO+NC
PR04
Rotary switch unit 2x16A 0-1-2-0-NO-NO
BCP40
Push/Pull button Emergency Stop NO+NC
PR05
Rotary switch unit 4x16A 0-1 4NO
BCP50
Push button, unlockable by key N° 455
PR06
Rotary switch unit 3x25A 0-1 3NO
PRC10
Rotary switch 2x16A 0-1 2NO
PR07
Rotary switch top
PRC20
Rotary switch operated by key No 455 2x 16A 0-1 2NO
PR07V
Key operated switch top
PRC30
Rotary switch 2x16A 1-2 NO+NC
BP02
Cap for push switch Green
PRC40
Rotary switch 2x16A 1-0-2 NO-0-NC
BP03
Cap for push switch Red
PRC50
Rotary switch 2x16A 0-1-2-0-NO-NO
BP04
Cap for push switch Black
PRC60
Rotary switch 4x16A 0-1 4NO
BP05
Cap for mushroom push/pull switch
PRC70
Lockable rotary switch 3x25A 3NO
BP05V
Cap for key operated mushroom push switch
VAV10
Indicator lamp 230V - Green
DE01
Indicator lamp lens Green
VAR10
Indicator lamp 230V - Red
DE02
Indicator lamp lens Red
VAC10
Indicator lamp 230V - White
DE03
Indicator lamp lens White
VAJ10
Indicator lamp 230V - Yellow
DE04
Indicator lamp lens Amber
VAB10
Indicator lamp 230V - Blue
DE05
Indicator lamp lens Blue
DE10
Lamp holder for BA9S lamp
Options
Rotary Switch Options:
- Spring return (40A max for SRC)
- Configuration on request (eg : 3NO+1NF, 1 NO/Position...)
Push button options:
- Colours: Green, Red, Black,Amber, Blue
- Contacts (model 1 & EJB):Max 3 contacts according to request NO or NC
- Contacts (model 2): Max 6 contacts according to request NO or NC
Indicator Lamp Options:
Other voltages are available on request up to 400V
- LED
For all products:
Legends as requested
132
www.tnb-hazardous.com
Options
Rotary Switch Options:
- Spring return (40A max for SRC)
- Configuration on request (eg : 3NO+1NF, 1 NO/Position...)
For all products:
- Legends as requested
Accessories & Spare Parts
Polyester / Aluminium Plug & Socket (Safe Disconnect)
DRX / DPX Range
Wall socket (30°)
ø
B
Plug
A
Ød
C
E
D
Wall socket DRX
Fitting plugged in to/unplugged from wall socket (30°)
G
Socket
Plug
Nominal
Power
Type DRX Type DPX Poles Current (A) Supply (V) Gland
A
B
Cable
ø
C
Dimensions (mm)
D E F G ø d AI A0 BI B0
Weight (kg)
Y Socket Plug
116E250
116E250 1P+N+PE
20
220/250
M20
125 58 8-13 127 131 68 90 78 4.5 204 215 162 168 180
0.3
0.16
216X24
216X24
2P
20
20 - 24
M20
125 58 8-13 127 131 68 90 78 4.5 204 215 162 168 180
0.3
0.16
316E250
316E250
3P+PE
20
130/230
M20
125 58 8-13 127 131 68 90 78 4.5 204 215 162 168 180
0.3
0.16
316E415
316E415
3P+PE
20
380/440
M20
125 58 8-13 127 131 68 90 78 4.5 204 215 162 168 180
0.3
0.16
416E415
416E415 3P+N+PE
20
380/440
M20
125 58 8-13 127 131 68 90 78 4.5 204 215 162 168 180
0.3
0.16
132E250
132E250 1P+N+PE
32
220/250
M25
145 68 13-19 138 132 84 107 70
0.46
0.24
232X24
232X24
2P
32
20 - 24
M25
145 68 13-19 138 132 84 107 70
6
214 229 162 171 200
0.46
0.24
332E250
332E250
3P+PE
32
150/230
M25
145 68 13-19 138 132 84 107 70
6
214 229 162 171 200
0.46
0.24
332E415
332E415
3P+PE
32
380/440
M25
145 68 13-19 138 132 84 107 70
6
214 229 162 171 200
0.46
0.24
432E415
432E415 3P+N+PE
32
380/440
M25
145 68 13-19 138 132 84 107 70
6
214 229 162 171 200
0.46
0.24
163E250
163E250 1P+N+PE
63
220/250
M32
152 83 17-25 165 162 89 122 88 6.5 233 259 184 199 236
0.64
0.42
263X24
263X24
2P
63
20 - 24
M32
152 83 17-25 165 162 89 122 88 6.5 233 259 184 199 236
0.64
0.42
363E415
363E415
3P+PE
63
380/440
M32
152 83 17-25 165 162 89 122 88 6.5 233 259 184 199 236
0.64
0.42
463E415
463E415 3P+N+PE
63
380/440
M32
152 83 17-25 165 162 89 122 88 6.5 233 259 184 199 236
0.64
0.42
Socket
Plug
Nominal
Power Cable
Type DRX Type DPX Poles Current (A) Supply (V) Gland
3125E415
3125E415
4125E415
4125E415 3P+N+T
3P+T
A
B
ø
C
6
214 229 162 171 200
Dimensions (mm)
D E F G ø d AI A0 BI B0
Weight (kg)
Y Socket Plug
125
380/440
M50
220 146 27-41 378 175 221 – 174 9.5 513 –
175 –
–
8.0
2.6
125
380/440
M50
220 146 27-41 378 175 221 – 174 9.5 513 –
175 –
–
8.0
2.6
Approved to: IEC 60079-0, 60079-1, 60079-7, 61241-0, 61241-1 60309-1, 60309-4
EC TYPE Examination Certificate: under new directive 94/9/EC
20A versions: LCIE 99 ATEX 6027X, IECEx LCI09.005X, ≤ -40°C to ≤ +60°C T5 T90ºC, ≤ -40°C to ≤ +40°C T6 T70ºC
32A versions: LCIE 05 ATEX 6149, IECEx LCI09.0006, ≤ -40°C to ≤ +60°C T4 T98ºC, ≤ -40°C to ≤ +40°C T6 T78ºC
63A versions: LCIE 05 ATEX 6150, IECEx LCI09.0007, ≤ -40°C to ≤ +60°C T4 T107ºC, ≤ -40°C to ≤ +40°C T5 T87ºC
125A versions: LCIE 04 ATEX 6038, IECEx LCI09.0015, ≤ -40°C to ≤ +60°C T5 T90ºC, ≤ -40°C to ≤ +50°C T6 T80ºC
ATEX II 2 G / D, IP6x Exd e II C tDA21 Ingress protection: IP66/67 (PBT), IP65 (aluminium)
133
www.tnb.com
A Member of the ABB Group
Conduit & Glands
134
26
www.tnb-hazardous.com
Conduit Systems
135
www.tnb.com
A Member of the ABB Group
Conduit Fittings - Selection Guide
For use with Nylon Conduits
Zones
Dust Gas
Group Group Protection Type
Nylon
Conduits
Page 138
DIV
1
I
DIV
2
DIV
1
136
DIV
2
www.tnb-hazardous.com
Metallic
Fittings
Page 140
Nylon
Fittings
Page 142
For use with Liquid Tight Conduits
Liquid Tight
Conduits
Page 148
Group 1
Glands
Page 152
Group 1
90º Elbow
Glands
Page 154
Group 1
Univeral
Fittings
Page 155
Group 1
Group II
Universal
Glands
Swivel Fittings Page 158
Page 157
Conduit Fittings - Selection Guide
XP Flex
Page 160
Ex d Cable
Glands
Page 162
Ex d Cable
Glands
Page 164
Ex e Cable
Glands
Page 166
Nylon Cable
Glands
Page 168
Thread
Convertors
Page 170
Standard
Stopping
Plugs
Page 174
Tamperproof
Stopping
Plugs
Page 174
Hex Head
Stopping
Plugs
Page 176
Dome Head
Stopping
Plugs
Page 176
Nylon
Stopping
Plugs
Page 176
137
www.tnb.com
A Member of the ABB Group
Non-metallic Nylon Conduit
Technical Specifications
EXB Anti-Static Conduit compatible with EXPQM / EXPQA Fittings
Anti-Static Nylon 12 (Black)
Type
Conduit Size (mm)
Metric
NW
Outside
Coil Lengths
Diameter (mm)
(m)
EXB03*
16
12
15.8
10/30/50
EXB04*
21
17
21.2
10/30/50
EXB05*
28
23
28.5
10/30/50
EXB06*
34
29
34.4
10/30/50
EXB07*
42
36
42.4
10/30/50
EXB08*
54
48
54.5
10/30/50
EXB09*
63
56
67.2
10/30/50
EXB010*
80
70
80
10/30/50
*Add coil length to complete part number, e.g. 10 metres = EXB0510
Ex e IIC Gb
Ex tb IIIC Db
Temperature: -20°C to 80ºC
RTI 110ºC to EN60079-0
EC TYPE Examination Certificate:
ATEX: Baseefa 08 ATEX 0003X
IECEx: IECEx BAS08.0001X
GOST R: POCC GB.ГБ05.B03850
INMETRO: TÜV 11.0091
Special Characteristics
EXB: Surface resistivity <106Ω
EXBB Overbraided Conduit compatible with EXBQM / EXBQA Fittings
Anti-Static Nylon 12 (Stainless Steel)
Type
Conduit Size (mm)
Metric
NW
Outside
Coil Lengths
Diameter (mm)
(m)
EXBB03*
16
12
12
50
EXBB04*
21
17
17
50
EXBB05*
28
23
23
50
EXBB06*
34
29
27
50
EXBB07*
42
36
36
30
EXBB08*
54
48
48
30
*Add coil length to complete part number, e.g. 10 metres = EXBB0510
EC TYPE Examination Certificate:
ATEX: Baseefa 08 ATEX 0003X
IECEx: IECEx BAS08.0001X
GOST R: POCC GB.ГБ05.B03850
INMETRO: TÜV 11.0091
Ex e IIC Gb
Ex tb IIIC Db
Temperature: -20°C to 80ºC
RTI 110ºC to EN60079-0
Special Characteristics
EXBB: Screening level 60dB at 1MHz
Related Products
138
EXPQM Fitting 140
www.tnb-hazardous.com
EXBQM Fitting 140
Non-Metallic Nylon Conduit - EXB / EXBB / XESX Range
Technical Specifications
XESX Anti-Static Nylon Multi-Layer Conduit compatible with EXPQM / EXBQA Fittings
Anti-Static Nylon 12 (Black)
Type
Conduit Size (mm)
Metric
NW
Coil Lengths
Outside
(m)
Diameter (mm)
XESX02*
12
10
50
12.8
XESX03*
16
12
50
15.6
XESX04*
21
17
50
21
XESX05*
28
23
50
28.5
XESX06*
34
29
50
34.4
XESX07*
42
36
30
42.4
XESX08*
54
48
30
54.4
*Add coil length to complete part number, e.g. 10 metres = XESX0510
Ex e IIC Gb
Ex tb IIIC Db
Temperature: -40°C to 85ºC
EC TYPE Examination Certificate:
ATEX: Baseefa 08 ATEX 0003X
IECEx: IECEx BAS08.0001X
RTI 110ºC to EN60079-0
Special Characteristics
XESX: Surface resistivity <106Ω
Related Products
EXPQM Fitting 140
EXBQM Fitting 140
XESX Anti-Static Conduit compatible with all Nylon Fittings
Anti-Static Nylon 12 (Black)
Type
Coil Lengths
(m)
XESXT-10BY.50
12
10
50
XESXT-12BY.50
16
12
50
XESXG-17BY.50
21
17
50
XESXG-23BY.50
28
23
50
XESXG-29BY.50
34
29
50
XESXG-36BY.30
42
36
30
XESXG-48BY.30
54
48
30
Ex eb IIC Gb
Ex tb IIIC Db
EC TYPE Examination Certificate:
ATEX SEV 05 ATEX0105
Conduit Size (mm)
Metric
NW
Temperature: -40°C to 85ºC
Special Characteristics:
XESX: Surface resistivity <106Ω
Related Products
139
NENV Fitting 142
NENZ Fitting
142
NEBV Fitting
144
NEWV Fitting 144
NEAV Fitting
144
www.tnb.com
A Member of the ABB Group
EXBQM / EXPQA Range
Nylon conduit fittings
Approvals / Characteristics
Features
• Manufactured in Nickel Plated Brass
• Approved for use in Ex e applications for
Zones 1, 2, 21 & 22
Certification & Standards
EC TYPE Examination Certificate:
ATEX: Baseefa 08 ATEX 0003X
IECEx: IECEx BAS08.0001X
GOST R: POCC GB.ГБ05.B03850
INMETRO: TÜV 11.0091
Ex e IIC Gb
Ex tb IIIC Db
Temperature: -40°C to 85ºC
140
www.tnb-hazardous.com
Non-Metallic Nylon Fittings - EXPQM / EXBQA Range
EXPQM Straight Male Conduit Fitting for EXB / XESX Nylon Conduit
Nickel Plated Brass
Type - Metric
Technical Specifications
Conduit Size (mm)
Metric
NW
Thread Size
Metric (mm)
EXPQM0203
12
10
16
EXPQM0303
16
12
16
EXPQM0304
16
12
20
EXPQM0404
20
17
20
EXPQM0505
28
23
25
EXPQM0606
34
29
32
EXPQM0707
42
36
40
EXPQM0808
54
48
50
EXPQM0909
63
56
63
EXPQM1010
80
70
75
Nickel Plated Brass
Type - NPT
Conduit Size (mm)
Metric
NW
12
Thread Size
NPT (inch)
1
/2
1
/2
3
/4
EXPQA0304
16
EXPQA0404
20
17
EXPQA0505
28
23
EXPQA0606
34
29
1
EXPQA0707
42
36
11/4
EXPQA0808
54
48
11/2
EXPQA0909
63
56
2
EXPQA1010
80
70
21/2
EXBQM Straight Male Conduit Fitting for EXBB Braided Conduit
Nickel Plated Brass
Type - Metric
Conduit Size (mm)
Metric
NW
Thread Size
Metric (mm)
EXBQM0304
16
12
20
EXBQM0404
20
17
20
EXBQM0505
28
23
25
EXBQM0606
34
29
32
EXBQM0707
42
36
40
EXBQM0808
54
48
50
Nickel Plated Brass
Type - NPT
Conduit Size (mm)
Metric
NW
12
Thread Size
NPT (inch)
1
/2
1
/2
3
/4
EXBQA0304
16
EXBQA0404
20
17
EXBQA0505
28
23
EXBQA0606
34
29
1
EXBQA0707
42
36
11/4
EXBQA0808
54
48
11/2
For Accessories see page 178-79
Related Products
141
Locknuts
178
Sealing
Washers
178
EXB Range
138
EXBB Range
138
XESX Multi-Layer 139
Range
www.tnb.com
A Member of the ABB Group
Nylon Conduit Fittings
Nylon conduit fittings for XESX conduit ( only)
Approvals / Characteristics
Features
• Manufactured in modified Nylon 12 with Nickel
Plated Brass threads
• Approved for use in Ex e applications for
Zones 1, 2, 21 & 22
Certification & Standards
EC TYPE Examination Certificate:
ATEX: SEV 05 ATEX 0105
Ex eb IIC
Ex tb IIIC
Temperature: -20°C to 85ºC
142
www.tnb-hazardous.com
Non-Metallic Nylon Fittings for XESX Conduit (
Technical Specifications
NENV Straight Male Conduit Fitting
Type - Metric
only)
Conduit Size (mm)
Metric
NW
Metric Thread
Size (mm)
NENV-M120-10
12
10
12
NENV-M160-10
12
10
16
NENV-M162-10
16
12
16
NENV-M202-10
16
12
20
NENV-M207-10
20
17
20
NENV-M257-11
20
17
25
NENV-M253-11
25
23
25
NENV-M323-13
25
23
32
NENV-M329-13
32
29
32
NENV-M409-13
32
29
40
NENV-M406-13
40
36
40
NENV-M506-14
40
36
50
NENV-M508-14
50
48
50
NENV-M638-114
50
48
63
NENZ Straight Male Conduit Fitting with Strain Relief
Type - Metric
Conduit Size (mm)
Metric
NW
Metric Thread
Size (mm)
NENZ-M120S/P
12
10
12
NENZ-M160S/P
12
10
16
NENZ-M202S/P
12
10
20
NENZ-M207S/P
16
12
20
NENZ-M257S/P
20
17
20
NENZ-M323S/P
20
17
25
NENZ-M409S/P
25
23
32
NENZ-M506S/P
32
29
40
NENZ-M508S/P
40
36
50
NENZ-M638S/P
50
48
63
*Available with various clamping ranges
Related Products
143
Locknuts
178
XESX Range
139
www.tnb.com
A Member of the ABB Group
Nylon Conduit Fittings for XESX Conduit (
only)
Technical Specifications
NEBV 90º Curved Elbow
Type - Metric
Conduit Size (mm)
Metric
NW
Metric Thread
Size (mm)
NEBV-M207-10
20
17
20
NEBV-M257-11
20
17
25
NEBV-M253-11
25
23
25
NEBV-M323-13
25
23
32
NEBV-M329-13
32
29
32
NEBV-M409-13
32
29
40
NEBV-M406-13
40
36
40
NEBV-M506-14
40
36
50
NEBV-M508-14
50
48
50
NEBV-M638-14
50
48
63
NEWV 90º Elbow
Type - Metric
Conduit Size (mm)
Metric
NW
Metric Thread
Size (mm)
NEWV-M120-10*
12
10
12
NEWV-M160-10*
12
10
16
NEWV-M162-10*
16
12
16
NEWV-M202-10*
16
12
20
NEAV 45º Elbow
Type - Metric
144
www.tnb-hazardous.com
Conduit Size (mm)
Metric
NW
Metric Thread
Size (mm)
NEAV-M120-10
20
17
20
NEAV-M162-10
20
17
25
NEAV-M207-10
25
23
25
NEAV-M257-11
25
23
32
NEAV-M253-11
32
29
32
NEAV-M323-13
32
29
40
NEAV-M329-13
40
36
40
NEAV-M409-13
40
36
50
NEAV-M406-13
50
48
50
NEAV-M506-14
50
48
63
NEAV-M508-14
50
48
50
NEAV-M638-14
50
48
63
Non-Metallic Nylon Fittings for XESX Conduit (
only)
Technical Specifications
BESGR Splice Connector
Conduit Size (mm)
Metric
NW
Type - Metric
BESGR-1212
16
BESGR-1212
20
12
17
BESGR-1212
25
23
BESGR-1212
32
29
BESGR-1212
40
36
BESGR-1212
50
48
BEYR Y Piece
Type - Metric
Conduit Size (mm)
Metric
NW
2 x Conduit Size (mm)
Metric
NW
BEYR-121010
16
12
12
10
BEYR-171212
20
17
16
12
BEYR-231717
25
23
20
17
BEYR-292323
32
29
25
23
BEYR-362929
40
36
32
29
BEYR-483636
50
48
40
36
BETR Tee Piece
Type - Metric
Conduit Size (mm)
Metric
NW
BETR-101010
12
10
BETR-121212
16
12
BETR-171717
20
17
BETR-232323
25
23
BETR-292929
32
32
BETR-363636
40
40
BETR-363636
50
50
For Accessories see page 178-79
Related Products
145
Locknuts
178
XESX Range
139
www.tnb.com
A Member of the ABB Group
Nylon Conduit Fittings for XESX Conduit (
only)
Technical Specifications
BEAVR Reducer
Type - Metric
Conduit Size (mm)
Metric
NW
BEAVR-12/10
16
BEAVR-17/12
20
12
17
BEAVR-23/17
25
23
BEAVR-29/23
32
29
BEAVR-36/29
40
36
BEAVR-48/36
50
48
NEIR Reducer Female Thread Adapter - Straight
Type - Metric
Conduit Size (mm)
Metric
NW
NEIR-M120
12
10
NEIR-M160
16
10
NEIR-M162
16
12
NEIR-M207
20
17
NEIR-M253
25
23
NEIR-M329
32
29
NEIR-M406
40
36
NEIR-M508
50
48
NEIR-M638
63
48
BENR-REM Corrugated Conduit to Rigid Metal Pipe Connection
Type - Metric
146
www.tnb-hazardous.com
Conduit Size (mm)
Metric
NW
External
Dimensions (mm)
BENR-REM162-24
16
12
54
BENR-REM207-28
20
17
65
BENR-REM253-32
25
23
71
BENR-REM329-44
32
29
71
BENR-REM406-50
40
36
90
BENR-REM508-65
50
48
90
Non-Metallic Nylon Fittings for XESX Conduit (
only)
Technical Specifications
HEAK EMC Connector with Conical Shielding Braid Clamp compatible with NENV / NENZ / NEBV / NEWV / NEAV
Nickel Plated Brass
Type - Metric
Conduit Size (mm)
Metric (Fits to thread)
NW
HEAK-M32/25-13
32 - 25
23
HEAK-M40/32-13
40 - 32
29
HEAK-M50/40-14
50 - 40
36
HEAK-M63/63-14
63 - 63
48
Accessories
BEH Conduit Clip
Type - Metric
Conduit Size (mm)
Metric
NW
BEH-10-0
12
10
BEH-12-0
16
12
BEH-17-0
20
17
BEH-23-0
25
23
BEH-29-0
32
29
BEH-36-0
40
36
BEH-48-0
50
48
For Accessories see page 178-79
Related Products
147
Locknuts
178
XESX Range
139
www.tnb.com
A Member of the ABB Group
Liquid Tight Conduit - Galvanised Steel Core
Technical Specifications
General Oil Resistant - Galzanised Steel Core with a general purpose oil resistant coating
General Oil Resistant (Black)
Type
Conduit Size
Metric (mm)
EXLB03*
16
EXLB04*
20
EXLB05*
25
US Trade
Size (inch)
3
/8
1
/2
3
/4
Inside Diameter Coil Lengths
(mm)
(m)
EXLB06*
32
1
26.4
10/20
EXLB07*
40
11/4
35.3
10/20
EXLB08*
50
11/2
40.4
10/20
EXLB09*
63
2
51.6
10/20
12.5
10/30
16.0
10/30
21.0
10/30
*Add coil length to complete part number, e.g. 10 metres = EXLB0510
Special Characteristics
Flame retardant PVC covering
Certification Standard: IEC 61386
Static Temp: -25°C to +105°C
Flexing Temp: -5°C to +105°C
Flame Propogation
Flame dies in less than 30 seconds after ignition
source is removed
Low Fire Hazard - Galzanised Steel Core with a LFH coating
Low Fire Hazard (Black)
Type
Conduit Size
Metric (mm)
EXLT03*
16
EXLT04*
20
EXLT05*
25
US Trade
Size (inch)
3
/8
1
/2
3
/4
EXLT06*
32
EXLT07*
Inside Diameter Coil Lengths
(mm)
(m)
12.5
10/30
16.0
10/30
21.0
10/30
1
26.4
10/20
40
11/4
35.3
10/20
EXLT08*
50
11/2
40.4
10/20
EXLT09*
63
2
51.6
10/20
*Add coil length to complete part number, e.g. 10 metres = EXLT0510
Certification Standard: IEC 61386
LUL Fully Compliant (E1042A6)
MOD to NES 518: Issue 3 DEF STAN 61-12
(Part 31) Issue 1
Static Temp: -25°C to +90°C
Flexing Temp: -5°C to +90°C
Special Characteristics
Limited Fire Hazard, zero halogen (BS6425 Pt 1)
Flame Propogation
Flame dies in less than 30 seconds after ignition
source is removed
Low Fire Hazard with EMC Protection - Galvanised Steel Core with a galvanised steel EMC shield and LFH Covering
Low Fire Hazard with EMC (Black) Conduit Size
Type
Metric (mm)
EXBBT03*
16
EXBBT04*
20
EXBBT05*
25
US Trade
Size (inch)
3
/8
1
/2
3
/4
Inside Diameter Coil Lengths
(mm)
(m)
EXBBT06*
32
1
26.4
10/20
EXBBT07*
40
11/4
35.3
10/20
EXBBT08*
50
11/2
40.4
10/20
EXBBT09*
63
2
51.6
10/20
12.5
10/30
16.0
10/30
21.0
10/30
*Add coil length to complete part number, e.g. 10 metres = EXBBT0510
148
Certification Standard: IEC 61386
MOD to NES 518: Issue 3 DEF STAN 61-12
(Part 31) Issue 1
www.tnb-hazardous.com
Static Temp: -25°C to +90°C
Flexing Temp: -5°C to +90°C
Special Characteristics
Limited Fire Hazard covering
EMC Screening level: 60db at 1MHz Braided
Liquid Tight Conduit - EXLB / EXLT / EXLH / EXBBT / EXLHC Range
Technical Specifications
High Temperature - Galvanised Steel Core with a high temperature resistant coating
High Temperature (Black)
Type
Conduit Size
Metric (mm)
EXLH03*
16
EXLH04*
20
EXLH05*
25
US Trade
Size (inch)
3
/8
1
/2
3
/4
Inside Diameter
(mm)
Coil Lengths
(inch)
EXLH06*
32
1
26.4
10/20
EXLH07*
40
11/4
35.3
10/20
EXLH08*
50
11/2
40.4
10/20
EXLH09*
63
2
51.6
10/20
Inside Diameter
(mm)
Coil Lengths
(inch)
12.5
10/30
16.0
10/30
21.0
10/30
*Add coil length to complete part number, e.g. 10 metres = EXLH0510
High Temperature (Blue)
Type
Conduit Size
Metric (mm)
US Trade
Size (inch)
EXLLH03*
16
3
10/30
20
1
16.0
10/30
EXLLH05*
25
/8
/2
3
/4
12.5
EXLLH04*
21.0
10/30
EXLLH06*
32
1
26.4
10/20
EXLLH07*
40
11/4
35.3
10/20
EXLLH08*
50
11/2
40.4
10/20
EXLLH09*
63
2
51.6
10/20
*Add coil length to complete part number, e.g. 10 metres = EXLLH0510
Certification Standard: IEC 61386
Static Temp: -50°C to +130°C
Flexing Temp: -5°C to +90°C
Special Characteristics
Flame resistance: UL94 V2
Chemical and oil resistant
Flame Propogation
Flame dies in less than 30 seconds after ignition
source is removed
High Temperature Highly Flexible - Galvanised Steel Core with a high temperature, highly flexible coating
High Temperature,
Highly Flexible (Blue)
Type
Conduit Size
Metric (mm)
EXLHC03*
16
EXLHC04*
20
EXLHC05*
25
US Trade
Size (inch)
3
/8
1
/2
3
/4
Inside Diameter
(mm)
Coil Lengths
(inch)
12.5
10/30
16.0
10/30
21.0
EXLHC06*
32
1
26.4
10/30
10/20
EXLHC07*
40
11/4
35.3
10/20
EXLHC08*
50
11/2
40.4
10/20
EXLHC09*
63
2
51.6
10/20
*Add coil length to complete part number, e.g. 10 metres = EXLHC0510
Certification Standard: IEC 61386
Static Temp: -65°C to +150°C
Flexing Temp: -45°C to +135°C
Special Characteristics
High Flexibility
High Temperature
Flame Propogation
Flame dies in less than 30 seconds after ignition
source is removed
Related Products
149
Group I Gland 152
Group II Gland 158
90º Elbow
Gland
144
www.tnb.com
A Member of the ABB Group
Liquid Tight Conduit - Stainless Steel Core
Technical Specifications
General Oil Resistant - Stainless Steel 316 Core with a general purpose oil resistant coating
General Oil Resistant (Black)
Type
Conduit Size
Metric (mm)
EXSB05*
25
US Trade
Size (inch)
3
/8
1
/2
3
/4
EXSB06*
32
1
26.4
10/20
EXSB07*
40
11/4
35.3
10/20
EXSB08*
50
11/2
40.4
10/20
EXSB09*
63
2
51.6
10/20
EXSB03*
16
EXSB04*
20
Inside Diameter Coil Lengths
(mm)
(m)
12.5
10/30
16.0
10/30
21.0
10/30
*Add coil length to complete part number, e.g. 10 metres = EXSB0510
Special Characteristics
Flame retardant PVC covering
Certification Standard: IEC 61386
Static Temp: -25°C to +105°C
Flexing Temp: -5°C to +105°C
Flame Propogation
Flame dies in less than 30 seconds after ignition
source is removed
Low Fire Hazard - Stainless Steel Core with a LFH coating
Low Fire Hazard (Black)
Type
Conduit Size
Metric (mm)
EXST03*
16
EXST04*
20
EXST05*
25
US Trade
Size (inch)
3
/8
1
/2
3
/4
Inside Diameter Coil Lengths
(mm)
(m)
EXST06*
32
1
26.4
10/20
EXST07*
40
11/4
35.3
10/20
EXST08*
50
11/2
40.4
10/20
EXST09*
63
2
51.6
10/20
12.5
10/30
16.0
10/30
21.0
10/30
*Add coil length to complete part number, e.g. 10 metres = EXLT0510
Certification Standard: IEC 61386
LUL Fully Compliant (E1042A6)
MOD to NES 518: Issue 3 DEF STAN 61-12
(Part 31) Issue 1
Static Temp: -25°C to +90°C
Flexing Temp: -5°C to +90°C
Special Characteristics
Limited Fire Hazard, zero halogen (BS6425 Pt 1)
Flame Propogation
Flame dies in less than 30 seconds after ignition
source is removed
Low Fire Hazard with EMC Protection - Stainless Steel Core with a galvanised steel EMC shield and LFH Covering
Low Fire Hazard with EMC (Black) Conduit Size
Type
Metric (mm)
EXSBBT03*
16
EXSBBT04*
20
EXSBBT05*
25
US Trade
Size (inch)
3
/8
1
/2
3
/4
Inside Diameter Coil Lengths
(mm)
(m)
EXSBBT06*
32
1
26.4
10/20
EXSBBT07*
40
11/4
35.3
10/20
EXSBBT08*
50
11/2
40.4
10/20
EXSBBT09*
63
2
51.6
10/20
12.5
10/30
16.0
10/30
21.0
10/30
*Add coil length to complete part number, e.g. 10 metres = EXBBT0510
150
Certification Standard: IEC 61386
MOD to NES 518: Issue 3 DEF STAN 61-12
(Part 31) Issue 1
www.tnb-hazardous.com
Static Temp: -25°C to +90°C
Flexing Temp: -5°C to +90°C
Special Characteristics
Limited Fire Hazard covering
EMC Screening level: 60db at 1MHz Braided
Liquid Tight Conduit - EXSB / EXST / EXSH / EXSBBT / EXSHC Range
Technical Specifications
High Temperature - Stainless Steel Core with a high temperature resistant coating
High Temperature (Black)
Type
Conduit Size
Metric (mm)
EXSH03*
16
EXSH04*
20
EXSH05*
25
US Trade
Size (inch)
3
/8
1
/2
3
/4
Inside Diameter
(mm)
Coil Lengths
(inch)
EXSH06*
32
1
26.4
10/20
EXSH07*
40
11/4
35.3
10/20
EXSH08*
50
11/2
40.4
10/20
EXSH09*
63
2
51.6
10/20
Inside Diameter
(mm)
Coil Lengths
(inch)
12.5
10/30
16.0
10/30
21.0
10/30
12.5
10/30
16.0
10/30
21.0
10/30
*Add coil length to complete part number, e.g. 10 metres = EXLH0510
High Temperature (Blue)
Type
Conduit Size
Metric (mm)
EXSLH03*
16
EXSLH04*
20
EXSLH05*
25
US Trade
Size (inch)
3
/8
1
/2
3
/4
EXSLH06*
32
1
26.4
10/20
EXSLH07*
40
11/4
35.3
10/20
EXSLH08*
50
11/2
40.4
10/20
EXSLH09*
63
2
51.6
10/20
*Add coil length to complete part number, e.g. 10 metres = EXLLH0510
Certification Standard: IEC 61386
Static Temp: -50°C to +130°C
Flexing Temp: -5°C to +130°C
Special Characteristics
Flame resistance: UL94 V2
Chemical and oil resistant
Flame Propogation
Flame dies in less than 30 seconds after ignition
source is removed
High Temperature Highly Flexible - Stainless Steel Core with a high temperature, highly flexible coating
High Temperature,
Highly Flexible (Blue)
Type
Conduit Size
Metric (mm)
EXSHC03*
16
EXSHC04*
20
EXSHC05*
25
US Trade
Size (inch)
3
/8
1
/2
3
/4
Inside Diameter
(mm)
Coil Lengths
(inch)
12.5
10/30
16.0
10/30
21.0
EXSHC06*
32
1
26.4
10/30
10/20
EXSHC07*
40
11/4
35.3
10/20
EXSHC08*
50
11/2
40.4
10/20
EXSHC09*
63
2
51.6
10/20
*Add coil length to complete part number, e.g. 10 metres = EXLHC0510
Certification Standard: IEC 61386
Static Temp: -65°C to +150°C
Flexing Temp: -45°C to +135°C
Special Characteristics
High Flexibility
High Temperature
Flame Propogation
Flame dies in less than 30 seconds after ignition
source is removed
Related Products
151
Group I Gland 152
Group II Gland 158
90º Elbow
Gland
144
www.tnb.com
A Member of the ABB Group
G1 Glands
Liquid tight hazardous area flameproof glands
Approvals / Characteristics
Features
• Constructed from either Brass or Stainless Steel
with an epoxy resin barrier the Group I Flameproof
Gland is a high specification product, ideal for all
hazardous area applications
Certification & Standards
I
DIV
2
152
www.tnb-hazardous.com
DIV
1
EC TYPE Examination Certificate:
ATEX: Sira 09 ATEX 1231X
IECEx: IECEx SIR09.0103X
CSA: CSA File No: 2310045
GOST R: POCC GB.ГБ05.B03850
INMETRO: TÜV 11.0339X
Ex de I Mb
Ex de IIC Gb
Ex tb IIIC Db
Class I Div 2 ABCD
Class II Div 1 EFG
Temperature: -60ºC to +130ºC
Liquid Tight Hazardous Area Flameproof G1 Glands
Technical Specifications
ATEX Flameproof G1 Gland
Nickel Plated
Type - NPT
Conduit Size
Metric (mm)
Thread Size
NPT (inch)
1
/2
1
/2
3
/4
Nickel Plated
Type - Metric
Conduit Size
Metric (mm)
Thread Size
Metric (mm)
HAMM0304G1
16
20
HAAM0304G1
16
HAMM0404G1
20
20
HAAM0404G1
20
HAMM0505G1
25
25
HAAM0505G1
25
HAMM0606G1
32
32
HAAM0606G1
32
1
HAMM0707G1
40
40
HAAM0707G1
40
11/4
HAMM0808G1
50
50
HAAM0808G1
50
11/2
HAMM0909G1
63
63
HAAM0909G1
63
2
Brass
Type - Metric
Conduit Size
Metric (mm)
Thread Size
Metric (mm)
Conduit Size
Metric (mm)
Thread Size
NPT (inch)
1
/2
1
/2
3
/4
Brass
Type - NPT
HAM0304G1
16
20
HAA0304G1
16
HAM0404G1
20
20
HAA0404G1
20
HAM0505G1
25
25
HAA0505G1
25
HAM0606G1
32
32
HAA0606G1
32
1
HAM0707G1
40
40
HAA0707G1
40
11/4
HAM0808G1
50
50
HAA0808G1
50
11/2
HAM0909G1
63
63
HAA0909G1
63
2
Conduit Size
Metric (mm)
Thread Size
Metric (mm)
HAMS0304G1
16
20
HAAS0304G1
16
HAMS0404G1
20
20
HAAS0404G1
20
HAMS0505G1
25
25
HAAS0505G1
25
HAMS0606G1
32
32
HAAS0606G1
32
1
HAMS0707G1
40
40
HAAS0707G1
40
11/4
HAMS0808G1
50
50
HAAS0808G1
50
11/2
HAMS0909G1
63
63
HAAS0909G1
63
2
Stainless Steel
Type - Metric
Stainless Steel
Type - NPT
Conduit Size
Metric (mm)
Thread Size
NPT (inch)
1
/2
1
/2
3
/4
For Accessories see page 178-79
See page 148-153 for suitable conduits
Related Products
153
General Oil
Resistant
148
High Temperature
Conduit
150
Low Fire Flexible
Conduit
150
Sealing
Washers
178
www.tnb.com
A Member of the ABB Group
Liquid tight hazardous area flameproof G1 glands
Technical Specifications
ATEX Flameproof 90º Elbow Gland
Nickel Plated
Type - Metric
Conduit Size
Metric (mm)
Thread Size
Metric (mm)
Nickel Plated
Type - NPT
Conduit Size
Metric (mm)
HAMM0304E
16
20
HAAM0304E
HAMM0404E
20
20
HAAM0404E
20
HAMM0505E
25
25
HAAM0505E
25
16
Thread Size
NPT (inch)
1
/2
1
/2
3
/4
HAMM0606E
32
32
HAAM0606E
32
1
HAMM0707E
40
40
HAAM0707E
40
11/4
HAMM0808E
50
50
HAAM0808E
50
11/2
HAMM0909E
63
63
HAAM0909E
63
2
Conduit Size
Metric (mm)
Thread Size
Metric (mm)
Brass
Type - NPT
Conduit Size
Metric (mm)
HAM0304E
16
20
HAA0304E
HAM0404E
20
20
HAA0404E
20
HAM0505E
25
25
HAA0505E
25
Thread Size
NPT (inch)
1
/2
1
/2
3
/4
Brass
Type - Metric
16
HAM0606E
32
32
HAA0606E
32
1
HAM0707E
40
40
HAA0707E
40
11/4
HAM0808E
50
50
HAA0808E
50
11/2
HAM0909E
63
63
HAA0909E
63
2
Stainless Steel gland available but elbow is Nickel Plated
Elbow supplied is for liquid tight conduit only
For Accessories see page 178-79
See page 148-151 for suitable conduits
Related Products
154
General Oil
Resistant
www.tnb-hazardous.com
148
High Temperature
Conduit
150
Low Fire Flexible
Conduit
150
Sealing
Washers
178
Liquid Tight Hazardous Area Flameproof Universal Glands
Universal Glands
Liquid tight hazardous area
flameproof glands
Approvals / Characteristics
Features
• Constructed from either Brass or Stainless Steel with
an epoxy resin barrier
• The Group I Universal Flameproof Gland is a high specification
product, ideal for all hazardous area applications
Certification & Standards
I
DIV
1
DIV
2
DIV
1
EC TYPE Examination Certificate:
ATEX: Sira 09 ATEX 1231X
IECEx: IECEx SIR09.0103X
CSA: CSA File No: 2310045
GOST R: POCC GB.ГБ05.B03850
INMETRO: TÜV 11.0339X
Ex de I Mb
Ex de IIC Gb
Ex tb IIIC Db
Class I DIv 1 BCD (Rigid conduit only)
Class I Div 2 ABCD
Class II Div 1 ABCD
Temperature: -60ºC to +130ºC
155
www.tnb.com
A Member of the ABB Group
Liquid tight hazardous area flameproof Universal glands
Technical Specifications
THREAD B
Dimensions
THREAD A
THREAD B
THREAD A
HAA 03 04 U
HAM 03 04 U
Thread A = M16
Thread B = M20
Thread A = 3/8” NPT
Thread B = 1/2” NPT
Universal Gland
Nickel Plated
Type - Metric
Male Thread Size
Metric (mm)
Female Thread Size
Metric (mm)
HAMM0304U
20
16
HAAM0304U
HAMM0404U
20
20
HAAM0404U
HAMM0505U
25
25
HAAM0505U
HAMM0606U
32
32
HAAM0606U
1
1
HAMM0707U
40
40
HAAM0707U
11/4
11/4
HAMM0808U
50
50
HAAM0808U
11/2
11/2
HAMM0909U
63
63
HAAM0909U
2
2
Male Thread Size
Metric (mm)
Female Thread Size
Metric (mm)
Brass
Type - NPT
HAM0304U
20
16
HAA0304U
HAM0404U
20
20
HAA0404U
HAM0505U
25
25
HAA0505U
Male Thread Size
NPT (inch)
1
/2
1
/2
3
/4
Female Thread Size
NPT (inch)
3
/8
1
/2
3
/4
HAM0606U
32
32
HAA0606U
1
1
HAM0707U
40
40
HAA0707U
11/4
11/4
HAM0808U
50
50
HAA0808U
11/2
11/2
HAM0909U
63
63
HAA0909U
2
2
Male Thread Size
Metric (mm)
Female Thread Size
Metric (mm)
HAMS0304U
20
16
HAAS0304U
HAMS0404U
20
20
HAAS0404U
HAMS0505U
25
25
HAAS0505U
Male Thread Size
NPT (inch)
1
/2
1
/2
3
/4
Female Thread Size
NPT (inch)
3
/8
1
/2
3
/4
HAMS0606U
32
32
HAAS0606U
1
1
HAMS0707U
40
40
HAAS0707U
11/4
11/4
HAMS0808U
50
50
HAAS0808U
11/2
11/2
HAMS0909U
63
63
HAAS0909U
2
2
Brass
Type - Metric
Stainless Steel
Type - Metric
156
For use with Rigid conduit or other fittings
www.tnb-hazardous.com
Nickel Plated
Type - NPT
Stainless Steel
Type - NPT
Male Thread Size
NPT (inch)
1
/2
1
/2
3
/4
Female Thread Size
NPT (inch)
3
/8
1
/2
3
/4
Liquid Tight Hazardous Area Flameproof Universal Glands
Technical Specifications
Dimensions
THREAD B
THREAD A
THREAD B
HAM 03 04 U/SW
Thread A = M16
THREAD A
HAA 03 04 U/SW
Thread B = M20
Thread A = 3/8” NPT
Thread B = 1/2” NPT
Universal Swivel Gland
Nickel Plated
Type - Metric
Male Thread Size
Metric (mm)
Female Thread Size
Metric (mm)
Nickel Plated
Type - NPT
HAMM0304U/SW
20
16
HAAM0304U/SW
HAMM0404U/SW
20
20
HAAM0404U/SW
HAMM0505U/SW
25
25
HAAM0505U/SW
HAMM0606U/SW
32
32
HAAM0606U/SW
1
1
HAMM0707U/SW
40
40
HAAM0707U/SW
11/4
11/4
HAMM0808U/SW
50
50
HAAM0808U/SW
11/2
11/2
HAMM0909U/SW
63
63
HAAM0909U/SW
2
2
Brass
Type - Metric
Male Thread Size
Metric (mm)
Female Thread Size
Metric (mm)
HAM0304U/SW
20
16
HAA0304U/SW
HAM0404U/SW
20
20
HAA0404U/SW
HAM0505U/SW
25
25
HAA0505U/SW
Male Thread Size
NPT (inch)
1
/2
1
/2
3
/4
Female Thread Size
NPT (inch)
3
/8
1
/2
3
/4
HAM0606U/SW
32
32
HAA0606U/SW
1
1
HAM0707U/SW
40
40
HAA0707U/SW
11/4
11/4
HAM0808U/SW
50
50
HAA0808U/SW
11/2
11/2
HAM0909U/SW
63
63
HAA0909U/SW
2
2
For use with Rigid conduit or other fittings
Brass
Type - NPT
Male Thread Size
NPT (inch)
1
/2
1
/2
3
/4
Female Thread Size
NPT (inch)
3
/8
1
/2
3
/4
For Accessories see page 178-79
Related Products
157
Sealing
Washers
178
www.tnb.com
A Member of the ABB Group
Group II Gland
Liquid tight hazardous area flameproof gland
Approvals / Characteristics
Features
• Constructed from either Brass or Stainless Steel
with an epoxy resin barrier the Group II Flameproof
Gland is a high specification product, ideal for all
hazardous area applications
Certification & Standards
EC TYPE Examination Certificate:
Baseefa 06 ATEX 0256X
IECEx BAS06.0059X
Ex d IIC
Ex e II
Ex tD A21
Temperature: -60ºC to +80ºC
158
www.tnb-hazardous.com
Liquid Tight Hazardous Area Flameproof Group II Gland
Technical Specifications
ATEX Flameproof Group II Gland
Nickel Plated
Type - Metric
Conduit Size
Metric (mm)
Thread Size
Metric (mm)
HAMM0304
16
20
HAAM0304
HAMM0404
20
20
HAAM0404
20
HAMM0505
25
25
HAAM0505
25
HAMM0606
32
32
HAAM0606
32
1
HAMM0707
40
40
HAAM0707
40
11/4
HAMM0808
50
50
HAAM0808
50
11/2
HAMM0909
63
63
HAAM0909
63
2
*See page 140-143 for suitable conduits
Brass
Type - Metric
Nickel Plated
Type - NPT
Conduit Size
Metric (mm)
16
Thread Size
NPT (inch)
1
/2
1
/2
3
/4
*See page 140-143 for suitable conduits
Conduit Size
Metric (mm)
Thread Size
Metric (mm)
HAM0304
16
20
HAA0304
HAM0404
20
20
HAA0404
20
HAM0505
25
25
HAA0505
25
HAM0606
32
32
HAA0606
32
1
HAM0707
40
40
HAA0707
40
11/4
HAM0808
50
50
HAA0808
50
11/2
HAM0909
63
63
HAA0909
63
2
*See page 140-143 for suitable conduits
Stainless Steel
Type - Metric
Brass
Type - NPT
Conduit Size
Metric (mm)
16
Thread Size
NPT (inch)
1
/2
1
/2
3
/4
*See page 140-143 for suitable conduits
Conduit Size
Metric (mm)
Thread Size
Metric (mm)
HAMS0304
16
20
HAAS0304
16
HAMS0404
20
20
HAAS0404
20
HAMS0505
25
25
HAAS0505
25
HAMS0606
32
32
HAAS0606
32
1
HAMS0707
40
40
HAAS0707
40
11/4
HAMS0808
50
50
HAAS0808
50
11/2
HAMS0909
63
63
HAAS0909
63
2
*See page 140-143 for suitable conduits
Stainless Steel
Type - NPT
Conduit Size
Metric (mm)
Thread Size
NPT (inch)
1
/2
1
/2
3
/4
*See page 140-143 for suitable conduits
For Accessories see page 178-79
Related Products
159
General Oil
Resistant
148
High Temperature
Conduit
150
Low Fire Flexible
Conduit
148
Sealing
Washers
178
www.tnb.com
A Member of the ABB Group
XP Flex™ Range
Explosion-proof flexible couplings
Approvals / Characteristics
Features
• UL Listed for use in hazardous and wet locations
• Corrosion-resistant - ideal for washdown areas
• Flexible bronze construction with arc-resistant inner
DIV
I
1
DIV
1
DIV
2
sleeve and brass fittings
• Terminated with two threaded female end fittings
and male close nipples
• No bonding jumper required
Certification & Standards
UL Listed and CSA Certified for Hazardous Locations:
0.5” and 0.75” Hub Sizes: Class I Div 1 & 2 ABCD;
Class II Div 1 EFG, Class III
1” Hub Size: Class I Div 1 & 2 CD;
Class II Div 1 EFG, Class III
UL Listed 886
160
www.tnb-hazardous.com
Explosion-Proof Flexible Couplings - XP Flex™ Range
Technical Specifications
Dimensions
B
A
Flexible
Length
NPT
Threads
Type
Flexible Length (mm)
XPLFL236
Thread Type (inch)
1
/2” NPT
1
/2” NPT
1
/2” NPT
1
/2” NPT
1
/2” NPT
1
/2” NPT
1
/2” NPT
3
/4” NPT
3
/4” NPT
3
/4” NPT
3
/4” NPT
3
/4” NPT
XPLFL318
1” NPT
XPLFL16
XPLFL18
XPLFL110
XPLFL112
XPLFL115
XPLFL118
XPLFL124
XPLFL212
XPLFL215
XPLFL218
XPLFL224
Dimensions (mm)
A
B
150
39.1
36.6
200
39.1
36.6
250
39.1
36.6
300
39.1
36.6
380
39.1
36.6
460
39.1
36.6
610
39.1
36.6
300
40.6
47.5
380
40.6
47.5
460
40.6
47.5
610
40.6
47.5
915
40.6
47.5
460
50.08
58.7
Explosion-Proof and Dust- Ignition-Proof for
Use in Hazardous Locations
With their flexible design, T&B® XP FlexTM Couplings
make it easy to achieve tight bends in conduit
systems in confined spaces - or to connect stationary
equipment to equipment that moves or vibrates.
Their explosion-proof and corrosion-resistant
construction mean you can use them with confidence
in hazardous and wet locations.
Related Products
161
Enlargers,
Reducers & Thread
Convertors
170
Locknuts
178
Sealing
Washers
178
www.tnb.com
A Member of the ABB Group
Ex d Double Compression Cable Gland
4 Function double compression cable gland
Approvals / Characteristics
Features
• Flameproof Ex d and increased safety Ex e
• Available in Brass, Nickel Plated Brass and
Stainless Steel 316
• Deluge proof
• Wide range of cable sizes
Certification & Standards
8
162
www.tnb-hazardous.com
Approved to: EN 60079-0, 60079-1, 60079-7, 60079-31
EC TYPE Examination Certificate:
CESI 13 ATEX 041X, IECEx CES 13.0014X
Ex d IIC Gb
Ex e IIC Gb
Ex tb IIIC Db
Temperature:
-30°C to +120°C NBR sealing ring
-40°C to +100°C Neoprene sealing ring
-60°C to +180°C Silicon sealing ring
Ex d Double Compression Cable Gland
Technical Specifications
Dimensions
L
1. Lower Body
2. Lower Sealing Ring
3. O-Ring
4. Grounding Cone
5. Swivel Braid Retainer
6. Midlle Body
7. Upper Sealing Ring
8. Pressure Cap
M
Position
Marking
CH3
D
D1
1
Brass Metric
Type
Metric Size
H
CH2
CH1
Sealings Range
D (min-max) D1 (min-max)
3
H Min
2
3
4
5 3
6
7
D2
8
Cable Gland Dimensions
L Min
CH1
CH2
CH3
D2 Min
Torque (Nm)
CH2
CH3
EX03MSC1
M16
3 - 8.5
6 - 12
47
16
22
26
26
29
27.0
25.0
EX03MMC1
M16
6 - 12
8.5 - 16
48
16
25
29
29
31.5
49.0
28.0
EX04MSC1
M20
3 - 8.5
6 - 12
47
16
24
26
26
29
27.0
25.0
EX04MMC1
M20
6 - 12
8.5 - 16
47
16
25
29
29
31.5
49.0
28.0
EX04MLC1
M20
12 - 14.5
16 - 20
50
16
28
30
32
35
33.0
33.0
EX05MSC1
M25
6 - 12
8.5 - 16
48
18
29
29
29
31.5
49.0
28.0
EX05MMC1
M25
12 - 16
16 - 21
53
18
32
34
34
37
30.0
27.0
EX05MLC1
M25
12 - 20
16 - 26
60
18
36
40
40
44
61.0
32.0
EX06MSC1
M32
12 - 20
16 - 26
62
18
40
40
40
44
61.0
32.0
EX06MMC1
M32
15 - 26
20 - 33
78
18
48
52
52
57
86.0
40.0
EX07MSC1
M40
15 - 26
20 - 33
78
18
48
52
52
57
86.0
40.0
EX07MMC1
M40
20 - 32
29 - 41
89
18
55
60
60
66
110.0
75.0
EX08MSC1
M50
22 - 35
33 - 48
97
18
60
70
75
82
110.0
75.0
EX08MMC1
M50
27 - 41
36 - 52
100
18
70
70
74
83
125.0
75.0
EX09MSC1
M63
35 - 45
43 - 57
106
20
75
80
80
89.5
160.0
140.0
EX09MMC1
M63
40 - 52
47 - 60
107
20
85
85
85
94
250.0
100.0
EX10MSC1
M75
40 - 52
47 - 60
107
20
85
85
85
94
250.0
100.0
EX10MMC1
M75
45 - 60
54 - 70
125
20
90
95
100
110.5
250.0
150.0
EX11MSC1
M90
45 - 60
54 - 70
125
20
95
95
100
110.5
250.0
150.0
EX11MMC1
M90
60 - 72
63 - 80
154
20
110
115
115
127
320.0
210.0
Brass NPT
Type
Sealings Range
D (min-max) D1 (min-max)
12 - 20
16 - 26
60
21
36
40
40
44
61.0
32.0
EX06ASC1
1”
12 - 20
16 - 26
62
26
40
40
40
44
61.0
32.0
EX06AMC1
1”
15 - 26
20 - 33
78
26
48
52
52
57
86.0
40.0
EX07ASC1
1 1/4”
15 - 26
20 - 33
78
28
48
52
52
57
86.0
40.0
EX07AMC1
1 1/4”
20 - 32
29 - 41
89
28
55
60
60
66
110.0
75.0
EX08ASC1
1 1/2”
22 - 35
33 - 48
97
28
60
70
75
82
110.0
75.0
EX08AMC1
1 1/2”
27 - 41
36 - 52
100
28
70
70
74
83
125.0
75.0
EX09ASC1
2”
35 - 45
43 - 57
106
28
75
80
80
89.5
160.0
140.0
EX03AMC1
EX04ASC1
EX04AMC1
EX04ALC1
EX05ASC1
EX05AMC1
D2 Min
Torque (Nm)
CH2
CH3
EX05ALC1
EX03ASC1
H Min
Cable Gland Dimensions
L Min
CH1
CH2
CH3
NPT (inch)
3
/8”
3
/8”
1
/2”
1
/2”
1
/2”
3
/4”
3
/4”
3
/4”
3 - 8,5
6 - 12
47
16
22
26
26
29
27.0
6 - 12
8.5 - 16
48
16
25
29
29
31.5
49.0
25.0
28.0
3 - 8.5
6 - 12
47
21
24
26
26
29
27.0
25.0
6 - 12
8.5 - 16
47
21
25
29
29
31.5
49.0
28.0
12 - 14.5
16 - 20
50
21
28
30
32
35
33.0
33.0
6 - 12
8.5 - 16
48
21
29
29
29
31.5
49.0
28.0
12 - 16
16 - 21
53
21
32
34
34
37
30.0
27.0
EX09AMC1
2”
40 - 52
47 - 60
107
28
85
85
85
94
250.0
100.0
EX10ASC1
2 1/2”
40 - 52
47 - 60
107
41
85
85
85
94
250.0
100.0
EX10AMC1
2 1/2”
45 - 60
54 - 70
125
41
90
95
100
110.5
250.0
150.0
EX11ASC1
3”
45 - 60
54 - 70
125
43
95
95
100
110.5
250.0
150.0
EX11AMC1
3”
60 - 72
63 - 80
154
43
110
115
115
127
320.0
210.0
163
*For Nickel Plated Brass version, add N to the reference, e.g. EXN03MSC1 for Metric / EXN03ASC1 for NPT
**For Stainless Steel 316 version, add S to the reference, e.g. EXS03MSC1 for Metric / EXS03ASC1 for NPT
Connector Description: EX - Brass / EXN - Nickel Plated Brass / EXS - Stainless Steel 316
www.tnb.com
A Member of the ABB Group
Ex d Single Compression Cable Gland
Single compression cable gland
Approvals / Characteristics
Features
• Flameproof Ex d and increased safety Ex e
• Available in Brass, Nickel Plated Brass and
Stainless Steel 316
• Deluge proof
• Wide range of cable sizes
Certification & Standards
8
164
www.tnb-hazardous.com
Approved to: EN 60079-0, 60079-1, 60079-7, 60079-31
EC TYPE Examination Certificate:
CESI 13 ATEX 041X, IECEx CES 13.0014X
Ex d IIC Gb
Ex e IIC Gb
Ex tb IIIC Db
Temperature:
-30°C to +120°C NBR sealing ring
-40°C to +100°C Neoprene sealing ring
-60°C to +180°C Silicon sealing ring
Ex d Single Compression Cable Gland
Technical Specifications
Dimensions
L
M
Metric Size
CH2
D1
D
1
Brass Metric
Type
Position
marking
H
CH1
2
Sealings Range
D (min-max)
H Min
3
4
L Min
Cable Gland Dimensions
CH1
CH2
D1 Min
Torque (Nm)
EX03MMC3
M16
28.5
25.0
29.0
31.5
6 - 12
35
16
EX04MSC3
M20
27.5
25
29
31.5
6 - 12
35
16
EX04MMC3
M20
29
28
30
33.5
6 - 12
33
16
EX05MSC3
M25
28.5
29
29
31.5
12 - 14.5
35
18
EX05MMC3
M25
28.5
32
35
37
6 - 12
30
18
EX05MLC3
M25
32.5
36
40
44.5
6 - 12
61
18
EX06MSC3
M32
33.5
40
40
44.5
12 - 16
61
18
EX06MMC3
M32
41
48
52
57
12 - 20
86
18
EX07MSC3
M40
41
48
52
57
15 - 26
86
18
EX07MMC3
M40
50
55
60
66
15 - 26
110
18
EX08MSC3
M50
50.5
60
70
77
20 - 32
110
18
EX08MMC3
M50
54
70
70
77
22 - 35
125
18
EX09MSC3
M63
61.5
75
80
89.5
27 - 41
165
20
EX09MMC3
M63
61.5
85
85
94
35 - 45
250
20
EX10MSC3
M75
61.5
85
85
94
40 - 52
250
20
EX10MMC3
M75
72
90
95
105
40 - 52
250
20
EX11MSC3
M90
72
95
85
105
45 - 60
250
20
EX11MMC3
M90
84
110
115
127
60 - 72
300
20
Brass NPT
Type
EX06AMC3
NPT (inch)
3
/8”
1
/2”
1
/2”
3
/4”
3
/4”
3
/4”
3
/4”
EX07ASC3
1”
EX03AMC3
EX04ASC3
EX04AMC3
EX05ASC3
EX05ALC3
EX06ASC3
Sealings Range
D (min-max)
H Min
L Min
Cable Gland Dimensions
CH1
CH2
D1 Min
Torque (Nm)
28.5
25
29
31.5
6 - 12
35
16
27.5
25
29
31.5
6 - 12
35
21
29
28
30
33.5
12 - 14.5
33
21
28.5
29
29
31.5
6 - 12
35
21
32.5
36
40
44.5
12 - 20
61
21
33.5
40
40
44.5
12 - 20
61
26
41.0
48
52
57
15 - 26
86
26
41.0
48
52
57
15 - 26
86
28
EX07AMC3
1”
50
55
60
66
20 - 32
110
28
EX08ASC3
1 1/4”
50.5
60
70
77
22 - 35
110
28
EX08AMC3
2 1/4”
54
70
70
77
27 - 41
125
28
EX09ASC3
1 1/2”
61.5
75
80
89.5
35 - 45
165
28
EX09AMC3
1 1/2”
61.5
85
85
94
40 - 52
250
28
EX10ASC3
2”
61.5
85
85
94
40 - 52
250
41
EX10AMC3
2”
72
90
95
105
45 - 60
250
41
EX11ASC3
2 1/2”
72
95
95
105
45 - 60
250
43
EX11AMC3
3 1/2”
84
110
115
127
60 - 72
300
43
*For Nickel Plated Brass version, add N to the reference, e.g. EXN03MMC3 for Metric / EXN03AMC3 for NPT
**For Stainless Steel 316 version, add S to the reference, e.g. EXS03MMC3 for Metric / EXS03AMC3 for NPT
165
Connector Description: EX - Brass / EXN - Nickel Plated Brass / EXS - Stainless Steel 316
www.tnb.com
A Member of the ABB Group
Ex e Cable Gland
Single compression cable gland
Approvals / Characteristics
Features
• Flameproof Ex d and increased safety Ex e
• Available in Brass, Nickel Plated Brass and
Stainless Steel 316
• Large cable range within one product with
removeable seals
Certification & Standards
Approved to: EN 60079-0:2012, EN 60079-1:2007, EN 60079-7:2007,
EN 60079-11:2010, EN 60079-31:2009
EC TYPE Examination Certificate:
IMQ 13 ATEX 015X
II 2GD / Exe IIC Gb -30°C to +120°C
Ex tb IIIC Db
IP test: IP66
Temperature:
-30°C to +120°C NBR sealing ring
-40°C to +100°C Neoprene sealing ring
-60°C to +180°C Silicon sealing ring
166
www.tnb-hazardous.com
Ex e Cable Gland
Technical Specifications
Dimensions
P = Sealing Combination
1
L
S1
1. Sealing Ring
2. Cap
3. Body
H
M
P
S2
2
3
L1
S3
Position Marking
Brass Metric
Type
Cable Gland Dimensions
L Min
CH
L
S1
Torque (Nm)
EX03MMC2
M16
40
16
22
20
3 - 12
3-6
6-9
9 - 12
19
EX04MSC2
M20
40
16
22
20
3 -12
3-6
6-9
9 - 12
19
EX04MMC2
M20
45
16
28
20
10 - 16
–
10 - 14
14 - 16
28
EX05MSC2
M25
40
16
28
20
10 - 16
–
10 - 14
14 - 16
28
EX05MMC2
M25
50
16
35
25
14 - 20
–
14 - 17
17 - 20
31
EX06MSC2
M32
43
16
35
25
14 - 24
14 - 17
17 - 20
20 - 24
31
EX06MMC2
M32
53
16
45
39
22 - 28
–
22 - 26
26 - 28
26
EX07MSC2
M40
45
18
45
39
22 - 32
–
22 - 26
26 - 32
26
EX07MMC2
M40
55
18
50
32
26 - 34
–
26 - 32
32 - 34
58
EX08MSC2
M50
46
18
55 / 50
32
26 -35
–
26 - 30
30 - 35
58
EX08MMC2
M50
63
18
55 / 58
38
35 - 42
–
35 - 38
38 - 42
68
EX09MSC2
M63
53
18
68 / 58
38
35 - 45
–
35 - 38
38 - 45
60
EX09MMC2
M63
62
18
75 / 80
25
46 - 56
–
46 - 51
51 - 56
75
EX10MSC2
M75
64
20
80
25
46 - 62
46 - 51
51 - 57
57 - 62
75
EX10MMC2
M75
75
20
95
36
60 - 69
–
60 - 63
63 - 69
110
EX11MSC2
M90
75
20
95
36
60 - 75
60 - 63
63 - 69
69 - 75
110
EX11MMC2
M90
77
20
105
38
75 - 82
–
75 - 79
79 - 82
130
EX12MSC2
M100
77
20
115 / 105
38
75 - 85
75 - 79
79 - 82
82 - 85
130
EX12MMC2
M100
77
20
115
38
85 - 95
85 - 89
89 - 92
92 - 95
140
L
S1
Torque (Nm)
EX05AMC2
NPT (inch)
3
/8”
1
/2”
1
/2”
3
/4”
3
/4”
EX06ASC2
Brass NPT
Type
EX03AMC2
Cable Gland Dimensions
L Min
CH
H Min
Sealing Ring Dimensions
Min-Max S1+S2+S3 S1+S2
Metric Size
H Min
Sealing Ring Dimensions
Min-Max S1+S2+S3
S1+S2
40
16
22
20
3 - 12
3-6
6-9
9 - 12
19
40
16
22
20
3 -12
3-6
6-9
9 - 12
19
45
16
28
20
10 - 16
–
10 - 14
14 - 16
28
40
16
28
20
10 - 16
–
10 - 14
14 - 16
28
50
16
35
25
14 - 20
–
14 - 17
17 - 20
31
1”
47
20
35
25
14 - 24
14 - 17
17 - 20
20 - 24
31
EX06AMC2
1”
57
20
45
39
22 - 28
–
22 - 26
26 - 28
26
EX07ASC2
1 1/4”
47
20
45
39
22 - 32
–
22 - 26
26 - 32
26
EX07AMC2
1 1/4”
57
20
50
32
26 - 34
–
26 - 32
32 - 34
58
EX08ASC2
1 1/2”
48
20
55 / 50
32
26 -35
–
26 - 30
30 - 35
58
EX08AMC2
1 1/2”
65
20
55 / 58
38
35 - 42
–
35 - 38
38 - 42
60
EX09ASC2
2”
55
20
68 / 58
38
35 - 45
–
35 - 38
38 - 45
60
EX09AMC2
2”
64
20
75 / 80
25
46 - 56
–
46 - 51
51 - 56
75
EX10ASC2
2 1/2”
70
26
80
25
46 - 62
46 - 51
51 - 57
57 - 62
75
EX10AMC2
2 1/2”
81
26
95
36
60 - 69
–
60 - 63
63 - 69
110
EX11ASC2
3”
81
26
95
36
60 - 75
60 - 63
63 - 69
69 - 75
110
EX11AMC2
3”
83
26
105
38
75 - 82
–
75 - 79
79 - 82
130
EX12ASC2
4”
83
26
115 / 105
38
75 - 85
75 - 79
79 - 82
82 - 85
130
EX12AMC2
4”
83
26
115
38
85 - 95
85 - 89
89 - 92
92 - 95
140
EX04ASC2
EX04AMC2
EX05ASC2
*For Nickel Plated Brass version, add N to the reference, e.g. EXN03MMC2 for Metric / EXN03AMC2 for NPT
**For Stainless Steel 316 version, add S to the reference, e.g. EXS03MMC2 for Metric / EXS03AMC2 for NPT
167
Connector Description: EX - Brass / EXN - Nickel Plated Brass / EXS - Stainless Steel 316
www.tnb.com
A Member of the ABB Group
Nylon Cable Gland
Ex e nylon cable gland
Approvals / Characteristics
Features
• Suitable for potentially explosive gas atmospheres
• Increased safety “e” and intrinsic safety “i”
b
Certification & Standards
Approved to: EN 60079-0, 60079-7, 60079-11, 60079-31
EC TYPE Examination Certificate:
IMQ 13 ATEX 016X, IECEx IMQ 13.0005X
Ex e IIC Gb
Ex tb IIIC Db
IP test: IP66-IP68
Temperature: -20°C to +80°C
168
www.tnb-hazardous.com
Nylon Cable Gland
Technical Specifications
Dimensions
L
Cable
Glands
CH1 R
Case
Thickness
M CH
Flat washer
for IP protection
degree
Locknut
H
Type
Dimensions
H min
CH
Metric Size
Min - Max
L
CH1
Torque (Nm)
EXCGM20S
20
6,0 - 12,0
10
40
24
24
5
EXCGM20SL
20
6,0 - 12,0
15
45
24
24
5
EXCGM20M
20
10,0 - 14,0
10
42
27
27
5.5
EXCGM20ML
20
10,0 - 14,0
15
50
27
27
5.5
EXCGM25S
25
13,0 - 18,0
10
47
33
33
7
EXCGM25SL
25
13,0 - 18,0
15
50
33
33
7
EXCGM25M
25
11,0 - 17,0
8
42.5
29
29
5
EXCGM32S
32
15,0 - 21,0
10
50
36
36
6
EXCGM32M
32
18,0 - 25,0
15
68
42
42
9
EXCGM40S
40
19,0 - 28,0
10
55
46
46
5
EXCGM40M
40
22,0 - 32,0
18
68
53
53
17
EXCGM50S
50
30,0 - 38,0
18
73
60
60
22
EXCGM63S
63
34,0 - 44,0
18
74
65
65
23
Min - Max
L
CH1
Torque (Nm)
6 - 12
15
45
24
24
5
10 - 14
15
47
27
27
5.5
EXCG075S
NPT Size (inch)
1
/2”
1
/2”
3
/4”
13 - 18
15
50
33
33
7
EXCG100S
1”
18 - 25
18
58
42
42
9
Type
EXCG050S
EXCG050M
Dimensions
H min
CH
For Accessories see page 178-79
Related Products
169
EVS Range
42
XB100 Range 104
XBi Range
116
www.tnb.com
A Member of the ABB Group
Thread Convertors
Enlargers, reducers & convertors
Approvals / Characteristics
Features
• Adaptors and Reducers provide a method of
matching threadforms on hazardous approved
equipment whilst ensuring the integrity and approval
of the installation is maintained
b
Certification & Standards
DIV
I
1
170
www.tnb-hazardous.com
DIV
1
Certification Standard:
ATEX: Baseefa07 ATEX 0247X,
IECEx: IECEx BAS07.0090X
GOST R: POCC GB.ГБ05.B03850
INMETRO: TÜV 11.0339X
Ex d IIC Gb
Ex e IIC Gb
Ex tb IIIC Db
Class I Div1 ABCD, Class II Div1 EFG
(does not include M16 & 3/8”NPT or unplated brass products)
Approved to UL 1203
Approved to CSA C22.2 No.60079-04
Approved to C22.2 No.60079-1
Enlargers, Reducers & Thread Convertors
Metric - Technical Specification
Male
External
Thread
M16
M16
M20
M25
EX/M16-M20/E
EX/M16-M25/E
Metric Female Internal Thread
M32
M40
EX/M20-M25/E
M50
M63
M75
M20
EX/M20-M16/R
M25
EX/M25-M16/R
EX/M25-M20/R
EX/M20-M32/E
M32
EX/M32-M16/R
EX/M32-M20/R
EX/M32-M25/R
M40
EX/M40-M16/R
EX/M40-M20/R
EX/M40-M25/R
EX/M40-M32/R
M50
EX/M50-M16/R
EX/M50-M20/R
EX/M50-M25/R
EX/M50-M32/R
EX/M50-M40/R
M63
EX/M63-M16/R
EX/M63-M20/R
EX/M63-M25/R
EX/M63-M32/R
EX/M63-M40/R
EX/M63-M50/R
M75
EX/M75-M16/R
EX/M75-M20/R
EX/M75-M25/R
EX/M75-M32/R
EX/M75-M40/R
EX/M75-M50/R
PG9
EX/PG9-M16/TC
EX/PG9-M20/TC
PG11
EX/PG11-M16/TC
EX/PG11-M20/TC
PG13
EX/PG13-M16/TC
EX/PG13-M20/TC
PG16
EX/PG16-M16/TC
EX/PG16-M20/TC
PG21
EX/PG21-M16/TC
EX/PG21-M20/TC
EX/PG21-M25/TC
EX/PG21-M32/TC
PG29
EX/PG29-M16/TC
EX/PG29-M20/TC
EX/PG29-M25/TC
EX/PG29-M32/TC
EX/PG29-M40/TC
PG36
EX/PG36-M16/TC
EX/PG36-M20/TC
EX/PG36-M25/TC
EX/PG36-M32/TC
EX/PG36-M40/TC
EX/PG36-M50/TC
PG42
EX/PG42-M16/TC
EX/PG42-M20/TC
EX/PG42-M25/TC
EX/PG42-M32/TC
EX/PG42-M40/TC
EX/PG42-M50/TC
EX/PG42-M63/TC
PG48
EX/PG48-M16/TC
EX/PG48-M20/TC
EX/PG48-M25/TC
EX/PG48-M32/TC
EX/PG48-M40/TC
EX/PG48-M50/TC
EX/PG48-M63/TC
NPT 3/8
EX/038-M16/TC
NPT 1/2
EX/050-M16/TC
EX/050-M20/TC
EX/050-M25/TC
NPT 3/4
EX/075-M16/TC
EX/075-M20/TC
EX/075-M25/TC
EX/075-M32/TC
NPT 1
EX/100-M16/TC
EX/100-M20/TC
EX/100-M25/TC
EX/100-M32/TC
EX/100-M40/TC
NPT 1 1/4
EX/125-M16/TC
EX/125-M20/TC
EX/125-M25/TC
EX/125-M32/TC
EX/125-M40/TC
EX/125-M50/TC
NPT 1 1/2
EX/150-M16/TC
EX/150-M20/TC
EX/150-M25/TC
EX/150-M32/TC
EX/150-M40/TC
EX/150-M50/TC
EX/150-M63/TC
NPT 2
EX/200-M16/TC
EX/200-M20/TC
EX/200-M25/TC
EX/200-M32/TC
EX/200-M40/TC
EX/200-M50/TC
EX/200-M63/TC
NPT 2 1/2
EX/250-M16/TC
EX/250-M20/TC
EX/250-M25/TC
EX/250-M32/TC
EX/250-M40/TC
EX/250-M50/TC
NPT 3
EX/300-M16/TC
EX/300-M20/TC
EX/300-M25/TC
EX/300-M32/TC
EX/300-M40/TC
EX/300-M50/TC
EX/M25-M32/E
EX/M25-M40/E
EX/M32-M40/E
EX/M32-M50/E
EX/M40-M50/E
EX/M40-M63/E
EX/M50-M63/E
EX/M50-M75/E
EX/M63-M75/E
EX/M75-M63/R
EX/PG16-M25/TC
EX/300-M75/TC
*For Nickel Plated Brass version, add N to the reference, e.g. EXN/M20-M16/R
**For Stainless Steel 316 version, add S to the reference, e.g. EXS/M20-M16/R
Connector Description:
EX - Brass
EXN - Nickel Plated Brass
EXS - Stainless Steel 316
Our comprehensive range of Adaptors and
Reducers provide a method of matching
threadforms on hazardous area approved
equipment whilst ensuring the integrity and
approval of the installation is maintained.
Enlargers (/E) are used where the thread size of
the Female side of the device is larger than the
male side.
Reducers (/R) are used where the thread size of
the female side of device is smaller than the
male side.
Thread Converters (/TC) are used where a
conversion is required between thread types, e.g.
Metric to PG.
Kopex’s Enlargers, Reducers and thread converters
are designed for hazardous area applications
and are certified to protection concepts Exd
“Flameproof” and Exe “Increased Safety” for use
in Zone 1, 2, 2.1, 2.2 applications. Under NEC
Class I Div1 ABCD Class II Div1 EFG.
Manufactured in the UK, this new range of
converters meets the latest ATEX / IECEx & CSA /
UL standards. This means that all the standards are
marked on the product around the main body.
This allows for them to be seen easily once
installed, a key component of the new standard.
Related Products
171
EFDC Range
122
GUV Range
120
XB100 Range 104
www.tnb.com
A Member of the ABB Group
NPT - Technical Specification
Male
External
Thread
NPT 1/2
M16
EX/M16-050/TC
M20
EX/M20-050/TC
M25
EX/M25-050/TC
EX/M25-075/TC
EX/M25-100/TC
M32
EX/M32-050/TC
EX/M32-075/TC
EX/M32-100/TC
EX/M32-125/TC
M40
EX/M40-050/TC
EX/M40-075/TC
EX/M40-100/TC
EX/M40-125/TC
EX/M40-150/TC
M50
EX/M50-050/TC
EX/M50-075/TC
EX/M50-100/TC
EX/M50-125/TC
EX/M50-150/TC
M63
EX/M63-050/TC
EX/M63-075/TC
EX/M63-100/TC
EX/M63-125/TC
EX/M63-150/TC
EX/M63-200/TC
M75
EX/M75-050/TC
EX/M75-075/TC
EX/M75-100/TC
EX/M75-125/TC
EX/M75-150/TC
EX/M75-200/TC
PG9
EX/PG9-050/TC
PG11
EX/PG11-050/TC
PG13
EX/PG13-050/TC
PG16
EX/PG16-050/TC
PG21
EX/PG21-050/TC
EX/PG21-075/TC
EX/PG21-100/TC
PG29
EX/PG29-050/TC
EX/PG29-075/TC
EX/PG29-100/TC
EX/PG29-125/TC
EX/PG29-150/TC
PG36
EX/PG36-050/TC
EX/PG36-075/TC
EX/PG36-100/TC
EX/PG36-125/TC
EX/PG36-150/TC
NPT 1
NPT Female Internal Thread
NPT 1 1/4
NPT 1 1/2
NPT 2
NPT 2 1/2
NPT 3
EX/M20-075/TC
EX/M50-200/TC
EX/PG16-075/TC
PG42
EX/PG42-050/TC
EX/PG42-075/TC
EX/PG42-100/TC
EX/PG42-125/TC
EX/PG42-150/TC
EX/PG42-200/TC
PG48
EX/PG48-050/TC
EX/PG48-075/TC
EX/PG48-100/TC
EX/PG48-125/TC
EX/PG48-150/TC
EX/PG48-200/TC
NPT 1/2
172
NPT 3/4
EX/050-075/E
NPT 3/4
EX/075-050/R
NPT 1
EX/100-050/R
EX/100-075/R
NPT 1 1/4
EX/125-050/R
EX/125-075/R
EX/125-100/R
NPT 1 1/2
EX/150-050/R
EX/150-075/R
EX/150-100/R
EX/150-125/R
NPT 2
EX/200-050/R
EX/200-075/R
EX/200-100/R
EX/200-125/R
X/200-150/R
NPT 2 1/2
EX/250-050/R
EX/250-075/R
EX/250-100/R
EX/250-125/R
EX/250-150/R
EX/250-200/R
NPT 3
EX/300-050/R
EX/300-075/R
EX/300-100/R
EX/300-125/R
EX/300-150/R
EX/300-200/R
EX/075-100/E
EX/100-125/E
EX/125-150/E
*For Nickel Plated Brass version, add N to the reference, e.g. EXN/M20-M16/R
**For Stainless Steel 316 version, add S to the reference, e.g. EXS/M20-M16/R
www.tnb-hazardous.com
EX/150-200/E
EX/250-300/E
EX/300-250/R
Enlargers, Reducers & Thread Convertors
PG - Technical Specification
Male
External
Thread
PG9
M16
EX/M16-PG9/TC EX/M16-PG11/TC
EX/M16-PG13/TC
PG11
PG13
PG16
PG Female Internal Thread
PG21
PG29
PG36
PG42
PG48
M20
EX/M20-PG9/TC EX/M20-PG11/TC
EX/M20-PG13/TC
EX/M20-PG16/TC
M25
EX/M25-PG9/TC EX/M25-PG11/TC
EX/M25-PG13/TC
EX/M25-PG16/TC EX/M25-PG21/TC
M32
EX/M32-PG9/TC EX/M32-PG11/TC
EX/M32-PG13/TC
EX/M32-PG16/TC EX/M32-PG21/TC
EX/M32-PG29/TC
M40
EX/M40-PG9/TC EX/M40-PG11/TC
EX/M40-PG13/TC
EX/M40-PG16/TC EX/M40-PG21/TC
EX/M40-PG29/TC
EX/M40-PG36/TC
M50
EX/M50-PG9/TC EX/M50-PG11/TC
EX/M50-PG13/TC
EX/M50-PG16/TC EX/M50-PG21/TC
EX/M50-PG29/TC
EX/M50-PG36/TC EX/M50-PG42/TC
M63
EX/M63-PG9/TC EX/M63-PG11/TC
EX/M63-PG13/TC
EX/M63-PG16/TC EX/M63-PG21/TC
EX/M63-PG29/TC
EX/M63-PG36/TC EX/M63-PG42/TC
EX/M63-PG48/TC
M75
EX/M75-PG9/TC EX/M75-PG11/TC
EX/M75-PG13/TC
EX/M75-PG16/TC EX/M75-PG21/TC
EX/M75-PG29/TC
EX/M75-PG36/TC EX/M75-PG42/TC
EX/M75-PG48/TC
PG11
EX/PG11-PG9/R
PG13
EX/PG13-PG9/R
EX/PG13-PG11/R
PG16
EX/PG16-PG9/R
EX/PG16-PG11/R
EX/PG16-PG13/R
PG21
EX/PG21-PG9/R
EX/PG21-PG11/R
EX/PG21-PG13/R
EX/PG21-PG16/R
PG29
EX/PG29-PG9/R
EX/PG29-PG11/R
EX/PG29-PG13/R
EX/PG29-PG16/R
EX/PG29-PG21/R
PG36
EX/PG36-PG9/R
EX/PG36-PG11/R
EX/PG36-PG13/R
EX/PG36-PG16/R
EX/PG36-PG21/R
EX/PG36-PG29/R
PG42
EX/PG42-PG9/R
EX/PG42-PG11/R
EX/PG42-PG13/R
EX/PG42-PG16/R
EX/PG42-PG21/R
EX/PG42-PG29/R
EX/PG42-PG36/R
PG48
EX/PG48-PG9/R
EX/PG48-PG11/R
EX/PG48-PG13/R
EX/PG48-PG16/R
EX/PG48-PG21/R
EX/PG48-PG29/R
EX/PG48-PG36/R
NPT 1/2
EX/050-PG9/TC
EX/050-PG11/TC
EX/050-PG13/TC
EX/050-PG16/TC
NPT 3/4
EX/075-PG9/TC
EX/075-PG11/TC
EX/075-PG13/TC
EX/075-PG16/TC
EX/075-PG21/TC
NPT 1
EX/100-PG9/TC
EX/100-PG11/TC
EX/100-PG13/TC
EX/100-PG16/TC
EX/100-PG21/TC
NPT 1 1/4
EX/125-PG9/TC
EX/125-PG11/TC
EX/125-PG13/TC
EX/125-PG16/TC
EX/125-PG21/TC
EX/125-PG29/TC
EX/125-PG36/TC
NPT 1 1/2
EX/150-PG9/TC
EX/150-PG11/TC
EX/150-PG13/TC
EX/150-PG16/TC
EX/150-PG21/TC
EX/150-PG29/TC
EX/150-PG36/TC
EX/150-PG42/TC
NPT 2
EX/200-PG9/TC
EX/200-PG11/TC
EX/200-PG13/TC
EX/200-PG16/TC
EX/200-PG21/TC
EX/200-PG29/TC
EX/200-PG36/TC
EX/200-PG42/TC
EX/P16-PG21/E
EX/PG21-PG29/E
EX/PG29-PG36/E
EX/PG36-PG48/E
EX/PG42-PG48/E
EX/PG48-PG42/R
EX/100-PG29/TC
EX/200-PG48/TC
*For Nickel Plated Brass version, add N to the reference, e.g. EXN/M20-M16/R
**For Stainless Steel 316 version, add S to the reference, e.g. EXS/M20-M16/R
Connector Description:
EX - Brass
EXN - Nickel Plated Brass
EXS - Stainless Steel 316
Our comprehensive range of Adaptors and
Reducers provide a method of matching
threadforms on hazardous area approved
equipment whilst ensuring the integrity and
approval of the installation is maintained.
Enlargers (/E) are used where the thread size of
the Female side of the device is larger than the
male side.
Reducers (/R) are used where the thread size of
the female side of device is smaller than the
male side.
Thread Converters (/TC) are used where a
conversion is required between thread types, e.g.
Metric to PG.
Kopex’s Enlargers, Reducers and thread converters
are designed for hazardous area applications
and are certified to protection concepts Exd
“Flameproof” and Exe “Increased Safety” for use
in Zone 1, 2, 2.1, 2.2 applications. Under NEC
Class I Div1 ABCD Class II Div1 EFG.
Manufactured in the UK, this new range of
converters meets the latest ATEX / IECEx & CSA /
UL standards. This means that all the standards are
marked on the product around the main body.
This allows for them to be seen easily once
installed, a key component of the new standard.
Related Products
173
EFDC Range
122
GUV Range
120
XB100 Range 104
www.tnb.com
A Member of the ABB Group
Standard Ex d Stopping Plug
& Tamperproof Ex d Stopping Plug
Exd stopping plugs
Approvals / Characteristics
Features
• For use in potentially explosive atmospheres
• Manufactured from either Brass, Nickel Plated Brass
or Stainless Steel
Certification & Standards
I
DIV
1
174
www.tnb-hazardous.com
DIV
1
EC TYPE Examination Certificate:
ATEX: Baseefa 08 ATEX 6324
IECEx: IECEx BAS08.0109X
GOST R: POCC GB.ГБ05.B03850
INMETRO: TÜV 11.0093
UL 1203 (Nickel Plated Brass and Stainless Steel only)
Ex d I Mb
Ex d IIC Gb
Class I Div 1 ABCD
Class II Div 1 EFG
Temperature: -60ºC to +130ºC
Ex d Stopping Plugs
Technical Specifications
Standard Exd Stopping Plug
Nickel Plated
Type - Metric
Thread Size
Metric (mm)
Brass
Type - Metric
Thread Size
Metric (mm)
Stainless Steel
Type - Metric
Thread Size
Metric (mm)
EXN/M16/SP
16
EX/M16/SP
16
EXS/M16/SP
16
EXN/M20/SP
20
EX/M20/SP
20
EXS/M20/SP
20
EXN/M25/SP
25
EX/M25/SP
25
EXS/M25/SP
25
EXN/M32/SP
32
EX/M32/SP
32
EXS/M32/SP
32
EXN/M40/SP
40
EX/M40/SP
40
EXS/M40/SP
40
EXN/M50/SP
50
EX/M50/SP
50
EXS/M50/SP
50
EXN/M63/SP
63
EX/M63/SP
63
EXS/M63/SP
63
Nickel Plated
Type - NPT
EXN/038/SP
EXN/050/SP
EXN/075/SP
Thread Size
NPT (inch)
3
/8
1
/2
3
/4
Brass
Type - NPT
EX/038/SP
EX/050/SP
EX/075/SP
Thread Size
NPT (inch)
3
/8
1
/2
3
/4
Stainless Steel
Type - NPT
EXS/038/SP
EXS/050/SP
EXS/075/SP
Thread Size
NPT (inch)
3
/8
1
/2
3
/4
EXN/100/SP
1
EX/100/SP
1
EXS/100/SP
1
EXN/125/SP
11/4
EX/125/SP
11/4
EXS/125/SP
11/4
EXN/150/SP
11/2
EX/150/SP
11/2
EXS/150/SP
11/2
EXN/200/SP
2
EX/200/SP
2
EXS/200/SP
2
*Does not include M16 & 3/8 NPT or Unplated Brass products
Tamperproof Exd Stopping Plug
Nickel Plated
Type - Metric
Thread Size
Metric (mm)
Brass
Type - Metric
Thread Size
Metric (mm)
Stainless Steel
Type - Metric
Thread Size
Metric (mm)
EXN/M16/TSP
16
EX/M16/TSP
16
EXS/M16/TSP
16
EXN/M20/TSP
20
EX/M20/TSP
20
EXS/M20/TSP
20
EXN/M25/TSP
25
EX/M25/TSP
25
EXS/M25/TSP
25
EXN/M32/TSP
32
EX/M32/TSP
32
EXS/M32/TSP
32
EXN/M40/TSP
40
EX/M40/TSP
40
EXS/M40/TSP
40
EXN/M50/TSP
50
EX/M50/TSP
50
EXS/M50/TSP
50
EXN/M63/TSP
63
EX/M63/TSP
63
EXS/M63/TSP
63
Nickel Plated
Type - NPT
Brass
Type - NPT
EXN/075/TSP
Thread Size
NPT (inch)
3
/8
1
/2
3
/4
EX/075/TSP
Thread Size
NPT (inch)
3
/8
1
/2
3
/4
EXN/100/TSP
1
EX/100/TSP
1
EXS/100/TSP
1
EXN/125/TSP
11/4
EX/125/TSP
11/4
EXS/125/TSP
11/4
EXN/150/TSP
11/2
EX/150/TSP
11/2
EXS/150/TSP
11/2
EXN/200/TSP
2
EX/200/TSP
2
EXS/200/TSP
2
EXN/038/TSP
EXN/050/TSP
EX/038/TSP
EX/050/TSP
Stainless Steel
Type - NPT
EXS/038/TSP
EXS/050/TSP
EXS/075/TSP
Thread Size
NPT (inch)
3
/8
1
/2
3
/4
*Does not include M16 & 3/8 NPT or Unplated Brass products
Related Products
175
XFF Range
28
EJB Range
126
GUV Range
120
XEL Range
32
www.tnb.com
A Member of the ABB Group
Hex Head Ex e Stopping Plug /
Dome Head Ex e & Nylon Stopping Plug
Ex e & nylon stopping plugs
Approvals / Characteristics
Features
• For use in potentially explosive atmospheres
• Hex Head and Dome Head stopping plugs manufactured
from either Brass, Nickel Plated Brass or Stainless Steel
b
• Nylon Stopping Plug manufactured in Nylon only
Certification & Standards
Hex Head Exe Stopping Plug & Dome Head Stopping Plug
EC TYPE Examination Certificate:
ATEX: Baseefa 08 ATEX 0325X
IECEx: IECEx BAS08.0108X
GOST R: POCC GB.ГБ05.B03850
INMETRO: TÜV 11.0090
UL 1203 (Nickel Plated Brass and Stainless Steel only)
Ex e I Mb
Ex e IIC Gb
Ex tb IIIC Db
Temperature: -60ºC to +80ºC
176
www.tnb-hazardous.com
Ex e & Nylon Stopping Plugs
Technical Specifications
Hex Head Exe Stopping Plug
Nickel Plated
Type - Metric
Thread Size
Metric (mm)
Brass
Type - Metric
Thread Size
Metric (mm)
EXN/M16/HSP
16
EX/M16/HSP
16
EXS/M16/HSP
16
EXN/M20/HSP
20
EX/M20/HSP
20
EXS/M20/HSP
20
EXN/M25/HSP
25
EX/M25/HSP
25
EXS/M25/HSP
25
EXN/M32/HSP
32
EX/M32/HSP
32
EXS/M32/HSP
32
EXN/M40/HSP
40
EX/M40/HSP
40
EXS/M40/HSP
40
EXN/M50/HSP
50
EX/M50/HSP
50
EXS/M50/HSP
50
EXN/M63/HSP
63
EX/M63/HSP
63
EXS/M63/HSP
63
Stainless Steel
Type - Metric
Thread Size
Metric (mm)
*Does not include M16 & 3/8 NPT or Unplated Brass products
Dome Head Exe Stopping Plug
Nickel Plated
Type - Metric
Thread Size
Metric (mm)
Brass
Type - Metric
Thread Size
Metric (mm)
EXN/M16/DSP
16
EX/M16/DSP
16
EXS/M16/DSP
16
EXN/M20/DSP
20
EX/M20/DSP
20
EXS/M20/DSP
20
EXN/M25/DSP
25
EX/M25/DSP
25
EXS/M25/DSP
25
EXN/M32/DSP
32
EX/M32/DSP
32
EXS/M32/DSP
32
EXN/M40/DSP
40
EX/M40/DSP
40
EXS/M40/DSP
40
EXN/M50/DSP
50
EX/M50/DSP
50
EXS/M50/DSP
50
EXN/M63/DSP
63
EX/M63/DSP
63
EXS/M63/DSP
63
Stainless Steel
Type - Metric
Thread Size
Metric (mm)
*Does not include M16 & 3/8 NPT or Unplated Brass products
Nylon Stopping Plug
8
Nylon
Type - Metric
Thread Size
Metric (mm)
EX-M16
16
EX-M20
20
EX-M25
25
EX-M32
32
EX-M40
40
EX-M50
50
EX-M63
63
Certification & Standards
Nylon Stopping Plug
EC TYPE Examination Certificate:
IMQ 13 ATEX 016X, IECEx IMQ 13.0005X
Exe IIC Gb
Ex tb III Db
IP test: IP66-IP68
*Supplied with Locknut
Related Products
177
XFF Range
28
XB Range
112
GUV Range
120
EVS Range
42
www.tnb.com
A Member of the ABB Group
Accessories
Technical Specifications
Coupler - Female to Female thread couplers for use in both Exd and Exe applications
Nickel Plated
Type - Metric
Thread Size
Metric (mm)
Brass
Type - Metric
Thread Size
Metric (mm)
Stainless Steel
Type - Metric
Thread Size
Metric (mm)
EXN/M16/C
16
EX/M16/C
16
EXS/M16/C
16
EXN/M20/C
20
EX/M20/C
20
EXS/M20/C
20
EXN/M25/C
25
EX/M25/C
25
EXS/M25/C
25
EXN/M32/C
32
EX/M32/C
32
EXS/M32/C
32
EXN/M40/C
40
EX/M40/C
40
EXS/M40/C
40
EXN/M50/C
50
EX/M50/C
50
EXS/M50/C
50
EXN/M63/C
63
EX/M63/C
63
EXS/M63/C
63
EXN/M75/C
75
EX/M75/C
75
EXS/M75/C
75
Nickel Plated
Type - NPT
Thread Size
NPT (inch)
3
/8
1
/2
3
/4
EXN/038/C
EXN/050/C
EXN/075/C
Brass
Type - NPT
EX/038/C
EX/050/C
EX/075/C
Thread Size
NPT (inch)
3
/8
1
/2
3
/4
Stainless Steel
Type - NPT
Thread Size
NPT (inch)
3
/8
1
/2
3
/4
EXS/038/C
EXS/050/C
EXS/075/C
EXN/100/C
1
EX/100/C
1
EXS/100/C
1
EXN/125/C
11/4
EX/125/C
11/4
EXS/125/C
11/4
EXN/150/C
11/2
EX/150/C
11/2
EXS/150/C
11/2
EXN/200/C
2
EX/200/C
2
EXS/200/C
2
EXN/250/C
21/2
EX/250/C
21/2
EXS/250/C
21/2
*Does not include M16 & 3/8 NPT or Unplated Brass products
Certification Standard: Baseefa 08 ATEX 0359U
IECEx BAS08.0121U
TÜV11.0158U
Ex de IIC Gb
Ex tb IIIC Db
Temperature: -60°C to +200°C
Hex Locknut
Nickel Plated
Type - Metric
www.tnb-hazardous.com
Nickel Plated
Type - NPT
16
WHMM04
20
WHAM04
WHMM05
25
WHAM05
WHMM06
32
WHAM06
1
WHMM07
40
WHAM07
11/4
WHMM08
50
WHAM08
11/2
WHMM09
63
WHAM09
2
Thread Size
Metric (mm)
–
Thread Size
NPT (inch)
3
/8
1
/2
3
/4
WHMM03
Stainless Steel
Type - Metric
178
Thread Size
Metric (mm)
Brass
Type - Metric
Thread Size
Metric (mm)
–
16
WHMB03
16
MXWH04
20
WHMB04
20
MXWH05
25
WHMB05
25
MXWH06
32
WHMB06
32
MXWH07
40
WHMB07
40
MXWH08
50
WHMB08
50
–
63
–
63
Cable Glands, Sealing Washers & Locknuts - Accessories
Technical Specifications
Sealing Joint Washer - for use with all ATEX and IECEx approved products (Nylon only)
Thread Size
Metric (mm)
Outside
Diameter
(mm)
Thickness
(mm)
EXFM03*
16
22
1.6
EXFM03F
16
22
1.6
EXFM04*
20
26
1.6
EXFM04F
20
26
1.6
EXFM05*
25
34.3
1.7
EXFM05F
25
34.3
1.7
EXFM06*
32
41.5
1.7
EXFM06F
32
41.5
1.7
EXFM07*
40
52
2
EXFM07F
40
52
2
EXFM08*
50
66.5
2
EXFM08F
50
66.5
2
EXFM09*
63
84.5
2
Nylon
Type - Metric
Fibre
Type - Metric
Thread Size
Metric (mm)
Outside
Diameter
(mm)
Thickness
(mm)
Certification Standard: Nylon Metric approved
for use with all ATEX / IECEx product
Earth Tag - to be used to create an earthing bond on an enclosure, when a cable gland is used
Brass
Type - Metric
Thread Size
Metric (mm)
EX/M16/TAG
16
EX/M20/TAG
20
EX/M25/TAG
25
EX/M32/TAG
32
EX/M40/TAG
40
EX/M50/TAG
50
EX/M63/TAG
63
EX/M75/TAG
75
Serrated Washer
Steel
Type - Metric
Thread Size
Metric (mm)
EX/M16/SER
16
EX/M20/SER
20
EX/M25/SER
25
EX/M32/SER
32
EX/M40/SER
40
EX/M53/SER
50
EX/M63/SER
63
EX/M75/SER
75
Related Products
179
EFDC Range
122
GUV Range
120
XB100 Range 104
EVS Range
42
www.tnb.com
A Member of the ABB Group
Index
Part No.
180
621201
621500
4GRA00001S
4GRA00002S
4GRA00002S
4GRA00002S
B001
B001
B002
B004
B005B
B006L
B007
B008B
B008C
B009
B009A
B010B
B013
B013K
B014B
B015
BCP30
BCP40
BCP50
BEAVR-12/10
BEAVR-17/12
BEAVR-23/17
BEAVR-29/23
BEAVR-36/29
BEAVR-48/36
BEH-10-0
BEH-12-0
BEH-17-0
BEH-23-0
BEH-29-0
BEH-36-0
BEH-48-0
BENR-REM162-24
BENR-REM207-28
BENR-REM253-32
BENR-REM329-44
BENR-REM406-50
BENR-REM508-65
BESGR-1212
BESGR-1212
BESGR-1212
BESGR-1212
BESGR-1212
BESGR-1212
BETR-101010
BETR-121212
BETR-171717
BETR-232323
BETR-292929
BETR-363636
BETR-363636
www.tnb-hazardous.com
Page
56
56
93
92
93
94
93
94
93
94
94
94
94
94
94
94
94
94
94
94
94
94
132
132
132
146
146
146
146
146
146
147
147
147
147
147
147
147
146
146
146
146
146
146
145
145
145
145
145
145
145
145
145
145
145
145
145
Part No.
BEYR-121010
BEYR-171212
BEYR-231717
BEYR-292323
BEYR-362929
BEYR-483636
BP02
BP03
BP04
BP05
BP05V
BPN10
BPR10
BPV10
D001
D001
D002
D002
D002EM
D005
D005
D010
D010
D010
D016
D021C
D021C
D021C
D022
D022
D022
D023
D024
D025
D026
D027
DE01
DE02
DE03
DE04
DE05
DE10
E007
E008C
EF110G-00000
EF110P-00000
EF140G-00000
EF140P-00000
EFDC21
EFDC21F
EFDC21G
EFDC21P
EFDC21V
EFDC22
EFDC23
EFDC24
EFDC25
Page
145
145
145
145
145
145
132
132
132
132
132
132
132
132
92
94
92
93
94
92
94
92
93
94
94
92
93
94
92
93
94
90
90
90
90
90
132
132
132
132
132
132
93
93
75
75
75
75
123
123
123
123
123
123
123
123
123
Part No.
EFDC36
EFDC37
EFDC38
EFDC39
EFDC40
EFDC41
EFDC42
EFDC43
EFDC44
EJB0
EJB1
EJB11
EJB11-V1
EJB11-V2
EJB12
EJB13
EJB13-V1
EJB13-V2
EJB2
EJB2-V1
EJB2-V2
EJB2-V3
EJB2-V4
EJB4
EJB4-V1
EJB4-V2
EJB4-V3
EJB4-V5
EJB4-V6
EJB5
EJB8
EJB8-V1
EJB8-V2
EJB8-V3
EL120-0G000
EL220-0G000
EL30011-0G000
EL30028-0G000
EL3008-0G000
EL3009-0G000
ESB220-0000
ESB220-A000
ESB240-0000
ESB240-A000
ESB240EM-0000
ESB240EM-A000
ESB265-0000
ESB265-A000
EST220-00J0
EST220-A0J0
EST240-00J0
EST240-A0J0
EST240EM-00J0
EST240EM-A0J0
EST265-00J0
EST265-A0J0
EVD120-00J0
Page
123
123
123
123
123
123
123
123
123
127
127
127
131
131
127
127
131
131
127
131
131
131
131
127
131
131
131
131
131
127
127
131
131
131
73
73
73
73
73
73
49
49
49
49
67
67
49
49
79
79
79
79
89
89
79
79
47
Part No.
EVD120-D0J0
EVD120EM-00J0
EVD120EM-D0J0
EVD140-00J0
EVD140-D0J0
EVD140EM-00J0
EVD140EM-D0J0
EVD165-00J0
EVD165-D0J0
EVD220-00J0
EVD220-D0J0
EVD220EM-00J0
EVD220EM-D0J0
EVD240-00J0
EVD240-D0J0
EVD240EM-00J0
EVD240EM-D0J0
EVD265-00J0
EVD265-D0J0
EVN120-0000
EVN120-D000
EVN120EM-0000
EVN120EM-D000
EVN140-0000
EVN140-D000
EVN140EM-0000
EVN140EM-D000
EVN165-0000
EVN165-D000
EVN220-0000
EVN220-D000
EVN220EM-0000
EVN220EM-D000
EVN240-0000
EVN240-D000
EVN240EM-0000
EVN240EM-D000
EVN265-0000
EVS120-0000
EVS120-D000
EVS120EMA-0000
EVS120EMA-D000
EVS120EME-0000
EVS120EME-C000
EVS140-0000
EVS140-D000
EVS140EM-0000
EVS140EMA-0000
EVS140EMA-D000
EVS140EM-C000
EVS165-0000
EVS165-D000
EVS220-0000
EVS220-D000
EVS220EMA-0000
EVS220EMA-D000
EVS220EME-0000
Page
47
65
65
47
47
65
65
47
47
47
47
65
65
47
47
65
65
47
47
45
45
63
63
45
45
63
63
45
45
45
45
63
63
45
45
63
63
45
43
43
61
61
59
59
43
43
59
61
61
59
43
43
43
43
61
61
59
Part No.
EVS220EME-C000
EVS240-0000
EVS240-D000
EVS240EM-0000
EVS240EMA-D000
EVS240EM-C000
EVS265-0000
EVS265-D000
EVT120-A0J0
EVT120-D0J0
EVT120EM-00J0
EVT120EM-D0J0
EVT140-A0J0
EVT140-D0J0
EVT140EM-00J0
EVT140EM-D0J0
EVT165-A0J0
EVT165-D0J0
EVT220-A0J0
EVT220-D0J0
EVT220EM-00J0
EVT220EM-D0J0
EVT240-A0J0
EVT240EM-00J0
EVT240EM-D0J0
EVT265-A0J0
EVX100-00000
EVX200-00000
EVX300-00000
EVXlm40-00000
EVXlm50-00000
EVXna20-00000
EVXna30-00000
EVXna40-00000
EVXna50-00000
EX/038/SP
EX/038/TSP
EX/038-M16/TC
EX/050/SP
EX/050/TSP
EX/050-075/E
EX/050-M16/TC
EX/050-M20/TC
EX/050-M25/TC
EX/050-PG11/TC
EX/050-PG13/TC
EX/050-PG16/TC
EX/050-PG9/TC
EX/075/SP
EX/075/TSP
EX/075-050/R
EX/075-100/E
EX/075-M16/TC
EX/075-M20/TC
EX/075-M25/TC
EX/075-M32/TC
EX/075-PG11/TC
Page
59
43
43
59
61
59
43
43
77
77
87
87
77
77
87
87
77
77
77
77
87
87
77
87
87
77
98
98
98
103
103
99
99
99
99
175
175
171
175
175
172
171
171
171
173
173
173
173
175
175
172
172
171
171
171
171
173
Index
Part No.
EX/075-PG13/TC
EX/075-PG16/TC
EX/075-PG21/TC
EX/075-PG9/TC
EX/100/SP
EX/100/TSP
EX/100-050/R
EX/100-075/R
EX/100-125/E
EX/100-M16/TC
EX/100-M20/TC
EX/100-M25/TC
EX/100-M32/TC
EX/100-M40/TC
EX/100-PG11/TC
EX/100-PG13/TC
EX/100-PG16/TC
EX/100-PG21/TC
EX/100-PG29/TC
EX/100-PG9/TC
EX/125/SP
EX/125/TSP
EX/125-050/R
EX/125-075/R
EX/125-100/R
EX/125-150/E
EX/125-M16/TC
EX/125-M20/TC
EX/125-M25/TC
EX/125-M32/TC
EX/125-M40/TC
EX/125-M50/TC
EX/125-PG11/TC
EX/125-PG13/TC
EX/125-PG16/TC
EX/125-PG21/TC
EX/125-PG29/TC
EX/125-PG36/TC
EX/125-PG9/TC
EX/150/SP
EX/150/TSP
EX/150-050/R
EX/150-075/R
EX/150-100/R
EX/150-125/R
EX/150-200/E
EX/150-M16/TC
EX/150-M20/TC
EX/150-M25/TC
EX/150-M32/TC
EX/150-M40/TC
EX/150-M50/TC
EX/150-M63/TC
EX/150-PG11/TC
EX/150-PG13/TC
EX/150-PG16/TC
EX/150-PG21/TC
Page
173
173
173
173
175
175
172
172
172
171
171
171
171
171
173
173
173
173
173
173
175
175
172
172
172
172
171
171
171
171
171
171
173
173
173
173
173
173
173
175
175
172
172
172
172
172
171
171
171
171
171
171
171
173
173
173
173
Part No.
EX/150-PG29/TC
EX/150-PG36/TC
EX/150-PG42/TC
EX/150-PG9/TC
EX/200/SP
EX/200/TSP
EX/200-050/R
EX/200-075/R
EX/200-100/R
EX/200-125/R
EX/200-150/R
EX/200-M16/TC
EX/200-M20/TC
EX/200-M25/TC
EX/200-M32/TC
EX/200-M40/TC
EX/200-M50/TC
EX/200-M63/TC
EX/200-PG11/TC
EX/200-PG13/TC
EX/200-PG16/TC
EX/200-PG21/TC
EX/200-PG29/TC
EX/200-PG36/TC
EX/200-PG42/TC
EX/200-PG48/TC
EX/200-PG9/TC
EX/250-M50/TC
EX/300-M50/TC
EX/M16/C
EX/M16/DSP
EX/M16/HSP
EX/M16/SER
EX/M16/SP
EX/M16/TAG
EX/M16/TSP
EX/M16-038/TC
EX/M16-050/TC
EX/M16-M20/E
EX/M16-M25/E
EX/M16-PG11/TC
EX/M16-PG13/TC
EX/M16-PG9/TC
EX/M20/C
EX/M20/DSP
EX/M20/HSP
EX/M20/SER
EX/M20/SP
EX/M20/TAG
EX/M20/TSP
EX/M20-050/TC
EX/M20-075/TC
EX/M20-M16/R
EX/M20-M25/E
EX/M20-M32/E
EX/M20-PG11/TC
EX/M20-PG13/TC
Page
173
173
173
173
175
175
172
172
172
172
172
171
171
171
171
171
171
171
173
173
173
173
173
173
173
173
173
171
171
178
177
177
179
175
179
175
172
172
171
171
173
173
173
178
177
177
179
175
179
175
172
172
171
171
171
173
173
Part No.
EX/M20-PG16/TC
EX/M20-PG9/TC
EX/M25/C
EX/M25/DSP
EX/M25/HSP
EX/M25/SER
EX/M25/SP
EX/M25/TAG
EX/M25/TSP
EX/M25-050/TC
EX/M25-075/TC
EX/M25-100/TC
EX/M25-M16/R
EX/M25-M20/R
EX/M25-M32/E
EX/M25-M40/E
EX/M25-PG11/TC
EX/M25-PG13/TC
EX/M25-PG16/TC
EX/M25-PG21/TC
EX/M25-PG9/TC
EX/M32/C
EX/M32/DSP
EX/M32/HSP
EX/M32/SER
EX/M32/SP
EX/M32/TAG
EX/M32/TSP
EX/M32-050/TC
EX/M32-075/TC
EX/M32-100/TC
EX/M32-125/TC
EX/M32-M16/R
EX/M32-M20/R
EX/M32-M25/R
EX/M32-M40/E
EX/M32-M50/E
EX/M32-PG11/TC
EX/M32-PG13/TC
EX/M32-PG16/TC
EX/M32-PG21/TC
EX/M32-PG29/TC
EX/M32-PG9/TC
EX/M40/C
EX/M40/DSP
EX/M40/HSP
EX/M40/SER
EX/M40/SP
EX/M40/TAG
EX/M40/TSP
EX/M40-050/TC
EX/M40-075/TC
EX/M40-100/TC
EX/M40-125/TC
EX/M40-150/TC
EX/M40-M16/R
EX/M40-M20/R
Page
173
173
178
177
177
179
175
179
175
172
172
172
171
171
171
171
173
173
173
173
173
178
177
177
179
175
179
175
172
172
172
172
171
171
171
171
171
173
173
173
173
173
173
178
177
177
179
175
179
175
172
172
172
172
172
171
171
Part No.
EX/M40-M25/R
EX/M40-M32/R
EX/M40-M50/E
EX/M40-M63/E
EX/M40-PG11/TC
EX/M40-PG13/TC
EX/M40-PG16/TC
EX/M40-PG21/TC
EX/M40-PG29/TC
EX/M40-PG36/TC
EX/M40-PG9/TC
EX/M50/C
EX/M50/DSP
EX/M50/HSP
EX/M50/SER
EX/M50/SP
EX/M50/TAG
EX/M50/TSP
EX/M50-050/TC
EX/M50-075/TC
EX/M50-100/TC
EX/M50-125/TC
EX/M50-150/TC
EX/M50-200/TC
EX/M50-M16/R
EX/M50-M20/R
EX/M50-M25/R
EX/M50-M32/R
EX/M50-M40/R
EX/M50-M63/E
EX/M50-M75/E
EX/M50-PG11/TC
EX/M50-PG13/TC
EX/M50-PG16/TC
EX/M50-PG21/TC
EX/M50-PG29/TC
EX/M50-PG36/TC
EX/M50-PG42/TC
EX/M50-PG9/TC
EX/M63/C
EX/M63/DSP
EX/M63/HSP
EX/M63/SER
EX/M63/SP
EX/M63/TAG
EX/M63/TSP
EX/M63-050/TC
EX/M63-075/TC
EX/M63-100/TC
EX/M63-125/TC
EX/M63-150/TC
EX/M63-200/TC
EX/M63-M16/R
EX/M63-M20/R
EX/M63-M25/R
EX/M63-M32/R
EX/M63-M40/R
Page
171
171
171
171
173
173
173
173
173
173
173
178
177
177
179
175
179
175
172
172
172
172
172
172
171
171
171
171
171
171
171
173
173
173
173
173
173
173
173
178
177
177
179
175
179
175
172
172
172
172
172
172
171
171
171
171
171
Part No.
Page
EX/M63-M50/R
EX/M63-M75/E
EX/M63-PG11/TC
EX/M63-PG13/TC
EX/M63-PG16/TC
EX/M63-PG21/TC
EX/M63-PG29/TC
EX/M63-PG36/TC
EX/M63-PG42/TC
EX/M63-PG48/TC
EX/M63-PG9/TC
EX/M75/C
EX/M75/SER
EX/M75/TAG
EX/M75-050/TC
EX/M75-075/TC
EX/M75-100/TC
EX/M75-125/TC
EX/M75-150/TC
EX/M75-200/TC
EX/M75-M16/R
EX/M75-M20/R
EX/M75-M25/R
EX/M75-M32/R
EX/M75-M40/R
EX/M75-M50/R
EX/M75-M63/R
EX/M75-PG11/TC
EX/M75-PG13/TC
EX/M75-PG16/TC
EX/M75-PG21/TC
EX/M75-PG29/TC
EX/M75-PG36/TC
EX/M75-PG42/TC
EX/M75-PG48/TC
EX/M75-PG9/TC
EX/PG11/DSP
EX/PG11/HSP
EX/PG11/SP
EX/PG11/TSP
EX/PG11-050/TC
EX/PG11-M16/TC
EX/PG11-M20/TC
EX/PG11-PG9/R
EX/PG13/DSP
EX/PG13/HSP
EX/PG13/SP
EX/PG13/TSP
EX/PG13-050/TC
EX/PG13-M16/TC
EX/PG13-M20/TC
EX/PG13-PG11/R
EX/PG13-PG9/R
EX/PG16/DSP
EX/PG16/HSP
EX/PG16/SP
EX/PG16/TSP
171
171
173
173
173
173
173
173
173
173
173
178
179
179
172
172
172
172
172
172
171
171
171
171
171
171
171
173
173
173
173
173
173
173
173
173
177
177
175
175
172
171
171
173
177
177
175
175
172
171
171
173
173
177
177
175
175
181
www.tnb.com
A Member of the ABB Group
Index
Part No.
182
EX/PG16-050/TC
EX/PG16-075/TC
EX/PG16-M16/TC
EX/PG16-M20/TC
EX/PG16-M25/TC
EX/PG16-PG11/R
EX/PG16-PG13/R
EX/PG16-PG21/E
EX/PG16-PG9/R
EX/PG21/DSP
EX/PG21/HSP
EX/PG21/SP
EX/PG21/TSP
EX/PG21-075/TC
EX/PG21-100/TC
EX/PG21-M16/TC
EX/PG21-M20/TC
EX/PG21-M25/TC
EX/PG21-M32/TC
EX/PG21-PG11/R
EX/PG21-PG13/R
EX/PG21-PG16/R
EX/PG21-PG29/E
EX/PG21-PG9/R
EX/PG29/DSP
EX/PG29/HSP
EX/PG29/SP
EX/PG29/TSP
EX/PG29-050/TC
EX/PG29-075/TC
EX/PG29-100/TC
EX/PG29-125/TC
EX/PG29-150/TC
EX/PG29-M16/TC
EX/PG29-M20/TC
EX/PG29-M25/TC
EX/PG29-M32/TC
EX/PG29-M40/TC
EX/PG29-PG11/R
EX/PG29-PG13/R
EX/PG29-PG16/R
EX/PG29-PG21/R
EX/PG29-PG36/E
EX/PG29-PG9/R
EX/PG36/DSP
EX/PG36/HSP
EX/PG36/SP
EX/PG36/TSP
EX/PG36-050/TC
EX/PG36-075/TC
EX/PG36-100/TC
EX/PG36-125/TC
EX/PG36-150/TC
EX/PG36-M16/TC
EX/PG36-M20/TC
EX/PG36-M25/TC
EX/PG36-M32/TC
www.tnb-hazardous.com
Page
172
172
171
171
171
173
173
173
173
177
177
175
175
172
172
171
171
171
171
173
173
173
173
173
177
177
175
175
172
172
172
172
172
171
171
171
171
171
173
173
173
173
173
173
177
177
175
175
172
172
172
172
172
171
171
171
171
Part No.
EX/PG36-M40/TC
EX/PG36-M50/TC
EX/PG36-PG11/R
EX/PG36-PG13/R
EX/PG36-PG16/R
EX/PG36-PG21/R
EX/PG36-PG29/R
EX/PG36-PG48/E
EX/PG36-PG9/R
EX/PG42/DSP
EX/PG42/HSP
EX/PG42/SP
EX/PG42/TSP
EX/PG42-050/TC
EX/PG42-075/TC
EX/PG42-100/TC
EX/PG42-125/TC
EX/PG42-150/TC
EX/PG42-200/TC
EX/PG42-M16/TC
EX/PG42-M20/TC
EX/PG42-M25/TC
EX/PG42-M32/TC
EX/PG42-M40/TC
EX/PG42-M50/TC
EX/PG42-M63/TC
EX/PG42-PG11/R
EX/PG42-PG13/R
EX/PG42-PG16/R
EX/PG42-PG21/R
EX/PG42-PG29/R
EX/PG42-PG36/R
EX/PG42-PG48/E
EX/PG42-PG9/R
EX/PG48/DSP
EX/PG48/HSP
EX/PG48/SP
EX/PG48/TSP
EX/PG48-050/TC
EX/PG48-075/TC
EX/PG48-100/TC
EX/PG48-125/TC
EX/PG48-150/TC
EX/PG48-200/TC
EX/PG48-M16/TC
EX/PG48-M20/TC
EX/PG48-M25/TC
EX/PG48-M32/TC
EX/PG48-M40/TC
EX/PG48-M50/TC
EX/PG48-M63/TC
EX/PG48-PG11/R
EX/PG48-PG13/R
EX/PG48-PG16/R
EX/PG48-PG21/R
EX/PG48-PG29/R
EX/PG48-PG36/R
Page
171
171
173
173
173
173
173
173
173
177
177
175
175
172
172
172
172
172
172
171
171
171
171
171
171
171
173
173
173
173
173
173
173
173
177
177
175
175
172
172
172
172
172
172
171
171
171
171
171
171
171
173
173
173
173
173
173
Part No.
EX/PG48-PG42/R
EX/PG48-PG9/R
EX/PG9/DSP
EX/PG9/HSP
EX/PG9/SP
EX/PG9/TSP
EX/PG9-050/TC
EX/PG9-M16/TC
EX/PG9-M20/TC
EX02AMC3
EX02MMC3
EX03ALC3
EX03AMC1
EX03AMC2
EX03AMC3
EX03ASC1
EX03MLC3
EX03MMC1
EX03MMC2
EX03MMC3
EX03MSC1
EX04ALC2
EX04ALC3
EX04AMC1
EX04AMC2
EX04AMC3
EX04ASC1
EX04ASC3
EX04MLC1
EX04MLC1
EX04MLC2
EX04MLC3
EX04MMC1
EX04MMC2
EX04MMC3
EX04MSC1
EX04MSC3
EX05ALC2
EX05ALC3
EX05AMC1
EX05AMC2
EX05AMC3
EX05ASC1
EX05ASC3
EX05MLC1
EX05MLC1
EX05MLC2
EX05MLC3
EX05MMC1
EX05MMC2
EX05MMC3
EX05MSC1
EX05MSC3
EX06ALC2
EX06ALC3
EX06AMC1
EX06AMC2
Page
173
173
177
177
175
175
172
171
171
165
165
165
163
167
165
163
165
163
167
165
163
167
165
163
167
165
163
165
163
163
167
165
163
167
165
163
165
167
165
163
167
165
163
165
163
163
167
165
163
167
165
163
165
167
165
163
167
Part No.
EX06AMC3
EX06ASC1
EX06ASC3
EX06MLC2
EX06MLC3
EX06MMC1
EX06MMC2
EX06MMC3
EX06MSC1
EX06MSC3
EX07ALC2
EX07AM3
EX07AMC1
EX07AMC2
EX07ASC1
EX07MLC2
EX07MM3
EX07MMC1
EX07MMC2
EX07MSC1
EX08ALC2
EX08ALC3
EX08AMC1
EX08AMC2
EX08AMC3
EX08ASC1
EX08MLC2
EX08MLC3
EX08MMC1
EX08MMC2
EX08MMC3
EX08MSC1
EX09ALC2
EX09ALC3
EX09AMC1
EX09AMC2
EX09AMC3
EX09ASC1
EX09MLC2
EX09MLC3
EX09MMC1
EX09MMC2
EX09MMC3
EX09MSC1
EX10ALC2
EX10AMC1
EX10AMC2
EX10AMC3
EX10MLC2
EX10MMC1
EX10MMC2
EX10MMC3
EX10MSC1
EX10MSC1
EX11ALC3
EX11AMC1
EX11ASC1
Page
165
163
165
167
165
163
167
165
163
165
167
165
163
167
163
167
165
163
167
163
167
165
163
167
165
163
167
165
163
167
165
163
167
165
163
167
165
163
167
165
163
167
165
163
167
163
167
165
167
163
167
165
163
163
165
163
163
Part No.
EX11MLC3
EX11MMC1
EX11MSC1
EX12ALC2
EX12AMC1
EX12AMC2
EX12MLC2
EX12MMC1
EX12MMC2
EX13AMC2
EX13MMC2
EX14AMC1
EX14AMC2
EX14MMC1
EX14MMC2
EXB0310
EXB0330
EXB0350
EXB0410
EXB0430
EXB0450
EXB0510
EXB0530
EXB0550
EXB0610
EXB0630
EXB0650
EXB0710
EXB0730
EXB0750
EXB0810
EXB0830
EXB0850
EXBB0310
EXBB0410
EXBB0430
EXBB0450
EXBB0510
EXBB0530
EXBB0550
EXBB0610
EXBB0630
EXBB0650
EXBB0710
EXBB0810
EXBBT0110
EXBBT0130
EXBBT0210
EXBBT0230
EXBBT0310
EXBBT0330
EXBBT0410
EXBBT0430
EXBBT0450
EXBBT0510
EXBBT0530
EXBBT0550
Page
165
163
163
167
163
167
167
163
167
167
167
163
167
163
167
138
138
138
138
138
138
138
138
138
138
138
138
138
138
138
138
138
138
138
138
138
138
138
138
138
138
138
138
138
138
148
148
148
148
148
148
148
148
148
148
148
148
Index
Part No.
EXBBT0610
EXBBT0630
EXBBT0710
EXBBT0720
EXBBT0810
EXBBT0820
EXBBT0910
EXBBT0920
EXBQA0304
EXBQA0404
EXBQA0505
EXBQA0606
EXBQA0707
EXBQA0808
EXBQM0303
EXBQM0404
EXBQM0505
EXBQM0606
EXBQM0707
EXBQM0808
EXCG050M
EXCG050S
EXCG075S
EXCG100S
EXCGM16S
EXCGM16SL
EXCGM20M
EXCGM20ML
EXCGM20S
EXCGM20S
EXCGM20SL
EXCGM25M
EXCGM25SL
EXCGM32S
EXCGM32SL
EXCGM40M
EXCGM40S
EXCGM50S
EXCGM63S
EXFM03
EXFM03F
EXFM04
EXFM04F
EXFM05
EXFM05F
EXFM06
EXFM06F
EXFM07
EXFM07F
EXFM08
EXFM08F
EXLB0110
EXLB0130
EXLB0210
EXLB0230
EXLB0310
EXLB0330
Page
148
148
148
148
148
148
148
148
141
141
141
141
141
141
141
141
141
141
141
141
179
179
179
179
179
179
179
179
179
179
179
179
179
179
179
179
179
179
179
179
179
179
179
179
179
179
179
179
179
179
179
148
148
148
148
148
148
Part No.
EXLB0410
EXLB0430
EXLB0450
EXLB0510
EXLB0530
EXLB0550
EXLB0610
EXLB0630
EXLB0710
EXLB0720
EXLB0810
EXLB0820
EXLB0910
EXLB0920
EXLH0310
EXLH0330
EXLH0410
EXLH0430
EXLH0510
EXLH0530
EXLH0610
EXLH0620
EXLH0710
EXLH0720
EXLH0810
EXLH0820
EXLH0910
EXLH0920
EXLHC0310
EXLHC0330
EXLHC0410
EXLHC0430
EXLHC0510
EXLHC0530
EXLHC0610
EXLHC0630
EXLHC0710
EXLHC0810
EXLHC0820
EXLHC0910
EXLLH0310
EXLLH0330
EXLLH0410
EXLLH0430
EXLLH0510
EXLLH0530
EXLLH0610
EXLLH0620
EXLLH0710
EXLLH0720
EXLLH0810
EXLLH0820
EXLLH0910
EXLLH0920
EXLT0310
EXLT0330
EXLT0410
Page
148
148
148
148
148
148
148
148
148
148
148
148
148
148
149
149
149
149
149
149
149
149
149
149
149
149
149
149
149
149
149
149
149
149
149
149
149
149
149
149
149
149
149
149
149
149
149
149
149
149
149
149
149
149
150
150
150
Part No.
EXLT0430
EXLT0510
EXLT0530
EXLT0610
EXLT0620
EXLT0710
EXLT0720
EXLT0810
EXLT0820
EXLT0910
EXLT0920
EXLT0930
EX-M16
EX-M20
EX-M25
EX-M32
EX-M40
EX-M50
EX-M63
EXN/038/SP
EXN/038/TSP
EXN/038-M16/TC
EXN/050/SP
EXN/050/TSP
EXN/050-075/E
EXN/050-M16/TC
EXN/050-M20/TC
EXN/050-M25/TC
EXN/050-PG11/TC
EXN/050-PG13/TC
EXN/050-PG16/TC
EXN/050-PG9/TC
EXN/075/SP
EXN/075/TSP
EXN/075-050/R
EXN/075-100/E
EXN/075-M16/TC
EXN/075-M20/TC
EXN/075-M25/TC
EXN/075-M32/TC
EXN/075-PG11/TC
EXN/075-PG13/TC
EXN/075-PG16/TC
EXN/075-PG21/TC
EXN/075-PG9/TC
EXN/100/SP
EXN/100/TSP
EXN/100-050/R
EXN/100-075/R
EXN/100-125/E
EXN/100-M16/TC
EXN/100-M20/TC
EXN/100-M25/TC
EXN/100-M32/TC
EXN/100-M40/TC
EXN/100-PG11/TC
EXN/100-PG13/TC
Page
150
150
150
150
150
150
150
150
150
150
150
150
177
177
177
177
177
177
177
175
175
171
175
175
172
171
171
171
173
173
173
173
175
175
172
172
171
171
171
171
173
173
173
173
173
175
175
172
172
172
171
171
171
171
171
173
173
Part No.
EXN/100-PG16/TC
EXN/100-PG21/TC
EXN/100-PG29/TC
EXN/100-PG9/TC
EXN/125/SP
EXN/125/TSP
EXN/125-050/R
EXN/125-075/R
EXN/125-100/R
EXN/125-150/E
EXN/125-M16/TC
EXN/125-M20/TC
EXN/125-M25/TC
EXN/125-M32/TC
EXN/125-M40/TC
EXN/125-M50/TC
EXN/125-PG11/TC
EXN/125-PG13/TC
EXN/125-PG16/TC
EXN/125-PG21/TC
EXN/125-PG29/TC
EXN/125-PG36/TC
EXN/125-PG9/TC
EXN/150/SP
EXN/150/TSP
EXN/150-050/R
EXN/150-075/R
EXN/150-100/R
EXN/150-125/R
EXN/150-200/E
EXN/150-M16/TC
EXN/150-M20/TC
EXN/150-M25/TC
EXN/150-M32/TC
EXN/150-M40/TC
EXN/150-M50/TC
EXN/150-M63/TC
EXN/150-PG11/TC
EXN/150-PG13/TC
EXN/150-PG16/TC
EXN/150-PG21/TC
EXN/150-PG29/TC
EXN/150-PG36/TC
EXN/150-PG42/TC
EXN/150-PG9/TC
EXN/200/SP
EXN/200/TSP
EXN/200-050/R
EXN/200-075/R
EXN/200-100/R
EXN/200-125/R
EXN/200-150/R
EXN/200-M16/TC
EXN/200-M20/TC
EXN/200-M25/TC
EXN/200-M32/TC
EXN/200-M40/TC
Page
173
173
173
173
175
175
172
172
172
172
171
171
171
171
171
171
173
173
173
173
173
173
173
175
175
172
172
172
172
172
171
171
171
171
171
171
171
173
173
173
173
173
173
173
173
175
175
172
172
172
172
172
171
171
171
171
171
Part No.
Page
EXN/200-M50/TC
EXN/200-M63/TC
EXN/200-PG11/TC
EXN/200-PG13/TC
EXN/200-PG16/TC
EXN/200-PG21/TC
EXN/200-PG29/TC
EXN/200-PG36/TC
EXN/200-PG42/TC
EXN/200-PG48/TC
EXN/200-PG9/TC
EXN/250-M50/TC
EXN/300-M50/TC
EXN/M16/C
EXN/M16/DSP
EXN/M16/HSP
EXN/M16/SP
EXN/M16/TSP
EXN/M16-038/TC
EXN/M16-050/TC
EXN/M16-M20/E
EXN/M16-M25/E
EXN/M16-PG11/TC
EXN/M16-PG13/TC
EXN/M16-PG9/TC
EXN/M20/C
EXN/M20/DSP
EXN/M20/HSP
EXN/M20/SP
EXN/M20/TSP
EXN/M20-050/TC
EXN/M20-075/TC
EXN/M20-M16/R
EXN/M20-M25/E
EXN/M20-M32/E
EXN/M20-PG11/TC
EXN/M20-PG13/TC
EXN/M20-PG16/TC
EXN/M20-PG9/TC
EXN/M25/C
EXN/M25/DSP
EXN/M25/HSP
EXN/M25/SP
EXN/M25/TSP
EXN/M25-050/TC
EXN/M25-075/TC
EXN/M25-100/TC
EXN/M25-M16/R
EXN/M25-M20/R
EXN/M25-M32/E
EXN/M25-M40/E
EXN/M25-PG11/TC
EXN/M25-PG13/TC
EXN/M25-PG16/TC
EXN/M25-PG21/TC
EXN/M25-PG9/TC
EXN/M32/C
171
171
173
173
173
173
173
173
173
173
173
171
171
178
177
177
175
175
172
172
171
171
173
173
173
178
177
177
175
175
172
172
171
171
171
173
173
173
173
178
177
177
175
175
172
172
172
171
171
171
171
173
173
173
173
173
178
183
www.tnb.com
A Member of the ABB Group
Index
Part No.
184
EXN/M32/DSP
EXN/M32/HSP
EXN/M32/SP
EXN/M32/TSP
EXN/M32-050/TC
EXN/M32-075/TC
EXN/M32-100/TC
EXN/M32-125/TC
EXN/M32-M16/R
EXN/M32-M20/R
EXN/M32-M25/R
EXN/M32-M40/E
EXN/M32-M50/E
EXN/M32-PG11/TC
EXN/M32-PG13/TC
EXN/M32-PG16/TC
EXN/M32-PG21/TC
EXN/M32-PG29/TC
EXN/M32-PG9/TC
EXN/M40/C
EXN/M40/DSP
EXN/M40/HSP
EXN/M40/SP
EXN/M40/TSP
EXN/M40-050/TC
EXN/M40-075/TC
EXN/M40-100/TC
EXN/M40-125/TC
EXN/M40-150/TC
EXN/M40-M16/R
EXN/M40-M20/R
EXN/M40-M25/R
EXN/M40-M32/R
EXN/M40-M50/E
EXN/M40-M63/E
EXN/M40-PG11/TC
EXN/M40-PG13/TC
EXN/M40-PG16/TC
EXN/M40-PG21/TC
EXN/M40-PG29/TC
EXN/M40-PG36/TC
EXN/M40-PG9/TC
EXN/M50/C
EXN/M50/DSP
EXN/M50/HSP
EXN/M50/SP
EXN/M50/TSP
EXN/M50-050/TC
EXN/M50-075/TC
EXN/M50-100/TC
EXN/M50-125/TC
EXN/M50-150/TC
EXN/M50-200/TC
EXN/M50-M16/R
EXN/M50-M20/R
EXN/M50-M25/R
EXN/M50-M32/R
www.tnb-hazardous.com
Page
177
177
175
175
172
172
172
172
171
171
171
171
171
173
173
173
173
173
173
178
177
177
175
175
172
172
172
172
172
171
171
171
171
171
171
173
173
173
173
173
173
173
178
177
177
175
175
172
172
172
172
172
172
171
171
171
171
Part No.
EXN/M50-M40/R
EXN/M50-M63/E
EXN/M50-M75/E
EXN/M50-PG11/TC
EXN/M50-PG13/TC
EXN/M50-PG16/TC
EXN/M50-PG21/TC
EXN/M50-PG29/TC
EXN/M50-PG36/TC
EXN/M50-PG42/TC
EXN/M50-PG9/TC
EXN/M63/C
EXN/M63/DSP
EXN/M63/HSP
EXN/M63/SP
EXN/M63/TSP
EXN/M63-050/TC
EXN/M63-075/TC
EXN/M63-100/TC
EXN/M63-125/TC
EXN/M63-150/TC
EXN/M63-200/TC
EXN/M63-M16/R
EXN/M63-M20/R
EXN/M63-M25/R
EXN/M63-M32/R
EXN/M63-M40/R
EXN/M63-M50/R
EXN/M63-M75/E
EXN/M63-PG11/TC
EXN/M63-PG13/TC
EXN/M63-PG16/TC
EXN/M63-PG21/TC
EXN/M63-PG29/TC
EXN/M63-PG36/TC
EXN/M63-PG42/TC
EXN/M63-PG48/TC
EXN/M63-PG9/TC
EXN/M75-050/TC
EXN/M75-075/TC
EXN/M75-100/TC
EXN/M75-125/TC
EXN/M75-150/TC
EXN/M75-200/TC
EXN/M75-M16/R
EXN/M75-M20/R
EXN/M75-M25/R
EXN/M75-M32/R
EXN/M75-M40/R
EXN/M75-M50/R
EXN/M75-M63/R
EXN/M75-PG11/TC
EXN/M75-PG13/TC
EXN/M75-PG16/TC
EXN/M75-PG21/TC
EXN/M75-PG29/TC
EXN/M75-PG36/TC
Page
171
171
171
173
173
173
173
173
173
173
173
178
177
177
175
175
172
172
172
172
172
172
171
171
171
171
171
171
171
173
173
173
173
173
173
173
173
173
172
172
172
172
172
172
171
171
171
171
171
171
171
173
173
173
173
173
173
Part No.
EXN/M75-PG42/TC
EXN/M75-PG48/TC
EXN/M75-PG9/TC
EXN/PG11/DSP
EXN/PG11/HSP
EXN/PG11/SP
EXN/PG11/TSP
EXN/PG11-050/TC
EXN/PG11-M16/TC
EXN/PG11-M20/TC
EXN/PG11-PG9/R
EXN/PG13/DSP
EXN/PG13/HSP
EXN/PG13/SP
EXN/PG13/TSP
EXN/PG13-050/TC
EXN/PG13-M16/TC
EXN/PG13-M20/TC
EXN/PG13-PG11/R
EXN/PG13-PG9/R
EXN/PG16/DSP
EXN/PG16/HSP
EXN/PG16/SP
EXN/PG16/TSP
EXN/PG16-050/TC
EXN/PG16-075/TC
EXN/PG16-M16/TC
EXN/PG16-M20/TC
EXN/PG16-M25/TC
EXN/PG16-PG11/R
EXN/PG16-PG13/R
EXN/PG16-PG21/E
EXN/PG16-PG9/R
EXN/PG21/DSP
EXN/PG21/HSP
EXN/PG21/SP
EXN/PG21/TSP
EXN/PG21-075/TC
EXN/PG21-100/TC
EXN/PG21-M16/TC
EXN/PG21-M20/TC
EXN/PG21-M25/TC
EXN/PG21-M32/TC
EXN/PG21-PG11/R
EXN/PG21-PG13/R
EXN/PG21-PG16/R
EXN/PG21-PG29/E
EXN/PG21-PG9/R
EXN/PG29/DSP
EXN/PG29/HSP
EXN/PG29/SP
EXN/PG29/TSP
EXN/PG29-050/TC
EXN/PG29-075/TC
EXN/PG29-100/TC
EXN/PG29-125/TC
EXN/PG29-150/TC
Page
173
173
173
177
177
175
175
172
171
171
173
177
177
175
175
172
171
171
173
173
177
177
175
175
172
172
171
171
171
173
173
173
173
177
177
175
175
172
172
171
171
171
171
173
173
173
173
173
177
177
175
175
172
172
172
172
172
Part No.
EXN/PG29-M16/TC
EXN/PG29-M20/TC
EXN/PG29-M25/TC
EXN/PG29-M32/TC
EXN/PG29-M40/TC
EXN/PG29-PG11/R
EXN/PG29-PG13/R
EXN/PG29-PG16/R
EXN/PG29-PG21/R
EXN/PG29-PG36/E
EXN/PG29-PG9/R
EXN/PG36/DSP
EXN/PG36/HSP
EXN/PG36/SP
EXN/PG36/TSP
EXN/PG36-050/TC
EXN/PG36-075/TC
EXN/PG36-100/TC
EXN/PG36-125/TC
EXN/PG36-150/TC
EXN/PG36-M16/TC
EXN/PG36-M20/TC
EXN/PG36-M25/TC
EXN/PG36-M32/TC
EXN/PG36-M40/TC
EXN/PG36-M50/TC
EXN/PG36-PG11/R
EXN/PG36-PG13/R
EXN/PG36-PG16/R
EXN/PG36-PG21/R
EXN/PG36-PG29/R
EXN/PG36-PG48/E
EXN/PG36-PG9/R
EXN/PG42/DSP
EXN/PG42/HSP
EXN/PG42/SP
EXN/PG42/TSP
EXN/PG42-050/TC
EXN/PG42-075/TC
EXN/PG42-100/TC
EXN/PG42-125/TC
EXN/PG42-150/TC
EXN/PG42-200/TC
EXN/PG42-M16/TC
EXN/PG42-M20/TC
EXN/PG42-M25/TC
EXN/PG42-M32/TC
EXN/PG42-M40/TC
EXN/PG42-M50/TC
EXN/PG42-M63/TC
EXN/PG42-PG11/R
EXN/PG42-PG13/R
EXN/PG42-PG16/R
EXN/PG42-PG21/R
EXN/PG42-PG29/R
EXN/PG42-PG36/R
EXN/PG42-PG48/E
Page
171
171
171
171
171
173
173
173
173
173
173
177
177
175
175
172
172
172
172
172
171
171
171
171
171
171
173
173
173
173
173
173
173
177
177
175
175
172
172
172
172
172
172
171
171
171
171
171
171
171
173
173
173
173
173
173
173
Part No.
EXN/PG42-PG9/R
EXN/PG48/DSP
EXN/PG48/HSP
EXN/PG48/SP
EXN/PG48/TSP
EXN/PG48-050/TC
EXN/PG48-075/TC
EXN/PG48-100/TC
EXN/PG48-125/TC
EXN/PG48-150/TC
EXN/PG48-200/TC
EXN/PG48-M16/TC
EXN/PG48-M20/TC
EXN/PG48-M25/TC
EXN/PG48-M32/TC
EXN/PG48-M40/TC
EXN/PG48-M50/TC
EXN/PG48-M63/TC
EXN/PG48-PG11/R
EXN/PG48-PG13/R
EXN/PG48-PG16/R
EXN/PG48-PG21/R
EXN/PG48-PG29/R
EXN/PG48-PG36/R
EXN/PG48-PG42/R
EXN/PG48-PG9/R
EXN/PG9/DSP
EXN/PG9/HSP
EXN/PG9/SP
EXN/PG9/TSP
EXN/PG9-050/TC
EXN/PG9-M16/TC
EXN/PG9-M20/TC
EXN02AMC3
EXN02MMC3
EXN03ALC3
EXN03AMC1
EXN03AMC2
EXN03AMC3
EXN03ASC1
EXN03MLC3
EXN03MMC1
EXN03MMC2
EXN03MMC3
EXN03MSC1
EXN04ALC2
EXN04ALC3
EXN04AMC1
EXN04AMC2
EXN04AMC3
EXN04ASC1
EXN04ASC3
EXN04MLC1
EXN04MLC1
EXN04MLC2
EXN04MLC3
EXN04MMC1
Page
173
177
177
175
175
172
172
172
172
172
172
171
171
171
171
171
171
171
173
173
173
173
173
173
173
173
177
177
175
175
172
171
171
165
165
165
163
167
165
163
165
163
167
165
163
167
165
163
167
165
163
165
163
163
167
165
163
Index
Part No.
EXN04MMC2
EXN04MMC3
EXN04MSC1
EXN04MSC3
EXN05ALC2
EXN05ALC3
EXN05AMC1
EXN05AMC2
EXN05AMC3
EXN05ASC1
EXN05ASC3
EXN05MLC1
EXN05MLC1
EXN05MLC2
EXN05MLC3
EXN05MMC1
EXN05MMC2
EXN05MMC3
EXN05MSC1
EXN05MSC3
EXN06ALC2
EXN06ALC3
EXN06AMC1
EXN06AMC2
EXN06AMC3
EXN06ASC1
EXN06ASC3
EXN06MLC2
EXN06MLC3
EXN06MMC1
EXN06MMC2
EXN06MMC3
EXN06MSC1
EXN06MSC3
EXN07ALC2
EXN07AM3
EXN07AMC1
EXN07AMC2
EXN07ASC1
EXN07MLC2
EXN07MM3
EXN07MMC1
EXN07MMC2
EXN07MSC1
EXN08ALC2
EXN08ALC3
EXN08AMC1
EXN08AMC2
EXN08AMC3
EXN08ASC1
EXN08MLC2
EXN08MLC3
EXN08MMC1
EXN08MMC2
EXN08MMC3
EXN08MSC1
EXN09ALC2
Page
167
165
163
165
167
165
163
167
165
163
165
163
163
167
165
163
167
165
163
165
167
165
163
167
165
163
165
167
165
163
167
165
163
165
167
165
163
167
163
167
165
163
167
163
167
165
163
167
165
163
167
165
163
167
165
163
167
Part No.
EXN09ALC3
EXN09AMC1
EXN09AMC2
EXN09AMC3
EXN09ASC1
EXN09MLC2
EXN09MLC3
EXN09MMC1
EXN09MMC2
EXN09MMC3
EXN09MSC1
EXN10ALC2
EXN10AMC1
EXN10AMC2
EXN10AMC3
EXN10ASC1
EXN10MLC2
EXN10MMC1
EXN10MMC2
EXN10MMC3
EXN10MSC1
EXN11ALC3
EXN11AMC1
EXN11ASC1
EXN11MLC3
EXN11MMC1
EXN11MSC1
EXN12ALC2
EXN12AMC1
EXN12AMC2
EXN12MLC2
EXN12MMC1
EXN12MMC2
EXN13AMC2
EXN13MMC2
EXN14AMC1
EXN14AMC2
EXN14MMC1
EXN14MMC2
EXPQA0303
EXPQA0404
EXPQA0505
EXPQA0606
EXPQA0707
EXPQA0808
EXPQM0303
EXPQM0404
EXPQM0505
EXPQM0606
EXPQM0707
EXPQM0808
EXS/038/SP
EXS/038/TSP
EXS/038-M16/TC
EXS/050/SP
EXS/050/TSP
EXS/050-075/E
Page
165
163
167
165
163
167
165
163
167
165
163
167
163
167
165
163
167
163
167
165
163
165
163
163
165
163
163
167
163
167
167
163
167
167
167
163
167
163
167
141
141
141
141
141
141
141
141
141
141
141
141
175
175
171
175
175
172
Part No.
EXS/050-M16/TC
EXS/050-M20/TC
EXS/050-M25/TC
EXS/050-PG11/TC
EXS/050-PG13/TC
EXS/050-PG16/TC
EXS/050-PG9/TC
EXS/075/SP
EXS/075/TSP
EXS/075-050/R
EXS/075-100/E
EXS/075-M16/TC
EXS/075-M20/TC
EXS/075-M25/TC
EXS/075-M32/TC
EXS/075-PG11/TC
EXS/075-PG13/TC
EXS/075-PG16/TC
EXS/075-PG21/TC
EXS/075-PG9/TC
EXS/100/SP
EXS/100/TSP
EXS/100-050/R
EXS/100-075/R
EXS/100-125/E
EXS/100-M16/TC
EXS/100-M20/TC
EXS/100-M25/TC
EXS/100-M32/TC
EXS/100-M40/TC
EXS/100-PG11/TC
EXS/100-PG13/TC
EXS/100-PG16/TC
EXS/100-PG21/TC
EXS/100-PG29/TC
EXS/100-PG9/TC
EXS/125/SP
EXS/125/TSP
EXS/125-050/R
EXS/125-075/R
EXS/125-100/R
EXS/125-150/E
EXS/125-M16/TC
EXS/125-M20/TC
EXS/125-M25/TC
EXS/125-M32/TC
EXS/125-M40/TC
EXS/125-M50/TC
EXS/125-PG11/TC
EXS/125-PG13/TC
EXS/125-PG16/TC
EXS/125-PG21/TC
EXS/125-PG29/TC
EXS/125-PG36/TC
EXS/125-PG9/TC
EXS/150/SP
EXS/150/TSP
Page
171
171
171
173
173
173
173
175
175
172
172
171
171
171
171
173
173
173
173
173
175
175
172
172
172
171
171
171
171
171
173
173
173
173
173
173
175
175
172
172
172
172
171
171
171
171
171
171
173
173
173
173
173
173
173
175
175
Part No.
EXS/150-050/R
EXS/150-075/R
EXS/150-100/R
EXS/150-125/R
EXS/150-200/E
EXS/150-M16/TC
EXS/150-M20/TC
EXS/150-M25/TC
EXS/150-M32/TC
EXS/150-M40/TC
EXS/150-M50/TC
EXS/150-M63/TC
EXS/150-PG11/TC
EXS/150-PG13/TC
EXS/150-PG16/TC
EXS/150-PG21/TC
EXS/150-PG29/TC
EXS/150-PG36/TC
EXS/150-PG42/TC
EXS/150-PG9/TC
EXS/200/SP
EXS/200/TSP
EXS/200-050/R
EXS/200-075/R
EXS/200-100/R
EXS/200-125/R
EXS/200-150/R
EXS/200-M16/TC
EXS/200-M20/TC
EXS/200-M25/TC
EXS/200-M32/TC
EXS/200-M40/TC
EXS/200-M50/TC
EXS/200-M63/TC
EXS/200-PG11/TC
EXS/200-PG13/TC
EXS/200-PG16/TC
EXS/200-PG21/TC
EXS/200-PG29/TC
EXS/200-PG36/TC
EXS/200-PG42/TC
EXS/200-PG48/TC
EXS/200-PG9/TC
EXS/250-M50/TC
EXS/300-M50/TC
EXS/M16/C
EXS/M16/DSP
EXS/M16/HSP
EXS/M16/SP
EXS/M16/TSP
EXS/M16-038/TC
EXS/M16-050/TC
EXS/M16-M20/E
EXS/M16-M25/E
EXS/M16-PG11/TC
EXS/M16-PG13/TC
EXS/M16-PG9/TC
Page
172
172
172
172
172
171
171
171
171
171
171
171
173
173
173
173
173
173
173
173
175
175
172
172
172
172
172
171
171
171
171
171
171
171
173
173
173
173
173
173
173
173
173
171
171
178
177
177
175
175
172
172
171
171
173
173
173
Part No.
Page
EXS/M20/C
EXS/M20/DSP
EXS/M20/HSP
EXS/M20/SP
EXS/M20/TSP
EXS/M20-050/TC
EXS/M20-075/TC
EXS/M20-M16/R
EXS/M20-M25/E
EXS/M20-M32/E
EXS/M20-PG11/TC
EXS/M20-PG13/TC
EXS/M20-PG16/TC
EXS/M20-PG9/TC
EXS/M25/C
EXS/M25/DSP
EXS/M25/HSP
EXS/M25/SP
EXS/M25/TSP
EXS/M25-050/TC
EXS/M25-075/TC
EXS/M25-100/TC
EXS/M25-M16/R
EXS/M25-M20/R
EXS/M25-M32/E
EXS/M25-M40/E
EXS/M25-PG11/TC
EXS/M25-PG13/TC
EXS/M25-PG16/TC
EXS/M25-PG21/TC
EXS/M25-PG9/TC
EXS/M32/C
EXS/M32/DSP
EXS/M32/HSP
EXS/M32/SP
EXS/M32/TSP
EXS/M32-050/TC
EXS/M32-075/TC
EXS/M32-100/TC
EXS/M32-125/TC
EXS/M32-M16/R
EXS/M32-M20/R
EXS/M32-M25/R
EXS/M32-M40/E
EXS/M32-M50/E
EXS/M32-PG11/TC
EXS/M32-PG13/TC
EXS/M32-PG16/TC
EXS/M32-PG21/TC
EXS/M32-PG29/TC
EXS/M32-PG9/TC
EXS/M40/C
EXS/M40/DSP
EXS/M40/HSP
EXS/M40/SP
EXS/M40/TSP
EXS/M40-050/TC
178
177
177
175
175
172
172
171
171
171
173
173
173
173
178
177
177
175
175
172
172
172
171
171
171
171
173
173
173
173
173
178
177
177
175
175
172
172
172
172
171
171
171
171
171
173
173
173
173
173
173
178
177
177
175
175
172
185
www.tnb.com
A Member of the ABB Group
Index
Part No.
186
EXS/M40-075/TC
EXS/M40-100/TC
EXS/M40-125/TC
EXS/M40-150/TC
EXS/M40-M16/R
EXS/M40-M20/R
EXS/M40-M25/R
EXS/M40-M32/R
EXS/M40-M50/E
EXS/M40-M63/E
EXS/M40-PG11/TC
EXS/M40-PG13/TC
EXS/M40-PG16/TC
EXS/M40-PG21/TC
EXS/M40-PG29/TC
EXS/M40-PG36/TC
EXS/M40-PG9/TC
EXS/M50/C
EXS/M50/DSP
EXS/M50/HSP
EXS/M50/SP
EXS/M50/TSP
EXS/M50-050/TC
EXS/M50-075/TC
EXS/M50-100/TC
EXS/M50-125/TC
EXS/M50-150/TC
EXS/M50-200/TC
EXS/M50-M16/R
EXS/M50-M20/R
EXS/M50-M25/R
EXS/M50-M32/R
EXS/M50-M40/R
EXS/M50-M63/E
EXS/M50-M75/E
EXS/M50-PG11/TC
EXS/M50-PG13/TC
EXS/M50-PG16/TC
EXS/M50-PG21/TC
EXS/M50-PG29/TC
EXS/M50-PG36/TC
EXS/M50-PG42/TC
EXS/M50-PG9/TC
EXS/M63/C
EXS/M63/DSP
EXS/M63/HSP
EXS/M63/SP
EXS/M63/TSP
EXS/M63-050/TC
EXS/M63-075/TC
EXS/M63-100/TC
EXS/M63-125/TC
EXS/M63-150/TC
EXS/M63-200/TC
EXS/M63-M16/R
EXS/M63-M20/R
EXS/M63-M25/R
www.tnb-hazardous.com
Page
172
172
172
172
171
171
171
171
171
171
173
173
173
173
173
173
173
178
177
177
175
175
172
172
172
172
172
172
171
171
171
171
171
171
171
173
173
173
173
173
173
173
173
178
177
177
175
175
172
172
172
172
172
172
171
171
171
Part No.
EXS/M63-M32/R
EXS/M63-M40/R
EXS/M63-M50/R
EXS/M63-M75/E
EXS/M63-PG11/TC
EXS/M63-PG13/TC
EXS/M63-PG16/TC
EXS/M63-PG21/TC
EXS/M63-PG29/TC
EXS/M63-PG36/TC
EXS/M63-PG42/TC
EXS/M63-PG48/TC
EXS/M63-PG9/TC
EXS/M75-050/TC
EXS/M75-075/TC
EXS/M75-100/TC
EXS/M75-125/TC
EXS/M75-150/TC
EXS/M75-200/TC
EXS/M75-M16/R
EXS/M75-M20/R
EXS/M75-M25/R
EXS/M75-M32/R
EXS/M75-M40/R
EXS/M75-M50/R
EXS/M75-M63/R
EXS/M75-PG11/TC
EXS/M75-PG13/TC
EXS/M75-PG16/TC
EXS/M75-PG21/TC
EXS/M75-PG29/TC
EXS/M75-PG36/TC
EXS/M75-PG42/TC
EXS/M75-PG48/TC
EXS/M75-PG9/TC
EXS/PG11/DSP
EXS/PG11/HSP
EXS/PG11/SP
EXS/PG11/TSP
EXS/PG11-050/TC
EXS/PG11-M16/TC
EXS/PG11-M20/TC
EXS/PG11-PG9/R
EXS/PG13/DSP
EXS/PG13/HSP
EXS/PG13/SP
EXS/PG13/TSP
EXS/PG13-050/TC
EXS/PG13-M16/TC
EXS/PG13-M20/TC
EXS/PG13-PG11/R
EXS/PG13-PG9/R
EXS/PG16/DSP
EXS/PG16/HSP
EXS/PG16/SP
EXS/PG16/TSP
EXS/PG16-050/TC
Page
171
171
171
171
173
173
173
173
173
173
173
173
173
172
172
172
172
172
172
171
171
171
171
171
171
171
173
173
173
173
173
173
173
173
173
177
177
175
175
172
171
171
173
177
177
175
175
172
171
171
173
173
177
177
175
175
172
Part No.
EXS/PG16-075/TC
EXS/PG16-M16/TC
EXS/PG16-M20/TC
EXS/PG16-M25/TC
EXS/PG16-PG11/R
EXS/PG16-PG13/R
EXS/PG16-PG21/E
EXS/PG16-PG9/R
EXS/PG21/DSP
EXS/PG21/HSP
EXS/PG21/SP
EXS/PG21/TSP
EXS/PG21-075/TC
EXS/PG21-100/TC
EXS/PG21-M16/TC
EXS/PG21-M20/TC
EXS/PG21-M25/TC
EXS/PG21-M32/TC
EXS/PG21-PG11/R
EXS/PG21-PG13/R
EXS/PG21-PG16/R
EXS/PG21-PG29/E
EXS/PG21-PG9/R
EXS/PG29/DSP
EXS/PG29/HSP
EXS/PG29/SP
EXS/PG29/TSP
EXS/PG29-050/TC
EXS/PG29-075/TC
EXS/PG29-100/TC
EXS/PG29-125/TC
EXS/PG29-150/TC
EXS/PG29-M16/TC
EXS/PG29-M20/TC
EXS/PG29-M25/TC
EXS/PG29-M32/TC
EXS/PG29-M40/TC
EXS/PG29-PG11/R
EXS/PG29-PG13/R
EXS/PG29-PG16/R
EXS/PG29-PG21/R
EXS/PG29-PG36/E
EXS/PG29-PG9/R
EXS/PG36/DSP
EXS/PG36/HSP
EXS/PG36/SP
EXS/PG36/TSP
EXS/PG36-050/TC
EXS/PG36-075/TC
EXS/PG36-100/TC
EXS/PG36-125/TC
EXS/PG36-150/TC
EXS/PG36-M16/TC
EXS/PG36-M20/TC
EXS/PG36-M25/TC
EXS/PG36-M32/TC
EXS/PG36-M40/TC
Page
172
171
171
171
173
173
173
173
177
177
175
175
172
172
171
171
171
171
173
173
173
173
173
177
177
175
175
172
172
172
172
172
171
171
171
171
171
173
173
173
173
173
173
177
177
175
175
172
172
172
172
172
171
171
171
171
171
Part No.
EXS/PG36-M50/TC
EXS/PG36-PG11/R
EXS/PG36-PG13/R
EXS/PG36-PG16/R
EXS/PG36-PG21/R
EXS/PG36-PG29/R
EXS/PG36-PG48/E
EXS/PG36-PG9/R
EXS/PG42/DSP
EXS/PG42/HSP
EXS/PG42/SP
EXS/PG42/TSP
EXS/PG42-050/TC
EXS/PG42-075/TC
EXS/PG42-100/TC
EXS/PG42-125/TC
EXS/PG42-150/TC
EXS/PG42-200/TC
EXS/PG42-M16/TC
EXS/PG42-M20/TC
EXS/PG42-M25/TC
EXS/PG42-M32/TC
EXS/PG42-M40/TC
EXS/PG42-M50/TC
EXS/PG42-M63/TC
EXS/PG42-PG11/R
EXS/PG42-PG13/R
EXS/PG42-PG16/R
EXS/PG42-PG21/R
EXS/PG42-PG29/R
EXS/PG42-PG36/R
EXS/PG42-PG48/E
EXS/PG42-PG9/R
EXS/PG48/DSP
EXS/PG48/HSP
EXS/PG48/SP
EXS/PG48/TSP
EXS/PG48-050/TC
EXS/PG48-075/TC
EXS/PG48-100/TC
EXS/PG48-125/TC
EXS/PG48-150/TC
EXS/PG48-200/TC
EXS/PG48-M16/TC
EXS/PG48-M20/TC
EXS/PG48-M25/TC
EXS/PG48-M32/TC
EXS/PG48-M40/TC
EXS/PG48-M50/TC
EXS/PG48-M63/TC
EXS/PG48-PG11/R
EXS/PG48-PG13/R
EXS/PG48-PG16/R
EXS/PG48-PG21/R
EXS/PG48-PG29/R
EXS/PG48-PG36/R
EXS/PG48-PG42/R
Page
171
173
173
173
173
173
173
173
177
177
175
175
172
172
172
172
172
172
171
171
171
171
171
171
171
173
173
173
173
173
173
173
173
177
177
175
175
172
172
172
172
172
172
171
171
171
171
171
171
171
173
173
173
173
173
173
173
Part No.
EXS/PG48-PG9/R
EXS/PG9/DSP
EXS/PG9/HSP
EXS/PG9/SP
EXS/PG9/TSP
EXS/PG9-050/TC
EXS/PG9-M16/TC
EXS/PG9-M20/TC
EXS02AMC3
EXS02MMC3
EXS03ALC3
EXS03AMC1
EXS03AMC2
EXS03AMC3
EXS03ASC1
EXS03MLC3
EXS03MMC1
EXS03MMC2
EXS03MMC3
EXS03MSC1
EXS04ALC2
EXS04ALC3
EXS04AMC1
EXS04AMC2
EXS04AMC3
EXS04ASC1
EXS04ASC3
EXS04MLC1
EXS04MLC1
EXS04MLC2
EXS04MLC3
EXS04MMC1
EXS04MMC2
EXS04MMC3
EXS04MSC1
EXS04MSC3
EXS05ALC2
EXS05ALC3
EXS05AMC1
EXS05AMC2
EXS05AMC3
EXS05ASC1
EXS05ASC3
EXS05MLC1
EXS05MLC1
EXS05MLC2
EXS05MLC3
EXS05MMC1
EXS05MMC2
EXS05MMC3
EXS05MSC1
EXS05MSC3
EXS06ALC2
EXS06ALC3
EXS06AMC1
EXS06AMC2
EXS06AMC3
Page
173
177
177
175
175
172
171
171
165
165
165
163
167
165
163
165
163
167
165
163
167
165
163
167
165
163
165
163
163
167
165
163
167
165
163
165
167
165
163
167
165
163
165
163
163
167
165
163
167
165
163
165
167
165
163
167
165
Index
Part No.
EXS06ASC1
EXS06ASC3
EXS06MLC2
EXS06MLC3
EXS06MMC1
EXS06MMC2
EXS06MMC3
EXS06MSC1
EXS06MSC3
EXS07ALC2
EXS07AM3
EXS07AMC1
EXS07AMC2
EXS07ASC1
EXS07MLC2
EXS07MM3
EXS07MMC1
EXS07MMC2
EXS07MSC1
EXS08ALC2
EXS08ALC3
EXS08AMC1
EXS08AMC2
EXS08AMC3
EXS08ASC1
EXS08MLC2
EXS08MLC3
EXS08MMC1
EXS08MMC2
EXS08MMC3
EXS08MSC1
EXS09ALC2
EXS09ALC3
EXS09AMC1
EXS09AMC2
EXS09AMC3
EXS09ASC1
EXS09MLC2
EXS09MLC3
EXS09MMC1
EXS09MMC2
EXS09MMC3
EXS09MSC1
EXS10ALC2
EXS10AMC1
EXS10AMC2
EXS10AMC3
EXS10ASC1
EXS10MLC2
EXS10MMC1
EXS10MMC2
EXS10MMC3
EXS10MSC1
EXS11ALC3
EXS11AMC1
EXS11ASC1
EXS11MLC3
Page
163
165
167
165
163
167
165
163
165
167
165
163
167
163
167
165
163
167
163
167
165
163
167
165
163
167
165
163
167
165
163
167
165
163
167
165
163
167
165
163
167
165
163
167
163
167
165
163
167
163
167
165
163
165
163
163
165
Part No.
EXS11MMC1
EXS11MSC1
EXS12ALC2
EXS12AMC1
EXS12AMC2
EXS12MLC2
EXS12MMC1
EXS12MMC2
EXS13AMC2
EXS13MMC2
EXS14AMC1
EXS14AMC2
EXS14MMC1
EXS14MMC2
EXSB0310
EXSB0330
EXSB0410
EXSB0430
EXSB0510
EXSB0530
EXSB0610
EXSB0620
EXSB0630
EXSB0710
EXSB0720
EXSB0730
EXSB0810
EXSB0820
EXSB0910
EXSB0920
EXSBBT0310
EXSBBT0330
EXSBBT0410
EXSBBT0430
EXSBBT0510
EXSBBT0530
EXSBBT0610
EXSBBT0620
EXSBBT0710
EXSBBT0720
EXSBBT0810
EXSBBT0820
EXSBBT0910
EXSBBT0920
EXSH0310
EXSH0330
EXSH0410
EXSH0430
EXSH0510
EXSH0530
EXSH0610
EXSH0620
EXSH0710
EXSH0720
EXSH0810
EXSH0820
EXSH0910
Page
163
163
167
163
167
167
163
167
167
167
163
167
163
167
150
150
150
150
150
150
150
150
150
150
150
150
150
150
150
150
150
150
150
150
150
150
150
150
150
150
150
150
150
150
151
151
151
151
151
151
151
151
151
151
151
151
151
Part No.
EXSH0920
EXSHC0310
EXSHC0310
EXSHC0330
EXSHC0330
EXSHC0410
EXSHC0410
EXSHC0430
EXSHC0430
EXSHC0510
EXSHC0510
EXSHC0530
EXSHC0530
EXSHC0610
EXSHC0610
EXSHC0620
EXSHC0630
EXSHC0710
EXSHC0710
EXSHC0720
EXSHC0810
EXSHC0810
EXSHC0820
EXSHC0910
EXSHC0910
EXSHC0920
EXSLH0310
EXSLH0330
EXSLH0410
EXSLH0430
EXSLH0510
EXSLH0530
EXSLH0610
EXSLH0620
EXSLH0710
EXSLH0720
EXSLH0810
EXSLH0820
EXSLH0910
EXSLH0920
EXST0310
EXST0330
EXST0410
EXST0430
EXST0510
EXST0530
EXST0610
EXST0620
EXST0710
EXST0720
EXST0810
EXST0820
EXST0910
EXST0920
FB30-00000
FB70-00000
FF005C
Page
151
151
151
151
151
151
151
151
151
151
151
151
151
151
151
151
151
151
151
151
151
151
151
151
151
151
151
151
151
151
151
151
151
151
151
151
151
151
151
151
150
150
150
150
150
150
150
150
150
150
150
150
150
150
81
81
95
Part No.
FF012
FF013
FF015C
FF019C
FF023D
FF024D
FF026
FF220-0G000
FF220EM-0G000
FF236-0G000
FF240-0G000
FF240EM-0G000
FF255-0G000
FF265-0G000
FL30P-00000
FL30P-0C000
FL30P-0D000
FL30P-0E000
FL30P-0F000
FR120-0G000
FR120EM-0G000
FR136-0G000
FR140-0G000
FR140EM-0G000
FR155-0G000
FR165-0G000
GUB01CS
GUB02DS
GUB03ES
GUB04FF
GUB0AS
GUB0BS
GUVC26-00000
GUVC36-00000
GUVL26-00000
GUVL36-00000
GUVT26-00000
GUVT36-00000
GUVX26-00000
GUVX36-00000
HAA0304
HAA0304E
HAA0304G1
HAA0304U
HAA0304U/SW
HAA0404
HAA0404E
HAA0404G1
HAA0404U
HAA0404U/SW
HAA0505
HAA0505E
HAA0505G1
HAA0505U
HAA0505U/SW
HAA0606
HAA0606E
Page
95
95
95
95
95
95
95
71
85
71
71
85
71
71
81
81
81
81
81
71
85
71
71
85
71
71
129
129
129
129
129
129
121
121
121
121
121
121
121
121
159
154
153
156
157
159
154
153
156
157
159
154
153
156
157
159
154
Part No.
Page
HAA0606G1
HAA0606U
HAA0606U/SW
HAA0707
HAA0707E
HAA0707G1
HAA0707U
HAA0707U/SW
HAA0808
HAA0808E
HAA0808G1
HAA0808U
HAA0808U/SW
HAA0909
HAA0909E
HAA0909G1
HAA0909U
HAA0909U/SW
HAAM0304
HAAM0304E
HAAM0304G1
HAAM0304U
HAAM0304U/SW
HAAM0404
HAAM0404E
HAAM0404G1
HAAM0404U
HAAM0404U/SW
HAAM0505
HAAM0505E
HAAM0505G1
HAAM0505U
HAAM0505U/SW
HAAM0606
HAAM0606E
HAAM0606G1
HAAM0606U
HAAM0606U/SW
HAAM0707
HAAM0707E
HAAM0707G1
HAAM0707U
HAAM0707U/SW
HAAM0808
HAAM0808E
HAAM0808G1
HAAM0808U
HAAM0808U/SW
HAAM0909
HAAM0909E
HAAM0909G1
HAAM0909U
HAAM0909U/SW
HAAS0304G1
HAAS0304U
HAAS0404
HAAS0404G1
153
156
157
159
154
153
156
157
159
154
153
156
157
159
154
153
156
157
159
154
153
156
157
159
154
153
156
157
159
154
153
156
157
159
154
153
156
157
159
154
153
156
157
159
154
153
156
157
159
154
153
156
157
153
156
159
153
187
www.tnb.com
A Member of the ABB Group
Index
Part No.
188
HAAS0404U
HAAS0505
HAAS0505G1
HAAS0505U
HAAS0606
HAAS0606G1
HAAS0606U
HAAS0707
HAAS0707G1
HAAS0707U
HAAS0808
HAAS0808G1
HAAS0808U
HAAS0909
HAAS0909G1
HAAS0909U
HAM0304
HAM0304E
HAM0304G1
HAM0304U
HAM0304U/SW
HAM0404
HAM0404E
HAM0404G1
HAM0404U
HAM0404U/SW
HAM0505
HAM0505E
HAM0505G1
HAM0505U
HAM0505U/SW
HAM0606
HAM0606E
HAM0606G1
HAM0606U
HAM0606U/SW
HAM0707
HAM0707E
HAM0707G1
HAM0707U
HAM0707U/SW
HAM0808
HAM0808E
HAM0808G1
HAM0808U
HAM0808U/SW
HAM0909
HAM0909E
HAM0909G1
HAM0909U
HAM0909U/SW
HAMM0304
HAMM0304E
HAMM0304G1
HAMM0304U
HAMM0304U/SW
HAMM0404
www.tnb-hazardous.com
Page
156
159
153
156
159
153
156
159
153
156
159
153
156
159
153
156
159
154
153
156
157
159
154
153
156
157
159
154
153
156
157
159
154
153
156
157
159
154
153
156
157
159
154
153
156
157
159
154
153
156
157
159
154
153
156
157
159
Part No.
HAMM0404E
HAMM0404G1
HAMM0404U
HAMM0404U/SW
HAMM0505
HAMM0505E
HAMM0505G1
HAMM0505U
HAMM0505U/SW
HAMM0606
HAMM0606E
HAMM0606G1
HAMM0606U
HAMM0606U/SW
HAMM0707
HAMM0707E
HAMM0707G1
HAMM0707U
HAMM0707U/SW
HAMM0808
HAMM0808E
HAMM0808G1
HAMM0808U
HAMM0808U/SW
HAMM0909
HAMM0909E
HAMM0909G1
HAMM0909U
HAMM0909U/SW
HAMS0304G1
HAMS0304U
HAMS0404
HAMS0404G1
HAMS0404U
HAMS0505
HAMS0505G1
HAMS0505U
HAMS0606
HAMS0606G1
HAMS0606U
HAMS0707
HAMS0707G1
HAMS0707U
HAMS0808
HAMS0808G1
HAMS0808U
HAMS0909
HAMS0909G1
HAMS0909U
HEAK-M32/25-13
HEAK-M40/32-13
HEAK-M50/40-14
HEAK-M63/63-14
HF55P-00000
HF70P-00000
L00
L013
Page
154
153
156
157
159
154
153
156
157
159
154
153
156
157
159
154
153
156
157
159
154
153
156
157
159
154
153
156
157
153
157
159
153
157
159
153
157
159
153
157
159
153
157
159
153
157
159
153
157
147
147
147
147
83
83
95
95
Part No.
L021
L022110VAC
L022110VCC
L022220VAC
L02224VCC
L02248VCC
M005
MXWH04
MXWH05
MXWH06
MXWH07
MXWH08
NEAV-M120-10
NEAV-M162-10
NEAV-M207-10
NEAV-M253-11
NEAV-M257-11
NEAV-M323-13
NEAV-M329-13
NEAV-M406-13
NEAV-M409-13
NEAV-M506-14
NEAV-M508-14
NEAV-M638-14
NEBV-M207-10
NEBV-M253-11
NEBV-M257-11
NEBV-M323-13
NEBV-M329-13
NEBV-M406-13
NEBV-M409-13
NEBV-M506-14
NEBV-M508-14
NEBV-M638-14
NEIR-M120
NEIR-M160
NEIR-M162
NEIR-M207
NEIR-M253
NEIR-M329
NEIR-M406
NEIR-M508
NEIR-M638
NENV-M120-10
NENV-M160-10
NENV-M162-10
NENV-M202-10
NENV-M207-10
NENV-M253-11
NENV-M257-11
NENV-M323-13
NENV-M329-13
NENV-M406-13
NENV-M409-13
NENV-M506-14
NENV-M508-14
NENV-M638-114
Page
95
95
95
95
95
95
93
178
178
178
178
178
144
144
144
144
144
144
144
144
144
144
144
144
144
144
144
144
144
144
144
144
144
144
146
146
146
146
146
146
146
146
146
143
143
143
143
143
143
143
143
143
143
143
143
143
143
Part No.
NENZ-M120S/P
NENZ-M160S/P
NENZ-M202S/P
NENZ-M207S/P
NENZ-M257S/P
NENZ-M323S/P
NENZ-M409S/P
NENZ-M506S/P
NENZ-M508S/P
NENZ-M638S/P
NEWV-M120-10*
NEWV-M160-10*
NEWV-M162-10*
NEWV-M202-10*
P001
P002
P004
P006
P006150SHP
P006250IM
P006250SHP
P006400IM
P006400SHP
P007
P008
P009
P010
P012
P017FC
PB01
PL11W
PL18W
PL36W
PL55W
PL7W
PL9W
PR01
PR02
PR03
PR04
PR05
PR06
PR07
PR07V
PRC10
PRC20
PRC30
PRC40
PRC50
PRC60
PRC70
QF250G-00000
QF250P-00000
QF400G-00000
QF400P-00000
REA20
S00755W
Page
143
143
143
143
143
143
143
143
143
143
144
144
144
144
93
93
93
93
97
97
97
97
97
93
93
93
93
93
93
132
96
96
96
96
96
96
132
132
132
132
132
132
132
132
132
132
132
132
132
132
132
75
75
75
75
132
97
Part No.
S00770W
SF150G-00000
SF150P-00000
SF250G-00000
SF250P-00000
SF400G-00000
SF400P-00000
SF70G-00000
SF70P-00000
SRC215
SRC215V
SRC330
SRC340
SRC415
TL18W
TL36W
TL58W
TL8W
V001
V004
V005S
V007N
V008
V008N
V011
V014
V015
V016
V018
V021
V023
V024
VAB10
VAC10
VAJ10
VAR10
VAV10
WHAM04
WHAM05
WHAM06
WHAM07
WHAM08
WHAM09
WHMB03
WHMB04
WHMB05
WHMB06
WHMB07
WHMB08
WHMM03
WHMM04
WHMM05
WHMM06
WHMM07
WHMM08
WHMM09
XB100-10BV
Page
97
75
75
75
75
75
75
75
75
123
123
123
123
123
96
96
96
96
91
91
91
91
91
91
91
90
90
90
90
90
90
90
132
132
132
132
132
178
178
178
178
178
178
178
178
178
178
178
178
178
178
178
178
178
178
178
105
Index
Part No.
XB100-6BR
XB100-6BV
XB100A-10BV
XB100A-6BR
XB100A-6BV
XB10A-SI
XB10-SI
XB215A
XB215VA
XB21A
XB21FA
XB21VA
XB22A
XB22AMP
XB23A
XB26A
XB300
XB38A
XB38AMP
XB400
XB41A
XB43A
XB510
XB520
XB570
XB700
XB710
XB750
XB950
XB960
XBAMP
XBI100
XBI150
XBI200
XBI215A
XBI21A
XBI21FA
XBI21VA
XBI22A
XBI23A
XBI26A
XBI300
XBI38A
XBI400
XBI41A
XBI43A
XBI500
XBI600
XBL15
XBL20
XBL215A
XBL215VA
XBL21A
XBL21FA
XBL21VA
XBL22A
XBL22AMP
Page
105
105
105
105
105
107
107
115
115
115
115
115
115
115
115
115
113
115
115
113
115
115
113
113
113
113
113
113
113
113
115
117
117
117
119
119
119
119
119
119
119
117
119
117
119
119
117
117
109
109
111
111
111
111
111
111
111
Part No.
XBL23A
XBL25
XBL26-25R
XBL26A
XBL28-25BR
XBL35
XBL38A
XBL38AMP
XBL40
XBL41A
XBL43A
XBL45
XBL55
XBL65
XBL75
XDF140-00000
XDF140-0D000
XDF165-00000
XDF165-0D000
XEF110G-00000
XEF110P-00000
XEF140G-00000
XEF140P-00000
XEL120-0G000
XEL120V-0G000
XEL220-0G000
XEL220V-0G000
XEL3001-00000
XEL30011-0G000
XEL30011V-0G000
XEL3001V-00000
XEL3002-00000
XEL30028-0G000
XEL30028V-0G000
XEL3002V-00000
XEL3008-0G000
XEL3008V-0G000
XEL3009-0G000
XEL3009V-0G000
XEL300A-00000
XEL300AI-00000
XEL300AK-00000
XEL300SI-00000
XEL300VA-00000
XEL300VAI-00000
XEL300VAK-00000
XEL300VSI-00000
XEL80A-00000
XEL80AI-00000
XEL80AK-00000
XEL80SI-0J000
XEL80VA-0J000
XEL80VAI-00000
XEL80VAK-00000
XEL80VSI-0J000
XEP120-0G000
XEP120V-0G000
Page
111
109
107
111
107
109
111
111
109
111
111
109
109
109
109
41
41
41
41
37
37
37
37
33
33
33
33
55
33
33
55
55
33
33
55
33
33
33
33
55
55
55
55
55
55
55
55
55
55
55
55
55
55
55
55
35
35
Part No.
XEP220-0G000
XEP220V-0G000
XEP30011-0G000
XEP30011V-0G000
XEP30028-0G000
XEP30028V-0G000
XEP3008-0G000
XEP3008V-0G000
XEP3009-0G000
XEP3009V-0G000
XESX0250
XESX0350
XESX0450
XESX0550
XESX0650
XESX0750
XESX0850
XESX-10BY.50
XESX-12BY.50
XESX-17BY.50
XESX-23BY.50
XESX-29BY.50
XESX-36BY.30
XESX-48BY.30
XFB230-00000
XFB270-00000
XFB30-00000
XFB330-00000
XFB370-00000
XFB70-00000
XFF012
XFF220-0G000
XFF220EM-0G000
XFF220V-0G000
XFF220VEM-0G000
XFF236-0G000
XFF236V-0G000
XFF240-0G000
XFF240EM-0G000
XFF240V-0G000
XFF240VEM-0G000
XFF255-0G000
XFF255V-0G000
XFF265-0G000
XFF265V-0G000
XFL230-00000
XFL230-0C000
XFL230-0D000
XFL230-0E000
XFL230-0F000
XFL30P-00000
XFL30P-0C000
XFL30P-0D000
XFL30P-0E000
XFL30P-0F000
XFL330-00000
XFL330-0C000
Page
35
35
35
35
35
35
35
35
35
35
139
139
139
139
139
139
139
139
139
139
139
139
139
139
39
39
39
39
39
39
95
29
51
29
51
29
29
29
51
29
51
29
29
29
29
39
39
39
39
39
39
39
39
39
39
39
39
Part No.
XFL330-0D000
XFL330-0E000
XFL330-0F000
XFP120-0G000
XFP120EM-0G000
XFP120V EM-0G000
XFP120V-0G000
XFP136-0G000
XFP136V-0G000
XFP140-0GG000
XFP140EM-0G000
XFP140V EM-0G000
XFP140V-0G000
XFP155-0G000
XFP155V-0G000
XFP165-0G000
XFP165V-0G000
XFP220-0G000
XFP220EM-0G000
XFP220V EM-0G000
XFP220V-0G000
XFP236-0G000
XFP236V-0G000
XFP240-0G000
XFP240EM-0G000
XFP240V EM-0G000
XFP240V-0G000
XFP255-0G0000
XFP255V-0G000
XFP265-0G000
XFP265V-0G000
XFR120-0G000
XFR120EM-0G000
XFR120V-0G000
XFR120VEM-0G000
XFR136-0G000
XFR136V-0G000
XFR140-0G000
XFR140EM-0G000
XFR140V-0G000
XFR140VEM-0G000
XFR155-0G000
XFR155V-0G000
XFR165-0G000
XFR165V-0G000
XMC36
XPLFL110
XPLFL112
XPLFL115
XPLFL118
XPLFL124
XPLFL16
XPLFL18
XPLFL212
XPLFL215
XPLFL218
XPLFL224
Page
39
39
39
31
53
53
31
31
31
31
53
53
31
31
31
31
31
31
53
53
31
31
31
31
53
53
31
31
31
31
31
29
51
29
51
29
29
29
51
29
51
29
29
29
29
123
161
161
161
161
161
161
161
161
161
161
161
Part No.
Page
XPLFL236
XPLFL318
XQF250G-00000
XQF250P-00000
XQF400G-00000
XQF400P-00000
XSF150G-00000
XSF150P-00000
XSF250G-00000
XSF250P-00000
XSF400G-00000
XSF400P-00000
XSF70G-00000
XSF70P-00000
Z001
Z007
161
161
37
37
37
37
37
37
37
37
37
37
37
37
91
91
189
www.tnb.com
A Member of the ABB Group
Thomas and Betts manufacture and design a wide range of electrical equipment for hazardous
and hostile environments to ensure the safety of the personnel working in them.
The extensive range covers Kopex-Ex metallic and non metallic conduit and fittings and the
DTS range of lighting junction and control boxes. These products are approved to a wide range
of hazardous area standards including ATEX, IECEx, UL, CSA, GOST and Inmetro.
Thomas & Betts | France / Belgium
T +33 (0) 1 64 40 27 26
E [email protected]
T
Thomas & Betts | Middle East
+971 (0) 4 609 1635
E [email protected]
T
T
Thomas & Betts | Germany / Austria
+49 (0) 62 51 669/0
E [email protected]
T
Thomas & Betts | Netherlands
+31 (0) 180 641 888
E [email protected]
T
Thomas & Betts | Italy
+39 039 65 79 028
T
Thomas & Betts | Spain
34 938 45 4570
E [email protected]
T
Thomas & Betts | UK
+44 (0) 1675 468 213
E [email protected]
Thomas & Betts | USA
901 252 5000
E [email protected]
LIT-140GBR 08/13 • Designed by www.uc4.co.uk
T
Thomas & Betts | Switzerland (PMA)
+41 44 905 61 11
E [email protected]
Product Catalogue
Lighting, Boxes, Cabinets,
Conduits, Fittings & Accessories for
Hazardous and Hostile Areas
The content of the Thomas & Betts catalogue has been carefully checked for accuracy at the time of print. However,
Thomas & Betts doesn’t give any warranty of any kind, express or implied, in this respect and shall not be liable for
any loss or damage that may result from any use or as a consequence of any inaccuracies in or any omissions from the
information which it may contain.
Copyright Thomas & Betts 2006. Copyright in these pages is owned by Thomas & Betts except where otherwise indicated.
No part of this publication may be reproduced, copied or transmitted in any form or by any means, without our prior
written permission. Images, trade marks, brands, designs and technology are also protected by other intellectual property
rights and may not be reproduced or appropriated in any manner without written permission of their respective owners.
Thomas & Betts reserves the right to change and improve any product specifications or other mentions in the catalogue
at its own discretion and at any time. These conditions of use are governed by the laws of the Netherlands and the courts
of Amsterdam shall have exclusive jurisdiction in any dispute.
Lighting, Boxes, Cabinets, Conduits, Fittings & Accessories for Hazardous and Hostile Areas
Thomas & Betts Sales Offices
A Member of the ABB Group
A Member of the ABB Group
Thomas & Betts Worldwide
Industrial Capabilities
T&B Headquarters
USA & Canada
Thomas & Betts Corporation
World Headquarters
8155 T&B Boulevard
Memphis, TN 38125
T 901.252.8000
I www.tnb-europe.com
Kopex-Ex
UK Sales Office
Thomas & Betts
Asia (Singapore) Pte Ltd
Station Road, Coleshill,
Birmingham, B46 1HT
T +44 (0) 1675 468 213
F +44 (0) 1675 468 280
I www.kopex-ex.com
10 Ang Mo kio
Street 65, #06-07 Techpoint
Singapore 569059
T +65 6720 8828
F +65 6720 8780
E [email protected]
Thomas & Betts
EMEA European Centre
DTS
International Call Centre
200 Chaussee de Waterloo
B-1640 Rhode-St-Genese
Belgium
T +32 (0) 2 359 82 00
F +44 (0) 2 359 82 01
E [email protected]
Z.I. Parc d’Activités de la Gare
19 à 21 avenue Henri Beaudelet
B.P. 27 - 77831 Ozoir Cedex
France
T +33 (0) 1 64 40 27 26
F +33 (0) 1 64 40 20 11
E [email protected]
I www.tnb-hazardous.com
190
www.tnb-hazardous.com
Introduction
Thomas & Betts - Industrial Capabilities
Key of Symbols
Key of Symbols
Welcome
Thomas &toBetts Worldwide
Thomas
& Capabilities
Betts
Industrial
DTS & Kopex Ex Symbols
Market Segments
At Thomas & Betts, our focus is on improving your business
performance by providing practical, reliable electrical
products & services. To connect & protect for life. To solve
Utilities /
Power
everyday problems in the area’s of Wire & Cable Management,
Cable Protection, Power Connection & Control and Safety.
Food &
Beverage
Marine &
Shipbuilding
Chemical &
Pharmaceutical
Mining
Ex de
Ex tb
Ex t
Zone 20
Zone 21
Zone 22
Class II
Division 1
Division 2
Onshore &
Offshore
Product Characteristics
Our extensive engineering, supply chain management
and technical sales support teams are committed to
understanding everything that impacts your ability to
accomplish your business objectives by reducing your total
cost of ownership.
Ex e
Ex d
Ex n
Ex nA
Ex ia
Ex eia
Zone 0
Zone 1
Zone 2
Gas IIB
Gas IIC
Dust IIIC
Group I
Group II
Class I
54
56
Ex tc
Ex tD
IK 09
IK 10
Whether you are designing, installing, operating, maintaining
or owning an office building, off-shore platform, hospital,
T&B Headquarters
or a high speed train, power generating plant, machine
Thomas
Betts Corporation
equipment
or a &manufacturing
facility, Thomas & Betts
World Headquarters
engineered products fit and function in your application
while providing
superior
performance, sustainability, and
8155 T&B
Boulevard
Memphis, the
TN 38125
value throughout
project life cycle.
T 901.252.8000
Thomas & Betts
I www.tnb-europe.com
All our brands are built upon four product
& service Pte Ltd
Asia (Singapore)
Europe, Middle East, Asia
solution platforms. Platforms that address you or your
10 Ang Mo kio
Kopex International
customers’
electrical
& lighting needs
covering
the Techpoint
Street
65, #06-07
UK critical
Head Offi
ce
Singapore
569059
protection of data, energy, processes, assets
and personal
T +65 6720 8828
Station
Road,
Coleshill,
safety. Beyond hi-performance application characteristics,
F +65 6720 8780
Birmingham, B46 1HT
Thomas T&+44
Betts(0)
products,
information
and services
facilitate
E asia.inquiry
1675 468
213
@tnb.com
F +44
1675
468critical
280 assembly, installation or
and speed
up(0)
your
time
I www.kopex-ex.com
maintenance process.
DTS
International Call Centre
Thomas & Betts
Z.I. Parc d’Activités de la Gare
EMEA European Centre
19 à 21 avenue Henri Beaudelet
B.P. 27 - 77831 Ozoir Cedex
200 Chaussee de Waterloo
France
B-1640 Rhode-St-Genese
T +33 (0) 1 64 40 27 26
Belgium
F +33 (0) 1 64 40 20 11
T +32 (0) 2 359 82 00
E [email protected]
F +44 (0) 2 359 82 01
I www.dtselec.fr
E [email protected]
IP 54
IP 56
64
IP 64
66
IP 66
67
IP 67
Battery LED Signals
SATI
Thomas & Betts in Europe:
2
98
Healthy
(test OK)
www.tnb.com
Emergency or
Indicator
Lamp Fault
(must be
replaced)
Test in
Progress
(waiting end
of test)
Fault
(replace
battery)
Healthy
Emergency or
Indicator
Lamp Fault
Test in
Progress
Fault
www.tnb-hazardous.com
A Member of the ABB Group
A Member of the ABB Group
Introduction
Thomas & Betts - Industrial Capabilities
Key of Symbols
Key of Symbols
Welcome
Thomas &toBetts Worldwide
Thomas
& Capabilities
Betts
Industrial
DTS & Kopex Ex Symbols
Market Segments
At Thomas & Betts, our focus is on improving your business
performance by providing practical, reliable electrical
products & services. To connect & protect for life. To solve
Utilities /
Power
everyday problems in the area’s of Wire & Cable Management,
Cable Protection, Power Connection & Control and Safety.
Food &
Beverage
Marine &
Shipbuilding
Chemical &
Pharmaceutical
Mining
Ex de
Ex tb
Ex t
Zone 20
Zone 21
Zone 22
Class II
Division 1
Division 2
Onshore &
Offshore
Product Characteristics
Our extensive engineering, supply chain management
and technical sales support teams are committed to
understanding everything that impacts your ability to
accomplish your business objectives by reducing your total
cost of ownership.
Ex e
Ex d
Ex n
Ex nA
Ex ia
Ex eia
Zone 0
Zone 1
Zone 2
Gas IIB
Gas IIC
Dust IIIC
Group I
Group II
Class I
54
56
Ex tc
Ex tD
IK 09
IK 10
Whether you are designing, installing, operating, maintaining
or owning an office building, off-shore platform, hospital,
T&B Headquarters
or a high speed train, power generating plant, machine
Thomas
Betts Corporation
equipment
or a &manufacturing
facility, Thomas & Betts
World Headquarters
engineered products fit and function in your application
while providing
superior
performance, sustainability, and
8155 T&B
Boulevard
Memphis, the
TN 38125
value throughout
project life cycle.
T 901.252.8000
Thomas & Betts
I www.tnb-europe.com
All our brands are built upon four product
& service Pte Ltd
Asia (Singapore)
Europe, Middle East, Asia
solution platforms. Platforms that address you or your
10 Ang Mo kio
Kopex International
customers’
electrical
& lighting needs
covering
the Techpoint
Street
65, #06-07
UK critical
Head Offi
ce
Singapore
569059
protection of data, energy, processes, assets
and personal
T +65 6720 8828
Station
Road,
Coleshill,
safety. Beyond hi-performance application characteristics,
F +65 6720 8780
Birmingham, B46 1HT
Thomas T&+44
Betts(0)
products,
information
and services
facilitate
E asia.inquiry
1675 468
213
@tnb.com
F +44
1675
468critical
280 assembly, installation or
and speed
up(0)
your
time
I www.kopex-ex.com
maintenance process.
DTS
International Call Centre
Thomas & Betts
Z.I. Parc d’Activités de la Gare
EMEA European Centre
19 à 21 avenue Henri Beaudelet
B.P. 27 - 77831 Ozoir Cedex
200 Chaussee de Waterloo
France
B-1640 Rhode-St-Genese
T +33 (0) 1 64 40 27 26
Belgium
F +33 (0) 1 64 40 20 11
T +32 (0) 2 359 82 00
E [email protected]
F +44 (0) 2 359 82 01
I www.dtselec.fr
E [email protected]
IP 54
IP 56
64
IP 64
66
IP 66
67
IP 67
Battery LED Signals
SATI
Thomas & Betts in Europe:
2
98
Healthy
(test OK)
www.tnb.com
Emergency or
Indicator
Lamp Fault
(must be
replaced)
Test in
Progress
(waiting end
of test)
Fault
(replace
battery)
Healthy
Emergency or
Indicator
Lamp Fault
Test in
Progress
Fault
www.tnb-hazardous.com
A Member of the ABB Group
A Member of the ABB Group
Thomas and Betts manufacture and design a wide range of electrical equipment for hazardous
and hostile environments to ensure the safety of the personnel working in them.
The extensive range covers Kopex-Ex metallic and non metallic conduit and fittings and the
DTS range of lighting junction and control boxes. These products are approved to a wide range
of hazardous area standards including ATEX, IECEx, UL, CSA, GOST and Inmetro.
Thomas & Betts | France / Belgium
T +33 (0) 1 64 40 27 26
E [email protected]
T
Thomas & Betts | Middle East
+971 (0) 4 609 1635
E [email protected]
T
T
Thomas & Betts | Germany / Austria
+49 (0) 62 51 669/0
E [email protected]
T
Thomas & Betts | Netherlands
+31 (0) 180 641 888
E [email protected]
T
Thomas & Betts | Italy
+39 039 65 79 028
T
Thomas & Betts | Spain
34 938 45 4570
E [email protected]
T
Thomas & Betts | UK
+44 (0) 1675 468 213
E [email protected]
Thomas & Betts | USA
901 252 5000
E [email protected]
LIT-140GBR 08/13 • Designed by www.uc4.co.uk
T
Thomas & Betts | Switzerland (PMA)
+41 44 905 61 11
E [email protected]
Product Catalogue
Lighting, Boxes, Cabinets,
Conduits, Fittings & Accessories for
Hazardous and Hostile Areas
The content of the Thomas & Betts catalogue has been carefully checked for accuracy at the time of print. However,
Thomas & Betts doesn’t give any warranty of any kind, express or implied, in this respect and shall not be liable for
any loss or damage that may result from any use or as a consequence of any inaccuracies in or any omissions from the
information which it may contain.
Copyright Thomas & Betts 2006. Copyright in these pages is owned by Thomas & Betts except where otherwise indicated.
No part of this publication may be reproduced, copied or transmitted in any form or by any means, without our prior
written permission. Images, trade marks, brands, designs and technology are also protected by other intellectual property
rights and may not be reproduced or appropriated in any manner without written permission of their respective owners.
Thomas & Betts reserves the right to change and improve any product specifications or other mentions in the catalogue
at its own discretion and at any time. These conditions of use are governed by the laws of the Netherlands and the courts
of Amsterdam shall have exclusive jurisdiction in any dispute.
Lighting, Boxes, Cabinets, Conduits, Fittings & Accessories for Hazardous and Hostile Areas
Thomas & Betts Sales Offices
A Member of the ABB Group
A Member of the ABB Group
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project