UVDI V-Mod Coil Irradiator Owner's Guide
The V-Mod Coil Irradiator is a flexible UV-C disinfection system designed for use in HVAC systems. It can be easily installed in almost any system, large or small. The V-Mod features a modular design that allows for easy installation and maintenance. It can be used to irradiate coils and drain pans, reducing microbial growth and promoting energy efficiency.
advertisement
Assistant Bot
Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.
V-Mod
®
Coil Irradiator
Owner’s Guide
1
17-3017 Rev I, 10/08/07
Important Safety Information:
UV-C exposure is harmful to the skin and eyes. Looking at an illuminated UV-C lamp can cause permanent blindness. UV-C skin exposure can cause cancer.
Always disconnect power before servicing. Do not operate if disconnect switch has not been disabled
This device contains mercury in the sealed ultraviolet bulb(s). Do not place your used bulb(s) in the trash. Dispose of properly.
IMPORTANT: ALWAYS RUN POWER SUPPLY THROUGH ELECTRICAL
INTERRUPTER (RELAY, CONDUCTOR OR SIMILAR DEVICE) CONTROLLED BY
ELECTRICAL INTER-LOCK SWITCH (P/N 18-6001) SO POWER TO FIXTURES IS CUT-
OFF WHEN SPACE IS ACCESSED.
WARNING: UV-C EXPOSURE IS HARMFUL TO SKIN AND EYES. LOOKING AT
ILLUMINATED UV-C LAMPS CAN CAUSE BLINDNESS AND SKIN DAMAGE.
Product Registration
Thank you for purchasing this product from UVDI! Prior to any other installation activities, please proceed with registering you product via the web at
http://www.altruv.com
or by returning the enclosed self-addressed postcard. Product registration will insure that your warranty is handled in a proper and expeditious manner. In addition, it will allow UVDI to provide you with important updates regarding your new product including reminders of when replacement parts are needed and also make you eligible for future parts discounts.
2
17-3017 Rev I, 10/08/07
Application:
The V-Mod’s flexible design allows for ease of installation in almost any system, large or small. V-
Mod fixtures plug one into the other in series, in any orientation, which eliminates individual wiring to each fixture. The nominal lengths (18”, 24” & 36”) can accommodate almost any installation.
The V-Mod functions as either a “side access” system or in a traditional “built-up bank” arrangement. This is made possible through the use of an exclusive stainless steel channel
“mounting rail” and fixture design. The combination becomes an optional sliding mechanism when needed. The V-Mod may be installed to irradiate coils and drain pans where UVC degrades organic and microbial build-up to save significant energy and maintenance costs. They are also used in return and supply ducts, mixed air plenums, to irradiate filters, and in exhaust systems. Once installed, the fixture position can be permanently fixed or left to slide out of the plenum through an access panel.
Specifications
Electrical Rating
Power Rating: 120VAC, 60Hz.
Electrical installation should be conducted by professional support personnel and in accordance with NEC regulations, and local building codes.
UVDI Fixture
Part Number
17-1001
(17-1001-01)
17-1011
(17-1011-01)
17-1021
(17-1021-01)
Germicidal Lamp Wattage
25
20
30
Input Power (Amps)
.5
.5
.7
Temperature Ratings:
Ambient Temperature Range: 50º F to 135º F
Relative Humidity: Up to 95% RH, non condensing
Approvals:
Underwriters Laboratories: File no.E212213, Vol. 1, Sec. 3.
The health aspects associated with the use of this product and its ability to aid in disinfection of environmental air have not been investigated by UL.
3
17-3017 Rev I, 10/08/07
Installation
Figure 1. Typical Installation
!
!
!
!
!
!
All Installations – Parts List
!
One (or more) Mounting Rail (17-4022 / MR-96)
!
One (or more) V-Mod Fixture with Lamp (17-1001 / VM-18-120, 17-1011 / VM-24-120, 17-
1021 / VM-36-120)
One (or more) Hard Wire Module (17-4018 / HWR-120V)
Two (or more) Vertical Supports – Angle Iron, U-Channel Unistrut, Square Unistrut – supplied by others
One (or more) Access Saftey Switch (18-6001 / UVDI-SS)
One (or more) Relay (Third Party Hardware supplied by others - Recommended Relay or
Contactor’s load capability; 4 amps per one installed V-Mod Fixture. Example: QTY
10 Installed V-Mods = 40 amp AC (min) Relay or Contactor. QTY 40 Installed V-
Mods = 160 amp AC (min) Relay or Contactor.)
!
One view port / access door (optional – 17-4013 / GVP or 17-4028 / VM-AD or 17-4023 /
VM-AVD)
Mounting Brackets (Third Party Hardware supplied by others)
Replacement Lamps (Recommended but optional)
4
17-3017 Rev I, 10/08/07
Build-Up Installation Steps:
1. Compare packing list with equipment received to confirm receipt of all equipment necessary for installation. (Consult your UVDI/Altru-V Representative or Distributor for a detailed drawing of where to properly mount rails and fixtures – See example on Page 4)
2. Measure the width of the cooling coil or target surface and the inside dimension of the plenum to insure combination of fixtures will fit in plenum.
3. Using the inside plenum dimension, measure and mark mounting rail so the mounting rail fits within the plenum walls. (P/N 17-4022)
4. With appropriate saw, cut the mounting rail to length
5. If length of the combined fixtures is longer than a single mounting rail, the Mounting Rail will need to be spliced together (see example).
Installation Tip #1- Splicing Mounting
Rails:
Splicing can be accomplished by first measuring and marking the extra length required using a square. Then using a hack saw or other cutting device; cut the rail to length. Next cut an 8” splice piece from the
Figure 2: MUST BE FLUSH
See Figure 3 for a detail of a Mounting Rail
Splice. (Pg.# 6) remainder of rail material. To secure the splice you must join the three pieces of rails together as seen in the example. Clamping and alignment are important to ensure that the track is square, and butted tightly together. At this point, drill 4 holes minimum (two each side) at 1” and 3” on both ends of splice as seen in the example. Once completed bolt together pieces and tighten. *Note: When you
are done creating the splice, track must be straight and aligned to not have any gaps, overlapping, or sagging of any kind. Track should be one continuous line and have a smooth transition.
5
17-3017 Rev I, 10/08/07
Figure 3
6
17-3017 Rev I, 10/08/07
6. Vertical supports (not supplied) will be necessary to mount the rail. The rail can overhang the vertical supports by no more than 24”. Mount vertical supports roughly 12”-15” from face of target surface.
Figure 4
Note: all dimensions given in Figure 4 are Maximum Recommended Dimensions.
7. Rails must be installed with notches facing downward.
Installation Tip #2- Support Placement:
When using only one rail length for the assembly, it is acceptable to use only two vertical supports. However, when additional rail lengths are required for the assemblies and where a splice is used, vertical supports must be a
maximum 48” on center.
7
17-3017 Rev I, 10/08/07
8. Secure mounting rail to vertical support using a bolt and pre-punched holes in mounting rail. If needed, drill holes in mounting rail to ensure a level rail.
Figure 5
Note: all dimensions given accept as noted in Figure 5 are Maximum Recommended
Dimensions.
Installation Tip #3:
R ails must be secured to the vertical supports to not have any buckle or binding of the rail, allowing rail to be straight and true.
8
17-3017 Rev I, 10/08/07
9. On the Rail end opposite the power source, drill a hole for a screw to act as a rail stop for the fixtures. Insert a sheet metal screw into the hole and tighten. This screw is meant to ensure the fixtures cannot slide off the end of the rail.
10. Slide the first fixture on the track with the male plug towards the stop screw. Slide the correct combination of fixtures onto mounting rail(s) so that the male end of the fixture plugs into the female receptacle of the next. Repeat until all fixtures are mounted on rail.
11. At the terminal end of the fixture row, slide the Hard-Wire Module (P/N 17-4018) onto the rail, plugging the male plug into the female receptacle of the last fixture. Using the screw provided, secure the Hard-Wire Module to the mounting rail. Ensure the fixtures will not slide off this side of the rail.
12. Install the End Cap. (see detail on page 11.)
13. Repeat steps 6-11 until each row is complete
NOTE: The Hard-Wire Module was designed for hardware connection to 120V/60Hz circuit and will accept standard ½” conduit fittings.
NOTE: Electrical installation shall be conducted by a certified or licensed professional support personnel and in accordance with NEC regulations, and local building codes. Please see Fig. 6 (pg. 12) and Fig. 7 (pg. 12) for Wiring diagram and electrical assembly instructions.
14. Remove the Hard Wire Module cover to provide access. Power to fixtures should be controlled by a safety switch(s) that will cause the UV fixtures to be shut-down if the space is accessed.
IMPORTANT: ALWAYS RUN POWER SUPPLY THROUGH ELECTRICAL
INTERRUPTER (RELAY, CONTACTOR OR SIMILAR DEVICE) CONTROLLED BY
INTER-LOCK SWITCH SO POWER TO FIXTURES IS CUT-OFF WHEN SPACE IS
ACCESSED.
9
17-3017 Rev I, 10/08/07
15. Caution/Safety warning labels are provided with each lamp fixture. LABELS MUST BE
AFFIXED TO ANY ACCESS PANEL OR DOOR TO WARN PERSONNEL THAT UV
EQUIPMENT IS INSTALLED.
WARNING: UV-C EXPOSURE IS HARMFUL TO SKIN AND EYES. LOOKING AT
ILLUMINATED UV-C LAMPS CAN CAUSE BLINDNESS AND SKIN DAMAGE.
16. Insert lamps. Place a log sheet (see insert 21-1025) at nearest access point and note the date of installation. It is recommended to log inspections on this datasheet as well to ensure timely replacement of lamps.
IMPORTANT: UVC LAMPS SHOULD BE REPLACED EVERY 12 MONTHS (8760
HRS).
10
17-3017 Rev I, 10/08/07
V-Mod End-Cap Installation
Tang Hole – circled Cap Lock Slot - Circled
1. Observe both the tang-hole at the male end of the V-mod also the slot at the connector between the plastic and metal surface. This is where the tang and lock tab will be inserted using the end cap.
End Cap Tang and Cap Lock - Circled
2. Insert end cap tang into the hole located at the end of the V-mod and slide forward while rotating the end cap so as to cover the V-mod electrical connector, at the same time shifting the locking tab approximately ¼ inch adjacent the lamp connector. Slip the Cap Lock inside the Cap Lock Slot behind the electrical connector and the metal surface shown earlier
3. Slide end cap down assuring the locking tab is in place and is flush to surfaces as seen here.
NOTE: check installation to ensure that End-Cap is flush with the V-Mod fixture.
11
17-3017 Rev I, 10/08/07
Electrical Configuration Recommendations:
Figure 6
Figure 7
12
17-3017 Rev I, 10/08/07
Alternate Installation Instructions for Side Mount Installation:
1. Identify location Mounting Rail and fixtures, recommended roughly 12”-15” from face of target surface is the optimum location. If there is no access to area, create an access hole and use V-
Mod Access /View Port Accessory (P/N: 17-4023) or V-Mod Access Door (P/N: 17-4028).
2. Measure the width of the cooling coil or target surface and the inside dimension of the plenum to insure combination of fixtures will fit in plenum.
3. Using the inside plenum dimension, measure and mark Mounting Rail (P/N 17-4022).
4. With appropriate saw, cut the Mounting Rail to length.
5. If length of the combined fixtures is longer than a single Mounting Rail, the Mounting Rail will need to be spliced together (see example Figure 2 on page 7).
6. Vertical supports (not supplied) will be necessary to mount the rail. The rail can overhang the vertical supports by no more than 20”, or it can be directly mounted to the inside of the plenum.
(Note: Mount vertical supports roughly 12”-15” from face of target surface).
7. Secure Mounting Rail to vertical support through pre-punched holes using a bolt. (Note:
“notched” edge of rail should face downward to insure proper sliding of fixtures) See Tech Tips
Insert on how to use notches (If you did not receive the insert, request P/N 21-1025).
8. On the opposite end of the rail from the Access Door, slide the Hard-Wire Module (P/N 17-
4018) onto the rail and secure using the screw provided.
13
17-3017 Rev I, 10/08/07
9. Slide correct combination of fixtures onto Mounting Rail(s) so that the female end goes on the rail first. Slide end “plugs” into Hard Wire Module at the opposite end of the unit.
10. At the terminal end of the fixture row, slide the Hard-Wire Module (P/N 17-4018) onto the rail, plugging its male end into the female end of the last fixture. Using the screw provided, secure the
Hard-Wire Module to the mounting rail. Ensure the fixtures will not slide off this side of the rail.
11. Install the End Cap. (see detail on page 11.)
12. Repeat steps 7-10 until each row is complete.
13. The Hard-Wire Module was designed for hardware connection to 120V/60Hz circuit and will accept standard ½” conduit fittings.
14. Electrical installation should be conducted by professional support personnel and in accordance with NEC regulations, and local building codes. Please see Fig. 6 (pg, 12) and Fig. 7 (pg. 12) for
Wiring diagram and electrical assembly instructions.
15. Remove the Hard Wire Module cover to provide access. Power to fixtures should be run through a safety switch (s) that will cause the UV fixtures to be shut-down if the space is accessed.
16. Caution/Safety warning labels are provided with each lamp fixture. LABELS MUST BE
AFFIXED TO ANY ACCESS PANEL OR DOOR TO WARN PERSONNEL THAT UV
EQUIPMENT IS INSTALLED.
IMPORTANT: ALWAYS RUN POWER SUPPLY THROUGH ELECTRICAL
INTERRUPTER (RELAY, CONDUCTOR OR SIMILAR DEVICE) CONTROLLED BY
ELECTRICAL INTER-LOCK SWITCH (P/N 18-6001) SO POWER TO FIXTURES IS CUT-
OFF WHEN SPACE IS ACCESSED.
17. Insert lamps.
Replacement Lamps
UVDI Fixture
Part Number
Replacement Lamp
Part Number
17-1001
(17-1001-01)
17-1011
(17-1011-01)
Single: 07-4000
25-Pack: 07-5006-04
Single: 07-4001
25-Pack: 07-5006-05
17-1021
(17-1021-01)
Single: 07-4002
25-Pack: 07-5006-06
14
17-3017 Rev I, 10/08/07
NOTES
15
17-3017 Rev I, 10/08/07
Equipment Warranty
UltraViolet Devices, Inc. (UVDI), warrants to original Buyer for one year from the date of original installation, or eighteen (18) months from date of shipment, whichever comes first, that its goods are free from defect in material and workmanship under normal use and service. UVDI’s obligation under this warranty shall be limited to the repair or replacement of those goods which prove defective, provided that such products are installed, maintained, and operated for the purpose and in the manner intended and for which UVDI instructs or recommends. Neither UVDI nor its dealers shall be liable for any special or consequential damages directly or indirectly arising from the design, construction, installation, servicing, or operation of the goods. THIS IS UVDI’S SOLE WARRANTY. NEITHER UVDI NOR ITS
DEALERS MAKE ANY OTHER WARRANTY OF ANY KIND, EXPRESSED OR IMPLIED. ALL IMPLIED
WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE WHICH EXCEED
UVDI’S AFFORESTATED OBLIGATIONS ARE HEREBY DISCLAIMED AND EXCLUDED FROM THIS
WARRANTY.
UVDI AND ITS DEALERS’ LIABILITY UNDER THIS WARRANTY SHALL IN NO EVENT EXCEED THE COST
OF THE GOODS SOLD UNDER THIS CONTRACT OF SALE. UVDI neither assumes, nor authorizes any person to assume for it, any obligation in connection with the goods. This warranty shall not apply to any goods (a) which have been subjected to misuse, tampering, negligence, or accidents; or (b) the serial numbers of which have been altered, defaced, or removed; or (c) which have been used in a manner contrary to UVDI’s instructions or recommendations.
Buyer shall not return to UVDI any allegedly defective goods without UVDI’s prior written authorization. This warranty may not be assigned or transferred.
Product Registration
It is highly recommended that you register you product via the web at http://www.altruv.com/ or return the enclosed selfaddressed postcard to UVDI. Product registration will insure that your warranty is handled in a proper and expeditious manner. In addition, it will allow UVDI to provide you with important updates regarding your new product including reminders of when replacement parts are needed and also make you eligible for future parts discounts.
Manufactured by:
26145 Technology Drive
Valencia, CA 91355
(877) PUREUVC
(661) 257-4698 fax www.uvdi.com
& www.altruv.com
Specifications subject to change without notice.
©Altru-V and V-Mod are brands owned by UVDI.
Copyright © 2003 by UltraViolet Devices, Inc. All rights reserved.
16
17-3017 Rev I, 10/08/07