Precision Circuits Inc
I/O Modules
Display Panels
Power Control System
Precision Circuits Inc
Service
50A GEN
30A 20A
Status
W/H
A/C-2
A/C-1
SELECT
00-10024-000 00-10024-100
120V Energy Management features usually found in high end Class A Motor homes are now made affordable for all RV's including Class C and Trailer Market. The
Mini-PCS monitors the total AC current of an RV and prevents circuit breaker tripping by momentarily shedding up to four loads. As the owner turns on additional appliances such as a Microwave, Coffee Pot, or Hair Dryer, the Mini-PCS can shed two 120VAC appliances such as the Refrigerator and Water Heater, then if additional reduction in power is required the second air conditioner, and lastly the first air conditioner is shed. As the owner selected appliances are turned off, the Mini-PCS will automatically turn power back on to each of the shed loads in reverse sequence. The
Mini-PCS will constantly monitor 120VAC RV power and shed and restore power to the four controlled loads.
Power Control System
Precision Circuits Inc
Service Status
50A GEN
30A 20A
SELECT
REFR
W/H
A/C-2
A/C-1
Power Control System
AC Amps
Precision Circuits Inc
Service Status
50A GEN
30A 20A
SELECT
REFR
W/H
A/C-2
A/C-1
The I/O Module is installed inside any circuit breaker panel and fits into a standard 3/4" knock-out hole. The screw terminals are used to make the 120VAC connections. Outside the circuit breaker panel a data cable is connected through the 3/4" knock-out which goes to the Display Panel. The Display Panel has a Data connector and also another connector to control the air conditioner units through low voltage signals.
Key Features:
1. Helps owners who are use to 50amp service, deal with the common situation of camp grounds where only
30amp service is available.
2. Limits total current to 30 amps, when 50amp service is not available.
3. Minimizes Circuit Breaker Tripping.
4. Monitors current draw for entire RV including owner added loads.
5. Learns controlled appliance current draw.
6. Allows 2 air conditioners to run on 30 amp service when other appliances are not in use.
7. I/O Module fits into a standard 3/4" knock-out
Two Relays capable of 120VAC 18 Amp load.
8. 120VAC Sense
I/O Module has built in 120VAC sense circuitry so that it knows when shore power is available and does not draw on the battery when dry camping. No AC wall adaptor or other sensors required.
9. Display Panel has built in relays to control two air conditioners, no other modules required.
10. All relays are normally closed allowing full operation of appliance in case of fault.
700 South Road Lisle, IL 60532 www.PrecisionCircuitsInc.com 630-240-9832 Rev C
Precision Circuits Inc
Operation:
30-amp Service -
PCS
senses 0VAC between L1 and L2.
The I/O Module has a current sensor which monitors the current on the neutral wire. When the current exceeds the
30-amp limit, because possibly the owner has turned on the
Microwave, the
Mini-PCS will limit the current by shedding appliances. Once the total RV current has dropped, for example because an owner operated appliance has been turned off, the
Mini-PCS will reverse the above procedure, returning power to appliances whose operation was not immediately critical. Appliance shed order is easily determined by the manufacturer by wiring the appliances to the appropriate number relay.
20-amp Service -
Mini-PCS senses 0VAC between L1 and L2, and the owner selects 20A on the Remote Display.
Mini-PCS
performs the same functions as above except that it limits total current to 20amps.
Generator - Mini-PCS
senses power to the
Genenerator Hour Meter. In this mode Mini-PCS assumes enough power is available and goes to sleep. It displays the fact that Gen-Set is running, that all Loads are powered.
50-amp Service - Mini-PCS senses 240VAC between
L1 and L2 to determine this mode of operation. In this mode
Mini-PCS assumes enough power is available and goes to sleep. It displays the fact that 50-amp Service is available and that all Loads are powered.
I/O Module - Features include:
!
Current Sensor
!
Two 18amp Relays
!
Power Line sensing
!
Two Screw Terminal configurations available
Remote Display - Features include:
!
Displays Service Type
!
Displays the Status of the Controlled Appliances
!
Custom Load Names available
Specifications:
Part Numbers: 00-10024-000 Mini- PCS I/O Module, w/Vertical Terminals
00-10024-100 Mini- PCS I/O Module, w/Right Angle Screw Terminals
00-10025-000 Mini-PCS Display Panel, 3 Loads, W/H, A/C-2, A/C-1
00-10025-100 Mini-PCS Display Panel, 4 Loads, Refr, W/H, A/C-2, A/C-1
00-10025-500 Mini-PCS Display Panel, Amp Meter, 4 Loads, Refr, W/H, A/C-2, A/C-1
Service type:
Relays:
Delay:
Environment:
Dimensions:
Mounting Hole:
120/240VAC max
(2) DC 16VDC, 1.0A (Display Panel, Thermostat)
(2) AC 120VAC, 18A, 1HP (I/O Module)
2 minute minimum off time on all loads
Indoor, Out of direct weather
6.25" wide, 3.20” high, 1.0” deep
5.45” wide, 2.91” high (centered with .15" clearance), .188" mount holes
Volts DC
Volts AC
Ambient Temperature
Minimum
9.0VDC
90VAC/line
Typical
12.0VDC
240VAC
Maximum
16.0VDC
135VAC/line
Display Panel Low Voltage Connector:
01 AIR COND 1 NC
02 AIR COND 1 COM
03 NO CONNECT
04 AIR COND 2 COM
05 AIR COND 2 NO
06 AIR COND 1 NO
07 GEN SET RUN
08 COACH BAT
09 GROUND
10 AIR COND 2 NC
AIR COND 2 NO
AIR COND 2 COM
NO CONNECT
AIR COND 1 COM
AIR COND 1 NC
Mating Connector: MOLEX MINI-FIT JR 10-PIN, #39-01-2100
Contact: MOLEX MINI-FIT JR 5556 18-24 AWG, 39-00-0039
AIR COND 2 NC
SYSTEM GROUND
COACH BATTERY
GEN-SET HOUR METER
AIR COND 1 NO
View of connector is from contact insertion side
Four different Air Condition Compressor wiring options are shown above. Relay Contacts are drawn in Non-Shed or Operation Mode.
Option 1, A/C sheds with Ground Signal
NC
Connect to Ground
COM
NO
Connect to Air Cond
Option 2, A/C sheds with +12V Signal
NC
Connect to +12V
COM
NO
Connect to Air Cond
Option 3, A/C operates with Ground Signal
NC
Connect to Air Cond
Connect to Ground
COM
NO
Option 4, A/C operates with +12V Signal
NC
Connect to Air Cond
Connect to +12 V
COM
NO
RJ12
4
5
6
1
2
3
Current Sense -
Current Sense +
Common
Line Sense
Relay 1 Coil
Relay 2 Coil
Data Cable
4
5
6
1
2
3
RJ12
RELAY 1
COM
VOLT SENSE
NC
COM NC
RELAY 2
R1
L1
N
L2
R2
To Load
L1 Breaker
To Neutral Bar
L2 Breaker
To Load
Route Main
Neutral Wire through this
Current Sensor
Hole.
I/O Module Screw Terminal Block Torque: 9-in-lbs
Note: The three Voltage Sense terminals must always be wired for proper
Service Type detection, even if corresponding relays are not used.
700 South Road Lisle, IL 60532 www.PrecisionCircuitsInc.com 630-240-9832