H614

H614
Installation Guide
Current Monitoring
TM
TM
H614
Installation Guide
Current Monitoring
H614
TM
Dimensions
Removable Mounting Bracket
0.6"
(16 mm)
1.2"
(31 mm)
0.7"
(18 mm)
2.1"
(54 mm)
Split-Core Current Switch, Auto Calibrating,
0.5"
(13 mm)
2.5" *
(64 mm)
For VFD Applications, 12 to 115 Hz
Product Overview
2.1"
(54 mm)
The H614 is a current-sensitive switching device designed for use with VFD systems. It is equipped with an auto
calibration feature that allows the device to distinguish between a reduced amp draw due to normal changes in
frequency and an abnormal drop due to belt loss or other mechanical failures.
RoHS
Compliant
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
•
•
•
•
•
Follow safe electrical work practices. See NFPA 70E in the USA, or applicable local codes.
This equipment must only be installed and serviced by qualified electrical personnel.
Read, understand and follow the instructions before installing this product.
Turn off all power supplying equipment before working on or inside the equipment.
Use a properly rated voltage sensing device to confirm power is off.
DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION
• Only install this product on insulated conductors.
Failure to follow these instructions will result in death or serious injury.
A qualified person is one who has skills and knowledge related to the construction and
operation of this electrical equipment and the installation, and has received safety
training to recognize and avoid the hazards involved.
NEC2011 Article 100
No responsibility is assumed by Veris Industries for any consequences arising out of the
use of this material.
NOTICE
•
•
•
•
This product is not intended for life or safety applications.
Do not install this product in hazardous or classified locations.
The installer is responsible for conformance to all applicable codes.
Mount this product inside a suitable fire and electrical enclosure.
The H614 is designed for HVAC fan and blower systems, as well as some pumping systems involving consistent
viscosity liquids. If an H614 is installed on one phase of the VFD, it detects changes in that phase that result from
the VFD compensating for changes elsewhere in the system. Alternatively, for increased sensitivity, H614s can be
used on all three phases for immediate detection of amperage changes anywhere in the system.
A change from the normal amperage and frequency profile in the monitored conductor will cause the resistance of
the FET status output to change state, similar to the action of a mechanical switch. The status output is suitable for
connection to building controllers or other appropriate data acquisition equipment operating at up to 30 volts. The
H614 requires no external power supply to generate its output.
0.4” x 0.2”
(10 mm x 5 mm)
Slot (2x)
Installation
1.0" *
(26 mm)
2.9"
(74 mm)
3.5"
(89 mm)
1. Establish normal operating conditions for the VFD (clean filter, normal load, etc.).
2. Disconnect and lock out power to the VFD, the enclosure, and the conductor to be monitored.
3. Choose a location for the sensor. The monitored conductor must pass through the center window, and the sensor must be at
least ½” from any uninsulated conductors. Mount the sensor on the load side output conductor of the Variable Frequency Drive.
Do not install on VFD input power conductors. If using a bypass system, place the H614 between the VFD and the bypass device.
Performance of the H614 can be optimized through an optional step. When the H614 is first powered and is in Learn
Mode, manually cycle through each 5 Hz frequency band, allowing the VFD to remain at each band for 15 seconds.
4. Install the mounting bracket in the enclosure using the included screws.
5. Wire the connections between the sensor and the
controller.
Specifications
Sensor Power
Amperage Range
Status Output
Response Time
Learn Time
Frequency
Temperature Range
Humidity Range
Alarm Limits
Induced from monitored current
1.5 to 150A Continuous*
N.O. [email protected]/DC
12 to 115 Hz
-15° to 60°C (5° to 140°F)
±20% of learned current in every 5 Hz freq. band
1 sec. nominal **
30VAC/DC, 1A
Insulation Class
600VAC (UL); 300VAC (CE)
Terminal Block Torque
Agency Approvals
Note: If the VFD current does not change during
the Learn mode period, the sensor will not learn
normal conditions. The LED will blink (green,
5 times per second) to indicate the sensor is in
Status Only mode, monitoring the circuit for on/
off status.
<30 sec (nominal)
Contact Ratings
Terminal Block Wire Size
9. 15 seconds after the VFD frequency ramping is
complete, the sensor self-calibration is finished.
The LED will blink (green only).
10-90% RH non-condensing
Alarm-to-Normal Status Output Delay
DI
IES 23
USTR 972 56
INDOregon 354-85
VERIStland, 1-800®
8. As the VFD frequency ramps up, the sensor enters
Learn mode. The LED will blink (alternating
red-green).
15 seconds after frequency ramping stablizes
5 sec. max.
CONTROL
VFD
7. Restore power to the VFD and the conductor.
1 second
Normal-to-Alarm Status Output Delay
Off Delay
6. Snap the sensor over the conductor to be
monitored. Snap the unit with the bracket latched
securely to ensure proper operation.
24 to 14 AWG (0.2 to 2.1 mm2)
Por
14
e 6
key
Haw
NOTE: The H614 is not intended for
use in staged pump or variable inlet
vane applications.
BYPASS DEVICE
(if used)
Fan or Pump
NOTE: (Optional) For phase loss
detection, use H614 devices on
all three phases of the VFD (see
Operation section for details).
Motor
3.5 to 4.4 in-lbs (0.4 to 0.5 N-m)
UL 508, CE: EN61010-1, Installation Category III, pollution
degree 2
* If the current is above 1.5 A, but neither LED is illuminated, the H614 is considered to be in on/off status mode.
** If the H614 experiences a momentary loss of power, the Alarm-to-Normal output delay may exceed 1 sec.
Specification Note: For CE compliance, conductor shall be insulated according to IEC 61010‑1:2001.
The product design provides for basic insulation only. Use wire with minimum 75°C rated insulation. Do not use
the LED status indicators as evidence of applied voltage.
This sensor detects abnormal operation by looking for sudden changes in current across the entire frequency
range. In Learn mode, the sensor calculates a margin 20% above and 20% below the learned frequency curve.
An abnormal condition in the circuit is one that falls outside this margin.
Z206036-0B
Page 1 of 4
©2014 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Z206036-0B
Page 2 of 4
©2014 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide
Current Monitoring
H614
Notes
TM
Installation Guide
Current Monitoring
H614
Memory Reset
For load currents less than sensor minimum rating:
Wrap the monitored conductor through the center window and around the sensor body to produce multiple turns. This increases
the current measured by the transducer. Program the controller to account for the extra turns (e.g., if four turns pass through the
sensor (as shown) divide the normal reading by 4).
< 1.5 A (Sensor Min.)
1. Establish normal operating conditions for the monitored conductor (e.g. clean air filters, close duct access doors).
Rated Max. Amps ÷ Number of Turns = Max. monitored Amps
e.g. : 100A ÷ 4 Turns = 25 Amps max. in monitored conductor
2. The reset button has two positions, in and out. Push the button until there is a noticable click to change the position. This
causes a change of state, which triggers the reset function. The nonvolatile memory is erased and the H614 enters the learning
mode (LEDs blink red/green) to learn the new amperage profile of the monitored conductor.
• Failure to follow these instructions can result in overheating
and permanent equipment damage.
Note: The reset function can be performed even if the H614 is not installed on a conductor. Pushing the button
(changing the state) will clear the nonvolatile memory at the next power-up.
Status LEDs
STATUS
Status LEDs
(left LED = Green; right LED = Red)
Memory Reset Button
(can be used whether unit is powered or unpowered)
Sensor Mode
On/Off Status only
Note: For normal operation, this button can be in either in or out position.
RESET
Learning Mode (first 15 sec of operation after frequency stabilizes)
Page 3 of 4
The sensor is reinstalled on a different motor.
The motor is re-sheaved.
The system is air balanced or air duct restrictions change
The motor load changes significantly.
To reset the H614:
RISK OF EQUIPMENT DAMAGE
• Derate the product’s maximum current for the number of turns
through the sensing window using the following formula.
Z206036-0B
During setup, the H614 automatically determines the normal amperage and frequency profile and stores it in nonvolatile
memory. The H614 requires a memory reset to clear the nonvolatile memory if any of the following conditions occur:
•
•
•
•
CAUTION
4x
0.5A
TM
Status LED Blink Pattern
Alternating Red/Green (1 per sec.)
Learn mode incomplete. VFD system does not meet
abnormal condition detection criteria
Green blink (5 times per sec. after 15 sec of stable
frequency)
Current is not adequate for the device to detect
abnormal conditions
No LED when status output is closed.
Note: if status output is open and no LEDs are illuminated,
see the Troubleshooting section.
Status OK
Green blink (1 per sec.)
Alarm
Red blink (1 per sec.)
©2014 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Troubleshooting
Z206036-0B
Page 4 of 4
Problem
Solution
Status output open with
current above 1.5 A,
with no alarm condition
• Check for amperage in monitored conductor (>1.5 A).
• Check that amperage in the monitored conductor does not exceed sensor max (150 A).
• Ensure that no more than 30 VAC/DC or 1.0 A has passed through the contact. Voltages or currents above these
levels will damage the unit.
• Ensure that sensor core mating surfaces are clean and that the core clamp is completely closed.
• Ensure that the sensor is operating within specified temperature range.
• Ensure that the sensor has completed Learn mode. If it has not, check circuit parameters and compliance.
• If the conditions listed above are satisfactory, contact Veris Customer Support as listed in the footer of this
document.
Unusual readings on VFD
outputs
Check all internal VFD wiring connections for proper tightness according to the manufacturer instructions.
©2014 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertisement