SUGGESTED SPECIFICATIONS FOR VENTILATOR MODEL DD
Exhaust Ventilator to be SOUTHERN ENGINEERING SYSTEMS by Duke Mfg Co., model DD,
Type I, UL Listed, and in compliance with NFPA Bulletin 96. Ventilator shall be high velocity, low
volume, wash type and have a nominal 95% grease extraction efficiency certified by an independent
testing laboratory.
Canopy, constructed of 18 gauge stainless steel (where exposed) with bottom perimeter edges gutter
less. Weld extraction chamber, plenum, and external seams and joints to form a liquid tight construction.
Polish stainless steel to a #3 finish.
Exhaust plenum Extraction Chamber to be single inlet, same material as canopy, full length of section
at the back. Furnish water wash manifold consisting of a series of spray nozzles installed within
chamber. Manifold to be positioned within plenum area out of air-stream to minimize nozzle clogging.
Bottom of exhaust plenum to be formed into a pitched trough to allow laminar flow, during wash cycle,
to drain pipe connection.
Water Wash System to serve the dual purpose of daily cleaning and fire control. The wash cycle shall
be initiated when the stop-wash button on the control cabinet (required with each hood system) is
depressed. Internal cleaning will be achieved by means of 110° - 160°F water mixed automatically with
injected detergent. In the event the fire control system is activated, the system shall supply a continuous
fire quenching spray. Fire quench shall continue to operate until the reset button is pushed. Pressing the
start button will restart the fan system
Install hinged, motorized Fire Damper full length at air inlet of ventilator. Damper opens when
ventilator is in normal operation, acting as an extracting baffle, and closes when ventilator is turned off
to allow thorough cleansing of extraction chamber interior. Damper automatically closes, sealing
interior of ventilator from fire when thermostat senses 325°F.
Furnish Duct Collar, fully welded, complete with fire detection thermostat, in top of canopy within
exhaust plenum area. Duct collar size based on an average 1800 FPM air velocity.
Integral Make-Up Air shall NOT be furnished.
Unit furnished with 1-5/8” OD stainless steel tubing leg with stainless steel adjustable bullet feet or
necessary channel Support framework for setting unit on floor. Unit must be secured to adjacent
equipment by applicable trades.
Canopy shall be UL Listed and NSF approved. All equipment built in an ISO 9001:2000
approved manufacturing facility
BY
"Your Solutions Partner"
2305 N. Broadway
St. Louis, MO 63012
Ph 314-231-1130
Fax314-231-5074
www.dukemfg.com
4/07
Exhaust Requirements
CFM ________________ SP (“w.g.) _____________
Duct Collar ________ “x ______________”
Fire Protection
(Submit cooking equipment plan showing make
Lighting Fixtures
Not Available
and model on equipment.)
Ansul Wet-R#-102
Other ___________________________________
Internal Piping Only
Complete System
By Others
NOTE: Fuel shut-off devices by others (unless specified
otherwise).
Optional Accessories
Enclosure paneling
(Finished ceiling higher than 9’0”)
Continuous Cold Water Mist
Design Option
VC-1C S/S Control Cabinet with push button controls
VC-1M S/S Control Cabinet with programmable Mode Commander Microprocessor
Shipping Wt. 85 lbs./Linear Ft.
COMMENTS/NOTES ______________________________________________________
3'-0" EQUIPMENT HEIGHT
18"
*MAY VARY*
*MAY VARY*
3" 2"
4'-6"
*MAY VARY*
2'-6"
*MAY VARY*
1 1/2"
EXHAUST COLLAR
4 1/2"
O.A. LENGTH
DUCT
2'-6"
DUCT
INDIRECT WASTE
T-STAT
H.W. INLET
CONDUIT & (4) WIRES FROM CONTROL
CABINET FOR T-STATS & DAMPER MOTOR
IF REQUIRED LENGTH OF CANOPY IS LONGER THAN 15’-0”, ADD EQUAL LENGTH CANOPIES
TOGETHER TO OBTAIN PROPER LENGTH. EACH CANOPY SELECTED REQUIRES SEPARATE DUCT
AND CFM REQUIREMENTS.
VENTILATOR
DRAIN SIZE
HOT WATER
LINE SIZE*
3’0” - 15’0”
1-1/2”
3/4”
15’6” - 30’0”
2”
1”
Ventilator requires 110° -160°F hot water. 1
G.P.M. per linear foot of ventilator length at 40 PSI
flow pressure. Allowable range is between 20 to 60
PSI flow pressure.
To satisfy most codes, allow a minimum of 6” canopy overhang on all exposed sides of cooking equipment.
However, more overhang should be considered for demanding equipment.
4'-0"
3"
EXHAUST CONNECTION
ACCESS PANEL
6"
1 1/2" DRAIN - PLUMBER
TO EXTEND TO 3" MIN
FLOOR DRAIN
18 GA. G.I. SUPPORT
CHANNEL FRAMEWORK
NOTE:
VENTILATOR IS NOT FREE
STANDING. REQUIRES
ADDITIONAL SUPPORT
We reserve the right to change specifications and product design without notice. Such revisions do not entitle
the buyer to corresponding changes, improvement, additions or replacements for previously purchased
equipment.
Model DD
Item Number: ____________
DOWN DRAFT STYLE
WATER WASH VENTILATOR
SOUTHERN ENGINEERING SYSTEMS
SOUTHERN ENGINEERING SYSTEMS Model DD, a Type I, Hi-Velocity, Down Draft Style Water
Wash Ventilator for use over low cooking equipment where a pass-over shelf is desired.
The DD is state-of-the-art in kitchen ventilation. The Southern Engineering Wash design utilizes
centrifugal grease extraction, automatic self-cleaning, and a built-in water barrier for duct and plenum
protection in a fire mode. A normally closed damper prevents the loss of conditioned air during off
hours, and the latest in microprocessor controls for programming hood functions is an optional
enhancement. This ventilator is 95% grease efficient with third party accreditations.
This design is specified where no make-up air is required.
PROJECT NAME:_____________________________
PROJECT LOCATION:_____________________________
ww-19-499