Bard WH301D, WH361D heat pump Installation instructions
Below you will find brief information for heat pump WH301D, heat pump WH361D. These are wall-mounted heat pumps that can be used for both heating and cooling your home. The units are designed to be easy to install and maintain, and they come with a number of features that make them energy efficient and reliable.
PDF
Document
Advertisement
Advertisement
Bard Manufacturing Company Bryan, Ohio 43506 Since 1914...Moving ahead, just as planned. Manual : Supersedes: File: Date: 2100-357 Volume IH Tab 17 07-08-99 © Copyright 1999 Wall Mount General Information ........mm==>=mrsesezanneso 2 Wall Mount NomenciatuUre ...........w.e.-.ww=evesarvene 2 Shipping Damage ................eeniservorirucacannariineocenonnes 5 General — ..........eeseanirerooreo enana cara cane rneenoeceneas 5 Duct Work ............e..rrnermeciocaoeravenrcoraracareoaceneiman eras 5 Filters — ree..eceorerirerenoenevencorernroreneacucete ren ciaren recono Fresh Air IntaKe ..................<..e-eicecezcacaoniooneracencoo venenos 6 Condensate Drain .................ercceveccrerirocrcuncanvevevennecos 6 instaliation instructions ...... 7 Wali Mounting Information rer rer rn Eee REG HE 7 Mounting the Unit ..........e-......e-sceceninsenar cananea enano 7 Typical instaliations ...................e-ererreczocasecarvenventacone 7 Top Outlet Only .................w..emmmnnenanennrin 7 с. Wiring — Main Power ....................orecezoneoneraencon IT Wiring — Low Voitage Wiring ...........+...«emrecereenenacanoos 11... Thermostat indicator Lamps .....i.....er-e.eseconervenna Lee 12° Emergency Heat Mode... Nn EEE 12 Compressor Maifunction Light ...............——.-.—e.ee...... 12 Figures Figure 1 Unit Dimensions ................e.e.nmrercacuaconanos 3 Figure2 Blower Damper Assembly ...................... 6 Figure 3 Mounting Instructions ..............——e— «ev... 8 Figure 3A Electric Heat Ciearance ............—.—.ew=..... 8 Figure 4 Wall Mounting Instructions ................—.. 9 Figure 5 Wali Mounting instructions ...................... 9 Figure 6 Common Wall Mounting INStRUCLIONS ….......….œ……cccoccsesosenercessansanrre 10 Figure 7 Unit 24V Terminal Board ....................... 11 Figure8 Start Up Label .................ecesemmennerennnónees 13 Figure9 Defrost Controi Board ......................... 15 Figure 10 Fan Blade Setting Dimensions .............. 18 Start Up ..... Important instalier Note................... esiraoonconcemareconaeas Crankcase Heaters .................—..e.—e.0m0ricivecanconecoras Service HintS ……...…….…aerrererssenenesasressassentenencanens Sequence of Operation .................e......... ascsaracsannene Pressure Service Ports enecocineroorammanearoneneta Defrost Cycle ..............enm1e=mrecrrearoneccccnenoccnoororeeconne. Troubleshooting Solid State Heat Pump Control Troubleshooting Procedure ................e.. meseros Checking Temperature Sensor Outside Unit Circuit ...................eeesscsmeiverercaverreneneas Temperature vs. Resistance of Temperature Sensor Chart................e......esvercerovenas - Fan Blade Setting Dimension ...............—.— e... — Tables Table 1 Table 2 Table 3 Table 4 Table 5 Table 6 Tabie 7 Tabie 8 Table 9 Table 10 Table 11 Table 12 Table 13 — “Removal of Fán Shroud .............——.—e.e..eneeeees Refrigerant ChAFGE .…….…..…………rreriseenmencanensennsensse Electric Heat Table 2 Electrical Specifications .................—e—... 4 Thermostat Wire Size 12 Wali Thermostats ess 12 Troubleshooting e... 16 Fan Blade Dimensions .......................... 18 Suction Line Temperatures ................. 18 Recommended Operating Ranges........ 18 indoor Blower Performance .............. 18 Maximum ESP of Operation Electric Heat Only .................... eee... 19 Pressure Table - Cooling 19 Pressure Tabie - Heating .................... 20 Optional Accessories ...................ervervaio. 20 13 13 13 13 13 14 14 16 Other Inf These publications can help you install the air conditioner or heat pump. You can usually find these at your local library or purchase them directly from the publisher. Be sure to consult current edition of each standard. National Electrical Code .................——.......... ANSINFPA 70 Standard for the Installation .................—... ANSUNFPA 90A of Air Conditioning and Ventilating Systems Standard for Warm Air ……….…rrccerrrsser ANSI/NFPA 90B Heating and Air Conditioning Systems Load Calculation for ....... ….. ACCA Manual J Residential Winter and Summer Air Conditioning Duct Design for Residential ...................... ACCA Manual D Winter and Summer Air Conditioning And Equipment Selection For more information, contact these publishers: ACCA — Air Conditioning Contractors of America 1712 New Hampshire Ave. N.W, Washington, DC 20009 Telephone: (202) 483-9370 Fax: (202) 234-4721 ANSI — American National Standards Institute 11 West Street, 13th Floor New York, NY 10036 Telephone: (212) 642-4900 Fax: (212) 302-1286 ASHRAE --- American Society of Heating Refrigerating and Air Conditioning Engineers, Incorporated 1791 Tullie Circle, N.E. Atlanta, GA 30329-2305 Telephone: (404) 636-8400 Fax: (404) 321-5478 NFPA — National Fire Protection Association Batterymarch Park Р.О. Вох 9101 Quincy, MA 02269-9901 Telephone: (800) 344-3555 Fax: (617) 984-7057 Manufactured under the following U.S. patent numbers: 5,485,878;5,301,744; 5,002,116; 4,924,934; 4,875,520; 4,825,936: 4,432,409 Manual 2100-357 Page 1 Mount Heat Pump Wall Mount Model Nomenclature MODEL NUMBER CONTROL MODULES \ WH 30 1 D A 1 0 Y X X Xx Y B (See Chart Below capot и \ 30 — 2.1/2Ton REVISION COIL OPTIONS 36 — 3 Ton X — Standard 1 — Phenolic Coated Evaporator VENTILATION OPTIONS 2 — Phenolic Coated Condenser DEHUMIDIFICATION X — Barometric Fresh Air Damper 3 — Phenolic Coated Evaporator VOLTS & PHASE (Standard) and Condenser A — 230/208/60-1 B — Blank-off Plate COLOR OPTIONS X - Beige (Standard) B — 230/208/60-3 KW C — 460/60-3 00—- No KW Y - Commercial Room Ventilator - 05 — 5 KW Motorized with Exhaust 06 — 6KW E ~ Economizer {intemal} - Fully 09 — 9 KW Modulating with Exhaust 10 — 10 KW В - Energy Recovery Ventilator - 16 — 15KW Motonzed with Exhaust M- Motorized Fresh Air Damper 1 —White 2 — Mesa Tan 3 ~ Colonial White à —Buckeye Gray FILTER OPTIONS QUTLET OPTIONS X — Front (Standard) T~ Top X - One inch Throwaway (Standard) W — One Inch Washable P - Two Inch Pleated NOTE: For OKW and circuit breakers (230/208 V) or pull disconnects (460 V) applications, insert 0Z in the KW field of model number. — TABLE 1 — ELECTRIC HEAT TABLE Models WH301DA WH301DB WH301DC WH361DA WH361DB WH361DC 240-1 208-1 240-3 ‘2084 460-3 240-1 208-1 240-3 208-3 460-3 KW À | BTU | A | ВТО | À | BTUI A } BTU | À | ВТО | А | BTU | À [| BTU | À | BTU | A | BTU! A | BTU 5 20.8] 17065] 18.1} 12800 20.81 17065 | 18.1} 12800 10 141.67 341301 36.2 | 25600 41.6 | 34130 | 36.21 25600 15 62.51 51200] 54.1} 38400 6 14.4 | 205004 12.5) 1536801 72 | 20480 9 21,71 30600 | 18.71 230301 10.8 1 30700 21.71 306001 18.7 123030 1 10.8] 30700 Manual 2100-357 Page 2 M31A MOVE НА 3015 AJÍA 1NOHS £90VAS > NOILVTIVISNI HOLLO8 tp fea N1VBO ANO SINN 137100 dOL + yy . PA Fe NOI LY TH INIA —— a —| (| > но | В $$320\ #311! > LIOR TV HO zl d , ; HONOUHL MOE SI а | | 1 JONVHIN] MOTJUIV VISNIONOS |, | X «ft 111931 ns Zl X | L— 3901104 407 y P| or | We oT | | === = ? ir uu Swan NY ==== | y, ЕЕ ЕЕ = = de Yi NANLIM SIINVELNG J 1991013313 == a ен 3 | НН (118Y701) 13NYd | 7 AWNO1LdO | $9300Y 193NN00SIO ВЫ! / UY 11941) —| | ` N1-1108) | [в | 1NYd a _ rd | — $$320\ YILVIH INTNIdO И YIY Addis (0 MIS | | MÍ | 21419313 |-- À — <a 3 > 91/1 — ре - 0 = a HOLId + - 3 > 0004 NIYH NI 11108 ret 0 — E B/1-18| 1 19/41) 6 | 9/0-00 1681 91/6-7) 20) 8/1-60 | v/0-87| 9/0-97 | 8l | 1/0-07] /1-81 | 8/4-65 | 8/1-17) e/1-511 8/1-17 | a/1-L | /1-01 | a/i-91 | 8/1-18] 90 y of g 2 | altY | НЮ |) 3 # + SNOISNIMIO LINA — L ENDE 2100-357 Manual Page 3 TABLE 2 — ELECTRICAL SPECIFICATIONS SINGLE CIRCUIT DUAL CIRCUIT a O @ @ © ® © © Maximum ‘ Minimum External Maximum - : ; rates | No Extemat | Fila potter | Torr | eg oe Volts Field | Minimum | Fuse or | Power | Ground Р and Power] Circuit Circuit | Wire Wire Model Phases | Ckts. | Ampacity | Breaker ! Size Size | Ckt À| Ckt B | Ckt À | Cki 8 | Ckt À | Ckt B{ Ckt Ai Ci B WH301DA00, AOZ 1 24 35 8 19 N/A N/A N/A N/A N/A N/A N/A N/A © AOS 230/208-1 1 50 50 8 10 N/A N/A N/A N/A N/A N/A N/A N/A - A10 1 76 80 4 8 50 26 50 30 8 10 10 10 WH301DB00, BOZ 1 19 25 10 10 N/A | N/A | N/A | NA | NA | NA {| NA | NA B06 | 230/208-3 1 37 40 8 10 N/A N/A N/A N/A N/A N/A N/A N/A © Bo 1 46 50 8 10 N/A | N/A | NA | NA | N/A | N/A | N/A | N/A WH301DC00, COZ 1 10 15 14 14 N/A N/A N/A N/A N/A N/A N/A N/A Coe] 460-3 1 19 20 12 12 N/A N/A N/A N/A N/A N/A N/A N/A © Cos 1 24 25 10 10 N/A | N/A | NA | NA | NA | NA | N/A | NA WH361DA00, AOZ 1 27 40 10 10 N/A NA N/A N/A N/A N/A N/A N/A A051 230/208-1 1] 1072 53 60 6 10 N/A N/A N/A N/A N/A N/A N/A N/A @ A10 1072 79 80 4 8 53 26 60 30 5 10 10 10 WH361DB00, BOZ 1 20 25 10 10 N/A N/A N/A N/A N/A N/A N/A N/A B06 | 230/208-3 1 38 40 8 10 N/A N/A N/A N/A N/A N/A N/A N/A © Bos 1 47 50 8 10 NA | NA | NA | NA | NA | NA | NA | NA WH361D C00, COZ 1 11 15 14 14 N/A N/A N/A N/A N/A N/A N/A N/A COB; 460-3 1 20 20 i2 12 N/A N/A N/A N/A NA | NA N/A N/A O Cos 1 25 25 10 10 | NA | NA | NA | NA | NA | NA | NA | NA D Maximumsize of the time delay fuse or HACR type circuit breaker for protection of field wiring conductors. @ Based on 75°C copper wire. All wiring must conform to NEC and all local codes. @ Maximum KW that can operate with heat pump on. @ These Minimum Circuit Ampacity" values are to be used for sizing the field power conductors. Referto the National Electrical Code {latest version), article 310 for power conductor sizing. CAUTION: When more than one field power conductor circuit is run through one conduit, the conductors must be derated. Pay special attention to ® note 8 of table 310 regarding Ampacity Adjustment Factors when more than 3 conductors are in a raceway. Not available in top outlet version. Manual Page 4 2100-357 SHIPPING DAMAGE Upon receipt of equipment, the carton should be checked for external signs of shipping damage. If damage is found, the receiving party must contact the last carrier immediately, preferably in writing, requesting inspection by the carrier’s agent. GENERAL The equipment covered in this manual is to be installed by trained, experienced service and installation technicians. The refrigerant system is completely assembled and charged. All internal wiring is complete. The unit is designed for use with or without duct work. Flanges are provided for attaching the supply and return ducts. These instructions and any instructions packaged with any separate equipment required to make up the entire heat - pump system should be carefully read before beginning the installation. Note particularly “Starting Procedure” and any tags and/or labels attached to the equipment. While these instructions are intended as a general recommended guide, they do not supersede any national and/or local codes in any way. Authorities having Jurisdiction should be consulted before the instaliation is made. See Page 1 for information on codes and standards. Size of unit for a proposed installation should be based on heat loss calculation made according to methods of Air Conditioning Contractors of America (ACCA). The air duct should be installed in accordance with the Standards of the National Fire Protection Association for the Installation of Air Conditioning and Ventilating Systems of Other Than Residence Type, NFPA No. 90A, and Residence Type Warm Air Heating and Air Conditioning Systems, NFPA No. 90B, Where local regulations are at a variance with instructions, installer should adhere to local codes. DUCT WORK Any heat pump is more critical of proper operating charge and an adequate duct system than a straight air conditioning unit, All duct work, supply and return, must be properly sized for the design air flow requirement of the equipment. Air Conditioning Contractors of America (ACCA) is an excellent guide to proper sizing. All duct work or portions thereof not in the conditioned space should be properly insulated in order to both conserve energy and prevent condensation or moisture damage. Refer to Table 10 for maximum static pressure available for duct design. Design the duct work according to methods given by the Air Conditioning Contractors of America (ACCA). When duct runs through unheated spaces, it should be insulated with a minimum of one inch of insulation. Use insulation with a vapor barrier on the outside of the insulation. Flexible joints should be used to connect the duct work to the equipment in order to keep the noise transmission to a minimum. À 1/4 inch clearance to combustible material for the first three feet (3) of duct attached to the outlet air frame is required. See Wall Mounting Instructions and Figures 3, 3A, 3B, and 3C for further details. Ducts through the walls must be insulated and all joints taped or sealed to prevent air or moisture entering the wall cavity. Some installations may not require any return air duct. A metallic return air grille is required with installations not requiring a return air duct. The spacing between louvers on the grille shall not be larger than 5/8 inches, Any grille that meets the 5/8 inch louver criteria, may be used, It is recommended that Bard Return Air Grille Kit RG-2 thru RG-5 or RFG-2 thru RFG-5 be installed when no return duct is used. Contact distributor or factory for ordering information. If using a return air filter grille, filters must be of sufficient size to allow a maximum velocity of 400 fpm. NOTE: If no return air duct is used, applicable installation codes may limit this cabinet to installation only in a single story structure. Filters A 1inch throwaway filter is supplied with each unit. The filter slides into position making it easy to service. This filter can be serviced from the outside by removing the service door. A 1 inch washable filter and 2 inch pleated filter are also available as optional accessories. The internal filter brackets are adjustable to accommodate the 2 inch filter by bending down the tabs to allow spacing for the 2 inch filters. Manual 2100-357 Page 5 Fresh Air Intake All units are built with fresh air inlet slots punched in the service panel. If the unit is equipped with the fresh air damper assembly, the assembly is shipped already attached to the unit. The damper blade is locked in the closed position. To allow the damper to operate, the maximum and minium blade position stops must be installed. See Figure 2. All capacity, efficiency and cost of operation information as required for Department of Energy “Energyguide” Fact Sheets is based upon the fresh air blank-off plate in place and is recommended for maximum energy efficiency. The blank-off plate is available upon request from the factory and is installed in place of the fresh air damper shipped with each unit. Condensate Drain A plastic drain hose extends from the drain pan at the top of the unit down to the unit base. There are openings in the unit base for the drain hose to pass through. In the event the drain hose is connected to a drain system of some type, it must be an open or vented type system to assure proper drainage. FIGURE 2 - BLOWER DAMPER ASSEMBLY BLADE IS LOCKED CLOSED FOR SHIPPING Mi5-838 Manual 2100-357 Page 6 TUN, WALL MOUNTING INFORMATION 1. Two holes, for the supply and return air openings, must be cut through the wall as shown in Figure 3. 2. On wood-frame walls, the wall construction must be strong and rigid enough to carry the weight of the unit without transmitting any unit vibration. See Figures 4 and 5. Fire hazard can resuit if 1/4 inch clearance to combustible materials for supply air duct is not maintained. See Figure 3. 3. Concrete block walls must be thoroughly inspected to insure that they are capable of carrying the weight of the installing unit. See Figure 4. MOUNTING THE UNIT 1. These units are secured by wall mounting brackets which secure the unit to the outside wall surface at both sides. A bottom mounting bracket is provided for ease of installation, but it is not required. 2. The unit itself is suitable for “0” inch clearance, but the supply air duct flange and the first 3 feet of supply air duct require a minimum of 1/4 inch clearance to combustible material. If a combustible wall, use a minimum of 28-1/2" x 8 -1/2" dimensions for sizing, However, 1t 1s generally recommended that a 1 inch clearance is used for ease of installation and maintaining the required clearance to combustible material. The supply air opening would then be 30" x 10". See Figures 3, 4 and 7 for details. Failure to provide the 1/4 inch clearance between the supply duct and a combustible | surface for the first 3 feet of duct can result in - fire. 3. Locate and mark lag bolt locations and bottom mounting bracket location, if desired. See Figure 4. 4. Mount bottom mounting bracket, if used. 5. Hook top rain flashing under back bend of top. Top rain flashing is shipped secured to the right side of the back. 6. Position unit in opening and secure with 5/16 lag bolts; use 3/4 inch diameter flat washers on the lag bolts. 7. Secure rain flashing to wall and caulk across entire length of top. See Figure 3. 8. For additional mounting rigidity, the retum air and supply air frames or collars can be drilled and screwed or welded to the structural wall itself (depending upon wall construction). Be sure to observe required clearance if combustible wall. 9. On side by side installations, maintain a minimum of 20 inches clearance on right side to allow access to heat strips and control panel, and to allow proper airflow to the outdoor coil. Additional clearance may be required to meet iocal or national codes. TYPICAL INSTALLATIONS See Figure 6 for common ways to install the wall-mount unit, Manual 2100-357 Page 7 ~ FIGURE 3 MOUNTING INSTRUCTIONS NOTE: His recommended that a bead of silicone caulking be piaced behind the side mounting flanges and SEAL ETRE SEAD CF CHALKING A B ED PE ALGU ENTIRE (ЕНОТ OF TOP. REQUIRED DIMENSIONS TO MAINTAIN | 28 1/2 | 84/2 | 51/4 1313/16 / 17 5/8 PE 1/4” WIN. CLEARANCE FROM Te CONBUSTISLE MATERIALS REQUIRED GIMENSIONS TO WAINTAIN | 3 1 141 ial 16 7/8 RECOMMENDED 1" CLEARANCE РАСЫ FOAY AIR SEAL COMBUSTIBLE MATERIALS HALL / | MALL STRUCTURE r Pal 1/4" CLEARANCE ON ALL — poo A m po ve FOUR SIDES OF SUPPLY AIR DUCT 15 REQUIRED | — и FROM COMBUSTABLE MATERIALS NET 1 8 DN “SUPPLY AIR DUCT 3 12.000 - | ! 12.088 | | —— Ш Ш и T REN MR > | 5 1/2 mo Fagen 28,000 ———— a 12.000 87 4.000 TYP.. 12.08 +008 7 3.000 B75 3.125 PY re 4.000 TYP. | | } | + : - , я | ” , = , " . il; ГС о — 412 417 no MIS-311 FIGURE 3A TYPICAL BUILDING у ELECTRIC HEAT CLEARANCE QUISIOE SHEETING N 7 WALL FRAME 7 INSIDE SHEETING É SUPPLY UNIT AN j "EN a a , / 14" HK. * A minimum of 1/4 inch clearance must be SUPPLY AIR DUCT maintained between the supply air duct and OT combustible materials. This is required for the first 3 feet of ducting. * |tis important to insure that the 1/4 inch N 7 Side section view of supply air minimum spacing is maintained at all points. uct for wall mounted unit N duct for wall d uni , , , , N showing 1/4 inch clearance to e Failure to do this could resuit in overheating N combustible surfaces. the combustible material and may resuit in MiS-277 N fire. Manual 2100-357 Page 8 + FIGURE4 WALL-MOUNTING INSTRUCTIONS SEE FIGURE 3 — MOUNTING INSTRUCTIONS Г MALL STRUCTURE / TACTORT SUPPLIED RAIN FLARHING MOUNT ON LEY BET ORT INSTALLATION SUPPLY AIR OPOMINE . SPPLY AIR CFENNS | + IT 10 SUPPLY AL DUCT 3 RETLRK AIR РОН; . REIN Al ORIG AT ; Г. > ; | WOOD JOR STEER SIBING ВОТ МОЖ INE BRAOKET. LOUIT Di WALL BEFORE. INSTALLING НиТ CONCRETE BLOCK WALL INSTALLATION WOOD FRAME WALL INSTALLATION MiS-548 FIGURE 5 WALL-MOUNTING INSTRUCTIONS SEE UNIT DIMENSIONS, FIGURE 1, a FOR ACTUAL DIMENSIONS £ + 1.000 3 ATTACH 70 1CA PLATE OF WALL SEE FIGURE 1 FOR DUCT DIMENSIONS 1.009" CLORAKE ALL ANUN SUPPLY QUE , OPENING INTIRIOR FINISHED BALL OVER FRAHE 1.000" CLEARARC МОК EXTERIOR FINISH WALL ATTACH 10 BOTTOM FRAMING MATERTAL PLATE OF MALL THIS STRUCTURAL NEWER LOCATED TO 2x 48, 21 ES LO MATCH STUD SPACING FOR BEST OF BALL. MIS-549 STRUCTURAL SIEUL À SÉCOHO NEWSER MAYBE REQUIRED FOR SOME WALLS. Manual 2100-357 Page 9 RAIN FLASHING FIGURE 6 COMMON WALL-MOUNTING INSTALLATIONS RAFTERS NN = or Te vr OUTSERE WALL Ш — SUPPLY AIR DUCT W/ GRILLE FIRISHED CEILING SURFACE % RETURN AIR OPENING W/ GRILLE FREE AIR FLOW NO DUCT SUPPLY DUCT MAYBE LOCATED IN AN ATTIC OR BELOW CEILING RAFTERS AS SHOMN RAIN FLASHING NN RAFTERS ee | SUPPLY AIR WT — ? a Ll Z FINISHED CEILING SURFACE 7 RETURN AIR OUTSIDE WALL % OPENING W/ GRILLE DUCTED SUPPLY RETURN AT UNIT RAIN FLASHING NN SUPPLY DUCT WAYBE LOCATED IN AN ATTIC OR BELOK CEILING RAFTERS AS SHOWN pp — RAFTERS > = ЗОРУ АЕ [37 — — { > И / FINISHED CEILING SURFACE OUTSIDE WALL | N— WALL SLEEVE | I RETURN AIR SPACE FALSE WALL x * "+ Ae 3 + RETURN AIR GRILLE FALSE WALL INSTALLATION SUPPLY DUCT MAYBE LOCATED IN AN ATTIC OR BELOW CEILING RAFTERS AS SHOWN RAIN TAE RAFTERS "a | EE 2 3 4 | > | | LOWERED CEILING | | | ее [| - SUPPLY AIR x. GRILLE - FINISHED CEILING SURFACE \ CLOSET WALL ; SF Nw | SLEEVE OUTSIDE MALL Le RAISED FLOOR — RETURN AIR Ÿ RETURN AIR GRILLE MIS-550 Manual 2100-357 Page 10 TTT WIRING — MAIN POWER Refer to the unit rating plate for wire sizing information and maximum fuse or “HACR" type circuit breaker size. Each outdoor unit is marked with a “Minimum Circuit Ampacity”. This means that the field wiring used must be sized to carry that amount of current. Depending on the installed KW of electric heat, there may be two field power circuits required. If this is the case, the unit serial plate will so indicate. All models are suitable only for connection with copper wire. Each unit and/or wiring diagram will be marked “Use Copper Conductors Only”. These instructions must be adhered to. Refer to the National Electrical Code (NEC) for complete current carrying capacity data on the various insulation grades of wiring material. All wiring must conform to NEC and all local codes. The electrical data lists fuse and wire sizes (75°C copper) for all models, including the most commonly used heater sizes. Also shown are the number of field power circuits required for the various models with heaters. The unit rating plate lists a “Maximum Time Delay Relay Fuse” or “HACR" type circuit breaker that is to be used with the equipment. The correct size must be used for proper circuit protection and also to assure that there will be no nuisance tripping due to the momentary high starting current of the compressor motor. ~The disconnect access door on this unit may be locked to . prevent unauthorized access to the disconnect. To convert for the locking capability, bend the tab located in the bottom left hand comer of the disconnect opening under the disconnect access panel straight out. This tab will now line up with the slot in the door. When shut, a padlock may be placed through the hole in the tab preventing entry, WIRING — LOW VOLTAGE WIRING 230/208V, 1 phase and 3 phase equipment dual primary voltage transformers. All equipment leaves the factory wired on 240V tap. For 208V operation, reconnect from 240V to 208V tap. The acceptable operating voltage range for the 240 ~~ and 208V taps are: Tap Range 240 253 - 216 208 220 - 187 В NOTE: The voltage should be measured at the field power connection point in the unit and while the unit is operating at full load (maximum amperage operating condition). - Nine (9) wires should be run from thermostat subbase to the 24V terminal board in the unit. A nine conductor, 18 gauge copper, color-coded thermostat cable is recommended. The connection points are shown in Figure 7. FIGURE 7 UNIT 24V TERMINAL BOARD pur оо о- SHP-2 or 300-227 GIT Tro | } 1851161070 © ba ® Ho © D Lope meme a Teme | I l TERA, OOO DOGBO0E Drm}: FACTORY JUMPER IMPORTANT NOTE: МАГ -- - -! ar REE BAL Ay MAT MARL AER we EME вым Eke WAT PIT AAA der VE ma © Ow 00 | 1 i | | Y] | | = MiS-1386 Only the thermostat and subbase combinations as shown above and in Table 4 will work with this equipment. The thermostat and subbase must be matched and the correct operation can be assured only by proper selection and application of these parts. Manual 2100-357 Page 11 | TABLE 3 THERMOSTAT WIRE SIZE 3 Maximum Transformer Distance VA | FLA Wire Gauge | In Feet 20 gauge 45 18 gauge 60 55 2.3 16 gauge 100 | 14 gauge 160 12 gauge 250 TABLE 4 WALL THERMOSTATS Thermostat Predominant Features 8403-042 1 stage cool; 2 stage heat Electronic Non-Programmable (1851 1 G1 070) Auto or-Manual changeover Robertshaw 300-227 2 stage cool; 3 stage heat 7 Day Programmable | Auto or Manual changeover Enerstat . SHP-2 2 stage cool; 3 stage heat 7 Day Programmabie Auto or Manual changeover THERMOSTAT INDICATOR LAMPS The red lamp will come on if there is any problem that: = prevents the compressor from running when it is supposed to be. EMERGENCY HEAT MODE The operator of the equipment must manually place the system switch in this position. This is done when there is a known problem with the unit, or when the red lamp comes on indicating a problem. COMPRESSOR MALFUNCTION LIGHT ~*~ Actuation of the red [amp is accomplished by a relay output from the heat pump control board which is factory installed. Any condition such as loss of charge, high head pressure, etc., that will prevent compressor from operation will cause red lamp to activate. This is a signal to the operator of the equipment to place system in emergency heat position. ‘Manual 2100-357 Page 12 и Start Up IMPORTANT INSTALLER NOTE For improved start-up performance, wash the indoor coil with a dishwashing detergent. CRANKCASE HEATERS All units are provided with some form of compressor crankcase heat. All single and three phase models have an insertion well- type heater located in the lower section of the compressor housing. This is a self-regulating type heater that draws only enough power to maintain the compressor at a safe temperature, Some form of crankcase heat i is essential to prevent liquid refrigerant from migrating to the compressor, causing oil pump out on compressor start-up and possible valve failure due to compressing a liquid. The decal in Figure 8 is affixed to all outdoor units detailing start-up procedure. ‘This i is very important. Please read carefully. В SERVICE HINTS 1. Caution homeowner to maintain clean air filters at all times. Also, not to needlessly close off supply and retum air registers. “This reduces air flow through the system, which shortens equipment service life as well as increasing operating costs. 2. Switching to heating cycle at 75° F or higher outside temperature may cause a nuisance trip of the remote reset high pressure switch, Turn thermostat off, then on to reset the high pressure switch. 3. The heat pump wall thermostats perform multiple functions. Be sure that all function switches are correctly set for the desired operating mode before trying to diagnose any reported service problems. 4. Check all power fuses or circuit breakers to be sure they are the correct rating. 5. Periodic cleaning of the outdoor coil to permit full and unrestricted airflow circulation is essential. SEQUENCE OF OPERATION COOLING ~ Circuit R-Y makes at thermostat pulling in compressor contactor, starting the compressor and outdoor motor. The G (indoor motor) circuit is automatically completed on any call for cooling operation or can be energized by manual fan switch on subbase for constant air circulation. FIGURE 8 START UP LABEL IMPORTANT THESE PROCEDURES MUST BE FOLLOWED AT INITIAL START UP AND AT ANY TIME POWER HAS BEEN REMOVED FOR 12 HOURS OR LONGER. TO PREVENT COMPRESSOR DAMAGE WHICH MAY RESULT FROM THE PRES- ENCE OF LIQUID REFRIGERANT IN THE COMPRESSOR CRANKCASE: 1. MAKE CERTAIN THE ROOM THERMO- STAT IS IN THE “OFF” POSITION, (THE COMPRESSOR IS NOT TO OPERATE.) 2. APPLY POWER BY CLOSING THE SYS- TEM DISCONNECT SWITCH. THIS EN- ERGIZES THE COMPRESSOR HEATER ~ WHICH EVAPORATES THE LIQUID RE- FRIGERANT IN THE CRANKCASE. 3. ALLOW 4 HOURS OR 60 MINUTES PER POUND OF REFRIGERANT IN THE SYS- TEM AS NOTED ON THE UNIT RATING PLATE, WHICHEVER IS GREATER, 4. AFTER PROPER ELAPSED TIME THE THERMOSTAT MAY BE SET TO OPER- ATE THE COMPRESSOR. 5. EXCEPT AS REQUIRED FOR SAFETY WHILE SERVICING, DO NOT OPEN SYSTEM DISCONNECT SWITCH, 7961-411 HEATING —~ A 24V solenoid coil on reversing valve controls heating cycle operation. Two thermostat options, one allowing "Auto" changeover from cycle to cycle and the other constantly energizing solenoid coil during heating season, and thus eliminating pressure equalization noise except during defrost, are to be used. On "Auto" option a circuit is completed from R-W1 and R-Y on each heating on” cycle, energizing reversing valve solenoid and pulling in compressor contactor starting compressor and outdoor motor. R-G also make starting indoor blower motor. Heat pump heating cycle now in operation. The second option has no "Auto" changeover position, but instead energizes the reversing valve solenoid constantly whenever the system switch on subbase is placed in "Heat" position, the "B" terminal being constantly energized from R. À Thermostat demand for heat completes r-Y circuit, pulling in compressor contactor starting compressor and outdoor motor. R-G also make starting indoor blower motor. Manual 2100-357 Page 13 OCCUPIED MODE VENTILATION SEQUENCE — The ERV and indoor blower will be continuously energized when the timer is energized. COOLING SEQUENCE — On a call for cooling, the compressor of the unit is energized to provide cooling. À call for cooling cancels dehumidification mode. Cooling mode is only available when the timer is energized. HEATING SEQUENCE — On a call for heating, the compressor and reversing valve of the unit are energized to provide heat pump heating. If the room temperature falls below the 2nd stage heating set point backup electric heat is energized. Heat pump heating is only available when the timer is energized. If heating is energized any call for dehumidification is ignored. If dehumidification is already energized a call for 2nd stage heating is needed to cancel dehumidification mode. DEHUMIDIFICATION SEQUENCE — On a call for dehumidification the compressor and three way valve of the unit are energized to provide denumidificatron. Dehumidification mode will continue until the humidistat is satisfied. If the room temperature falis below ist stage heating setpoint, electric heat will be energized by the room thermostat and cycle to maintain room temperature. If 2nd stage heating setpoint is reached, dehumidification is de- energized and heat pump heating is energized. A call for cooling cancels dehumidification mode. UNOCCUPIED MODE Cooling, heating, emergency heat and ventilation are inhibited. DEHUMIDIFICATION SEQUENCE — On a call for dehumidification the compressor and three way valve of the unit are energized to provide dehumidification. Dehumidification mode will continue until the humidistar ; is satisfied. If the room temperature falls below 65 degrees and dehumidification is energized, electric heat will be energized by the return air thermostat and cycle to maintain room temperature. a Dehumidification mode can be deactivated during periods when the timer is not energized by changing the connection of the humidistat wiring in the low voltage box, a OTHER CONTROL SEQUENCE Any time the indoor coil temperature falls below 32 degrees the compressor will be de-energized until the coil temperature rises above 57 degrees. PRESSURE SERVICE PORTS High and low pressure service ports are installed on all units so that the system operating pressures can be observed. Pressure tables can be found later in the manual covering all models on both cooling and heating cycles. It is imperative to match the correct pressure curve to the unit by model number. DEFROST CYCLE The defrost cycle is controlled by temperature and time on the solid state heat pump control. When the outdoor temperature is in the lower 40° F temperature range or colder, the outdoor coil temperature is 32° F or below. This coil temperature is sensed by the coil sensor mounted near the bottom of the outdoor coil. Once coil temperature reaches 30° F or below, the coil sends a signa to the control logic of the heat pump control and the defrost timer will start, After 60 (90 or 30) minutes at 30° F or below, the heat pump control will piace the system in the defrost mode. During the defrost mode, the refrigerant cycle switches back to the cooling cycle, the outdoor motor stops, electric heaters are energized, and hot gas passing through the outdoor coil melts any accumulated frost. When the temperature rises to approximately 57° F, the coil sensor will send a signal to the heat pump control which will return the system to heating operations automatically, If some abnormal or temporary condition such as a high wind caused the heat pump to have a prolonged defrost cycle, the heat pump control will restore the system to heating operating automatically after 10 minutes... There is a cycle speed up jumper on the control. This can be used to reduce the time between defrost cycle operation without waiting for time to elapse. There is an initial defrost (init def) jumper on the control that can be used at any outdoor ambient during the heating cycle to simulate a 0° coil temperature. This can be used to check defrost operation of the unit without waiting for the outdoor ambient to fall into the defrost region. Manual 2100-357 Page 14 - FIGURE 9 Ш DEFROST CONTROL BOARD | a = | = 5 5 Lin 0 rR na 0 “ | —— CONTROL CIRCUIT ot SENSOR SPEEDUP > 0 | I. NIT DEF 90 о Manual 2100-357 Page 15 SOLID STATE HEAT PUMP CONTROL TROUBLESHOOTING PROCEDURE 1. Turn on AC power supply to indoor and outdoor units. 2. Tum thermostat blower switch to fan "on" -— the indoor blower should start. (If it doesn't, troubleshoot indoor unit and correct problem). 4. Set system to heat or cool. Adjust thermostat to call for heat or cool — the indoor blower, compressor, and outdoor fan should start. NOTE: If there was no power to 24 volt transformer, the compressor and outdoor fan motor will not start for 5 minutes. This is because of the compressor short cycle protection. 3. Turn thermostat blower switch to auto position. Indoor blower should stop. contactor does not energize (heating or cooling) and 24 volt between R - С TABLE 5 TROUBLESHOOTING Symptom Possible Causes What to Check How to Dheck or Repair Comprassor Control circuit wiring Check for R connectio at unit — | Run R connection to outdoor unit to power heat pump control. Compressor lock out 1. Check for 24Y between contro! 2. Check across high presure switch. 1. . high pressure switch is open and will not if no voltage between L1-C, tum thermostat off and on again to reset high pressure switch. reset, replace high pressure switch. Compressor short cycle protection Check for 24 V between CC-C and Y-C on heat pump control. If not voitage between CC-C, jumper speed up terminal, and within 10 seconds power should appear between CC-C. Remove speed up jumper after 10 seconds. Heat pump contro! detective Check all other possible causes. Manual 2100-065 Replace heat pump control. Contactor defective Check for open or shorted coil winding. Replace contactor. Power phasing not correct Check for red LED on phase monitor (3 phase units only). Switch two power leds to the unit, Fan outdoor motor does not run {cooling or heating except during defrost) Motor defective Check for open or shorted Repiace motor. motor winding. Motor capacitor Check capacitor ratng. Check | Replace capacitor. defective for open or shorted capacitor. Heat pump contro! defective Check across fan relay on heat pump contro? (Com-NC). Replace heat pump control. Reversing valve does not energize (heating only) Reversing vaive solenoid coil defective Check for open or shorted coil. Replace solenoid Coil. Heat pump contro! defective Check for 24V between RV-C and B-C. Check control circuit wiring. Replace heat pump control. Unit will not go into defrost {heating only) Temperature sensor or heat pump contro! defective Disconnect temperature sensor from board and jumper across speed up terminals and sen jump terminals. This should caruse the unit to go through a defrost cycle within one minute. 1. ff unit goes through defrost cycle, replace temperature sensor. . If unit does not go through defrost cycle, replace heat pump control. Unit will not come Temperature sensor or Jumper across speed up . KF unit comes out of defrost cycle replace out of defrost heat pump control terminals. This should cause temperature sensor. (heating only) defective the unit to come out of defrost | 2. If unit does not come out of defrost within one minute. cycle, replace heat pump control. Manual 2100-357 Page 16 CHECKING TEMPERATURE SENSOR OUTSIDE UNIT CIRCUIT 1. Disconnect temperature sensor from board and from outdoorcoil. ~~ «= © o | 3. Check resistance reading to chart of resistance. Use sensor ambient temperature. (Tolerance of part is о + 10%.) М Ва 4. If sensor resistance reads very low, then sensor is shorted E a | and will not allow proper operation of the heat pump 2. Use an ohmmeter and measure the resistance of the control. : E | SE sensor. Also use ohmmeter to check for short or open. o | | : a Ве 5. If sensor is out of tolerance, shorted, open or reads very - low ohms then it should be replaced. — TEMPERATURE F VS. RESISTANCE R OF TEMPERATURE SENSOR AA Page Е В Е В Е В -25.0 196871 25.0 39898 75.0 10501 -24.0 190099 26.0 38757 760.0 10247 -23.0 183585 27.0 37652 77.0 10000 -22.0 177318 28.0 36583 78.0 9760 -21,0 171289 29.0 35548 79.0 9526 «20.0 165487 30.0 34545 80.0 9299 -19.0 159904 31.0 33574 81.0 9077 -18.0 154529 32.0 32634 82.0 8862 -17.0 149355 33.0 31723 83.0 8653 -16.0 144374 34.0 ‚ 30840 84.0 8449 -15.0 139576 35.0 29986 85.0 8250 -14.0 134956 36.0 29157 86.0 8057 -13.0 130506 37.0 28355 87.0 7869 -12.0 126219 38.0 27577 88.0 7686 -11.0 122089 39.0. 26823 89.0 7507 -10.0 118108 40.0 20092 90.0 7334 "9.0 114272 41.0 25383 91.0 7165 -8.0 110575 42.0 24696 92.0 7000 „7,0 107010 43,0 24030 93.0 6840 -6.0 103574 44.0 23384 94.0 6683 «5.0 100260 45.0 22758 95.0 6531 -4.0 97064 46.0 22150 96.0 0383 -3.0 93981 47.0 21561 97.0 6239 -2.0 91008 48.0 20989 98.0 6098 -1.0 88139 49.0 20435 99.0 5961 0.0 85371 50.0 19896 100.0 5827 1.0 82099 51.0 19374 101.0 5697 2.0 80121 52.0 18867 102.0 5570 3.0 77632 53.0 18375 103.0 5446 4.0 75230 54.0 17898 104.0 5326 5.0 72910 55.0 17434 105.0 5208 6.0 70670 56.0 16984 106.0 5094 7.0 68507 57.0 16547 107.0 4982 8.0 66418 58.0 16122 108.0 4873 9.0 64399 59.0 15710 109.0 4767 10.0 62449 60.0 15310 110.0 4663 11.0 60565 61.0 — 14921 111.0 4562 12.0 58745 62.0 — 14544 112.0 4464 13.0 56985 63.0 14177 113.0 4367 14.0 55284 64.0 13820 114.0 4274 15.0 53640 65.0 13474 115.0 4182 16.0 52051 66.0 13137 116.0 4093 17.0 50514 67.0 12810 117.0 4006 18.0 49028 68.0 -12492 118.0 3921 19.0 47590 69.0 12183 119.0 3838 20.0 46200 70.0 11883 120.0 3757 21,0 44855 71.0 11591 121.0 3678 22.0 43554 | 72.0 11307 122.0 3601 23.0 42295 73.0 11031 123.0 3526 24.0 41077 74.0 10762 124.0 3452 Manual 2100-357 17 FAN BLADE SETTING DIMENSIONS Shown in the drawing in Figure 10 are the correct fan blade setting dimensions for proper air delivery across the outdoor coil. - Any service work requiring removal or adjustment in the fan and/or motor area will require that the dimensions below be checked and blade adjusted in or out on the motor shaft accordingly. FIGURE 10 FAN BLADE SETTING TABLE 6 FAN BLADE DIMENSIONS Model Dimension A WH301D WH361D 125 | | | | | | | | | REMOVAL OF FAN SHROUD 1. Disconnect ali power to unit. ны NA MIS-1190 2. Remove the screws holding both grilles — one on each side of unit — and remove grilles. 3. Remove screws holding fan shroud to condense and bottom — (9) screws. 4. Unwire condenser fan motor. 5. Slide complete motor, fan blade, and shroud assembly out the left side of the unit. ее 6. Service motor/fan as needed. 7. Reverse steps to reinstall. REFRIGERANT CHARGE The correct system R-22 charge is shown on the unit rating plate. Optimum unit performance will occur witha refrigerant charge resulting in a suction line temperature (6 inches from compressor) as shown in the Table 7. TABLE 7 — SUCTION LINE TEMPERATURES Model Rated 95 FOD 82 FOD Airflow | Temperature | Temperature WH301D 1000 56 -- 58 63 -- 65 WH361D 1100 49 -- 51 66 -- 68 The suction line temperatures in Table 7 are based upon 80°F dry bulb/67 degrees F wet bulb (50 percent R.H.) temperature and rated airflow across the evaporator during coolingcycle. | TABLE 8 RECOMMENDED OPERATING RANGES Model Rated Rated Recommended СЕМ * ESP * Air Flow Range WH301D 1100 .30 930 -- 1300 WH361D 1100 30 930 --1350 * Rated CFM and ESP on high speed tap. ~~ TABLES INDOOR BLOWER PERFORMANCE CFM € 230V WH301D, WH361D ESP. Low 230V : High 230V In H,O | Dry Coll | WetCoif | Dry Coil | Wet Coil 0 | 950 935 1395 1315 1 930: 915 1340 1270 2 910: 885 1285 1190 3 855 830 1205 1100 4 800 755 1110 1000 5 ene ———- 1005 870 6 wan me — wore Manual 2100-357 Page 18 ( ин, ит, TABLE 10 MAXIMUM ESP OF OPERATION ELECTRIC HEAT ONLY Front Outlet | $ Low High Model Speed Speed "А10 35 40 WH301D "ВОО ‚50 ‚50 WH361D -BO6 40 50 - — -BO9 35 1 45 WH30 1D ~C00 50 S50 WH351D -C06 50 S50 -CO9 30 40 Values shown are for unites equipped with STD 1 inch throw- away filter on 1 inch washable filter. Derate ESP by .15 for 2 inch pleated filters, | TABLE 11 COOLING PRESSURE — (Ali temperatures *F) - Return Air Model | Temperature | Pressure! 75 | 80 | 65 | 90 | 95 | 100 | 105 1.110 | 115 75 dey.DB ¡LowSide| 76] 78] 80] 81| 83| 84] .85] 871 es 62 deg. WB | HighSide| 235| 249] 263] 277| 291| 305| 319| 3331 347 80 дед. ОВ | LowSide| 81] 83| 85] 87] 88| so) 91] es] gal... WH301D 1 67 deg. WB |HighSide| 241] 255] 269] 284] 208| 312| 327| 341| 356 “85 deg.DB | LowSide| 88) 90| 92} 93| 95] 97| 98! 100] 101 72 deg. WB | HighSide| 250| 264| 279| 294| 308| 323] sss| 353| aes| —— 75 deg. DB | LowsSide| 69| 71) 73| 75 76] 78} ‘80 e2l ea). 62 deg. WB | HighSide| 210| 226| 242| 257] 273] 290] 306| 323) asal WHss1p | 80 deg.DB | LowSide| 73| 76] 78| 80| 82| 84| 85] 7) es 67 deg. WB { High Side] 216] 232] 248] 264| 281} 297| 314] 331] 348 -85deg.DB |LowSide| 79} 811 84| 86] 88f 90| 921 94! 95 72 deg. WB | High Side| 223] 240| 256] 273] 290 308| 325 3421 360 Low side pressure + 2 psig High side pressure + 5 psig Tables are based upon rated CFM (airflow) across the evaporator coil. if there is any doubt as to correct operating charge being in the system, the charge should be removed, system evacuated and - recharged to serial plate instruction. a _ Manual 2100-357 Page 19 TABLE 12 HEATING PRESSURES — (AI temperatures °F) Model Return Air Temperature Pressure 0 5 10 15 17 20 25 30 35 40 45 47 50 55 60 WH301D 70 deg. Low Side High Side 21 143 5 148 28 153 32 159 33 161 36 165 39 172 43 180 47 188 51 197 55 207 57 211 59 217 63 228 67 239 WH361D 70 deg. Low Side 22 145 25 152 28 159 31 167 32 171 34 177 38 186 42 197 46 208 50 220 High Side 55 233 57 238 60 246 65 260 70 275 Low side pressure + 2 psig High side pressure + 5 psig Tables are based upon rated CFM (airflow) across the evaporator coil. if there is any doubt as to correct operating charge being in the system, the charge should be removed, system evacuated and recharged to serial piate instruction. Model TABLE 13 OPTIONAL ACCESSORIES Description WH301DB WH301DC WH361DA WH361DB WH361DC EHWH30-A05 EMWH30-A10 Heater Packages Heater Packages > > | WH301DA EHWH36-A05 EHWH36-A15 EHWH36-A10 | Heater Packages Heater Packages Heater Packages xxx EHWH03-B06 EHWH03-B09 EHWHO3-B15 [Heater Packages Heater Packages Heater Packages EHWH03-C06 EHWHO03-C09 EHWHO03-C15 Heater Packages Heater Packages Heater Packages BOP-3 BFAD-3 MFAD-3 Blank Off Plate’ a. Barometric Fresh Air Damper Motorized Fresh Air Damper CRV-3 EIFM-3 WERV-A3B WERV-C3B — |Classroom Ventilator with Exhaust — Economizer with Exhaust Energy Recovery Ventilator Energy Recovery Ventilator о x > >< - > > > PX XK NK Xx HFK XK XK Xx Xx XxX IP XXX CMH-3 CMH-7 CMH-9 CMH-15 start kit (SK) Low Pressure Control (LPC) Low Ambient Control (LAC) LAC + LPC. << x X ix XxX XIXXX xxx MEM MME XXX XXX WMCB-058 WMCB-03B WMPD-01 WMCB-06A Circuit Breaker Circuit Breaker Circuit Breaker Circuit Breaker >< | >< > XX xxx] Manual Page 20 2100-357 Y 071-9607 || y 021-0606 YI a 7 Fa mo] | НЕ a : — e Hoe = 1-09-00 *- o @ 21 = 1 10) д а я | n @ | INE (5) es 0] — | pie SV SRA ADT] G1] AVES IVA ANDE | №0 0 £21-060p| un | WM A @ aq 100 TA ED AVI AVE MiL | 301 AND TERN OT | an TRIN 19020 | 920 Mid Xd | JUN E) NIDO 20 — INA WA THE | АЕ | НН $ ISIE ADT | BN КАНО НО Trio | 200 — Wi. 1! LIDIA A wy MI | TT » ЗАЛА НН. JIM) REL | GOL] АВА БАН MODONE | Bl oF VIR THING | 80 0) “DAR CUYO 30 На) Tel ols ai X08 RIK IV A | I HLH ED MOORE | rai Sf AVES RIND o - , 078 WNGBL | 91] MULEJVCYO CESADO MORE | 08! Y AV TRIND O OT E O — NOLIVIJOD AROZ DI VI AGOZ OL ЗНА CES WM XP СЛ Но ON 41 LIADO SUR В) уу om | 1 | ADO SHIM] J с В М) | £10 UNIS | Ro WINING BIH] CH 28 WR THING | 20 DOES IMA TAM | A 16 BOLDVINDO BIH | IH IVE TN | IVISORERL JIV MIJO - dus whl an | ASTRO #0 A | su | 141 1 ISIS IH | LH {eH IYI SSR 5 | = ITH HY BORD “Cie saines | 00) BOLING) S520 MOLÍAS LIME Cows | 26 BND {IBID - THR FSR ADT DIVA DAR 12939 | 83 If ОМЗ НОА 2007 INFOS) 5,61 1791 IV 80 31VIINS A'NO SUDIONONDO 43403 251 dy waa pay sas bis Mal ume AW A EE wae Eas mir a e dae aad ee aE wk A CU A PTA A NA CNE A O YT Th ENT “Hr a A EE SE Sigh family e e dl CAE CS dems ar dl eR PVE SE MA MMe He lll RE dls aj Че cheek eee de ell q | { | 00 0 = iff = «= +9 a ~~ Se WS (SIP MBA AT IB Of “NE Am] mL ma 0 727-0601 wan 1 49 61 XT E HT DO CNA ae | MAL WAND JOIN ADT OTL AVY IVE ADORE | Mid | Mad (41! 30 J) ME в oC IDA КИ OI TUL | ul | ПАННО ЗНА НН НОЕ ON THI JS | 04) у WL 1 Som AlAMU i] xm wT AHH Ten mes ОА | Hi WB BUDE HO | 39 OF AY TND | 99 do a TEO ЗО ВЛ ма нон TOWEL | | „OBEN | kl] di Di | | | ¿ED i Á TRA BW NT NDIVUZID AGOZ 901 VL ABO OL UN ВЫ ЗК NT "О 3003 @ Af LOW SHA BEN Y Y | IHS tés | ú THOM ES Rai | LA м ние DANDO | 0 CEN OPS (AO) 0 “WI BY RM + LO ZF WLOVINGD LH | 2H a AVE THING | 70 О 51 15V31 1¥ 404 JEVLINS | ad] 1d М ВИНО ВАН | TA НА TEND | 18) A'RO SUDLONNDO 14d) 391 DN Emo | kl = USA A} SSRN a #0 НН YS E0000 Eo M ANS YH HIV VINE ESRI KILIAS LEHI + (НЫ IN |. ОНО 055334) TINE TEESE ROT — 718-1333 26 DNI LONE CSVAO JUSTA EDT | 6411. GONILINZA EMO ASIZU НО LINNEO 2007 0) 3 61 19031 1 804 IBIS A SHULD) 43440) 257 a rs o Cr e A CA EEE EEE Eas aan CC CU CU CU E A ERE ERE MA A AA dr Sr mal bee o e ARCA A ATA Fr Gr o e e A EEE Ear ap A e e e E E CT CU CU CU e E PEF A AAA Sd AAA CAR AA ETA EAE ARA ES SA VE Ger e heel ue A E e dr TU A O CU CU O TEE ESE TERE A A A NA A PEE MRE ET aah war ek wae ee eek e de A DWE EE AA \ 125-9607 IM | w © DON iS] 8 V 126-960 uE] e ws (5j Mw 91 ue — TINO JUDO 101] a1 | GUIVILINZA AEDDOJO 200] | MO 9 y7£-9607| En 1| ww E в — ITA O AYTO AVEO SEL | 20 Soya TST AT! 641) AVE VR DIO | ua Mid Xi JV 1! NDA œi ! INA A BEL | ML THD ANSIA MOT) 91 BON TNT ISO | 94 aa NULO 11 RDA A XXI то ЗНА КВ - 4010 WOHL à 001 | TONNOO SSYDAN INJIEAY DT} EN oF AYER ND | 080 03 "MR [VE T5 55 Hi Mads nears X08 WHIRL IIA AO | Bl AVES BAO a В y om THD. 0 : ХО WHIRDE | Gi SOLO 2407 MODONE | - AEH TRIN TS SOLO ON 31 13000 SMA IBNT YY | BROS 1 1] оыоММа ВАО НОНО | 991 ES AYER DADO | €) 9 ,5£:19Y31 1Y | | vi Was | A 1 TO Hl и ЕКО ЭВ | ASH | | АЗЫ RV ЖУКИ: 24 NS 1H LIVE VDI) SSSR Гоп | = 0108 NY 300010 ; I$ dis 1H! = ALND ARSE LETS) RY HOW GI) INDIO ZEN ПЛМ = | кои Het | IVIS-L 27328 li Re НОМ J ,SL 19731 1 ЮТК AMO ОДЕН 43440 350 — — — — — — ds ss y a dl deed o E A AA E MA AA E AA A AA BAe AWE чей wad O ar mle A RAE A WN HMA ae TA TA bly PERE PEWS FTV EE EE EE EE Es EERE TEER JME o UU o CU CA CA lr A SOON TRE E TREE Y TEE A Ce A a Cs e de e TE AR JE dir die AE PR MTR Meal aE PER RT REE EER ЕЕК AO Sei Gea br mas wk ded e o lr lr er ek bly me Ea ay Es En EEE EE Ey ан | нЕ ">

Download
Just a friendly reminder. You can view the document right here. But most importantly, our AI has already read it. It can explain complex things in simple terms, answer your questions in any language, and help you quickly navigate even the longest or most compilcated documents.
Advertisement
Key features
- Wall Mounted
- Heating and Cooling
- Energy Efficient
- Easy Installation
- Easy Maintenance
Frequently asked questions
The model numbers are WH301D and WH361D.
These heat pumps are designed to provide both heating and cooling for your home.
These heat pumps are designed to be installed on a wall.
These heat pumps are typically powered by electricity.