F6 GRV GMX24 MFT X1

F6 GRV GMX24 MFT X1
F6…VIC Butterfly Valves 2”–12” 2-Way Ductile Iron Grooved End Body
• 200 psi (2” to 12”) bubble tight shut-off
• Long stem design allows for 2” insulation
• Completely assembled and tested, ready for installation
Application
These valves are designed to meet the needs of HVAC and commercial
applications requiring bubble tight shut-off for liquids. Typical applications
include chiller isolation, cooling tower isolation, change-over systems, large
air handler coil control, bypass and process control applications. The large
Cv values provide for an economical control valve solution for larger flow
applications.
Jobsite Note
Valves should be stored in a weather protected area prior to construction.
N40019 - 04/11 - Subject to change. © Belimo Aircontrols (USA), Inc.
-22°F to 122°F [-30°C to 50°C]
200 psi
20 FPS
Spring
Return
DN
[mm]
2-way
VIC
VIC
IN
115
36
2”
50
F650VIC
260
80
2½”
65
F665VIC
440
140
3”
80
F680VIC
820
250
4”
100
F6100VIC
1200
370
5”
125
F6125VIC
1800
560
6”
150
F6150VIC
3400
1050
8”
200
F6200VIC
5800
1800
10”
250
F6250VIC
9000
2790
12”
300
F6300VIC
Non-Spring Return
VIC
VIC
SY Series
ductile iron ASTM A536, grade 65-45-12
electroless nickel coated ductile iron
EPDM
416 stainless steel
300 psi at -30°F to 275°F
-30°F to 250°F [-34°C to 120°C]
Cv
60°
Type
GM Series
Cv
90°
chilled, hot water, 60% glycol
modified equal percentage
90° rotation
2” to 12”
grooved ANSI/AWWA (C606)
Valve
Nominal Size
AM
Series
Technical Data
Service
Flow characteristic
Action
Sizes
Type of end fitting
Materials*
Body
Disc
Seat
Shaft
Body pressure rating
Media temperature range
Operation ambient
temperature range
Maximum close-off pressure
Maximum velocity
Suitable Actuators
AF Series
2-way
*VIC®300 Masterseal™ as manufactured by Victaulic Company
Valve
F650VIC
F665VIC
F680VIC
F6100VIC
F6125VIC
F6150VIC
F6200VIC
F6250VIC
F6300VIC
Size
2”
2-1/2”
3”
4”
5”
6”
8”
10”
12”
Cv
115
260
440
820
1200
1800
3400
5800
9000
800-543-9038 USA
30°
7
16
26
50
70
110
200
350
540
40°
14
30
50
100
140
220
410
700
1080
50°
23
50
90
160
240
360
670
1150
1780
60°
36
80
140
250
370
560
1050
1800
2790
866-805-7089 CANADA
70°
60
140
230
430
620
940
1770
3020
4680
90°
115
260
440
820
1200
1800
3400
5800
9000
203-791-8396 LATIN AMERICA
1
F6…VIC Butterfly Valves 2”–12” 2-Way Ductile Iron Grooved End Body
C (Max)
8.0 [204]
8.0 [204]
8.0 [204]
8.0 [204]
8.0 [204]
8.6 [219]
8.6 [219]
8.6 [219]
8.6 [219]
2.4 [61]
2.4 [61]
2.4 [61]
9.2 [234]
9.2 [234]
9.2 [234]
9.2 [234]
10.9 [275]
10.9 [275]
10.9 [275]
D(Max)
13.2 [334]
13.6 [345]
14.0 [358]
14.3 [364]
19.6 [499]
14.0 [357]
14.5 [368]
18.7 [476]
14.7 [374]
15.7 [398]
16.2 [409]
16.4 [415]
26 [660]
26.7 [679]
27.7 [704]
28.2 [717]
33.3 [846]
35 [890]
36 [916]
Actuator
AM...
GM...
2*GM
AF…
2*AF…
AF…
SY1...
SY2...
SY2…/ SY3…
SY2…/ SY3…
SY4…
SY4…/ SY5…
SY6…
Close-Off (PSI)
200
50
200
200
200
200
50
200
50
200
200
50
200
200
50/200
50/200
200
50/200
200
Non-Spring
Return
B (Max)
4.7 [120]
4.7 [120]
7.0 [178]
7.0 [178]
8.6 [219]
2.0 [51]
2.0 [51]
8.6 [219]
2.0 [51]
3.2 [82]
3.2 [82]
3.2 [82]
4.6 [117]
4.6 [117]
4.6 [117]
4.6 [117]
7.3 [184]
7.3 [184]
7.3 [184]
Spring
Return
A(Max)
3.21 [81.5]
3.77 [95.8]
3.77 [95.8]
3.77 [95.8]
4.63 [117.6]
3.21 [81.5]
3.77 [95.8]
3.77 [95.8]
3.77 [95.8]
3.21 [82]
3.77 [96]
3.77 [96]
3.77 [96]
4.63 [118]
5.88 [150]
5.88 [150]
5.33 [136]
6.40 [163]
6.50 [165]
Non-Spring Return
Maximum Dimensions (Inches)
Valve
Size
Cv 90°
F650VIC
2”
115
F665VIC
2½”
260
F665VIC
2½”
260
F680VIC
3”
440
F6100VIC
4”
820
F650VIC
2”
115
F665VIC
2½”
260
F665VIC
2½”
260
F680VIC
3”
440
F650VIC
2”
115
F665VIC
2½”
260
F680VIC
3”
440
F680VIC
3”
440
F6100VIC
4”
820
F6125VIC
5”
1200
F6150VIC
6”
1800
F6200VIC
8”
3400
F6250VIC
10”
5800
F6300VIC
12”
9000
†SY6 and larger available in 110/220 VAC versions only.
SY... maximum actuator ambient temperature is 150°F.
Dimensions
3.858
[97.99]
8.553
[217.25]
Flow Rate (GPM)
10
m
m
m
0
7
9.
9.
15
13
&
.1
m
m
&
4
[101.6]
A
.9
mm
23
”/3
12
10
”/2
73
.0
mm
9.1
/21
8”
mm
65
B
&1
m
m
.3
68
41
/1
/1
6”
5”
.0
8.
0
33
10
&
,1
m
m
m
.3
m
3
4.
/11
4”
m
m
m
m
m
m
.1
76
&
m
m
mm
.9
/88
2”
1/
2
3”
/7
3.
0
mm
.3
/60
2”
Pressure Drop - psi
1
C
m
B
D
0.1
0.01
10
100
1000
10000
C
A
800-543-9038 USA
2
866-805-7089 CANADA
203-791-8396 LATIN AMERICA
N40019 - 04/11 - Subject to change. © Belimo Aircontrols (USA), Inc.
1.852
[47.05]
D
6.393
[162.38]
Application Notes
1. Valves are rated at 200 psi differential pressure in the closed position
2. 2-way assemblies are furnished assembled and tested, ready for installation.
3. Dimension “D” allows for actuator removal without the need to remove the
valve from the pipe.
4. Belimo SY Series actuators are NEMA 4X rated.
5. Provide support for the actuator if it is mounted at any angle other than 90°
vertical.
6. Installer is to use rigid type couplings for connecting the valve to the piping.
F7…VIC Butterfly Valves 2”–12” 3-Way Ductile Iron Grooved End Body
• 200 psi (2” to 12”) bubble tight shut-off
• Long stem design allows for 2” insulation
• Completely assembled and tested, ready for installation
Application
These valves are designed to meet the needs of HVAC and commercial
applications requiring bubble tight shut-off for liquids. Typical applications
include chiller isolation, cooling tower isolation, change-over systems, large
air handler coil control, bypass and process control applications. The large
Cv values provide for an economical control valve solution for larger flow
applications.
Jobsite Note
Valves should be stored in a weather protected area prior to construction.
N40019 - 04/11 - Subject to change. © Belimo Aircontrols (USA), Inc.
-22°F to 122°F [-30°C to 50°C]
200 psi
20 FPS
Non-Spring Return
Cv
90°
Cv
60°
IN
DN
[mm]
2-way
VIC
VIC
VIC
115
36
2”
50
F750VIC
260
80
2½”
65
F765VIC
GM Series
ductile iron ASTM A536, grade 65-45-12
electroless nickel coated ductile iron
EPDM
416 stainless steel
300 psi at -30°F to 275°F
-30°F to 250°F [-34°C to 120°C]
Type
AM
chilled, hot water, 60% glycol
modified linear
90° rotation
2” to 12”
grooved ANSI/AWWA (C606)
AF
Series
Technical Data
Service
Flow characteristic
Action
Sizes
Type of end fitting
Valve Materials*
Body
Disc
Seat
Shaft
Body pressure rating
Media temperature range
Operation ambient
temperature range
Maximum close-off pressure
Maximum velocity
Suitable Actuators
Spring
Return
440
140
3”
80
F780VIC
820
250
4”
100
F7100VIC
1200
370
5”
125
F7125VIC
1800
560
6”
150
F7150VIC
3400
1050
8”
200
F7200VIC
5800
1800
10”
250
F7250VIC
9000
2790
12”
300
F7300VIC
VIC
SY Series
3-way
Valve
Nominal Size
®
*VIC 300 Masterseal™ as manufactured by Victaulic Company
Valve
F750VIC
F765VIC
F780VIC
F7100VIC
F7125VIC
F7150VIC
F7200VIC
F7250VIC
F7300VIC
Size
2”
2-1/2”
3”
4”
5”
6”
8”
10”
12”
Cv
115
260
440
820
1200
1800
3400
5800
9000
800-543-9038 USA
30°
7
16
26
50
70
110
200
350
540
40°
14
30
50
100
140
220
410
700
1080
50°
23
50
90
160
240
360
670
1150
1780
60°
36
80
140
250
370
560
1050
1800
2790
866-805-7089 CANADA
70°
60
140
230
430
620
940
1770
3020
4680
90°
115
260
440
820
1200
1800
3400
5800
9000
203-791-8396 LATIN AMERICA
1
F7…VIC Butterfly Valves 2”–12” 3-Way Ductile Iron Grooved End Body
D(Max)
13.2 [334]
13.6 [345]
14.0 [358]
14.3 [364]
19.6 [499]
14.0 [357]
14.5 [368]
18.7 [476]
15.7 [398]
16.2 [409]
16.4 [415]
26 [660]
26.7 [679]
27.7 [704]
28.2 [717]
33.3 [846]
35 [890]
35.1 [890]
38.7 [981]
39.7 [1007]
Actuator
AM...
Close-Off (PSI)
50
200
50
200
50
200
50
200
200
50
200
200
200
200
50
200
200
50
200
200
GM...
2*GM
AF…
2*AF…
SY1...
SY2...
SY3...
SY4...
SY6...
SY7...
Non-Spring
Return
C (Max)
13.1 [334]
13.6 [347]
14.1 [356]
14.1 [356]
14.3 [364]
8.6 [219]
8.6 [219]
8.6 [219]
15.7 [398]
16.2 [409]
25.7 [654]
26.0 [660]
26.7 [679]
27.7 [704]
28.3 [717]
32.1 [814]
33.3 [846]
35.1 [890]
38.7 [981]
39.7 [1007]
Spring
Return
B (Max)
6.5 [165]
6.5 [165]
7.5 [191]
7.5 [191]
8.0 [204]
2.0 [51]
2.0 [51]
8.6 [219]
6.5 [165]
7.5 [191]
7.5 [191]
8.0 [204]
9.6 [245]
11.4 [290]
12.4 [315]
12.4 [315]
13.1 [333]
15.4 [392]
15.4 [392]
16.5 [419]
Non-Spring Return
Maximum Dimensions (Inches)
Valve
Size
Cv 90°
A(Max)
F750VIC
2”
115
3.2 [82]
F750VIC
2”
115
3.2 [82]
F765VIC
2½”
260
3.8 [96]
F765VIC
2½”
260
3.8 [96]
F780VIC
3”
440
3.8 [96]
F650VIC
2”
115
3.21 [81.5]
F665VIC
2½”
260
3.77 [95.8]
F665VIC
2½”
260
3.77 [95.8]
F750VIC
2”
115
3.2 [82]
F765VIC
2½”
260
3.8 [96]
F765VIC
2½”
260
3.8 [96]
F780VIC
3”
440
3.8 [96]
F7100VIC
4”
820
4.6 [118]
F7125VIC
5”
1200
5.9 [150]
F7150VIC
6”
1800
5.9 [150]
F7150VIC
6”
1800
5.9 [150]
F7200VIC
8”
3400
5.3 [135]
F7250VIC
10”
5800
6.4 [163]
F7250VIC
10”
5800
6.4 [163]
F7300VIC
12”
9000
6.5 [165]
†SY6 and larger available in 110/220 VAC versions only.
SY... maximum actuator ambient temperature is 150°F.
Dimensions
7.559
[192]
4.551
[115.6]
3.627
[92.12]
D
Application Notes
1. Valves are rated at 200 psi differential pressure in the closed position
2. 2-way assemblies are furnished assembled and tested, ready for installation.
3. Dimension “D” allows for actuator removal without the need to remove the
valve from the pipe.
4. Belimo SY Series actuators are NEMA 4X rated.
5. Provide support for the actuator if it is mounted at any angle other than 90°
vertical.
6. Installer is to use rigid type couplings for connecting the valve to the piping.
C
Flow Rate (GPM)
3.858
[97.99]
10
0
9.
15
13
&
.9
mm
.0
”/3
A
12
73
10
”/2
9.1
/21
8”
C
23
mm
m
m
.3
68
/1
mm
65
.1
m
m
m
m
m
m
0
8.
.0
33
10
&
,1
m
m
m
m
.3
41
/1
5”
6”
3
4.
/11
4”
&1
m
m
.1
76
&
m
m
.9
/88
2”
1/
2
3”
/7
3.
0
mm
mm
.3
/60
2”
Pressure Drop - psi
1
&
9.
7
m
m
m
m
D
3.627
[92.12]
0.1
10
100
1000
10000
D
0.01
C
B
800-543-9038 USA
2
866-805-7089 CANADA
A
203-791-8396 LATIN AMERICA
B
N40019 - 04/11 - Subject to change. © Belimo Aircontrols (USA), Inc.
B
A
8.406
[213.51]
GMB24-3-X1 Actuators, On/Off, Floating Point
7.024
[178.4]
7.59
[192.8]
2_Way_GM_VIC
Dimensions with 2-Way Valve
D
4.551
[115.6]
B
C
3.627
[92.12]
A
Valve
F665VIC
F680VIC
Models
Size
2½”
3”
Dimensions (Inches)
B
C
7.00
8.00
7.00
8.00
A
3.80
3.80
D(Max)
14.00
14.30
PSI
GM
50
200
GMB24-3-X1
C
B
A
Valve
F765VIC
F765VIC
Size
2½”
2½”
Dimensions (Inches)
B
C
7.50
8.00
7.50
8.00
A
3.80
3.80
D(Max)
14.00
14.00
PSI
GM
50
200
D(Max)
19.60
19.60
PSI
2*GM
200
50
2_Way_2XGM_VIC
Dimensions with 2*GM
7.559
[192]
7.024
[178.4]
D
Noise level
Servicing
Quality standard
3.627
[92.12]
6.393
[162.38]
Overload protection
Control signal
Input impedance
Angle of rotation
Direction of rotation
Position indication
Running time
Humidity
Ambient temperature
Storage temperature
Housing
Housing material
Agency listings
4.551
[115.6]
1.852
[47.05]
N40019 - 04/11 - Subject to change. © Belimo Aircontrols (USA), Inc.
Transformer sizing
Electrical connection
7.559
[192]
D
Power consumption
24 VAC ± 20% 50/60 Hz
24 VDC ± 10%
running 4.0 W
holding 2 W
6 VA (class 2 power source)
3 ft, 18 GA appliance cable,
1/2” conduit connector
electronic throughout 0 to 95° rotation
On/Off, Floating Point
600 Ω
mechanically limited to 95°
reversible with switch A/B
0 to 1 and reversible indicator
150 sec.
5 to 95% RH non-condensing
-22°F to 122°F [-30°C to 50°C]
-40°F to 176°F [-40°C to 80°C]
NEMA 2/IP54
UL94-5VA (flammability rating)
cULus according to UL60730-1A/-2-14,
CAN/CSA E60730-1, CSA C22.2 No.24-93,
CE according to 89/336/EEC
max. 45 dB (A)
maintenance free
ISO 9001
3_Way_GM_VIC
Dimensions with 3-Way Valve
Technical Data
Power supply
B
C
A
Valve
F6100VIC
F780VIC
800-543-9038 USA
866-805-7089 CANADA
Size
4”
3”
4
[101.6]
4.551
[115.6]
A
4.60
3.80
Dimensions (Inches)
B
C
8.60
8.00
8.00
8.00
203-791-8396 LATIN AMERICA
1
Wiring Diagrams
24 VAC Transformer
2
2
5
Blk (1) Common
Line
Volts
CAUTION Equipment damage!
3
W559
GMB24-3-X1 Actuators, On/Off, Floating Point
Red (2) +
Actuators may be connected in parallel.
Power consumption and input impedance must be observed.
a
Wht (3) +
a open
a closed
3
Actuators may also be powered by 24 VDC.
5
Actuators with plenum rated cable do not have numbers on wires; use
color codes instead. Actuators with appliance cables are numbered.
1 0
The indication of direction
is valid for switch position 1.
GMB24-3-X1
j y
24 VAC Transformer
Line
Volts
WARNING Live Electrical Components!
During installation, testing, servicing and troubleshooting of this
product, it may be necessary to work with live electrical components. Have a
qualified licensed electrician or other individual who has been properly trained
in handling live electrical components perform these tasks. Failure to follow all
electrical safety precautions when exposed to live electrical components could
result in death or serious injury.
2
3
5
Blk (1)
Common
Red (2)
+
Wht (3)
+
W559
On/Off
Meets cULus or UL and CSA requirements without the
need of an electrical ground connection.
1 0
The indication of direction
is valid for switch position 1.
GMB24-3-X1
N40019 - 04/11 - Subject to change. © Belimo Aircontrols (USA), Inc.
Floating Point
800-543-9038 USA
2
866-805-7089 CANADA
203-791-8396 LATIN AMERICA
GMX24-MFT-X1 Actuators, Multi-Function Technology
7.024
[178.4]
7.59
[192.8]
2_Way_GM_VIC
Dimensions with 2-Way Valve
D
4.551
[115.6]
B
C
3.627
[92.12]
A
Valve
F665VIC
F680VIC
Models
Size
2½”
3”
Dimensions (Inches)
B
C
7.00
8.00
7.00
8.00
A
3.80
3.80
D(Max)
14.00
14.30
PSI
GM
50
200
GMX24-MFT-X1
Noise level
Servicing
Quality standard
Valve
F765VIC
F765VIC
Size
2½”
2½”
A
3.80
3.80
D(Max)
14.00
14.00
PSI
GM
50
200
D(Max)
19.60
19.60
PSI
2*GM
200
50
Dimensions with 2*GM
7.559
[192]
7.024
[178.4]
B
C
A
Valve
F6100VIC
F780VIC
800-543-9038 USA
B
A
Dimensions (Inches)
B
C
7.50
8.00
7.50
8.00
2_Way_2XGM_VIC
Angle of rotation
Direction of rotation
Position indication
Running time
Humidity
Ambient temperature
Storage temperature
Housing
Housing material
Agency listings
C
D
Input impedance
3.627
[92.12]
6.393
[162.38]
N40019 - 04/11 - Subject to change. © Belimo Aircontrols (USA), Inc.
Overload protection
Control signal
4.551
[115.6]
D
Transformer sizing
Electrical connection
7.559
[192]
1.852
[47.05]
Power consumption
24 VAC ± 20% 50/60 Hz
24 VDC ± 10%
running 4.5 W
holding 2 W
7 VA (class 2 power source)
3 ft, 18 GA appliance cable,
1/2” conduit connector
electronic throughout 0 to 95° rotation
2 to 10 VDC, 4 to 20 mA
(with 500 Ω, 1/4 W resistor) ZG-R01
100 k Ω for 2 to 10VDC (0.1 mA)
500 Ω for 4 to 20 mA
750 Ω for PWM
1500 Ω for on/off and floating point
mechanically limited to 95°
reversible with switch A/B
0 to 1 and reversible indicator
150 sec.
5 to 95% RH non-condensing
-22°F to 122°F [-30°C to 50°C]
-40°F to 176°F [-40°C to 80°C]
NEMA 2/IP54
UL94-5VA (flammability rating)
cULus according to UL60730-1A/-2-14,
CAN/CSA E60730-1, CSA C22.2 No.24-93,
CE according to 89/336/EEC
max. 45 dB (A)
maintenance free
ISO 9001
3_Way_GM_VIC
Dimensions with 3-Way Valve
Technical Data
Power supply
866-805-7089 CANADA
Size
4”
3”
4
[101.6]
4.551
[115.6]
A
4.60
3.80
Dimensions (Inches)
B
C
8.60
8.00
8.00
8.00
203-791-8396 LATIN AMERICA
3
GMX24-MFT-X1 Actuators, Multi-Function Technology
3
24 VAC Transformer
3
5
8
10
Red (2) + Hot
Ω
Actuators with plenum rated cable do not have numbers on wires; use
color coded instead. Actuators with appliance rated cable use numbers.
Control signal may be pulsed from either the Hot (Source) or
Common (Sink) 24 VAC line.
For triac sink the Common connection from the actuator must be
connected to the Hot connection of the controller.
5
Blk (1) Common
Line
Volts
Actuators may also be powered by 24 VDC.
W545_No_2
Wiring Diagrams
Control Signal
4 to 20 mA
or
2 to 10 VDC
500Ω
1/4 watt
(–)
(+)
Wht (3) Y1 Input, 2 to 10V
7
Org (5) U Output, 2 to 10V
CCW CW
Blk (1) Common
Line
Volts
Red (2) Hot
Position
a
(–)
Wht (3) Y Input
Feedback VDC (+)
WARNING Live Electrical Components!
During installation, testing, servicing and troubleshooting of this product,
it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling
live electrical components perform these tasks. Failure to follow all electrical
safety precautions when exposed to live electrical components could result in
death or serious injury.
Org (5) U Output
Two Position
3
24 VAC Transformer
Blk (1) Common –
Line
Volts
5
8
Wht (3) Y1 Input
B
Pnk (4) Y2 Input
9
2 to 10 VDC
Feedback Signal
Blk (1) Common
Line
Volts
Org (5) U Output 2 to 10V
11
Red (2) + Hot
Direction of rotation switch
3
CCW
CCW
CW
(–)
Control Signal
(+)
2 to 10 VDC
A
Wht (3) Y Input, 2 to 10 V
Org (5) U Output 2 to 10 V
CW
B 5
A
B 5
Floating Point
CCW CW
24 VAC Transformer (AC only)
Blk (1) Common
Line
Volts
Slave
5
Position
8
(–)
Feedback VDC (+)
Blk (1) Common
Red (2) + Hot
Wht (3) Y Input
Org (5) U Output
Red (2) + Hot
Wht (3) Y Input, 2 to 10 V
PWM
Org (5) U
CCW CW
Master/Slave
800-543-9038 USA
4
10
866-805-7089 CANADA
203-791-8396 LATIN AMERICA
N40019 - 04/11 - Subject to change. © Belimo Aircontrols (USA), Inc.
Master
Red (2) Hot +
A
Master_Slave
24 VAC Transformer
W545_No_2
11
3
W545_No_2
9
24 VAC/DC Transformer
W545_No_2
VDC/4-20 mA
Meets cULus or UL and CSA requirements without the
need of an electrical ground connection.
Contact closures A & B also can be triacs. A & B should
both be closed for triac source and open for triac sink.
Position feedback cannot be used with a Triac sink controller. The
actuator internal common reference is not compatible.
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertisement