Appleton's MS Series Motor Starters Catalog Pages

Appleton's MS Series Motor Starters Catalog Pages
MS Series Motor Starters
Flameproof
Zone 1 and 2 - 21 and 22
II 2 GD
ATEX/IECEx
IP66 - IK10
Applications
• These motor starters are used in areas where hazardous
material are handled or stored. These units provide:
— Disconnecting means
— Undervoltage protection
— Circuit protection
— Motor running protection
— Thermal time delay overload protection
Features
Ex d Version
Controls
CONTROLS: HAZARDOUS LOCATION MOTOR STARTERS
• Magnetic circuit breaker protects equipment and personnel and
eliminates replacement of fuses.
• Three pole contactor.
• Thermal overload relay with manual reset push button.
• Green pilot light “Running/ON”.
• Rated voltage 400/415 Vac 50/60 Hz AC-3 category.
• Control circuit supplied via a transformer fed between phases.
• Direct entries or indirect entries with Ex e box allows use of
cable gland with elastomer seal.
• Type 2 coordinated protection (IEC 60947-4-1) has the following
benefits:
— Safety - limiting the energy delivered to the short circuit
ensures the safest applications for personnel, facilities and
equipment.
— Reduced costs - preventing short circuit damage to
components minimizes labor and replacement costs.
— Increased productivity - as component replacement due to
short circuits is minimized, so are interruptions to production.
• Direct ammeter for 0.37 kW to 2.2 kW versions. Ammeter with
current transformer for 3 kW to 75 kW versions.
Standard Materials
•
•
Body and cover:
— Gray painted marine grade aluminum alloy (RAL 7038)
— Cover bolts: stainless steel
— Hinges: stainless steel
Ex e box for indirect entries:
— Gray (RAL 7038) painted aluminum alloy (size 2 and 6) or
stainless steel (size 8 and 11)
— Cover bolts: stainless steel
Standard Finish
• Corrosion resistant gray powder coat epoxy
Options
• Available up to 300 kW - contact your local representative.
Certifications and Compliances
• Certification Type CF
— Gas: Zone 1 and 2
– Conforming to ATEX 94/9/CE: CE 0081
– ATEX/IEC Protection: Ex d IIB
– T Rating: T6
—Dust: Zone 21 and 22
– Conforming to ATEX 94/9/CE: CE 0081
– ATEX/IEC Protection: Ex td A21
– Surface Temperature: T176 °F/T80 °C
II 2 G
II2 D
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010
Ex de Version
• Ambient Temperature:
— CF 60: -58 °F/-50 °C to +131 °F/+55 °C
— CF 20, 40, 50: -40 °F/-40 °C to +131 °F/+55 °C
— CF 30: -4 °F/-20 °C to +131 °F/+55 °C
• CE Declaration of Conformity: 50229
• ATEX Certificate: LCIE 02 ATEX 6057X
• IEC Certificate: IECEx LCI 08.0023X
• Other Certifications: GOST
• Index of Protection (shock and liquid): IP66
• Impact Resistance (shock): IK10
• Internal Volume: > 2 dm3 (2 liters)
• Ex Standards: En/IEC 60079-0; 60079-1; 61241-0; 61241-1
• Other Standards: EN/IEC 60529 (IP); 62262 (IK)
473
MS Series Motor Starters
Flameproof
Zone 1 and 2 - 21 and 22
II 2 GD
ATEX/IECEx
IP66 - IK10
Catalog Numbering Guide
MS
B
003
Series:
MS - Motor Starters
Zone 1
ATEX/IEC Ex Certified
D
Type:
D - D.O.L. Direct On Line
Classification:
B - Ex d IIB
H - Ex d IIB + H2
CONTROLS: HAZARDOUS LOCATION MOTOR STARTERS
Controls
Power kW:
003 = 0.37
090 = 9
005 = 0.55
110 = 11
007 = 0.75
150 = 15
011 = 1.1
185 = 18.5
015 = 1.5
220 = 22
022 = 2.2
300 = 30
030 = 3
370 = 37
040 = 4
450 = 45
055 = 5.5
550 = 55
075 = 7.5
750 = 75
474
4
2
A
Control Circuit Voltage:
2 - 230 Vac 50/60 Hz via
Transformer
Rated Voltage:
4 - 400/415 V 50/60 Hz
Options:
A - Ammeter
B - Indirect entries with
Ex e Box
E - Local emergency Stop
H - Anti-condensation
(Heater, Thermostat,
Blue pilot light)
S - Selector switch
Hand/Off/Auto
T - Fault trip signal with
yellow pilot light
F - Full Options
(A,B,E,H,S,T)
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010
MS Series Motor Starters
Flameproof
Zone 1 and 2 - 21 and 22
II 2 GD
ATEX/IECEx
IP66 - IK10
Motor Capacity
AC-3 to 415 Vac
Size
Terminals
Cross Section (in2/mm2)
Cable Entries
at Bottom
Weight in Pounds/
Kilograms
Volume in3/dm3
Catalog Number
Standard Version
Fitted with magnetic circuit breaker, contactor with overload relay, Start/Stop buttons and green pilot light. (1 x M20 plugged).
0.004/2.5
2 x M20 + 1 M20
35/16
1525.59/25
MSB003D42
1
0.004/2.5
2 x M20 + 1 M20
35/16
1525.59/25
MSB005D42
0.75 kW
1
0.004/2.5
2 x M20 + 1 M20
35/16
1525.59/25
MSB007D42
1.1 kW
1
0.004/2.5
2 x M20 + 1 M20
35/16
1525.59/25
MSB011D42
1.5 kW
1
0.004/2.5
2 x M20 + 1 M20
35/16
1525.59/25
MSB015D42
2.2 kW
1
0.004/2.5
2 x M20 + 1 M20
35/16
1525.59/25
MSB022D42
3 kW
1
0.004/2.5
2 x M20 + 1 M20
35/16
1525.59/25
MSB030D42
4 kW
1
0.004/2.5
2 x M20 + 1 M20
35/16
1525.59/25
MSB040D42
5.5 kW
5
0.006/4.0
2 x M25 + 1 M20
123/56
7688.99/126
MSB055D42
7.5 kW
5
0.009/6.0
2 x M25 + 1 M20
123/56
7688.99/126
MSB075D42
9 kW
5
0.016/10.0
2 x M25 + 1 M20
123/56
7688.99/126
MSB090D42
11 kW
5
0.016/10.0
2 x M25 + 1 M20
123/56
7688.99/126
MSB110D42
15 kW
5
0.025/16.0
2 x M32 + 1 M20
123/56
7688.99/126
MSB150D42
18.5 kW
7
0.039/25.0
2 x M32 + 1 M20
159/72
14401.60/236
MSB185D42
22 kW
7
0.039/25.0
2 x M32 + 1 M20
159/72
14401.60/236
MSB220D42
30 kW
7
0.054/35.0
2 x M40 + 1 M20
159/72
14401.60/236
MSB300D42
37 kW
9
0.078/50.0
2 x M40 + 1 M20
291/132
22578.79/370
MSB370D42
45 kW
9
0.109/70.0
2 x M50 + 1 M20
291/132
22578.79/370
MSB450D42
55 kW
9
0.147/95.0
2 x M50 + 1 M20
291/132
22578.79/370
MSB550D42
75 kW
9
0.189/120.0
2 x M63 + 1 M20
291/132
22578.79/370
MSB750D42
Full Options Version
Standard version + HOA selector switch, local emergency stop, fault trip signal, ammeter, anti-condensation and indirect entries. (1 x M20 plugged.)
0.37 kW
4
0.004/2.5
2 x M20 + 1 x M20
112/51
42716.62/700
MSB003D42F
0.55 kW
4
0.004/2.5
2 x M20 + 1 x M20
112/51
42716.62/700
MSB005D42F
0.75 kW
4
0.004/2.5
2 x M20 + 1 x M20
112/51
42716.62/700
MSB007D42F
1.1 kW
4
0.004/2.5
2 x M20 + 1 x M20
112/51
42716.62/700
MSB011D42F
1.5 kW
4
0.004/2.5
2 x M20 + 1 x M20
112/51
42716.62/700
MSB015D42F
2.2 kW
4
0.004/2.5
2 x M20 + 1 x M20
112/51
42716.62/700
MSB022D42F
3 kW
4
0.004/2.5
2 x M20 + 1 x M20
112/51
42716.62/700
MSB030D42F
4 kW
4
0.004/2.5
2 x M20 + 1 x M20
112/51
42716.62/700
MSB040D42F
5.5 kW
6
0.006/4.0
2 x M25 + 1 x M20
137/62
42716.62/700
MSB055D42F
7.5 kW
6
0.009/6.0
2 x M25 + 1 x M20
137/62
42716.62/700
MSB075D42F
9 kW
6
0.016/10.0
2 x M25 + 1 x M20
137/62
42716.62/700
MSB090D42F
11 kW
6
0.016/10.0
2 x M25 + 1 x M20
137/62
42716.62/700
MSB110D42F
15 kW
6
0.025/16.0
2 x M32 + 1 x M20
137/62
42716.62/700
MSB150D42F
18.5 kW
8
0.039/25.0
2 x M32 + 1 x M20
179/81
42716.62/700
MSB185D42F
22 kW
8
0.039/25.0
2 x M32 + 1 x M20
179/81
42716.62/700
MSB220D42F
30 kW
8
0.054/35.0
2 x M40 + 1 x M20
179/81
42716.62/700
MSB300D42F
37 kW
10
0.078/50.0
2 x M40 + 1 x M20
320/145
42716.62/700
MSB370D42F
45 kW
10
0.109/70.0
2 x M50 + 1 x M20
320/145
42716.62/700
MSB450D42F
55 kW
10
0.147/95.0
2 x M50 + 1 x M20
320/145
42716.62/700
MSB550D42F
75 kW
10
0.189/120.0
2 x M63 + 1 x M20
320/145
42716.62/700
MSB750D42F
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010
475
CONTROLS: HAZARDOUS LOCATION MOTOR STARTERS
1
0.55 kW
Controls
0.37 kW
MS Series Motor Starter Wiring Diagram and Dimensions
Flameproof
Zone 1 and 2 - 21 and 22
II 2 GD
ATEX/IECEx
IP66 - IK10
Wiring Diagram
KM1.1
KM1.5
Stop
Reset
Start
Controls
Manual
Reset
Green
3PH.AC
Dimensions
(4) Ø 0.43”/11 mm
9.6”/245 mm
10.6”/270 mm
9.6”/245 mm
22.5”/572 mm
9.8”/250 mm
(4) Ø 0.43”/11 mm
14.5”/369 mm
0.59”/15 mm
9.9”/252 mm
Size 2: CF20B + CAe1
0.59”/15 mm
9.9”/252 mm
CONTROLS: HAZARDOUS LOCATION MOTOR STARTERS
Size 1: CF20B
9.6”/250 mm
10.6”/270 mm
476
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010
MS Series Motor Starter Dimensions
Flameproof
Zone 1 and 2 - 21 and 22
II 2 GD
ATEX/IECEx
IP66 - IK10
Dimensions
1.0”/25 mm
14.8”/375 mm
Size 6: CF40B + CAe2
1.0”/25 mm
10.8”/275 mm
(4) Ø 0.35”/9 mm
14.8”/375 mm
Size 5: CF40B
0.79”/20 mm
Size 4: CF30B + CAe2
0.79”/20 mm
(4) Ø 0.35”/9 mm
(4) Ø 0.43”/11 mm
17.9”/455 mm
15.4”/391 mm
10.9”/278 mm
12.6”/320 mm
15.6”/320 mm
10.1”/256 mm
CONTROLS: HAZARDOUS LOCATION MOTOR STARTERS
21.7”/552 mm
11.7”/298 mm
(4) Ø 0.43”/11 mm
Controls
13.4”/340 mm
11.7”/298 mm
12.6”/320 mm
10.9”/278 mm
26.3”/667 mm
15.4”/391 mm
10.8”/275 mm
Size 3: CF30B
10.1”/256 mm
15.6”/320 mm
1.0”/25 mm
18.5”/470 mm
Size 10: CF60B + JBe55
1.0”/25 mm
18.5”/470 mm
Size 9: CF60B
1.0”/25 mm
15.9”/405 mm
Size 8: CF50B + JBe47
1.0”/25 mm
15.9”/405 mm
Size 7: CF50B
Ø 0.55”/14 mm
Ø 0.43”/11 mm
(4) Ø 0.43”/11 mm
Ø 0.55”/11 mm
17.3”/440 mm
14.8”/376 mm
17.3”/440 mm
17.9”/455 mm
15.4”/391 mm
14.8”/376 mm
(2) Ø
0.35”/9 mm
16.0”/407 mm
24.3”/616 mm
41.7”/1060 mm
24.3”/616 mm
26.8”/680 mm
15.4”/391 mm
11.3”/286 mm
14.8”/376 mm
17.3”/440 mm
28.5”/725 mm
HEATER ON
FAULT TRIP
RUNNING
HAND
AUTO
14.8”/376 mm
17.3”/440 mm
16.0”/407 mm
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010
(2) Ø
0.35”/9 mm
477
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertising