Delta DVP-SV DVP28SV11R, DVP28SV11R2, DVP28SV11T, DVP24SV11T2, DVP28SV11S2, DVP28SV11T2 PLC Instruction Sheet

Delta DVP-SV DVP28SV11R, DVP28SV11R2, DVP28SV11T, DVP24SV11T2, DVP28SV11S2, DVP28SV11T2 PLC Instruction Sheet

Below you will find brief information for PLC DVP-SV DVP28SV11R, PLC DVP-SV DVP28SV11R2, PLC DVP-SV DVP28SV11T, PLC DVP-SV DVP24SV11T2, PLC DVP-SV DVP28SV11S2. The DVP-SV/SV2 is a 28-point (16 inputs + 12 outputs)/24-point (10 inputs + 12 outputs + 2 analog input channels) PLC MPU, offering various instructions and with 16k (SV)/30k (SV2) steps program memory, able to connect to all Slim type series extension models, including digital I/O (max. 512 points), analog modules (for A/D, D/A conversion and temperature measurement) and all kinds of high-speed extension modules. 4 groups of high-speed (200 kHz) pulse outputs (and two axes which generate 10 kHz outputs in 24SV2) and 2 two-axis interpolation instructions satisfy all kinds of applications. DVP-SV/SV2 is small in size and easy to install.

advertisement

Assistant Bot

Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.

Delta DVP-SV DVP28SV11R, DVP28SV11R2, DVP28SV11T, DVP24SV11T2, DVP28SV11S2 Instruction Sheet | Manualzz

2014-04-30

5011669007-SV08

…………………………………………………………………

ENGLISH  ……………………………………………………………………

Thank you for choosing Delta DVP-SV

#1

/DVP-SV2

#1

. The SV/SV2 is a 28-point (16 inputs + 12 outputs)/24-point (10 inputs + 12 outputs + 2 analog input channels) PLC

MPU, offering various instructions and with 16k (SV)/30k (SV2) steps program memory, able to connect to all Slim type series extension models, including digital I/O (max. 512 points), analog modules (for A/D, D/A conversion and temperature measurement) and all kinds of high-speed extension modules. 4 groups of high-speed (200 kHz) pulse outputs (and two axes which generate 10 kHz outputs in 24SV2) and 2 two-axis interpolation instructions satisfy all kinds of applications. DVP-SV/SV2 is small in size and easy to install.

Note #1: DVP28SV11R/T is represented by SV, and DVP24SV11T2 and DVP28SV11R2/T2/S2 are represented by SV2.

EN  DVP-SV/SV2 is an OPEN-TYPE device. It should be installed in a control cabinet free of airborne dust, humidity, electric shock and vibration. To prevent non-maintenance staff from operating DVP-SV/SV2, or to prevent an accident from damaging DVP-SV/SV2, the control cabinet in which DVP-SV/SV2 is installed should be equipped with a safeguard. For example, the control cabinet in which DVP-SV/SV2 is installed can be unlocked with a special tool or key.

EN  DO NOT connect AC power to any of I/O terminals, otherwise serious damage may occur. Please check all wiring again before DVP-SV/SV2 is powered up.

After DVP-SV/SV2 is disconnected, Do NOT touch any terminals in a minute.

Make sure that the ground terminal on DVP-SV/SV2 is correctly grounded in order to prevent electromagnetic interference.

FR  DVP-SV/SV2 est un module OUVERT. Il doit être installé que dans une enceinte protectrice (boitier, armoire, etc.) saine, dépourvue de poussière, d’humidité, de vibrations et hors d’atteinte des chocs électriques. La protection doit éviter que les personnes non habilitées à la maintenance puissent accéder à l’appareil (par exemple, une clé ou un outil doivent être nécessaire pour ouvrir a protection). 

FR  Ne pas appliquer la tension secteur sur les bornes d’entrées/Sorties, ou l’appareil

DVP-SV/SV2 pourra être endommagé. Merci de vérifier encore une fois le câblage avant la mise sous tension du DVP-SV/SV2. Lors de la déconnection de l’appareil, ne pas toucher les connecteurs dans la minute suivante. Vérifier que la terre est bien reliée au connecteur de terre afin d’éviter toute interférence

électromagnétique.

Product Profile

1 Left-side module connection port

9 POWER/RUN/BAT.LOW/ERROR indicator

10

Direct fastening hole

3 COM1(RS-232) receiving communication (Rx) indicator

2 Nameplate

14 COM2(RS-485) communication port

(Master/Slave)

4 COM2(RS-485) sending communication (Tx) indicator

5 I/O indicator

6 RUN/STOP switch

7

VR0: M1178 enabled /D1178 corresponding value

8

VR1: M1179 enabled/D1179 corresponding value

16 3PIN removable terminal

(standard component)

15 Power input port

13 DIN rail clip

11 I/O terminal

12 COM1(RS-232) program I/O communication port

[ Figure 1 ]

18

I/O module positioning hole

19

I/O module connection port

20 Mounting slot

(35mm)

17 Power input connection cable (standard component)

- 1 -

21 I/O module fastening clip

[ Figure 2 ]

Electrical Specifications

Model

Item

Power supply voltage

DVP28SV11R DVP28SV11R2 DVP28SV11T

DVP24SV11T2

DVP28SV11T2

DVP28SV11S2

24VDC (-15% ~ 20%) (with counter-connection protection on the polarity of DC input power)

Inrush current Max. 2.2A@24VDC

Fuse capacity

Power consumption

Insulation resistance

2.5A/30VDC, Polyswitch

6W

> 5MΩ (all I/O point-to-ground: 500VDC)

Noise immunity

Grounding

Operation / storage

Agency approvals

Vibration / shock immunity

Weight (g)

ESD (IEC 61131-2, IEC 61000-4-2): 8kV Air Discharge

EFT (IEC 61131-2, IEC 61000-4-4): Power Line: 2kV, Digital I/O: 1kV,

Analog & Communication I/O: 1kV

Damped-Oscillatory Wave: Power Line: 1kV, Digital I/O: 1kV

RS (IEC 61131-2, IEC 61000-4-3): 26MHz ~ 1GHz, 10V/m

The diameter of grounding wire shall not be less than that of the wiring terminal of the power. (When PLCs are in use at the same time, please make sure every PLC is properly grounded.)

Operation: 0ºC ~ 55ºC (temperature); 5 ~ 95% (humidity); pollution degree 2

Storage: -25ºC ~ 70ºC (temperature); 5 ~ 95% (humidity)

UL508

European community EMC Directive 89/336/EEC and Low Voltage

Directive 73/23/EEC

International standards: IEC61131-2, IEC 68-2-6 (TEST Fc)/IEC61131-2 &

IEC 68-2-27 (TEST Ea)

260 260 240 240 230

Items

Input No.

Spec.

