380 - 415V LOW AMBIENT KIT TOP EER LOW NOISE LEVEL

380 - 415V LOW AMBIENT KIT TOP EER LOW NOISE LEVEL
380 - 415V
LOW AMBIENT KIT
TOP EER
LOW NOISE LEVEL
R-410A
SUPER DIGITAL INVERTER 3N
OUTDOOR UNIT
Toshiba outdoor units are equipped with a
Super Digital Inverter - energy savings of up to 60%
rotary compressor for a high reliability, a
compared to fix-speed units
high efficiency and a low noise level.The
Superior EER (Energy efficiency ratio)
compact and lightweight design guarantees
an easy and convenient installation.
Twin rotary compressor
Furthermore they are fitted with a smaller
CFC-free refrigerant R410A
piping diameter than conventional models,
Toshiba Hybrid Inverter PAM & puls wide modulation
which leads to an easier installation, shorter
installation time and lower installation
costs.
For quickly reaching the desired
Compact and space-saving design - the weight is up to
35% lower than with comparable F/S-models
Quiet operation
temperature the Inverter-controller uses
Heat pump system (cooling & heating)
PAM (pulse amplitude modulation, varies
Cooling down to an outside temperature of minus 15 °C
the voltage while pulse wide remains), then
possible
it changes to pulse wide modulation (low
voltage with modulated pulse wide) to
control compressor speed and to maintain
accurate temperatures with reduced energy
consumption.
RAV-SP1104AT8-E
Technical data Heat pump
Outdoor unit
Cooling capacity (cooling)
kW
10,00
Range of performance (cooling)
kW
2,60 - 12,00
Heating capacity (heating)
kW
11,20
Range of performance (heating)
kW
2,40 - 15,60
Energy label (cooling)
A++
Energy label (heating)
A+
Efficiency (EER) (cooling)
4,22
Efficiency (COP) (heating)
4,63
Efficiency (SEER) (cooling)
6,57
Efficiency (SCOP) (heating)
4,28
Power supply
V
400
Fusing
A
3 x 20
Power consumption (cooling)
kW
0,66 - 3,60
Power consumption (heating)
kW
0,53 - 4,30
Dimensions (H/W/D)
mm
1340x900x320
kg
95
Air power volume
m³/h
6060
Sound pressure level (cooling)
db(A)
49
Sound pressure level (heating)
db(A)
50
Sound power level (cooling)
db(A)
66
Sound power level (heating)
db(A)
67
Pipe dimension liquid
mm/"
9,5 (3/8)
Pipe dimension gas
mm/"
15,9 (5/8)
Pipe length, maximum
m
75
Pipe length, pre-charged
m
30 (40g/m)
Refrigerant, charged
kg
3,10
Height difference (outdoor unit higher/lower)
m
30
Outdoor temperature (cooling)
°C
-15 - +46
Outdoor temperature (heating)
°C
-20 - +15
Net weight
www.toshiba-aircondition.com