Corning EDC-06P-NH manual

Corning EDC-06P-NH manual

advertisement

Assistant Bot

Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.

Manual
Corning EDC-06P-NH manual | Manualzz
Corning Cable Systems
Standard Recommended Procedure (SRP) 003-545
Issue 4, July 2004
Page 1 of 13
Environmental Distribution Center (EDC-06P-NH)
1.2 To purchase any accessories that are sold
separately, contact your Corning Cable Systems
service representative for assistance.
1.3 This document is being reissued to clarify
cable cleaning directions.
NOTE: Read and understand this procedure (as
well as the instructions provided with related
assemblies) before beginning an installation. Make
sure you know how the unit will be mounted and
how the distribution cable and drop cable will be
routed to the unit.
2.
Figure 1
Table of Contents
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
1.
General ........................................................ 1
Description .................................................. 1
Precautions .................................................. 2
Tools and Materials ..................................... 2
Components................................................. 3
Unpacking Stubbed Units ........................... 3
Installing Holes ............................................ 4
Mounting ..................................................... 4
Preparing Cable ........................................... 5
Connector Panels ........................................ 7
Splicing ........................................................ 8
Installing Fan-outs .....................................10
Installing Drop Cable ................................11
Maintenance ..............................................13
Specifications ............................................. 13
General
1.1 This instruction describes recommended
procedure for the installation of the six-panel
Environmental Distribution Center (EDC)
(p/n EDC-06P-NH) manufactured by Corning
Cable Systems.
p/n 003-545
Description
2.1 The EDC that stores and protects fiber
optic connections and splices in an outdoor
environment. The cabinet carries a NEMA 250
Type 4X and Type 13 rating in addition to a
IEC 529 IP66 rating. The unit provides
environmental protection and strain-relief for
one distribution cable and up to six drop cables.
2.2 Connector panels are used to provide
interconnection between the distribution and
drop cables. The EDC accommodates up to six
LANscape® connector panels. Colored icons are
available with different symbols for a quick
visual reference of the data type at each
connector location. Panels and connector panel
icons are ordered separately.
2.3 The unit accommodates six Type 2S or
three Type 4S splice trays that protect
mechanical or fusion splices. Splice trays are
ordered separately.
2.4 The unit can be field connectorized using
buffer tube fan-out (BTF) kits, which are
ordered separately.
2.5 The EDC comes with brackets to mount
the unit to a wall or a standard utility pole. The
unit may be rack-mounted with an optional
rack-mount kit.
Page 2
SRP-003-545 • Issue 4 • July 2004
3.3
2.6 The unit may be padlocked with a user
supplied padlock after installation of the
provided quick-release latch kit.
WARNING: Cleaved glass fibers are very
sharp and can pierce the skin easily. Do not let cut
pieces of fiber stick to your clothing or drop in the work
area where they can cause injury later. Use tweezers to
pick up cut or broken pieces of the glass fibers and place
them on a loop of tape kept for that purpose alone.
Good housekeeping is very important.
2.7 Factory stubbed units are available with a
specific length of preconnectorized cable
installed and strain-relieved in the unit.
3.
Precautions
3.1
Laser Handling Precautions
3.4
WARNING: Never look directly into the
end of a fiber that may be carrying laser light.
Laser light may be invisible and can damage your eyes.
Viewing it directly does not cause pain. The iris of the
eye will not close involuntarily as when viewing a
bright light. Consequently, serious damage to the
retina of the eye is possible. Should accidental eye
exposure to laser light be suspected, arrange for an eye
examination immediately.
WARNING: DO NOT use magnifiers in the
presence of laser radiation. Diffused laser light can
cause eye damage if focused with optical instruments.
Should accidental eye exposure be suspected, arrange
for an eye exam immediately.
3.2
CAUTION: The wearing of safety gloves to
protect hands from accidental injury is strongly
recommended when using sharp instruments.
CAUTION: Isopropyl alcohol is flammable
with a flashpoint at 50°F. It can cause irritation to
eyes on contact. In case of eye contact, flush eyes with
water for at least 15 minutes. Inhaling fumes may
induce mild narcosis. In case of ingestion, consult a
physician.
Cable Handling Precautions
NOTE: Fiber optic cable is sensitive to excessive
pulling, bending and crushing forces. Consult the cable
specification sheet for the cable you are installing. Do
not bend the cable more sharply than the
minimum recommended bend radius. Do not
apply more pulling force to the cable than
specified. Do not crush the cable or allow it to
kink. Doing so may cause damage that can alter the
transmission characteristics of the cable — the cable
may have to be replaced.
3.5
Installer Precautions
WARNING: Do not install this unit or work
with telephone wiring during a lightning storm.
Telephone lines can carry high voltages from lightning
causing electrical shock resulting in severe injury or
death.
Safety Precautions
CAUTION: The wearing of safety glasses to
protect the eyes from accidental injury is strongly
recommended when handling chemicals and cutting
fiber. Pieces of glass fiber are very sharp and can
damage the cornea easily.
Glass Fiber Precautions
4.
Tools and Materials
In addition to the usual complement of
installation tools, the following are required for
this installation:
•
Slotted and Phillips-head screwdrivers
•
Tape measure
•
Pliers
•
8-mm (5/16-inch) open or box wrench
•
Hole saw
•
Two cable entry port fittings and sealant (if
required)
Mounting hardware is not provided. The type
of hardware used is dependant on the mounting
location; wall anchors may be required for
adequate support on sheetrock walls.
Page 3
SRP-003-545 • Issue 4 • July 2004
5.
Components
5.1
Components are illustrated in Figure 2.
•
The base plate is the dark metal part inside
the enclosure to which the components are
attached. It is secured by one screw in each
corner.
•
There are top and bottom mounting
brackets.
•
The splice tray holder is removed for
clarity.
•
The fan-out bracket is underneath the splice
tray mounting location.
Ground Kit Location
(When Required)
5.2 An installation kit is provided that
includes cable ties, central member strain-relief
hardware, a sheath retention kit and a quickrelease latch kit.
6.
Unpacking Stubbed Units
Follow the directions in Standard
Recommended Procedure 003-310, provided
with the shipping container, to remove the
stubbed unit from its packaging.
Mounting Bracket
Radius Control Guides
Record
Label
Splice Tray
Mounting
Location
Sheath
Central MemRetention Drop Cable
ber
Strain-Relief
Strain-Relief Connector Bracket
Bracket
Panel
Bracket
Bracket
Splice Tray Holder
Figure 2
Page 4
7.
SRP-003-545 • Issue 4 • July 2004
Installing Holes
IMPORTANT: Remove the base plate from the
housing before cutting any holes.
7.1 Determine the size hole needed based on
the fitting being used. Based on dimensions in
Figure 3, measure and mark the location of the
hole centers on the bottom of the unit. The 2inch conduit fitting holes are represented by the
larger circles and the 1-inch conduit holes by
the smaller circles.
b) Drive 1/4-inch screws or wall anchors
through the stabilizer bracket and into the
mounting surface. Do not install a screw in the
bottom hole of the stabilizer bracket at this time.
Hang the unit over the
mounted stabilizer bracket.
7.2 Cut holes as required for your coupling
fitting. Follow local safety practices.
7.3 Install the fittings (purchased separately).
Fitting kits are dependant on the type of fitting
desired for your application.
7.4
Reinstall the base plate.
Figure 5
6 cm
(2.375 in.)
3.2 cm
(1.25 in.)
18 cm (7 in.)
3.5 cm
(1.375 in.)
4.4 cm
(1.75 in.)
6.7 cm
(2.625 in.)
Figure 3
8.
Mounting
NOTE: If you will be mounting the EDC without
the stabilizer bracket, remove and discard the
stabilizer bracket. Position the housing as desired
and secure using 1/4-inch screws in the top and
bottom mounting brackets.
Stabilizer Bracket
c) Hang the unit on the stabilizer bracket,
ensuring that the top mounting bracket is
resting between the two tabs on the
stabilizer bracket (Figure 5).
d) Align the elliptical hole in the bottom
mounting bracket and the bottom hole in
the stabilizer bracket and install a 1/4-inch
screw through it and into the mounting
surface.
e) Mounting hardware is not provided.
8.2 When the EDC will be mounted onto a
utility pole:
a) Secure the stabilizer bracket to the pole
using 1/4-inch screws. Do not install a screw
in the bottom hole of the bracket at this time.
b) Hang the EDC on the stabilizer bracket,
ensuring that the top mounting bracket is
resting between the two tabs on the
stabilizer bracket.
c) Line up the elliptical hole in the bottom
mounting bracket with the bottom hole in
the stabilizer bracket and drive a 1/4-inch
screw through the brackets and into the
utility pole.
Figure 4
8.1
Drive a screw through the mounting
bracket and stabilizer bracket and
into the mounting surface.
When wall-mounting is desired,
a) Remove the stabilizer bracket (Figure 4).
d) Mounting hardware is not provided.
8.3 To rack mount the unit, a universal rackmount kit (ordered separately) is required.
Remove the stabilizer bracket and follow
instructions supplied with the rack-mount kit.
Page 5
SRP-003-545 • Issue 4 • July 2004
9.
Preparing Cable
9.1 Route the incoming distribution (feeder)
cable through the fitting on the left at the base
of the unit.
9.2 Perform cable sheath removal steps per
instructions for the type of cable being
installed. Cut the cable to 3 meters (10 feet)
inside the unit.
NOTE: Do not expose the bare fiber until you are
ready to terminate it.
1) Wrap a section of clamp material around
the cable to determine the length needed
for one full wrap.
2) Use side cutters to cut the clamp material
so that it ends up one section shorter than
this length.
3) Place the cut length of clamp material 5 cm
(2 inch) from the end of the cable sheath.
4) Install a hose clamp over it, covering as
many holes as possible. Hand tighten with a
slotted screwdriver or a 5/16-inch driver.
5) Wrap the sheath retention assembly with
vinyl tape. (Shown without vinyl tape for
clarity)
9.3 Install a sheath retention clamp onto the
cable sheath as illustrated in Figure 6. If an
armored cable is used, install the ground clamp
before installing the sheath retention clamp.
9.4 Armored cable (metallic cable sheath)
should be grounded using a ground clamp
(Figure 7).
Cut a slit into opposite sides of the outer sheath
and armor about 5 cm (2 inches). To do this, score
the armor with a cable knife (being careful not
to damage the inner sheath) and split the
sheath by flexing it.
3
2
1
4
2 in.
Position the grounding clamp base plate under
the armor. The stops of the clamp should just
touch the outside of the armor and sheath.
Tap the sheath above the ground clamp base
to set the teeth.
Base Plate
Stop
Position the top plate and lock nut on the
outer sheath over the base plate. Tighten with
a 10 mm (3/8 inch) wrench so that the teeth on
the upper plate are driven into the sheath.
Tighten the assembly with a 10 mm (3/8 inch)
wrench.
Top Plate
Armored cable requires a ground clamp.
Stop
Base Plate
Wrap the grounding connector and split
portion of the sheath with a few wraps of vinyl
Vinyl Tape
tape.
3.0 cm (1.2 in.)
Figure 6
Figure 7
Page 6
SRP-003-545 • Issue 4 • July 2004
9.5 Secure the cable to the sheath retention
bracket using cable ties. Make sure the tabs on
the clamp material are in the recessed section of
the bracket (Figure 8).
Yarn
Buffer Tubes
Figure 8
9.6 When central member strain-relief is
required, the central member bolt must be
installed into the strain-relief bracket as shown
(Figure 9).
NOTE: Smaller diameter central members require
a shim to make sure they are adequately secured in
the central member clamp. Use a central member
clamp shim when necessary (Figure 10).
a) Remove the bracket from the housing.
b) Install the U-shaped washer as shown in
Figure 9.
c) Loosely install the hex nut.
d) Use two nylon nuts to install the bracket
into the housing.
e) Insert the central member of the cable
between the bracket and the U-shaped
washer.
f) Arrange the buffer tubes to ensure clearance
around the central member clamp assembly
and hardware.
g) Tighten the hex nut.
h) Install the two flat washers.
i)
Loosely install the other hex nut.
j)
Wrap the strength member yarn in a
clockwise direction around the bolt and
between the flat washers.
Central
Member
Bracket
Figure 9
Insert the central member into the hole in the shim.
If the central member does not fit in the hole, discard
the shim.
If the central member passes through the hole, the shim
is required to secure the central member.
Position the shim between the U-shaped washer and the
bracket
U-Washer
Shim
Central
Member
Central
Member
Shim
Figure 10
9.7 When cable grounding is necessary, a
hardware ground kit (purchased separately) is
required. Install the ground kit as shown in
Figure 11.
k) Tighten the second hex nut.
l)
Trim off the excess yarn and central
member.
NOTE: The exposed length of the central member
(after strain-relief) is to be less than or equal to 6.5
cm (2 1/2 inches) between the U-shaped washer and
the end of the cable sheath.
Figure 11
Page 7
SRP-003-545 • Issue 4 • July 2004
10. Connector Panels
10.1 LANscape connector panels (Figure 12)
are generally shipped separately with connector
adapters installed.
NOTE: Pigtails are fiber optic cables with
connectors on one end which are installed into
connector panels. The other end is terminated in a
splice tray.
10.3 Remove the splice tray holder from the
housing (Figure 13).
10.4 Install connectors into the appropriate
panels (Figure 14).
Buffer Tubes
Pigtail
Figure 12
10.2 If fibers are not already connectorized,
install connectors onto the fibers using pigtail
splicing or direct connectorization per
manufacturer’s instructions. If installing BTF
kits, proceed to section 12.
Figure 14
Splice
Tray
Holder
Splice
Tray
Holder
Bracket
Figure 13
Page 8
SRP-003-545 • Issue 4 • July 2004
CAUTION: The connector is a delicate device.
Obey the following precautions. Damage to the
surface of the connector will make it unusable:
•
Use a clean tissue soaked in alcohol to
gently clean the connector. Do not press
heavily on it as you clean.
•
Dry the connector prior to installation with
compressed air or a dry tissue.
•
Clean all areas that will contact the
connector adapter.
•
Do not force the connector into the
receptacle. If the connector does not fit
easily into the receptacle, back it out and
reinstall.
•
Install threaded connectors into the adapter
and tighten. Do not OVERTIGHTEN. Do
not allow the connector body (ferrule) to
turn as you screw it into place. This causes
the surfaces to grind against each other.
10.5 Remove the blank connector panels from
the unit (Figure 15). Install the loaded
connector panels into the connector support
bracket (Figure 16).
11. Splicing
11.1 The unterminated ends of pigtails are
spliced to buffered fibers in a splice tray
(Figure 14). Prepare the buffer tubes for
splicing.
a) Route three complete loops of fiber around
the radius guides in a counterclockwise
direction. The radius guides are divided into
three sections. Begin routing from the back
section and work your way forward with
each loop in a different section of the guide.
b) Reinstall the splice tray holder and install
one of the splice trays you will be using.
c) Place ALL the buffer tubes as they will lie
after installation and mark the cable 2 cm
(3/4 inch) from where it will enter the corner
of the splice tray as shown in Figure 17.
(This is where the buffer tube will be
removed.)
d) Refer to the instructions provided with the
splice tray to determine the appropriate
length of fiber required in the tray. Measure
from the first mark toward the end of the
buffer tubes and mark the buffer tubes.
e) Trim the excess buffer tube beyond the
second mark.
10.6 Repeat for all required panels.
Plunger
f) Remove the splice tray and the coiled buffer
tubes.
Pull the plunger fastener
out all the way so that
the fingers collapse.
Housing
Position the fastener into
the mounting holes in
the housing.
g) Remove the buffer tubes to the marked
point (plus the length needed inside the
tray). Strip and clean the fibers according to
the cable manufacturer’s instructions.
Fingers
Push the plunger in to
expand the fingers and
lock the unit to the housing.
To remove the unit, pull the plungers out.
Figure 15
Figure 16
Figure 17
Page 9
SRP-003-545 • Issue 4 • July 2004
11.2 Prepare the pigtail for splicing in the same
manner.
11.3 Work on one splice tray at a time. Bring
both pigtails and buffered fibers to a convenient
splicing area - one pair at a time. Secure these
fibers to the same corner of the splice tray.
11.7 Place the spliced trays into the holder as
shown in Figure 19. The fibers exiting the trays
are positioned around the radius control guide.
Secure the trays to the holder using the
provided hook-and-loop strap.
IMPORTANT: When securing 900 µm fiber to
the splice tray, 1.5 inches of electrical tape around
the sheath as protection for the 900 µm fiber is
recommended. Feed a cable tie through the strainrelief holes in the corner of the splice tray. Carefully
tighten the cable tie around the tape-wrapped
portion of the fibers to secure the fibers to the tray.
DO NOT tighten the cable tie too tightly.
11.4 Splice fibers as described in instructions
for the splicing method you are using.
11.5 As you complete a splice, label the
connector end of the pigtail with its port
identifier. Record information appropriately on
the record label inside the front door
(Figure 18).
11.6 Repeat for all required splice trays.
Figure 19
11.8 Once all splicing is complete, route all
buffer tubes (beginning at the cable sheath
opening) and pigtails (starting at the connector
panels) counterclockwise around the radius
guides (Figure 20).
Figure 18
NOTE: Accurate record keeping is imperative for
an organized installation.
Figure 20
Page 10
SRP-003-545 • Issue 4 • July 2004
a) Place pigtails on the outside of the loops
and the buffer tubes closest to the guides.
b) Make sure the fiber from the connector
boot is not pulled too tightly and the bend
radius is not violated.
c) The first loop should be in the back section
of the radius guides and each successive loop
should be in the section above the previous
loop.
12. Installing Fan-outs
12.1 Fiber optic cable can be installed using
BTF kits (ordered separately).
12.2 Slide the splice tray holder toward the top
of the housing and remove it. Remove the splice
tray holder mounting bracket also (Figure 22).
(The fan-out bracket is underneath it.)
d) At the third loop, reinstall the splice tray
holder and trays (Figure 21).
NOTE: Cable ties can be loosely attached to
organize the coils of buffer tubes and pigtail
assemblies.
Splice
Tray
Holder
Splice
Tray
Holder
Bracket
Figure 22
Figure 21
Page 11
SRP-003-545 • Issue 4 • July 2004
12.3 Route the buffer tubes around the radius
guides three times in a counterclockwise
direction. Mark the location of the fan-out
bracket on the buffer tubes as shown in
Figure 23 to determine the length required.
12.6 Route the connectorized fan-out tubing
around the guides and plug connectors into the
connector panel (Figure 25). Refer to the
previous connector care caution to avoid
damaging the connectors during installation.
12.4 Install fan-out assemblies and connectors
according to the instructions provided with the
BTF kits.
Figure 25
12.7 Label the connector end of the pigtail
with its port identifier. Record information
appropriately on the record label inside the
front door (Figure 18).
IMPORTANT: Accurate record keeping is
imperative for an organized installation.
Figure 23
12.5 Route the buffer tubes around the radius
guides and secure the fan-out assemblies to the
fan-out bracket as shown using a cable tie
(Figure 24).
NOTE: The splice tray holder and its mounting
bracket should be reinstalled to allow future splicing
capabilities.
13. Installing Drop Cable
13.1 The EDC is designed to accept up to six
drop cables. Feed 3 meters (10 feet) of drop
cable through the fitting you installed on the
right at the base of the closure.
1) Route three complete loops of the subunit
around the radius guides (Figure 28).
2) Match the subunits to the corresponding
panels and simulate how they will lie.
3) Mark the length on the subunit and trim the
cable to this length.
13.2 Gently secure cable with no central
members to the bracket using cable ties.
Figure 24
Page 12
SRP-003-545 • Issue 4 • July 2004
13.3 When central member strain-relief is
necessary, remove the drop cable strain-relief
bracket and secure the cable to the bracket
using a cable tie as shown (Figure 26).
Strength-Member Yarn
Central Member
U-Shaped Washer
Figure 27
13.4 Route cable around the guides as shown in
Figure 28 and plug in connectors. Refer to the
connector installation instructions in Section 10
and the fiber precautions in Section 3 to avoid
damaging the cable during installation.
Figure 26
a) Install the 8-32x5/8 screw from the front side
of the strain-relief bracket through the flat
washer and U-shaped washer. Loosely
install the hex nut.
b) From the front side of the strain-relief
bracket, wrap the strength member yarn in a
clockwise direction around the screw and
under the U-shaped washer (Figure 27).
c) Insert the central member of the cable
between the flat washer and the U-shaped
washer (Figure 27).
d) Tighten the hex nut.
e) If the central member is metallic, place the
eye of a ground wire (#6 AWG, purchased
separately in appropriate length from any
electrical supply store) under the U-shaped
washer or under the flat washer.
f) Trim off the excess yarn and central
member.
g) Reinstall the strain-relief bracket.
NOTE: The exposed length of the central member
(after strain-relief) is to be less than or equal to 6.5
cm (2 1/2 inches) between the U-shaped washer and
the end of the cable sheath.
Figure 28
Page 13
SRP-003-545 • Issue 4 • July 2004
14. Maintenance
The unit requires very little maintenance to
make sure fibers and parts remain in good
condition.
Loose Parts: Check nuts, bolts and screws for
looseness and tighten.
Moisture: Check the housing for accumulated
moisture and place moisture absorbent
packets as needed.
Fiber Bends: Check fiber optic cable to make
sure bends do not exceed the minimum bend
radius. Check cable for unnecessary strain.
Check cable entries and exits for crimping
or crushing.
42 cm
(16.5 in.)
Documentation: Check record label to make
sure it is clear and accurate.
15. Specifications
37 cm
(14.5 in.)
The unit weighs 6.9 kg (15.2 lb).
21 cm
(8.3 in.)
Customer Service—US or Canada: 1-800-743-2671
International: +1-828-901-5000
Fax: +1-828-325-5060
Corning Cable Systems LLC, PO Box 489, Hickory, NC 28603-0489 USA
http://www.corning.com/cablesystems
Corning Cable Systems reserves the right to improve, enhance and modify the features and specifications
of Corning Cable Systems’ products without prior notification. Discovering Beyond Imagination is a
trademark of Corning Incorporated. LANscape is a trademark of Corning Cable Systems Brands, Inc. All
other trademarks are the properties of their respective owners. Corning Cable Systems is ISO 9001
certified.
© 1999, 2000, 2004 Corning Cable Systems. All rights reserved. Published in the USA.
p/n 003-545 / July 2004

advertisement

Related manuals

Download PDF

advertisement