Input voltage (±10%)

Input impedance

Input Point

200kHz

24VDC single common port input

X0, X1, X4, X5

20kHz

X10, X11, X14, X15

10kHz

X2, X3, X6, X7, X12,

X13, X16, X17

24VDC, 5mA

4.7kΩ 3.3kΩ 4.7kΩ

OffOn > 4mA (16.5V) > 6mA (18.5V) > 4mA (16.5V)

Action level

OnOff < 1.5mA (8V) < 2.2mA (8V) < 1.5mA (8V)

Response time

OffOn

OnOff

< 150ns

Filter time Adjustable within 10 ~ 60ms by D1020, D1021 (Default: 10ms)

Note: 24SV2 does not support X12~X17.

Output Point

Items

Spec.

Relay

High-speed

Transistor

Low-speed

Output No. Y0 ~ Y7, Y10 ~ Y13 Y0 ~ Y4, Y6 Y5, Y7, Y10 ~ Y13

Max. frequency 1Hz

Working voltage

Max. load Resistive

250VAC, < 30VDC

1.5A/1 point (5A/COM)

Inductive

#2

Max. load

Lamp 20WDC/100WAC

200kHz 10kHz

5 ~ 30VDC

#1

0.3A/1 point @ 40°C

9W (30VDC)

Response time

OffOn

Approx. 10ms

0.2μs 20μs

OnOff 0.2μs 30μs

#1: For a PNP output model, UP and ZP must be connected to a 24VDC (-15% ~ +20%) power supply. The rated consumption is 10mA/point.

- 2 -

#2: Life curves

Model

DVP28SV11S2

3000

2000

1000

DVP28SV11R 16

DVP28SV11R2 16

DVP28SV11T 16

DVP24SV11T2 10

16

DC

(Sink Or

Source)

120VAC Resistive

30VDC Inductive(t=7ms)

240VAC Inductive(cos

ψ

= 0.4)

500

300

200

100

50

30VDC

Inductive

(t=40ms)

0.1

0.2

0.3

0.5

0.7 1 2

Contact

Current(A)

[ Figure 3 ]

Specifications for analog inputs (Only applicable to DVP24SV11T2)

Analog input range

Digital conversion range

Resolution

Input impedance

Overall accuracy

Voltage input

0 ~ 10V

0 ~ 4,000

Current input

0 ~ 20mA

0 ~ 2,000

12-bit (2.5mV) 11-bit (10uA)

> 1MΩ 250Ω

1% of full scale within the range of PLC operation temperature

Response time

Absolute input range

Digital data format

2ms (It can be set by means of D1118.)

#1

±15V

16-bit 2’s complement (12 significant bits)

±32mA

16-bit 2’s complement (11 significant bits)

Provided (It can be set by means of D1062)

#2

Average function

Isolation method No isolation between digital circuits and analog circuits

#1: If the scan cycle is longer than 2 milliseconds or greater than the setting value, the scan cycle is given preference.

#2: If the value in D1062 is 1, the present value is read.

I/O Configuration

Input

Power

Point Type Point

Output

Type Relay

12

12

12

12

Transistor

(NPN)

12

12

Relay

Transistor

(PNP)

S/S

X10

X11

X12

X13

X14

X15

X16

X17

X3

X4

X5

X6

X7

S/S

X0

X1

X2

C0

Y0

Y1

Y2

C1

Y3

Y4

Y5

C2

Y6

Y7

Y10

C3

Y11

Y12

Y13

S/S

X10

X11

X12

X13

X14

X15

X16

X17

S/S

X0

X1

X2

X3

X4

X5

X6

X7

I/O configuration

Transistor (NPN)

28SV 24SV2

C0

Y0

Y1

C1

Y2

Y3

C2

Y4

Y5

C3

Y6

Y7

C4

Y10

Y11

Y12

Y13

S/S

X0

X1

X2

X3

X4

X5

X6

X7

X10

X11

V0+

I0+

VI0-

V1+

I1+

VI1-

C0

Y0

Y1

C1

Y2

Y3

C2

Y4

Y5

C3

Y6

Y7

C4

Y10

Y11

Y12

Y13

Transistor

(PNP)

S/S

X10

X11

X12

X13

X14

X15

X16

X17

S/S

X0

X1

X2

X3

X4

X5

X6

X7

UP0

ZP0

Y0

Y1

Y2

Y3

Y4

Y5

Y6

Y7

UP1

ZP1

Y10

Y11

Y12

Y13

- 3 -

Installation

70

53.2

[ Figure 4 ]

Unit: mm

Please install the PLC in an enclosure with sufficient space around it to allow heat dissipation. See [Figure 5].

[ Figure 6 ]

Direct Mounting: Use M4 screw according to the dimension of the product.

DIN Rail Mounting: When mounting the PLC to 35mm DIN rail, be sure to use the retaining clip to stop any side-to-side movement of the PLC and reduce the chance of wires being loose. The retaining clip is at the bottom of the PLC. To secure the PLC to

DIN rail, pull down the clip, place it onto the rail and gently push it up. To remove the

PLC, pull the retaining clip down with a flat screwdriver and gently remove the PLC from

DIN rail. See [Figure 6].

Wiring

1. Use 22-16AWG (1.5mm) single or multiple core wire on

22-16AWG

I/O wiring terminals. See the figure in the right hand side for its specification. PLC terminal screws should be tightened to 1.90 kg-cm (1.65 in-lbs) and please use only

60/75ºC copper conductor.

< 1.5mm

2. DO NOT wire empty terminal. DO NOT place the I/O signal cable in the same wiring circuit.

3. DO NOT drop tiny metallic conductor into the PLC while screwing and wiring. Tear off the sticker on the heat dissipation hole for preventing alien substances from dropping in, to ensure normal heat dissipation of the PLC.

Power Supply

The power input of DVP-SV/SV2 is DC. When operating DVP-SV/SV2, note the following points:

1. The power is connected to two terminals, 24VDC and 0V, and the range of power is

20.4 ~ 28.8VDC. If the power voltage is less than 20.4VDC, the PLC will stop running, all outputs go “Off”, and the ERROR LED indicator will start to blink continuously.

2. The power shutdown for less than 10ms will not affect the operation of the PLC.

However, the shutdown time that is too long or the drop of power voltage will stop the operation of the PLC, and all outputs will go off. When the power returns to normal status, the PLC will automatically resume the operation. (Please take care of the latched auxiliary relays and registers inside the PLC when doing the programming).

- 4 -

Safety Wiring

Since DVP-SV/SV2 is only compatible with DC power supply, Delta’s power supply modules (DVPPS01/DVPPS02) are the suitable power supplies for DVP-SV/SV2. We suggest you install the protection circuit at the power supply terminal to protect

DVPPS01 or DVPPS02. See the figure below.

○ AC power supply: 100 ~ 240VAC, 50/60Hz

Breaker

Emergency stop: This button cuts off the system power supply when accidental emergency takes place.

○ Power indicator

○ Power supply circuit protection fuse (2A)

○ DC power supply output: 24VDC, 500mA

AC power supply load

DVPPS01/DVPPS02

DVP-PLC (main processing unit)

○ Digital I/O module

Input Point Wiring

There are 2 types of DC inputs, SINK and SOURCE. (See the example below. For detailed point configuration, please refer to the specification of each model.)

