+Power Modular UPS
O n lin e
U P S
Modular Type
+Power Modular UPS
U P S
• Input / Output
• Maintenance Bypass
• Breakers
LCD Panel
Display
STS Module Includes
Communication Ports
O N L I N E
Power Module
Battery Module
• High efficiency online double conversion technology
+Power is applied online double conversion technology with
high performance over 94.5% at 50% load. It significantly
reduces overall Total Cost of Ownership (TCO).
• Ease of installation and maintenance
Built-in maintenance bypass assures continuous power to critical
loads during UPS maintenance. Besides, to facilitate installation and
maintenance, all panel control and connectors are front accessibility.
• High scalability
• Flexible battery configuration adapts
different applications
DSP control provides an improved solution with high
performance. Integrated with modular design and parallel
technology, +Power simplifies future power expansion.
Battery numbers can be adjusted flexibly. It will adapt
different power demands and shorten system downtime.
Battery voltage can be set from 32 to 40 pieces per string.
• Unity output power factor
+Power delivers unity output power (kVA=kW) providing the
maximum power capacity to mission critical loads. It satisfies the
requirements of the latest servers and optimizes IT investment
with every penny.
• Modular design lowers MTTR
• Graphic 5.7” LCD design for easy management
Designed for easy management, +Power is equipped with
5.7” graphic LCD screen. Intuitive design enhances display
information identified and advanced configuration.
• N+1 or N+X parallel redundancy for power
guarantee
Modular design is applied in power module, STS module and
battery module. It will simplify maintenance and replacement
with low MTTR (Mean Time To Repair).
Scalable architecture allows you to optimize cost expense to
meet power demands by vertically expanding in a single rack
enclosure from 30KVA to 210KVA and achieve N+1 or N+X
redundancy in the same rack.
• High reliable operation with redundant
power supply in STS
+Power provides 2 power supplies in STS. It will ensure no
shutdown risk for STS.
• Optional 10" touch LCD panel
• User-adjustable charging current
+Power provides maximum 8A or 6A charging current for every
power module and it's user-adjustable based on requirement.
• High overload capability
+Power supports, 110% overload for 60 minutes, 125% for 10
minutes, and 150% for 1 minute.
Standard Series
+Power 30U-90
45 www.voltronicpower.com
Extended Series
+Power 42U-120
+Power 30U-120
+Power 30U-180
+Power 42U-200
+Power 42U-210
O n line
U P S
Modular Type
+Power 3P/3P 400V Modular UPS Selection Guide
+Power 30U-90
+Power 42U-120
+Power 30U-120
+Power 30U-180
+Power 42U-200
+Power 42U-210
200 KW
210 KW
3-phase in / 3-phase out
CABINET CAPACITY*
90 KW
BATTERY TYPE
120 KW
120 KW or 80 KW
180 KW or 120 KW
Built-in Battery
ONE POWER MODULE CAPACITY
External Battery
20KW
30KVA / 30KW
MAX. POWER MODULE NO.
3
30KVA / 30KW
4
30KVA / 30KW or 20KVA / 20KW
4
6
10
8
MAX. BATTERY SET NO.**
3
5
-
-
-
-
6A
8A
U P S
MODEL
PHASE
INPUT
3 x 380VAC/400VAC/415VAC (3Ph+N)
Voltage Range
O N L I N E
Nominal Voltage
305 ~ 478 VAC at 100% load; 208 ~ 304VAC at <70% load
Nominal Frequency
50/60Hz (Auto Sensing)
Frequency Range
40Hz ~70Hz
Power Factor
> 0.99 @ 100% Load , >0.98 @ 50% Load
Harmonic Distortion (THDi)
< 3% @ 100% load
OUTPUT
Nominal Voltage
3 x 380VAC/400VAC/415VAC (3Ph+N)
Voltage Regulation (Steady state)
≦± 1% Typical (balanced load) ; ≦ ± 2% Typical (unbalanced load)
Nominal Frequency
50/60Hz
Frequency Range (Synchronized)
46Hz ~ 54Hz or 56Hz ~ 64Hz
Overload Capability
1 hour for 110%, 10 mins for 125%,; 1 min for 150%, 200ms for >150%
Harmonic Distortion
≦1.5% THD (Linear Load) ; ≦ 4% THD (Non-linear Load)
Efficiency
Up to 94.5%
BATTERY / CHARGER
Nominal Voltage
+/- 216V (12V x 36 pcs)
Maximum Voltage
+/- 240V (12V x 40 pcs)
Minimum Voltage
+/- 192V (12V x 32 pcs)
Float Charging Voltage
2.25V / Cell
Boost Charging Voltage
2.35V / Cell
Temperature Compensation
Yes
Maximum Charging Current
(Per Power Module)
8A for 30KW power module
6A for 20KW power module
8A
PHYSICAL
Cabinet Dimension (D x W x H) mm
1100 x 600 x 1475 [30U] 1100 x 600 x 2010 [42U] 1100 x 600 x 1475 [30U] 1100 x 600 x 1475 [30U]
Net Weight (Kg)
675
932
335 or 333
437.5 or 434.5
1100 x 600 x 2010 [42U]
625
549
ENVIRONMENT
0 ~ 40°C
Operation Temperature
Relative Humidity
0 ~ 95% non-condensing
Altitude
<1000m for Nominal power
IP Class
IP 20
MANAGEMENT
Supports Windows2 2000/2003/XP/Vista/2008, Windows2 7/8, Linux and MAC
Smart RS-232 / USB
Optional SNMP
Power management from SNMP manager and web browser
STANDARDS
Safety
IEC/EN 60950-1; IEC/EN 62040-1
EMC
IEC/EN 62040-2 Category C3
*When temperature is above 30℃, the output power factor will be de-rated, 0.9 at 31℃~35℃ and 0.8 at 36℃~40℃.
** One battery module contains 10 pcs of 12V/7Ah or 12/9Ah sealed lead acid batteries in one tray. One complete battery set contains 4 battery modules.
***If the UPS is installed or used in a place where the altitude is above than 1000m, the output power must be derated one percent per 100m.
Product specifications are subject to change without further notice
Model
Description
Dimension DxWxH(mm)
Weight (kg)
PM-20HV
3P/3P 20KVA / 20KW power module
650 x 440 x 132(3U)
34
PM-30HV
3P/3P 30KVA / 30KW power module
650 x 440 x 132(3U)
34.5
10 pcs of 12V 9Ah batteries
735 x 107 x 155
26
Battery Module
Advancing Power
46
O n lin e
U P S
Modular Type
+Power 3P/3P 208V Modular UPS Selection Guide
MODEL
+Power 30U-60
+Power 42U-80
+Power 30U-80
PHASE
CABINET CAPACITY*
U P S
+Power 30U-120
+Power 42U-140
108 KW
126 KW
3-phase in / 3-phase out
54 KW
BATTERY TYPE
72 KW
72 KW
Built-in Battery
External Battery
ONE POWER MODULE CAPACITY
20KVA/18KW
MAX. POWER MODULE NO.
3
4
4
6
7+1
MAX. BATTERY SET NO.**
3
4
-
-
-
O N L I N E
INPUT
Nominal Voltage
3 x 208 VAC (3Ph+N)
Voltage Range
156 ~ 253 VAC at 100% load; 121 ~ 155VAC at <70% load
Nominal Frequency
50/60Hz (Auto sensing)
Frequency Range
40Hz ~70Hz
Power Factor
> 0.99 at 100% load, >0.98 at 50% load
Harmonic Distortion (THDi)
< 3% @ 100% load
OUTPUT
Nominal Voltage
3 x 208V/220VAC (3Ph+N)
Voltage Regulation (Steady state)
≦± 1% Typical (balanced load) ; ≦ ± 2% Typical (unbalanced load)
Voltage Regulation (Transient)
≦± 5% Typical
Nominal Frequency
50/60Hz
Frequency Range (Synchronized)
46Hz ~ 54Hz or 56Hz ~ 64Hz
Overload Capability
1 hour for 110%, 10 mins for 125%,; 1 min for 150%, 200ms for >150%
Harmonic Distortion
≦1.5% THD (Linear Load) ; ≦ 4% THD (Non-linear Load)
Efficiency
Up to 92.5% at over 50% load
BATTERY / CHARGER
Nominal Voltage
+/- 120V (12V x 20 pcs)
Float Charging Voltage
2.25V / Cell
Boost Charging Voltage
2.35V / Cell
Temperature Compensation
Yes
Maximum Charging Current
8A for each power module (User-djustable)
PHYSICAL
Cabinet Dimension (D x W x H) mm
1100 x 600 x 1475 [30U]
1100 x 600 x 2010 [42U]
1100 x 600 x 1475 [30U]
1100 x 600 x 1475 [30U]
1100 x 600 x 2010 [42U]
670.5
926
329
428.5
7 Power Modules: 504
8 Power Modules: 537
Net Weight (kg)
ENVIRONMENT
0 ~ 40°C
Operation Temperature
Relative Humidity
0 ~ 95% non-condensing
Altitude
<1000m for Nominal power
IP Class
IP 20
MANAGEMENT
Smart RS-232 / USB
Supports Windows2 2000/2003/XP/Vista/2008, Windows2 7/8, Linux and MAC
Optional SNMP
Power management from SNMP manager and web browser
STANDARDS
Safety
UL1778, CSA C22.2 No. 107.3-05
EMC
FCC Part 15,Subpart B Class A
*When temperature is above 30℃, the output power factor will be de-rated, 0.8 at 31℃~35℃ and 0.7 at 36℃~40℃.
** One battery module contains 10 pcs of 12V/7Ah or 12/9Ah sealed lead acid batteries in one tray. One complete battery set contains 4 battery modules.
***If the UPS is installed or used in a placewhere the altitude is above than 1000m, the output power must be derated one percent per 100m.
Product specifications are subject to change without further notice
Model
PM-20LV
Battery Module
47 www.voltronicpower.com
Description
Dimension DxWxH(mm)
Weight (kg)
3P/3P 20KVA / 18KW power module
650 x 440 x 132(3U)
33
10 pcs of 12V 9Ah batteries
735 x 107 x 155
26