PUMV-PUMN-PUMT -Installation Manual PUM-V-N-T (TN1PUMV-E)

PUMV-PUMN-PUMT -Installation Manual PUM-V-N-T (TN1PUMV-E)
1-1
2-3
• This equipment is intended to be used under the following conditions.
-10 to 50 degree C
Ambient humidity
90% RH or below (with no condensation)
Vibration
10 to 70Hz less than 9.8m/s² (1G)
Warm-up time
30 min. or more
Installation category
IEC1010-1: class II
Pollution level
IEC1010-1: degree 2
• Between the temperature sensor and the location where the voltage reaches or
generates the values described below, secure clearance space and creepage
distance as shown in the table below.
If such space cannot be secured, the EN61010 safety compliance may become
invalid
Voltage used or generated
by any assemblies
Up to 50 Vrms or Vdc
Up to 100 Vrms or Vdc
Up to 150 Vrms or Vdc
Up to 300 Vrms or Vdc
Above 300 Vrms or Vdc
Clearance Space [mm]
2-4
Creepage Space [mm]
2-5
Functional insulation (AC1000V)
I/O terminal switch
See [Wiring]
F012
I/O terminal switch
See [Wiring]
2
2
3
3
4
4
5
5
6
6
7
7
8
- Base part
8
9
9
10
Mounting screw hole
A
11
B
12
C
13
D
14
E
15
F
16
Module connector
(Connect controllers
laterally)
Power terminal block
See [Wiring]
RS-485 terminal block
See [Wiring]
LED indicator
LED (6 points) indicates the operation status.
Color
Operational condition
Green
Normal operation
(Slave station of internal communication)
Blinking
Green
Normal operation
(Master station of internal communication)
ON
Red
System FAULT
(A/D converter error, internal communication
error)
Blinking
Red
Input error
ON
PWR
COM
OUT1 to 4
COM
IN1 to 4
STATION
345
OUT3
OUT4
ON
Green
ON
Orange RS-485 being sent
ON
Green
Corresponding channel outputting
ON
Red
Corresponding channel input error
Terminal block
(when detached from the main unit)
30
PWR
COM
(10)
Base part
(when detached from
the main unit)
85
PUM-V
LOADER
OUT1
OUT2
STATION
OUT3
RS-485 being received
OUT4
1.5
6
DIN rail
Terminal
Screw size M3
LED Status
Color
Operational condition
ON
Green
Normal operation
(Slave station of internal communication)
Blinking
Green
Normal operation
(Master station of internal communication)
ON
Red
System FAULT
(A/D converter error, internal communication
error)
Blinking
Red
Input error
ON
Green
RS-485 being received
ON
Orange RS-485 being sent
ON
Red
When locking tab is released
(when mounting /
dismounting to / from DIN rails)
Terminal
Screw size M3
Main unit
(when detached from the base part)
[mm]
Cautions when mounting
In order to aid heat dissipation, 30mm of clearance (50mm recommended) above and
under the controllers should be provided.
Corresponding channel input error
- Actions to be displayed for COM and IN1 to 4 can be allocated by programming.
nAnalog output module
LED
Others
PWR
COM
Station No.
Configuration switch
Front screw terminal cover
(optional)
nAnalog input module
PWR
OUT2
- Dimensions
- Actions to be displayed for COM and OUT1 to 4 can be allocated by programming.
LED
LOADER
OUT1
Mounting
nAnalog I/O module
LED Status
PUM‑V
COM
- Each of connected controllers must have a different Station No. from other
controllers. Duplicate Station No. may cause malfunction of the equipment.
Locking tab
LED
PWR
50
Mounting screw hole
See [Mounting]
OUT1 to 4
-1-
1
1
F012
St. No. configuration
switch
See [Setting]
E
345
E
F012
E
F012
E
STATION
OUT4
LED Status
Color
Operational condition
ON
Green
Normal operation
(Slave station of internal communication)
Blinking
Green
Normal operation
(Master station of internal communication)
ON
Red
System FAULT
(A/D converter error, internal communication
error)
ON
Green
RS-485 being received
ON
Orange RS-485 being sent
ON
Green
[mm]
Corresponding channel outputting
- Actions to be displayed for COM and OUT1 to 4 can be allocated by programming.
Ai1
Ai2
Ai3
Ai4
OUT1 (Current)
OUT2 (Current)
OUT3 (Current)
OUT4 (Current)
Functional insulation (AC500V)
Error Operation
- Please do not wipe the equipment with organic solvents such as alcohol or benzene,
etc. If wiping is necessary, use a neutral cleaning agent.
- Do not use mobile phones near this equipment (within 50cm). Otherwise a
malfunction may result.
- Malfunctions may occur if the equipment is used near a radio, TV, or wireless device.
- This equipment requires approx. 20 seconds before it starts to output.
- Before installing and wiring, take necessary measures for electrostatic discharge
(ESD).
• For the above, if voltage exceeds 50Vdc (called danger voltage), basic insulation is
required between the earth and all terminals of the equipment.
Note that the insulation class for this equipment is as follows. Before installing,
please confirm that the insulation class for the equipment meets usage requirements.
Loader Communication
RS-485 Communication
Cautions for Wiring
- The alarm function does not work properly when an error occurs unless the settings
are made correctly. Always verify its setting before operation.
- In case of error input, PWR LED will flash. When replacing the sensor, make sure to
turn the power OFF.
0.2
1.2
0.2
1.4
0.5
1.6
1.5
3.0
Please consult our distributor
Power
Cautions when Mounting to Cabinets / DIN rails
- For thermocouple input, use the designated compensation lead. For resistance bulb
input, use wires with small lead wire resistance and without any resistance difference
among three wires.
- To avoid the influence of inductive noise, signal wires should be separated from
electric power lines or load lines.
- Input signal wire and output signal wire should be separated from each other. And
both should be shielded.
- To comply with CE marking (EMC), we recommend to attach ferrite core to
communication cable and power cable.
- For wiring to the terminal block, apply crimp type terminals size M3.
Screw size
:M3 x 7 (with square washer)
Screw tightening torque:0.78N-m (8kgf-cm)
Installation and Wiring
Ambient temperature
I/O terminal switch
See [Wiring]
Cautions when Installing
- In case of mounting the temperature controllers to DIN rails, remember to push up
the locking tabs to fasten the controllers onto DIN rail.
- To connect controllers, first release all locking tabs. Then, connect controllers and
push up all locking tabs. Make sure that all locking tabs are fastened.
- Never fail to turn the power OFF, before detaching the terminal block or removing the
main unit from the base part.
- In order to aid heat dissipation, do not block the top and the bottom of the equipment.
- When mounting / dismounting controllers to / from DIN rails, 30mm of clearance
above and under the controllers should be provided.
- Use terminal screws in this product only.
Warning
OUT2
OUT3
St. No. configuration
switch
See [Setting]
(8)
1
LED indicator
345
(30)
Improper use of the equipment may cause injury to the user or property
damage.
IN4
Station No.
0
30 or more
Please read this section thoroughly before using and observe the mentioned safety
warnings fully.
Safety warnings are categorized as "Warning" or "Caution".
STATION
IN3
SW setting
30 or more
2-2
IN2
St. No. configuration
switch
See [Setting]
Loader communication
port
100
Please Read First (Safety Warnings)
LED indicator
345
OUT4
OUT1
6.1
INPTN5A0201-E
Warning
STATION
OUT3
Loader communication
port
5
ECNO 1162
INPTN5A0203-E
Improper use of the equipment may result in death or serious injuries.
Caution
Please avoid installing in the following locations.
- Locations in which the ambient temperature falls outside the range of 0 to 50 degrees
C when equipment is in use.
- Locations in which the ambient humidity falls outside the range of 45 to 85% RH
when equipment is in use.
- Locations with rapid temperature changes, leading to dew condensation
- Locations with corrosive gases (especially sulfide gas, ammonia, etc.) or flammable
gases.
- Locations with vibration or shock directly.
- Locations in contact with water, oil, chemicals, steam or hot water.
(If the equipment gets wet, there is a risk of electric shock or fire, so have it
inspected by Fuji distributor.)
- Locations with high concentrations of atmospheric dust, salt or iron particles.
- Locations with large inductive interference, resulting in static electricity, magnetic
fields or noise.
- Locations in direct sunlight.
- Locations that build up heat from radiant heat sources, etc.
Material No.
Caution
OUT2
IN1
BCD
Material
name
Specification Catalog
Operating
Analog IO/
instruction
I/O Module
User's
manual
Tool
PUM
parameter
loader
LOADER
Loader communication
port
789A
1 unit per voltage/current input
Content
PUM-T
COM
6
Related Information
Refer to "Module Type Temperature
Controller Analog IO/I/O Module User's
Manual" for details about the items
described in this manual.
Temperature Controller Analog IO/I/O Module 1 Unit
Instruction Manual
1 copy
I/V unit (250 ohm resistance)
PWR
LOADER
7 8 9A
Confirming Specifications and Accessories
PUM-N
COM
Module connector
2-1
Before using the product, confirm that it
matches the type ordered.
(For model code, please refer to page 4.)
Confirm that all of the following
accessories are included.
PWR
LOADER
6
2
CT connector
See [Wiring]
PUM-V
COM
OUT1
LED indicator
CT connector
See [Wiring]
PWR
7 8 9A
The contents of this manual are subject to change without notice.
This manual is complied with possible care for the purpose of accuracy, however,
Fuji Electric Systems shall not be held liable for any damages, including indirect
damage, caused by typographical errors,
absence of information or use of information in this manual.
CT connector
See [Wiring]
Set Station No. of each controller before mounting.
Apply a fine tip flat-head screwdriver to turn the Station No. configuration switch.
Analog Output module
Maintenance
- When installing or removing the equipment, turn the power OFF. Otherwise, shock,
operational errors or failures may be caused.
- Periodic maintenance is recommended for continuous and safe use of this
equipment.
- Some parts installed on this equipment have a limited life and/or may deteriorate with
age.
- The warranty period for this unit (including accessories) is one year, if the product is
used properly.
CAUTION
Analog Input module
6
1-2
Thank you for purchasing the Fuji module type temperature controller.
Once you have confirmed that this is the product you ordered, please use it in
accordance with the following instructions.
For detailed information on operating this equipment, please refer to the separate
user's manual.
In addition, please keep this instruction manual within easy reach of the actual person
using this equipment.
- Analog I/O module
7 8 9A
INP-TN1PUMV-E
- Setting Station No.
BCD
Model : PUMV/N/T
Setting
- Main unit
BCD
Analog IO/I/O Module
Part names and Functions
BCD
Multi-loop module type Temperature Controller
6
- In cases where damage or problems with this equipment may lead to serious
accidents, install appropriate external protective circuits.
- To prevent damage and failure of the equipment, provide the rated power voltage.
- To prevent electric shock and equipment failure, do not turn the power ON until all
wiring is complete.
- Before turning the power ON, confirm that clearance space has been secured to
prevent shock or fire.
- Do not touch the terminal while the machine is ON. Doing so risks shock or
equipment errors.
- Never disassemble, convert, modify or repair this equipment. Doing so risks abnormal
operation, shock or fire.
Instruction Manual (Installation)
-2-
1-1
2-3
• This equipment is intended to be used under the following conditions.
-10 to 50 degree C
Ambient humidity
90% RH or below (with no condensation)
Vibration
10 to 70Hz less than 9.8m/s² (1G)
Warm-up time
30 min. or more
Installation category
IEC1010-1: class II
Pollution level
IEC1010-1: degree 2
• Between the temperature sensor and the location where the voltage reaches or
generates the values described below, secure clearance space and creepage
distance as shown in the table below.
If such space cannot be secured, the EN61010 safety compliance may become
invalid
Voltage used or generated
by any assemblies
Up to 50 Vrms or Vdc
Up to 100 Vrms or Vdc
Up to 150 Vrms or Vdc
Up to 300 Vrms or Vdc
Above 300 Vrms or Vdc
Clearance Space [mm]
2-4
Creepage Space [mm]
2-5
Functional insulation (AC1000V)
I/O terminal switch
See [Wiring]
F012
I/O terminal switch
See [Wiring]
2
2
3
3
4
4
5
5
6
6
7
7
8
- Base part
8
9
9
10
Mounting screw hole
A
11
B
12
C
13
D
14
E
15
F
16
Module connector
(Connect controllers
laterally)
Power terminal block
See [Wiring]
RS-485 terminal block
See [Wiring]
LED indicator
LED (6 points) indicates the operation status.
Color
Operational condition
Green
Normal operation
(Slave station of internal communication)
Blinking
Green
Normal operation
(Master station of internal communication)
ON
Red
System FAULT
(A/D converter error, internal communication
error)
Blinking
Red
Input error
ON
PWR
COM
OUT1 to 4
COM
IN1 to 4
STATION
345
OUT3
OUT4
ON
Green
ON
Orange RS-485 being sent
ON
Green
Corresponding channel outputting
ON
Red
Corresponding channel input error
Terminal block
(when detached from the main unit)
30
PWR
COM
(10)
Base part
(when detached from
the main unit)
85
PUM-V
LOADER
OUT1
OUT2
STATION
OUT3
RS-485 being received
OUT4
1.5
6
DIN rail
Terminal
Screw size M3
LED Status
Color
Operational condition
ON
Green
Normal operation
(Slave station of internal communication)
Blinking
Green
Normal operation
(Master station of internal communication)
ON
Red
System FAULT
(A/D converter error, internal communication
error)
Blinking
Red
Input error
ON
Green
RS-485 being received
ON
Orange RS-485 being sent
ON
Red
When locking tab is released
(when mounting /
dismounting to / from DIN rails)
Terminal
Screw size M3
Main unit
(when detached from the base part)
[mm]
Cautions when mounting
In order to aid heat dissipation, 30mm of clearance (50mm recommended) above and
under the controllers should be provided.
Corresponding channel input error
- Actions to be displayed for COM and IN1 to 4 can be allocated by programming.
nAnalog output module
LED
Others
PWR
COM
Station No.
Configuration switch
Front screw terminal cover
(optional)
nAnalog input module
PWR
OUT2
- Dimensions
- Actions to be displayed for COM and OUT1 to 4 can be allocated by programming.
LED
LOADER
OUT1
Mounting
nAnalog I/O module
LED Status
PUM‑V
COM
- Each of connected controllers must have a different Station No. from other
controllers. Duplicate Station No. may cause malfunction of the equipment.
Locking tab
LED
PWR
50
Mounting screw hole
See [Mounting]
OUT1 to 4
-1-
1
1
F012
St. No. configuration
switch
See [Setting]
E
345
E
F012
E
F012
E
STATION
OUT4
LED Status
Color
Operational condition
ON
Green
Normal operation
(Slave station of internal communication)
Blinking
Green
Normal operation
(Master station of internal communication)
ON
Red
System FAULT
(A/D converter error, internal communication
error)
ON
Green
RS-485 being received
ON
Orange RS-485 being sent
ON
Green
[mm]
Corresponding channel outputting
- Actions to be displayed for COM and OUT1 to 4 can be allocated by programming.
Ai1
Ai2
Ai3
Ai4
OUT1 (Current)
OUT2 (Current)
OUT3 (Current)
OUT4 (Current)
Functional insulation (AC500V)
Error Operation
- Please do not wipe the equipment with organic solvents such as alcohol or benzene,
etc. If wiping is necessary, use a neutral cleaning agent.
- Do not use mobile phones near this equipment (within 50cm). Otherwise a
malfunction may result.
- Malfunctions may occur if the equipment is used near a radio, TV, or wireless device.
- This equipment requires approx. 20 seconds before it starts to output.
- Before installing and wiring, take necessary measures for electrostatic discharge
(ESD).
• For the above, if voltage exceeds 50Vdc (called danger voltage), basic insulation is
required between the earth and all terminals of the equipment.
Note that the insulation class for this equipment is as follows. Before installing,
please confirm that the insulation class for the equipment meets usage requirements.
Loader Communication
RS-485 Communication
Cautions for Wiring
- The alarm function does not work properly when an error occurs unless the settings
are made correctly. Always verify its setting before operation.
- In case of error input, PWR LED will flash. When replacing the sensor, make sure to
turn the power OFF.
0.2
1.2
0.2
1.4
0.5
1.6
1.5
3.0
Please consult our distributor
Power
Cautions when Mounting to Cabinets / DIN rails
- For thermocouple input, use the designated compensation lead. For resistance bulb
input, use wires with small lead wire resistance and without any resistance difference
among three wires.
- To avoid the influence of inductive noise, signal wires should be separated from
electric power lines or load lines.
- Input signal wire and output signal wire should be separated from each other. And
both should be shielded.
- To comply with CE marking (EMC), we recommend to attach ferrite core to
communication cable and power cable.
- For wiring to the terminal block, apply crimp type terminals size M3.
Screw size
:M3 x 7 (with square washer)
Screw tightening torque:0.78N-m (8kgf-cm)
Installation and Wiring
Ambient temperature
I/O terminal switch
See [Wiring]
Cautions when Installing
- In case of mounting the temperature controllers to DIN rails, remember to push up
the locking tabs to fasten the controllers onto DIN rail.
- To connect controllers, first release all locking tabs. Then, connect controllers and
push up all locking tabs. Make sure that all locking tabs are fastened.
- Never fail to turn the power OFF, before detaching the terminal block or removing the
main unit from the base part.
- In order to aid heat dissipation, do not block the top and the bottom of the equipment.
- When mounting / dismounting controllers to / from DIN rails, 30mm of clearance
above and under the controllers should be provided.
- Use terminal screws in this product only.
Warning
OUT2
OUT3
St. No. configuration
switch
See [Setting]
(8)
1
LED indicator
345
(30)
Improper use of the equipment may cause injury to the user or property
damage.
IN4
Station No.
0
30 or more
Please read this section thoroughly before using and observe the mentioned safety
warnings fully.
Safety warnings are categorized as "Warning" or "Caution".
STATION
IN3
SW setting
30 or more
2-2
IN2
St. No. configuration
switch
See [Setting]
Loader communication
port
100
Please Read First (Safety Warnings)
LED indicator
345
OUT4
OUT1
6.1
INPTN5A0201-E
Warning
STATION
OUT3
Loader communication
port
5
ECNO 1162
INPTN5A0203-E
Improper use of the equipment may result in death or serious injuries.
Caution
Please avoid installing in the following locations.
- Locations in which the ambient temperature falls outside the range of 0 to 50 degrees
C when equipment is in use.
- Locations in which the ambient humidity falls outside the range of 45 to 85% RH
when equipment is in use.
- Locations with rapid temperature changes, leading to dew condensation
- Locations with corrosive gases (especially sulfide gas, ammonia, etc.) or flammable
gases.
- Locations with vibration or shock directly.
- Locations in contact with water, oil, chemicals, steam or hot water.
(If the equipment gets wet, there is a risk of electric shock or fire, so have it
inspected by Fuji distributor.)
- Locations with high concentrations of atmospheric dust, salt or iron particles.
- Locations with large inductive interference, resulting in static electricity, magnetic
fields or noise.
- Locations in direct sunlight.
- Locations that build up heat from radiant heat sources, etc.
Material No.
Caution
OUT2
IN1
BCD
Material
name
Specification Catalog
Operating
Analog IO/
instruction
I/O Module
User's
manual
Tool
PUM
parameter
loader
LOADER
Loader communication
port
789A
1 unit per voltage/current input
Content
PUM-T
COM
6
Related Information
Refer to "Module Type Temperature
Controller Analog IO/I/O Module User's
Manual" for details about the items
described in this manual.
Temperature Controller Analog IO/I/O Module 1 Unit
Instruction Manual
1 copy
I/V unit (250 ohm resistance)
PWR
LOADER
7 8 9A
Confirming Specifications and Accessories
PUM-N
COM
Module connector
2-1
Before using the product, confirm that it
matches the type ordered.
(For model code, please refer to page 4.)
Confirm that all of the following
accessories are included.
PWR
LOADER
6
2
CT connector
See [Wiring]
PUM-V
COM
OUT1
LED indicator
CT connector
See [Wiring]
PWR
7 8 9A
The contents of this manual are subject to change without notice.
This manual is complied with possible care for the purpose of accuracy, however,
Fuji Electric Systems shall not be held liable for any damages, including indirect
damage, caused by typographical errors,
absence of information or use of information in this manual.
CT connector
See [Wiring]
Set Station No. of each controller before mounting.
Apply a fine tip flat-head screwdriver to turn the Station No. configuration switch.
Analog Output module
Maintenance
- When installing or removing the equipment, turn the power OFF. Otherwise, shock,
operational errors or failures may be caused.
- Periodic maintenance is recommended for continuous and safe use of this
equipment.
- Some parts installed on this equipment have a limited life and/or may deteriorate with
age.
- The warranty period for this unit (including accessories) is one year, if the product is
used properly.
CAUTION
Analog Input module
6
1-2
Thank you for purchasing the Fuji module type temperature controller.
Once you have confirmed that this is the product you ordered, please use it in
accordance with the following instructions.
For detailed information on operating this equipment, please refer to the separate
user's manual.
In addition, please keep this instruction manual within easy reach of the actual person
using this equipment.
- Analog I/O module
7 8 9A
INP-TN1PUMV-E
- Setting Station No.
BCD
Model : PUMV/N/T
Setting
- Main unit
BCD
Analog IO/I/O Module
Part names and Functions
BCD
Multi-loop module type Temperature Controller
6
- In cases where damage or problems with this equipment may lead to serious
accidents, install appropriate external protective circuits.
- To prevent damage and failure of the equipment, provide the rated power voltage.
- To prevent electric shock and equipment failure, do not turn the power ON until all
wiring is complete.
- Before turning the power ON, confirm that clearance space has been secured to
prevent shock or fire.
- Do not touch the terminal while the machine is ON. Doing so risks shock or
equipment errors.
- Never disassemble, convert, modify or repair this equipment. Doing so risks abnormal
operation, shock or fire.
Instruction Manual (Installation)
-2-
- Front terminal block (3ch, 4ch)
OUT1
PWR
PUM-V
COM
LOADER
OUT2
STATION
STATION
345
F012
E
E
7 8 9A
OUT4
BCD
Voltage/Current
input*
21
Resistance
bulb input
21
22
22
Thermocouple
input
21
PWR
PUM-V
COM
LOADER
22
RS-485 interface
Communication standard : RS-485
Communication, synchro
method
: Two-wire, half-duplex, asynchronous cycle
Communication speed
: 9.6k, 19.2k, 38.4k, 115.2kbps
Data form
: data bit ; 8, parity ; even/odd/none
Communication distance : 1km (38.4kbps or less), 250m (115.2kbps)
Connectable units
: 33 units (both master and slave units included)
(32 units if any modules other than PUM series is included in slaves)
Protocol
: Modbus RTU compatible
OUT2
STATION
345
OUT3
23
OUT4
7 8 9A
23
23
Locking tab
3. Push up the locking tab to
fasten the controller onto DIN
rail.
- When connecting controllers
after mounting to DIN rail, push
up the locking tab after doing so.
Locking tab
Analog output 3
PUMV/T
BCD
Side
connector
Current
output
24
25
PWR
PUM-A
PWR
PUM-A
PWR
PUM-V
COM
LOADER
COM
LOADER
COM
LOADER
OUT1
STATION
BCD
E
7 8 9A
OUT4
6
F012
345
OUT3
7 8 9A
OUT4
6
F012
345
OUT3
7 8 9A
BCD
E
OUT2
STATION
345
6
OUT4
OUT1
OUT2
STATION
OUT3
F012
OUT2
E
OUT1
BCD
Voltage/Current
input*
26
Resistance
bulb input
26
Thermocouple
input
26
27
27
27
28
28
28
Analog output 4
PUMV/T
4. All connected controllers are connected
to power supply and RS-485 via side
connectors if one of controllers is directly
connected to them.
Analog input 4
PUMV/N
CH4
3. After mounting controllers onto DIN rail,
make sure to push up all locking tabs.
Controllers are fastened to DIN rail and to
each other.
Current
output
29
21
11
22
12
23
13
24
14
25
15
26
16
27
17
28
18
29
19
30
20
Loader (RS-232C) interface
Communication standard : RS-232C
Communication, synchro
method
: Half-duplex, asynchronous cycle
Communication speed
: 19.2kbps (fixed)
Data form
: data bit 8, no parity
Protocol
: Modbus RTU compatible
Crimp terminal size
30
Please prepare power cables and crimp terminals of the size indicated below.
Power cable
*In case of currenet input, attach I/V unit which comes with the controller to the voltage input terminal.
How to detach the base part
When mounting controllers to DIN rails, we recommend to attach side connecting
terminal covers (right and left 1set), then end plates (optional) to the ends of the
rightmost and leftmost controllers.
OUT2
STATION
STATION
345
PUM-E
PWR
LOADER
COM
STATION
345
PUM-E
Do1
Do2
Do3
Do4
Do5
Do6
Do7
Do8
LOADER
Lock lever
Power terminal
2. Pull down the upper part of main unit.
DIN rail mounting
end plate
345
B (-)
DC 24V (+)
A (+)
BCDE
BCD
- Fixing with screws
When mounting controllers inside a cabinet with screws, connect the base parts of
controllers first.
- Fixing screws are not included. Please prepare screws
as required.
(30)
2-M3
9±0.2
1. Refer to the figure below for the mounting screw hole
size to decide the mounting position.
Main unit
Projection
Power Supply
Power Consumption
Dimensions
Weight
Installation method
Ambient temperature*
Ambient humidity
(100)
88.5 ±0.2
Wiring
Analog output 1
PUMV/T
(3)
CH1
Current
output
PWR
PUM-V
COM
LOADER
11
12
OUT1
OUT2
345
E
7 8 9A
F012
6
OUT4
Thermocouple Resistance
input
bulb input
13
13
BCD
21
Voltage/Current
input*
13
11
22
12
23
13
14
14
14
15
15
15
Analog input 1
PUMV/N
STATION
OUT3
CH2
15
26
16
27
17
28
18
29
19
30
20
Current
output
Analog output 2
PUMV/T
14
25
16
17
Thermocouple Resistance
input
bulb input
18
18
Voltage/Current
input*
18
19
19
19
20
20
20
Analog input 2
PUMV/N
24
1
2
3
4
6
7
8
9 10 11 12 13
1
0
0
0 0
V
N
T
T
A
C
Y
No. of input
: 4 points
Input signal
: Thermocouple K, J, T, E, R, B, S, N, PL-II
Resistance bulb Pt100, JPt100
DC voltage or DC current
: 0 to 5Vdc, 1 to 5Vdc, 0 to 10Vdc,
2 to 10Vdc,
0 to 20mAdc, 4 to 20mAdc
Input impedance
: Thermocouple input, voltage input : 1M ohm or more
- Voltage input (V)
: Approx. 1M ohm
- Current input
: 250 ohm
Signal source resistance - Thermocouple
: 0.3%FS ± 1 digit per 100 ohm
- Voltage input (V)
: 0.3%FS ± 1 digit per 500 ohm
Allowable wiring resistance- Resistance bulb input
: 10 ohm or less per wire
Y Y
E E
A
B
Y crimp terminal
Contents
Module type
Analog I/O module AI4/AO4
Analog Input module AI4
Analog Output module AO4
Input type
Thermocouple/resistance bulb
Voltage/current
Thermocouple/resistance bulb [ch1, 2]
Voltage/current [ch3, 4]
Analog output module
Output type
None
Current output 4 to 20mA
Operation Manual
Japanese
English
Accessories (optional)
1
2
3
4
5
6
7
8
A
A
A
A
L
0
0
0
0
0
1
2
3
4
1
P U M Z *
Analog output (PUMV/T)
No. of output
Control output behavior
Output type
5
P U M
: 4 points
: Re-transmission output or distribution output
: Current output (4-20mAdc, 0-20mAdc)
- Actual output range
: 0mA to 20.6mAdc
- Accuracy
: ±0.3%FS (1mA or less : ±5%FS)
- Linearity
: ±0.3%FS (1mA or less : ±5%FS)
- Resolution
: 5000 or more
- Ripple current
: P-P0.3mA or less
- Load resistance
: 300 ohm or less
Contents
RS-485 terminating resistance
DIN rail mounting end plate
Side connecting terminal cover (right & left 1 set)
Front face screw terminal cover
Loader connecting cable (RS-232C)
Head Office
Gate City Osaki East Tower 11-2, Osaki 1-chome, Shinagawa-ku, Tokyo 141-0032, Japan
http://www.fesys.co.jp/eng
*In case of currenet input, attach I/V unit which comes with the controller to the voltage input terminal.
-3-
Ring crimp terminal
Analog IO/I/O module
: DC24V±10%
: Maximum 3.2W (135mA) [when DC24V is applied]
: 30 (W)×100 (H)×85 (D) mm (excluding terminal cover and projection)
: Approx.200g
: DIN rail mounting or mounting inside a cabinet with M3 screws
: -10 to 50 degrees C
* "Ambient temperature" is the temperature underneath the controller
inside the equipment or the cabinet where the controller is installed.
: 90% RH or less (non condensing)
Analog input (PUMV/N)
- Front terminal block (1ch type / 2ch)
[mm]
3.2mm
Model code
General Specification
+0.2
30+0.7
Screw tightening torque
0.8Nm
SG
Specification
4. Fixate the base parts onto the mounting position inside the cabinet with screws.
5. Attach the main unit to the base parts.
1.25mm2 or less
1.25mm2 or less
All connected controllers are connected to power supply and RS-485 via side connectors
if one of controllers is directly connected to them.
Side connecting terminal cover
(right & left 1 set)
3. Connect base parts. Push up to fasten all the locking tabs.
Size
Thermocouple (Compensation lead wire)
Power supply
Crimp terminal
RS-485 terminal
DC 24V (-)
- When attaching the main unit to the
base part, take the reverse procedure
to removing the main unit from the
base part.
- Make sure that the lock lever of the
main unit is fitted into the base part.
2. Remove the main unit from the base part.
See [How to detach the base part]
Cable type
Cable size
0.25 to 1.25mm2
3. Detach the cutout on the lower end of
back of main unit from the projection
on the base part.
STATION
789
Di1
Di2
Di3
Di4
Di5
Di6
Di7
Di8
6
Do1
Do2
Do3
Do4
Do5
Do6
Do7
Do8
789
Di1
Di2
Di3
Di4
Di5
Di6
Di7
Di8
6
F012
COM
789
F012
PWR
LOADER
6
OUT4
789
7 8 9A
E
345
6
6
OUT4
STATION
OUT3
A
345
OUT3
PUM-E
F012
OUT1
OUT2
Do1
Do2
Do3
Do4
Do5
Do6
Do7
Do8
F012
OUT1
Di1
Di2
Di3
Di4
Di5
Di6
Di7
Di8
F012
COM
BCDE
PWR
LOADER
A
PUM-V
COM
BCDE
PWR
LOADER
A
PUM-A
COM
BCDE
PWR
A
DIN rail mounting
end plate
1. Press the lock lever on the top of the
main unit.
- Base part (power terminal, RS-485 terminal)
6.0mm or less
- Attaching end plates
: 4points
: Current output (4-20mAdc, 0-20mAdc)
Communication functions
OUT1
6
Analog input 3
PUMV/N
2. Connect controllers with each other using
side connectors.
DIN rail
No. of output
Output type
345
OUT3
7 8 9A
F012
OUT3
OUT4
CH3
OUT1
OUT2
Analog re-transmission output
3.2mm
COM
LOADER
F012
PUM-A
E
PWR
6
1. Check that locking tabs are pulled down
(released).
6.0mm or less
- Connecting controllers
Hook the back
of controller
6
1. Pull down the locking tab of the
base part. Hook the back of the
controller onto the upper part of
DIN rail.
2. Push the controller in the
direction of arrow 2.
BCD
- Mounting to DIN rails
-4-
- Front terminal block (3ch, 4ch)
OUT1
PWR
PUM-V
COM
LOADER
OUT2
STATION
STATION
345
F012
E
E
7 8 9A
OUT4
BCD
Voltage/Current
input*
21
Resistance
bulb input
21
22
22
Thermocouple
input
21
PWR
PUM-V
COM
LOADER
22
RS-485 interface
Communication standard : RS-485
Communication, synchro
method
: Two-wire, half-duplex, asynchronous cycle
Communication speed
: 9.6k, 19.2k, 38.4k, 115.2kbps
Data form
: data bit ; 8, parity ; even/odd/none
Communication distance : 1km (38.4kbps or less), 250m (115.2kbps)
Connectable units
: 33 units (both master and slave units included)
(32 units if any modules other than PUM series is included in slaves)
Protocol
: Modbus RTU compatible
OUT2
STATION
345
OUT3
23
OUT4
7 8 9A
23
23
Locking tab
3. Push up the locking tab to
fasten the controller onto DIN
rail.
- When connecting controllers
after mounting to DIN rail, push
up the locking tab after doing so.
Locking tab
Analog output 3
PUMV/T
BCD
Side
connector
Current
output
24
25
PWR
PUM-A
PWR
PUM-A
PWR
PUM-V
COM
LOADER
COM
LOADER
COM
LOADER
OUT1
STATION
BCD
E
7 8 9A
OUT4
6
F012
345
OUT3
7 8 9A
OUT4
6
F012
345
OUT3
7 8 9A
BCD
E
OUT2
STATION
345
6
OUT4
OUT1
OUT2
STATION
OUT3
F012
OUT2
E
OUT1
BCD
Voltage/Current
input*
26
Resistance
bulb input
26
Thermocouple
input
26
27
27
27
28
28
28
Analog output 4
PUMV/T
4. All connected controllers are connected
to power supply and RS-485 via side
connectors if one of controllers is directly
connected to them.
Analog input 4
PUMV/N
CH4
3. After mounting controllers onto DIN rail,
make sure to push up all locking tabs.
Controllers are fastened to DIN rail and to
each other.
Current
output
29
21
11
22
12
23
13
24
14
25
15
26
16
27
17
28
18
29
19
30
20
Loader (RS-232C) interface
Communication standard : RS-232C
Communication, synchro
method
: Half-duplex, asynchronous cycle
Communication speed
: 19.2kbps (fixed)
Data form
: data bit 8, no parity
Protocol
: Modbus RTU compatible
Crimp terminal size
30
Please prepare power cables and crimp terminals of the size indicated below.
Power cable
*In case of currenet input, attach I/V unit which comes with the controller to the voltage input terminal.
How to detach the base part
When mounting controllers to DIN rails, we recommend to attach side connecting
terminal covers (right and left 1set), then end plates (optional) to the ends of the
rightmost and leftmost controllers.
OUT2
STATION
STATION
345
PUM-E
PWR
LOADER
COM
STATION
345
PUM-E
Do1
Do2
Do3
Do4
Do5
Do6
Do7
Do8
LOADER
Lock lever
Power terminal
2. Pull down the upper part of main unit.
DIN rail mounting
end plate
345
B (-)
DC 24V (+)
A (+)
BCDE
BCD
- Fixing with screws
When mounting controllers inside a cabinet with screws, connect the base parts of
controllers first.
- Fixing screws are not included. Please prepare screws
as required.
(30)
2-M3
9±0.2
1. Refer to the figure below for the mounting screw hole
size to decide the mounting position.
Main unit
Projection
Power Supply
Power Consumption
Dimensions
Weight
Installation method
Ambient temperature*
Ambient humidity
(100)
88.5 ±0.2
Wiring
Analog output 1
PUMV/T
(3)
CH1
Current
output
PWR
PUM-V
COM
LOADER
11
12
OUT1
OUT2
345
E
7 8 9A
F012
6
OUT4
Thermocouple Resistance
input
bulb input
13
13
BCD
21
Voltage/Current
input*
13
11
22
12
23
13
14
14
14
15
15
15
Analog input 1
PUMV/N
STATION
OUT3
CH2
15
26
16
27
17
28
18
29
19
30
20
Current
output
Analog output 2
PUMV/T
14
25
16
17
Thermocouple Resistance
input
bulb input
18
18
Voltage/Current
input*
18
19
19
19
20
20
20
Analog input 2
PUMV/N
24
1
2
3
4
6
7
8
9 10 11 12 13
1
0
0
0 0
V
N
T
T
A
C
Y
No. of input
: 4 points
Input signal
: Thermocouple K, J, T, E, R, B, S, N, PL-II
Resistance bulb Pt100, JPt100
DC voltage or DC current
: 0 to 5Vdc, 1 to 5Vdc, 0 to 10Vdc,
2 to 10Vdc,
0 to 20mAdc, 4 to 20mAdc
Input impedance
: Thermocouple input, voltage input : 1M ohm or more
- Voltage input (V)
: Approx. 1M ohm
- Current input
: 250 ohm
Signal source resistance - Thermocouple
: 0.3%FS ± 1 digit per 100 ohm
- Voltage input (V)
: 0.3%FS ± 1 digit per 500 ohm
Allowable wiring resistance- Resistance bulb input
: 10 ohm or less per wire
Y Y
E E
A
B
Y crimp terminal
Contents
Module type
Analog I/O module AI4/AO4
Analog Input module AI4
Analog Output module AO4
Input type
Thermocouple/resistance bulb
Voltage/current
Thermocouple/resistance bulb [ch1, 2]
Voltage/current [ch3, 4]
Analog output module
Output type
None
Current output 4 to 20mA
Operation Manual
Japanese
English
Accessories (optional)
1
2
3
4
5
6
7
8
A
A
A
A
L
0
0
0
0
0
1
2
3
4
1
P U M Z *
Analog output (PUMV/T)
No. of output
Control output behavior
Output type
5
P U M
: 4 points
: Re-transmission output or distribution output
: Current output (4-20mAdc, 0-20mAdc)
- Actual output range
: 0mA to 20.6mAdc
- Accuracy
: ±0.3%FS (1mA or less : ±5%FS)
- Linearity
: ±0.3%FS (1mA or less : ±5%FS)
- Resolution
: 5000 or more
- Ripple current
: P-P0.3mA or less
- Load resistance
: 300 ohm or less
Contents
RS-485 terminating resistance
DIN rail mounting end plate
Side connecting terminal cover (right & left 1 set)
Front face screw terminal cover
Loader connecting cable (RS-232C)
Head Office
Gate City Osaki East Tower 11-2, Osaki 1-chome, Shinagawa-ku, Tokyo 141-0032, Japan
http://www.fesys.co.jp/eng
*In case of currenet input, attach I/V unit which comes with the controller to the voltage input terminal.
-3-
Ring crimp terminal
Analog IO/I/O module
: DC24V±10%
: Maximum 3.2W (135mA) [when DC24V is applied]
: 30 (W)×100 (H)×85 (D) mm (excluding terminal cover and projection)
: Approx.200g
: DIN rail mounting or mounting inside a cabinet with M3 screws
: -10 to 50 degrees C
* "Ambient temperature" is the temperature underneath the controller
inside the equipment or the cabinet where the controller is installed.
: 90% RH or less (non condensing)
Analog input (PUMV/N)
- Front terminal block (1ch type / 2ch)
[mm]
3.2mm
Model code
General Specification
+0.2
30+0.7
Screw tightening torque
0.8Nm
SG
Specification
4. Fixate the base parts onto the mounting position inside the cabinet with screws.
5. Attach the main unit to the base parts.
1.25mm2 or less
1.25mm2 or less
All connected controllers are connected to power supply and RS-485 via side connectors
if one of controllers is directly connected to them.
Side connecting terminal cover
(right & left 1 set)
3. Connect base parts. Push up to fasten all the locking tabs.
Size
Thermocouple (Compensation lead wire)
Power supply
Crimp terminal
RS-485 terminal
DC 24V (-)
- When attaching the main unit to the
base part, take the reverse procedure
to removing the main unit from the
base part.
- Make sure that the lock lever of the
main unit is fitted into the base part.
2. Remove the main unit from the base part.
See [How to detach the base part]
Cable type
Cable size
0.25 to 1.25mm2
3. Detach the cutout on the lower end of
back of main unit from the projection
on the base part.
STATION
789
Di1
Di2
Di3
Di4
Di5
Di6
Di7
Di8
6
Do1
Do2
Do3
Do4
Do5
Do6
Do7
Do8
789
Di1
Di2
Di3
Di4
Di5
Di6
Di7
Di8
6
F012
COM
789
F012
PWR
LOADER
6
OUT4
789
7 8 9A
E
345
6
6
OUT4
STATION
OUT3
A
345
OUT3
PUM-E
F012
OUT1
OUT2
Do1
Do2
Do3
Do4
Do5
Do6
Do7
Do8
F012
OUT1
Di1
Di2
Di3
Di4
Di5
Di6
Di7
Di8
F012
COM
BCDE
PWR
LOADER
A
PUM-V
COM
BCDE
PWR
LOADER
A
PUM-A
COM
BCDE
PWR
A
DIN rail mounting
end plate
1. Press the lock lever on the top of the
main unit.
- Base part (power terminal, RS-485 terminal)
6.0mm or less
- Attaching end plates
: 4points
: Current output (4-20mAdc, 0-20mAdc)
Communication functions
OUT1
6
Analog input 3
PUMV/N
2. Connect controllers with each other using
side connectors.
DIN rail
No. of output
Output type
345
OUT3
7 8 9A
F012
OUT3
OUT4
CH3
OUT1
OUT2
Analog re-transmission output
3.2mm
COM
LOADER
F012
PUM-A
E
PWR
6
1. Check that locking tabs are pulled down
(released).
6.0mm or less
- Connecting controllers
Hook the back
of controller
6
1. Pull down the locking tab of the
base part. Hook the back of the
controller onto the upper part of
DIN rail.
2. Push the controller in the
direction of arrow 2.
BCD
- Mounting to DIN rails
-4-