IC697MDL350

IC697MDL350
1
Discrete Output Modules
IC697MDL350
49
GFK-0081H
August 1997
Discrete Output Modules
120 Volt AC 0.5 Amp, 32-Point Output Module
120 Volt AC 0.5 Amp, 32-Point Output Module (IC697MDL350)
datasheet GFK-0081H
a44710
Features
D 32 Points - Four isolated groups of 8 points each
D 0.5 amp capacity per point
D High inrush capacity (20x rated current)
A1
A2
A3
A4
A5
A6
A7
A8
The 120 Volt AC 0.5 Amp Output Module provides 32
output points in four isolated groups of 8 points each.
This allows each group of 8 points to be used on a different phase of the AC supply. Each group of 8 outputs is individually fused with a 5 amp fuse.
The module provides a high degree of inrush current
which makes the outputs suitable for a wide range of
inductive and incandescent loads. The module will
pick up most size 2 contactors.
LED indicators which give the ON-OFF status of each
point on the logic (PLC) side of the circuits as well as
an LED to indicate the status of the fuses are located
together at the top of the module.
The module is mechanically keyed to ensure correct
replacement with a similar type in the field. I/O references are user configurable without the use of jumpers or DIP switches on the module.
Configuration is done using the configuration function of the MS-DOSr or Windowsr programming
software running on Windowsr 95 or Windows NTr
over Ethernet TCP/IP or through the SNP port. The
Programming Software configuration function is
installed on the programming device. The programming device can be an IBM XT, AT, PS/2 or compatible Personal Computer.
B1
B2
B3
B4
B5
B6
B7
B8
FUSE
ÎÎ
ÎÎ
ÎÎ
ÎÎ
ÎÎ
ÎÎ
ÎÎ
ÎÎ
ÎÎ
ÎÎ
ÎÎ
ÎÎ
ÎÎ
ÎÎ
ÎÎ
ÎÎ
ÎÎ
ÎÎ
ÎÎ
ÎÎ
ÎÎ
ÎÎ
ÎÎ
ÎÎ
ÎÎ
ÎÎ
Î
ÎÎ
ÎÎ Î
D1
D2
D3
D4
D5
D6
D7
D8
A1
A2
A3
A4
A5
A6
A7
A8
B1
B2
B3
B4
B5
B6
B7
B8
C1
C2
C3
C4
C5
C6
C7
C8
D1
D2
D3
D4
D5
D6
D7
D8
FUSE
OUTPUT
120VAC
0.5A/PT
PILOT DUTY
A1
A2
A3
A4
A5
A6
A7
A8
B1
B2
B3
B4
B5
B6
B7
B8
C1
C2
C3
C4
C5
C6
C7
C8
D1
D2
D3
D4
D5
D6
D7
D8
SLOT
r
C1
C2
C3
C4
C5
C6
C7
C8
50/60 HZ
2A MAX/GRP
1
2
A1
3
A2
5
A4
4
A3
A5
6
7
A6
9
A8
8
H
~
N
A7
10
11
12
B1
13
B2
15
B4
B3
14
16
B5
17
B6
19
B8
18
H
~
N
B7
20
21
22
C1
23
C2
25
C4
27
C6
29
C8
24
C3
26
C5
28
H
~
N
C7
30
31
D1
32
33
D2
35
D4
D3
34
D5
36
37
D6
39
D8
H
~
N
D7
38
40
MODULE IC697MDL350
LABEL 44A726758-005R01
IBM and PS/2 are registered trademarks of International Business Machines Corporation.
r MS-DOS, Windows, Windows 95, and Windows NT are registered trademarks of Microsoft Corporation.
t
Series 90 -70 Programmable Controller Data Sheet Manual
GFK-0600F
49-1
Discrete Output Modules
2
GFK-0081H
August 1997
120 Volt AC 0.5 Amp, 32-Point Output Module
Operation of the 120 Volt AC 0.5 Amp Output Module
TO OTHER OUTPUTS
OPTO
ISOLATOR
OPEN FUSE
DETECTOR
ÎÎ Î
a42138
~
FUSE
SYSTEM
INTERFACE
BACKPLANE
LED
OPTO
ISOLATOR
OUTPUT
DRIVER
COMMON
ÎÎÎ
LOAD
FIELD
CONNECTIONS
MODULE
Figure 1. Block Diagram for IC697MDL350
Output Characteristics
Fault Mode Selection
The 120 Volt AC 0.5 Amp Output Module is compatible with a wide variety of load devices, such as:
D Solenoids and motor starters
D Indicators
The rating of 0.5 amps per point applies to the longterm current capacity of each point. Because of overall heat dissipation within the module, the maximum
current capacity for each group of 8 outputs is limited
at higher temperatures (refer to the specifications on
the last page of this data sheet).
Each output on this module is capable of transiently
conducting a surge current which is much greater
than its long-term current rating.
The rate at which such surges can be repeated depends on the current rating of the device and the
duty cycle (percent of time the device is ON). For typical incandescent devices operating at a 50% duty
cycle, the following repetition rates apply.
Steady-state
Current (mA)
100
250
500
49-2
Repetition Rate
(Hz)
The module can be configured from the programmer
so that output points assume one of two states in response to certain operating or default conditions.
D Maintain existing output state
D Turn outputs OFF
This is explained in more detail in the applicable Programmable Controller Reference Manual.
Fusing
Each group of 8 outputs is fused with a 5 amp fuse.
Replaces with a 5 amp fuses. Replace with either of
the following types:
D 3AG - 5 amp, 250V, Fast Acting
D Metric 5 x 20 mm - 5 amp, 250V, Fast Acting
5
1
0.1
t
Series 90 -70 Programmable Controller Data Sheet Manual
GFK-0600F
Discrete Output Modules
3
GFK-0081H
August 1997
120 Volt AC 0.5 Amp, 32-Point Output Module
Module Mechanical Keying
This module includes a mechanical key that prevents
inadvertent substitution of one module type for
another in a given slot. The key fits a uniquely
shaped area on the board below the connector. The
key is included with each module.
a42146
TERMINALS
1
A1
2
3
4
If it is necessary to change the module location in the
rack after the key has been latched onto the center rail
of the rack, the key can be removed by pushing it upward to unhook the latch while pulling if off the rail.
It may then be reinstated onto the module and the
module inserted into the rack in the desired location.
Note: only the power supply can be placed in he leftmost rack position.
A2
A3
5
6
When the module is first installed, the key latches
onto the backplane center rail. When the module is
extracted, the key remains in the center rail, configuring the slot to accept only identical module types.
FIELD WIRING
H
A4
7
~
N
A5
A6
A7
8
9
A8
10
11
12
B1
13
14
B2
B3
15
16
H
B4
17
18
~
N
B5
B6
B7
19
B8
20
21
22
C1
23
Field Wiring
24
25
26
The module is wired as shown. Since each group of
eight outputs is isolated from the others, a wire from
the power source to the power input terminals for
each group is required (power input terminals for
each group are not connected inside the module).
C2
C3
27
28
~
N
C5
C6
C7
29
C8
30
31
32
D1
33
The detachable field wiring terminal board will accept
wire sizes from AWG #22 (0.36 mm2) through AWG
#14 (2.10 mm2). Two wires may be terminated on a
given lug if both wires are the same size. There is
room for a bundle of forty AWG #14 wires to be
routed out through the terminal board cavity.
H
C4
34
D2
D3
36
H
D4
35
D5
D6
37
38
~
N
D7
39
D8
40
The wire bundle can be secured to the terminal board
by passing a cable tie through a cleat located at the
lower corner of the terminal board.
t
Series 90 -70 Programmable Controller Data Sheet Manual
GFK-0600F
Figure 2. Field Wiring Connections
49-3
Discrete Output Modules
4
GFK-0081H
August 1997
120 Volt AC 0.5 Amp, 32-Point Output Module
Recommended Field Wiring Procedures
The following procedures are recommended when
connecting field wiring to the detachable terminal
board on this input module. Module features referenced in the following procedures which are common
to all IC697 I/O modules are illustrated in the following figure.
a43855
JACKSCREW
HINGED
DOOR
TERMINAL
BOARD
CORD
TIE
ÎÎ
ÎÎ
CORD
TIE
CLEAT
ÎÎ
ÎÎ
JACKSCREW
ÎÎÎÎ
ÎÎÎÎ
ÎÎÎÎ
ÎÎÎÎ
ÎÎÎÎ
ÎÎÎÎ
ÎÎÎÎ
ÎÎÎÎ
ÎÎÎÎ
ÎÎÎÎ
ÎÎÎÎ
ÎÎÎÎ
ÎÎÎÎ
Î
Î
ÎÎÎÎ
Î
Î
Î
CORD
TIE
CLEAT
CORD
TIE
STRAP
CLEAT
Î
Î
Î
Î
STRAP
STRAP
Figure 3. I/O Module Features
1. Turn off power before removing or installing terminal boards. Open the hinged door on the module to access a jackscrew which holds the terminal
board securely in place. The detachable field wiring terminal board can now be removed from the
module by turning the jackscrew counter-clockwise until it is fully disengaged.
2. To remove the terminal board, grasp the top of the
terminal board and swing it outward as shown in
Figure 4.
Caution
Do not use the hinged door to remove the
terminal board. The hinged door could
be damaged if this is done.
49-4
3. The terminal board is designed to accept wire sizes
from AWG #22 (0.36 mm) through AWG #14 (2.1
mm). It is important that when using AWG #14
(2.1 mm2) wire for wiring all points, that a maximum insulation diameter of .135 inch (3.43mm)
not be exceeded. To ensure proper connection,
two wires may be terminated on any one terminal
only if both wires are the same size.
4. The terminal board is designed to accept a maximum of (40) AWG #14 (2.1 mm2)wires. If AWG
#14 (2.1 mm2) wires are to be used, then wire
markers should be placed at least 8 inches (203
mm) from termination end to provide sufficient
space for the hinged door to close.
t
Series 90 -70 Programmable Controller Data Sheet Manual
GFK-0600F
Discrete Output Modules
5
GFK-0081H
August 1997
120 Volt AC 0.5 Amp, 32-Point Output Module
Î
Î
ÎÎ
ÎÎÎÎ
ÎÎÎ
ÎÎ
ÎÎ
ÎÎ
ÎÎ
ÎÎÎÎ
ÎÎ
Î
Î
ÎÎ
Î
ÎÎ
ÎÎÎ
ÎÎ
ÎÎ
ÎÎ
ÎÎ
Î
Î
Î
ÎÎ
ÎÎ
JACKSCREW
a43747
ÎÎ
ÎÎ
ÎÎ
ÎÎ
ÎÎÎ
ÎÎ
ÎÎÎÎ
ÎÎ
ÎÎÎÎÎ
ÎÎÎÎÎ
DO NOT
PULL
ON DOOR
WIRE BUNDLE CABLE TIE CLEAT
Figure 4. Removal of I/O Terminal Board
5. After completing connections to all modules in a
rack, the wire bundle must be secured. To ensure
that the wire bundle is secured properly, it is recommended that a cable tie be wrapped around the
wire bundle and tightly secured through the cable
tie cleat located at the lower right corner of the
terminal board. For extremely large wire bundles,
additional cable ties should be used.
6. A door label insert is included with each module to
indicate circuit wiring information and provide
space to record user circuit wiring identification.
A slot is provided on the hinged door to allow for
insertion of this label. If the label is difficult to insert, crease the scored edge before insertion. The
outside label has a color coded stripe to allow
quick identification of the module voltage type
(blue: low voltage; red: high voltage).
7. After field wiring is completed, the terminal board
should be securely fastened to the rack by inserting the terminal board strap (attached to each
module) into the small rectangular slots in the bottom card guide grill on the rack. This strap not
t
Series 90 -70 Programmable Controller Data Sheet Manual
GFK-0600F
only secures the terminal board to the rack, it also
provides a way of identifying the wired terminal
board with its correct mating rack slot location.
8. For adequate module ventilation, it is recommended that at least a 6 inch (152mm) clearance be
allowed above and below the rack grill. Wire
bundles should not obstruct the rack grill work.
Removing an I/O Module
The instructions below should be followed when removing an I/O module from its slot in a rack.
D Grasp the board firmly at the top and bottom of
the board cover with your thumbs on the front of
the cover and your fingers on the plastic clips on
the back of the cover.
D Squeeze the rack clips on the back of the cover
with your fingers to disengage the clip from the
rack rail and pull the board firmly to remove it
from the backplane connector.
D Slide the board along the card guide and remove it
from the rack.
49-5
Discrete Output Modules
6
GFK-0081H
August 1997
120 Volt AC 0.5 Amp, 32-Point Output Module
Table 1. Specifications for IC697MDL350 [
Rated Voltage:
120 volts AC
Outputs per Module:
32 (four groups of 8 outputs each)
Isolation:
1500 volts - any output to backplane
500 volts between groups
Output Voltage Range:
85 to 132 volt, 47-63 Hz
Output Current:
0.5 amps maximum per point
2 amps maximum per group
Output Characteristics Inrush Current:
10 amps maximum per point for one cycle (20 ms)
Output Voltage Drop:
3 volts maximum
Response Time-On:
1 ms maximum
Response Time-Off:
1/2cycle
OutputLeakage:
1.5 mA maximum
Current Required from 5V Bus:
0.5 amp
VME
System designed to support the VME standard C.1
[ Refer to GFK-0867B, or later for product standards and general specifications. For installations requiring compliance to more
stringent requirements (for example, FCC or European Union Directives), refer to Installation Requirements for Conformance to
Standards.
Table 2. Ordering Information
Description
Catalog Number
Output Module - 120 Volt AC 0.5 Amp, 32 Points
IC697MDL350
Note: For Conformal Coat option, or Low Temperature Testing option please consult the
factory for price and availability.