Appleton's DPD Series Distribution Panelboards Catalog Pages

Appleton's DPD Series Distribution Panelboards Catalog Pages
DPD Series Distribution Panelboards
Flameproof
Zone 1 and 2 – 21 and 22
II 2 GD
ATEX / IECEx
IP66 / IK10
Applications
• Protection and control of electrical equipment in hazardous areas where ignitable vapors, gases or highly combustible dusts are present.
• For installation in:
— Chemical plants
— Petrochemical plants
— Refineries
— Other process industries in Zone 1 and 2 and Zone 21 and
22
• These compact units provide a centrally controlled switching system
• Lighting panelboards are available in 6, 12, 18 and 24 circuits.
• Heat tracing panelboards are available in 6, 12, 18 and 20 circuits.
DISTRIBUTION EQUIPMENT: PANELBOARDS
Distribution Equipment
Features
Available versions:
• 3- or 4-Pole isolator switch or main breaker.
• 1, 2, 3, 4 and 1+N poles branch circuit breakers.
— Branch circuit breaker available with B, C or D tripping curve.
— GFI branch circuit breaker available with B, C or D tripping
curves except for 1+N poles.
• Isolator and breaker handles included as standard, can be
padlocked in OFF position.
• Copper bus-bar as standard.
• Fully prewired on outgoing terminal block.
• M8 earth-crossing terminal.
• Hinged door.
• 4 fixing lugs.
• Cable glands and plugs to be ordered separately.
Standard Materials
• Housing: gray marine grade aluminum alloy
• Hardware: stainless steel
• Bus-bar: copper
Options
• Other rating and tripping curves.
• Other voltage.
• Indirect cable entries available through Ex e connection
enclosure.
• Switch rack assembly.
8 Circuit Panelboard
Certifications and Compliances
•
•
•
•
•
•
•
•
•
744
Certification Type CF
Zones 1 and 2
— Conforming to ATEX 94/9/CE: CE 0081
II 2 G
— ATEX/IEC Protection: Ex d IIB
— T Rating: T6 to T4
Zones 21 and 22
— Conforming to ATEX 94/9/CE: CE 0081
II 2 D
— ATEX/IEC Protection: Ex tD A21
— Surface Temperature: T 176 °F/T80 °C to T266 °F/T130 °C
Ambient Temperature: CF70B: -4 °F/-20 °C to +131 °F/+55 °C,
CF50B: -40 °F/-40 °C to +131 °F/+55 °C, CF60B: -58 °F/-50 °C
to +131 °F/+55 °C
CE Declaration of Conformity: 50229
ATEX Certificate: LCIE 02 ATEX 6057X
IECEx Certificate: IECEx LCI 08.023X
Other Certifications: GOST
Ingress Protection (solid and liquid): IP66
• Impact Resistance (shock): IK10
• Internal Volume: > 2 dm3 (2 liters)
• Ex Standards: EN/IEC 60079-0; 60079-1, 60079-7; 61241-0,
61241-1
• Product Standards: EN/IEC 60947-1; 60947-2; 60947-3
• Other Standards: EN/IEC 60529 (IP), 62262 (IK)
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010
DPD Series Distribution Panelboards
Flameproof
Zone 1 and 2 – 21 and 22
II 2 GD
ATEX / IECEx
IP66 / IK10
Catalog Numbering Guide
DPD
B
0
Series:
DPD - DPD Series
Zone 1, 2 – 21, 22
ATEX / IEC Certified
A
03
1 01 B
Panel Size Layout :
A
B
C
D
Main Protection:
B - Main Circuit
Breaker
S - Isolator Switch
#
GFI :
0 - without
1 - 30 mA (individual
branch)
2 - 300 mA (individual
branch)
3 - 30 mA (main
branch breaker)
4 - 300 mA (main
branch breaker)
E
F
G
H
Branch Breakers
Quantity:
03
06
08
09
12
18
24
Suffix for Other Options/Features:
Must be listed in
alphanumeric sequence
# - Customized
Panelboard
# 6 digit number will be
assigned at time of order
placement
Branch Circuit Breaker:
Number of Poles:
1 - 1-Pole
2 - 2-Pole
3 - 3-Pole
4 - 4-Pole
9 - 1-Pole + N
Curve:
B - Curve B
C - Curve C
D - Curve D
DISTRIBUTION EQUIPMENT: PANELBOARDS
Intensity:
01 - 1 A
20 - 20 A
02 - 2 A
25 - 25 A
03 - 3 A
32 - 32 A
04 - 4 A
40 - 40 A
06 - 6 A
50 - 50 A
10 - 10 A 63 - 63 A
16 - 16 A
 See DPD Series Distribution Panelboard Dimensions page for panel size dimensions.
 1+N pole is not for use with GFI.
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010
Distribution Equipment
Main Protection Value:
0 - 3 x 40 A
5 - 4 x 100 A
1 - 4 x 40 A
6 - 3 x 125 A
2 - 3 x 63 A
7 - 4 x 125 A
3 - 4 x 63 A
8 - 3 x 160 A
4 - 3 x 100 A
9 - 4 x 160 A
0
745
DPD Series Distribution Panelboards
Flameproof
Zone 1 and 2 – 21 and 22
II 2 GD
ATEX / IECEx
IP66 / IK10
Distribution Panelboard with Branch Circuit Breakers (for Lighting Circuits, etc.)
4-pole main isolator switch and 2-pole Branch Circuit Breakers Tripping Curve C wired on terminals.
Branch Circuit Breakers
2P - Curve C
Quantity
Rating
Type
Main
Switch
Layout
Panel
Cable
Entries
Volume
(dm3)
Weight
(lb/kg)
Catalog Number
CF50B
4 x 63 A
6
2P 16 A
A
1 x M32 - 6 x M20
100
529/240
DPDS3A06216C0
CF60B
4 x 63 A
12
2P 16 A
B
1 x M32 - 12 x M20
150
833/378
DPDS3B12216C0
CF70B
CF70B
4 x 125 A
18
2P 16 A
C
1 x M40 - 18 x M20
180
942/382
DPDS7C18216C0
4 x 160 A
24
2P 16 A
D
1 x M50 - 24 x M20
180
942/382
DPDS9D24216C0
DISTRIBUTION EQUIPMENT: PANELBOARDS
Distribution Equipment
Distribution Panelboard with GFI Branch Circuit Breakers (for Heat Tracing Circuits, etc.)
4-pole main isolator switch and 1-pole + N branch circuit breakers with GFI Branch Circuit Breakers Tripping Curve C wired on terminals.
Branch Circuit Breakers
N by 2-Poles - Curve C
Quantity
Rating
Type
Main
Switch
CF50B
4 x 63 A
6
16 A/30 mA
CF60B
4 x 63 A
12
16 A/30 mA
CF70B
4 x 125 A
18
CF70B
4 x 160 A
20
Layout
Panel
Cable
Entries
Volume
(dm3)
Weight
(lb/kg)
Catalog Number
E
1 x M32 - 6 x M20
100
529/240
DPDS3E06916C1
F
1 x M32 - 12 x M20
150
833/378
DPDS3F12916C1
16 A/30 mA
G
1 x M40 - 18 x M20
180
942/382
DPDS7G18916C1
16 A/30 mA
H
1 x M50 - 20 x M20
180
942/382
DPDS9H20916C1
Distribution Panelboard with GFI Branch Circuit Breakers (for Heat Tracing Circuits, etc.)
4-pole main isolator switch and 1-pole + N branch circuit breakers with GFI Branch Circuit Breakers Tripping Curve B wired on terminals.
Branch Circuit Breakers
N by 2-Poles - Curve B
Quantity
Rating
Type
Main
Switch
CF50B
4 x 63 A
6
CF60B
4 x 63 A
CF70B
CF70B
746
Layout
Panel
Cable
Entries
Volume
(dm3)
Weight
(lb/kg)
Catalog Number
16 A/30 mA
E
1 x M32 - 6 x M20
100
529/240
DPDS3E06916B1
12
16 A/30 mA
F
1 x M32 - 12 x M20
150
833/378
DPDS3F12916B1
4 x 125 A
18
16 A/30 mA
G
1 x M40 - 18 x M20
180
942/382
DPDS7G18916B1
4 x 160 A
20
16 A/30 mA
H
1 x M50 - 20 x M20
180
942/382
DPDS9H20916B1
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010
DPD Series Distribution Panelboard Wiring Diagram and Technical Data
Flameproof
Zone 1 and 2 – 21 and 22
II 2 GD
ATEX / IECEx
IP66 / IK10
Wiring Diagram
Branch Circuit Breaker Versions
GFI Branch Circuit Breaker Versions
4 x 63 A or 4 x 125 A or 4 x 160 A
Technical Data
GFI Branch Circuit Breaker
Outgoing
Incoming
Main Contacts
160 Amps
16 A
Rated Insulation Voltage (Ui)
690 V
800 V
800 V
400 Vac
Rated Operating Voltage (Ue)
415 V / 500 V / 690 V
415 V / 500 V / 690 V
415 V / 500 V / 690 V
230/400 Vac
Rated Operating Current (Ie)
63 A / 63 A / 40 A
125 A
160 A / 160 A / 125 A
16 A /30 amA
Rated Surge Voltage (Uimp)
8 kV
8 kV
8 kV
4 kV
50 kA (with fuse)
63 kA (with fuse)
80 kA (with fuse)
10 kA /400 V IEC 947.2
415 V
63 A
125 A
160 A
—
500 V
63 A
125 A
160 A
—
690 V
63 A
125 A
160 A
—
415 V
63 A
125 A
160 A
—
500 V
63 A
125 A
125 A
—
690 V
40 A
80 A
100 A
—
415 V
63 A / 30 kW
125 A / 55 kW
125 A / 75 kW
—
500 V
63 A / 30 kW
100 A / 55 kW
100 A / 75 kW
—
Short Circuit Resistance (Icu)
Switching Capacity
AC 21 A
Switching Capacity
AC 22 A
Switching Capacity
AC 23 A
690 V
Termination (Flexible / Solid)
40 A / 30 kW
80 A / 75 kW
80 A / 75 kW
—
0.006 to 0.054 in2 /
0.078 in2
4 to 35 mm2 / 50 mm2
0.006 to 0.078 in2 /
0.109 in2
4 to 50 mm2 / 70 mm2
0.006 to 0.078 in2 /
0.109 in2
4 to 50 mm2 / 70 mm2
0.0008 to 0.006 in2 /
0.002 to 0.009 in2
0.5 to 4 mm2/1.5 to 6 mm2
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010
747
DISTRIBUTION EQUIPMENT: PANELBOARDS
125 Amps
Distribution Equipment
63 Amps
DPD Series Distribution Panelboard Dimensions
Flameproof
Branch Circuit Breaker Version Dimensions
Layout Panel B
17.52”/445 mm
14.96”/380 mm
Layout Panel A
M8
4 Ø 0.43”/11 mm
M8
26.77”/680 mm
Fix. 24.25”/616 mm
17.91”/455 mm
Fix. 15.39”/391 mm
4 Ø 0.55”/14 mm
Distribution Equipment
Fix. 14.80”/376 mm
20.08”/510 mm
Fix. 14.80”/376 mm
20.08”/510 mm
M8
Layout Panel D
17.52”/445 mm
17.52”/445 mm
DISTRIBUTION EQUIPMENT: PANELBOARDS
Layout Panel C
M8
4 Ø 0.55”/14 mm
26.77”/680 mm
Fix. 24.25”/616 mm
26.77”/680 mm
Fix. 24.25”/616 mm
4 Ø 0.55”/14 mm
Fix. 22.68”/576 mm
27.95”/710 mm
Fix. 22.68”/576 mm
27.95”/710 mm
748
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010
DPD Series Distribution Panelboard Dimensions
Flameproof
GFI Branch Circuit Breaker Version Dimensions
Layout Panel F
17.52”/445 mm
14.96”/380 mm
Layout Panel E
M8
M8
4 Ø 0.43”/11 mm
Fix. 14.80”/376 mm
20.08”/510 mm
Distribution Equipment
26.77”/680 mm
Fix. 24.25”/616 mm
17.91”/455 mm
Fix. 15.39”/391 mm
4 Ø 0.55”/14 mm
Fix. 14.80”/376 mm
20.08”/510 mm
17.52”/445 mm
M8
Layout Panel H
DISTRIBUTION EQUIPMENT: PANELBOARDS
17.52”/445 mm
Layout Panel G
M8
4 Ø 0.55”/14 mm
26.77”/680 mm
Fix. 24.25”/616 mm
26.77”/680 mm
Fix. 24.25”/616 mm
4 Ø 0.55”/14 mm
Fix. 22.68”/576 mm
27.95”/710 mm
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010
Fix. 22.68”/576 mm
27.95”/710 mm
749
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertising