pwr i0a2 z206731-0a

pwr i0a2 z206731-0a
Installation Guide
Pressure
TM
PWR Series
Wet Media Remote Pressure Transducer
Product Overview
The PWR Series remote pressure transducers are designed for differential pressure applications. The sensors are
remotely installed on existing plumbing runs. The PWR is available with either armored (6 ft.) or shielded (10
or 20 ft) sensor cables, and it requires a 15 to 30 VDC or 24 VAC power source to generate its output. The PWR is
warranted for a period of five years.
RoHS
Product Identification
Compliant
NOTICE
• This product is not intended for life or safety applications.
• Do not install this product in hazardous or classified locations.
• Read and understand the instructions before installing
this product.
• Turn off all power supplying equipment before working on it.
• The installer is responsible for conformance to all applicable codes.
PWR
Display
L
NIST
X
= LCD
Operational Range Media
S
= Standard
No responsibility is assumed by Veris Industries for any consequences arising out of the
use of this material.
03 = 0-50 psid
04 = 0-100 psid
05 = 0-250 psid
Cable Length
= Water
006 = 6 ft (1.8 m)
010 = 10 ft (3.1 m)
020 = 20 ft (6.1 m)
Cable
Blank = Standard†
A = Armored‡
† Standard cable available only in 10 ft and 20 ft lengths.
‡ Armored cable available only in 6 ft length.
Note: Extension of total cable length greater than 20 feet
may result in reduced accuracy.
Specifications
Media Compatibility
Input Power
Maximum Current Draw
Output
Status Indication
17-4 PH stainless steel
15 to 30VDC, 24VAC nom. 50/60 Hz*
DC: 125mA; AC: 280mA
3-wire transmitter; user-selectable 4-20mA/0-5V/0-10V
Dual color LED
Proof Pressure
2x max. F.S. range**
Burst Pressure
5x max. F.S. range**
Accuracy at 25°C***
Surge Damping
Long Term Stability
Zero Offset
(Bidirectional and Port
Swap Modes Only)
Zero Adjust
Fittings
Ranges A and B: ±1% F.S. typical; Range C: ±1.5% F.S. typical;
Range D: ±2% F.S. typical.
(For less than or equal to 20 ft. (6.1 m) cable length)
Electronic; 1 or 5 second averaging
±0.25%
0.5%
Pushbutton auto-zero and digital input (2-position terminal block)
¼” NPT female thread, stainless steel 17-4 PH;
Overall thread length: 0.59” (conforms to ANSI/ASME B1.20.1 standard)
OPERATIONAL RANGES
0-50 psig
Z206731-0A
Page 1 of 4
5/10/25/50 psid
0-100 psig
10/20/50/100 psid
0-250 psig
25/50/125/250 psid
©2014 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide
Pressure
PWR Series
Specifications (cont.)
TM
OPERATING CONDITIONS
Temperature Compensated
Range
Sensor Operating Range
Operating Environment
0° to 50°C (32° to 122°F);
TC Zero <1.5% of product F.S. per sensor;
TC Span <1.5% of product F.S. per sensor
-20° to 85°C (-4° to 185°F)
-10° to 50°C (14° to 122°F); 10-90% RH noncondensing
COMPLIANCE INFORMATION
Approvals
RoHS, IP65, CE
* VFD systems and system wiring generate fields that can disrupt electrical devices. Ensure that these fields are minimized and
are not affecting the sensor or sensor wiring.
** F.S. is defined as full span of selected range.
*** Accuracy combines linearity, hysteresis, and repeatability.
Dimensions
6.7"
(170 mm)
3.1"
(78 mm)
2.4"
(61 mm)
Installation
Disconnect power from the power source before beginning the installation.
Observe precautions for handling static sensitive
devices to avoid damage to the circuitry that
is not covered under the factory warranty.
1. Mount the housing using the included screws. Avoid locations where excessive vibrations occur.
2. Remove the housing cover by pressing the corner tabs. There are two tabs on each side of the housing. One side is shown below.
Press tabs to remove cover
(2 tabs per side)
Z206731-0A
Page 2 of 4
©2014 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide
Pressure
PWR Series
Installation (cont.)
TM
3. Run the digital control and power source wiring and connect to the left-most terminal block.
4. The sensors and monitor assembly are matched at the factory and calibrated as a unit. They must be kept paired to obtain the
accuracy stated in the product specifications. Verify that the serial numbers on the sensors match the serial number on the
main housing.
Main Housing serial number located
on label on the top of the housing
Sensor serial numbers
located on the sensor labels
HI
PWR
S/N
LO
PWR
S/N
5. Run wires from the remote pressure sensor cables and connect to the pair of 4-terminal blocks at the right side of the board. To
maintain the correct calibration, it is important not to confuse the high side and the low side. To assist, the sensors are labeled,
“HI” and “LO.”
Zero
mA
Volt
ON
OFF
Range
Status LED
Power
Shield
Signal
Common
Low Sensors Hi
POWER
SIGNAL
POWER SOURCE
15 to 30 VDC/24 VAC
A
B
C
D
1 2 3 4 5 6
COM
Wire Colors
(coming from sensor cable)
Red
Power
DIGITAL CONTROL
Analog Input: 0-5V/0-10V
or 4-20mA
Uninsulated
Shield
Optional
Digital Output
White/Clear
Signal
Black
Common
Range
DIP Switches
Off/On*
D
Num
Function
10
5
1
Damping
Fast/Slow
20
10
2
Test
Operate/Test
50
25
3
Mode
Normal/Bidirec.
4
Analog
Normal/Reverse
5
Port
Normal/Swap
6
Voltage Out**
0-10V/0-5V
A
B
C
-03
50
25
-04
100
50
-05
250
125
Model
* “Off” position is the default setting for all DIP switches.
** Ignored in mA mode.
6. If the sensors are installed on the wrong side, they can be reversed in one of two ways:
• Swap the cables at the sensor end.
• Swap the headers at the control unit end.
7. Adjust the switches on the board as desired.
8. Reconnect power to the power source. Check that the green LED illuminates, indicating normal operation. If not, check the
wiring.
9. Re-affix the cover onto the housing, ensuring that the cover is properly seated. .Do not operate the PWR without the housing
cover in place.
10. Choose sensor mounting locations that minimize cable length. Use plumbing connections of appropriate “tees” or equivalent,
made of compatible material. Observe safety precautions for plumbing connections. Release pressure from the system. Tighten
sensor connections according to ANSI B1.20.3 (hand tighten plus one turn).
Z206731-0A
Page 3 of 4
©2014 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide
Pressure
PWR Series
Configuration
TM
Test Mode
Test mode overrides the output to full-scale. If the PWR is configured for current (mA) operation, Test mode sets the output to 20.0
mA. If configured for voltage (VDC) operation, Test mode sets the output to 5.0 VDC or 10.0 VDC (depending on the position of the
output selection switch).
Status LED
LED
Status
Solid Green
Normal operation.
Flashing Green
Low > High; use port swap jumper or bidirectional mode.
Solid Red
Differential pressure is too high; select a higher pressure range.
Flashing Red
Gauge pressure over sensor range; reduce line pressure or replace with a higher range device.
Alternating Red/Green Flash
Sensor input is below sensor range. Verify that the sensor is connected correctly.
Auto Zero Function
To automatically reset the output to zero pressure, press and hold the Zero push-button for 2 seconds or provide contact closure
on the auxiliary remote tare terminal. To protect the unit from accidental tare, this feature is enabled only when the detected
pressure is within 5% of factory calibration.
Z206731-0A
Page 4 of 4
©2014 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.