Basic Rack PDU
Basic Rack PDU
Overview
The American Power Conversion® Basic Rack
PDU distributes power to devices in the rack.
Outlets. The Rack PDU has twenty (20)
IEC-320-C13 outlets, and four (4) IEC-320-C19
outlets.
Power cord. The 3-foot (0.91-meter) power cord
terminates with a IEC-309 16 A connector.
AP7551
Specifications for AP7551
Electrical
Input connector
IEC-309 16 A plug
Output connectors
(20) IEC-320-C13,
(4) IEC-320-C19 outlets
Nominal input voltage
230 VAC
Acceptable input voltage
± 10% of normal voltage
Input frequency
47– 63 Hz
Cord length
0.91 m (3 ft)
Physical
(H × W × D)
161.92×5.56×4.39 cm
(63.75×2.19×1.73 in)
Shipping dimensions
(H × W × D)
213.36×15.24×12.7 cm
(84.00×6.00×5.00 in)
Weight
5.56 kg (12.25 lb)
Shipping weight
6.46 kg (14.25 lb)
Environmental
Maximum elevation
(above MSL)
Operating
Storage
15 000 ft (4500 m)
50 000 ft (15 000 m)
Temperature
Operating
Storage
–5 to 45° C (23 to 115° F)
–25 to 65° C (–13 to 149° F)
Humidity
Operating
Storage
5 – 95% RH non-condensing
5 – 95% RH non-condensing
Compliance
Safety verification
VDE 0805, CE, EN 60950,
IEC 60950
990-1940-001
07/2004
*990-1940-001*