- Industrial & lab equipment
- Electrical equipment & supplies
- Circuit protection
- SymCom
- 777-575-FT
- Installation Guide
- 20 Pages
SymCom 777-575-FT Installation Instructions Manual
SymCom 777-575-FT is an electronic overload relay designed to protect medium voltage systems in conjunction with power transformers and external current transformers. It offers customizable protection with a digital readout and RS-485 communications. The relay features fast linear trip mode for sensitive motors, quick trips in test panels, and high torque systems. With programmable parameters, it can be tailored to specific application needs.
advertisement
Assistant Bot
Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.
INSTALLATION INSTRUCTIONS
FOR SYMCOM’S OVERLOAD RELAY
MODEL 777-MV-FT
BE SURE POWER IS DISCONNECTED PRIOR TO INSALLATION!
FOLLOW NATIONAL, STATE, AND LOCAL CODES!
READ THESE INSTRUCTIONS ENTIRELY BEFORE INSTALLATION!
SymCom’s electronic overload relays are fully programmable for customized protection with a digital readout and RS-485 communications. The 777-MV-FT is designed for use, in conjuction with power transformers and external current transformers, on medium voltage systems. The 777-MV-FT also has a fast linear trip mode.
CONNECTIONS
1. Using the four corner tabs or the DIN rail mounting bracket, mount the
unit near the magnetic contactor. To use the DIN rail bracket,
hook the top clip first, then apply downward pressure until the lower clip
“clicks” onto the rail.
2. External current transformers must be used (see Figure No. 1 and Table
No. 1). SymCom recommends that the external CTs have terminals for
installation convenience. All CTs must be facing the same direction and all
CT secondaries must be wired identically (i.e., all “+” terminal connected
wires must enter the loop window from the same side).
3. Power input to unit may be three-phase or single-phase. Three-phase inputs
to the unit should have instrument transformers with 120 VAC secondaries,
5 VA minimum. A separate power supply potential transformer should be
used to power the contactor coil because its signal will vary as the load is
energized and de-energized.
3.1.Three-phase voltage input: 120V three-phase can be made available by
using three potential transformers in a wye-wye configuration. Reverse
phase, single-phase and unbalance protection is available when
using the wye-wye configuration shown in Figure 2a. The motor will not start
under the above voltage fault conditions. Connect the three-phase power
from the secondary of the potential transformers to “L1”, “L2” and “L3” on the
unit using a #12 - #18 AWG wire.
3.2.Three-phase voltage input: Alternatively, a three-phase voltage input may
be constructed by connecting two potential transformers in an open delta
configuration (See Figure 2b).
2880 North Plaza Drive, Rapid City, SD 57702 • (800) 843-8848
3.3.Single-phase voltage input: If only single-phase, 120V control power is available, insert control power into L1 and L2 inputs (See Figure 2c). L3 does not need to be connected. When single-phase voltage input is used, single-phase faults are detected only after the motor starts and reverse phase protection is not available.
NOTE: VUB setting must be set to “999” for proper operation with single- phase voltage input.
4. Connect the output relay to the circuitry to be controlled (see Figure No. 3).
To control a motor, connect the normally open contact in series with the magnetic coil of the motor starter as shown. To sound an alarm, connect the normally closed contact in series with the alarm (not shown).
FULL LOAD
AMPS
12.5-25
25-50
50-75
75-100
100-150
150-200
200-300
300-400
400-500
500-600
CT RATIO
PASSES THROUGH
777 WITH CT
SECONDARY
MULT PROGRAM SETTING
50:5
50:5
75:5
100:5
150:5
200:5
2
1
1
1
1
1
300:5
400:5
1
1
500:5 1
600:5 1
TABLE NO. 1: EXTERNAL CT SELECTION
25
50
75
100
150
200
300
400
500
600
Operation
The relay operation of SymCom’s overload relays is a fail safe design. This means when everything is within the limits programmed into the unit, the relay will energize; the normally open (NO) contact will close and the normally closed
(NC) contact will open. Once the unit has been wired and programmed, the unit is ready to operate. Turn the mode select to the “RUN” position. The display will show “RUN” alternating with a number (the numbers displayed will be the number corresponding to where the “DISPLAY/PROGRAM” knob is pointed). It will do this for the amount of time programmed into “RD1”. After this time has expired, the relay will energize (normally open will close and normally closed contact will open). If something else is in the display, see the troubleshooting section for more information. If the mode select is taken out of the “RUN” position, the units relay will de-energize.
06/26/03 -2-
-FT
FIGURE 1: TYPICAL WIRING DIAGRAM USING EXTERNAL CTs
NOTE: All potential transformers have 120VAC secondaries. The unit may be installed with three-phase voltage input (Figure No. 2,A & B); for full voltage monitoring and protection. If the single-phase voltage input is used (Figure No. 2, C), the 777-MV is a current monitor only.
FIGURE NO. 2: Potential Transformer Diagrams
-3- 06/26/03
-FT
FIGURE NO. 3: Typical control wiring diagram
PROGRAMMING
1. Select the feature to program by
rotating the “MODE SELECT” switch
to the desired position. The “MULT”
setting must be programmed before
any of the current settings to ensure
proper display of actual current
setpoints. Therefore, SymCom
-FT
recommends programming the “LV”
setting first, then move clockwise
through the postions to complete the
process.
2. Push and hold the RESET / PROGRAM button.
3. Rotate the DISPLAY / PROGRAM adjustment to the desired setting of the
feature as shown in the LED display.
4. Release the RESET / PROGRAM button. The unit is programmed when the
button is released.
5. Continue steps 1-4 until all features are programmed.
NOTE: Some “MODE SELECT” positions are dual functioning such as the
“#RU / ADDR” position. When the “MODE SELECT” switch is pointed at “#RU / ADDR,” you may view and program “#RU” and “ADDR.” To view the two settings rotate the “DISPLAY / PROGRAM” adjustment
across its entire range. You will see the “#RU” setting when the
“DISPLAY / PROGRAM” adjustment is between approximately 7 o’clock and 11 o’clock. You will see the “ADDR” setting when the “DISPLAY/PROGRAM”adjustment is between approximately
11 O’Clock and 5 o’clock. To program “#RU” or “ADDR,” follow the programming instructions above. The “#RU” setting will only be programmed when the “DISPLAY / PROGRAM” adjustment is between
approximately 7 o’clock and 11 O’Clock. Likewise, the “ADDR” setting will only be programmed when the “DISPLAY/PROGRAM”adjustment is between approximately 11 o’clock and 5 o’clock. “ADDR” settings will
06/26/03
be an “A” followed by a number between 1 and 99.
-4-
FAST LINEAR TRIP MODE
The Fast Linear Trip Mode provides an adjustable linear trip that can be used for very quick or very slow trips. The Model 777-FT family offers superior protection for sensitive motors, quick trips in test panels, and fast trips to protect high torque systems.
When the Fast Linear Trip Mode is activated (TC = J00), two new parameters,
“Motor Acceleration” time and “OverCurrent Trip Delay” are viewed and programmed in the RD1 and RD2 positions. The RD1 and RD2 setpoints are still valid, but can only be viewed and programmed by setting the trip class to any other class other than J00.
Note: Ensure Trip Class is set appropriately when changing RD1, RD2, MA,
or OCTD.
When the Fast Linear Trip Mode is used, the restart delays (RD1, RD2, and RD3) will be reduced by approximately 50%. Example: RD1 setting = 010; RD1 time = 5
PROGRAMMABLE PARAMETERS
NOTE: The unit can be programmed prior to installation by applying
120VAC to terminals ‘L1’ and ‘L2’.
The programmable parameters are the values the user must program to provide the correct protection for the application. All parameters are actual values except the “VUB” and “CUB’ settings, which are percentages. The range these parameters can be programmed to is found in the specifications at the end of the manual.
THE FOLLOWING ARE GENERAL RECOMMENDATIONS. THE MOTOR
MANUFACTURUR SHOULD BE CONSULTED FOR EXACT SETTINGS.
LV/HV-The recommended settings for “LV” (low voltage) and “HV” (high
voltage) depend on many factors such as motor usage, motor size,
environmental factors and tolerance of the motor. The motor
manufacturer should be consulted for “HV” and “LV” settings.
However, the NEMA MG1 standard recommends that “LV” and “HV” be
set to no more than 10% of the motor’s nameplate voltage. The setting
can be determined by multiplying the motor’s nameplate voltage by the
recommended percent over and under voltage (eg. The motor name
plate voltage is 4160 V. Potential transformer(s) is 4160V/120V.
Therefore, set “LV” to 0.9 x 120 = 108 and “HV” to 1.10 x 120 = 132).
“LV” can not be set higher than “HV”, so “HV” may have to be adjusted
higher before the proper “LV” setting can be programmed.
VUB- “VUB” is the voltage unbalance trip point. The NEMA MG1 standard
does not recommend operating a motor above a 1% voltage unbalance
without derating the motor. Voltage unbalance is determined from the
following formula:
-5- 06/26/03
Percent Unbalance =
Maximum Deviation from the Average
Average x 100
Example: The measured line-to-line voltages are 203, 210, and 212.
3
= 208.3
The maximum deviation from the average is the largest difference between the average voltage (208.3) and any one voltage reading.
208.3 - 203 = 5.3
210 - 208.3 = 1.7
212 - 208.3 = 3.7
The maximum deviation from the average is 5.3.
5.3
208.3
x 100 = 2.5% Unbalance
Note: A setting of “999” in this position will disable reverse phasing, single
phasing, and voltage unbalance protection. This setting should be
used when single-phase voltage control power is used. Single phase
faults will only be detected from current measurements after the
motor starts.
MULT- “MULT” is the multiplication factor for determining true current settings
based on current transformer ratio of external CTs. The appropriate
number can be determined from Table No. 1 on page 2. “MULT” must be
correctly programmed in order to accurately program the current settings.
OC- Represents the manufacturer’s maximum Service Factor Amperage (SFA).
The “OC” (overcurrent) setting depends on many factors such as motor
usage, motor size, environmental factors and tolerance of the motor. The
motor manufacturer should be consulted for “OC” settings. However, “OC”
is typically between 110% and 125% of Full Load Amperage (FLA).
UC- The “UC” (undercurrent) setting is typically set to 80% of full load
amperage (FLA). The overload relay with a “UC” setting of 80% of FLA
will typically detect a loss of load for many pumps and motors such as
a dry well condition for submersible pumps. The “UC” setting may be set
to 0.00 to disable undercurrent (loss of load) protection.
CUB- “CUB” is the current unbalance trip point. Most motor manufacturers
recommend operating under no more than 5% current unbalance,
therefore, a setting of “5” is a good place to start. However, your motor
manufacturer should be contacted for exact settings.
Note: Current unbalance is calculated the same way as voltage unbalance.
Note: A setting of “999” in this position will eliminate single phasing and
current unbalance protection.
TC- “TC” designates the trip class for overload protection. The trip class
defines the trip delay when an overload is detected. Trip class is
determined by the type of motor and application. Your motor manufacturer
should be consulted for the proper setting. Table No. 2 on page 9 shows
the trip class and a general description of the applications.
06/26/03 -6-
RD1- “RD1” is the rapid cycle timer. To view and adjust RD1, TC must not be
J00. It will engage when the motor is first powered-up or after the motor
controls shut down the motor. An “RD1” setting of 20-30 minutes will
generally protect the motor from rapid, successive power outages or short
cycling caused by the motor controls. A setting of 0 minutes will allow the
motor to start immediately after power-up or after a normal shutdown.
Note: In linear trip mode (TC = J00), the RD1 time is appoximately 50% of
the normal RD1 time. Example: If RD1 is set to 10 minutes, the
TC = J00, then the actual RD1 time in the linear trip mode will be 5
minutes.
Note: Display increments by 2.
RD2- “RD2” is the restart delay after the overload relay trips on current unbalance,
single phasing, and overload (if “oc” is programmed in “#RF”). To view and
adjust RD2, TC must not be J00. This delay allows the motor to cool down
after experiencing the above faults. It is also known as a motor cool down
timer. Your motor manufacturer should be contacted to determine this
setting. Under normal circumstances, a setting of 30-60 minutes will give
the motor enough time to cool down between faults. The Motor
Manufacturer should be consulted for their recommendation.
MA- In linear trip mode (TC = J00), the RD1 position becomes the motor
acceleration time. To view and adjust MA, TC must be J00. The motor
acceleration time is related to the load on a motor. For high inertia loads
such as fly wheels or conveyor systems, the motor acceleration time is
considerably longer than low inertia loads such as submersible pumps.
Therefore, “MA” is typically set higher for high inertia loads and lower for
low inertia loads. During the motor acceleration time, the linear overcurent
trip feature is ignored. Therefore, it is important not to set “MA” too high
because damage could occur to the motor. The minimum MA time is
0.158 seconds. The actual MA time is the display value times 0.158
seconds (±0.315 seconds). Example: If MA is set to 60, MA Time = (60 x
0.158 seconds) = 9.48 seconds ±0.315 seconds.
Note: In linear trip mode (TC = J00), the RD2 time is appoximately 50% of
the normal RD2 time. Example: If RD2 is set to 10 minutes, the
TC = J00, then the actual RD2 time in the linear trip mode will be 5
minutes.
OCTD- In linear trip mode (TC = J00), the RD2 position becomes the
Overcurrent Trip Delay. To view and adjust OCTD, TC must be
J00. This setting represents the maximum time that the
Model 777-MV-FT will tolerate an overcurrent condition before tripping.
The minimum OCTD time is 0.158 seconds. The actual OCTD is the
display value times 0.158 seconds (±0.315 seconds). Example: If
OCTD is set to 6, OCTD = (6 x 0.158 seconds) = 0.948 seconds ±0.315
seconds.
-7- 06/26/03
RD3- “RD3” is the restart delay after an undercurrent. It is also known as a dry
well recovery timer and is usually used in submersible pumping
applications. The setting of “RD3” depends on the recovery time of the
water well and varies widely from application to application.
Note: In linear trip mode (TC = J00), the RD3 time is appoximately 50% of
the normal RD3 time. Example: If RD3 is set to 30 minutes, the
TC = J00, then the actual RD3 time in the linear trip mode will be 15
minutes.
#RU- “#RU” is the number of successive restart attempts allowed after an under
current fault before the overload relay requires manual reset. A setting of
“0” is manual reset and a setting of “A” is continuously automatic reset.
ADDR-“ADDR” is the address setting for RS-485 communications. Available
settings are from A01 - A99. This setting is programmed on the right half
of the PROGRAM/DISPLAY adjustment (see programming instruction
note for explanation of dual function settings). You may ignore this
setting if RS-485 communications are not used.
#RF- “#RF” is the number of successive restart attempts allowed after a current
unbalance, single phasing or overload fault. The following settings are
available: “0”, “1”, “oc1”, “2”, “oc2”, “3”, “oc3”, “4”, “oc4”, “A”, and “ocA”.
A setting which includes “oc” will allow the overload relay to automatically
reset after an overload fault (eg., a setting of “oc2” will allow the overload
relay to reset 2 times after an overload condition, current unbalance, or
single phasing before locking out if an overload condition, current
unbalance, or single phasing is detected within one minute after
restarting). A setting which does not include “oc” requires a manual reset
for all overload faults. A setting of “0” is manual reset and a setting of “A”
is continuously automatic restart.
UCTD-“UCTD” is the undercurrent trip delay timer. This setting represents the
maximum time that the Model 777-MV-FT will tolerate an under current
condition. Typically, UCTD is set to 2 - 4 seconds.
GF- “GF” is the ground fault protection amperage threshold. This setting
detects a leakage current to ground and signals an insulation breakdown
in the system. The “GF” setting should be some where between 10% and
20% of the full load motor current. Short circuit protection is provided by
separate branch protective devices such as circuit breakers or fuses.
Ground fault protection is a Class II ground fault protector and should not
be used for personnel safety, but can be used to indicate motor
degradation for maintenance purposes.
06/26/03 -8-
Trip Class
5
10
15
20
30
J Prefix
J00
Application Description
Small fractional horsepower motors where acceleration times are almost instantaneous or where extremely quick trip times are required.
(Fast Trip) Hermetic refrigerant motors, compressors, submersible pumps, and general purpose motors that reach rated speed in less than 4 seconds.
Certain specialized applications.
(Standard Trip) Most NEMA-rated general purpose motors will be protected by this setting.
(Slow Trip) Motors with long acceleration times (>10 seconds) or high inertia loads.
Programming any of the above trip classes with the J prefix will enable jam protection. This additional protection is enabled 1 minute after the motor starts and provides a 2-second trip time for motors exceeding 400% SFA, regardless of trip class.
(Fast Linear Trip Mode) This setting provides an adjustable linear trip that can be used for very quick or very slow trips. This is used for sensitive motors, quick trips in test panels, and fast trips to protect high torque systems.
TABLE NO. 2: TRIP CLASS DESCRIPTIONS
10000
1000
100
10
Class 30
Class 20
Class 15
Class 10
Class 5
1
0 100 200 300 400 500 600
% of OC Setting
700 800 900 1000
FIGURE NO. 4: OVERLOAD TRIP CLASSES AND TRIP TIMES
PROGRAMMING EXAMPLES
#1 - Motor To Be Protected: 3∅, 4160 Volt, 400 Hp vertical hollow shaft pump
with a full load amperage of 56.2A and maximum service factor amps of
61.6. Three potential transformers (4160/120) have been installed in a
wye-wye configuration to allow three-phase voltage protection. This
voltage monitoring will disable the motor from starting on reverse-phase,
single-phase or unbalanced conditions. Use the following calculations and
reasoning to determine the appropriate settings for this application.
-9- 06/26/03
LV- 120 x 0.90 = 108
HV- 120 x 1.10 = 132
VUB- VUB = 5
MULT- From Table No. 1, MULT = 75 with 75:5 CTs
OC- Service Factor Amperage = 61.6
UC- FLA x 0.80 = 56.2 x 0.80 = 45.0
CUB- Manufacturer suggests 5
TC- TC = 010 (To program RD1 and RD2), then TC = J00
RD1- To protect the pump from rapid cycling and reduce the number of
starts per hour, RD1 = 10 (Display value) x 0.5 = 5 Minutes.
RD2- Since the motor is large it will cool off slowly, RD2 = 60 x 0.5 = 30
Minutes.
MA- MA = 64 (Displayed value) x 0.158 = 10.1 Seconds.
OCTD- OCTD = 10 (Displayed value) x 0.158 = 1.58 Seconds.
RD3- The well history shows that it will fully recover in 2 hours.
RD3 = 240 x 0.5 = 120 Minutes
#RU- In this application, we know that the well will eventually recharge
itself, #RU = A.
#RF- This well is known for sand to jam the impeller, therefore “oc”
should be included so that the pump will attempt to automatically
restart after an overloaded condition. History shows that 1 start
attempt usually clears the sand out of the impeller. #RF = oc1
UCTD- UCTD = 10
GF- Because it may take several days to get a new pump motor and
schedule for maintenance personnel to remove and replace the
pump motor, GF setting of 10% of full load amperage will give the
well owner enough time to prepare for pump replacement.
GF = 56.2A x 0.10 = 5.6
#2- Motor To Be Protected: 3∅, 4160 Volt, 200 Hp air compressor with a full
load amperage rating of 27A and maximum service factor amps of 30. One
4160/120 potential transformer is used for control power. Voltage monitoring
and reverse phase protection is not implemented. Use the following
calculations and reasoning to determine the appropriate settings for this
application.
LV- 120 x .9 = 108
HV- 120 x 1.1 = 132
VUB- Since L3 is not connected, VUB = 999
MULT- From Table No. 1, MULT = 50 with 50:5 CTs
OC- Service Factor Amperage = 30
UC- FLA x 0.80 = 27A x 0.80 = 21
CUB- Standard NEMA motor = 5
TC- General purpose motor = 20
RD1- Since this compressor takes about 60 seconds to bleed off excess pressure after a shutdown, setting RD1 = 002 will allow the compressor to unload before being restarted.
RD2- Because the motor may be hot from running in an unbalance or
06/26/03
single phase condition, a motor cool down time of 10 minutes,
-10-
RD2 = 10, should be appropriate.
RD3/#RU-Because an undercurrent would signal a serious problem in this application (a broken shaft or belt), #RU should be set = 0 for a manual reset. Therefore, RD3 does not have any function.
#RF- Because an overload (overcurrent) fault signals a serious problem in this application (e.g., worn bearings), “oc” should
not
be included in the #RF setting so that a manual reset after an overload fault is required. A #RF= 1 will give the system 1 chance to recover from an unbalance or single phasing problem before manual reset is required.
UCTD- Setting UCTD = 5 will allow normal operation and not allow the motor to run too long in an undercurrent failure mode.
GF- A ground fault setting of 15% of full load amps will be a significant indicator that the motor should be evaluated for repair or replacement. Therefore, GF = 27A x 0.15 = 4.0.
MULTI-FUNCTION SYSTEM DISPLAY
The output display can show various system operating parameters:
•
L1-L2 Voltage •L2-L3 Voltage •L3-L1 Voltage •Average Voltage
•
Average Current
•
A∅ Current •B∅ Current •C∅ Current
When the “MODE SELECT” switch is in the “RUN” position, the LED will display one of the above operating parameters. To select or change the displayed parameter, turn the “DISPLAY / PROGRAM” adjustment to the desired position as shown on the label.
The multi-function display also announces system faults such as low voltage, high voltage, single phasing, unbalance, and reverse phasing errors. Any time the “MODE SELECT” switch is in the “RUN” position, the “RESET / PROGRAM” button may be pushed to view the last fault which occured. Table No. 3 shows the possible messages.
DISPLAYED MESSAGE
oc
SP ub uc
CF
GrF
HI
Lo rP oFF
MEANING
Tripped on Overcurrent
Tripped on Single-Phasing
Tripped on Unbalance
Tripped on Undercurrent
Tripped on Contactor Failure
(Current Unbalance without Voltage Unbalance)
Tripped on Ground Fault
Preventing the motor from starting due to High Voltage
Preventing the motor from starting due to Low Voltage
Preventing the motor from starting due to Reverse Phasing
A stop command was issued from a remote source
TABLE NO.3: DISPLAY MESSAGES
-11- 06/26/03
TROUBLESHOOTING
PROBLEM
The unit will not start.
Display alternates “rP” with the
“DISPLAY / PROGRAM’ switch value.
SOLUTION
The voltage inputs are reverse phased. If this is the initial start up, swap the “L1” and “L3” leads to correct the problem. If the overload relay has been previously running, the power system has been reverse phased. Check the phase sequence of the incoming power lines.
The unit will not start.
Display alternates “SP”, “uB”,
“HI”, or “Lo with “DISPLAY /
PROGRAM” switch parameter value.
Display alternates “SP”, “uB”, or “oc” with “RUN”.
Display alternates “uc” with
“RUN”.
Display is showing a solid “SP”,
“uB”, or “oc”.
Display is showing a solid “uc”.
Display is showing a solid “CF”.
The incoming voltage is not within the limits programmed in the
“VUB”, “HV”, and “LV” settings. Adjust the “DISPLAY /
PROGRAM” switch to read the incoming line voltage values.
Correct the incoming power problem and check programmed limits to verify they are correct.
The overload relay has tripped on the fault shown on the display and is timimg down “RD2” before restarting.
The overload relay has tripped on undercurrent and is timing down “RD3” before restarting. If undercurrent is not a normal condition for this installation, check for broken shafts, broken belts, etc.
The unit has tripped on the fault shown and manual reset is required because of the programmed setting in”#RF”. Check the system for problems that would produce the single phase, overload, or current unbalance fault like a jam.
The unit has tripped on undercurrent and a manual reset is required because of the setting in “#RU”. Check the system for problems that would produce a loss of load like a broken belt or a pump is out of liquid.
The unit has tripped on a single phasing of the current, but was not single phased by the incoming power. Check for damaged contacts or loose wiring.
Any questions or comments call SymCom at 1-800-843-8848 or
1-605-348-5580
06/26/03 -12-
COMMUNICATIONS PORT / REMOTE RESET
The Model 777-MV-FT comes standard with a 9-pin sub-D connector for remote communications. The Model 777-MV-FT supports the RS-485 communication standard using the MODBUS protocol. This standard allows up to 99 Model 777-
MV-FTs to be controlled and monitored from a single remote personal computer.
Control and monitoring is also possible from SymCom’s RM-1000 and RM-2000.
PLC and SCADA systems using the RS-485 standard and MODBUS protocol can also be used.
NOTE: An RS-485MS-2W module is required to operate the communications bus. (Refer to RS-485MS-2W Installation Instructions for more information on this subject). The communications port also provides connections for remote reset as shown in Figure No. 6.
5 4 3 2
9 8 7 6
1
Normally Open Push Button
FIGURE NO. 6: REMOTE RESET CONNECTIONS
-13- 06/26/03
CLEARING LAST FAULT
The last fault stored can be cleared on the unit. This procedure is outline as follows:
1. Rotate the Mode Select Switch to GF .
2. Press and hold the Reset/Program Button. Adjust the Display/Program
adjustment until cLr appears on the display. Release the Reset/
Program Button.
To verify the last fault was cleared, place the Mode Select switch in the Run position. Then press and hold the Reset/Program Button, cLr should be on the display.
TAMPER GUARD
The unit can be protected from unauthorized program changes by locking in the setpoints.
This procedure is outlines as follows:
1. Rotate the Mode Select switch to GF .
2. Rotate Display/Program adjustment fully clockwise.
3. Press and hold the Reset Button. Adjust the Display/Program
adjustment until Loc appears in the display.
4. Release the Reset Button.
5. Turn Mode Select switch to run .
The program is now locked, but all settings can be viewed. The unit can be unlocked by following the procedure above except step three. This step should say: Press and hold the Reset Button. Adjust the Display/Program adjustment until unL appears in the display.
SymCom warrants its microcontroller based products against defects in material or workmanship for a period of five (5) years* from the date of manufacture. All other products manufactured by
SymCom shall be warranted against defects in material and workmanship for a period of two (2) years from the date of manufacture. For complete information on warranty, liability, terms, and conditions, please refer to the SymCom Terms and Conditions of Sale document.
* The 520 Series has a one (1) year warranty and the LSRU series has a two (2) year warranty.
06/26/03 -14-
SPECIFICATIONS
ELECTRICAL
Input Voltage
Frequency
Motor Full Load Amp Range
115 - 230 VAC, 1∅ OR 115 - 230, 3∅
(Programmable)
50 - 60 Hz
12.5 - 600 Amps, 3∅ (external CT’s)
Power Consumption
Output Contact Rating SPDT (Form C)
10 W (Maximum)
Pilot Duty Rating: 480 VA @ 240 VAC
General Purpose: 10 A @ 240 VAC
Expected Life
Mechanical
Electrical
Accuracy at 25 o
C (77 o
F)
Voltage
Current
GF Current
1 x 10
6
Operations
1 x 10
±1%
5
Operations at rated load
±3% plus CT accuracy
Timing
Repeatability
Voltage
±15%
5% ±1 second
±0.5% of nominal voltage
Current ±1% of nominal current
TRIP TIMES (Those not shown have user selectable trip times)
Ground Fault
101-200% of Setpoint
201-300% of Setpoint
301-400% of Setpoint
401% or Greater of Setpoint
Current Unbalance
1% Over Setpoint
2% Over Setpoint
3% Over Setpoint
4% Over Setpoint
5% Over Setpoint
6% Over Setpoint
10% Over Setpoint
15% Over Setpoint
SAFETY MARKS
UL
CE
Trip Time
8 Seconds ±1 Second
4 Seconds ±1 Second
3 Seconds ±1 Second
2 Seconds ±1 Second
Trip Time
30 Seconds
15 Seconds
10 Seconds
7.5 Seconds
6 Seconds
5 Seconds
3 Seconds
2 Seconds
UL508, UL1053
IEC60947-1, IEC60947-5-1
-15- 06/26/03
Standards Passed
Electrostatic Discharge (ESD)
Radio Frequency Immunity (RFI),
Conducted
IEC 1000-4-2, Level 3, 6 KV Contact, 8 KV Air
IEC 1000-4-6, Level 3 10 V/M
Radio Frequency Immunity (RFI), Radiated IEC 1000-4-3, Level 3 10 V/M
Fast Transient Burst IEC 1000-4-4, Level 3, 3.5 KV Input Power
Surge
IEC
ANSI / IEEE
Hi-Potential Test
Vibration
Shock
1000-4-5
Level 3, 2 KV Line-to-Line
Level 4, 4 KV Line-to-Ground
C62.41 Surge and Ring Wave Compliance to a
Level of 6 KV Line-to-Line
Meets UL508 (2 x Rated Voltage + 1000 Volts for
1 Minute
IEC 68-2-6, 10-55 Hz, 1 mm Peak-to-Peak, 2
Hours, 3 Axis
IEC 68-2-27, 30 G, 3 Axis, 11 mS Duration, Half
Sine Pulse
MECHANICAL
Dimensions
Terminal Torque
Enclosure Material
3.0” H x 5.1” D x 3.6” W
7 inch/pounds
Weight
Maximum Conductor Size Through Unit
ENVIRONMENTAL
Polycarbonate
1.2 pounds
0.65” with insulation
Temperature Range
Pollution Degree
Class of Protection
Ambient Operating: -20 o
- 70 o
C (-4 o
- 158 o
F)
Ambient Storage: -40 o
- 80 o
C (-40 o
- 176 o
F)
3
IP20, NEMA 1
06/26/03 -16-
PROGRAMMABLE OPERATING POINTS
LV- Low Voltage Threshold
HV - High Voltage Threshold
VUB - Voltage Unbalance Threshold
MULT - CT Ratio (xxx:5)
OC - Overcurrent Threshold
UC - Undercurrent Threshold
CUB - Current Unbalance Threshold
TC - Overcurrent Trip Class
**
RD1 - Rapid Cycle Timer
MA - Motor Acceleration Timer
RD2 - Motor Cool Down Timer
OCTD - Overcurrent Trip Delay (Linear)
RD3 - Dry Well Recovery Timer
#RU - Number of Restarts After UC Fault
ADDR - RS-485 Address
#RF - Number of Restarts After All Faults
Except UC
***
UCTD - Undercurrent Trip Delay
GF - Ground Fault Current Threshold
85 V - HV Setting
LV Setting - 264 V
2 - 15% or 999 (OFF)
25 - 600 Ratio
40 - 120% of CT Ratio
0, 20 - 100% of CT Primary
2 - 25% or 999 (OFF)
5, J5, 10, J10, 15, J15, 20, J20, 30, J30, or J00
0, 2 - 500 Minutes (x 0.5 if TC = J00)
0 - 250 x (0.158 through 0.315) Seconds
2 - 500 Minutes (x 0.5 if TC = J00)
2-250 x (0.158 - 0.315) Seconds
2 - 500 Minutes (x 0.5 if TC = J00)
0, 1, 2, 3, 4, or A (Automatic)
A01 - A99
0, 1, oc1, 2, oc2, 3, oc3, 4, oc4, A, or ocA
2 - 60 Seconds
10 - 20% of CT Primary or OFF
NOTES: SymCom’s Overload Relay can be preprogrammed prior to installation by applying
120 VAC between the L1 and L2 terminals.
** If J Prefix is displayed in trip class setting, jam protection is enabled.
*** If “oc” is displayed in the #RF setting, then Over Current will be included as a
normal
fault and the relay will automatically restart after RD2 expires, otherwise, manual
reset is required after an Over Current fault.
-17- 06/26/03
DIMENSIONS
������ ������
������
�������
������
�������
������
�������
DISPLAY MESSAGE
SYMCOM, INC.
800-843-8848 RAPID CITY, SD
������ �������
������ �������
������ �������
������
�������
�� ������ �������
������
��������
������
��������
06/26/03
������ �������
������ �������
-18-
INDEX
Clear Last Fault
Communications Port
Connections
Dimensions
Fast Linear Trip Mode
Multi-Function System Display
Operation
Programmable Operationg Points
Programming Examples
Programmable Parameters
Programming
Remote Reset
Specifications
Tamper Guard
Troubleshooting
Warranty
15
14
12
14
9
5
4
13
5
11
2
17
14
13
1
18
Visit our website at www.symcominc.com for our complete catalog and new product listings!
2880 North Plaza Drive, Rapid City, SD 57702
Phone: (800) 843-8848 or (605) 348-5580
FAX: (605) 348-5685
advertisement