Historique des Révisions du Firmware des CPU

Historique des Révisions du Firmware des CPU
CTI 2500 Series Processor
Firmware Revision History
*************************************************************************************************
Firmware Version 8.04 (10/29/2015)
**************************************************************************************************
Issues Resolved:
FT-407: The initial values of the Control Blocks for both Alarms and Loops did not
match that of the 555 PLC. These initialization values were modified to match the 555
controller. For both Alarms and PID Loops, the Rate of Change (ROC) alarm detection
check was moved from pre-SFP execution to post-SFP execution to match the
execution of the 555 PLC. PID Loop execution cycle was changed to provide Rate of
Change (ROC) monitoring in all Loop operation modes (Manual/Auto/Cascade).
*************************************************************************************************
Firmware Version 8.03 (10/19/2015)
**************************************************************************************************
Issues Resolved:
FT-408: The correction for issues FT-293/FT-405 (listed below in “Firmware Version
8.02 (9/10/2015”) was applied to the rungs in RLL Subroutines. In some instances, the
RLL Subroutine logic would cause the PLC to go to FE 300 when transitioning from
Program to Run.
*************************************************************************************************
Firmware Version 8.02 (9/10/2015)
**************************************************************************************************
Issues Resolved:
1148: Immediately after a firmware update, powering up the 2500 series controller while
a 2500P-ACP1 module was attempting to initiate a data caching connection sometimes
caused a fatal error condition (FE102 or FE10B) or caused the controller to halt during
startup.
1144: Because the routine used to count broadcast packets over an interval of time was
not operating correctly, broadcast storm protection software could erroneously detect a
broadcast storm and turn off the Ethernet port prematurely.
1140: During the firmware update process, an event containing an error code of 138
was erroneously being logged, due to a system startup order problem in the Ethernet
link status logic. This problem occurred only on the first execution after a firmware
update.
1139: The size of the TCP/IP queue was not big enough, resulting in dropped packets
and other artifacts when the packet rate was high or when a large burst of packets was
received in a short amount of time. The queue size was increased from 32 to 128.
1138: After updating firmware, the data displayed on the Ethernet Statistics web page
was incorrect until the data was cleared by the user.
1137: Corrected a memory boundary mapping that exceeded its designated region by
four bytes. This issue was discovered by CTI development and is not known to have
caused a field problem.
1131/1129/1106/1104: When receiving packets at a rate of approximately 1400 packets
per second or greater, the Ethernet port link status would periodically toggle between
connected and disconnected, interrupting communications between the PLC and
2500P-ECC1 modules, 2500P-ACP1 modules, HMI terminals and SCADA
workstations. Events indicating Ethernet link Inactive were being successively logged
without an interposing event indicating Ethernet Link Active. Continuous toggling of the
link status eventually caused the Ethernet port to stop communicating and, in some
cases, caused the PLC to declare a fatal error. Restoration of communications required
cycling power to the PLC.
1090: DCP requests for drum addresses other than 1 yielded incorrect values.
1038: The scan overrun bit was not being set properly in all cases. When a scan
overrun occurred, the Siemens 555 PLC set the scan overrun bit only when in RUN or
EDIT mode. The 2500 PLC correctly set the overrun bit while in RUN or EDIT mode but
also set the overrun bit when in PROGRAM mode, an incorrect action.
909: When a fatal error occurred while the PLC Ethernet port storm protection firmware
was active, the Ethernet storm protection duration value reported on the Ethernet
Statistics page was inaccurate.
890: If the PLC was powered off while the Normal I/O task was communicating with the
I/O processor, the PLC would go to fatal error mode (60F). NOTE: This issue was
originally addressed in firmware version 7.05 but was re-opened to fix another error
case.
880: When Port Lockout was engaged, it did not prevent a change to the V memory
size or a change from RUN to PROGRAM mode as required.
844: Discrete I/O points, control registers, and words could not be forced using task
code 9E.
833: After a power up start, the “Last Counter Clear” date and time on the Ethernet
Statistics web page was not correct.
823: For TC56 (Write I/O Configuration Table), if more than one message was required
to transfer all the configuration data, it was possible to create a request that would
overwrite data. This issue was discovered by CTI development. Since this task code is
used by programming and test software only, it is very unlikely that this condition would
have occurred in the field.
807: After disabling an enabled password, the reported status remained “enabled”.
FT-293 / FT-405: User programs created in an old Workshop version (3.30, SP1)
erroneously created invalid rungs for various complex RLL rungs and because of this
they could incorrectly execute and set outputs.
FT-406: When both Loop PV Low/High values were changed from the default 0-100
range, the Loop Set Point (LSP) initial value was set to High limit instead of the Low
Limit as done in 555 controllers. This issue could also affect the Sequential Shift
Register (SSR) statement when using an address of type LPVL, LPVH, APVL, or APVH
for the Table Register Start Address.
New Features and Improvements:
1150: Added the baud rate of the serial port to the Product Information web page.
1096: Added the subnet mask in dotted decimal and CIDR (Classless Inter-Domain
Routing) notation to the Product Information web page.
1019: Added Unicast Packets Received and transmitted to the Ethernet Statistics page.
Also added the number of transmitted Ethernet packets with Ethertype 837A. Ethertype
837A is used to transfer data between the PLC and an advanced function module using
data caching.
937: Added the capability to change the PLC IP parameters via the local Ethernet port
using PLC Workshop or by accessing a PLC web page (enabled by SW11). Also added
the capability to reset the IP parameters to the factory default (enabled by Jumper D)
and added the capability to display of the subnet mask in CIDR notation on the MultiSegment Display.
*************************************************************************************************
Firmware Version 8.01 (6/30/2014)
**************************************************************************************************
Issues Resolved:
1050: After a duplicate IP address was detected, causing the Network Status (NS) LED
to turn RED, a subsequent duplicate IP test, initiated by removing and reinserting the Ethernet cable, did not set the NS LED to GREEN, even though the
duplicate IP address problem had been corrected.
FT-401: Incorrect non-fatal error bit in STW162 was set when the CTI 2500 controller
attempted to execute a missing SF program. Bit 8 (Attempt to invoke a
restricted SF program or subroutine) was set instead of bit 16 (Attempt to
execute an undefined SF program or subroutine).
FT-402: The PID Loop Velocity algorithm generated an incorrect output value when the
calculated output was full scale negative.
FT-403: The EDRUM preset time was not reset when a JOG input caused the drum to
advance to the next step.
New Features and Improvements:
875: Extended the number of control relays supported by the C400 processor from
32,768 to 56,320. The additional control relays are non-retentive. Access to this
feature via PLC Workshop requires V4.8 and above. TISOFT cannot access the
additional control relays.
1047: Clarified the text of the event logged when the number of outstanding data cache
read requests exceeded 175. The data cache protocol is used to transfer data
between the PLC and Advanced Function modules, such as the 2500P-ECC1.
*************************************************************************************************
Firmware Version 7.10 (4/8/2014)
**************************************************************************************************
Issues Resolved:
1043: A timing anomaly during power-up start occasionally caused the processor
firmware to erase the user program. This problem was introduced in firmware version
7.08.
1044: A “low power” event was erroneously logged during power-up start.
*************************************************************************************************
Firmware Version 7.09 (2/25/2014)
**************************************************************************************************
Issues Resolved:
FT-399: Using the ‘Find’ function resulted in Fatal Error 113 (scan watchdog) in certain
situations (for example, a large amount of L memory allocated and a search
address that was not contained in the program). The error occurred because
the Find function, which is a deferred task code, did not yield to the time slice
allocated for Normal Communications and attempted to complete the
operation in a single scan.
New Features and Improvements:
1026:
The method for filtering multicast packets was improved and an entry was
added to the Ethernet Statistics web page that counts the multicast packets
that have been discarded by software. NOTE: If the Ethernet controller
hardware is rejecting all multicast packets, as expected, the count of multicast
packets rejected by software will be 0.
*************************************************************************************************
Firmware Version 7.08 (1/21/2014)
**************************************************************************************************
Issues Resolved:
FT-398: When located within MCR zone, the On-Delay and Off-Delay Coil outputs did
not turn OFF when the MCR power flow is OFF. Similarly, the ONDC and
OFFDC outputs did not "hold last state" when located within JMP zone.
1014:
On occasion, a long period of time would expire (up to 5 minutes) before the
PLC would allow a 2500P-ECC1 module to reconnect after a broadcast storm
occurred.
1000:
The PLC failed to perform a duplicate IP address test during power up start, as
specified.
995:
The PLC was not ready to update firmware immediately after when the “U01”
status code was displayed
901:
The Web server was slow to display some web pages.
New Features and Improvements:
1013:
To aid in identifying the source of an Event Log, the PLC serial number and
firmware revision is now written to the event log after it is cleared.
1006:
To assist in identifying power supply problems, the capability to monitor the 5V
supply has been added to the PLC.
992:
The number of supported Advanced Function modules (such as the 2500PECC1), was increased from 4 to 8.
882:
Added the capability to execute logic conditioned on last scan when
transitioning to program mode. After the request to go to program mode, a Last
Scan before Program Mode” flag (stw201.5) is set, and a final scan is initiated.
The RLL logic can detect this condition and perform operations such as setting
WY values to a designated state.
832:
Added a log event when a program is copied from RAM to EEPROM (Flash
Memory).
788:
Added logging of loop mode transitions, loop lock/unlock transitions, and
transition to Program-Freeze mode.
680:
Added a means to clear Ethernet Statistics and a means to Display All
Statistics, which is useful when transmitting diagnostic information to CTI
support personnel. Improved the capability to navigate among web server
pages.
671:
Added the capability to send an ARP announcement and check for a duplicate
IP address when the Ethernet link is re-established (cable is re-connected).
The ARP announcement can improve the ability to re-connect in certain
situations.
*************************************************************************************************
Firmware Version 7.07 (4/8/2013)
**************************************************************************************************
Issues Resolved:
976: Peak scan time was reported incorrectly when running a fast cyclic RLL task while
scan type was set to “variable with limit”.
961: A 2500 Series controller, running a pre-release of the firmware and communicating
with a 2500P-ECC1 module as a Host Controller, sometimes encountered a Fatal Error
113 (scan watchdog overrun) while downloading a user program. Note: NOTE: This
problem occurred only with a CTI test build and was not introduced to the field.
945: The Ethernet Statistics web page was not working correctly when the 2500
controller was executing a pre-release version of the firmware. Note: NOTE: This
problem occurred only with a CTI test build and was not introduced to the field.
938: The 2500 Series controller would stop responding to data cache update requests
from the 2500P-ECC1 module when the scan mode was set to “variable with limit.”
917: When the IP address of a 2500-Cxxx controller was changed while it was
communicating with a 2500P-ECC1 module as a Host Controller, the ECC1 module
could not re-connect to it until power to the controller was cycled.
894: The Dual Power Supply status STW76 was not updating properly when only one
RBC was operational in a redundant base.
762: Some diagnostic statistics displayed on the Ethernet Statistics web page, such as
total number of bytes and packets received, were incorrect. A new method for
gathering Ethernet statistics was implemented and the Ethernet Statistics web page
was revised.
New Features and Improvements:
953: Updated Product Information web page to document dipswitch position 7 and 8
and to clarify the use of other switches and jumpers.
952: Increased the maximum Ethernet packet rate limit from 300 to 330 packets per
50ms. This allows the 2500-ECC1 to provide broadcast storm protection for the 2500
controller when its Ethernet port is connected directly to the Ethernet port of the ECC1
module using a 2% setting. (See the 2500P-ECC1 User Manual).
885: Provided a user-selectable method for reducing scan time with I/O configurations
using only one RBC per base (non-redundant). When the method is selected, the I/O
system will not consume time attempting to poll secondary RBCs.
884: Provided a user-selectable method for automatically disabling bases that are
enabled but unconfigured, potentially reducing overall scan time. When a base is
enabled but there is no I/O configuration for the base, the 2500-Cxxx controller will still
consume a small amount of scan time attempting to communicate with the base. This
feature is primarily intended for APT users, who have no manual means to disable
bases.
**************************************************************************************************
Firmware Version 7.05 (11/7/2012)
**************************************************************************************************
Issues Resolved:
FT-396: The Move Element (MOVE) instruction incorrectly calculated the “last used
Address” when using a BYTE data type with a “Source Index”(SI) parameter.
This could cause an invalid “Table Overflow” error to be reported when the
source table is located near the top of configured memory.
904:
When the 2500 controller auto-selected crossover (MDIX) mode for the local
Ethernet port, reception and transmission of Ethernet packets became erratic
in certain circumstances. The problem did not occur when the mode of the
2500 controller Ethernet port is MDI, which is the default mode.
When two Ethernet devices are connected using a standard Ethernet cable,
one device must use MDI mode while the other uses MDIX mode. Because
Ethernet ports on switches and hubs are MDIX, the 2500 uses the MDI mode
when connected to them. Consequently, typical installations will not encounter
the problem.
The 2500 controller could auto-select MDIX mode only when it is directly
connected to the port of a device that is normally in MDI mode, such as a PC
or the 2500P-ECC1. In this case, the two devices negotiate the mode and
either may ultimately auto-select MDIX.
The problem was resolved by disabling auto-negotiation on the 2500 controller
Ethernet port, resulting in the permanent selection of MDI mode. This should
not prevent a directly connected PC, 2500P-ECC1, or other device supporting
auto-MDIX negotiation from communicating with the 2500 controller, since the
device will auto-select MDIX. For existing installations that directly connect an
Ethernet device that does not support auto-MDIX, you can re-enable autonegotiation by setting jumper C to the enabled position.
902:
Replies to task code 7F, 50 and 9D did not return the correct format when
DCC was accessed.
900:
Routine for servicing Task Code 52 did not support Loop or Alarm data types.
In order to duplicate the SIMATIC® 505 controllers, the operation must ignore
undefined data blocks while continuing to process all other blocks in the
command range that are defined. Full support for TC52 is now provided, as
well as allowing writes to other undefined Loop or Alarm control blocks without
reporting an error condition.
898:
The CAMP Memory Exchange command was not supported correctly.
891:
The controller firmware could not be updated using an SD card due to a
problem with the firmware file loader.
890:
Powering down the PLC while a Normal I/O cycle was in process caused Fatal
Error 60F.
New Features and Improvements:
Added support for the 2500P-ECC1 Ethernet Communications Coprocessor module.
Modified the system startup procedure to write the serial number of the CTI 2500
controller to the event log at system startup. This was done to facilitate matching of log
files with the appropriate controller (#881).
Changed firmware update procedure to retain event log after update rather than
deleting it (#859).
Labeled switch functions in the 2500 Product Information Web Page (#809)
**************************************************************************************************
Firmware Version 6.18 (12/21/2011)
**************************************************************************************************
FT-390: Downloading an APT program without performing a prior Clear All could
generate an invalid expression, causing Fatal Error 701 to be reported. The
execution engine has been modified to duplicate SIMATIC 505-1106 error
reporting.
FT-387: Executing a TSET instruction in RLL program while a deferred task code
request (such as “Find”) was being processed created a time synchronization
error and caused all currently executing timers to immediately expire.
Added support for SD High Capacity (SDHC) cards (DT# 670).
Added new RLL instructions: Delay Coils, Floating Point Compare Instructions, and
Mega Event Drum. NOTE: Access to new instructions requires PLC Workshop V4.60.
Revised power monitoring routine to improve reporting of power supply anomalies
(DT# 848).
**************************************************************************************************
Firmware Version 6.17 (9/13/2011)
**************************************************************************************************
Issues Resolved:
862:
An invalid request message sent by a special function module, such as a
2572-A, could cause the 2500 Series controller to transition to the fatal error
state (Code 300).
754:
The 2500 Series controller erroneously logged off a base when the base was
requested to execute diagnostics.
FT-382: If all Profibus slaves were deleted from an “Online” Profibus network, the
Profibus operational mode could not be changed from OPERATE to STOP.
This problem caused Workshop to become unresponsive when the user
attempted to change the operational mode to STOP or attempted to load
Profibus data using the “Load by Parts” method (which automatically
attempted to place the Profibus network in STOP mode).
FT-381: The operation of the SF SWITCH statement was indeterminate when no
accompanying CASE statement was present.
New Features and Improvements:
Added support for dual remote base controller configurations.
Added support for the CAMP General Module Query command. This support provides a
common means for application software to obtain product information such as model
number and serial number. (DT# 822)
**************************************************************************************************
Firmware Version 6.14 (3/29/2011)
**************************************************************************************************
Issues Resolved:
842:
Task Code 9E incorrectly wrote V and K memory when multiple items of the
same memory type were sent in the same transaction.
839:
Accessing diagnostic information via the Web server was very slow when
the PLC scan was set to a fixed value that substantially exceeded the time
required to process the user logic.
831:
Added fatal error 102 to differentiate an unknown error from a hardware
watchdog error (Fatal Error 103).
826:
Corrected an error introduced in V6.11 that caused the SF Print instruction
to drop the first 8 characters in the print string.
820:
The Profibus diagnostic bytes accessed by the RSD command were
contained incorrect data.
816:
The Ethernet stack would stop accepting TCP connections once the
connections were closed 256 times.
725:
An invalid request from a special function module to the 2500 Series
controller could cause a fatal error 300.
FT- 379:
The MIRFT instruction did not execute correctly within active JMP/MCR
zones.
FT- 378:
The Special Function FSTR instruction did not execute when bit-of-word
addresses were assigned to status bits.
FT- 377:
The RSD instruction was incorrectly calculating the length for the Profibus
Diagnostic data, and the message size was 2 bytes shorter than maximum
specified length.
FT- 375:
When a Special Function program was called from an Analog Alarm, the
First Run (T7) flag was not cleared after the first execution
**************************************************************************************************
Firmware Version 6.11 (9/1/2010)
**************************************************************************************************
Issues Resolved:
801:
When a user program was saved to EEEPROM, the fixed scan time was not
saved.
796:
Task Code 9D returned invalid data when attempting to read TT type 0x1E
(Loop Status).
769:
After the configuration of a single Profibus slave was modified, the other
Profibus slaves were left in a deactivated state.
735:
After a period of heavy Ethernet traffic (network storm), programming
workstations and HMI were unable to reconnect to the Ethernet port on the
2500 PLC after the storm subsided.
732:
Heavy Ethernet Traffic (network storm), caused fatal error 103 (Hardware
Watchdog Timeout).
669:
CVU workstations and other devices using task codes 77 and 7A could not
access loop and alarms data, since these task codes were not supported by
the previous version of the 2500 controller firmware.
FT-369: The controller did not prohibit invalid values from being written into Loop
Setpoint (LSP) and Sample Time (LTS) variables via SFPGM or HMI. This
caused the loop calculation to produce an invalid Loop Error (LERR) value
that resulted in invalid Loop Bias (LMX) and Loop Output (LMN) terms.
FT-368: Parameters values P6 - P10 could not be accessed by the called SFSUB. An
“Address out of range” error (value = 02) was returned when attempting to
access these parameters.
FT-367: When the LEAD-LAG statement was inserted in a SFSUB program called by a
Loop, Alarm, or Cyclic SFP, a “Non-cyclic SFP statement” error (value = 83)
was returned.
FT-366: Attempting a 'Block Move' while editing a program On-Line Program using
TISOFT caused CPU Fatal Error.
FT-364: The STFN instruction did not allow 'W' memory-type address to be used as
INDEX (IN) parameter
FT-363: An in-line PID instruction running within a Cyclic Task caused a Fatal Error
113 (Scan Watchdog).
FT-362: The MATH statement produced imprecise results when converting a long
integer value to a real number.
New Features and Improvements:
800:
Increased SFIO stack size to accommodate new features.
799:
The system exception handler was modified so that multiple events were
logged using a repetition counter, improving diagnostic capabilities.
772:
The I/O Interface was modified to log extended text when an SF module in the
local base generates an invalid request to the 2500 controller, improving
diagnostic capabilities.
771:
The TCP/IP stack was modified to send an ARP Announcement during powerup start. The ARP announcement causes the ARP caches on all network
hosts to be updated, enabling HMI and programming workstations to
immediately connect to a replacement 2500 controller
714:
Enhancements to system status words. Added bit 6 to STW231 to flag that at
least one Profibus slave is not in data exchange mode. Modified STW3STW9 to set bits to 0 only when the corresponding slaves are in data
exchange mode. Unconfigured slaves or configured but not activated slaves
will have their corresponding bits set to 1.
**************************************************************************************************
Firmware Version 6.08(3/24/2010)
**************************************************************************************************
Issues Resolved:
768: In some Profibus configurations, the status of the Profibus slaves (as reported by
status bits in STW3-STW9) erroneously transitioned between 0-1, indicating a
temporary “offline” state. This problem, introduced in V6.07 in an attempt to improve
performance of the Profibus interface, was the result of a timing conflict in the data
transfer between the main controller and Profibus processor. The issue was resolved by
increasing the time interval allowed for completion of the data transfer.
**************************************************************************************************
Firmware Version 6.07(3/15/2010)
**************************************************************************************************
Issues Resolved:
764 and 765: When communicating with I/O bases that contained more than 256 bytes
of input data (i.e. 9 modules with 16 words of input data) the I/O base would be
logged out. NOTE: This error existed only in firmware versions 6.0, 6.02, 6.03,
and 6.05 using CPLD version 6.02.
763: The 2500 I/O interface did not comply with product functional specifications which
required that the interface send a “disable outputs” request to all I/O bases (local
and remote) if the main processor stopped communicating with it.
761: When two 2500 series controllers running firmware version 6.03 or 6.05 were
connected to an Ethernet hub, a task code request sent by a PC connected to the
hub to one controller would be responded to by both controllers. This problem did
not occur if the hub was replaced with an Ethernet switch.
751: When all remote bases were disabled, the remote base controller status would
periodically change from 3 (no communications) to 7(communications OK, no
configuration). This occurred because the 2500 controller was sending a keepalive poll to the bases. When all bases are disabled, no keep-alive polls should be
sent. NOTE: This did not affect the operation of field I/O.
746: The address decoder error handling routine did not have a default case. As a
result, it was possible for an unanticipated error to cause a memory exception.
NOTE: this issue was created as a result of an internal code review. It is highly
unlikely that this error would actually occur.
740: The Profibus processor did not respond to data access requests from the main
processor in some circumstances, causing the main processor to attempt
recovery by resetting the Profibus processor. This caused to Profibus network to
go offline while the Profibus processor was rebooting.
722: Workshop was unable to read Profibus status when port lockout was enabled on
another port or when HMI port 4450/1505 was used to access the PLC.
662: The 2500 controller would erroneously log out a Series 500 series base that did
not respond to an operator initiated request for “RBC Part Number”.
647: Downloading a program that attempted to set the fixed scan time beyond 255ms
caused the 2500 Series controller to report a fatal error 113. The maximum fixed
scan time is now clamped at 255ms. NOTE: Programs transferred from older
PLCs such as the 525 may have fixed scan times above 255ms.
485: Certain recurring I/O error events, such as a duplicate remote base controller
address, could fill the event log, potentially overwriting other significant events in
the log.
FT- 359 SF bit-of word access was not reporting all bit values correctly for V, K, WX
and WY memory addresses greater than 1024.
FT- 357 SF Variable LVF mode bits (bits 1-3) were not cleared after a “Complete
Restart”. This interfered with the ability to change the loop mode using LVF.
FT- 356 Event Log Text for a SF compile error is in error; failure reason is reported as
“success”.
FT- 355 Added support for Task Code 4B and 4C used by the CTI TCAM and other
Operator Interfaces. .
FT- 353 Discrete outputs in MWIR, DCAT, MCAT, SHRB, and all drum instructions
within a JMP/MCR did not hold last value in output-disabled state.
FT- 351 A PACK statement that moved an integer into discrete bits did not work
correctly as generated by an APT program.
FT- 350 The RLL COMPARE instruction “GT” and “LT” bits were updated every scan
within a JUMP and MCR zones even when output-disable state was active.
FT -345 The search function could not find bit of Word addresses in an SFSUB
FT- 344 Entering a value of 0 as the time base for an EDRUM instruction caused an
“illegal instruction” error when the 2500 controller was set to RUN mode.
New Features and Improvements:
717: Increased maximum number of Profibus slots per slave that could be configured
from 64 to 128. This was done to facilitate the use of devices such as the DP/PA
link coupler.
714: Added new status bits to STW244 and STW245. Added reporting of Fatal Error
code in STW246.
713: Added the capability to automatically assign an IP address at power-up start if no
IP address is present or the IP address is 0.
710: Added the capability to log an event when a data point is forced or unforced.
694: Enhanced the information added to the event log when a scan watchdog error
occurs to facilitate troubleshooting.
692: Reduced the TCP keep-alive interval and number of retries for the local Ethernet
port to allow faster reconnection after the connection is disrupted.
688: Added the capability to set the IP address of the local Ethernet port while the 2500
controller is in RUN mode.
672: Added the capability to logically detect whether the Ethernet port is connected or
disconnected from an Ethernet network.
337: Added communications support allowing the CTI 5250-TI5 Operator Interface (and
other products using task code 4B and 4C) to read timer/counter and drum
program tables.
CTI Internal Issues Resolved
The following resolved issues relate to development versions that were never released
to the field: 757, 750, FT-358.
**************************************************************************************************
Firmware Version 6.05 (12/15/2009)
**************************************************************************************************
740: Profibus network could not be automatically restarted after the Profibus
processor stopped communicating. NOTE: This resolves one of the issues
contained in DevTrack 740.
698: The local Ethernet port stopped processing Ethernet packets after an
indeterminate period of time when connected to a network with moderate
activity. Recovery required cycling power to the 2500 Series controller. Heavy
Ethernet activity could cause a fatal error 113 or fatal error 103, despite the
changes introduced in firmware version 6.03. NOTE: This release substantially
improves the susceptibility of the local Ethernet port to excessive network traffic.
However, extreme packet rates, sufficient to disable most devices on the
network, can still cause the Ethernet port to quit communicating or a fatal error
to occur.
**************************************************************************************************
Firmware Version 6.03 (10/23/2009)
**************************************************************************************************
Firmware Issues Resolved:
727: The controller would not allow task Code 39 to be used to set the scan time to
variable mode.
723: In rare circumstances, unconfigured Series 500® remote bases could time out
when Special Function modules were installed.
720: Series 500® bases were erroneously logged out because of an error in handling
the RBC serial port.
712: Web based scan time statistics were incorrect when the “Start with Overlap”
option was selected.
698: Heavy Ethernet activity could cause the scan watchdog to trip, resulting in fatal
error 113. In some cases, the hardware watchdog could trip, causing fatal error
103.
695: TCP/IP processing was changed from scan-triggered to preemptive operation.
669: Analog loop and alarm data could not be accessed using a CVU because it
used task codes not supported by the 2500 controller. A user activated means
of logging rejected task codes in STW401-410 was added.
Improvements:
Enhanced Ethernet diagnostic statistics to aid in analyzing network problems.
**************************************************************************************************
Firmware Version 6.02 (8/31/2009)
**************************************************************************************************
Firmware Issues Resolved:
709:
Changes to I/O timing introduced in V6.00 and V5.00 caused some Siemens®
RBCs in certain I/O installations to report a diagnostic failure (error 01) on the
RBC display.
**************************************************************************************************
Firmware Version 6.00 (8/5/2009)
**************************************************************************************************
686:
The Siemens® ASCII module did not work with the 2500 controller.
682:
If the 2500 controller shipped with an invalid IP address, the IP address could
not be changed.
679:
The Link Status, Interface Speed, and Duplex mode were incorrectly reported
in the Ethernet Statistics web page.
677:
The serial port communications task did not execute during idle time within a
fixed scan. Allowing the task additional time to run can improve serial
communications performance for applications using a fixed scan.
642:
The 2500 controller would go to fatal error state (error 618), when a task code
request to read networks (TC20) was received from TISOFT connected to an
RBC serial port.
596:
The 2500 controller erroneously detected a module mismatch when an SF
module was installed and the SF bit was not set in the I/O configuration.
FT-329: A process “bump” could occur when the PID loop operating mode was
changed from manual to auto if the Loop PV Address parameter contained an
address and the LPV value was also set by a special function program called
from the loop.
FT-328: The SDT instruction did not allow T memory to be specified for an output
address.
FT-326: The PACKRS instruction allowed Invalid data to be loaded into a Ramp/Soak
Table.
FT-319: STW232 bits were not set properly immediately after an RLL program
containing an RSD instruction was compiled.
FT-317: STW1 bits could be overwritten by the MWI instruction.
New Features and Improvements:
Improved Remote I/O reliability in high noise environments when used with CPLD
firmware V6.02.
Improved the I/O diagnostic statistics Web Page (requires CPLD firmware V6.02).
Reduced Remote I/O scan time for I/O configurations that do not contain Series 500
I/O.
Added support for new SF program/subroutine instructions and password protection for
SF subroutines. NOTE: Requires PLC Workshop V4.50, anticipated to be released in
August 2009.
**************************************************************************************************
Firmware Version 5.00 (5/4/2009)
**************************************************************************************************
Firmware Issues Resolved:
654:
Removing power while in run-time edit mode could cause the controller to start
up in fatal error mode (FE60C).
653:
The time reported in the PLC Scan Statistics diagnostic web page for cyclic
RLL execution was twice the actual value.
651:
Changing the IP address while a TCP connection was established caused a
fatal error to be reported.
645:
Reduced scan overhead for bases that were enabled but not configured.
643:
Priority for Profibus immediate I/O task needed to be increased (CTI internal).
639:
A temporary undocumented change allowing SW9 to force the Ethernet speed
to 10Mb was removed.
637:
Peak times on the PLC Scan Statistics diagnostic web page were
underreported when using the “Start with Overlap” option.
630:
An APT program that would load in a Siemens® 545L would not load in a model
C100 due to differences in memory allocation.
613:
Noise occurring on the remote I/O network while the 2500 controller was
waiting on a reply message would cause the controller to miss the reply. Under
certain circumstances this could cause a remote base to be logged out and
placed in a fail-safe condition.
575:
During the firmware update process, if power was removed while I/O flash was
being written, the controller would start up in fatal error mode with a confusing
fatal error code. The firmware update procedure was changed to detect and
report the problem by returning a specific error code.
FT-316: When the PACK instruction was used to pack less than 16 bits into a word,
unused bit bits were not cleared (set to 0).
FT-315: SF lead-lag instruction results did not match the Siemens 505® controller
when the lead-lag ratio was greater than 1.0, less than 1.0, or when the
output was specified as a real number.
FT-309: The PACK statement did not permit bit memory types to be written to
loop/alarm CF variables.
FT-308: An error was not reported when the user attempted to create a loop that
already existed.
FT-307: Cyclic Special Function programs would stop running when an Exit on Error
instruction was executed.
FT-306: Output of a multiple parallel branch was ON when the input conditions were
NOT met (introduced in 4.03).
FT-302: The DCAT instruction did not honor changes new timer preset when the
associated TCP value was changed.
FT-271: Executing a syntax check on a very large program could cause the scan
watchdog to trip in certain circumstances.
New Features and Improvements:
• Added the capability to update firmware using the SD card interface.
• Improved the scan execution time and remote I/O performance.
• Added PLC mode changes to the event log.
• Improved readability of fatal error log event (#661).
• Added a log event for normal power down (#660).
• Reduced run-time checksum evaluation overhead (#652).
• Improved Profibus logging (#648, #633)).
• Added a duplicate IP address test for the local Ethernet port (#481).
• Added web diagnostic statistics for Ethernet, TCP/IP, and remote I/O.
**************************************************************************************************
Firmware Version 4.03 (12/15/2008)
**************************************************************************************************
Firmware Issues Resolved:
632:
Control Relay forces that were cleared using the “Clear All Forces” command
(Workshop) or “Unforce All” command (APT and TISOFT) did not remain
cleared after a subsequent power on start.
620:
User was unable to re-connect to port 4452 after changing the IP address while
all TCP connections were in use.
619:
When the user program was stored in flash and the program source was set to
flash, items designated as read-only could still be written using task code 5A.
614:
Excessive PRINT activity on the RS-232 serial port prevented the USB port
from communicating.
569:
An attempt to access DCP for unconfigured drums using the CAMP protocol
did not return an error as expected.
557:
An attempt to access word code 7800 did not return error code 09 as expected.
FT-301: The PACK statement did not work correctly when attempting to move
Loop/Alarm Control Flags to/from bit memory (C, X, and Y).
FT-300: Performing an on-line edit to an RLL program that contained two Task 2
instructions caused the controller to go to fatal error mode.
FT-299: Cyclic SF programs triggered erratically when the “Time Set” instruction was
executed.
FT-298: The LVF address data field could be interpreted incorrectly in a loop
calculation function when the loop transitioned to manual mode. Under certain
conditions, this could result in bit ‘C1’ erroneously being set to zero.
FT-295: A cyclic SF program did not immediately stop executing after the related
SFPGM instruction was edited on-line to change the execution to “in-line”.
FT-294: Cyclic SF programs with the “continue on error” parameter set to “no” did not
stop on error after an error was encountered.
FT-293: SFPGM instructions were being triggered when the input conditions were
false. This occurred because of a bug in the Workshop fss file. The 2500
firmware was modified to detect and correct the bug.
FT-292: This issue corrected multiple problems:
• The following RLL instructions were not operating properly when W or B
memory addresses were used: DCMP (W), MOVE (W), DIV (W), IMC (W
and B), MWFT (W), MWTT (W), PID (W), RSD (W), SMC (W and B),
TCMP (W), TSET (W), DCAT (B), DRUM (B), EDRUM (B), MCAT (B),
MDRMD ( B), MDRMW (B), MIRFT (B), MIRTT (B), MIRW (B), CTR (B).
•
•
MOVE instruction would fail if the destination address included the last
configured location for specified memory type.
RSD instruction would not turn on the output coil if called when Profibus
mode was set to STOP or the specified slave had not issued a
diagnostic.
SMC instruction could operate incorrectly because the mask bits with a
value of 0 were not being stored and evaluated properly.
•
The PID instruction (called as Fast Loop from RLL) would terminate with
error if triggered to run with no SFP defined for execution within PID
calculation (SFPGM = None).
New Features:
Status words can now be read when the controller is in fatal error (DT- 371).
Implemented remote I/O improvements that reduce susceptibility to RBC jabber.
Modified TCP/IP stack data message processing to run within the network time slice.
Set serial port parameters to 7, odd and 1 when port is selected for printing.
**************************************************************************************************
Firmware Version 4.00 (9/30/2008)
**************************************************************************************************
Firmware Issues Resolved:
609: First Scan flag bit 9 was not set after a power up restart with a bad battery.
608: V memory was not properly cleared after a power cycle with a bad or missing
battery.
603: Under certain conditions, the event log could be corrupted, causing FE 103.
600: After a power up start in RUN mode, the image register was not updated before
the first scan.
598: Excessive noise on the serial port could cause the controller to report a fatal
error.
592: Task code 14 failed to validate the upper bound of an address (CTI Internal).
590: Removing power from the Profibus network would cause the controller to report
a fatal error.
584: Reported peak scan time was erratic when there was no user program was
loaded and no I/O was installed.
552:
Powering off a DP slave which provided active bus termination when there was
no termination at the CTI 2500 Profibus port would cause the controller to report
a fatal error.
480: GRIDCONNECT Serial to Ethernet converter would not work when connected to
the CTI 2500 local Ethernet port.
FT-291: “NOT” contacts were improperly executing when contained in a complex
network with more than 16 parallel branches.
FT-289: The MIRW instruction did not execute properly in an RLL subroutine using
“B” memory.
FT-288: TCC values were not restored after power was cycled.
FT-287: The operation of setpoint clamping for PID loops differed from the Siemens
505® controller.
FT-286: Analog alarms were not handled properly when the alarm deadband
overlapped the low/High alarm values.
FT-284: Loop Reset Time could be set to 0 using the MATH or PACKLOOP
statements, causing the loop to function erratically.
FT-283: One Shot contacts erroneously triggered when transitioning from Run to Edit
mode.
New Features
• The special function PRINT instruction is now supported by the controller.
NOTE: Workshop V 4.30 and above is required to program the PRINT
statement.
• The product serial number is now reported in STW 258 – 259. (DT-601).
• Task code processing was enhanced to support Maple Systems terminals.
• Added a new diagnostic web page with enhanced scan statistics. (DT-602).
• Added support to report dual power supply status in STW 168.
**************************************************************************************************
Firmware Version 3.20 (8/21/2008)
**************************************************************************************************
FT-279: Loop reset time could be set to 0 via HMI or a data window. This invalid value
caused erratic loop operation.
FT-277: MCR instruction did not work correctly in some cases where the program
contained more than one MCR statement. .
FT-276: B memory was not accepted as a valid memory type within a Compare
instruction.
**************************************************************************************************
Firmware Version 3.18 (8/18/2008)
**************************************************************************************************
Firmware Issues Resolved:
589: Discrete forces were erroneously cleared after cycling AC power off and back on.
585: An attempt to execute an immediate input mapped to a Profibus network that had
never been brought online caused the RLL to stop processing instructions
following the immediate I/O instruction.
573: The firmware update procedure did not display an error code when a problem was
encountered updating the Profibus interface firmware.
555: Remote I/O bases in some installations would erroneously log off during
operation. This situation was most prevalent when the configuration contained
Series 500 I/O.
549: Some installations using Series 500 I/O were reporting a significant number of
remote I/O channel receive errors (STW 145) and timeout errors (STW 146).
543: Using the Complete Restart or Partial Restart commands to clear a fatal error
while the battery was disconnected caused the 2500 controller to erroneously
clear the user program.
GT-275: An RLL network that contained parallel branches, each branch containing a
NOT instruction combined with another after the branch ended did not execute
properly. The output was always off regardless of the condition of the inputs.
FT-272: The CTR instruction was operating differently than the Siemens Series 505®
controller in certain situations. When TCC=TCP the output was on (as
expected). Subsequently moving a value from V memory to TCC that is less
than TCP caused the output to go off.
FT-270: T memory addresses T1 – T7 were erroneously re-initialized every time an SF
program that was called from a Loop or an Alarm started execution. This
occurred even if the SF program had been previously suspended because the
time slice expired before the SF completed execution. If the user had re-used
T1-T7 for other purposes before execution was suspended, these values were
overwritten.
FT-269: The RLL BCD to Binary conversion instruction was not working properly when
the most significant bit (Bit 1) was set in the starting value.
FT-268: The SF Program MOD operation did not always work correctly when used in a
MATH statement due to the rounding precision being used in floating point
calculations.
FT-267: The WorkShop “Find” operation used to search for a specific instruction within
a PLC program could return a failure or fatal error due to an error in decoding
the network address.
FT-266: Fatal error 704 (Invalid SF number) was encountered after completing a runtime edit of the RLL that changed the address of the output coil following a
subroutine call.
FT-265: The PID Loop Ramp/Soak operation could not be restarted by setting its
associated LRSN value to the step number that corresponds to the start of an
R/S profile. The same problem could be encountered when attempting to
change LSRN from HMI.
Enhancements:
567:
Enhanced product web server to provide the capability to display/print all
events in the event log and to improve presentation of information and
options.
FT- 264: Reduced scan time overhead when tasks running in a time slice had nothing
to do.
**************************************************************************************************
Firmware Version 3.12 (6/4/2008)
**************************************************************************************************
Firmware Issues Resolved:
565: After installing V3.08, some CTI 2500 processors reported a fatal error. This
occurred when the flash area reserved for the user program contained an invalid
value, causing the flash checksum to fail on startup.
563: An unsupported or invalid request from a special function module caused the
processor to report a fatal error #113.
**************************************************************************************************
Firmware Version 3.08 (5/15/2008)
**************************************************************************************************
Issues Resolved:
FT-264: The “PACK TO” instruction did not allow the Data Start Address to be entered
as a constant.
FT-263: When multiple instances of the same SF subroutine were called from cyclic
RLL, the SFS would eventually stop executing.
FT-260: Executing a SF subroutine in-line within a cyclic task could cause a fatal error
when another SFS, running in a time slice, was interrupted after allocating
temporary memory.
FT-259: The IMATH statement produced an incorrect result when the “shift left” was
used with a long integer.
FT-258: An online search of SF subroutines in WorkShop did not find in-line SF
subroutines.
FT-257: A Task 1 label inserted after the first network would cause a cyclic task that
did nothing execute every 10ms. This added unnecessary PLC scan overhead
with no other adverse effect.
FT-255: Executing a syntax check of a program containing a large number of SKP and
LBL instructions caused the scan watchdog to trip, resulting in a fatal error.
553: Cyclic RLL Task did not execute on the first scan after transition from Program to
RUN mode except after CPU restart or complete download.
551: A problem reporting an error on the remote I/O network caused a Fatal Error 300.
545: Single Scan mode did not work properly using TISOFT.
543: When the Partial or Complete Restart command was used to clear a fatal error
while the battery was not installed or enabled, the user program was cleared.
541: A recurring Profibus network error eventually caused a Fatal Error 300.
Enhancements:
Implemented the capability to store a user program in on-board flash memory.
Added STW 455-469 to display receive errors by base.
Added STW 487 – 501 to display RBC timeouts by base. (DT533).
Improved Event Log formatting of variable text strings (DT435).
**************************************************************************************************
Firmware Version 3.07 (4/24/2008)
**************************************************************************************************
Issues Resolved:
558: Using V3.05 firmware, the CTI 2500 processor would erroneously report a fatal
error when connected to a Series 500 TIWAY NIM.
556: Following a fatal error condition, the CTI 2500 processor would erroneously log an
error if the SFIO input queue contained a deferred task code request.
**************************************************************************************************
Firmware Version 3.05 (3/17/2008)
**************************************************************************************************
Issues Resolved:
413: Remote I/O bases, attached using RS-485 cable, were erroneously logged off in
some installations where line jitter was high.
502: Remote I/O bases, attached by coaxial cable, were erroneously logged off in some
installations where line jitter was high.
522: A fatal error 300 would sometimes occur when removing RS-485 remote I/O
connections.
524: Web server pages did not contain proper product nomenclature.
526: A fatal error would occur when attempting to connect to the CTI 2500 Ethernet port
when the maximum number of TCP connections was exceeded.
528: STW 139 (number of forced bits) and STW 140 (number of forced words) were not
cleared when a Clear All request was received.
532: Entering an IP address of 0.0.0.0 prevented the TCP/IP stack from restarting until
power was cycled.
535: STW 146 (Channel 0 Timeout) was occasionally incremented in error.
537: TC17, Find Word Force, reported incorrect values for WX and WY addresses
above 1024.
540: TC55 failed to recognize position of Jumper A when configuring PLC memory.
Enhancements:
This release contains several modifications which reduce scan time when using remote
I/O.
This release contains significant improvements that increase remote I/O tolerance to
sub-optimal conditions. For best results, customers having remote I/O timeout
problems should concurrently update the remote I/O CPLD code to V5.0. Contact
CTI or your distributor for upgrade information.
**************************************************************************************************
Firmware Version 3.02 (2/21/2008)
**************************************************************************************************
NOTE: V3.02 files with a file date earlier than 2/21/08 should not be used. These
files did not support C100 processors and the local serial port correctly.
Issues Resolved:
FT-254: Loops were not set to manual mode when a Complete Restart command was
initiated.
FT-253: Loops were not queued for execution in the correct order when multiple loop
execution timers expired concurrently. Loops with shorter cycle times should
have been queued before loops with longer cycle times but were not.
FT-250: SF Scale Statement integer results were truncated instead of rounded.
FT-249: The MOVW instruction was not executing properly when using memory
locations TCP1024 or TCC1024 as either source/destination parameter.
Corrected limit checking issue with this instruction.
FT-248: See FT-247
FT-247: Frequently toggling loops in and out of cascade mode without a configured
remote setpoint would eventually cause a system exception, resulting in fatal
error 300. NOTE: This fix was included in V3.00 but not confirmed to be
resolved at the time V3.00 was released.
FT-246: The method used to queue SF programs would not allow all enabled SF
programs to run in certain configurations. In the worst case scenario, the
problem would occur when attempting to queue more than 32 Priority SF
programs or 32 Normal SF programs. NOTE: The fix allows up to 1023 Priority
or Normal SF programs to be queued concurrently.
520:
PLC memory was not cleared when executing a Power-On Restart command
(TC 34) with the battery bad, missing, or off as required.
517:
Loop Mode could not be unlocked from the Ladder Mode when both modes
were in Run.
515:
Changes to time slice values did not take effect immediately as required. A soft
restart or power cycle was required before taking effect. NOTE: This problem
was introduced in firmware version 3.0.
514:
User was able to change the value in STW139 (number of discrete forces) and
STW140 (number of word forces) by manually writing to the status word. This
has been prevented in the new release.
513:
The CTI 2500 controller would not communicate properly with a Simatic MP370 Operator panel using an RS-422 serial connection, sometimes resulting in
fatal error #103. This was caused by the failure of the serial controller interface
to recover from corrupted data packets.
410:
The local Ethernet port would stop responding after a storm of network
broadcast packets and would not recover until power was cycled.
**************************************************************************************************
Firmware Version 3.00 (1/15/2008)
**************************************************************************************************
Issues Resolved:
FT-244 Edits to analog alarms were erroneously limited to 64 on model C200 and 16
on model C100.
FT-241 The loop and alarm deadband was not functioning properly when the PV went
negative, potentially causing the alarm to chatter.
FT-240 The loop and alarm setpoint was not being clamped properly when remote
setpoint was not used and the clamping limit was 0.
FT-239 When using an in-line SFSUB, the SFSUB would not stop execution when the
SFEC variable was written and “Continue on Error” was set to no.
FT-238 The PID instruction incorrectly passed power flow when an “S Memory Busy”
error was encountered, preventing the PID from executing.
FT-236 An SF edit that disabled a Special Function Program caused other Special
Function Programs to stop executing
FT-234 When a three word SFEC block was written and subsequently cleared, all
words were cleared. This has been changed to clear only the first word,
emulating the Siemens 505® controller.
512
The C2500 rejected requests from TISOFT 7.1 to change the PLC time/day,
which contained invalid data in the high nibble of the day number byte. The
modified code ignores the high nibble.
510
The peak and dynamic discrete execution times were incorrectly reported when
the controller was in Program mode.
508
Fatal Error 103 was occasionally returned when the web server End button was
clicked.
505
A task code request to read I/O channel status did not return the same value as
the Siemens 505® controller.
503
Scan watchdog would occasionally trip when running a fixed scan with a
frequent cyclic task.
498
Connecting and disconnecting cable from a coax RBC while running
sometimes caused Fatal Error 300 to be reported.
494
0.1 second timer (TMR) would count too fast when a TSET instruction was
executed during the timer interval.
453
Changing the IP parameters for the local Ethernet port while a TCP client was
connected prevented all clients from re-connecting to the local Ethernet port.
Enhancements:
New, faster TCP/IP stack
**************************************************************************************************
Firmware Version 2.16 (11/16/2007)
**************************************************************************************************
Issues Resolved:
FT-231 Multiplexed timers embedded in a SUBR did not work correctly.
FT-232 Alarms were not cleared properly when other alarms became active before the
next sample interval.
FT-233 Incremental download using APT programming software caused an “illegal
instruction” error.
325
CTI 2500 controller did not support the 2541 Redundant Processor Module.
449
Old 2112 and 2114 RBC modules were not supported by the CTI 2500
controller.
466
467
STW 223-224 (binary time of day) value was not calculated correctly.
STW 226 bit 10 was not cleared during startup when default time/date used.
470
Cyclic Scan time interval was erroneously extended when using fixed scan time.
472
Slow performance when using the 2572-A in multicast mode with the CTI 2500
caused the 2572-A message queue to fill up. As a result, the application would
not work properly.
473
STW 299 did not reset when changing from fixed to variable scan mode.
476
Profibus did not automatically recover (go back to Operate mode) when a bus
error (such as a shorted wire) occurred.
477
Changing the time occasionally caused a fatal error to be reported.
479
Profibus startup memory diagnostics were not reported correctly.
484
PID reset value could be set to an invalid value (0) using a task code, which
caused the loop algorithm to fail (divide by 0 error).
486
STW 145 and 146 (remote I/O communications error and timeout counters)
could not be cleared when communicating via a 2572-A or an RBC serial port.
489
The CTI 2500 controller caused the CTI 2572-A module to reset when the
CAMP protocol was used to request an unconfigured loop or alarm value. This
occurred because the controller response to this request was not compatible to
the Siemens 505© controller. (Note: Some I/O servers will request a block of
data, including items not requested by the HMI).
Enhancements:
Added support for RBC serial port for remote I/O using CTI 2500-RIO or Siemens® 5056851 remote base controllers.
Enabled hardware watchdog on the master processor.
Improved execution speed of contacts and coils slightly.
**************************************************************************************************
Firmware Version 2.14 (10/3/2007)
**************************************************************************************************
Issues Resolved:
FT-222 RSD Instruction did not load diagnostic data into the designated memory
location.
409
The CTI 2500 controller did not support high-density mixed-mode modules
properly, including the Siemens® 505-7003 high speed counter module and
the CTI 2505 Vibration Sensor Interface Module.
464
STW 231 bit 16 was not set when a program with no Profibus configuration
was loaded.
469
The USB port failed to function after a power-on start when the PLC clock
month was set to October.
**************************************************************************************************
Firmware Version 2.12 (9/24/2007)
**************************************************************************************************
Issues Resolved:
FT-192: The CTI 2500-C100 controller reported the incorrect maximum number of
loops and alarms to the programming software.
FT-210: Special Function SCALE and UNSCALE instructions did not handle long
integer addresses correctly. The high 16 bits of the address were ignored.
FT-212: An RLL program containing a MWIR instruction using a B variable for the IR
parameter prevented the C500 controller from transitioning to RUN mode.
FT-214: The Special Function LEAD/LAG statements did not produce the same
results as the Siemens 505® PLCs.
FT-215: When attempting to use the TISOFT block and delete functions to delete a
single SF program, all SF programs were deleted.
FT-216 When performing a run-time edit in APT, an “unsupported task code” error
was returned.
FT-219: A checksum evaluation bug caused the CTI 2500 controller to erroneously go
to the fatal error state when evaluating some SF programs.
FT-220: The MOVW instruction did not execute correctly in an RLL subroutine when
the destination address = W20.
FT-223: All output coils within the JMP/JMPE zone were not frozen when the JMP
instruction lost power flow.
FT-224: Some coils within a MCR/MCRE zone did not function like the Siemens
Series 505® PLC when the MRC instruction was disabled. Coils with bit of
word addresses and DCAT/MCAT alarm output coils were not cleared as
required.
FT-225: Setting the time and date caused user program timers to time out.
388:
413:
426:
433:
441:
Intermittent Profibus connection occasionally caused the CTI 2500 controller
to go to the fatal error state. Changes were made to report this condition as a
non-fatal error.
The CTI 2500 controller would not maintain communications with remote
bases in noisy environments or installations with out-of-spec topologies.
Substantial changes were made to the I/O interface software to enhance
noise immunity.
User Programs with heavy cyclic RLL programs could cause update of the
Multi Segment Display (MSD) to become sluggish.
Status Word 299 was not consistently cleared when peak scan time was
cleared.
Some Profibus configurations caused the CTI 2500 controller to erroneously
go to the fatal error state when starting up in RUN mode.
442:
IP Address failed to advance when some user programs are running.
444:
Profibus interface diagnostic failure during startup caused the PLC to go to
the fatal error state, even if Profibus was not used. The behavior was
modified to log an event if the Profibus interface reports a diagnostic error at
startup. The Profibus interface will be evaluated for errors only after it is
configured for use.
Program download over the local Ethernet port was slower than expected.
The modification results in a speed improvement of 2 times.
Status word 144 did not report tenths and hundredths of a second correctly.
A slower than expected response of the Profibus interface occasionally
caused the controller to go to the fatal error state. The timeout was increased
to allow the interface to process special conditions.
Using APT with APTNet to perform run time edits on the CTI 2500 controller
via a 2572-A module would sometimes cause the 2572-A module to reset.
446:
448:
450:
452:
454:
459:
462:
An “Address Out of Range” error was incorrectly reported when attempting to
load some programs to a CTI 2500-C200. The highest analog point address
was improperly calculated when a low density discrete module was in the slot
following an analog module.
The user was prevented from entering the month as October when setting the
date.
The C2500 controller prevented a program containing a Profibus
configuration from being loaded unless all slaves were mapped to I/O register
addresses.
Enhancements:
The Fatal Error code is now displayed on the Multi Segment Display (MSD) when in
fatal error.
Event logging has been modified so that consecutive occurrences of the same event
increment an event counter rather than creating a new event record. This change
reduces clutter in the event log.
The TCP/IP Address can now be set when the controller is in Fatal Error state.
**************************************************************************************************
Firmware Version 2.11 (9/10/2007)
**************************************************************************************************
Issues Resolved:
417: The Remote I/O interface was overly sensitive to noisy environments and
improperly terminated cables (including RS-485 cabling). As a result, remote
bases were erroneously logged off. Changes were made to the I/O interface code
to enhance noise immunity.
**************************************************************************************************
Firmware Version 2.09 (8/29/2007)
**************************************************************************************************
Issues Resolved
FT-207: The Index Matrix Compare instruction did not function properly. The CUR PTR
value selected the incorrect mask for comparison.
FT-208: “S Memory Busy” error was erroneously set in STW 200 when editing SF
programs that are queued for execution (not marked as In-Line). This error
should be returned only for SF programs that are marked as In-Line. When
this error was set for a queued SF program, the program was erroneously
removed from the execution queue.
FT-209: The FIND operation would not locate implied addresses in a ladder logic
instruction. For example, if you entered a MOVW instruction that moved 10
words from V1 to V100, a search for V5 would not locate this instruction.
OTHER: Corrected syntax check problems with DCMP/DSET, MDRUMD/MDRUMW,
MWFT/MWTT, and SHRB instructions.
379: Merging or downloading certain Profibus configurations sometimes caused the
Profibus polling to stop, resulting in a fatal error.
415: Profibus modular slaves with more than 16 slots per slave were not supported.
417: When using Siemens 500 series® I/O, remote bases using coax connections
would occasionally go offline. The I/O interface has been modified to retry certain
base status requests when the base is logged in and to increase timeout
parameters in certain cases.
420: V memory addresses were incorrectly written on download when the V memory
size was configured to 64K words or greater. V memory addresses below 64 K
were overwritten with values contained in the addresses 64K and larger.
431: When using Profibus I/O with modules having discrete outputs and analog inputs,
the output and the input points on that module were incorrectly assigned to I/O
addresses.
432: I/O addresses ranges were not validated on download. This caused problems
when downloading programs to C100 or C200 processors that were developed on
larger models using I/O configurations that the model C100/C200 did not support.
434: The IP address of the local Ethernet port could not be changed if a TCP client was
connected to the local Ethernet port. Error message of “Configuration Lock” is
displayed. A change was made to allow the IP parameters to be changed even if
a TCP connection was present.
436: Incorrect amount of data was returned from task code 73 request. This error did
not affect user operation.
437: Drum Step Current (DSC) value was reported incorrectly for undefined drums.
439: The TCP/IP default router address was not preserved over a power cycle.
440: TISoft displayed incorrect drum parameters for DSP and DSC. DSP and SDC
values are 1 step more than the actual drum step.
Enhancements
The capability to log and event when an abnormal base logoff is detected has been
added to the I/O subsystem.
STW 471 – 485 have been added to maintain a cumulative count of abnormal base
logoff events by base.
Support for the Network Status (NS) LED has been added.
**************************************************************************************************
Firmware Version 2.08 (8/10/2007)
**************************************************************************************************
This release resolves the following issues.
FT-197: If the cyclic RLL task interrupts an analog scan task, the Cyclic RLL execution
time may be extended waiting on the analog scan task to complete.
FT-200: An SF program with a PRINT statement will not compile. PRINT statements
should be ignored.
FT-201: Analog Alarm V flags write 16 bits instead of 11 bits when the V flag is
assigned to control relays (C). This may cause the V flag data to overwrite
other control relays in use.
FT-202: The SF MATH instruction erroneously sets the SFEC when you assign the
maximum address value to an element.
FT-203: If you attempt to specify values rather than addresses when using the
PACKRS instruction, the SF program or subroutine will not compile.
FT-205: If you attempt to use the FIND command to locate a timer, Workshop may
cease responding.
FT-206: Timers presets are occasionally not written properly during a user program
download.
391:
When the PLC is set to a fixed scan time, the reported peak scan time is
always 1ms more than the fixed scan time, regardless of the fixed scan time
setting.
397:
A System Exception error is sometimes reported when a power outage
occurs.
399:
The Cyclic Peak Execution time as reported in CTI diagnostics status word
330 is not correct.
401:
TPET1 values not are calculated the same as the Siemens 505® PLC, which
uses TPET1 to display the peak scan time. The CTI 2500 uses TPET1 to
represent the peak time required to execute the Main RLL task (task 1) and
TPET2 to represent the peak cyclic RLL time (task2). NOTE: This was
resolved by adding a status word to allow the peak scan time to be read using
STW299.
404:
PLC scan time peaks are larger than expected.
405:
Scan time values in CTI diagnostic status words 308 – 327 are erroneous
when the PLC is set to fixed scan mode.
411:
Unable to change the IP address more than once when Ethernet cable is
attached.
412:
419:
420:
425:
431:
Entering an IP router address and then changing the router address causes
the PLC to halt.
Series 500 low density modules that have a mixture of word and discrete
points are not supported by the C2500. Also, module configurations 7X/1Y,
6X/2Y, 4X/4Y, 3X/5Y, 2X/6Y, and 1X/7Y are not properly supported.
When downloading a user program that configures 65 K or greater words of V
memory, V memory will be improperly written. This anomaly will cause V
memory addresses below 65 K to be erroneously cleared or overwritten with
values contained in higher addresses.
The Delta Computer Systems TMC188/40Q will cause the CPU to lock up if
the module is inserted into a remote base. NOTE: Although the fix prevents
PLC lockup; this module will not function in a remote base.
When a Profibus slave has a single slot configured for both discrete inputs and
discrete outputs, the incorrect outputs will be driven.
**************************************************************************************************
Firmware Version 2.07 (7/26/2007)
**************************************************************************************************
Resolved the following issues:
190: Using timer Instructions in Cyclic RLL causes erroneous RLL checksum fatal error.
195: When a MATH instruction contains an integer for the destination, the resulting
value is truncated instead of rounded as it should be.
198: Using a Model C100, you cannot enter a loop remote setpoint WX address greater
than WX1020.
395: Heavy Ethernet traffic will cause USB communications to become erratic or lock
up.
400: “Brownout” conditions (low AC power) or power up start in low voltage conditions
can cause the controller to go to the fatal error state.
403: Some large programs will not complete download via USB
407: Using two timers to set and reset C contacts, the C contacts are locked to 0 after
changing from RUN mode to PROGRAM mode and then back to RUN mode.
**************************************************************************************************
Firmware Version 2.06 (7/16/2007)
**************************************************************************************************
Revised task code responses to support C100 processor.
Resolved the following problems:
187: SFSUB SSR Statement does not allow parameter in register start address field.
191: Loop parameters specified as integer values in a packed loop instruction are being
packed as real numbers.
193: Analog tasks are sometimes reporting done when they have not finished.
194: Temporary memory is erroneously re-initialized on occasion when the program did
not complete in the previous time slice.
**************************************************************************************************
Firmware Version 2.00 (6/28/2007)
**************************************************************************************************
Original Production Release
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertisement