BL20 I/O Bus Systems
TURCK
Modular Industrial I/O System
C1
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Industrial
Automation
The BL20 Solution
The BL20 modular concept is a very flexible approach to terminal-wired I/O. The gateway, base and electronic modules
provide many benefits to the user.
BL20
• The gateway provides communication between the fieldbus and I/O modules; modules are not dependent on the
fieldbus protocol.
• DIN-rail mountable base modules are available with different wiring configurations to suit the user’s needs.
• Electronic modules are hot swappable.
• Power distribution modules can be used to create isolated power segments within the system.
BL20’s openness and flexibility provide a viable alternative to traditional PLC I/O.
Maximum Size of a BL20 Station
BL20 stations consist of a gateway and a maximum of 74 I/O modules (equivalent to 1 m station length). Some high-tech
and analog I/O modules may consume or produce large amounts of data, and therefore may further limit the number of
modules that may be used. It is highly recommended that I/Oassistant software is used when planning and commissioning
BL20 systems. This program allows you to build the BL20 node on your computer and verify that all restrictions with regard
to power and size are met. The free I/Oassistant software is available to download from www.turck.com.
Addressing
As a node on a network, the BL20 station must have an address. The setting of this address is dependent on the network
system being used. Each network gateway has a set of rotary switches (one for the most significant digit, or 10’s multiplier,
and one for the least significant digit, or 1’s multiplier) that are used to set the address for the node. DeviceNet™ gateways
may be addressed between 0 and 63, while PROFIBUS ®-DP and CANopen gateways can be set from 0 to 99.
BL20 Power Distribution
The power supply for a BL20 station is fed via power feeding or bus refreshing modules; the latter also being responsible for
the power supply to the internal module bus. Bus refreshing modules are used within a BL20 station (without gateway
supply) if the system supply to the BL20 modules (nominal current IMB 1.5 A) is no longer sufficiently guaranteed. Bus
refreshing modules are used with tension clamp (BL20-P3T-SBB-B or BL20-P4T-SBBC-B) or screw connection base modules
(BL20-P3S-SBB-B or BL20-P4S-SBBC-B). Power feeding modules are used if the system supply to the BL20 modules
(nominal current IL < 10 A) is no longer sufficiently guaranteed.
System Supply Via Module Bus
The amount of BL20 modules that may be supplied by a bus refreshing module via the internal module bus depends on the
respective minimal current IMB of the individual modules on the bus. The sum of the nominal current inputs of the
connected BL20 modules must not exceed 1.5 A. BL20 gateway power requirements (supplied by the first bus refreshing
module) should be considered when calculating the required number of bus refreshing modules. If I/Oassistant software is
used, an error message is generated automatically via the <Station - Verify> as soon as the system supply is no longer
sufficiently guaranteed.
All bus refreshing modules used in a BL20 station should be connected via the same frame potential. The power supply to
the bus is fed via the connections 11 (plus) and 21 (ground) of the respective base module for the bus refreshing module.
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
C2
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
TURCK
Modular Industrial I/O System
Creating Potential Groups
Both bus refreshing modules and power feeding modules may be used to create a potential group. The base module
creates the possible isolation of the potential group on the left-hand side of the respective power distribution module.
It is not permitted for modules with 24 VDC and with 120/230 VAC field supply to be used in a joint potential group.
Therefore, when using digital input modules for 120/230 VAC, the power feeding module BL20-PF-120/230VAC-D is to be
used to create a special potential group.
C-rail (Cross Connection)
C-rails run through all I/O base modules. The C-rail for base modules for power distribution is mechanically separated; thus
potentially isolating the adjoining supply groups.
Access to the C-rail
Access to the C-rail is made via base modules with a C designation (i.e. BL20-S4T-SBCS). The corresponding connection
level is indicated by a thick black line on all base modules for BL20 I/O modules. For base modules for power distribution,
the black line is only above the connection “24" to indicate that the C-rail is separated from the adjoining potential group to
its left.
It is permitted to load the C-rail with a maximum of 24 V; never with 120/230 VAC.
Using the C-rail with Relay Modules
The C-rail may be used to supply a common voltage when relay modules are used. To accomplish this, the load voltage (24
VDC) is connected to a power distribution module and the base module BL20-P4x-SBBC with either tension clamp or screw
connections.
If the C-rail is used for the joint supply of voltage to relay modules, there must be a power distribution module used for the
potential isolation of the BL20 modules. The C-rail may still be used as protective earth (PE) once the potential isolation has
been made.
Using the C-rail as a Protective Earth
A C-rail may be used as a protective earth (PE), where the PE connection for each power distribution modules must be
connected to the mounting rail via an additional PE terminal, which is available as an accessory.
C3
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Industrial
Automation
Environmental Conditions
General Technical Data
Potential isolations
Via Optocoupler
Ambient temperature
Operating temperature
+32 to +131°F (0 to +55°C)
Storage temperature
-13 to +185°F (-25 to +85°C
Relative humidity
5 to 95% (indoor), Level RH-2, without condensation (storage at 45°C)
SO2
10 ppm (rel. humidity <75%, without condensation)
H2S
1.0 ppm (rel. humidity <75%, without condensation)
Resistant to vibration
According to EN 61131
Operating conditions
According to EN 61131
Resistant to shock
According to IEC 68-2-27
Resistant to repetitive shock
According to IEC 68-2-29
Topple and fall
According to IEC 68-2-31 and free fall according to IEC 68-2-32
Protection class
IP 20
Electromagnetic compatibility (EMC)
According to EN 50 082-2 (Industry)
Tests
According to EN 61131-2
BL20
Noxious gas
Base Modules
Measurement data
According to VDE 0611 part 1/8.92 / IEC 947-7-1/1989
Connection to technology in TOP construction
Tension clamp or screw connection
Insulation stripping length
8 mm
Crimpable wire
Nominal diameter
1.5 mm2
“e” solid core H 07V-U
0.5 to 2.5 mm2
“f” flexible core H 07V-K
0.5 to 1.5 mm
“f” with ferrules according to DIN 46 228/1 (ferrules crimped gas-tight)
0.5 to 1.5 mm
Plug gauge according to IEC 947-1/1988
A1
Protection class
IP 20
Approvals
2
2
CE
UL
CSA
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
C4
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
TURCK
Modular Industrial I/O System
TURCK’s USA website is your most complete and up-to-date source for product documentation,
CAD files and more. Search results produce downloadable documentation or request for quote
(RFQ). Additional product information or CAD files are easily requested and promptly filled.
Visit our site for new product releases, approvals, white papers, application support and more.
Access to all TURCK catalogs, press
releases, white papers and tutorials
Complete category listing
of TURCK products
Search for products
by part number, ID
number or key word
Access to CAD, wiring
and pinout diagrams
Download or e-mail
files, request for quote
Option to
e-mail pages
Contact a
TURCK representative
www.turck.com
C5
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Industrial
Automation
BL20 Gateway Selection Guide
Higher Level System
Pages
DeviceNet™
C7
PROFIBUS®-DP
C8
Ethernet
C9
Ethernet
C10
CANopen
C11
BL20
Gateways
BL20 Module Selection Guide
Modules
Type
I/O Direction
Pages
Discrete
Input
C13 - C18, C25, C29
Output
C19 - C24, C27, C31
Input
C33 - C38
Output
C39
Serial
Input & Output
C41
Counter
Input
C43
Motor Starter
Input & Output
C49
Analog
Power Feed
C45
Base Modules
C58
Accessories
C64
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
C6
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
TURCK
Modular Industrial I/O System
DeviceNet Gateway
• Modular I/O
• IP 20 Protection
• Fieldbus Independent Configuration
• Various I/O Styles
Electrical
• Operating Current: <250 mA from BR power supply
• Supply Current: <10 A to I/O (from UL)
<1.5 A to backplane (from USYS)
Mechanical
• Operating Temperature: 0 to +55°C (+32 to +131°F)
• Protection: IP 20
• Vibration: 1 g @ 5-100 Hz
Material
BL20-GWBR-DNET
• Housing: PC-V0 (Lexan)
Diagnostics (Logical)
• Diagnostic information available through the DeviceNet I/O map
Diagnostics (Physical)
• LEDs to indicate status of DeviceNet and Module Bus communication
DeviceNet Connector
Power Connection
1 = USYS
2 = GndSYS
3 = UL
4 = GndL
C7
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Industrial
Automation
PROFIBUS-DP Gateway
• Modular I/O
• IP 20 Protection
• Fieldbus Independent Configuration
• Various I/O Styles
Electrical
• Operating Current: <430 mA from BR power supply (USYS)
• Supply Current: <10 A to I/O (from UL)
<1.5 A to backplane (from USYS)
Mechanical
BL20
• Operating Temperature: 0 to +55°C (+32 to +131°F)
• Protection: IP 20
• Vibration: 1 g @ 5-100 Hz
Material
• Housing: PC-V0 (Lexan)
Diagnostics (Logical)
• Diagnostic information available through the PROFIBUS-DP interface
BL20-GW-DPV1
Diagnostics (Physical)
• LEDs to indicate status of PROFIBUS-DP and Module Bus communication
Power Connectors
PROFIBUS-DP
Connector
1 = Shield
3 = BUS_B
5 = DGnd
6 = +5 VDC
8 = BUS_A
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
C8
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
TURCK
Modular Industrial I/O System
Ethernet Gateway
• Modular I/O
• IP 20 Protection
• Fieldbus Independent Configuration
• Various I/O Styles
Electrical
• Operating Current: <430 mA from BR power supply (USYS)
• Supply Current: <10 A to I/O (from UL)
<1.5 A to backplane (from USYS)
Mechanical
• Operating Temperature: 0 to +55°C (+32 to +131°F)
• Protection: IP 20
• Vibration: 1 g @ 5-100 Hz
Material
• Housing: PC-V0 (Lexan)
Diagnostics (Logical)
• Diagnostic information available through the PROFIBUS-DP interface
BL20-GW-EN
BL20-PG-EN
Diagnostics (Physical)
• LEDs to indicate status of PROFIBUS-DP and Module Bus communication
Programmability
• PG in part number designates a programmable gateway
• Progammable according to IEC 61131.3 using CodeSys (includes ladder logic)
• Use CodeSys to create logic programs to control local I/O
Power Connectors
RJ45 Ethernet Standard
1 = WH/or (+TX)
2 = OR (-TX)
3 = WH/GN (+RX)
4 = BU
5 = WH/BU
6 = GN (-RX)
7 = WH/BN
8 = BN
C9
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Industrial
Automation
Ethernet Gateway
• Modular I/O
• IP 20 Protection
• Fieldbus Independent Configuration
• Various I/O Styles
Electrical
• Operating Current: <430 mA from BR power supply (USYS)
• Supply Current: <10 A to I/O (from UL)
<1.5 A to backplane (from USYS)
Mechanical
BL20
• Operating Temperature: 0 to +55°C (+32 to +131°F)
• Protection: IP 20
• Vibration: 1 g @ 5-100 Hz
Material
• Housing: PC-V0 (Lexan)
Diagnostics (Logical)
• Diagnostic information available through the PROFIBUS-DP interface
BL20-GW-EN-IP
BL20-PG-EN-IP
Diagnostics (Physical)
• LEDs to indicate status of PROFIBUS-DP and Module Bus communication
Programmability
• PG in part number designates a programmable gateway
• Progammable according to IEC 61131.3 using CodeSys (includes ladder logic)
• Use CodeSys to create logic programs to control local I/O
Power Connectors
RJ45 Ethernet Standard
1 = WH/or (+TX)
2 = OR (-TX)
3 = WH/GN (+RX)
4 = BU
5 = WH/BU
6 = GN (-RX)
7 = WH/BN
8 = BN
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
C10
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
TURCK
Modular Industrial I/O System
CANopen Gateway
• Modular I/O
• IP 20 Protection
• Fieldbus Independent Configuration
• Various I/O Styles
Electrical
• Operating Current: <350 mA from BR power supply (USYS)
• Supply Current: <10 A to I/O (from UL)
<1.5 A to backplane (from USYS)
Mechanical
• Operating Temperature: 0 to +55°C (+32 to +131°F)
• Protection: IP 20
• Vibration: 1 g @ 5-100 Hz
Material
• Housing: PC-V0 (Lexan)
BL20-GWBR-CANOPEN
Diagnostics (Logical)
• Diagnostic information available through the CANopen interface
Diagnostics (Physical)
• LEDs to indicate status of CANopen and Module Bus communication
CANopen Connector
1 = NC
2 = CAN_H
3 = Shield
4 = CAN_L
5 = Gnd
Power connector
1 = UL+
2 = VL3 = USYS+
4 = USYS-
C11
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Industrial
Automation
BL20
Notes:
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
C12
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
TURCK
Modular Industrial I/O System
Discrete Input Modules
• Modular I/O
• IP 20 Protection
• Fieldbus Independent Configuration
• Various I/O Styles
Electrical
• Operating Current:
<28 mA from VMB
<20 mA from VIO (...-2DI...)
<40 mA from VIO (...-4DI...)
Power Distribution
• Inputs: VIO
• Logic: VMB and VIO
Mechanical
• Operating Temperature: 0 to +55°C (+32 to +131°F)
• Protection: IP 20
BL20-2DI-24VDC-N
BL20-2DI-24VDC-P
BL20-4DI-24VDC-N
BL20-4DI-24VDC-P (shown)
C13
Diagnostics
• LED to indicate module bus communication status as well as I/O diagnostics
• LEDs for each I/O point to indicate on/off status
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Industrial
Automation
Data
BL20-2DI-24VDC-P with
BL20-S3*-SBB**
2
B20-3A
PNP
1
BL20-2DI-24VDC-N with
BL20-S3*-SBB**
2
B20-3A
NPN
1
BL20-4DI-24VDC-P with
BL20-S6*-SBBSBB**
4
B20-6A
PNP
2
BL20-4DI-24VDC-N with
BL20-S6*-SBBSBB**
4
B20-6A
NPN
2
BL20
I/O
Ma
p
Gro
up
Dia
gno
stic
s
Ind
ivi
Dia dual
gno
stic
s
Wi
reDe Break
tec
tion
le
Part Number
Sty
Inp
Pin
out
ut C
oun
t
Inputs
* T = Tension clamp
S = Screw clamp
** Base modules sold separately. See page C58 - C61.
Input Connectors
B20-3A
B20-6A
I/O Data Map 2
I/O Data Map 1
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
In
n–1
n
n+1
n–1
(Data from modules to the left)
Data from next discrete modules
I-1
(Data from modules to the right)
I-0
In
n
n+1
(Data from modules to the left)
Data from next discrete
modules
I-3
I-2
I-1
I-0
(Data from modules to the right)
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
C14
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
TURCK
Modular Industrial I/O System
Discrete Input Economy
Module
• Modular I/O
• Fieldbus Independent Configuration
• Base and Electronics in One
Part
• IP 20 Protection
Electrical
• Operating Current: <30 mA from VMB
<2 mA from VIO
Power Distribution
• Inputs: VIO
• Logic: VMB and VIO
Mechanical
• Operating Temperature: 0 to +55°C (+32 to +131°F)
• Protection: IP 20
BL20-E-8DI-24VDC-P
BL20-E-16DI-24VDC-P
Diagnostics
• LED to indicate module bus communication status as well as I/O diagnostics
• LEDs for each I/O point to indicate on/off status
16DI..
8DI..
C15
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Industrial
Automation
I/O
Ma
p
le
Data
Gro
up
Dia
gno
stic
s
Ind
ivi
Dia dual
gno
stic
s
Wi
reDe Break
tec
tion
Co
Part Number
Sty
unt
Pin
out
Inputs
8
B20-E1
PNP
1
BL20-E-16DI-24VDC-P
16
B20-E2
PNP
2
BL20
BL20-E-8DI-24VDC-P
Note: This module can only be used with other tension clamp modules.
Input Connectors
B20-E1
B20-E2
8Dlp
24 Vdc
DIA
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
9
10
I/O Data Map 2
I/O Data Map 1
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
In
n–1
n
n+1
n–1
(Data from modules to the left)
I-7
I-6
I-5
I-4
I-3
I-2
I-1
(Data from modules to the right)
I-0
In
(Data from modules to the left)
n
I-7
I-6
I-5
I-4
I-3
I-2
I-1
I-0
n+1
I-8
I-9
I-10
I-11
I-12
I-13
I-14
I-15
n+2
(Data from right)
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
C16
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
TURCK
Modular Industrial I/O System
NAMUR Input Module
• Modular I/O
• IP 20 Protection
• Fieldbus Independent Configuration
• NAMUR Inputs
Electrical
• Operating Current:
<40 mA from VMB
<30 mA from VIO
Power Distribution
• Inputs: VIO
• Logic: VMB and VIO
Mechanical
• Operating Temperature: 0 to +55°C (+32 to +131°F)
• Protection: IP 20
Diagnostics (Logical)
• Diagnostic information available through the fieldbus gateway
BL20-4DI-NAMUR
Diagnostics (Physical)
• LED to indicate module bus communication status as well as I/O diagnostics
• LEDs for each I/O point to indicate on/off status
C17
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Industrial
Automation
BL20-4DI-NAMUR with
BL20-S4*-SBBS**
4
B20-4C
NAMUR
X
I/O
Ma
p
Data
Gro
up
Dia
gno
stic
s
Ind
ivi
Dia dual
gno
stic
s
Wi
reDe Break
tec
tion
le
Part Number
Sty
Inp
Pin
out
ut C
oun
t
Inputs
1
BL20
* T = Tension clamp
S = Screw clamp
** Base modules sold separately. See page C58 - C61.
Input Connectors
B20-4C
I/O Data Map 1
Byte Bit 7
In
Bit 6
n–1
n
n+1
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
I-1
I-0
(Data from modules to the left)
S-3
S-2
S-1
S-0
I-3
I-2
(Data from modules to the right)
Note: S = status bit
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
C18
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
TURCK
Modular Industrial I/O System
Discrete DC Output
Modules
• Modular I/O
• IP 20 Protection
• Fieldbus Independent Configuration
• Various I/O Styles
Electrical
• Operating Current: <33 mA from VMB
<25 mA from VIO (...-0.5A...)
<50 mA from VIO (...-2A...)
• Output Current: see table on facing page (from VIO)
Power Distribution
• Outputs: VIO
• Logic: VMB and VIO
Mechanical
• Operating Temperature: 0 to +55°C (+32 to +131°F)
• Protection: IP 20
Diagnostics (Logical)
BL20-2DO-24VDC-2A-P
BL20-2DO-24VDC-0.5A-N
BL20-2DO-24VDC-0.5A-P
BL20-4DO-24VDC-0.5A-P
C19
• Diagnostic information available through the fieldbus gateway
Diagnostics (Physical)
• LED to indicate module bus communication status as well as I/O diagnostics
• LEDs for each I/O point to indicate on/off status
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Industrial
Automation
BL20-2DO-24VDC-0.5A-P with BL20-S3*-SBC**
4
B20-3B
0.5 A
1
BL20-2DO-24VDC-0.5A-N with BL20-S3*-SBC**
4
B20-3B
0.5 A
1
BL20-2DO-24VDC-2A-P with BL20-S3*-SBC**
4
B20-3B
2A
1
BL20-4DO-24VDC-0.5A-P with BL20-S6*-SBCSBC**
4
B20-6B
0.5 A
2
BL20
I/O
Ma
p
Data
Ind
ivi
Dia dual
gno
stic
s
Wi
reDe Break
tec
tion
nt
Cu
rre
Part Number
Pin
out
Inp
ut C
oun
t
Outputs
* T = Tension clamp
S = Screw clamp
** Base modules sold separately. See page C58 - C61.
Output Connectors
B20-3B
B20-6B
I/O Data Map 1
I/O Data Map 2
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Out
n–1
n
n+1
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
(Data for modules to the left)
Data for next discrete modules
O-1
(Data for modules to the right)
n–1
O-0
Out
n
n+1
(Data for modules to the left)
Data for next discrete
modules
O-3
O-2
O-1
O-0
(Data for modules to the right)
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
C20
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
TURCK
Modular Industrial I/O System
Discrete Output Economy
Module
• Modular I/O
• IP 20 Protection
• Fieldbus Independent Configuration
• Base and Electronics in One
Part
Electrical
• Operating Current: <30 mA from VMB
<10 mA from VIO
• Output Current: <0.5 A per output (from VIO)
Power Distribution
• Outputs: VIO
• Logic: VMB and VIO
Mechanical
BL20-E-8DO-24VDC-0.5A-P
BL20-E-16DO-24VDC-0.5A-P
• Operating Temperature: 0 to +55°C (+32 to +131°F)
• Protection: IP 20
Diagnostics (Logical)
• Diagnostic information available through the fieldbus gateway
Diagnostics (Physical)
• LED to indicate module bus communication status as well as I/O diagnostics
• LEDs for each I/O point to indicate on/off status
C21
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Industrial
Automation
Data
I/O
Ma
p
Wi
re
De -Brea
tec
k
tion
nt
Ind
iv
Dia idual
gno
stic
s
Part Number
Cu
rre
Inp
Pin
out
ut C
oun
t
Outputs
8
BO-E1
0.5 A
X
1
BL20-E-16DO-24VDC-0.5A-P
16
BO-E2
0.5 A
X
2
BL20
BL20-E-8DO-24VDC-0.5A-P
Output Connectors
BO-E1
BO-E2
8DOp
24Vdc 0.5A
DIA
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
9
10
I/O Data Map 2
I/O Data Map 1
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Out
n–1
n
n+1
(Data for modules to the left)
O-7
O-6
O-5
O-4
O-3
O-2
O-1
(Data for modules to the right)
n–1
Out
O-0
(Data for modules to the left)
n
O-7
O-6
O-5
O-4
O-3
O-2
O-1
O-0
n+1
0-8
O-9
O-10
O-11
O-12
O-13
O-14
O-15
n+2
(Data from right)
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
C22
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
TURCK
Modular Industrial I/O System
Discrete relay Output
Modules
• Modular I/O
• IP 20 Protection
• Fieldbus Independent Configuration
• Relay Outputs
Electrical
• Operating Current:
<28 mA from VMB
<20 mA from VIO
Power Distribution
• Outputs: VIO
• Logic: VMB and VIO
Mechanical
• Operating Temperature: 0 to +55°C (+32 to +131°F)
• Protection: IP 20
Diagnostics (Logical)
BL20-2DO-R-CO
BL20-2DO-R-NO
BL20-2DO-R-NC
C23
• Diagnostic information available through the fieldbus gateway
Diagnostics (Physical)
• LED to indicate module bus communication status as well as I/O diagnostics
• LEDs for each I/O point to indicate on/off status
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Industrial
Automation
BL20-2DO-R-NO with BL20-S4*-SBCS**
2
B20-4A
2A
1
BL20-2DO-R-NC with BL20-S4*-SBCS**
2
B20-4A
2A
1
BL20-2DO-R-CO with BL20-S4*-SBBS**
2
B20-4B
2A
1
BL20
I/O
Ma
p
Data
Ind
ivi
Dia dual
gno
stic
s
Wi
reDe Break
tec
tion
nt
rre
Cu
Co
Part Number
Pin
out
unt
Outputs
* T = Tension clamp
S = Screw clamp
** Base modules sold separately. See pages C58 - C61.
Output Connectors
B20-4A
B20-4B
I/O Data Map 1
Byte Bit 7
Out
n–1
n
n+1
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
O-1
O-0
(Data for modules to the left)
Data for next discrete modules
(Data for modules to the right)
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
C24
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
TURCK
Modular Industrial I/O System
Discrete AC Input Module
• Modular I/O
• IP 20 Protection
• Fieldbus Independent Configuration
• AC Inputs
Electrical
• Operating Current:
<28 mA (from VMB)
<20 mA (from VIO)
Power Distribution
• Inputs: VIO
• Logic: VMB and VIO
Mechanical
BL20-2DI-120/230VAC-P
• Operating Temperature: 0 to +55°C (+32 to +131°F)
• Protection: IP 20
Diagnostics (Physical)
• LED to indicate module bus communication status as well as I/O diagnostics
• LEDs for each I/O point to indicate on/off status
C25
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Industrial
Automation
BL20-2DI-120/230VAC-P with
BL20-S3*-SBB**
2
Sty
Pin
out
B20-3C
le
oun
ut C
Inp
Part Number
Data
Gro
up
Dia
gno
stic
s
Ind
ivi
Dia dual
gno
stic
s
Wi
reDe Break
tec
tion
t
Inputs
AC
I/O Map
1
BL20
* T = Tension clamp
S = Screw clamp
** Base modules sold separately. See pages C58 - C61.
Input Connectors
B20-3C
I/O Data Map 1
Byte Bit 7
In
n–1
n
n+1
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
I-1
I-0
(Data from modules to the left)
Data from next discrete modules
(Data from modules to the right)
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
C26
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
TURCK
Modular Industrial I/O System
Discrete AC Output Module
• Modular I/O
• IP 20 Protection
• Fieldbus Independent Configuration
• AC Outputs
Electrical
• Operating Current:
<35 mA from VMB
<20 mA from VIO
• Output Current: <0.5 A per output (from VIO)
Power Distribution
• Outputs: VIO
• Logic: VMB and VIO
Mechanical
• Operating Temperature: 0 to +55°C (+32 to +131°F)
• Protection: IP 20
BL20-2DO-120/230VAC-0.5A
Diagnostics (Logical)
• Diagnostic information available through the fieldbus gateway
Diagnostics (Physical)
• LED to indicate module bus communication status as well as I/O
diagnostics
• LEDs for each I/O point to indicate on/off status
C27
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Industrial
Automation
BL20-2DO-120/230VAC-0.5A-P with
BL20-S3*-SBC**
2
B20-3B
0.5 A
I/O
Ma
p
Data
Ind
ivi
Dia dual
gno
stic
s
Wi
reDe Break
tec
tion
nt
rre
Cu
Part Number
Pin
out
Ou
tp
Co ut
unt
Outputs
1
BL20
* T = Tension clamp
S = Screw clamp
** Base modules sold separately. See pages C58 - C61.
Output Connectors
B20-3B
I/O Data Map 1
Byte Bit 7
Out
n–1
n
n+1
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
O-1
O-0
(Data for modules to the left)
Data for next discrete modules
(Data for modules to the right)
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
C28
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
TURCK
Modular Industrial I/O System
Discrete Input Blocks
• Modular I/O
• IP 20 Protection
• Fieldbus Independent Configuration
• Various I/O Styles
Electrical
• Operating Current: <45 mA from VMB
<40 mA from VIO (...-16DI...)
<30 mA from VIO (...-32DI...)
Power Distribution
• Inputs: VIO
• Logic: VMB and VIO
Mechanical
BL20-32DI-24VDC-P
BL20-16DI-24VDC-P
• Operating Temperature: 0 to +55°C (+32 to +131°F)
• Protection: IP 20
Diagnostics (Physical)
• LED to indicate module bus communication status as well as I/O diagnostics
• LEDs for each I/O point to indicate on/off status
C29
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Industrial
Automation
Data
BL20-16DI-24VDC-P with
BL20-B3*-SBB**
16
B20-B3A
PNP
1
BL20-32DI-24VDC-P with
BL20-B6*-SBBSBB**
32
B20-B6A
PNP
2
BL20
I/O
Ma
p
Gro
up
Dia
gno
stic
s
Ind
ivi
Dia dual
gno
stic
s
Wi
reDe Break
tec
tion
le
Sty
Part Number
Pin
out
Inp
ut C
oun
t
Inputs
* T = Tension clamp
S = Screw clamp
** Base modules sold separately. See pages C58 - C61.
Input Connectors
B20-B6A
B20-B3A
I/O Data Map 1
In
I/O Data Map 2
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
n–1
n–1
(Data from modules to the left)
n
I-7
I-6
I-5
I-4
I-3
I-2
I-1
I-0
n+1
I-15
I-14
I-13
I-12
I-11
I-10
I-9
I-8
n+2
(Data from modules to the right)
In
(Data from modules to the left)
n
I-7
I-6
I-5
I-4
I-3
I-2
I-1
n+1
I-15
I-14
I-13
I-12
I-11
I-10
I-9
I-8
n+2
I-23
I-22
I-21
I-20
I-19
I-18
I-17
I-16
n+3
I-31
I-30
I-29
I-28
I-27
I-26
I-25
I-24
n+4
I-0
(Data from modules to the right)
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
C30
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
TURCK
Modular Industrial I/O System
Discrete Output Blocks
• Modular I/O
• IP 20 Protection
• Fieldbus Independent Configuration
• Various I/O Styles
Electrical
• Operating Current:
<120 mA from VMB
<50 mA from VIO
• Output Current: <0.5 A per output (from VIO)
Power Distribution
• Outputs: VIO
• Logic: VMB and VIO
BL20-32DO-24VDC-0.5A-P
BL20-16DO-24VDC-0.5A-P
Mechanical
• Operating Temperature: 0 to +55°C (+32 to +131°F)
• Protection: IP 20
Diagnostics (Logical)
• Diagnostic information available through the fieldbus gateway
Diagnostics (Physical)
• LED to indicate module bus communication status as well as I/O diagnostics
• LEDs for each I/O point to indicate on/off status
C31
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Industrial
Automation
Data
BL20-16DO-24VDC-0.5A-P with
BL20-B3*-SBC**
16
B20-B3B
0.5 A
1
BL20-32DO-24VDC-0.5A-P with
BL20-B6*-SBCSBC**
32
B20-B6B
0.5 A
2
BL20
I/O
Ma
p
Ind
ivi
Dia dual
gno
stic
s
Wi
reDe Break
tec
tion
nt
Cu
rre
Part Number
Pin
out
Ou
tp
Co ut
unt
Outputs
* T = Tension clamp
S = Screw clamp
** Base modules sold separately. See pages C58 - C61.
Output Connectors
B20-B6B
B20-B3B
I/O Data Map 1
Out
I/O Data Map 2
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
n–1
n–1
(Data for modules to the left)
n
O-7
O-6
O-5
O-4
O-3
O-2
O-1
O-0
n+1
O-15
O-14
O-13
O-12
O-11
O-10
O-9
O-8
n+2
(Data for modules to the right)
out
(Data for modules to the left)
n
O-7
O-6
O-5
O-4
O-3
O-2
O-1
n+1
O-15
O-14
O-13
O-12
O-11
O-10
O-9
O-8
n+2
O-23
O-22
O-21
O-20
O-19
O-18
O-17
O-16
n+3
O-31
O-30
O-29
O-28
O-27
O-26
O-25
O-24
n+4
O-0
(Data for modules to the right)
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
C32
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
TURCK
Modular Industrial I/O System
Analog Input Modules
• Modular I/O
• IP 20 Protection
• Fieldbus Independent Configuration
• Various I/O Styles
Electrical
• Operating Current:
<41 mA from VMB (...-1AI...)
<35 mA from VMB (...-2AI...)
<50 mA from VIO (...-1AI...)
<12 mA from VIO (...-2AI...)
Power Distribution
• Inputs: VIO
• Logic: VMB and VIO
Mechanical
BL20-2AI-U(-10/0 to +10VDC)
BL20-2AI-I(0/4 to 20MA)
BL20-1AI-U(-10/0 to +10VDC)
BL20-1AI-I(0/4 to 20MA)
• Operating Temperature: 0 to +55°C (+32 to +131°F)
• Protection: IP 20
Diagnostics (Logical)
• Diagnostic information available through the fieldbus gateway
Diagnostics (Physical)
• LED to indicate module bus communication status as well as I/O
diagnostics
C33
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Industrial
Automation
Data
BL20-1AI-U(-10/0 to +10VDC) with
BL20-S4*-SBBS**
1
B20-4D
-10/0 to 10 V
1
BL20-1AI-I(0/4 to 20MA) with
BL20-S4*-SBBS**
1
B20-4D
0/4 to 20 mA
1
BL20-2AI-U(-10/0 to +10VDC) with
BL20-S4*-SBBS**
2
B20-4E
-10/0 to 10 V
2
BL20-2AI-I(0/4 to 20MA) with
BL20-S4*-SBBS**
2
B20-4E
0/4 to 20 mA
2
BL20
I/O
Ma
p
Gro
up
Dia
gno
stic
s
Ind
ivi
Dia dual
gno
stic
s
Wi
reDe Break
tec
tion
le
Sty
Part Number
Pin
out
Inp
ut C
oun
t
Inputs
* T = Tension clamp
S = Screw clamp
** Base modules sold separately. See pages C58 - C61.
Input Connectors
B20-4D
I/O Data Map 1
In
B20-4E
I/O Data Map 2
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
n–1
(Data from modules to the left)
n–1
(Data from modules to the left)
n
Channel 0, LSB
n
Channel 0, LSB
n+1
Channel 0, MSB
n+1
Channel 0, MSB
n+2
(Data from modules to the right)
n+2
Channel 1, LSB
In
n+3
Channel 1, MSB
n+4
(Data from modules to the right)
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
C34
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
TURCK
Modular Industrial I/O System
Analog Input Module
• Modular I/O
• IP 20 Protection
• Fieldbus Independent Configuration
• Voltage and Current Inputs
Electrical
• Operating Current:
<50 mA from VMB
<20 mA from VIO (...-2AI...)
Power Distribution
• Inputs: VIO
• Logic: VMB and VIO
Mechanical
• Operating Temperature: 0 to +55°C (+32 to +131°F)
• Protection:IP 20
BL20-4AI-U/I
Diagnostics (Logical)
• Diagnostic information available through the fieldbus gateway
Diagnostics (Physical)
• LED to indicate module bus communication status as well as I/O diagnostics
C35
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Industrial
Automation
4
Sty
le
Pin
out
B20-6C
0/4 to 20 mA
or
-10/0 to 10V
1
BL20
BL20-4AI-U/I with
BL20-S6*-SBCSBC**
I/O
Ma
p
oun
ut C
Inp
Part Number
Data
Gro
up
Dia
gno
stic
s
Ind
ivid
Dia ual
gno
stic
s
Wi
reDe Break
tec
tion
t
Inputs
* T = Tension clamp
S = Screw clamp
** Base modules sold separately. See pages C58 - C61.
Input Connectors
B20-6C
I/O Data Map 1
Byte Bit 7
In
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
n–1
(Data from modules to the left)
n
Channel 0, LSB
n+1
Channel 0, MSB
n+2
Channel 1, LSB
n+3
Channel 1, MSB
n+4
Channel 2, LSB
n+5
Channel 2, MSB
n+6
Channel 3, LSB
n+7
Channel 3, MSB
n+8
(Data from modules to the right)
Bit 1
Bit 0
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
C36
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
TURCK
Modular Industrial I/O System
Temperature Input Modules
• Modular I/O
• IP 20 Protection
• Fieldbus Independent Configuration
• Thermocouple or RTD Inputs
Electrical
• Operating Current:
<45 mA from VMB
<30 mA from VIO
• Thermocouple Types: B, E, J, K, N, R, S, T (... THERMO-PI)
• RTD Types: PT100, PT500, PT1000, Ni100, Ni1000 (...PT/Ni-2/3)
Power Distribution
• Inputs: VIO
• Logic: VMB and VIO
Mechanical
• Operating Temperature: 0 to +55°C (+32 to +131°F)
• Protection: IP 20
BL20-2AI-THERMO-PI
BL20-2AI-PT/NI-2/3
Diagnostics (Logical)
• Diagnostic information available through the fieldbus gateway
Diagnostics (Physical)
• LED to indicate module bus communication status as well as I/O diagnostics
C37
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Industrial
Automation
BL20-2AI-PT/NI-2/3 with
BL20-S4*-SBBS**
2
B20-4F
RTD
1
BL20-2AI-THERMO-PI with
BL20-S4*-SBBS-CJ**
2
B20-4G
TC
1
BL20
I/O
Ma
p
Wi
re
De -Brea
tec
k
tion
Ind
iv
Dia idual
gno
stic
s
Data
Gro
u
Dia p
gno
stic
s
le
Sty
Part Number
Pin
out
Inp
ut C
oun
t
Inputs
* T = Tension clamp
S = Screw clamp
** Base modules sold separately. See pages C58 - C61.
Note: BL20-S4*-SBBS-CJ has integrated cold junction compensation fro thermocouples.
Input Connectors
B20-4G
B20-4F
I/O Data Map 1
Byte Bit 7
In
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
n–1
(Data from modules to the left)
n
Channel 0, LSB
n+1
Channel 0, MSB
n+2
Channel 1, LSB
n+3
Channel 1, MSB
n+4
(Data from modules to the right)
Bit 1
Bit 0
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
C38
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
TURCK
Modular Industrial I/O System
Analog Output Modules
• Modular I/O
• IP 20 Protection
• Fieldbus Independent Configuration
• Various I/O Styles
Electrical
• Operating Current: <43 mA (from VMB)
• Sensor Current: <50 mA (from VIO)
Power Distribution
• Inputs: VIO
• Logic: VMB and VIO
Mechanical
• Operating Temperature: 0 to +55°C (+32 to +131°F)
• Protection: IP 20
Diagnostics (Logical)
BL20-2AO-I(0/4 to 20MA)
BL20-2AO-U(-10/0 to +10VDC)
BL20-1AO-I(0/4 to 20MA)
C39
• Diagnostic information available through the fieldbus gateway
Diagnostics (Physical)
• LED to indicate module bus communication status as well as I/O
diagnostics
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Industrial
Automation
BL20-1AO-I(0/4 to 20MA) with
BL20-S3*-SBB**
1
B20-3D
0/4 to 20 mA
1
BL20-2AO-I(0/4 to 20MA) with
BL20-S3*-SBB**
1
B20-3E
0/4 to 20 mA
2
BL20-2AI-U(-10/0 to +10VDC) with
BL20-S3*-SBB**
2
B20-3E
-10/0 to 10 V
2
BL20
I/O
Ma
p
Data
Gro
up
Dia
gno
stic
s
Ind
ivi
Dia dual
gno
stic
s
Wi
reDe Break
tec
tion
le
Sty
Part Number
Pin
out
Ou
tp
Co ut
unt
Outputs
* T = Tension clamp
S = Screw clamp
** Base modules sold separately. See pages C58 - C61.
Output Connectors
B20-3D
I/O Data Map 1
Out
B20-3E
I/O Data Map 2
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
n–1
(Data for modules to the left)
n–1
(Data for modules to the left)
n
Channel 0, LSB
n
Channel 0, LSB
n+1
Channel 0, MSB
n+2
(Data for modules to the right)
Out n+1
n+2
Channel 0, MSB
Channel 1, LSB
n+3
Channel 1, MSB
n+4
(Data for modules to the right)
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
C40
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
TURCK
Modular Industrial I/O System
Serial I/O Modules
• Modular I/O
• IP 20 Protection
• Fieldbus Independent Configuration
• Various I/O Styles
Electrical
• Operating Current:
<25 mA from VIO
<140 mA from VMB (...1RS232)
<50 mA from VMB (...1SSI)
<60 mA from VMB (...1RS485/422)
Power Distribution
• I/O: VIO
• Logic: VMB and VIO
Mechanical
BL20-1RS232
BL20-1SSI
BL20-1RS485/422
• Operating Temperature: 0 to +55°C (+32 to +131°F)
• Protection: IP 20
Diagnostics (Logical)
• Diagnostic information available through the fieldbus gateway
Diagnostics (Physical)
• LED to indicate module bus communication status as well as I/O diagnostics
• LEDs for each I/O point to indicate on/off status
C41
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Industrial
Automation
BL20-1RS232 with
BL20-S4*-SBBS**
1
B20-4H
RS232
1
B20-4H
RS232
#
BL20-1RS485/422
with
BL20-S4*-SBBS**
1
B20-4I
RS485/422
1
B20-4I
RS485/422
#
BL20-1SSI with
BL20-S4*-SBBS**
1
B20-4J
SSI
1
B20-4J
SSI
#
BL20
I/O
Ma
p
Data
Ind
iv
Dia idual
gno
stic
s
Wi
reDe Brea
tec
k
tion
le
Sty
Pin
out
Outputs
Gro
u
Dia p
gno
stic
s
Ind
ivid
Dia ual
gno
stic
s
Wi
reB
r
De
tec eak
tion
Ou
tp
Co ut
unt
Sty
le
Pin
out
Part Number
Inp
ut C
oun
t
Inputs
* T = Tension clamp
S = Screw clamp
** Base modules sold separately. See pages C58 - C61.
# I/O data map is dependant on the fieldbus being used. Consult the user manual for details.
Input/Output Connectors
B20-H4
B20-4I
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
B20-4J
www.turck.com
C42
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
TURCK
Modular Industrial I/O System
Counter Module
• Modular I/O
• IP 20 Protection
• Fieldbus Independent Configuration
• Counter Input
Electrical
<50 mA (from VIO)
<40 mA (from VMB)
0...7FFFFFFF (positive)
80000000...FFFFFFFF (negative)
• Operating Current:
• Count Range:
Power Distribution
• Inputs: VIO
• Logic: VMB and VIO
Mechanical
BL20-1CNT-24VDC
• Operating Temperature: 0 to +55°C (+32 to +131°F)
• Protection: IP 20
Diagnostics (Logical)
• Diagnostic information available through the fieldbus gateway
Diagnostics (Physical)
• LED to indicate module bus communication status as well as I/O diagnostics
• LEDs for each I/O point to indicate on/off status
C43
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Industrial
Automation
BL20-1CNT-24VDC with
BL20-S4*-SBBS**
1
B20-4K
Counter
I/O
Ma
p
Wi
reDe Break
tec
tion
Data
Ind
ivi
Dia dual
gno
stic
s
Gro
up
Dia
gno
stic
s
le
Sty
Pin
out
Part Number
Inp
ut C
oun
t
Inputs
See below
BL20
* T = Tension clamp
S = Screw clamp
** Base modules sold separately. See pages C58 - C61.
Input Connectors
B20-4K
I/O data map is dependant on the fieldbus being used. Consult the user manual for details.
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
C44
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
TURCK
Modular Industrial I/O System
Power Feeding Modules
• Modular I/O
• IP 20 Protection
• Fieldbus Independent Configuration
• Supply AC or DC I/O Power
Electrical
• Operating Current: <28 mA (from VMB)
• Output Current: <10 A for downstream I/O
Power Distribution
• Accepts AC (...120/230VAC...) or DC (...24VDC...) supply to provide V IO for
downstream modules
Mechanical
• Operating Temperature: 0 to +55°C (+32 to +131°F)
• Protection: IP 20
BL20-PF-120/230VAC-D
BL20-PF-24VDC-D
Diagnostics (Logical)
• Diagnostic information available through the fieldbus gateway
Diagnostics (Physical)
• LED to indicate module bus communication and power supply status.
C45
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Industrial
Automation
Pinout
BL20-PF-120/230VAC-D with BL20-P3*-SBB**
B20-P3
BL20-PF-120/230VAC-D with BL20-P4*-SBBC**
B20-P4
BL20-PF-24VDC-D with BL20-P3*-SBB**
B20-P3
BL20-PF-24VDC-D with BL20-P4*-SBBC**
B20-P4
BL20
Part Number
* T = Tension clamp
S = Screw clamp
** Base modules sold separately. See pages C58 - C61.
Input Connectors
B20-P3
B20-P4
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
C46
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
TURCK
Modular Industrial I/O System
Bus Refreshing Module
• Modular I/O
• IP 20 Protection
• Fieldbus Independent Configuration
Electrical
• Module Bus Supply: <1.5 A
• I/O Supply: <10 A (24 VDC only)
Power Distribution
• Refreshes backplane (VMB) supply and provides new VIO segment for
downstream modules
Mechanical
• Operating Temperature: 0 to +55°C (+32 to +131°F)
• Protection: IP 20
Diagnostics (Logical)
BL20-BR-24VDC-D
• Diagnostic information available through the fieldbus gateway
Diagnostics (Physical)
• LED to indicate module bus communication and power supply status.
C47
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Industrial
Automation
Part Number
Pinout
B20-P3A
BL20-BR-24VDC-D with BL20-P4*-SBBC-B**
B20-P4A
BL20
BL20-BR-24VDC-D with BL20-P3*-SBB-B**
* T = Tension clamp
S = Screw clamp
** Base modules sold separately. See pages C58 - C61.
Input Connectors
B20-P3A
B20-P4A
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
C48
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
TURCK
Modular Industrial I/O System
BL20 Motor Starter Modules
BL20 motor starters allow 3-phase motor control to be connected to the same BL20 rack as the standard I/O. BL20 motor
starters can be mounted on the same rail as the BL20 gateway, or they can be mounted on another rail to ease placement
within panels. The motor starters will be controlled by the gateways via the chosen fieldbus (DeviceNet, PROFIBUS-DP, or
CANopen).
How to order a motor starter
PKZM0-1
+
PKZM0-XDM12
+
DILM7-10 (24 VDC)
+
BL20-SWIRE-DIL =
How to implement the motor starters
Each SWIRE slice can manage up to 16 non-reversing motor starters.
Each gateway can support up to 3 SWIRE modules for a total of 48 non-reversing motor starters on a single gateway. Any
reversing motor starter is considered as 2 non-reversing. The motor starters are rated for .06kW to 15kW (0.08hp to 20hp).
By ordering parts of the motor starter separately will allow for fewer parts to be stored within your inventory and will cost
less to repair if just one piece of the motor starter fails. Motor starters are hot-swappable as long as the SWIRE-DIL module
stays connected to the SWIRE system.
Refer to the user manual for details on installing and configuring the BL20 motor starter system.
C49
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Industrial
Automation
BL20
Available Motor Starter Sizes
Motor Rating @ 480 VAC
Rated Operational
Current @ 480 VAC
Rated Uninterrupted
Current @ 480 VAC
Classification Type
0.08
0.21
0.25
2
Part Number
kW
hp
PKZM0-0.25
0.06
PKZM0-0.4
0.09
0.12
0.31
0.4
2
PKZM0-0.63
0.18
0.24
0.6
0.63
2
PKZM0-1
0.25
0.33
0.8
1
2
PKZM0-1.6
0.55
0.74
1.5
1.6
2
PKZM0-2.5
0.75
1
1.9
2.5
1
PKZM0-4
1.5
2
3.6
4
1
PKZM0-6.3
2.2
2.95
5
6.3
1
PKZM0-10
3
4
6.6
10
1
PKZM0-10*
4
5.4
8.5
10
1
PKZM0-12
5.5
7.38
11.3
12
1
PKZM0-16
7.5
10
15.2
16
1
PKZM0-25
11
15
21.7
25
1
PKZM0-32
15
20
29.3
32
1
*Can be achieved by using DILM9-10(24VDC) instead of the DILM7-10(24VDC)
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
C50
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
TURCK
Modular Industrial I/O System
Non-Reversing Part Numbers
hp
Motor Contactor Part Number
0.08
PKZM0-0.25
0.12
PKZM0-0.4
0.24
PKZM0-0.63
0.33
PKZM0-1
0.74
PKZM0-1.6
1
PKZM0-2.5
2
PKZM0-4
2.95
PKZM0-6.3
Wiring Set Part
Number
Relay Part Number
SWIRE
Communication
DILM7-10(24 VDC)
PKZM0-XDM12
BL20-SWIRE-DIL
4
PKZM0-10
5.4
PKZM0-10*
DILM9-10(24 VDC)
7.38
PKZM0-12
DILM12-10(24 VDC)
10
PKZM0-16
DILM15-10(24 VDC)
15
PKZM0-25
20
PKZM0-32
PKZM0-XDM32
DILM25-10(24 VDC)
DILM32-10(24 VDC)
* To order a motor starter with the rated hp, order one of each part number that appears to the right.
C51
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Industrial
Automation
BL20
Reversing Part Numbers
hp
Part Number
0.08
PKZM0-0.25
0.12
PKZM0-0.4
0.24
PKZM0-0.63
0.33
PKZM0-1
0.74
PKZM0-1.6
1
PKZM0-2.5
2
PKZM0-4
2.95
PKZM0-6.3
Wiring Set
Number
Relay Part Number
Relay Part Number
DILM7-10(24 VDC)
DILM7-10(24 VDC)
SWIRE
Communication
SWIRE
Communication
Mechanical
Interlock
BL20-SWIRE-DIL
BL20-SWIRE-DIL
DILM12-XMV
PKZM0-XRM12
4
PKZM0-10
5.4
PKZM0-10*
DILM9-10(24 VDC)
DILM9-10(24 VDC)
7.38
PKZM0-12
DILM12-10(24 VDC)
DILM12-10(24 VDC)
10
PKZM0-16
DILM15-10(24 VDC)
DILM15-10(24 VDC)
15
PKZM0-25
DILM25-10(24 VDC)
DILM25-10(24 VDC)
20
PKZM0-32
DILM32-10(24 VDC)
DILM32-10(24 VDC)
PKZM0-XRM32
* To order a motor starter with the rated hp, order one of each part number that appears to the right.
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
C52
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
TURCK
Modular Industrial I/O System
SWIRE Economy
Communication Module
• Modular Motor Starter Control
• IP 20 Protection
• Fieldbus Independant
Configuration
• Base and Electronics in One Part
Electrical
• Operating Current:
≤60 mA from VMB
<3 A from VIO
Mechanical
• Operating Temperature: 0 to +55°C (+32 to +131°F)
• Protection: IP 20
Diagnostics (Logical)
• Diagnostic information available through the fieldbus gateway
Diagnostics (Physical)
• LEDs for status and I/O diagnostics
Supported Gateways
BL20-E-1SWIRE
C53
• BL20-GW-DPV1
• BL20-GWBR-CANopen
• BL20-GWBR-DNET
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
X
X
I/O
Ma
p
Wi
reDe Break
tec
tion
3A
Ind
ivi
Dia dual
gno
stic
s
1
BL20-E-1SWIRE
Gro
up
Dia
gno
stic
s
nt
Cu
rre
Part Number
Pin
out
Inp
ut C
oun
t
Industrial
Automation
1
BL20
Note: This module can only be used with other tension clamp modules unless it is separated using a BL20-PF-24VDC-D and
BL20-P4T-SBBC base.
1
Mating Cordsets:
From SWIRE slice to first motor starter: BL20-SWIRE-CAB-XXX.
End cap for last motor starter; BL20-SWIRE-CAB-000
From one motor starter to an adjacent motor starter: BL20-SWIRE-CAB-008
XXX = Cable length in cm, cable lengths available in 25, 50, 100 and 200 cm.
I/O Data Map 1
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2
n-1
n
n+1
n+2
In
n+3
n+4
n+5
n+6
n+7
n+8
Bit 1
Bit 0
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
(Data from modules to the left)
SWIRE Slave 2
SD2
PKZ-ST2 SI2
SD1
SWIRE Slave 4
SD4
PKZ-ST2 SI2
PKZ-ST2 SI2
SD3
PKZ-ST2 SI2
SD5
PKZ-ST2 SI2
SD7
PKZ-ST2 SI2
SD9
PKZ-ST2 SI2
SD11
PKZ-ST2 SI2
PKZ-ST7
PKZ-ST9
SI7
SI9
PKZ-ST11 SI11
SD13
PKZ-ST13 SI13
SWIRE Slave 15
SD15
PKZ-ST15 SI15
(Data from modules to the right)
SIx: Motor Starter is On
PKZ-STx: Motor Starter is OK
SDx:Slave Diagnostics Available
n+2
SI5
SWIRE Slave 13
SWIRE Slave 16
SD16
PKZ-ST5
SWIRE Slave 11
SWIRE Slave 14
SD14
n+1
SI3
SWIRE Slave 9
SWIRE Slave 12
SD12
PKZ-ST3
SWIRE Slave 7
SWIRE Slave 10
SD10
n
SI1
SWIRE Slave 5
SWIRE Slave 8
SD8
PKZ-ST1
SWIRE Slave 3
SWIRE Slave 6
SD6
n-1
SWIRE Slave 1
OUT
n+3
n+4
n+5
n+6
n+7
n+8
(Data from modules to the left)
SWIRE Slave 2
SWIRE Slave 1
SO2
SWIRE Slave 4
SO1
SWIRE Slave 3
SO4
SWIRE Slave 6
SO3
SWIRE Slave 5
SO6
SWIRE Slave 8
SO5
SWIRE Slave 7
SO8
SWIRE Slave 10
SO7
SWIRE Slave 9
SO10
SWIRE Slave 12
SO9
SWIRE Slave 11
SO12
SWIRE Slave 14
SO11
SWIRE Slave 13
SO14
SWIRE Slave 16
SO13
SWIRE Slave 15
SO16
SO15
(Data from modules to the right)
SOx: Turn on Motor Starter
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
C54
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
TURCK
Modular Industrial I/O System
Motor Overload Contactor
• Protects Motor from Current Overload
Housing
Part Number
PKZM0-*
Application
•
•
Available in multiple amperages
See table on page C50 for Specs.
Motor Starter Wiring Set
• Wires Motor Overload Contactor to Relay Module
Housing
Part Number
PKZM0-X*M*2
C55
Application
•
•
Different styles for different amperages
See tables on C51 & C52 for correct part numbers
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Industrial
Automation
Relay Module
• Controls whether or not Power is Supplied to Connected Motor
Part Number
Application
BL20
Housing
DILM*
•
•
•
•
Available in different styles for different amperages
See pages C51 & C52 for correct part numbers
"10" in part number refers to normally open contact
"01" in part number refers to normally closed contact
SWIRE Communication
• Controls SWIRE Communication and Activates the Motor Starter
Housing
Part Number
BL20-SWIRE-DIL
Application
•
•
Use with all DILM* modules
Control motor starter through SWIRE network
Trip Indication
• Provide Feedback Status of Motor Starter because of Overcurrent or
Short Circuit
Housing
Part Number
NHI-E-10L-PL20
Application
•
Monitor motor starter status
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
C56
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
TURCK
Modular Industrial I/O System
Bus Commoning Bars
• Easily Connect Multiple Motor Starters without the need for Separate
Wiring
Housing
Part Number
BK25/3-PKZ0
B3.0/2-PKZ0*
B3.0/4-PKZ0*
B3.0/5-PKZ0*
Application
•
BK25 is used to land 3 phase wires to beginning of the
bus
•
B3.0/x; x refers to the number of motor starters can be
connected to the bar
•
Max 63A can be carried through a bus bar
* If bussing a reverse motor starter, a cover may be necessary for finger safe needs. Order a cap with p/n H-B3-PKZ0.
Power Feed Module
• Safety Zone Separation
Housing
Part Number
BL20-SWIRE-PF
C57
Application
•
Separate motor starter sets into separate safety zones
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Industrial
Automation
Base Modules for Slice I/O
Housing
Description
BL20-S3T-SBB
Tension Clamp Connection
BL20-S3S-SBB
Screw Terminal Connection
Three Terminal Block with
C-Connection
BL20-S3T-SBC
Tension Clamp Connection
BL20-S3S-SBC
Screw Terminal Connection
Four Terminals
BL20-S4T-SBBS
Tension Clamp Connection
BL20-S4S-SBBS
Screw Terminal Connection
BL20-S4T-SBBS-CJ
Tension Clamp Connection
BL20-S4S-SBBS-CJ
Screw Terminal Connection
BL20
Three Terminal Block
Part Number
Four Terminals with Cold Junction
Compensation for Thermocouples
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
C58
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
TURCK
Modular Industrial I/O System
Base Modules for Slice I/O
Housing
Part Number
Four Terminals with C-Connection
Description
BL20-S4T-SBBC
Tension Clamp Connection
BL20-S4S-SBBC
Screw Terminal Connection
Four Terminals with C-Connection,
Dual Signal
BL20-S4T-SBCS
Tension Clamp Connection
BL20-S4S-SBCS
Screw Terminal Connection
Six Terminals
BL20-S6T-SBBSBB
Tension Clamp Connection
BL20-S6S-SBBSBB
Screw Terminal Connection
BL20-S6T-SBCSBC
Tension Clamp Connection
BL20-S6S-SBCSBC
Screw Terminal Connection
Six Terminals with C-Connection
C59
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Industrial
Automation
Base Modules for Block I/O
Housing
Description
BL20-B3T-SBB
Tension Clamp Connection
BL20-B3S-SBB
Screw Terminal Connection
Three Terminal Block with
C-Connection
BL20-B3T-SBC
Tension Clamp Connection
BL20-B3S-SBC
Screw Terminal Connection
Four Terminal Block with
C-Connections
BL20-B4T-SBBC
Tension Clamp Connection
BL20-B4S-SBBC
Screw Terminal Connection
Six Terminal Block
BL20-B6T-SBBSBB
Tension Clamp Connection
BL20-B6S-SBBSBB
Screw Terminal Connection
BL20
Three Terminal Block
Part Number
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
C60
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
TURCK
Modular Industrial I/O System
Base Modules for Block I/O
Housing
Part Number
Six Terminal Block with
C-Connection
C61
Description
B6T-SBCSBC
Tension Clamp Connection
B6S-SBCSBC
Screw Terminal Connection
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Industrial
Automation
Base Modules for Power Input
Housing
Description
BL20-P3T-SBB
Tension Clamp Connection
BL20-P3S-SBB
Screw Terminal Connection
Three Terminal Power Base with
Gateway Feed
BL20-P3T-SBB-B
Tension Clamp Connection
BL20-P3S-SBB-B
Screw Terminal Connection
Four Terminal Power Base with
C-Connection
BL20-P4T-SBBC
Tension Clamp Connection
BL20-P4S-SBBC
Screw Terminal Connection
Four Terminal Power Base with
C-Connection and Gateway Feed
BL20-P4T-SBBC-B
Tension Clamp Connection
BL20-P4S-SBBC-B
Screw Terminal Connection
BL20
Three Terminal Power Base
Part Number
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
C62
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
TURCK
Modular Industrial I/O System
Housing
Part Number
Description
Markers
Used for color coding terminals on
BL20 base modules
XN-ANBZ-WS
(10/PKG)
XN-ANBZ-GN/GE/BED (10/PKG)
XN-ANBZ-RT/BL-BED (10/PKG)
XN-ANBZ-BR
(10/PKG)
XN-ANBZ-SW
(10/PKG)
XN-ANBZ-GN
(10/PKG)
XN-ANBZ-RT
(10/PKG)
XN-ANBZ-BL
(10/PKG)
White
Green/Yellow
Red/Blue
Brown
Black
Green
Red
Blue
Jumpers
For use with BL20 relay modules
XN-QV/8
XN-QV/7
XN-QV/6
XN-QV/5
XN-QV/4
XN-QV/3
XN-QV/2
XN-QV/1
(10/PKG)
(10/PKG)
(10/PKG)
(10/PKG)
(10/PKG)
(10/PKG)
(10/PKG)
(10/PKG)
8 pair
7 pair
6 pair
5 pair
4 pair
3 pair
2 pair
1 pair
Coding Blocks
For keying electronic modules to
base modules
XN-KO/17
XN-KO/16
XN-KO/14
XN-KO/13
XN-KO/12
(10/PKG)
(10/PKG)
(10/PKG)
(10/PKG)
(10/PKG)
XN-KO/11
XN-KO/10
XN-KO/9
XN-KO/8
XN-KO/6
XN-KO/2
(10/PKG)
(10/PKG)
(10/PKG)
(10/PKG)
(10/PKG)
(10/PKG)
BL20-PF-120/230VAC-D
BL20-PF-24VDC-D
BL20-2AO-U(-10/0...+10V)
BL20-1AO-I(0/4...20MA)
RTD and TC temperature modules,
BL20-1AI-U(-10/0...+10V)
BL20-1AI-I(0/4...20MA)
BL20-2DO-R-CO
BL20-2DO-R-NC
BL20-2DO-R-NO
BL20-*DO-24VDC*
BL20-*DI-24VDC*
C63
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Industrial
Automation
Housing
Part Number
Labels
FW5/151-200
FW5/101-150
FW5/51-100
FW5/1-50
(10 SETS/PKG)
(10 SETS/PKG)
(10 SETS/PKG)
(10 SETS/PKG)
End Bracket
XN-WEW-35/2-SW
End Plate
XN-ABPL
Shield Connection - For use with analog modules
XN-KLBU/S
XN-KLBU/T
Labels - For labeling electronic modules. DIN A5 sheets
BL20-LABEL/BLOCK (5 SHEETS/PKG)
BL20-LABEL/SCHEIBE (5 SHEETS/PKG)
Tension Clamp Tool - For ease of operating tension clamp
connections
ZBW5-2
Ferrite Ring - For damping high frequency inteference on data
and supply lines
PS416-ZBX-405
Shield Connection - For use with direct wiring gateways
SCH-1-WINBLOC (1/PKG)
Programming Cable - For connecting the BL20/BL67 system to
the I/O Assistant software
XN-PS2-CABLE
Description
Numbered 151-200
Numbered 101-150
Numbered 51-100
Numbered 1-50
BL20
(1/PKG)
(10/PKG)
(10/PKG)
Screw terminal
Tension clamp
For block modules
For slice modules
(2/PKG)
TURCK Inc. 3000 Campus Drive Minneapolis, MN 55441 Application Support: 1-800-544-7769 Fax: (763) 553-0708
www.turck.com
C64
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Was this manual useful for you? yes no
Thank you for your participation!