DC Signal IN – SINK mode

Input point loop equivalent circuit

+24V

24G

S/S

24VDC

X0

X1

DC Signal IN – SOURCE mode

Input point loop equivalent circuit

+24V

24G

24VDC

S/S

[ Figure 8 ]

X0

X1

[ Figure 9 ]

Output Point Wiring

1. DVP-SV/SV2 has two output modules, relay and transistor. Be aware of the connection of shared terminals when wiring output terminals.

2. Output terminals, Y0, Y1, and Y2, of relay models use C0 common port; Y3, Y4, and

Y5 use C1 common port; Y6, Y7, and Y10 use C2 common port; Y11, Y12, and Y13

- 5 -

use C3 common port. See [Figure 10].

When the output points are enabled, their corresponding indicators on the front panel will be on.

3. The output terminals Y0 and Y1 of the transistor (NPN) model are connected to the common terminals C0. Y2 and Y3 are connected to the common terminal C1. Y4 and

Y5 are connected to the common terminal C2. Y6 and Y7 are connected to the common terminal C3. Y10, Y11, Y12, and Y13 are connected to the common terminal C4. See [Figure 11a]. The output terminals Y0~Y7 on the transistor (PNP) model are connected to the common terminals UP0 and ZP0. Y10~Y13 are connected to the common terminals UP1 and ZP1. See [Figure 11b].

4. Isolation circuit: The optical coupler is used to isolate signals between the circuit inside PLC and input modules.

Relay (R) output circuit wiring

DC power supply

Emergency stop: Uses external switch

○ Fuse: Uses 5~10A fuse at the shared terminal of output contacts to protect the output circuit

Transient voltage suppressor (SB360 3A 60V): Extends the life span of contact.

1. Diode suppression of DC load: Used when in smaller power [Figure 13]

2. Diode + Zener suppression of DC load: Used when in larger power and frequent On/Off

[Figure 14]

○ Incandescent light (resistive load) AC power supply

- 6 -

Manually exclusive output: For example, Y3 and Y4 control the forward running and reverse running of the motor, forming an interlock for the external circuit, together with the PLC

○ internal program, to ensure safe protection in case of any unexpected errors.

Neon indicator

Absorber: Reduces the interference on AC load [Figure 15]

Transistor output circuit wiring

Transistor output (NPN) Transistor output (PNP)

[ Figure 17 ]

[ Figure 18 ]

Y

S mal ler power

D

+

UP

+

V DC

V DC

S mal ler power

Y

D

C

D: 1N4001 diode or equi valent com ponen t

[ F ig ure 19 ]

ZP

D: 1N4001 diode or equi valent com ponent

[ F ig ure 20]

Y

La rger power and f requent on/off

+

UP

Larger power and frequent on/of f

+

V DC

V DC

+

ZD D

V DC

Y

C

D: 1N4001 diode or equi valent com ponen t

ZD: 9V Z ener, 5W

[ F ig ure 21 ]

DC power supply

ZP D ZD

D: 1N4001 diode or equi valent com ponent

ZD: 9V Z ener, 5W

[ F ig ure 22 ]

Emergency stop Circuit protection fuse

○ The output of the transistor model is “open collector”. If Y0/Y1 is set to pulse output, the output current has to be bigger than 0.1A to ensure normal operation of the model.

1. Diode suppression: Used when in smaller power [Figure 19] and [Figure 20]

2. Diode + Zener suppression: Used when in larger power and frequent On/Off [Figure 21]

[Figure 22]

5

Manually exclusive output: For example, Y2 and Y3 control the forward running and reverse running of the motor, forming an interlock for the external circuit, together with the PLC internal program, to ensure safe protection in case of any unexpected errors.

A/D External Wiring (For DVP24SV11T2 Only)

Active

U

I N

Vol tage i nput

+

-

Shielded c abl e

CH0

V0+

I0+

VI0-

Passive

Vol tage i nput

+

U

I N

-

Shielded c abl e

CH0

V0+

I0+

V0-

U

I N

Current i nput

+

-

Shielded c abl e

CH1

V1+

I1+

VI1-

Current i nput

-

+

Shielded c abl e

CH1

V1+

I1+

VI1-

ter minal of a power module

ter minal of a power module

24G

+24V

24G

+24V

Gr ounding 100 (100 or below)

Gr ounding 100 (100 or below)

- 7 -

BAT.LOW LED Indicator

After the 24 V DC power is switched off, the data in the latched area will be stored in the

SRAM memory, and the rechargeable battery will supply power to the SRAM memory.

Therefore, if the battery is damaged or cannot be charged, the data in the program and latched area will be lost. If you need to permanently store the data in the program and latched data register, please refer to the mechanism of storing the data in the Flash

ROM permanently and the mechanism of restoring the data in Flash ROM stated below.

Mechanism of storing the data in the Flash ROM permanently:

You can use WPLSoft (Options -> PLC<=>Flash) to indicate whether to permanently store the data in the latched area in Flash ROM memory (the new indicated data will replace all data previously saved in the memory).

Mechanism of restoring the data in Flash ROM:

If the rechargeable battery is in low voltage, resulting in possible loss of data in the program, the PLC will automatically restore the data in the latched area in the program and device D of Flash ROM into SRAM memory (M1176 = On) next time when DC24V is re-powered. The ERROR LED flashing will remind you that if the recorded program is able to resume its execution. You only need to shut down and re-power the PLC once to restart its operation (RUN).

1. The rechargeable lithium-ion battery in DVP-SV/SV2 is mainly used on the latched procedure and data storage.

2. The lithium-ion battery has been fully charged in the factory and is able to retain the latched procedure and data storage for 6 months. If DVP-SV/SV2 has not been powered for less than 3 months, the life of the battery does not decrease. To prevent the electricity emitted by the battery from resulting in short life of the battery, before disconnecting DVP-SV/SV2 for a long time, you need to power DVP-SV/SV2 for 24 hours to charge the battery.

3. If the lithium-ion battery is put in an environment in which temperature is above 40 which the data can be stored is less than 6 moths. o

C, or if it is charged for more than 1000 times, its effect becomes bad, and the time for

4. The lithium-ion battery is rechargeable, and has a longer life span than an ordinary battery. However, it still has its own life cycle. When the power in the battery is not sufficient to retain the data in the latched area, please send it to the distributor for repair.

5. Please be aware of the date of manufacturing. The charged battery can sustain for 6 months from its date of manufacture. If you find that the BAT.LOW indicator stays on after PLC is powered, it means the battery voltage is low and the battery is being charged. DVP-SV/SV2 has to remain on for more than 24 hours to fully charge the battery. If the indicator turns from on to “flash” (every 1 second), it means that the battery cannot be charged anymore. Please correctly process your data in time and send the PLC back to the distributor for repair.

Accuracy (second /month) of RTC

Temperature (ºC/ºF)

Max. inaccuracy (second)

0/32

-117

25/77

52

55/131

-132

- 8 -

…………………………………………………………………

 繁體中文 ………………………………………………………………………

感謝您採用台達

DVP 系列可程式控制器。DVP-SV

#1

/SV2

#1

28 點(16 輸入點 + 12 輸

並具有

16k(SV)/30k(SV2) steps 的程式記憶體,可連接薄型全系列 I/O 模組,包含數位輸

入∕輸出(最大輸入∕輸出擴充點數可達

512 點)、類比模組(A/D、D/A 轉換及溫度單

元)及新型高速

I/O 模組等各類機型。四組高速(200kHz)脈波輸出(24SV2 再加兩軸

10KHz 輸出)、新增兩軸補間指令,可滿足各種應用場合,並且體積小,安裝容易。

#1:SV 為 DVP28SV11R/T 之簡稱;SV2 為 DVP24SV11T2 及 DVP28SV11R2/T2/S2 之簡稱。

本使用說明書僅提供電氣規格、功能規格、安裝配線部份說明,其它詳細之程式設計

及指令說明請見《

DVP-PLC 應用技術手冊:程式篇》,選購之週邊裝置詳細說明請見

該產品隨機手冊或《

DVP-PLC 應用技術手冊:特殊模組篇》。

本機為開放型(OPEN TYPE)機殼,因此使用者使用本機時,必須將之安裝於具防塵、

防潮及免於電擊

/衝擊意外之外殼配線箱內。另必須具備保護措施(如:特殊之工具或

鑰匙才可打開)防止非維護人員操作或意外衝擊本體,造成危險及損壞。

交流輸入電源不可連接於輸入∕出信號端,否則可能造成嚴重損壞,請在上電之前再

次確認電源配線。請勿在上電時觸摸任何端子。本體上之接地端子

務必正確的接

地,可提高產品抗雜訊能力。

產品外觀與部位介紹

 詳細外觀圖示請參閱英文版頁碼 1 之 [Figure 1] 及 [Figure 2]。

左側高速

I/O 模組連接口

銘牌

○ COM1(RS-232)通訊接收(Rx)指示燈 ○

○ COM2(RS-485)通訊傳送(Tx)指示燈 ○

輸入∕輸出點指示燈

RUN∕STOP 開關

○ VR0:M1178 啟動∕D1178 對應值

○ VR1:M1179 啟動∕D1179 對應值

電源、運行、錯誤及電池狀態指示燈

直接固定孔

輸入∕輸出端子

COM1(RS-232)程式輸入∕輸出通訊口

DIN 軌固定扣

COM2(RS-485)通訊口(Master/Slave)

電源輸入口

3PIN 脫落式端子(標準附件)

電源輸入連接線(標準附件)

I/O 模組定位孔

I/O 模組連接口

DIN 軌槽 (35mm)

I/O 模組固定扣

電氣規格

機種

項目

電源電壓

DVP28SV11R DVP28SV11R2 DVP28SV11T

DVP24SV11T2

DVP28SV11T2

DVP28SV11S2

24VDC (-15% ~ 20%)(具直流輸入電源極性反接保護)

突入電流

Max.

電源保險絲容量

2.5A/30VDC,可恢復式 (Polyswitch)

消耗電力

6W

絕緣阻抗

>

雜訊免疫力

接地

認證標準

操作∕儲存環境

ESD (IEC 61131-2, IEC 61000-4-2): 8kV Air Discharge

EFT (IEC 61131-2, IEC 61000-4-4): Power Line: 2kV, Digital I/O: 1kV,

Analog & Communication I/O: 1kV

Damped-Oscillatory Wave: Power Line: 1kV, Digital I/O: 1kV

RS (IEC 61131-2, IEC 61000-4-3): 26MHz ~ 1GHz, 10V/m

接地配線之線徑不得小於電源端配線線徑(多台

PLC 同時使用時,請務必單

點接地)

操作:

0ºC ~ 55ºC(溫度)5 ~ 95%(濕度)污染等級 2

儲存:

-25ºC ~ 70ºC(溫度)5 ~ 95%(濕度)

UL508

European community EMC Directive 89/336/EEC and Low Voltage Directive

73/23/EEC

- 9 -

項目

機種

DVP28SV11R DVP28SV11R2 DVP28SV11T

DVP24SV11T2

DVP28SV11T2

DVP28SV11S2

耐振動∕衝擊

國際標準規範 IEC61131-2, IEC 68-2-6 (TEST Fc)/IEC61131-2 & IEC

68-2-27 (TEST Ea)

重量

260g 240g

輸入點電氣規格

機種

項目

24VDC 單端共點輸入

輸入點

No.

200kHz

X0, X1, X4, X5

20kHz

X10, X11, X14, X15

10kHz

X2, X3, X6, X7, X12, X13,

X16, X17

輸入點阻抗

4.7kΩ 3.3 kΩ

動作

位凖

OffOn

OnOff

> 4mA (16.5V)

< 1.5mA (8V)

> 6mA (18.5V)

< 2.2mA (8V)

> 4mA (16.5V)

< 1.5mA (8V)

輸入信號電(

±10%) 24VDC,

反應時間

雜訊抑制

OffOn

OnOff

< 150ns

濾波時間 由

D1020 及 D1021 可作 10 ~ 60 ms 的調整 (預設:10ms)

註:

24SV2 主機無 X12~X17 輸入點

輸出點電氣規格

機種

項目

繼電器

電晶體

高速 低速

輸出點 No. Y0 ~ Y7, Y10~Y13 Y0 ~ Y4, Y6 Y5, Y7, Y10~Y13

最高切換頻率

1Hz 10kHz

電壓規格

250VAC, < 30VDC 5 ~ 30VDC

#1

電流規格

反應時間

電阻性

1.5A/1 point (5A/COM)

電感性

#2

燈泡 20WDC/100WAC

OffOn

10ms

OnOff

0.3A/1 點@ 40°C

9W (30VDC)

0.2μs 20μs

0.2μs 30μs

#1:PNP 輸出機種 UP, ZP 必須外加輔助電源 24VDC (-15% ~ +20%) 額定消耗約 10mA/點。

#2:生命週期曲線圖請參閱英文版頁碼 3 之 [Figure 3]。

類比輸入規格(僅

DVP24SV11T2 適用)

類比輸入範圍

電壓輸入

0 ~ 10V

電流輸入

0 ~ 20mA

數位轉換範圍

解析度

0 ~ 4,000 0 ~ 2,000

12-bit (2.5mV) 11-bit (10uA)

> 1MΩ 250Ω

輸入阻抗

總和精密度

回應時間

1%在整個溫度範圍內滿刻度時

2ms (可由 D1118 設定)

#1

絕對輸入範圍

±15V ±32mA

數位資料格式

16 位 2 補數(有效位 12 bits) 16 位 2 補數(有效位 11 bits)

平均功能

隔離方式

是 (由 D1062 設定)

#2

數位及類比電路間無隔離

#1: 當掃描週期大於 2ms 或設定值時,以掃描週期為主

#2: 當平均次數 D1062 為 1 時,即是讀取現在值。

- 10 -

輸入/輸出配置

輸入單元

機種 電源

點數 形式 點數

DVP28SV11R 16 12

DVP28SV11R2 16

DVP28SV11T 16

直流

(Sink or

Source)

12

12

12

12

DVP28SV11S2 16 12

輸出單元

形式

繼電器

電晶體(

NPN)

電晶體(

PNP)

I/O 配置

繼電器 電晶體

請參閱英

文版圖示

請參閱英

文版圖示

安裝方式

 詳細外觀尺寸圖請參閱英文版頁碼 3 之[Figure 4],單位:mm。

PLC 在安裝時,請裝配於封閉式之控制箱內,其周圍應保持一定之空間,以確保 PLC 散

熱功能正常,請參閱英文版頁碼

3 之[Figure 5]。

 直接鎖螺絲方式:請依產品外型尺寸並使用 M4 螺絲。

 DIN 鋁軌之安裝方法:適用於 35mm 之 DIN 鋁軌。在將主機掛上鋁軌時,請先將主機

(或

I/O 模組)下方之固定塑膠片,以一字形起子插入凹槽並向外撐開拉出(請參閱英

文版頁碼

3 之[Figure 6]),再將主機(或 I/O 模組)掛上鋁軌,之後將固定塑膠片壓扣

回去即可。欲取下主機時,同樣以一字形起子先將固定塑膠片撐開,再將主機以往外向

上的方式取出即可。該固定機構塑膠片為保持型,因此撐開後便不會彈回去。

配線端子

1. 輸出/輸入配線端請使用 22-16AWG (1.5mm) 單蕊裸線或多蕊線,端子規格如頁碼 4 之

圖示。

PLC 端子螺絲扭力為 1.90 kg-cm (1.65 in-lbs)。只能使用 60/75°C 的銅導線。

2. 空端子請勿配線。輸入點信號線與輸出點等動力線請勿置於同一線糟內。

3. 鎖螺絲及配線時請避免微小的金屬導體掉入 PLC 內部,並在配線完成後,將位於 PLC

上方散熱孔位置的防異物掉入之貼紙撕去,以保持散熱良好。

電源端

DVP-SV/SV2 機種為直流電源輸入,在使用上應注意下列事項:

1. 電源請接於 24VDC 及 0V 兩端,電源範圍為 20.4 ~ 28.8VDC,當電源電壓低於

20.4VDC 時,PLC 會停止運轉,輸出全部 Off,ERROR LED 快速閃爍。

2. 當停電時間低於 10ms 時,PLC 不受影響繼續運轉,當停電時間過長或電源電壓下降

將使

PLC 停止運轉,輸出全部 Off,當電源恢復正常時,PLC 亦自動回復運轉。(PLC

內部具停電保持的輔助繼電器及暫存器,使用者在規劃程式設計時應特別注意使用。)

安全配線回路

由於

DVP-SV/SV2 的電源為 DC Only 的機種,因此可搭配台達之電源供應模組

(DVPPS01/DVPPS02) 提供電源給 DVP-SV/SV2。為保護 DVPPS01/DVPPS02,建議可

在電源的輸入回路端配置如下的保護回路,配置圖請參閱英文版頁碼

4 之[Figure 7]所示:

交流電源供應:

100 ~ 240VAC, 50/60Hz

直流電源供應輸出:

24VDC,500mA

斷路器

緊急停止:為預防突發狀況發生,設置緊急停止按鈕,可在狀況發生時,切斷系統電源。

電源指示燈 交流電源負載

電源回路保護用保險絲(

2A) DVPPS01/DVPPS02 本體

DVP PLC 本體

數位輸入

/輸出模組

輸入點之配線

輸入點之入力信號為直流電源

DC 輸入型式,共有兩種接法:SINK 及 SOURCE,其定義與輸入

點回路等效電路配線圖,請參閱英文版頁碼 5 之[Figure 8]及[Figure 9]。

- 11 -

輸出點之配線

1.

DVP-SV/SV2 系列 PLC 輸出模組共有二種:繼電器及電晶體。輸出端在實際配線時,應特別

注意共用端的連接。

2.

繼電器機種輸出端

Y0、Y1、Y2 用 C0 共同端,Y3、Y4、Y5 用 C1 共同端,Y6、Y7、Y10

共用 C2 共同端,Y11、Y12、Y13 共用 C3 共同端,請參閱英文版頁碼 5 之[Figure 10]。動作

指示:當輸出點動作時,正面的該點指示燈亮。

3.

電晶體(

NPN)機種輸出端 Y0、Y1 用 C0 共同端,Y2、Y3 用 C1 共同端,Y4、Y5 共用 C2

共同端,

Y6、Y7 共用 C3 共同端,Y10、Y11、Y12、Y13 共用 C4 共同端,請參閱英文版頁

5 之[Figure 11a]。電晶體(PNP)機種輸出端 Y0 ~Y7 用 UP0、ZP0 共同端,而輸出端 Y10

~Y13 用 UP1、ZP1 共同端,請參閱英文版頁碼 5 之[Figure 11b]。

4.

隔離回路:

PLC 內部回路與輸入模組之間使用光耦合器作信號隔離。

 繼電器輸出回路配線。詳細配線圖請參閱英文版頁碼 5 之[Figure 12]。

直流電源供給

緊急停止:使用外部開關

保險絲:使用

5 ~ 10A 的保險絲容量於輸出接點的共用點,保護輸出點回路

突波吸收二極體:可增加接點壽命。

1. DC 負載電源之二極體抑制:功率較小時使用(請參閱英文版頁碼 6 之[Figure 13])

2. DC 負載電源之二極體+Zener 抑制:大功率且 On/Off 頻繁時使用 (請參閱英文版頁碼

6 之[Figure 14])

白熾燈(電阻性負載) 交流電源供給

互斥輸出:例如,將

Y3 與 Y4 用以控制對應馬達的正轉及反轉,使外部電路形成互鎖,配

PLC 內部程式,確保任何異常突發狀況發生時,均有安全的保護措施。

指示燈:氖燈

突波吸收器:可減少交流負載上的雜訊(請參閱英文版頁碼 6 之[Figure 15])

 電晶體輸出回路配線。

詳細配線圖請參閱英文版頁碼

6 之 [Figure 17]及[Figure 18]。

直流電源供應

緊急停止 電路回路保護用保險絲

因電晶體模組輸出均為開集極輸出 (Open Collector),若 Y0/Y1 設定為脈波串輸出,為確

保電晶體模組能夠動作正常,其輸出提升電阻,必須維持輸出電流大於 0.1A。

1. 二極體抑制:功率較小時使用(請參閱英文版頁碼

6 之[Figure 19]及[Figure 20])

2. 二極體

+Zener 抑制:大功率且 On/Off 頻繁時使用(請參閱英文版頁碼 6 之[Figure 21]

[Figure 22])

互斥輸出:例如,將

Y2 與 Y3 用以控制對應馬達的正轉及反轉,使外部電路形成互鎖,配

PLC 內部程式,確保任何異常突發狀況發生時,均有安全的保護措施。

A/D

外部配線(僅 DVP24SV11T2 支援)

主動式

被動式

電壓 輸入

U

IN

+

-

CH0

V0+

I0+

VI0-

U

I N

+

-

隔離 線

電壓輸入

隔離線

CH0

V0+

I0+

V0-

電流 輸入

U

IN

+

-

CH1

V1+

I1+

VI1-

+

-

電流輸入

隔離線

CH1

V1+

I1+

VI1-

隔離 線

接至電源模

組之 端

接至電源模

組之 端

24G

+24V

24G

+24V

第三種接地 ( 接地阻抗

100

以下

)

第三種接地 (

接地阻抗 100 以下 )

電池 BAT.LOW 指示燈

24V 電源下電後,停電保持區域的資料皆存放於 SRAM 記憶體中,此時由電池提供維

SRAM 內資料的電源,故當電池損壞或無法充電時,其程式區與停電保持區之資料將

- 12 -

會消失。因此,若程式設計者需將程式區與

D 裝置停電保持區做永久保存時,請參照下述

Flash ROM 永久保持與回復機制。

 永久保持機制:程式設計者可使用 WPLSoft 軟體提供之設定選項(”設定”-->

“PLC<=>Flash”)來指定程式區及 D 裝置停電保持區的資料是否永久保持至 Flash

ROM 記憶體中。每次指定後之資料將會覆蓋掉前次存於 Flash ROM 內的所有資料。

 回復機制:當電池電力不足(即電源下電前電池低電壓燈亮),而造成程式區資料遺失

時,則

PLC 內部會在下次電源上電時,自動將 Flash ROM 內之程式區與 D 裝置停電

保持區的資料,全部回存至

SRAM 記憶體中。若使用者確認重新回復之程式可繼續執

行,則只需再做一次下電與上電之動作,即可讓

PLC 重新運行(RUN)。

1. DVP-SV/SV2 主機內部使用二次可充電式鋰電池,主要用於主機內部停電保持區之程

序與資料保存。

2. 所使用之鋰電池已於出廠前將電力充飽,其停電保持區之程序與資料保存可達 6 個

月,但建議主機未上電時間不超過三個月,可使電池使用循環壽命最佳化;主機長時

間不上電之前,需先將主機連續上電

24 小時以將電池充飽,避免長時間過度放電導致

電池失效或壽命減短。

3. 鋰電池長時間置於環温 40 o

料保存時間可能小於

6 個月。

4. 鋰電池可重複充電使用,壽命較傳統電池長,但仍具有生命週期,當電池電力不足以

保存停電區資料時,請送回經銷商維修。

5. 請注意出廠日期,以 6 個月為期限或上電發現指示燈 BAT.LOW 持續亮起時,則表示

鋰電池電壓不足且正在進行充電中,此時請讓

DVP-SV/SV2 主機連續上電 24 小時以

上,即可將鋰電池電力充飽。當指示燈由持續亮轉為「閃爍」

1 秒),表示

鋰電池已無法再繼續充電,請及時正確處理程序與資料後,將

PLC 送回經銷商維修。

萬年曆的精度(秒/月)

溫度

(°C/°F) 0/32 25/77 55/131

最大誤差(秒)

-117 52 -132

- 13 -

…………………………………………………………………… 

简体中文 ……………………………………………………………………

感谢您采用台达

DVP 系列可编程控制器。DVP-SV

#1

/SV2

#1

28 点(16 输入点 + 12 输

出点) /24 点(10 输入点 + 12 输出点 + 2 通道模拟输入)PLC 主机,提供丰富的指令集,

并具有 16k(SV)/30k(SV2) steps 的程序内存,可连接薄型全系列 I/O 模块,包含数字输入

/输出(最大输入/输出扩展点数可达 512 点)、模拟模块(A/D、D/A 转换及温度单元)

及新型高速

I/O 模块等各类机型。四组高速(200kHz)脉冲输出(24SV2 再加两轴 10KHz

输出)、新增两轴插补指令,可满足各种应用场合,并且体积小,安装容易。

#1:SV 为 DVP28SV11R/T 之简称;SV2 为 DVP24SV11T2 及 DVP28SV11R2/T2/S2 之简称。

本使用说明书仅提供电气规格、功能规格、安装配线部份说明,其它详细的程序设计

及指令说明请见《

DVP-PLC 应用技术手册:程序篇》,选购外围装置详细说明请见该

产品随机手册或《

DVP-PLC 应用技术手册:特殊模块篇》。

本机为开放型 (OPEN TYPE) 机种,因此使用者使用本机时,必须将的安装于具防尘、

防潮及免于电击/冲击意外的外壳配线箱内。另必须具备保护措施(如:特殊的工具

或钥匙才可打开)防止非维护人员操作或意外冲击本体,造成危险及损坏。

交流输入电源不可连接于输入/出信号端,否则可能造成严重损坏,请在上电的前再

次确认电源配线。请勿在上电时触摸任何端子。本体上的接地端子

务必正确的接

地,可提高产品抗干扰能力。

产品外观与部位介绍

 详细外观图示请参阅英文版页码 1 之 [Figure 1] 及 [Figure 2]。

○ 左侧高速 I/O 模块连接口

○ 铭牌

COM1(RS-232)通讯接收(Rx)指示灯

COM2(RS-485)通讯传送(Tx)指示灯 ○

输入/输出点指示灯

○ RUN/STOP 开关

○ VR0:M1178 启动/D1178 对应值

VR1:M1179 启动/D1179 对应值

电源、运行、错误及电池状态指示灯

直接固定孔

○ 输入/输出端子

电气规格

COM1(RS-232)程序输入/输出通讯口

DIN 轨固定扣

COM2(RS-485)通讯口(Master/Slave)

电源输入口

3PIN 脱落式端子(标准附件)

电源输入连接线(标准附件)

I/O 模块定位孔

I/O 模块连接口

DIN 轨槽(35mm)

I/O 模块固定扣

项目

机种

DVP28SV11R DVP28SV11R2 DVP28SV11T

DVP24SV11T2

DVP28SV11T2

DVP28SV11S2

电源电压 24VDC (-15% ~ 20%) (具直流输入电源极性反接保护)

突入电流

Max.

电源保险丝容量 2.5A/30VDC,可恢复式 (Polyswitch)

消耗电力

6W

绝缘阻抗 >

干扰免疫力

ESD (IEC 61131-2, IEC 61000-4-2): 8kV Air Discharge

EFT (IEC 61131-2, IEC 61000-4-4): Power Line: 2kV, Digital I/O: 1kV, Analog

& Communication I/O: 1kV

Damped-Oscillatory Wave: Power Line: 1kV, Digital I/O: 1kV

RS (IEC 61131-2, IEC 61000-4-3): 26MHz ~ 1GHz, 10V/m

接地

操作/储存环境

接地配线的线径不得小于电源端配线线径(多台 PLC 同时使用时,请务必单

点接地)

操作:

0ºC ~ 55ºC(温度)5 ~ 95%(湿度)污染等级 2

储存: -25ºC ~ 70ºC(温度)5 ~ 95%(湿度)

认证标准

UL508

European community EMC Directive 89/336/EEC and Low Voltage Directive

73/23/EEC

- 14 -

项目

机种

DVP28SV11R DVP28SV11R2 DVP28SV11T

DVP24SV11T2

DVP28SV11T2

DVP28SV11S2

耐振动/冲击

国际标准规范 IEC61131-2, IEC 68-2-6 (TEST Fc)/IEC61131-2 & IEC 68-2-27

(TEST Ea)

重量

260g 240g

输入点电气规格

机种

项目

输入点 No.

输入信号电( ±10%)

输入阻抗

动作临界点

OffOn

反应时间

干扰抑制

OnOff

OffOn

OnOff

滤波时间

200kHz

X0, X1, X4, X5

24VDC 单端共点输入

20kHz

X10, X11, X14, X15

10kHz

X2, X3, X6, X7, X12,

X13, X16, X17

< 1.5mA (8V)

< 150ns

24VDC, 5mA

4.7kΩ 3.3kΩ 4.7kΩ

> 4mA (16.5V) > 6mA (18.5V) > 4mA (16.5V)

< 2.2mA (8V) < 1.5mA (8V)

由 D1020 及 D1021 可作 10 ~ 60 ms 的调整 (预设:10ms)

注:

24SV2 主机无 X12~X17 输入点

输出点电气规格

机种

项目

输出点

No.

Y0 ~ Y7, Y10 ~ Y13

最高切换频率

电压规格

电流规格

250VAC, < 30VDC

电阻性 1.5A/1 point (5A/COM)

电感性

#2

反应时间

灯泡

OffOn

OnOff

继电器

约 10ms

高速

Y0 ~ Y4, Y6

晶体管

低速

Y5, Y7, Y10 ~ Y13

5 ~ 30VDC

#1

0.3A/1 点@ 40°C

9W (30VDC)

0.2μs 20μs

0.2μs 30μs

#1:PNP 输出机种 UP, ZP 必须外加辅助电源 24VDC (-15% ~ +20%) 额定消耗约 10mA/点。

#2:生命周期曲线图请参阅英文版页码 3 之[Figure 3]。

模拟输入规格(仅 DVP24SV11T2 适用)

模拟输入范围

电压输入

0 ~ 10V

电流输入

0 ~ 20mA

数字转换范围

0 ~ 4,000 0 ~ 2,000

分辨率

12-bit (2.5mV) 11-bit (10uA)

输入阻抗

总和精密度

平均功能

隔离方式

> 1MΩ 250Ω

1%在整个温度范围内满刻度时

响应时间

2ms (可由 D1118 设定)

#1

绝对输入范围 ±15V ±32mA

数字数据格式 16 位 2 补码(有效位 12 bits) 16 位 2 补码(有效位 11 bits)

是 (由 D1062 设定)

#2

数字及模拟电路间无隔离

#1: 当扫描周期大于 2ms 或设定值时,以扫描周期为主

#2: 当平均次数 D1062 为 1 时,即是读取现在值。

- 15 -

输入/输出配置

输入单元

机种 电源

点数 形式 点数

DVP28SV11R 16 12

DVP28SV11R2 16

DVP28SV11T 16

直流

(Sink or

Source)

12

12

12

12

DVP28SV11S2 16 12

输出单元

形式

继电器

晶体管( NPN)

晶体管( PNP)

I/O 配置

继电器 晶体管

请参阅英

文版图示

请参阅英

文版图示

安装方式

 详细外观尺寸图请参阅英文版页码 3 之[Figure 4],单位:mm。

PLC 在安装时,请装配于封闭式的控制箱内,其周围应保持一定的空间,以确保 PLC 散

热功能正常,请参阅英文版页码 3 的[Figure 5]。

直接锁镙丝方式:请依产品外型尺寸并使用 M4 镙丝。

DIN 铝轨的安装方法:适用于 35mm 的 DIN 铝轨。在将主机挂上铝轨时,请先将主机

(或 I/O 模块)下方的固定塑料片,以一字形起子插入凹槽并向外撑开拉出(请参阅英

文版页码 3 的[Figure 6]),再将主机(或 I/O 模块)挂上铝轨,之后将固定塑料片压扣

回去即可。欲取下主机时,同样以一字形起子先将固定塑料片撑开,再将主机以往外向

上的方式取出即可。该固定机构塑料片为保持型,因此撑开后便不会弹回去。

配线端子

1. 输出/入配线端请使用 22-16AWG (1.5mm) 单蕊祼线或多蕊线,端子规格如页码 4 之图

示。

PLC 端子螺丝扭力为 1.90 kg-cm (1.65 in-lbs)。只能使用 60/75°C 的铜导线。

2. 空端子请勿配线。输入点信号线与输出点等动力线请勿置于同一线糟内。

3. 锁螺丝及配线时请避免微小的金属导体掉入 PLC 内部,并在配线完成后,将位于 PLC

上方散热孔位置的防异物掉入的贴纸撕去,以保持散热良好。

电源端

DVP-SV/SV2 机种为直流电源输入,在使用上应注意下列事项:

1. 电源请接于 24VDC 及 0V 两端,电源范围为 20.4VDC ~ 28.8VDC,当电源电压低于

20.4VDC 时,PLC 会停止运行,输出全部 Off,ERROR LED 快速闪烁。

2. 当停电时间低于 10ms 时,PLC 不受影响继续运转,当停电时间过长或电源电压下降

将使 PLC 停止运转,输出全部 Off,当电源恢复正常时,PLC 亦自动回复运转。 PLC

安全配线回路

由于 DVP-SV/SV2 的电源为 DC Only 的机种,因此可搭配台达的电源供应模块

(DVPPS01/DVPPS02) 提供电源给 DVP-SV/SV2。为保护 DVPPS01/DVPPS02,建议可

在电源的输入回路端配置如下的保护回路,配置图请参阅英文版页码

4 的[Figure 7]所示:

交流供应电源:

100 ~ 240VAC, 50/60Hz

断路器

紧急停止:为预防突发状况发生,设置紧急停止按钮,可在状况发生时,切断系统电源。

电源指示灯

电源回路保护用保险丝(

2A)

交流电源负载

DVPPS01/DVPPS02 本体

直流供应电源输出: 24VDC,500mA

数字量输入 /输出模块

DVP PLC 本体

输入点的配线

输入点的接入信号为直流电源 DC 输入,DC 型式共有两种接法:漏型及源型,其定义与

输入点回路等效电路配线图,请参阅英文版页码 5 的[Figure 8]及[Figure 9]。

输出点的配线

1. DVP-SV/SV2 系列 PLC 输出模块共有二种:继电器及晶体管。输出端在实际配线时,

- 16 -

应特别注意共享端的连接。

2. 继电器机种输出端 Y0、Y1、Y2 用 C0 共同端,Y3、Y4、Y5 用 C1 共同端,Y6、Y7、

Y10 共享 C2 共同端,Y11、Y12、Y13 共享 C3 共同端,请参阅英文版页码 5 之[Figure

10]。动作指示:当输出点动作时,正面的该点指示灯亮。

3. 晶体管(NPN)机种输出端 Y0、Y1 用 C0 共同端,Y2、Y3 用 C1 共同端,Y4、Y5

共享

C2 共同端,Y6、Y7 共享 C3 共同端,Y10、Y11、Y12、Y13 共享 C4 共同端,

请参阅英文版页码

5 之[Figure 11a]。晶体管(PNP)机种输出端 Y0 ~Y7 用 UP0、ZP0

共同端,

Y10 ~Y13 用 UP1、ZP1 共同端,请参阅英文版页码 5 之[Figure 11b]。

4. 隔离回路:PLC 内部回路与输入模块之间使用光耦合器作信号隔离。

 继电器输出回路配线

详细配线图请参阅英文版页码

5 之[Figure 12]。

直流电源供给

紧急停止:使用外部开关

保险丝:于输出接点的公共端使用容量 5 ~ 10A 的保险丝,保护输出点回路

突波吸收二极管:可增加接点寿命。

1.

DC 负载电源的二极管抑制:功率较小时使用(请参阅英文版页码 6 的[Figure 13])

2.

DC 负载电源的二极管+Zener 抑制:大功率及 On/Off 频繁时使用(请参阅英文版页码 6

的 [Figure 14])

白炽灯(电阻性负载)

交流电源供给

7 互斥输出:例如,将

Y3 与 Y4 用于控制对应马达的正转及反转,使外部电路形成互锁,配

PLC 内部程序,确保任何异常突发状况发生时,均有安全的保护措施。

指示灯:氖灯

突波吸收器:可减少交流负载上的干扰(请参阅英文版页码 6 的[Figure 15])

 晶体管输出回路配线

詳細配線圖請參閱英文版页码

6 之[Figure17]及[Figure18]。

直流供应电源

紧急停止

电路回路保护用保险丝

4 因晶体管模块输出均为开集极输出

(Open Collector),若 Y0/Y1 设定为脉冲式输出,为确

保晶体管模块能够动作正常,其输出负载电阻,必须维持输出电流大于

0.1A。

1. 二极管抑制:功率较小时使用(请参阅英文版页码 6 的[Figure 19]

[Figure20])

2. 二极管+Zener 抑制:大功率及 On/Off 频繁时使用(请参阅英文版页码 6 的[Figure 21]

[Figure 22])

互斥输出:例如,将

Y2 与 Y3 用于控制对应马达的正转及反转,使外部电路形成互锁,配

PLC 内部程序,确保任何异常突发状况发生时,均有安全的保护措施。

A/D

外部配线(仅

DVP24SV11T2

支持

)

主动式

被动式

電壓 輸入

CH0

電壓 輸入

U

I N

-

+

V0+

I0+

VI0-

U

I N

+

-

隔 離 線

隔離 線

CH0

V0+

I0+

V0-

電流 輸入

U

I N

+

-

CH1

V1+

I1+

VI1-

+

-

電流 輸入

隔離 線

CH1

V1+

I1+

VI1-

隔 離 線

接 至 電源 模

組之 端

接至 電源模

組之 端

24G

+24V

24G

+24V

第三 種接地 ( 接地 阻抗

100

以下

)

第 三 種接 地 ( 接 地 阻 抗 100 以 下 )

电池 BAT.LOW 指示灯

在 24V 电源下电后,停电保持区域的数据皆存放于 SRAM 内存中,此时由电池提供维持

SRAM 内资料的电源,故当电池损坏或无法充电时,其程序区与停电保持区的数据将会消

失。因此,若程序设计者需将程序区与 D 装置停电保持区做永久保存时,请参照下述 Flash

ROM 永久保持与回复机制。

- 17 -

永 久 保 持 机制 : 程序设 计 者 可使 用 WPLSoft 软 件 提供 的 设定选 项 ( ” 设定 ”-->

“PLC<=>Flash”)来指定程序区及 D 装置停电保持区的数据是否永久保持至 Flash

ROM 内存中。每次指定后的数据将会覆盖掉前次存于 Flash ROM 内的所有数据。

 回复机制:当电池电力不足(即电源下电前电池低电压灯亮),且电源下电达 1 分钟以

上时,则 PLC 内部会在下次电源上电时,自动将 Flash ROM 内的程序区与 D 装置停

电保持区的数据,全部回存至 SRAM 内存中。若使用者确认重新回复的程序可继续执

行,则只需再做一次下电与上电的动作,即可让 PLC 重新运行(RUN)。

1. DVP-SV/SV2 主机内部使用二次可充电式锂电池,主要用于主机内部停电保持区的程

序与数据保存。

2. 所使用的锂电池已于出厂前将电力充饱,其停电保持区的程序与数据保存可达 6 个月,

但建议主机未上电时间不超过三个月,可使电池使用循环寿命最佳化;主机长时间不

上电之前,需先将主机连续上电

24 小时以将电池充饱,避免长时间过度放电导致电池

失效或寿命减短。

3. 锂电池长时间置于环温 40 o

C 以上或经过多次(1000 以上),充放电后效能将变差,数

据保存时间可能小于

6 个月。

4. 锂电池可重复充电使用,寿命较传统电池长,但仍具有生命周期,当电池电力不足以

保存停电区数据时,请送回经销商维修。

5. 请注意出厂日期,以 6 个月为期限或上电发现指示灯 BAT.LOW 持续亮起时,则表示

锂电池电压不足且正在进行充电中,此时请让

DVP-SV/SV2 主机连续上电 24 小时以

上,即可将锂电池电力充饱。当指示灯由持续亮转为「闪烁」

1 秒),表示

锂电池已无法再继续充电,请及时正确处理程序与数据后,将

PLC 送回经销商维修。

万年历的精度(秒/月)

温度

(°C/°F) 0/32 25/77 55/131

最大误差(秒) -117 52 -132

- 18 -

advertisement

Key Features

  • 28-point (16 inputs + 12 outputs)/24-point (10 inputs + 12 outputs + 2 analog input channels) PLC MPU
  • 16k (SV)/30k (SV2) steps program memory
  • Connect to all Slim type series extension models
  • 4 groups of high-speed (200 kHz) pulse outputs
  • 2 two-axis interpolation instructions
  • Small in size and easy to install

Frequently Answers and Questions

What is the power supply voltage range for the DVP-SV/SV2?
The power supply voltage range is 24VDC (-15% ~ 20%).
What is the maximum number of I/O points that can be expanded with the DVP-SV/SV2?
The maximum number of I/O points that can be expanded is 512 points.
What type of extension modules can the DVP-SV/SV2 connect to?
The DVP-SV/SV2 can connect to all Slim type series extension models, including digital I/O, analog modules, and high-speed extension modules.

Related manuals

Download PDF

advertisement