G2…(S) 2-way Globe Valve, Bronze or Stainless Steel Trim Application

G2…(S) 2-way Globe Valve, Bronze or Stainless Steel Trim Application
G2…(S) 2-way Globe Valve, Bronze or Stainless Steel Trim
Application
This valve is typically used in Air Handling Units on heating or cooling coils and Fan Coil
Unit heating or cooling coils. Some other common applications include Unit Ventilators, VAV Box reheat coils and bypass loops. This valve is suitable for use in a hydronic
system with variable flow.
Bronze and stainless steel trim valves can be used for steam applications, depending on
actuator and close-off combinations.
50 psi (345 kPa)
100 psi (689 kPa)
20°F to 250°F
(-7°C to 120°C)
20°F to 300°F
(-7°C to 149°C)
35 psi (241 kPa)
15 psi (103 kPa)
20 psi (138 kPa)
35 psi (241 kPa)
35 psi (241 kPa)
35 psi (241 kPa)
5:1 G212(S)
15:1 G213(S)
25:1 G214(S)
40:1 G215(S)
50:1 G219(S)
60:1 G220(S), G224(S)
75:1 all others
*(50% or more open)
G2...(S) 2-way Flow Patterns
Flow Direction
800-543-9038 USA
8
NVF Series
LF Series
AF(X)
NF
Series
NV Series
LM Series
Dimensions
Valve Body
G212(S)-G215(S)
G219(S)-G220(S)
G224(S)-G225(S)
G232(S)
G240(S)
G250(S)
Valve Nominal Size
Inches DN [mm]
½”
15
¾”
20
1”
25
1¼
32
1½
40
2
50
Dimensions (Inches [mm])
A
B
3.06” [78]
1.06” [27]
3.62” [92]
1.06” [27]
4.62” [117]
1.12” [29]
4.62” [117]
1.37” [35]
5.37” [137]
1.50” [38]
6.12” [156]
1.56” [40]
Piping
The valves should be mounted in a weather-protected area in a location that is within
the ambient limits of the actuator. Allow sufficient room for valve with actuator and for
service. For the NV Series, allow 6” for cover removal and 12” for complete actuator
removal. The G2(S) and G3(D) preferred mounting position of the valve is with the
valve stem vertical above the valve body, for maximum life. However, the assemblies
can be mounted with the valve stem vertical or horizontal in relation to the pipe. The
actuators should never be mounted underneath the valve, as condensation can build
up and result in a failure of the actuators. Do not reverse flow direction.
Stem Up - Open A to AB
866-805-7089 CANADA
203-791-8396 LATIN AMERICA
M40026 - 07/10 - Subject to change. © Belimo Aircontrols (USA), Inc.
Maximum ΔP*
Water
Steam (NV Actuator)
Steam (Rotary Actuator)
Rangeability
15 psi (103 kPa)
35 psi (241 kPa)
Suitable Actuators
Non-Spring
Spring
D031-2W
bronze
bronze
bronze
stainless steel
stainless steel
stainless steel
brass
stainless steel
spring loaded TFE
spring loaded TFE
composition (EPDM)
Teflon
ANSI 250 (up to 400 psi below 150°F)
ANSI class IV
Type
2-way NPT
G212(S)
G213(S)
G214(S)
G215(S)
G219(S)
G220(S)
G224(S)
G225(S)
G232(S)
G240(S)
G250(S)
NM
Series
G2
G2...S
chilled or hot water, 60% glycol, steam
equal percentage
linear
stem up - open A to AB
½” to 2”
NPT female ends
Service
Flow characteristic
Action
Sizes
End fitting
Materials
Body
Seat
Stem
Plug
Packing
Disc
ANSI class
Leakage
Max steam inlet
NV actuators
Rotary actuators
Media temperature
Water
Valve Nominal Size
Inches DN [mm]
½
15
½
15
½
15
½
15
¾
20
¾
20
1
25
1
25
1¼
32
1½
40
2
50
AM
Technical Data
Cv
0.4
1.3
2.2
4.4
5.5
7.5
10
14
20
28
40
NVF(D)24(-E) US Actuators, On/Off
7.05" [179]
4.35" [110]
D031
Dimensions with G2... Series 2-Way Valve
Assembly using UNV-001 Bracket
C
B
A
Valve Body
G2
G2
G2
G2
G2
G2
Models
NVF24 US
Spring Up
NVF24-E US Spring Down
NVFD24 US Spring Up
NVFD24-E US
Spring Down
M40026 - 07/10 - Subject to change. © Belimo Aircontrols (USA), Inc.
Overload protection
Control Signal Y
Operating range
Maximum stroke
Plunger
NVF...24 US
NVF...24-E US
Force
NVFD24(-E) US
NVF24(-E) US
Position indication
Manual override
Running time
24 VAC ± 20% 50/60 Hz, 24 VDC ± 10%
19.2...28.8 VAC, 21.6...28.8 VDC
5.5 W
10 VA (Class 2 power source)
3 ft, 18 GA plenum rated cable
½” conduit connector
electronic throughout stroke
On/Off
2 to 10 VDC
¾” [20mm]
Dimensions with G2...S Series 2-Way Valve
Assembly using UNV-035 Bracket (Bracket is 1.563” longer than UNV-001)
7.05" [179]
spring up
spring down
Humidity
Ambient temperature
Storage temperature
Housing
Housing material
Agency listings†
EMC
Software
Mode of operation
Noise level
Quality standard
4.35" [110]
C
90 lbf [400 N]
180 lbf [800 N]
stroke indicator on bracket
3/16” hex, 5mm hex or phillips screwdriver
motor 150 seconds, independent of load
spring 30 seconds at ¾” [20mm] stroke
5 to 95% RH non-condensing
32°F to 122°F [0°C to 50°C]
20°F to 250°F [-7°C to 120°C]
NEMA 2/IP54 with cable entry down
UL94-5V (flammability rating)
CE, UL 60730-1, CSA C22.2 No. 139 certified
CE acc. to 89/336/EEC
Class A to UL 60730-1
Type 1 to UL 60730-1
<35 dB(A)
ISO 9001
800-543-9038 USA
Dimensions (Inches [mm])
A
B
C
9.75" [248]
3.00" [76]
1.06" [27]
9.75" [248]
3.62" [92]
1.06" [27]
4.62" [117]
1.12" [29] 10.43" [265]
4.62" [117]
1.37” [35] 10.43" [265]
5.37" [137]
1.50” [38] 10.50" [267]
6.12" [156]
1.56” [40] 10.81" [275]
D056
Technical Data
Power supply
Nominal Voltage Range
Power consumption
Transformer sizing
Electrical connection
Valve Nominal Size
Inches DN [mm]
1/2"
15
3/4"
20
1"
25
1-1/4"
32
1-1/2"
40
2"
50
B
A
Valve Body
G2S
G2S
G2S
G2S
G2S
G2S
866-805-7089 CANADA
Valve Nominal Size
Inches DN [mm]
1/2"
15
3/4"
20
1"
25
1-1/4"
32
1-1/2"
40
2"
50
Dimensions (Inches [mm])
A
B
C
3.00" [76]
1.06" [27] 11.31" [287]
3.62" [92]
1.06" [27] 11.31" [287]
4.62" [117]
1.12" [29] 12.00" [305]
4.62" [117]
1.37” [35] 12.00" [305]
5.37" [137]
1.50” [38] 12.06” [306]
6.12" [156]
1.56” [40] 12.37” [314]
203-791-8396 LATIN AMERICA
47
NVF(D)...24(-E) US Actuators, On/Off
7.05" [179]
Wiring Diagrams
W136-ON-OFF
Dimensions with G3...(D) Series 3-Way Valve
4.35" [110]
C
B
A
Valve Body
G3(D)
G3(D)
G3(D)
G3(D)
G3(D)
G3(D)
G3(D)
Valve Nominal Size
Inches DN [mm]
1/2"
15
1/2"
15
3/4"
20
1"
25
1-1/4"
32
1-1/2"
40
2"
50
Dimensions (Inches [mm])
A
B
C
9.75" [248]
3.00" [76]
1.37" [35]
9.75" [248]
3.00" [76]
1.37" [35]
9.75" [248]
3.62" [92]
1.68” [43]
4.62" [117]
1.56" [40]
9.81” [249]
4.62" [117]
1.62" [41] 10.06” [256]
9.18” [234]
5.37" [137]
1.62" [41]
9.25” [235]
6.12" [156]
1.87” [48]
On/Off control
Spring Return Actuators Model Designation
NVF(D)24 US
retracting plunger (spring up)
M40026 - 07/10 - Subject to change. © Belimo Aircontrols (USA), Inc.
NVF(D)24-E US
extending plunger (spring down)
800-543-9038 USA
48
866-805-7089 CANADA
203-791-8396 LATIN AMERICA
Close-Off Pressures (psi)
G2/G3 Spring Return and Non-Spring Return
Non-Spring Return
NVD
2-way
G212(S)
G213(S)
G214(S)
G215(S)
G219(S)
G220(S)
G224(S)
G225(S)
G232(S)
G240(S)
G250(S)
NV
NVG
250
250
250
250
250
250
G315
G320
G325
G332
G340
G350
AM
NVFD
NVF
250
250
250
250
250
250
250
250
158
160
190
LF
250
250
250
250
250
250
250
250
250
250
250
250
250
250
250
250
250
250
250
250
250
250
250
AFX
169
93
230
127
169
93
230
127
250
250
250
250
250
158
250
250
250
250
250
250
250
M40026 - 07/10 - Subject to change. © Belimo Aircontrols (USA), Inc.
250
250
250
207
130
88
47
169
93
AF
250
250
158
250
168
105
NF
250
250
250
250
185
185
207
207
130
88
47
230
127
250
162
110
58
3-way Diverting
G315D
G320D
G325D
G332D
G340D
G350D
Spring Return
NM
250
250
250
250
250
250
250
250
162
110
58
3-way Mixing
G314
LM
800-543-9038 USA
86
866-805-7089 CANADA
203-791-8396 LATIN AMERICA