CB Report for PoE Adapter

CB Report for PoE Adapter
<11003268 001>
Page 2 of 70
Particulars: test item vs. test requirements
Equipment mobility .......................................: movable and transportable
Operating condition .......................................: continuous
Mains supply tolerance (%)...........................: -10/+10
Tested for IT power systems ........................: Yes
IT testing, phase-phase voltage (V) .............: 230 V (for Norway)
Class of equipment .......................................: Class I
Mass of equipment (kg).................................: 0.23
Protection against ingress of water ..............: IPX0
Test case verdicts
Test case does not apply to the test object ..: N/A
Test item does meet the requirement ..........: P(ass)
Test item does not meet the requirement ....: F(ail)
Testing
Date of receipt of test item ...........................: December, 2004
Date(s) of performance of test .....................: November to December, 2004
General remarks
”This report is not valid as a CB Test Report unless appended to a CB Test Certificate issued by a
NCB, in accordance with IECEE 02”.
This report shall not be reproduced except in full without the written approval of the testing laboratory.
The test results presented in this report relate only to the item(s) tested.
”(see remark #)" refers to a remark appended to the report.
"(see Annex #)" refers to an annex appended to the report.
Throughout this report a point is used as the decimal separator.
Procedure deviation:
Argentina, Australia, Austria, Belgium, Canada, Denmark, Finland, France, Germany, Greece, Hungary,
India, Israel, Italy, Korea, Malaysia, Netherlands, Norway, Poland, Singapore, Slovenia, Sweden,
Switzerland, United Kingdom, United States of America
Manufacturer:
Same as applicant.
Factory(ies):
1. Phihong (Dongguan) Electronics Co., Ltd.
Keji Road, Yinhu IND. Zone, Qingxi Town, Dongguan City, Guangdong, P.R. China
2. Dongguan Phitek Electronics Co., Ltd.
Xie Kng Cuen, Qingxi Town, Dongguan City, Guangdong, P.R. China.
3. Phitek (Tianjin) Electronics Co., Ltd.
No. 11, Wei Shan Road, Tianjin Economic-Technological Development Area, Tianjin 300457, P.R. China
4. PhiHong Electronics (Suzhou) Co., Ltd .
No.98 ( No. 6 Factory) Hengshan Rd., New District, Suzhou, Jiangsu, P.R. China
TRF No.:IECEN60950_1B
TRF originator: SGS Fimko
<11003268 001>
Page 3 of 70
Comments:
Brief description of the test sample:
The equipment with type designation PSA16U-480yyyyy(y=any character, blank or brackets)for marketing
purpose only) is an external AC power adapter (desk top) for DC supply of information technology equipment.
The adaptor’s top enclosure is secured to bottom enclosure by three screws and four snaps.
Maximum ambient temperature is specified as 40 °C.
The output of the adaptor is in compliance with the requirements of limited power source
(sub-clause 2.5).
This power adapter is not for TNV
TRF No.:IECEN60950_1B
TRF originator: SGS Fimko
<11003268 001>
Page 4 of 70
Copy of marking plate(s):
TRF No.:IECEN60950_1B
TRF originator: SGS Fimko
<11003268 001>
Page 5 of 70
IEC 60950-1 / EN 60950-1
Clause
Requirement – Test
Result – Remark
Verdict
1
GENERAL
P
1.5
Components
P
1.5.1
General
See below.
P
Comply with IEC 60950 or relevant component
standard
(see appended table 1.5.1)
P
1.5.2
Evaluation and testing of components
Components, which are
certified to IEC and/or national
standards, are used correctly
within their ratings or had been
evaluated during this approval.
P
1.5.3
Thermal controls
No thermal controls provided.
N
1.5.4
Transformers
Transformer used is suitable for
the intended application and
complies with the relevant
requirements of the standard.
P
1.5.5
Interconnecting cables
Interconnection o/p cable to
other device is carrying only
SELV on an energy level below
240 VA.
P
→ Except the insulation
material, there are no further
requirements to the o/p
interconnection cable.
1.5.6
Capacitors in primary circuits ............................. : Between the lines one capacitor
subclass X2 according to IEC
60384-14:1993 with 21 days
damp heat test.
P
1.5.7
Double insulation or reinforced insulation bridged See below.
by components
Double or reinforced insulation
between primary and
secondary bridged by Y1capacitor C37.
P
1.5.7.1
General
See below.
N
1.5.7.2
Bridging capacitors
Y1-capacitor C37 according
IEC 60384-14:1993.
P
1.5.7.3
Bridging resistors
No bridging resistors
N
1.5.7.4
Accessible parts
The adapter’s output connector
is designed as limited current
circuit (see 2.4).
P
1.5.8
Components in equipment for IT power systems
Phase to PE designed in
according to phase-to-phase
working voltage.
P
1.6
Power interface
TRF No.:IECEN60950_1B
P
TRF originator: SGS Fimko
Page 6 of 70
<11003268 001>
IEC 60950-1 / EN 60950-1
Clause
Requirement – Test
Result – Remark
Verdict
1.6.1
AC power distribution systems
TN power system. IT power
system for Norway.
P
1.6.2
Input current
Highest load according to
1.2.2.1 for this equipment is the
operation with the maximum
specified DC-load (see
appended table 1.6.2).
P
1.6.3
Voltage limit of hand-held equipment
This appliance is not a handheld equipment.
N
1.6.4
Neutral conductor
The neutral is not identified in
the equipment. Basic insulation
for rated voltage between
earthed parts and primary
phases.
P
1.7
Marking and instructions
1.7.1
Power rating
P
See below.
P
Rated voltage(s) or voltage range(s) (V) ............ : 100-240V~
P
Symbol for nature of supply, for d.c. only ............ : Mains from AC source
N
Rated frequency or rated frequency range (Hz) . : 50-60Hz
P
Rated current (mA or A) ..................................... : 0.4A
P
Manufacturer’s name or trademark or
PHIHONG
identification mark ............................................... :
P
Type/model or type reference ............................. : PSA16U-480yyyyy(y=any
character, blank or brackets)
P
Symbol for Class II equipment only .................... : Class I equipment.
N
Other symbols .................................................... : Additional symbols or marking
does not give rise to
misunderstanding.
P
Certification marks .............................................. : TÜV GS mark, others see the
copy of marking plates.
N
1.7.2
Safety instructions
User manual is provided. It
also contains instructions
regarding the disconnect
device. States the max.
allowed ambient and intended
use.
P
1.7.3
Short duty cycles
Equipment is designed for
continuous operation.
N
1.7.4
Supply voltage adjustment ................................. : Full range circuit.
N
Methods and means of adjustment; reference to
installation instructions ....................................... :
N
TRF No.:IECEN60950_1B
TRF originator: SGS Fimko
Page 7 of 70
<11003268 001>
IEC 60950-1 / EN 60950-1
Clause
Requirement – Test
Result – Remark
1.7.5
Power outlets on the equipment ......................... : No outlet.
N
1.7.6
Fuse identification (marking, special fusing
F1 T2A 250V
characteristics, cross-reference) ........................ :
P
1.7.7
Wiring terminals
N
1.7.7.1
Protective earthing and bonding terminals ......... : Appliance inlet used
N
1.7.7.2
Terminal for a.c. mains supply conductors
The equipment with appliance
inlet, which is intended to use
the detachable type power
supply cord.
N
1.7.7.3
Terminals for d.c. mains supply conductors
See below
N
1.7.8
Controls and indicators
Green and red LED on sec.o/p.
Green LED indicates
connection OK red Fault.
P
1.7.8.1
Identification, location and marking .................... : See below.
N
1.7.8.2
Colours .............................................................. : Green and red
N
1.7.8.3
Symbols according to IEC 60417 ........................ : Ditto.
N
1.7.8.4
Markings using figures ...................................... : Ditto.
N
1.7.9
Isolation of multiple power sources .................... : Only one main connection.
N
1.7.10
IT power distribution systems
To be evaluated when
submitted for national
approval.
N
1.7.11
Thermostats and other regulating devices
No thermostat or other
regulating device.
N
1.7.12
Language(s) ....................................................... : Safety instructions in English
and German and marking in
English.
⎯
1.7.13
Durability
P
See below.
The label was subjected to the
permanence of marking test.
The label was rubbed with
cloth soaked with water for 15s
and then again for 15s with the
cloth soaked with petroleum
spirit.
Verdict
After this test there was no
damage to the label. The
marking on the label did not
fade. There was no curling nor
lifting of the label edge.
1.7.14
Removable parts
No removable parts.
P
1.7.15
Replaceable batteries
No batteries.
N
1.7.16
Language(s) ........................................................ :
⎯
Operator access with a tool................................. : No operator access with a tool.
N
TRF No.:IECEN60950_1B
TRF originator: SGS Fimko
Page 8 of 70
<11003268 001>
IEC 60950-1 / EN 60950-1
Clause
Requirement – Test
Result – Remark
1.7.17
Equipment for restricted access locations........... : Equipment not limited for the
use in restricted access
locations.
N
2
PROTECTION FROM HAZARDS
P
2.1
Protection from electric shock and energy hazards
P
2.1.1
Protection in operator access areas
See below.
P
2.1.1.1
Access to energized parts
See below.
P
Test by inspection ............................................... : No access with test finger to
any parts with only basic
insulation to ELV or hazardous
voltage.
Verdict
P
The test pin can not touch
hazardous voltage. There are
no openings within the whole
enclosure.
Test with test finger ............................................ : Ditto.
P
Test with test pin ................................................. : Ditto.
P
Test with test probe ............................................ : No TNV circuits.
N
2.1.1.2
Battery compartments ........................................ : No battery compartment.
N
2.1.1.3
Access to ELV wiring
No ELV wiring in operator
accessible area.
N
Working voltage (Vpeak or Vrms); minimum
distance (mm) through insulation
(see appended table 2.10.5)
⎯
2.1.1.4
Access to hazardous voltage circuit wiring
No hazardous voltage wiring in
operator accessible area.
N
2.1.1.5
Energy hazards .................................................. : Energy does not exceed
240VA between any two points
of output connector of
secondary circuit.
P
Results see appended table.
2.1.1.6
Manual controls
No manual controls.
N
2.1.1.7
Discharge of capacitors in equipment
No risk of electric shock, see
below.
P
Time-constant (s); measured voltage (V)............ :
(see appended table 2.1.1.7)
⎯
2.1.2
Protection in service access areas
No maintenance works in
operation mode necessary.
N
2.1.3
Protection in restricted access locations
The unit is not limited to be
used in restricted locations.
N
2.2
SELV circuits
TRF No.:IECEN60950_1B
P
TRF originator: SGS Fimko
<11003268 001>
Page 9 of 70
IEC 60950-1 / EN 60950-1
Clause
Requirement – Test
Result – Remark
Verdict
2.2.1
General requirements
42.4V peak or 60VDC are not
exceeded in SELV circuit
under normal operation or
single fault condition.
2.2.2
Voltages under normal conditions (V) ................. : Results see appended table.
P
2.2.3
Voltages under fault conditions (V) ..................... : Single fault did not cause
excessive voltage in accessible
SELV circuits. Limits of 71V
peak and 120V DC were not
exceeded for a period longer
than 0.2s.
P
P
Results see appended table.
2.2.3.1
Separation by double insulation or reinforced
insulation (method 1)
Primary and secondary are
separated by double or
reinforced insulation.
P
2.2.3.2
Separation by earthed screen (method 2)
Method 2 is not used.
N
2.2.3.3
Protection by earthing of the SELV circuit
(method 3)
Method 3 is not used.
N
2.2.4
Connection of SELV circuits to other circuits ...... : In compliance with 1.5.7, 2.2.2,
2.2.3.and 2.4
P
2.3
TNV circuits
N
2.3.1
Limits
N
Type of TNV circuits ............................................ :
⎯
Separation from other circuits and from accessible
parts
N
Insulation employed............................................. :
⎯
Separation from hazardous voltages
N
Insulation employed............................................. :
⎯
Connection of TNV circuits to other circuits
N
Insulation employed............................................. :
⎯
2.3.5
Test for operating voltages generated externally
N
2.4
Limited current circuits
P
2.4.1
General requirements
2.3.2
2.3.3
2.3.4
TRF No.:IECEN60950_1B
The pins of the output
connector are accessible to the
user and connected to the
primary circuit by bridging Y1capacitor C37. Therefore, the
circuit for the output pins must
be designed as a limited current
circuit.
P
TRF originator: SGS Fimko
<11003268 001>
Page 10 of 70
IEC 60950-1 / EN 60950-1
Clause
Requirement – Test
Result – Remark
2.4.2
Limit values
0.7mA
Verdict
P
Frequency (Hz).................................................... : See appended table 2.4.
⎯
Measured current (mA) ....................................... : See appended table 2.4.
⎯
Measured voltage (V) .......................................... : See appended table 2.4.
⎯
Measured capacitance (µF)................................. : 2200pF
⎯
2.4.3
Connection of limited current circuits to other
circuits
P
2.5
Limited power sources
P
Inherently limited output
N
Impedance limited output
N
Overcurrent protective device limited output
N
Regulating network limited output under normal
operating and single fault condition
See 2.4.1.
Results see appended table
2.5.
P
Regulating network limited output under normal
operating conditions and overcurrent protective
device limited output under single fault condition
N
Output voltage (V), output current (A), apparent
Results see appended table
power (VA)........................................................... : 2.5.
⎯
Current rating of overcurrent protective device (A)
⎯
2.6
Provisions for earthing and bonding
P
2.6.1
Protective earthing
The PE-pin of the appliance
inlet is direct fixed to the PCB
and to secondary by EMC
board
P
2.6.2
Functional earthing
Secondary functional earthing
is connected to protectively
earthed conductive part which
part is separated from primary
by basic insulation.
P
2.6.3
Protective earthing and protective bonding
conductors
See below.
P
2.6.3.1
General
2.6.3.2
Size of protective earthing conductors
2.6.3.3
N
No power cord provided.
N
Rated current (A), cross-sectional area (mm2),
AWG .................................................................... :
⎯
Size of protective bonding conductors
N
Rated current (A), cross-sectional area (mm2),
AWG .................................................................... :
⎯
TRF No.:IECEN60950_1B
TRF originator: SGS Fimko
Page 11 of 70
<11003268 001>
IEC 60950-1 / EN 60950-1
Clause
Requirement – Test
2.6.3.4
Resistance (Ω) of earthing conductors and their
terminations, test current (A) ............................... :
P
2.6.3.5
Colour of insulation.............................................. :
N
2.6.4
Terminals
See below.
P
2.6.4.1
General
Appliance inlet considered as
protective earthing terminal.
P
2.6.4.2
Protective earthing and bonding terminals
Ditto
P
Rated current (A), type and nominal thread
Ditto
diameter (mm) ..................................................... :
⎯
2.6.4.3
Separation of the protective earthing conductor
from protective bonding conductors
N
2.6.5
Integrity of protective earthing
See below.
P
2.6.5.1
Interconnection of equipment
The equipment has its own
earthing connection. Any other
units interconnected to it via the
DC output connector shall
provide SELV only.
P
2.6.5.2
Components in protective earthing conductors
and protective bonding conductors
No switch or overcurrent
protective device in protective
earthing or protective bonding
conductor.
P
2.6.5.3
Disconnection of protective earth
It is not possible to disconnect
earth without disconnecting the
mains as an approved
appliance inlet is used.
P
2.6.5.4
Parts that can be removed by an operator
Ditto
P
2.6.5.5
Parts removed during servicing
Ditto
P
2.6.5.6
Corrosion resistance
All part comprising the
connections are plated and
metal to metal which comply
with annex J.
P
2.6.5.7
Screws for protective bonding
No such screw used.
P
2.6.5.8
Reliance on telecommunication network or cable
distribution system
No TNV.
N
2.7
Overcurrent and earth fault protection in primary circuits
P
2.7.1
Basic requirements
P
TRF No.:IECEN60950_1B
Result – Remark
The equipment relies on a 16 A
rated fuse or circuit breaker of
the wall outlet protection of the
building installation in regard to
L to N short-circuits. Over
current protection is provided by
the built-in fuse.
Verdict
TRF originator: SGS Fimko
Page 12 of 70
<11003268 001>
IEC 60950-1 / EN 60950-1
Clause
Requirement – Test
Result – Remark
Instructions when protection relies on building
installation
Not applicable for pluggable
equipment type A.
N
2.7.2
Faults not covered in 5.3
The protection device is well
dimensioned and mounted.
P
2.7.3
Short-circuit backup protection
Pluggable equipment type A.
The building installation is
considered as providing shortcircuit backup protection.
P
2.7.4
Number and location of protective devices ........ : Over current protection by one
fuse. Protection devices in the
building installation will provide
sufficient protection against
earth faults.
P
2.7.5
Protection by several devices
N
2.7.6
Warning to service personnel.............................. : Not intended for repairing.
N
2.8
Safety interlocks
N
2.8.1
General principles
N
2.8.2
Protection requirements
N
2.8.3
Inadvertent reactivation
N
2.8.4
Fail-safe operation
N
2.8.5
Moving parts
N
2.8.6
Overriding
N
2.8.7
Switches and relays
N
2.8.7.1
Contact gaps (mm) ............................................. :
N
2.8.7.2
Overload test
N
2.8.7.3
Endurance test
N
2.8.7.4
Electric strength test
N
2.8.8
Mechanical actuators
N
2.9
Electrical insulation
2.9.1
Properties of insulating materials
Natural rubber, asbestos or
hygroscopic material is not
used.
P
2.9.2
Humidity conditioning
See below.
P
Only one fuse provided.
Verdict
Humidity (%) ....................................................... : Required is a test at 20-30°C,
91-95% R.H. for 48h. However,
the test was performed at 40°C
at 95% R.H. for 120h
⎯
Temperature (°C) ................................................ : 40 °C
⎯
TRF No.:IECEN60950_1B
TRF originator: SGS Fimko
Page 13 of 70
<11003268 001>
IEC 60950-1 / EN 60950-1
Clause
Requirement – Test
Result – Remark
Verdict
2.9.3
Grade of insulation
Insulation comply with subclauses 2.10, 4.5.1 and 5.2.
2.10
Clearances, creepage distances and distances through insulation
P
2.10.1
General
See 2.10.3, 2.10.4 and 2.10.5.
P
2.10.2
Determination of working voltage
The rms and the peak voltage
were measured on the
switching power supply.
P
P
The unit was connected to a
240V TN power system and
secondary ground was
maintained during
measurement.
Results see appended table
2.10.2.
2.10.3
Clearances
P
See below.
Alternative method of Annex G
not considered.
2.10.3.1
General
See below.
P
2.10.3.2
Clearances in primary circuits
(See appended table 2.10.3
and 2.10.4)
P
2.10.3.3
Clearances in secondary circuits
In compliance with 5.3.4 c).
N
2.10.3.4
Measurement of transient voltage levels
Alternative method of Annex G
not considered.
N
2.10.4
Creepage distances
(See appended table 2.10.3
and 2.10.4)
P
CTI tests .............................................................. : CTI rating for all materials of
minimum 100.
⎯
2.10.5
Solid insulation
See below.
P
2.10.5.1
Minimum distance through insulation
(See appended table 2.10.5)
P
2.10.5.2
Thin sheet material
Thin sheet material (polyester
tape) used in transformer T1.
P
2.10.5.3
2.10.5.4
Number of layers (pcs) ........................................ : 3 layers
⎯
Electric strength test
3000Vac each layer
⎯
Printed boards
Not applied for.
N
Distance through insulation
N
Electric strength test for thin sheet insulating
material
⎯
Number of layers (pcs) ........................................ :
N
Wound components
N
TRF No.:IECEN60950_1B
TRF originator: SGS Fimko
Page 14 of 70
<11003268 001>
IEC 60950-1 / EN 60950-1
Clause
Requirement – Test
Result – Remark
Verdict
Number of layers (pcs) ........................................ :
N
Two wires in contact inside wound component;
angle between 45° and 90° ................................ :
N
2.10.6
Coated printed boards
2.10.6.1
General
N
2.10.6.2
Sample preparation and preliminary inspection
N
2.10.6.3
Thermal cycling
N
2.10.6.4
Thermal ageing (°C) ............................................ :
N
2.10.6.5
Electric strength test
⎯
2.10.6.6
Abrasion resistance test
N
Electric strength test
⎯
Enclosed and sealed parts .................................. : No hermetically sealed
component.
N
Temperature T1=T2 + Tma – Tamb +10K (°C)... :
N
Spacings filled by insulating compound .............. : Optical isolators are approved
components. Other components
not applied for (see appended
table 2.10.5).
P
Electric strength test
Dto
⎯
2.10.9
Component external terminations
See appended table 2.10.3
and 2.10.4.
P
2.10.10
Insulation with varying dimensions
No reduction of distances
applied.
N
3
WIRING, CONNECTIONS AND SUPPLY
P
3.1
General
P
3.1.1
Current rating and overcurrent protection
No wires in this unit
N
3.1.2
Protection against mechanical damage
See below
N
3.1.3
Securing of internal wiring
No wires in this unit
N
3.1.4
Insulation of conductors
The insulation of the individual
conductors is suitable for the
application and the working
voltage. For the insulation
materials see sub-clause 3.1.1.
P
3.1.5
Beads and ceramic insulators
Not used.
N
3.1.6
Screws for electrical contact pressure
No electrical contact pressure
by screwed connections.
N
3.1.7
Insulating materials in electrical connections
All current carrying
connections are metal to metal.
P
2.10.7
2.10.8
TRF No.:IECEN60950_1B
No coated printed boards
N
TRF originator: SGS Fimko
Page 15 of 70
<11003268 001>
IEC 60950-1 / EN 60950-1
Clause
Requirement – Test
Result – Remark
Verdict
3.1.8
Self-tapping and spaced thread screws
No self-tapping or spaced
thread screws.
P
3.1.9
Termination of conductors
All conductors are reliably
secured by use of solder-pins
or glue or other mechanical
fixing means.
P
10 N pull test
Force of 10 N applied to the
termination points of the
conductors.
P
3.1.10
Sleeving on wiring
No sleeving used to provide
supplementary insulation.
N
3.2
Connection to an a.c. mains supply or a d.c. mains supply
P
3.2.1
Means of connection .......................................... : The adapter provided with an
appliance inlet for mains
connection.
P
3.2.1.1
Connection to an a.c. mains supply
Dtto
P
3.2.1.2
Connection to a d.c. mains supply
Not applicable.
N
3.2.2
Multiple supply connections
Only one mains connection.
N
3.2.3
Permanently connected equipment
Appliance inlet provided, not a
permanently connected
equipment.
N
⎯
Number of conductors, diameter (mm) of cable
and conduits ....................................................... :
3.2.4
Appliance inlets
The appliance inlet complies
with IEC 60320-1. A power
cord can be inserted without
difficulties and does not
support the unit.
P
3.2.5
Power supply cords
No power cord provided. An
approved cord set will be
provided when submitted for
national approval.
N
3.2.5.1
AC power supply cords
ditto
N
Type..................................................................... :
⎯
Rated current (A), cross-sectional area (mm2),
AWG .................................................................... :
⎯
3.2.5.2
DC power supply cords
N
3.2.6
Cord anchorages and strain relief
Appliance inlet.
N
Mass of equipment (kg), pull (N) ....................... :
⎯
Longitudinal displacement (mm) ........................ :
⎯
TRF No.:IECEN60950_1B
TRF originator: SGS Fimko
Page 16 of 70
<11003268 001>
IEC 60950-1 / EN 60950-1
Clause
Requirement – Test
Result – Remark
Verdict
3.2.7
Protection against mechanical damage
Enclosure design without sharp
edges or points that could
damage the power supply
cord.
P
3.2.8
Cord guards
Appliance inlet.
N
D (mm); test mass (g) ......................................... :
⎯
Radius of curvature of cord (mm)........................ :
⎯
3.2.9
Supply wiring space
3.3
Wiring terminals for connection of external conductors
Appliance inlet provided, no wiring terminal for connection of external conductors.
N
3.3.1
Wiring terminals
N
3.3.2
Connection of non-detachable power supply
cords
N
3.3.3
Screw terminals
N
3.3.4
Conductor sizes to be connected
N
Rated current (A), cord/cable type, cross-sectional
area (mm2) .......................................................... :
⎯
Wiring terminal sizes
N
Rated current (A), type and nominal thread
diameter (mm) .................................................... :
⎯
3.3.6
Wiring terminals design
N
3.3.7
Grouping of wiring terminals
N
3.3.8
Stranded wire
N
3.4
Disconnection from the mains supply
P
3.4.1
General requirement
Disconnect device provided.
P
3.4.2
Disconnect devices
Appliance coupler
P
3.4.3
Permanently connected equipment
Not a permanently connected
equipment.
N
3.4.4
Parts which remain energized
When appliance coupler is
disconnected no remaining
parts with hazardous voltage in
the equipment.
P
3.4.5
Switches in flexible cords
No switches.
N
3.4.6
Single-phase equipment and d.c. equipment
The power cord or appliance
coupler disconnects both poles
simultaneously.
P
3.4.7
Three-phase equipment
Single phase.
N
3.4.8
Switches as disconnect devices
No switches.
N
3.3.5
TRF No.:IECEN60950_1B
Appliance inlet.
N
TRF originator: SGS Fimko
Page 17 of 70
<11003268 001>
IEC 60950-1 / EN 60950-1
Clause
Requirement – Test
Result – Remark
Verdict
3.4.9
Plugs as disconnect devices
Appliance coupler used.
N
3.4.10
Interconnected equipment
Not interconnected equipment.
N
3.4.11
Multiple power sources
Only one supply connection.
N
3.5
Interconnection of equipment
3.5.1
General requirements
3.5.2
Types of interconnection circuits ......................... : LCC and SELV interconnection
circuit.
P
3.5.3
ELV circuits as interconnection circuits
N
4
PHYSICAL REQUIREMENTS
P
4.1
Stability
P
P
See below.
P
No ELV interconnection.
Angle of 10°
Length and width exceed height
by far.
P
Test: force (N).....................................................:
Not floor standing.
N
4.2
Mechanical strength
4.2.1
General
See below. After the tests, the
adapter continued to comply
with 2.1.1 and 2.10.
P
4.2.2
Steady force test, 10 N
10N applied to components.
P
4.2.3
Steady force test, 30 N
No internal enclosure.
N
4.2.4
Steady force test, 250 N
250N applied to outer
enclosure. No energy or other
hazards.
P
4.2.5
Impact test
No hazard as result from steel
sphere ball impact test.
P
Fall test
Dtto
P
Swing test
Dtto
P
Drop test
The AC adapter was subjected
to three drops from 1m height
on hard wooden surface. After
the test, no damage to
insulation, no energy hazards or
damage to enclosure
integration.
P
4.2.6
TRF No.:IECEN60950_1B
P
TRF originator: SGS Fimko
Page 18 of 70
<11003268 001>
IEC 60950-1 / EN 60950-1
Clause
Requirement – Test
Result – Remark
4.2.7
Stress relief test
After 7 hours at 70°C and
cooling down to room
temperature, no shrinkage ,
distortion or loosening any
enclosure part was noticeable
on the adapter.
P
4.2.8
Cathode ray tubes
No cathode ray tube.
N
Picture tube separately certified .......................... :
Verdict
N
4.2.9
High pressure lamps
4.2.10
Wall or ceiling mounted equipment; force (N) .... : Optional: Wall or ceiling
mounted equipment. According
to the installation manual if
fixed on the wall, equipment
should get fixed with 2 screws
which can stand least 6kg
each.
P
4.3
Design and construction
P
4.3.1
Edges and corners
4.3.2
Handles and manual controls; force (N).............. : No such components.
N
4.3.3
Adjustable controls
No adjustable controls.
N
4.3.4
Securing of parts
Electrical and mechanical
connections can be expected
to withstand usual mechanical
stress.
P
4.3.5
Connection of plugs and sockets
No mismating of connector,
plug or socket possible. IEC
60083 and IEC 60320
connectors are not used in
SELV.
P
4.3.6
Direct plug-in equipment
Not direct plug-in type.
N
No high pressure lamps.
Edges and corners of the
enclosure are rounded.
N
P
Dimensions (mm) of mains plug for direct plug-in:
N
Torque and pull test of mains plug for direct
plug-in; torque (Nm); pull (N)............................... :
N
4.3.7
Heating elements in earthed equipment
No heating elements.
N
4.3.8
Batteries
No batteries.
N
4.3.9
Oil and grease
No oil or grease.
N
4.3.10
Dust, powders, liquids and gases
Equipment in intended use not
considered to be exposed to
these.
N
4.3.11
Containers for liquids or gases
No containers for liquid or
gases.
N
TRF No.:IECEN60950_1B
TRF originator: SGS Fimko
Page 19 of 70
<11003268 001>
IEC 60950-1 / EN 60950-1
Clause
Requirement – Test
Result – Remark
4.3.12
Flammable liquids...............................................:
No flammable liquids.
Verdict
N
Quantity of liquid (l).............................................:
N
Flash point (°C)...................................................:
N
4.3.13
Radiation; type of radiation ................................:
No ionizing radiation, ultraviolet
light or laser present.
N
4.3.13.1
General
See below.
N
4.3.13.2
Ionizing radiation
N
Measured radiation (pA/kg) .................................:
⎯
Measured high-voltage (kV) ................................:
⎯
Measured focus voltage (kV) ..............................:
⎯
CRT markings .....................................................:
⎯
Effect of ultraviolet (UV) radiation on materials
N
Part, property, retention after test, flammability
classification ......................................................:
N
4.3.13.4
Human exposure to ultraviolet (UV) radiation ...:
N
4.3.13.5
Laser (including LEDs)
Three indicator LED provided
sec.o/p.
P
Laser class ........................................................:
LED Class 1
⎯
4.3.13.3
4.3.13.6
Other types ........................................................:
N
4.4
Protection against hazardous moving parts
N
4.4.1
General
N
4.4.2
Protection in operator access areas
N
4.4.3
Protection in restricted access locations
N
4.4.4
Protection in service access areas
N
4.5
Thermal requirements
P
4.5.1
Maximum temperatures
See appended table 4.5.1.
P
Normal load condition per Annex L ....................:
See 1.6.2.
P
4.5.2
Resistance to abnormal heat
Phenolic bobbin material is
used in transformer T1 and NF1
accepted without test. Others
see table 4.5.2
P
4.6
Openings in enclosures
4.6.1
Top and side openings
TRF No.:IECEN60950_1B
P
No openings within the whole
enclosure.
P
TRF originator: SGS Fimko
Page 20 of 70
<11003268 001>
IEC 60950-1 / EN 60950-1
Clause
Requirement – Test
Result – Remark
⎯
Dimensions (mm) ..............................................:
4.6.2
Bottoms of fire enclosures
Verdict
Ditto.
P
⎯
Construction of the bottom .................................:
4.6.3
Doors or covers in fire enclosures
No doors or covers.
N
4.6.4
Openings in transportable equipment
No openings within the whole
enclosure.
P
4.6.5
Adhesives for constructional purposes
N
Conditioning temperature (°C)/time (weeks) ......:
⎯
4.7
Resistance to fire
P
4.7.1
Reducing the risk of ignition and spread of flame
Use of materials with the
required flammability classes.
P
Method 1, selection and application of
components wiring and materials
(see appended table 4.7)
P
Method 2, application of all of simulated fault
condition tests
Not applied for.
N
4.7.2
Conditions for a fire enclosure
See below.
P
4.7.2.1
Parts requiring a fire enclosure
With having the following parts:
P
•
components in primary
•
components in secondary
(not supplied by LPS)
•
components having
unenclosed arcing parts at
hazardous voltage or
energy level
insulated wiring
the fire enclosure is required.
4.7.2.2
Parts not requiring a fire enclosure
4.7.3
Materials
4.7.3.1
General
PCB rated V-0
P
4.7.3.2
Materials for fire enclosures
Protective enclosure with no
decorative parts. Enclosure of
this unit with flammability class
V-1 or better.
P
4.7.3.3
Materials for components and other parts outside See sub-clause 4.7.2.
fire enclosures
N
4.7.3.4
Materials for components and other parts inside
fire enclosures
Internal components except
small parts are V-2 or better.
P
4.7.3.5
Materials for air filter assemblies
No air filter assemblies.
N
TRF No.:IECEN60950_1B
Ditto.
N
P
TRF originator: SGS Fimko
Page 21 of 70
<11003268 001>
IEC 60950-1 / EN 60950-1
Clause
Requirement – Test
Result – Remark
Verdict
4.7.3.6
Materials used in high-voltage components
No high voltage components.
N
5
ELECTRICAL REQUIREMENTS AND SIMULATED ABNORMAL CONDITIONS
P
5.1
Touch current and protective conductor current
P
5.1.1
General
See sub-clauses 5.1.2 to 5.1.6.
P
5.1.2
Equipment under test (EUT)
EUT has only one mains
connection.
P
5.1.3
Test circuit
Using test circuit as in figure
5A.
P
5.1.4
Application of measuring instrument
Using measuring instrument as
in Annex D.1.
P
5.1.5
Test procedure
The touch current was
measured from primary to
output connector and primary to
enclosure accessible parts
wrapped by metal foil.
P
5.1.6
Test measurements
See appended table 5.1.6.
P
Test voltage (V) .................................................:
⎯
Measured touch current (mA) ............................:
⎯
Max. allowed touch current (mA) .......................:
⎯
Measured protective conductor current (mA) ....:
⎯
Max. allowed protective conductor current (mA) :
⎯
5.1.7
Equipment with touch current exceeding 3.5 mA :
N
5.1.8
Touch currents to and from telecommunication
No TNV.
networks and cable distribution systems and from
telecommunication networks
N
5.1.8.1
Limitation of the touch current to a
telecommunication network and a cable
distribution system
N
No TNV.
Test voltage (V) .................................................:
⎯
Measured touch current (mA) ............................:
⎯
Max. allowed touch current (mA) .......................:
⎯
5.1.8.2
Summation of touch currents from
telecommunication networks ..............................:
5.2
Electric strength
5.2.1
General
(see appended table 5.2)
P
5.2.2
Test procedure
(see appended table 5.2)
P
TRF No.:IECEN60950_1B
No TNV.
N
P
TRF originator: SGS Fimko
Page 22 of 70
<11003268 001>
IEC 60950-1 / EN 60950-1
Clause
Requirement – Test
Result – Remark
Verdict
5.3
Abnormal operating and fault conditions
5.3.1
Protection against overload and abnormal
operation
Output overload test, the most
unfavorable load test (see
appended table 5.3).
P
5.3.2
Motors
No motors.
N
5.3.3
Transformers
With the shorted output of the
transformer, no high
temperature of the transformer
is to be observed or to be
expected (see appended
Annex C and table 5.3).
P
5.3.4
Functional insulation...........................................:
Short-circuit test, results see
appended table 5.3.
P
5.3.5
Electromechanical components
No electromechanical
component.
N
5.3.6
Simulation of faults
Results see appended table
5.3.
P
5.3.7
Unattended equipment
No thermostat, temperature
limiter or thermal cut-out.
N
5.3.8
Compliance criteria for abnormal operating and
fault conditions
No fire or molten metal accured.
P
P
Electric strength test primary to
secondary, primary to enclosure
and prim. to PE passed.
6
CONNECTION TO TELECOMMUNICATION NETWORKS
N
6.1
Protection of telecommunication network service persons, and users of other
equipment connected to the network, from hazards in the equipment
N
6.1.1
Protection from hazardous voltages
N
6.1.2
Separation of the telecommunication network from earth
N
6.1.2.1
Requirements
N
Test voltage (V) .................................................:
⎯
Current in the test circuit (mA) ..........................:
⎯
6.1.2.2
Exclusions ..........................................................:
N
6.2
Protection of equipment users from overvoltages on telecommunication networks
N
6.2.1
Separation requirements
N
6.2.2
Electric strength test procedure
N
6.2.2.1
Impulse test
N
6.2.2.2
Steady-state test
N
6.2.2.3
Compliance criteria
N
TRF No.:IECEN60950_1B
TRF originator: SGS Fimko
Page 23 of 70
<11003268 001>
IEC 60950-1 / EN 60950-1
Clause
Requirement – Test
6.3
Protection of the telecommunication wiring system from overheating
N
Max. output current (A).......................................:
⎯
Current limiting method ......................................:
⎯
7
CONNECTION TO CABLE DISTRIBUTION SYSTEMS
N
7.1
Protection of cable distribution system service
persons, and users of other equipment
connected to the system, from hazardous
voltages in the equipment
N
7.2
Protection of equipment users from overvoltages
on the cable distribution system
N
7.3
Insulation between primary circuits and cable
distribution systems
N
7.3.1
General
N
7.3.2
Voltage surge test
N
7.3.3
Impulse test
N
A
ANNEX A, TESTS FOR RESISTANCE TO HEAT AND FIRE
P
A.1
Flammability test for fire enclosures of movable equipment having a total mass
exceeding 18 kg, and of stationary equipment (see 4.7.3.2)
N
A.1.1
Samples..............................................................:
⎯
Wall thickness (mm) ...........................................:
⎯
A.1.2
Conditioning of samples; temperature (°C) ........:
N
A.1.3
Mounting of samples ..........................................:
N
A.1.4
Test flame (see IEC 60695-11-3)
N
Flame A, B, C or D ............................................:
⎯
A.1.5
Test procedure
N
A.1.6
Compliance criteria
N
Sample 1 burning time (s) ..................................:
⎯
Sample 2 burning time (s) ..................................:
⎯
Sample 3 burning time (s) ..................................:
⎯
A.2
Flammability test for fire enclosures of movable equipment having a total mass not
exceeding 18 kg, and for material and components located inside fire enclosures
(see 4.7.3.2 and 4.7.3.4)
P
A.2.1
Samples, material...............................................:
⎯
Wall thickness (mm) ...........................................:
⎯
Conditioning of samples
N
A.2.2
TRF No.:IECEN60950_1B
Result – Remark
Verdict
TRF originator: SGS Fimko
Page 24 of 70
<11003268 001>
IEC 60950-1 / EN 60950-1
Clause
Requirement – Test
A.2.3
Mounting of samples .........................................:
N
A.2.4
Test flame (see IEC 60695-11-4)
N
Flame A, B or C .................................................:
⎯
A.2.5
Test procedure
N
A.2.6
Compliance criteria
N
Sample 1 burning time (s) ..................................:
⎯
Sample 2 burning time (s) ..................................:
⎯
Sample 3 burning time (s) ..................................:
⎯
Alternative test acc. to IEC 60695-2-2, cl. 4 and 8
N
Sample 1 burning time (s) ..................................:
⎯
Sample 2 burning time (s) ..................................:
⎯
Sample 3 burning time (s) ..................................:
⎯
A.3
Hot flaming oil test (see 4.6.2)
N
A.3.1
Mounting of samples
N
A.3.2
Test procedure
N
A.3.3
Compliance criterion
N
B
ANNEX B, MOTOR TESTS UNDER ABNORMAL CONDITIONS (see 4.7.2.2 and
5.3.2)
N
B.1
General requirements
N
Position ..............................................................:
⎯
Manufacturer .....................................................:
⎯
Type ...................................................................:
⎯
Rated values .....................................................:
⎯
B.2
Test conditions
N
B.3
Maximum temperatures
N
B.4
Running overload test
N
B.5
Locked-rotor overload test
N
Test duration (days) ...........................................:
⎯
Electric strength test: test voltage (V) ................:
⎯
B.6
Running overload test for d.c. motors in
secondary circuits
N
B.7
Locked-rotor overload test for d.c. motors in secondary circuits
N
B.7.1
Test procedure
N
B.7.2
Alternative test procedure; test time (h) .............:
N
B.7.3
Electric strength test
N
A.2.7
TRF No.:IECEN60950_1B
Result – Remark
Verdict
TRF originator: SGS Fimko
Page 25 of 70
<11003268 001>
IEC 60950-1 / EN 60950-1
Clause
Requirement – Test
B.8
Test for motors with capacitors
N
B.9
Test for three-phase motors
N
B.10
Test for series motors
N
Operating voltage (V) ........................................:
⎯
ANNEX C, TRANSFORMERS (see 1.5.4 and 5.3.3)
P
Position ..............................................................:
T1
⎯
Manufacturer .....................................................:
See table 1.5.1.
⎯
Type ...................................................................:
See table 1.5.1.
⎯
Rated values .....................................................:
See table 1.5.1.
⎯
Method of protection...........................................:
Over current protection by
circuit design.
⎯
C.1
Overload test
(see appended table 5.3)
P
C.2
Insulation
(see appended table C.2)
P
Protection from displacement of windings..........:
Refer to appended table C.2.
P
C
Result – Remark
Verdict
D
ANNEX D, MEASURING INSTRUMENTS FOR TOUCH-CURRENT TESTS
(see 5.1.4)
P
D.1
Measuring instrument
P
D.2
Alternative measuring instrument
N
E
ANNEX E, TEMPERATURE RISE OF A WINDING (see 1.4.13)
N
F
ANNEX F, MEASUREMENT OF CLEARANCES AND CREEPAGE DISTANCES
(see 2.10)
P
G
ANNEX G, ALTERNATIVE METHOD FOR DETERMINING MINIMUM
CLEARANCES
N
G.1
Summary of the procedure for determining
minimum clearances
N
G.2
Determination of mains transient voltage (V) .....:
N
G.2.1
AC mains supply
N
G.2.2
DC mains supply
N
G.3
Determination of telecommunication network
transient voltage (V) ...........................................:
N
G.4
Determination of required withstand voltage (V) :
N
G.5
Measurement of transient levels (V)...................:
N
G.6
Determination of minimum clearances ...............:
N
TRF No.:IECEN60950_1B
TRF originator: SGS Fimko
Page 26 of 70
<11003268 001>
IEC 60950-1 / EN 60950-1
Clause
Requirement – Test
H
ANNEX H, IONIZING RADIATION (see 4.3.13)
N
J
ANNEX J, TABLE OF ELECTROCHEMICAL POTENTIALS (see 2.6.5.6)
N
Metal used .........................................................:
⎯
K
ANNEX K, THERMAL CONTROLS (see 1.5.3 and 5.3.7)
N
K.1
Making and breaking capacity
N
K.2
Thermostat reliability; operating voltage (V).......:
N
K.3
Thermostat endurance test; operating voltage
(V) .....................................................................:
N
K.4
Temperature limiter endurance; operating voltage
(V) ......................................................................:
N
K.5
Thermal cut-out reliability
N
K.6
Stability of operation
N
L
ANNEX L, NORMAL LOAD CONDITIONS FOR SOME TYPES OF ELECTRICAL
BUSINESS EQUIPMENT (see 1.2.2.1 and 4.5.1)
P
L.1
Typewriters
N
L.2
Adding machines and cash registers
N
L.3
Erasers
N
L.4
Pencil sharpeners
N
L.5
Duplicators and copy machines
N
L.6
Motor-operated files
N
L.7
Other business equipment
M
ANNEX M, CRITERIA FOR TELEPHONE RINGING SIGNALS (see 2.3.1)
N
M.1
Introduction
N
M.2
Method A
N
M.3
Method B
N
M.3.1
Ringing signal
N
M.3.1.1
Frequency (Hz) ..................................................:
⎯
M.3.1.2
Voltage (V) .........................................................:
⎯
M.3.1.3
Cadence; time (s), voltage (V) ...........................:
⎯
M.3.1.4
Single fault current (mA).....................................:
⎯
M.3.2
Tripping device and monitoring voltage .............:
N
TRF No.:IECEN60950_1B
Result – Remark
Continuous operation at rated
output load.
Verdict
P
TRF originator: SGS Fimko
Page 27 of 70
<11003268 001>
IEC 60950-1 / EN 60950-1
Clause
Requirement – Test
Result – Remark
M.3.2.1
Conditions for use of a tripping device or a
monitoring voltage
N
M.3.2.2
Tripping device
N
M.3.2.3
Monitoring voltage (V) ........................................:
N
N
ANNEX N, IMPULSE TEST GENERATORS (see 2.10.3.4, 6.2.2.1, 7.3.2 and
clause G.5)
N
N.1
ITU-T impulse test generators
N
N.2
IEC 60065 impulse test generator
N
P
ANNEX P, NORMATIVE REFERENCES
P
Q
ANNEX Q, BIBLIOGRAPHY
P
R
ANNEX R, EXAMPLES OF REQUIREMENTS FOR QUALITY CONTROL
PROGRAMMES
N
R.1
Minimum separation distances for unpopulated
coated printed boards (see 2.10.6)
N
R.2
Reduced clearances (see 2.10.3)
N
S
ANNEX S, PROCEDURE FOR IMPULSE TESTING (see 6.2.2.3)
N
S.1
Test equipment
N
S.2
Test procedure
N
S.3
Examples of waveforms during impulse testing
N
T
ANNEX T, GUIDANCE ON PROTECTION AGAINST INGRESS OF WATER
(see 1.1.2)
N
Not tested for IP code.
U
ANNEX U, INSULATED WINDING WIRES FOR USE WITHOUT INTERLEAVED
INSULATION (see 2.10.5.4)
Verdict
⎯
N
⎯
V
ANNEX V, AC POWER DISTRIBUTION SYSTEMS (see 1.6.1)
P
V.1
Introduction
P
V.2
TN power distribution systems
TRF No.:IECEN60950_1B
Single-phase TN power system
considered and used for
testing.
P
TRF originator: SGS Fimko
<11003268 001>
Page 28 of 70
IEC 60950-1 / EN 60950-1
Clause
Requirement – Test
Result – Remark
Verdict
V.3
TT power systems
Not considered.
N
V.4
IT power systems
Considered, however not
relevant for testing for this
equipment design.
P
W
ANNEX W, SUMMATION OF TOUCH CURRENTS
N
W.1
Touch current from electronic circuits
N
W.1.2
Earthed circuits
N
W.2
Interconnection of several equipments
N
W.2.1
Isolation
N
W.2.2
Common return, isolated from earth
N
W.2.3
Common return, connected to protective earth
N
X
ANNEX X, MAXIMUM HEATING EFFECT IN TRANSFORMER TESTS
(see clause C.1)
N
X.1
Determination of maximum input current
N
X.2
Overload test procedure
N
Y
ANNEX Y, ULTRAVIOLET LIGHT CONDITIONING TEST (see 4.3.13.3)
N
Y.1
Test apparatus ...................................................:
N
Y.2
Mounting of test samples ..................................:
N
Y.3
Carbon-arc light-exposure apparatus ................:
N
Y.4
Xenon-arc light exposure apparatus .................:
N
TRF No.:IECEN60950_1B
TRF originator: SGS Fimko
Page 29 of 70
<11003268 001>
IEC 60950-1 / EN 60950-1
Clause
Requirement – Test
Result – Remark
Verdict
CENELEC COMMON MODIFICATIONS [C],
SPECIAL NATIONAL CONDITIONS [S] AND A-DEVIATIONS (NATIONAL DEVIATIONS) [A]
(EN 60950-1:2001, Annex ZB and Annex ZC)
P
General
Deleted.
N
C: Delete all the "country" notes in the reference
document according to the following list:
1.1.5
Note 2
1.7.2
Note 4
2.2.3
Note
2.3.3
Note 1, 2
2.10.3.1 Note 4
3.2.5.1 Note 2
4.7.3.1 Note 2
6.2.2
Note
7
Note 4
G2.1
Note 1, 2
1.5.8
1.7.12
2.2.4
2.3.4
3.2.1.1
4.3.6
6.1.2.1
6.2.2.1
7.1
Annex H
Note 2
Note 2
Note
Note 2,3
Note
Note 1,2
Note
Note 2
Note
Note 2
1.6.1
2.6
2.3.2
2.7.1
3.2.3
4.7.2.2
6.1.2.2
6.2.2.2
Note
Note
Note 2, 7, 8
Note
Note 1, 2
Note
Note
Note
1.2.4.1
S (DK): Certain types of Class I appliances (see
3.2.1.1) may be provided with a plug not
establishing earthing conditions when inserted
into Danish socket-outlets.
No power cord provided
N
1.5.1
A (SE, Ordinance 1990:944 and
CH, Ordinance on environmentally hazardous
substances SR 814.013, Annex 3.2, Mercury):
Add NOTE – Switches containing mercury such as
No such switches used.
N
thermostats, relays and level controllers are not allowed.
1.5.8
S (NO): Due to the IT power system used (see
annex V, Fig. V.7), capacitors are required to be
rated for the applicable line-to-line voltage
(230 V).
Capacitor is rated suitably.
P
1.7.2
S (FI, NO, SE): CLASS I PLUGGABLE EQUIPMENT
TYPE A intended for connection to other
equipment or a network shall, if safety relies on
connection to protective earth or if surge
suppressors are connected between the network
terminals and accessible parts, have a marking
stating that the equipment must be connected to
an earthed mains socket-outlet.
Should be evaluated in final
systems
N
The marking text in the applicable countries shall
be as follows:
FI: "Laite on liitettävä suojamaadoituskoskettimilla varustettuun pistorasiaan"
N
NO: "Apparatet må tilkoples jordet stikkontakt"
N
SE: "Apparaten skall anslutas till jordat uttag"
N
A (DK, Heavy Current Regulations): Supply cords No power cord provided
of class I equipment, which is delivered without a
plug, must be provided with a visible tag with the
following text:
N
Vigtigt!
Lederen med grøn/gul isolation må kun tilsluttes
en klemme mærket
TRF No.:IECEN60950_1B
TRF originator: SGS Fimko
<11003268 001>
Page 30 of 70
IEC 60950-1 / EN 60950-1
Clause
Requirement – Test
Result – Remark
Verdict
eller
If essential for the safety of the equipment, the
tag must in addition be provided with a diagram
which shows the connection of the other
conductors, or be provided with the following text:
"For tilslutning af de øvrige ledere, se
medfølgende instalationsvejledning."
1.7.5
1.7.5
S (DK): Socket-outlets for providing power to
other equipment shall be in accordance with the
Heavy Current Regulations, Section 107-2-D1,
Standard Sheet DK 1-3a, DK 1-5a or DK 1-7a,
when used on Class I equipment. For stationary
equipment the socket-outlet shall be in accordance with Standard Sheet DK 1-1b or DK 1-5a.
No socket outlets.
N
A (DK, Heavy Current Regulations):
No socket outlets provided.
shall not be fitted with socketoutlets for providing power to other equipment.
P
A (DE, Gesetz über technische Arbeitsmittel
User's manual in German
(Gerätesicherheitsgesetz) [Law on technical
language provided.
labour equipment {Equipment safety law}], of 23rd
October 1992, Article 3, 3rd paragraph, 2nd
sentence, together with the "Allgemeine
Verwaltungsvorschrift zur Durchführung des
Zweiten Abschnitts des Gerätesicherheitsgesetzes" [General administrative regulation on
the execution of the Second Section of the
Equipment safety law], of 10th January 1996,
article 2, 4th paragraph item 2):
Directions for use with rules to prevent certain
hazards for (among others) maintenance of the
technical labour equipment, also for imported
technical labour equipment shall be written in the
German language.
P
CLASS II EQUIPMENT
1.7.12
NOTE: Of this requirement, rules for use even only by service
personnel are not exempted.
1.7.15
A (CH, Ordinance on environmentally hazardous
substances SR 814.013):
Annex 4.10 of SR 814.013 applies for batteries.
N
A (DE, Regulation on protection against hazards
by X-ray, of 8th January 1987, Article 5
[Operation of X-ray emission source], clauses 1
to 4):
a) A licence is required by those who operate an
X-ray emission source.
b) A licence in accordance with Cl. 1 is not
required by those who operate an X-ray emission
source on which the electron acceleration voltage
does not exceed 20 kV if
1) the local dose rate at a distance of 0,1 m from
the surface does not exceed 1 µSv/h and
N
TRF No.:IECEN60950_1B
TRF originator: SGS Fimko
<11003268 001>
Page 31 of 70
IEC 60950-1 / EN 60950-1
Clause
Requirement – Test
Result – Remark
Verdict
2) it is adequately indicated on the X-ray
emission source that
i) X-rays are generated and
ii) the electron acceleration voltage must not
exceed the maximum value stipulated by
the manufacturer or importer.
c) A licence in accordance with Cl. 1 is also not
required by persons who operate an X-ray
emission source on which the electron
acceleration voltage exceeds 20 kV if
1) the X-ray emission source has been granted a
type approval and
2) it is adequately indicated on the X-ray
emission source that
i) X-rays are generated
ii) the device stipulated by the manufacturer or
importer guarantees that the maximum
permissible local dose rate in accordance
with the type approval is not exceeded and
iii) the electron acceleration voltage must not
exceed the maximum value stipulated by
the manufacturer or importer.
d) Furthermore, a licence in accordance with
Cl. 1 is also not required by persons who operate
X-ray emission sources on which the electron
acceleration voltage does not exceed 30 kV if
1) the X-rays are generated only by intrinsically
safe CRTs complying with Enclosure III, No. 6,
2) the values stipulated in accordance with
Enclosure III, No. 6.2 are limited by technical
measures and specified in the device and
3) it is adequately indicated on the X-ray
emission source that the X-rays generated are
ade-quately screened by the intrinsically safe
CRT.
2.2.4
S (NO): Requirements according to this annex,
1.7.2 and 6.1.2.1 apply.
N
2.3.2
S (NO): Requirements according to this annex,
6.1.2.1 apply.
N
2.3.3 and
2.3.4
S (NO): Requirements according to this annex,
1.7.2 and 6.1.2.1 apply.
N
2.6.3.3
S (GB): The current rating of the circuit shall be
taken as 13 A, not 16 A.
N
2.7.1
C: Replace the subclause as follows:
Basic requirements
Considered, see the relevant
subclauses in the test report.
P
To protect against excessive current, shortcircuits and earth faults in PRIMARY CIRCUITS,
protective devices shall be included either as
TRF No.:IECEN60950_1B
TRF originator: SGS Fimko
<11003268 001>
Page 32 of 70
IEC 60950-1 / EN 60950-1
Clause
Requirement – Test
Result – Remark
Verdict
integral parts of the equipment or as parts of the
building installation, subject to the following, a),
b) and c):
a) except as detailed in b) and c), protective
devices necessary to comply with the
requirements of 5.3 shall be included as parts of
the equipment;
b) for components in series with the mains input
to the equipment such as the supply cord,
appliance coupler, r.f.i. filter and switch, shortcircuit and earth fault protection may be provided
by protective devices in the building installation;
c) it is permitted for PLUGGABLE EQUIPMENT TYPE B
or PERMANENTLY CONNECTED EQUIPMENT, to rely
on dedicated overcurrent and short-circuit
protection in the building installation, provided
that the means of protection, e.g. fuses or circuit
breakers, is fully specified in the installation
instructions.
If reliance is placed on protection in the building
installation, the installation instructions shall so
state, except that for PLUGGABLE EQUIPMENT TYPE
A the building installation shall be regarded as
providing protection in accordance with the rating
of the wall socket outlet.
S (GB): To protect against excessive currents
and short-circuits in the PRIMARY CIRCUIT OF
DIRECT PLUG-IN EQUIPMENT, protective device shall
be included as integral parts of the DIRECT PLUGIN EQUIPMENT.
N
2.7.2
C: Void.
N
2.10.2
C: Replace in the first line "(see also 1.4.7)" by
"(see also 1.4.8)".
Replaced.
P
2.10.3.1
S (NO): Due to the IT power distribution system
used (see annex V, Fig. V.7), the A.C. MAINS
SUPPLY voltage is considered to be equal to the
line-to-line voltage and will remain at 230 V in
case of a single earth fault
Considered.
P
TRF No.:IECEN60950_1B
TRF originator: SGS Fimko
<11003268 001>
Page 33 of 70
IEC 60950-1 / EN 60950-1
Clause
Requirement – Test
Result – Remark
3.2.1.1
S (CH): Supply cords of equipment having a
not exceeding 10 A shall be
provided with a plug complying with SEV 1011 or
IEC 60884-1 and one of the following dimension
sheets:
Verdict
N
RATED CURRENT
SEV 6532-2.1991, Plug type 15, 3P+N+PE 250/400 V, 10 A
SEV 6533-2.1991, Plug type 11, L+N
250 V, 10 A
SEV 6534-2.1991, Plug type 12, L+N+PE
250 V, 10 A
In general, EN 60309 applies for plugs for
currents exceeding 10 A. However, a 16 A plug
and socket-outlet system is being introduced in
Switzerland, the plugs of which are according to
the following dimension sheets, published in
February 1998:
SEV 5932-2.1998, Plug type 25, 3L+N+PE
SEV 5933-2.1998, Plug type 21, L+N
SEV 5934-2.1998, Plug type 23, L+N+PE
230/400 V, 16 A
250 V, 16 A
250 V, 16 A
S (DK): Supply cords of single-phase equipment
having a rated current not exceeding 13 A shall
be provided with a plug according to the Heavy
Current Regulations, Section 107-2-D1.
N
CLASS I EQUIPMENT provided with socket-outlets
with earth contacts or which are intended to be
used in locations where protection against
indirect contact is required according to the
wiring rules shall be provided with a plug in
accordance with standard sheet DK 2-1a or
DK 2-5a.
If ply-phase equipment and single-phase
equipment having a RATED CURRENT exceeding
13 A is provided with a supply cord with a plug,
this plug shall be in accordance with the Heavy
Current Regulations, Section 107-2-D1 or
EN 60309-2.
S (ES): Supply cords of single-phase equipment
having a rated current not exceeding 10 A shall
be provided with a plug according to
UNE 20315:1994.
N
Supply cords of single-phase equipment having a
rated current not exceeding 2,5 A shall be
provided with a plug according to
UNE-EN 50075:1993.
CLASS I EQUIPMENT provided with socket-outlets
with earth contacts or which are intended to be
used in locations where protection against
indirect contact is required according to the
wiring rules, shall be provided with a plug in
accordance with standard UNE 20315:1994.
If poly-phase equipment is provided with a supply
cord with a plug, this plug shall be in accordance
with UNE-EN 60309-2.
TRF No.:IECEN60950_1B
TRF originator: SGS Fimko
<11003268 001>
Page 34 of 70
IEC 60950-1 / EN 60950-1
Clause
Requirement – Test
Result – Remark
S (GB): Apparatus which is fitted with a flexible
cable or cord and is designed to be connected to
a mains socket conforming to BS 1363 by means
of that flexible cable or cord and plug, shall be
fitted with a 'standard plug' in accordance with
Statutory Instrument 1768:1994 – The Plugs and
Socket etc. (Safety) Regulations 1994, unless
exempted by those regulations.
Verdict
N
NOTE – 'Standard plug' is defined in SI 1768:1994 and
essentially means an approved plug conforming to BS 1363
or an approved conversion plug.
S (IE): Apparatus which is fitted with a flexible
cable or cord and is designed to be connected to
a mains socket conforming to I.S. 411 by means
of that flexible cable or cord and plug, shall be
fitted with a 13 A plug in accordance with
Statutory Instrument 525:1997 – National
Standards Authority of Ireland (section 28) (13 A
Plugs and Conversion Adaptors for Domestic
Use) Regulations 1997.
N
3.2.3
C: Delete Note 1 and in Table 3A, delete the
conduit sizes in parentheses.
Deleted.
N
3.2.5.1
C: Replace
Replaced.
N
"60245 IEC 53" by "H05 RR-F";
"60227 IEC 52" by "H03 VV-F or H03 VVH2-F";
"60227 IEC 53" by "H05 VV-F or H05 VVH2-F2".
In Table 3B, replace the first four lines by the
following:
Up to and including 6
Over 6 up to and including 10 (0,75)2)
Over 10 up to and including 16 (1,0)3)
0,751)
1,0
1,5
In the Conditions applicable to Table 3B delete
the words "in some countries" in condition 1).
In Note 1, applicable to Table 3B, delete the
second sentence.
3.2.5.1
S (GB): A power supply cord with conductor of
1,25 mm2 is allowed for equipment with a rated
current over 10 A and up to and including 13 A.
3.3.4
C: In table 3D, delete the fourth line: conductor
sizes for 10 to 13 A, and replace with the
following:
"Over 10 up to and including 16
1,5 to 2,5
N
Deleted.
N
1,5 to 4"
Delete the fifth line: conductor sizes for 13 to
16 A.
TRF No.:IECEN60950_1B
TRF originator: SGS Fimko
<11003268 001>
Page 35 of 70
IEC 60950-1 / EN 60950-1
Clause
Requirement – Test
Result – Remark
3.3.4
S (GB): The range of conductor sizes of flexible
cords to be accepted by terminals for equipment
with a RATED CURRENT of over 10 A up to and
including 13 A is:
- 1,25 mm2 to 1,5 mm2 nominal cross-sectional
area.
No power cord provided.
4.3.6
S (GB): The torque test is performed using a
socket outlet complying with BS 1363 and the
plug part of DIRECT PLUG-IN EQUIPMENT shall be
assessed to BS 1363: Part 1, 12.1, 12.2, 12.3,
12.9, 12.11, 12.12, 12.16 and 12.17, except that
the test of 12.17 is performed at not less than
125 °C.
N
S (IE): DIRECT PLUG-IN EQUIPMENT is known as
plug similar devices. Such devices shall comply
with Statutory Instrument 526:1997 – National
Standards Authority of Ireland (Section 28)
(Electrical plugs, plug similar devices and
sockets for domestic use) Regulations, 1997.
N
4.3.13.6
C: Add the following note:
Added.
Verdict
N
N
NOTE Attention is drawn to 1999/519/EC: Council
Recommendation on the limitation of exposure of the general
public to electromagnetic fields 0 Hz to 300 GHz. Standards
taking into account this recommendation are currently under
development.
6.1.2.1
S (FI, NO, SE): Add the following text between
the first and second paragraph:
N
If this insulation is solid, including insulation
forming part of a component, it shall at least
consist of either
- two layers of thin sheet material, each of which
shall pass the electric strength test below, or
- one layer having a distance through insulation
of at least 0,4 mm, which shall pass the electric
strength test below.
If this insulation forms part of a semiconductor
component (e.g. an optocoupler), there is no
distance through insulation requirement for the
insulation consisting of an insulating compound
completely filling the casing, so that CLEARANCES
AND CREEPAGE DISTANCES do not exist, if the
component passes the electric strength test in
accordance with the compliance clause below
and in addition
- passes the tests and inspection criteria of
2.10.8 with an electric strength test of 1,5 kV
multiplied by 1,6 (the electric strength test of
2.10.7 shall be performed using 1,5 kV), and
- is subject to ROUTINGE TESTING for electric
strength during manufacturing, using a test
TRF No.:IECEN60950_1B
TRF originator: SGS Fimko
Page 36 of 70
<11003268 001>
IEC 60950-1 / EN 60950-1
Clause
Requirement – Test
Result – Remark
Verdict
voltage of 1,5 kV.
It is permitted to bridge this insulation with a
capacitor complying with EN 132400:1994,
subclass Y2.
A capacitor classified Y3 according to
EN 132400:1994, may bridge this insulation
under the following conditions:
- the insulation requirements are satisfied by
having a capacitor classified Y3 as defined by
EN 132400, which in addition to the Y3 testing, is
tested with an impulse test of 2,5 kV defined in
EN 60950:2000, 6.2.2.1;
- the additional testing shall be performed on all
the test specimens as described in EN 132400;
- the impulse test of 2,5 kV is to be performed
before the endurance test in EN 132400, in the
sequence of tests as described in EN 132400.
6.1.2.2
S (FI, NO, SE): The exclusions are applicable for
No TNV circuits provided.
N
PERMANENTLY CONNECTED EQUIPMENT and
PLUGGABLE EQUIPMENT TYPE B and equipment
intended to be used in a RESTRICTED ACCESS
LOCATION where equipotential bonding has been
applied, e.g. in a telecommunication centre, and
which has provision for a permanently connected
PROTECTIVE EARTHING CONDUCTOR and is provided
with instructions for the installation of that
conductor by a service person.
7.1
S (FI, NO, SE): Requirements according to this
annex, 6.1.2.1 and 6.1.2.2 apply with the term
TELECOMMUNICATION NETWORK in 6.1.2 being
replaced by the term CABLE DISTRIBUTION SYSTEM.
N
G.2.1
S (NO): Due to the IT power distribution system
used (see annex V, Fig. V.7), the A.C. MAINS
SUPPLY voltage is considered to be equal to the
line-to-line voltage, and will remain at 230 V in
case of a single earth fault.
N
Annex H
C: Replace the last paragraph of this annex by:
N
At any point 10 cm from the surface of the
operator access area, the dose rate shall not
exceed 1 µSv/h (0,1 mR/h) (see note). Account is
taken of the background level.
Replace the notes as follows:
NOTE These values appear in Directive 96/29/Euratom.
Delete Note 2.
Annex P
C: Replace the text of this annex by:
Replaced.
P
See annex ZA.
Annex Q
C: Replace the title of IEC 61032 by "Protection of persons and equipment by
TRF No.:IECEN60950_1B
P
TRF originator: SGS Fimko
<11003268 001>
Page 37 of 70
IEC 60950-1 / EN 60950-1
Clause
Requirement – Test
Result – Remark
Verdict
enclosures – Probes for verification".
Add the following notes for the standards indicated:
IEC 60127
NOTE Harmonized as EN 60127 (Series) (not modified)
IEC 60269-2-1 NOTE Harmonized as HD 630.2.1 S4:2000 (modified)
IEC 60529
NOTE Harmonized as EN 60529:1991 (not modified)
IEC 61032
NOTE Harmonized as EN 61032:1998 (not modified)
IEC 61140
NOTE Harmonized as EN 61140:2001 (not modified)
ITU-T Recommendation K.31
NOTE in Europe, the suggested document is EN 50083-1.
TRF No.:IECEN60950_1B
TRF originator: SGS Fimko
<11003268 001>
Page 38 of 70
IEC 60950-1 / EN 60950-1
Clause
Requirement – Test
Result – Remark
Annex ZA
C: NORMATIVE REFERENCES TO INTERNATIONAL PUBLICATIONS WITH
THEIR RELEVANT EUROPEAN PUBLICATIONS
Verdict
P
This European Standard incorporates, by dated or undated reference, provisions
from other publications. These normative references are cited at the appropriate
places in the text and the publications are listed hereafter. For dated references,
subsequent amendments to or revisions of any of these publications apply to this
European Standard only when incorporated in it by amendment or revision. For
undated references, the latest edition of the publication referred to applies
(including amendments).
NOTE When an international publication has been modified by common modifications, indicated by
(mod), the relevant EN/HD applies.
⎯
⎯
EN 60065:1998 + corr. June 1999
EN 60073:1996
HD 566 S1:1990
HD 214 S2:1980
HD 611.4.1.S1:1992
HD 21 1) Series
HD 22 2) Series
EN 60309 Series
EN 60317-43:1997
EN 60320 Series
HD 384.3 S2:1995
HD 384.4.41 S2:1996
EN 132400:1994 4)
+ A2:1998 + A3:1998 + A4:2001
EN 60417-1
HD 625.1 S1:1996 + corr. Nov. 1996
EN 60695-2-2:1994
EN 60695-2-11:2001
⎯
⎯
⎯
⎯
EN 60695-11-10:1999
EN 60695-11-20:1999
EN 60730-1:2000
EN 60825-1:1994 + corr. Febr. 1995 +
A11:1996 + corr. July 1997
EN 60825-2:2000
⎯
EN 60851-3:1996
EN 60851-5:1996
EN 60851-6:1996
⎯
EN 60990:1999
⎯
EN 61965:2001
EN ISO 178:1996
EN ISO 179 Series
EN ISO 180:2000
⎯
TRF No.:IECEN60950_1B
IEC 60050-151
IEC 60050-195
IEC 60065 (mod):1998
IEC 60073:1996
IEC 60085:1984
IEC 60112:1979
IEC 60216-4-1:1990
IEC 60227 (mod) Series
IEC 60245 (mod) Series
IEC 60309 Series
IEC 60317-43:1997
IEC 60320 (mod) Series
IEC 60364-3 (mod):1993
IEC 60364-4-41 (mod):1992 3)
IEC 60384-14:1993
IEC 60417-1
IEC 60664-1 (mod):1992
IEC 60695-2-2:1991
IEC 60695-2-11:2000
IEC 60695-2-20:1995
IEC 60695-10-2:1995
IEC 60695-11-3:2000
IEC 60695-11-4:2000
IEC 60695-11-10:1999
IEC 60695-11-20:1999
IEC 60730-1:1999 (mod)
IEC 60825-1:1993
IEC 60825-2:2000
IEC 60825-9:1999
IEC 60851-3:1996
IEC 60825-5:1996
IEC 60851-6:1996
IEC 60885-1:1987
IEC 60990:1999
IEC 61058-1:2000
IEC 61965:2000
ISO 178:1993
ISO 179 Series
ISO 180:1993
ISO 261:1998
TRF originator: SGS Fimko
<11003268 001>
Page 39 of 70
IEC 60950-1 / EN 60950-1
Clause
Requirement – Test
⎯
EN ISO 527 Series
⎯
EN ISO 4892 Series
⎯
EN ISO 8256:1996
⎯
EN ISO 9773:1998
⎯
⎯
Result – Remark
Verdict
ISO 262:1998
ISO 527 Series
ISO 386:1984
ISO 4892 Series
ISO 7000:1989
ISO 8256:1990
ISO 9772:1994
ISO 9773:1998
ITU-T:1988 Recommendation K.17
ITU-T:2000 Recommendation K.21
1) The HD 21 series is related to, but not directly equivalent with the IEC 60227 series
2) The HD 22 series is related to, but not directly equivalent with the IEC 60245 series
3) IEC 60364-4-41:1992 is superseded by IEC 60364-4-41:2001
4) EN 132400, Sectional Specification: Fixed capacitors for electromagnetic interference suppression
and connection to the supply mains (Assessment level D), and its amendments are related to, but not
directly equivalent to IEC 60384-14
TRF No.:IECEN60950_1B
TRF originator: SGS Fimko
Page 40 of 70
<11003268 001>
1.5.1
TABLE: list of critical components
P
Object/part no.
Manufacturer/
trademark
Type/model
Technical data
Standard
Mark(s) of
conformity 1.
AC Inlet
Surpercom
SC-8R
10A, 250V
IEC 60320-1,
UL498,
CSA C22.2 NO.
182.3
UL, SEMKO,
VDE
Inalways
0711
10A, 250V
IEC 60320-1,
UL498,
CSA C22.2 NO.
182.3
UL, SEMKO,
VDE
SOLTEAM
ST-01
10A, 250V
IEC 60320-1,
UL498,
CSA C22.2 NO.
182.3
UL, SEMKO,
VDE
Bel
RRT
T 2A, 250Vac
IEC 60127-3
VDE, UL, CSA
Conquer
MST
T 2A, 250Vac
IEC 60127-3
VDE, UL, CSA
NSF
SST
T 2A, 250Vac
IEC 60127-3
VDE, UL, CSA
Wickmann
392
T 2A, 250Vac
IEC 60127-3
VDE, UL, CSA,
Ever Island
2010
T 2A, 250Vac
IEC 60127-3
VDE, UL, CSA,
Success
SE, SB
Max. 100pF,
min. 250Vac,
125°C
IEC 6038414/1993
VDE, SEMKO,
SEV, UL
Murata
KX
Max. 100pF,
min. 250Vac,
125°C
IEC 6038414/1993
VDE, SEMKO,
SEV, UL
TDK
CD
Max. 100pF,
min. 250Vac,
125°C
IEC 6038414/1993
VDE, SEMKO,
SEV, UL
Matsushita
NS-A
Max. 100pF,
min. 250Vac,
125°C
IEC 6038414/1993
VDE, SEMKO,
SEV, UL
Pan Overseas
AH, AC
Max. 100pF,
min. 250Vac,
125°C
IEC 6038414/1993
VDE, SEMKO,
SEV, UL
Vishay
VKP
Max. 100pF,
min. 250Vac,
125°C
IEC 6038414/1993
VDE, SEMKO,
SEV, UL
Marcon
TNR9G471K
300Vac,
CECC 42200
VDE, UL
385 Vdc.
CECC 42201
300Vac,
CECC 42200
385 Vdc.
CECC 42201
300Vac,
CECC 42200
385 Vdc.
CECC 42201
Fuse (F1)
Y Capacitor
(C52, C53), Y1
type
Varistor (ZNR1)
(Optional)
Centra Science
Song Long
TRF No.:IECEN60950_1B
CNR10D471K
MOV471KD10
VDE, UL
VDE, UL
TRF originator: SGS Fimko
Page 41 of 70
<11003268 001>
Wujin Thinking
Uppermost
TVR10471K
V10K420
Electronic
X-Cap (C3)
300Vac,
CECC 42200
385 Vdc.
CECC 42201
300Vac, 385
Vdc.
CECC 42200
VDE, UL
VDE, UL
CECC 42201
Roederstein
F1772
0.1µF max.,
85°C, 250Vac
min.
IEC 6038414/1993
VDE, SEMKO,
UL, CSA
Okaya
RE, PA
0.1µF max.,
85°C, 250Vac
min.
IEC 6038414/1993
VDE, SEMKO,
UL, CSA
Arcotronics
R.46
0.1µF max.,
85°C, 250Vac
min.
IEC 6038414/1993
VDE, FIMKO,
UL, CSA
Hua Jung
MKP
0.1µF max.,
85°C, 250Vac
min.
IEC 6038414/1993
VDE, FIMKO,
UL, CSA
Evox Rifa
PHE 840M
Various
IEC 6038414/1993
VDE, FIMKO,
UL, CSA
Pilkor
PCX2 335,
PCX2 335M,
PCX2 337
Various
IEC 6038414/1993
VDE, SEMKO,
SEV, UL
Bleeder
Resistor (R1,
R1A)
Various
Various
510 kΩ, 1/4W
---
---
Noise Filter
(NF1)
Phihong
23301N20301
Class 120°C
---
---
Bridge Diode
(D1, D2, D3,
D4)
Various
Various
1 A, 600 V
---
---
Storage
Capacitor (C4)
Various
Various
68 µF, 400 V,
105°C.
---
---
Transformer
(T1)
Phihong
26420170001
Class E
according to
IEC 60950-1
and applicable
parts of IEC
60085
accepted by
TÜV Rheinland
Insulation Tape
3M
1350F, 1318,
V-0, 130°C min.
56, 1350, 1350T CTI >400 min.
UL 94
UL
Photo coupler
(PC1)
Sharp
PC817, PC814
Di = 0.5 mm,
VDE 0884 IEC TUV, UL
Int. di = 4.4 mm, 60950
FIMKO
Ext. di = 7.7 mm
Liteon
LTV817
Di = 0.8 mm,
VDE 0884
Int. di = 5.2 mm, IEC 60950
Ext. di = 7.8 mm
TRF No.:IECEN60950_1B
VDE, UL
FIMKO
TRF originator: SGS Fimko
Page 42 of 70
<11003268 001>
Cosmo
K1010
VDE 0884
Di = 1.0 mm,
Int. di = 5.3 mm, IEC 60950
Ext. di = 8.0 mm
VDE, UL
FIMKO
NEC
PS2561
Di = 0.5 mm,
VDE 0884
Int. di > 4.0 mm, IEC 60950
Ext. di > 7.0 mm
VDE, UL
FIMKO
Fairchild
H11A817
Di = 0.4 mm,
VDE 0884
Int. di = Thermal IEC 60950
cycling test
Ext. di > 7.0 mm
VDE, UL
FIMKO
Success
SE, SB
Max. 2200pF,
min. 250Vac,
125°C
IEC 6038414/1993
VDE, SEMKO,
SEV, UL
Murata
KX
Max. 2200pF,
min. 250Vac,
125°C
IEC 6038414/1993
VDE, SEMKO,
SEV, UL
TDK
CD
Max. 2200pF,
min. 250Vac,
125°C
IEC 6038414/1993
VDE, SEMKO,
SEV, UL
Matsushita
NS-A
Max. 2200pF,
min. 250Vac,
125°C
IEC 6038414/1993
VDE, SEMKO,
SEV, UL
Pan Overseas
AH, AC
Max. 2200pF,
min. 250Vac,
125°C
IEC 6038414/1993
VDE, SEMKO,
SEV, UL
Vishay
VKP
Max. 2200pF,
min. 250Vac,
125°C
IEC 6038414/1993
VDE, SEMKO,
SEV, UL
Zener Diode
(ZD3, ZD3A)
Various
Various
51V / 1W
---
---
Zener Diode
( ZD5 )
Various
Various
18.63V - 19.59V --/ 0.5W
---
PCB Material
Various
Various
V-0. 105°C min. UL 94
UL
Enclosure
GE Plastics
940
V-0, thick
1.5mm min,
120°C min.
UL 94
UL
GE Plastics
SE1
V-1, thick
1.5mm min,
105°C min.
UL 94
UL
Mitsubishi
AV60+
V-1, thick
1.5mm min,
105°C min.
UL 94
UL
Asahi Kasei
500V, 540V,
540Z
V-1, thick
1.5mm min,
105°C min.
UL 94
UL
Bridge
Capacitor
(C37), Y1 type
TRF No.:IECEN60950_1B
TRF originator: SGS Fimko
Page 43 of 70
<11003268 001>
--EMI shielding
broad (PCB)
contact between
C52, C53 and
Secondary
---
V-0. 105°C min. UL 94
117x 34 x 1 mm
UL
Note(s):
1. An asterisk indicates a mark that assures the agreed level of surveillance.
1.6.2
TABLE: electrical data (in normal conditions)
Fuse #
Irated (A)
U (V)
F1
---
90V
P
P (W)
I (A)
Ifuse (A)
Condition/status
22.9
0.39
0.39
50Hz Maximum normal load
according to manufacturer
recommend.
F1
---
90V
22.9
0.39
0.39
60Hz
F1
0.4
100V
22.5
0.35
0.35
50Hz
F1
0.4
100V
22.5
0.35
0.35
60Hz
F1
0.4
240V
21.9
0.18
0.18
50Hz
F1
0.4
240V
21.9
0.18
0.18
60Hz
F1
---
264V
22.0
0.17
0.17
50Hz
F1
---
264V
22.0
0.17
0.17
60Hz
Note(s):
2.1.1.5
TABLE: max. V, A, VA test
P
Voltage (rated)
(V)
Current (rated)
(A)
Voltage (max.)
(V)
Current (max.)
(A)
48 Vdc
0.32
48.64
0.33
VA (max.)
(VA)
47.89 x 0.33=15.8
Note(s): Test voltage: 240 V at 60 Hz.
2.1.1.7
Condition
TABLE: discharge test
N
τ calculated τ measured
(s)
(s)
t u→ 0V
(s)
Comments
Note(s): Overall capacity: C1= 0.1µF
2.2.2
TABLE: Hazardous voltage measurement
TRF No.:IECEN60950_1B
P
TRF originator: SGS Fimko
Page 44 of 70
<11003268 001>
Transformer
Location
T1
max. Voltage
Pin 6.7 to Pin 8
T1
Pin 9 to Pin 10
Voltage Limitation
Component
V peak
V d.c.
304
--
--
--
49.5
D7
107
--
--
--
20
D9
Note(s): Test voltage: 240 V at 60 Hz.
2.2.3
TABLE: SEL voltage measurement
Location
P
Voltage measured (V)
Comments
D7 (n) to RTN
0
D7 short
D9 (n) to DG
0
D9 short
Note(s): Test voltage: 240 V at 60 Hz.
2.4.2
TABLE: limited current circuit measurement
Location
Y-Capacitor (C37)
secondary pin to earth
P
Voltage
(V)
Current
(mA)
Freq.
(kHz)
Limit
(mA)
0.6
0.3
0.06
0.7
Comments
Normal
Note(s): Unit was supplied with 240 V ac, 60Hz.
C37 = 2200pF, C52=C53 = 100pF=200pF (Y1 type)
2.5
TABLE: limited power source measurement
P
Limits
Measured
Verdict
According to Table 2B (normal condition)
UOc=48.64V
8A
0.33
P
(5 x 48.64) = 243.2
47.89 x 0.33 = 15.8
P
8A
0
P
(5 x 48.64) = 243.2
0
P
0
P
current (in A)
apparent power (in VA)
According to Table 2B (single fault condition) PC1 pin1 open
current (in A)
apparent power (in VA)
According to Table 2B (single fault condition) PC1 pin(1-2) shorted
current (in A)
TRF No.:IECEN60950_1B
8A
TRF originator: SGS Fimko
Page 45 of 70
<11003268 001>
(5 x 48.64) = 243.2
apparent power (in VA)
0
P
8A
0
P
(5 x 48.64) = 243.2
0
P
8A
0.33
P
(5 x 48.64) = 243.2
47.80 x 0.32 = 15.3
P
8A
0.33
P
(5 x 48.64) = 243.2
47.72 x 0.32 = 15.3
P
According to Table 2B (single fault condition) PC1 pin3 open
current (in A)
apparent power (in VA)
According to Table 2B (single fault condition) R13 shorted
current (in A)
apparent power (in VA)
According to Table 2B (single fault condition) R19 shorted
current (in A)
apparent power (in VA)
Note(s): Test voltage: 240 V at 60 Hz.
2.6.3.3
TABLE: ground continue test
Location
P
Resistance measured (mΩ) Comments
Inlet PE to PCB bonding
2
25A / 1 minute
Inlet PE to PCB bonding
2
40A / 2 minute
Note(s):
2.10.2
Table: working voltage measurement
Location
RMS voltage (V)
P
Peak voltage (V) Comments
T1 pin 1 – pin 6. 7
221
320
T1 pin 1 – pin 8.
234
500
T1 pin 1 – pin 9
220
400
T1 pin 1 – pin 10
220
330
T1 pin 3 – pin 6. 7
261
455
T1 pin 3 – pin 8.
228
400
T1 pin 3 – pin 9
251
440
T1 pin 3 – pin 10
261
450
T1 pin 4 – pin 6. 7
190
370
T1 pin 4 – pin 8.
207
425
T1 pin 4 – pin 9
195
385
T1 pin 4 – pin 10
190
370
T1 pin 5 – pin 6. 7
192
430
T1 pin 5 – pin 8.
201
410
T1 pin 5 – pin 9
191
375
TRF No.:IECEN60950_1B
*MAX. CL=4.4 mm
*MAX. CR=5.4 mm
TRF originator: SGS Fimko
Page 46 of 70
<11003268 001>
T1 pin 5 – pin 10
192
452
PC1 pin 1 – pin 3
205
390
PC1 pin 1 – pin 4
206
395
PC1 pin 2 – pin 3
207
395
PC1 pin 2 – pin 4
208
400
C37 Pri. – Sec.
190
370
C29 – C4( – )
191
375
Note(s): Test voltage: 240 V at 60 Hz.
2.10.3 and TABLE: clearance and creepage distance measurements
2.10.4
P
Clearance cl and creepage
distance dcr at/of:
Up
(V)
U r.m.s.
(V)
Required
cl (mm)
cl
(mm)
Required
dcr (mm)
dcr
(mm)
primary components to
outside enclosure
420
250
4.0
5.0
5.0
5.0
primary components to
secondary components (10N)
(U20 – C4)
420
250
4.0
7.0
5.0
7.0
primary traces to secondary
traces (under T1)
500
261
4.4
9.3
5.4
9.3
primary traces to secondary
traces (under PC1)
420
250
4.0
6.0
5.0
6.0
primary traces to secondary
traces (C37) (with 1x6mm cut)
420
250
4.0
4.6
5.0
6.5
Traces under fuse
420
250
1.8
2.7
2.5
2.7
Note(s):
1. Functional insulation according to subclause 5.3.4 a).
2. Tubed components: R7, R20, C41, C1
3. Glued components: R19, C4
2.10.5
TABLE: distance through insulation measurements
Distance through insulation di at/of:
P
U r.m.s.
(V)
Test voltage
(V)
Required di
(mm)
di
(mm)
Optocoupler (reinforced insulation)
250
3000
0.4
0.41)
Enclosure material (reinforced insulation)
250
3000
0.4
1.8
Note(s):
4.5.1
TABLE: maximum temperatures
P
test voltage (V) ............................................: 100V-10%/240V+10%
⎯
TRF No.:IECEN60950_1B
TRF originator: SGS Fimko
<11003268 001>
Page 47 of 70
t1 (°C) ..........................................................: --
⎯
t2 (°C) ..........................................................: --
⎯
Maximum temperature T of part/at:
T (°C)
allowed Tmax (°C)
test voltage (V) label up
90
264
--
1. Ambient
40
40
--
2. T1 coil
82
79
105
3. T1 core
81
79
105
4. CN1 (inlet pin)
68
64
70
5. C52 body
67
61
125
6. C53 body
57
49
125
7. C3 body
66
64
85
8. F1 body
66
61
105
9. NF1 Coil
75
56
120
10. Heat sink for Q8
68
64
105
11. C4 body
65
57
105
12. C41 body
69
67
85
13. PC1 body
77
75
100
14. C37 body
77
72
125
15. PCB near U20
64
62
105
16. C35 body
79
79
85
17. CN3 body
54
54
70
18. CN4 body
53
53
70
19. Top case inside above T1
53
52
95
20. Bottom case Outside under T1
45
45
95
test voltage (V) vertical
90
264
--
1. Ambient
40
40
--
2. T1 coil
87
85
105
3. T1 core
86
85
105
4. CN1 (inlet pin)
62
57
70
5. C52 body
72
67
125
6. C53 body
71
58
125
7. C3 body
72
70
85
8. F1 body
73
68
105
9. NF1 Coil
84
66
120
10. Heat sink for Q8
79
76
105
11. C4 body
74
65
105
TRF No.:IECEN60950_1B
TRF originator: SGS Fimko
Page 48 of 70
<11003268 001>
12. C41 body
72
70
85
13. PC1 body
79
78
100
14. C37 body
84
80
125
15. PCB near U20
70
68
105
16. C35 body
79
80
85
17. CN3 body
52
52
70
18. CN4 body
50
50
70
19. Top case inside above T1
60
60
95
20. Bottom case Outside under T1
49
50
95
Temperature T of winding:
R1
(Ω)
R2
(Ω)
T
(°C)
allowed
Tmax (°C)
insulation
class
Note(s):
1. The temperatures were measured under worst case normal mode defined in 1.2.2.1 and as described in
1.6.2 at voltages as above.
2. With a specified maximum ambient temperature and test temperature of 40 °C, the maximum permitted
temperatures are calculated as follows:
Winding components (providing safety isolation):
•
Class E
•
For temperature ratings of other relevant components refer to appended table 1.5.1.
4.5.2
→ Tmax = 115°C - 10°C = 105°C
TABLE: ball pressure test of thermoplastic parts
P
allowed impression diameter (mm) .................. : ≤ 2 mm
⎯
Part
Bobbin material of T1 (Dupont, type: FR530, FR530L)
Test temperature
(°C)
Impression diameter
(mm)
125
0.2
Note(s): Phenolic materials accepted without test for test temperatures not exceeding 125 °C.
4.6.1, 4.6.2 Table: enclosure openings
Location
P
Size (mm)
Comments
Note(s): No any openings
TRF No.:IECEN60950_1B
TRF originator: SGS Fimko
Page 49 of 70
<11003268 001>
4.7
Table: resistance to fire
Part
P
Manufacturer of material
Type of material
Thickness
(mm)
Flammability
class
See table 1.5.1
See table 1.5.1
1.5
V-0
Enclosure
Note(s):
5.1.6
TABLE: touch current measurement
P
Condition
L→ terminal A
(mA)
N → terminal
A
(mA)
Limit
(mA)
Power on
0. 1
0.1
3.5
Power on
0.01
0.01
3.5
Comments
From AC mains to o/p DC connector
(conductive part).
From AC mains to plastic material that
wrapped with metal foil.
Note(s): Test voltage: 240 V at 60 Hz. C37=2200pF
5.2
TABLE: electric strength tests and impulse tests
Test voltage applied between:
P
Test voltage (V)
Breakdown
Unit: primary circuit to secondary circuit
DC 4242
No
Unit: primary circuit to enclosure (cover foil)
DC 4242
No
T1: primary winding to secondary winding
AC 3000
No
T1: core to primary and secondary winding
AC 1740
No
Insulation tape (1-layer) for used in T1
AC 3000
No
Note(s):
5.3
No.
01
TABLE: fault condition tests
P
ambient temperature (°C) ...................................... : 25, if not otherwise stated
⎯
model/type of power supply ................................... :
⎯
manufacturer of power supply ............................... :
⎯
rated markings of power supply ............................ :
⎯
Component no.
Z1
TRF No.:IECEN60950_1B
Fault
Test
voltage (V)
Test
time
Fuse
no.
s-c
240V
10s
F1
Fuse
Result
current (A)
0 Fuse “F1” open in less than
1s, PT1 damaged, no
hazard
TRF originator: SGS Fimko
Page 50 of 70
<11003268 001>
02
C3
s-c
240V
10s
F1
0 Fuse “F1” open in less than
1s, PT1 damaged, no
hazard
03
D1
s-c
240V
10s
F1
0 Fuse “F1” open in less than
1s, D1, D2 damaged, no
hazard
04
D3
s-c
240V
10s
F1
0 Fuse “F1” open in less than
1s, no hazard
05
C3
s-c
240V
10s
F1
0 Fuse “F1” open in less than
1s, no hazard
06
C4
s-c
240V
10s
F1
0 Fuse “F1” open in less than
1s, PT1 damaged, no
hazard
07
R4
s-c
240V
5min.
F1
0.05 Input : decreased to 2.8W,
Unit output shutdown, no
damaged, no hazard
08
R5
o-c
240V
5min.
F1
0.02 Input : decreased to 0.62W,
Unit output shutdown, no
damaged, no hazard
09
R6
s-c
240V
5min.
F1
0.02 Input : decreased to 0.67W,
Unit output shutdown, no
damaged, no hazard
10
R14
s-c
240V
5min.
F1
0.05 Input : decreased to 2.8 W,
Unit output shutdown, no
damaged, no hazard
11
R15
o-c
240V
5min..
F1
0.02 Input : decreased to 0.67 W,
Unit shutdown, no damaged,
no hazard
12
R17
o-c
240V
5min.
F1
0.02 Input : decreased to 0.64 W,
Unit shutdown, no damaged,
no hazard
13
R17
s-c
240V
10s
F1
0.0 Fuse “F1” open in less than
1s, Q8, PT1 damaged, no
hazard
14
C38
s-c
240V
10s
F1
0.0 Fuse “F1” open in less than
1s, Q8, PT1, IC1, ZD1
damaged, no hazard
15
C41
s-c
240V
5min.
F1
0.02 Input : decreased to 0.62 W,
Unit shutdown, no damaged,
no hazard
16
C33
s-c
240V
5min.
F1
0.02 Input : decreased to 0.76 W,
Unit shutdown, no damaged,
no hazard
17
R68
o-c
240V
5min.
F1
0.03 Input : decreased to 1.46 W,
Unit shutdown, no damaged,
no hazard
TRF No.:IECEN60950_1B
TRF originator: SGS Fimko
Page 51 of 70
<11003268 001>
18
C11
s-c
240V
5min.
F1
0.03 Input : decreased to 1.40 W,
Unit shutdown, no damaged,
no hazard
19
C34
s-c
240V
5min.
F1
0.02 Input : decreased to 0.66 W,
Unit shutdown, no damaged,
no hazard
20
C39
s-c
240V
5min.
F1
0.02 Input : decreased to 0.63 W,
Unit shutdown, no damaged,
no hazard
21
D7
s-c
240V
5min.
F1
0.05 ZD3, ZD3A damaged, no
hazard
22
D7
o-c
240V
5min.
F1
0.04 ZD3, ZD3A damaged, no
hazard
23
C1
s-c
240V
5min.
F1
0.04 R2 damaged, no hazard
24
C2
s-c
240V
5min.
F1
0.02 R2, Q10 damaged, no
hazard
25
D6
s-c
240V
10s
F1
26
D9
s-c
240V
5min.
F1
0.03 ZD5 damaged, no hazard
27
D9
s-c
240V
5min.
F1
0.03 Input : decreased to 0.58 W,
Unit shutdown, no damaged,
no hazard
28
D23
s-c
240V
5min.
F1
0.02 Input : decreased to 0.67 W,
Unit shutdown, no damaged,
no hazard
29
Q8 (G-S)
s-c
240V
5min.
F1
0.01 Input : decreased to 0.64 W,
Unit shutdown, no damaged,
no hazard
30
Q8 (G-D)
s-c
240V
10s
F1
0.0 Fuse “F1” open in less than
1s, PT1, ZD1, IC1 damaged,
no hazard
31
Q8 (D-S)
s-c
240V
10s
F1
0.0 Fuse “F1” open in less than
1s, PT1, ZD1, IC1, Q8, R17
damaged, no hazard
32
Q8 (G)
o-c
240V
5min.
F1
0.01 Input : decreased to 0.52 W,
Unit shutdown, no damaged,
no hazard
33
Q8 (D)
o-c
240V
5min.
F1
0.01 Input : decreased to 0.62 W,
Unit shutdown, no damaged,
no hazard
34
Q8 (S)
o-c
240V
5min.
F1
0.01 Input : decreased to 0.69 W,
Unit shutdown, no damaged,
no hazard
35
C27
s-c
240V
5min.
F1
0.02 ZD5 damaged, no hazard
36
C42
s-c
240V
5min.
F1
0.03 ZD5 damaged, no hazard
TRF No.:IECEN60950_1B
0.0 Fuse “F1” open in less than
1s, PT1, ZD1, IC1, Q8
damaged, no hazard
TRF originator: SGS Fimko
Page 52 of 70
<11003268 001>
37
PC1
(Pin1-Pin2)
s-c
240V
5min.
F1
0.02 Input : decreased to 0.68 W,
Unit shutdown, U2
damaged, no hazard
38
PC1
(Pin3-Pin4)
s-c
240V
5min.
F1
0.09 Input : decreased to 0.57 W,
Unit shutdown, U2
damaged, no hazard
39
PC1 (Pin4)
o-c
240V
5min.
F1
0.12 Input : decreased to 6.3 W,
Unit shutdown, no damaged,
no hazard
40
PC1 (Pin1)
o-c
240V
5min.
F1
0.03 Input : decreased to 0.62
`W, Unit shutdown, U2
damaged, no hazard
41
IC1 (Pin2-Pin7)
s-c
240V
5min.
F1
0.02 Input : decreased to 0.69 W,
Unit shutdown, no damaged,
no hazard
42
IC1 (Pin7-Pin8)
s-c
240V
5min.
F1
0.02 Input : decreased to 0.73 W,
Unit shutdown, no damaged,
no hazard
43
IC1 (Pin3-Pin8)
s-c
240V
5min.
F1
0.02 Input : decreased to 0.67 W,
Unit shutdown, no damaged,
no hazard
44
IC1 (Pin6-Pin8)
s-c
240V
5min.
F1
0.02 Input : decreased to 0.66 W,
Unit shutdown, no damaged,
no hazard
45
IC1 (Pin1-3)
s-c
240V
5min.
F1
0.02 Unit option normal,
Input : 0.73W, No damaged,
no hazard
46
T1
(Pin 1 - 3)
s-c
240V
5min.
F1
0.06 Input : decreased to 3.5W,
Unit shutdown, no damaged,
no hazard
47
T1
(Pin 4-5)
s-c
240V
10s
F1
0.0 F1 open, ZD1, Q8, Q10
damaged, no hazard
48
T1
(Pin 6 - 8)
s-c
240V
10s
F1
0.0 F1 open, ZD1, Q8,
damaged, no hazard
49
T1
(Pin 9 - 10)
s-c
240V
10s
F1
0.0 F1 open, ZD1, Q8,
damaged, no hazard
50
output
o-l
240V
5h
F1
51
T1
(pin 6, 7 -after
D7)
o-l
240V
6.2 h
F1
TRF No.:IECEN60950_1B
0.19 Unit output shut down
I/P: 22.15W/0.19A.
O/P:47.5V/0.33A
T1=83°C
no damaged, no hazard
1.9 Unit output shut down
I/P:52W/1.9A,
O/P: 47.8V/0.32A,
T1 (pin 6, 7 to pin 8 after
D7):42.45/1.2A
T1=140°C
No damaged, no hazard
TRF originator: SGS Fimko
Page 53 of 70
<11003268 001>
52
T1 (pin 10 - after
D9)
o-l
240V
5.5 h
F1
2.0 Unit output shut down
I/P:46W/0.4A,
O/P: 47.8V/0.32A,
T1 (pin 10 to pin9 after
D9):32V/0.8A
T1=150°C
no damaged, no hazard
53
output
s-c
240V
5 min
F1
0.02 Input : decreased to 0.63 W,
Unit shutdown, no damaged,
no hazard
54
IC1 (Pin5-8)
s-c
240V
5 min
F1
0.02 Unit option normal ,
Input : 0.67W, No damaged,
no hazard
Note(s): The abbreviation denote as below:
Every test item with F1 opened as protector function was repeated with 3 times for each different source of
fuse. Source details refer to table 1.5.1.
C.2
Safety isolation transformer
P
Construction details:
Transformer part name:T1
Manufacturer: Phihong
Type:
See appended table 1.5.1
Recurring peak voltage
500 V
Required clearance for reinforced
insulation (from table 2H and 2J)
4.0 mm + 0.4 mm
Effective voltage rms
261 V
Required creepage distance for reinforced
insulation (from table 2L) interpolated
5.4 mm
Location
inside (mm)
outside (mm)
Primary-secondary
5.5
12.0 (sec.pin –core prim pin)
Primary-core
5.5
6.0
Secondary core
5.5
6.0
Primary-primary
--
--
Measured min. clearances
Location
TRF No.:IECEN60950_1B
inside (mm)
outside (mm)
TRF originator: SGS Fimko
<11003268 001>
Page 54 of 70
Primary-secondary
5.5
12.0 (sec.pin –core prim pin)
Primary-core
5.5
6.0
Secondary core
5.5
6.0
Primary-primary
--
--
Construction:
Concentric windings on type EF25 bobbin, three layers insulation between primary and secondary windings.
Distance tape =4.4mm on both sides. Winding ends additionally fixed with tape. Tubing on all windings exit
end. Two shielding are provided by one layer of insulation tape providing an overlapping of 4.0 mm at both
edges for the inner shielding and 2.0mm for the outer shielding. Core is considered as floating. There is one
layer Insulation tape on the bobbin before the first winding. All windings Outer winding is secondary.
Pin numbers
Prim.
1 – 3, Shielding – 4 – 5
Sec.
6/7 – 8, 10 - 9
Bobbin
Material
Chang Chun, T375J, V-0, 150°C; Dupont,
FR530, FR530L, V-0, 155°C,
Thickness
0.8 mm min.
Electric strength test
With 3000 V a.c. after humidity treatment
Result
TRF No.:IECEN60950_1B
Pass
TRF originator: SGS Fimko
Page 55 of 70
<11003268 001>
National Differences
Clause
Requirement − Test
Result – Remark
APPENDIX Australian National Differences according to CB Bulletin No. 107A, May 2004
(AS/NZS 60950.1:2003)
Verdict
P
(IEC Publication 60950-1:2001)
EXPLANATION FOR ABBREVIATIONS
P=Pass, F=Fail, N=Not applicable. Placed in the column to the right.
Annex ZZ Variations
1.2
Between the definitions for "Person, service" and
"Range, rated frequency" insert the following:
Potential ignition source
1.2.12.15
Inserted.
N
1.2.12.201
After the definition of 1.2.12.15, add the following: Added.
N
1.2.12.201 Potential ignition source:
Possible fault which can start a fire if the opencircuit voltage measured across an interruption or
faulty contact exceeds a value of 50 V (peak) a.c.
or d.c. and the product of the peak value of this
voltage and the measured r.m.s. current under
normal operating conditions exceeds 15 VA.
Such a faulty contact or interruption in an
electrical connection includes those which may
occur in conductive patterns on printed boards.
NOTE 201: An electronic protection circuit may
be used to prevent such a fault from becoming a
potential ignition source.
NOTE 202: This definition is from AS/NZS
60065:2003.
1.5.1
Add the following to the end of first paragraph:
Added.
N
Add the following to the end of first and third dash Added.
items:
N
"or the relevant Australian/New Zealand
Standard."
1.5.2
"or the relevant Australian/New Zealand
Standard."
2.1
Delete the Note.
Deleted.
N
3.2.3
Delete Note 2.
Deleted.
N
3.2.5
Modify Table 3B as follows:
Modified.
N
Rated current of
equipment A
Over 0.2 up to
and including 3
Nominal
crosssectional
area mm2
AWG or kcmil
(cross-sectional
area in mm2)
see note 2
0.51)
18 [0.8]
Australian National Differences according to CB Bulletin No. 107A, May 2004
Page 56 of 70
<11003268 001>
National Differences
Clause
Requirement − Test
Result – Remark
Over 3 up to and
including 7.5
0.75
16 [1.3]
Over 7.5 up to
and including 10
(0.75)2) 1.00
16 [1.3]
Over 10 up to
and including 16
(1.0)3) 1.5
14 [2]
Verdict
Replace footnote 1) with the following:
1)
This nominal cross-sectional area is only
allowed for Class II appliances if the length of the
power supply cord, measured between the point
where the cord, or cord guard, enters the
appliances, and the entry to the plug does not
exceed 2 m (0.5 mm² three-core supply flexible
cords are not permitted; see AS/NZS 3191).
Delete Note 1.
4.3.6
Replace paragraph three with:
Replaced.
N
Added.
N
Add the following paragraph:
Added.
N
For alternative tests refer to clause 4.7.201.
Material in compliance with
IEC 60950-1. For details see
table 1.5.1 of the IEC 60950-1
test report.
Equipment with a plug portion, suitable for
insertion into a 10 A 3-pin flat-pin socket-outlet
complying with AS/NZS 3112, shall comply with
the requirements in AS/NZS 3112 for equipment
with integral pins for insertion into socket-outlets.
4.3.13.5
Add the following to the end of the first
paragraph:
", or AS/NZS 2211.1"
4.7
Overall acceptance has to be
evaluated during the national
approval process.
4.7.201
Add the following after clause 4.7.3.6:
Dto.
N
Dto.
N
4.7.201 Resistance to fire - Alternative tests
4.7.201.1
General
Parts of non-metallic material shall be resistant to
ignition and spread of fire.
This requirement does not apply to decorative
trims, knobs and other parts unlikely to be ignited
or to propagate flames originating from inside the
apparatus, or the following:
(a) Components that are contained in an
enclosure having a flammability category of
FV-0 according to AS/NSZ 4695.707 and
Australian National Differences according to CB Bulletin No. 107A, May 2004
Page 57 of 70
<11003268 001>
National Differences
Clause
Requirement − Test
Result – Remark
Verdict
having openings only for the connecting
wires filling the openings completely, and for
the ventilation not exceeding 1 mm in width
regardless of the length.
(b) The following parts which would contribute
negligible fuel to a fire:
-
small mechanical parts, the mass of which
does not exceed 4 g, such as mounting
parts, gears, cams, belts and bearings;
-
small electrical components, such as
capacitors with a volume not exceeding
1750 mm3, integrated circuits, transistors and
optocoupler packages, if these components
are mounted on material flammability
category FV-1 or better according to AS/NZS
4695.707
NOTE - In considering how to minimize
propagation of fire and what “small parts” are,
account should be taken of the cumulative effect
of small parts adjacent to each other for the
possible effect of propagating fire from one part
to another.
Compliance is checked by tests of 4.7.201.2,
4.7.201.3, 4.7.201.4 and 4.7.201.5.
For the base materials of printed boards,
compliance is checked by the test of 4.7.201.5.
The tests shall be carried out on parts of nonmetallic material, which have been removed from
the apparatus. When the glow-wire test is carried
out, the parts shall be placed in the same
orientation, as they would be in normal use.
These tests are not carried out on internal wiring.
4.7.201.2
Parts of non-metallic material are subjected to
glow wire test of AS/NZS 4695.2.11, which is
carried out at 550 °C.
Dto.
N
Dto.
N
Parts for which the glow-wire test cannot be
carried out, such as those made of soft or foamy
material, shall meet the requirements specified in
ISO 9772 for category FH-3 material. The glowwire test shall be not carried out on parts of
materials classified at least FH-3 according to
ISO 9772 provided that the sample was not
thicker than the relevant part.
4.7.201.3
Testing of insulating materials
Parts of insulating materials supporting potential
ignition sources shall be subject to the glow-wire
test of AN/NZS 4695.2.11, which is carried out at
750 °C.
Australian National Differences according to CB Bulletin No. 107A, May 2004
Page 58 of 70
<11003268 001>
National Differences
Clause
Requirement − Test
Result – Remark
The test shall be also carried out on other parts of
insulating material which are within a distance of
3 mm of the connection.
NOTE - Contacts in components such as switch
contacts are considered to be connections.
For parts, which withstand the glow-wire test but
produce a flame, other parts above the
connection within the envelope of a vertical
cylinder having a diameter of 20 mm and a height
of 50 mm shall be subjected to the needle-flame
test. However, parts shielded by a barrier which
meets the needle-flame test shall not be tested.
The needle-flame test shall be made in
accordance with AS/NZS 4695.2.2 with the
following modifications:
5 Severities
Replace with:
The duration of application of the test flame shall
be 30 s ± 1 s.
8 Test procedure
8.2 Modification:
Replace the first sentence with:
The specimen shall be arranged so that the flame
can be applied to a vertical or horizontal edge as
shown in the examples of figure 1.
8.4 Modification:
The first paragraph does not apply.
Addition:
If possible, the flame shall be applied at least
10 mm from a corner.
8.5 Replacement:
The test shall be made on one specimen. If the
specimen does not withstand the test, the test
may be repeated on two further specimens, both
of which shall then withstand the test.
10 Evaluation of test results
Replace with:
The duration of burning (tb) shall not exceed 30 s.
However, for printed circuit boards, it shall not
exceed 15 s.
The needle-flame test shall not be carried out on
parts of material classified as V-0 or V-1
Australian National Differences according to CB Bulletin No. 107A, May 2004
Verdict
<11003268 001>
Page 59 of 70
National Differences
Clause
Requirement − Test
Result – Remark
Verdict
according to IEC 60695-11-10, provided that the
sample tested was not thicker than the relevant
part.
4.7.201.4
Testing in the event of non-extinguishing material Dto.
N
If parts, other than enclosures, do not withstand
the glow-wire tests of 4.7.201.3, by failure to
extinguish within 30 s after the removal of the
glow-wire tip, the needle-flame test detailed in
4.7.201.3 is made on all parts of non-metallic
material which are within a distance of 50 mm or
which are likely to be impinged upon by flame
during the tests of 4.7.201.3. Parts shielded by a
separate barrier which meets the needle-flame
test need not to be tested.
NOTE 1 - If the enclosure does not withstand the
glow-wire test the equipment is considered to
have failed to meet the requirement of clause
4.7.201 without the need for consequential
testing.
NOTE 2 - If other parts do not withstand the glowwire test due to ignition of the tissue paper and if
this indicates that burring or glowing particles can
fall onto an external surface underneath the
equipment, the equipment is considered to have
failed to meet the requirement of clause 4.7.201
without the need for consequential testing.
NOTE 3 - Parts likely to be impinged upon by the
flame are considered to be those within the
envelope of a vertical cylinder having a radius of
10 mm and a height equal to the height of the
flame, positioned above the point of the material
supporting in contact with or in close proximity to
connections.
4.7.201.5
Testing of printed boards
Dto.
The base material of printed boards is subjected
to needle-flame test to Clause 4.7.201.3. The
flame is applied to the edge of the board where
the heat sink effect is lowest when the board is
positioned as in normal use. The flame shall not
be applied to an edge, consisting of broken
perforations, unless the edge is less than 3 mm
for a potential ignition source.
The test is not carried out if the –
- Printed board does not carry any potential
ignition source;
- Base material of printed boards, on which the
available apparent power at a connection
exceeds 15 VA operating at a voltage
exceeding 50 V and equal or less than 400 V
Australian National Differences according to CB Bulletin No. 107A, May 2004
N
<11003268 001>
Page 60 of 70
National Differences
Clause
Requirement − Test
Result – Remark
Verdict
(peak) a.c. or d.c. under normal operating
conditions, is of flammability category FV-1 or
better according to AS/NZS 4695.707, or the
printed boards are protected by an enclosure
meeting the flammability category FV-0
according to AS/NZS 4695.707, or made of
metal, having openings only for connecting
wires which fill the opening completely, or
- Base material of printed boards, on which the
available apparatus power at a connection
exceeds 15 VA operating at a voltage
exceeding 400 V (peak) a.c. or d.c. under
normal operating conditions, and base material
printed boards supporting spark gaps which
provide protection against overvoltages, is of
flammability category FV-0 according to
AS/NSZ 4695.707 or the printed boards are
contained in a metal enclosure, having
openings only for connecting wires fill the
openings completely.
Compliance is determined using the smallest
thickness of the material.
NOTE - Available apparent power is the
maximum apparent power, which can be drawn
from the supplying circuit through a resistive load
whose value is chosen to maximise the apparent
power for more than 2 min when the circuit
supplied is disconnected.
6.2.2
Add the following after the first paragraph:
Added.
N
Deleted.
N
In Australia (this variation does not apply in New
Zealand), compliance with 6.2.2 is checked by
the tests of both 6.2.2.1 and 6.2.2.2.
Delete the note.
6.2.2.1
Delete Note 2.
Add the following after the first paragraph:
In Australia (this variation does not apply in New
Zealand), the electrical separation is subjected to
10 impulses of alternating polarity, using the
impulse test generator of annex N for 10/700 µs
impulses. The interval between successive
impulses is 60 s and the initial voltage, Uc, is:
- for 6.2.1 a):
7.0 kV for hand-held telephones and for
headsets and 2.5 kV for other equipment; and
- for 6.2.1b) and 6.2.1c):
1.5 kV.
NOTE 201 - The 7 kV impulse simulates lightning
Australian National Differences according to CB Bulletin No. 107A, May 2004
<11003268 001>
Page 61 of 70
National Differences
Clause
Requirement − Test
Result – Remark
Verdict
surges on typical rural and semi-rural network
lines.
NOTE 202 – The 2.5 kV impulse for 6.2.1a) was
chosen to ensure adequacy of the insulation
concerned and does not necessarily simulate
likely overvoltages.
6.2.2.2
Delete the note.
Deleted.
N
Added.
N
Add the following after the second paragraph:
In Australia (this variation does not apply in New
Zealand), the a.c. test voltage is:
- for 6.2.1a):
3 kV; and
- for 6.2.1b) and 6.2.1c):
1.5 kV.
NOTE 201 – Where there are capacitors across
the insulation under test, it is recommended that
d.c. test voltages are used.
NOTE 202 – The 3 kV and 1.5 kV values have
been determined considering the low frequency
induced voltages from the power supply
distribution system.
Annex P
Add the following Normative References to
Annex P:
IEC 60065, Audio, Video and similar electronic
apparatus - Safety requirements
AS/NZS 3112, Approval and test specification Plugs and socket-outlets
AS/NZS 3191, Approval and test specification Electric flexible cords
AS/NZS 4695.707, Fire hazard testing of
electrotechnical products - Methods of test for the
determination of the flammability of solid
electrical insulating materials when exposed to an
igniting source
Australian National Differences according to CB Bulletin No. 107A, May 2004
Page 62 of 70
<11003268 001>
National Differences
Clause
Requirement − Test
Result – Remark
APPENDIX Canadian National Differences according to CB Bulletin No. 107A, May 2004
(CAN/CSA C22.2 No. 60950-1/UL60950-1)
Verdict
P
(IEC Publication 60950-1:2001)
Special National Conditions
1.1.1
All equipment is to be designed to allow
Overall acceptance has to be
installations in accordance with the National
evaluated during the national
Electrical Code (NEC), ANSI/NFPA 70,the
approval process.
Canadian Electrical Code (CEC), Part I,
CAN/CSA C22.1, and when applicable, the
National Electrical Safety Code, IEEE C2. Also,
unless marked or otherwise identified, installation
is allowed per the Standard for the Protection of
Electronic Computer/Data-Processing
Equipment, ANSI/NFPA 75.
N
1.4.14
For Pluggable Equipment Type A, the protection
in the installation is assumed to be 20A.
Considered.
P
1.5.5
For lengths exceeding 3.05 m, external
interconnecting flexible cord and cable
assemblies are required to be a suitable cable
type (e.g. DP, CL2) specified in the NEC.
No power cord set provided.
For the interconnection cables
is to be evaluated when
submitted for national
approval.
N
Single-phase equipment.
N
For lengths 3.05 m or less, external
interconnecting flexible cord and cable
assemblies that are not types specified in the
NEC are required to have special construction
features and identification markings.
1.7.1
Equipment for use on a.c. mains supply systems
with a neutral and more than one phase
conductor (e.g. 120/240 V, 3-wire) require a
special marking format for electrical ratings.
A voltage rating that exceeds an attachment plug
cap rating is only permitted if it does not exceed
the extreme operating conditions in Table 2 of
CAN/CSA C22.2 No. 235, and if it is part of a
range that extends into the Table 2 “Normal
Operating Conditions.” Likewise, a voltage rating
shall not be lower than the specified “Normal
Operating Conditions,” unless it is part of a range
that extends into the “Normal Operating
Conditions.”
2.5
Where a fuse is used to provide Class 2, Limited No such fuse provided.
Power Source, or TNV current limiting, it shall not
be operator-accessible unless it is not
interchangeable.
Korean National Differences according to CB Bulletin No. 107A, May 2004
N
<11003268 001>
Page 63 of 70
National Differences
Clause
Requirement − Test
2.7.1
Suitable NEC/CEC branch circuit protection rated No such components
at the maximum circuit rating is required for all
provided.
standard supply outlets, receptacles and
medium-base or smaller lampholders if the
supply branch circuit protection is not suitable.
Result – Remark
Verdict
N
Power distribution transformers distributing power
at 100 volts or more, and rated 10 kVA or more,
require transformer overcurrent protection.
3.2
Wiring methods (terminals, leads, etc.) used for
the connection of the equipment to the mains
shall be in accordance with the NEC/CEC.
3.2.1
Power supply cords are required to have
No cords provided.
attachment plugs rated not less than 125 percent
of the rated current of the equipment.
N
3.2.3
Permanent connection of equipment to the mains Pluggable type equipment.
supply by a power supply cord is not permitted,
except for certain equipment, such as ATMs.
N
3.2.5
Power supply cords are required to be no longer
than 4.5 m in length.
No cords provided.
N
Pluggable type equipment.
N
Appliance inlet is provided..
N
Flexible power supply cords are required to be
compatible with Article 400 of the NEC, and
Tables 11 and 12 of the CEC.
3.2.9
Permanently connected equipment is required to
have a suitable wiring compartment and wire
bending space.
3.3
Wiring terminals and associated spacings for field No terminals provided.
wiring connections shall comply with CSA C22.2
No. 0.
N
3.3.3
Wire binding screws are not permitted to attach
conductors larger than 10 AWG (5.3 mm²).
N
3.3.4
Terminals for permanent wiring, including
No terminals provided.
protective earthing terminals, are required to be
suitable for U.S./Canadian wire gauge sizes,
rated 125 percent of the equipment rating, and be
specially marked when specified (1.7.7).
N
3.4.2
Motor control devices are required for cordEquipment is not such a
connected equipment with a motor if the
device.
equipment is rated more than 12A, or if the motor
has a nominal voltage rating greater than 120V,
or is rated more than 1/3 hp (locked rotor current
over 43 A)
N
3.4.8
Vertically-mounted disconnect switches and
circuit breakers are required to have the ”on”
position indicated by the handle in the up
position.
N
No screws provided.
No such devices incorporated.
Korean National Differences according to CB Bulletin No. 107A, May 2004
<11003268 001>
Page 64 of 70
National Differences
Clause
Requirement − Test
Result – Remark
3.4.11
For computer room applications, equipment with
battery systems capable of supplying 750 VA for
five minutes are required to have a battery
disconnect means that may be connected to the
computer room remote power-off circuit.
Not such an application.
4.3.12
The maximum quantify of flammable liquid stored Overall acceptance has to be
in equipment is required to comply with NFPA 30. evaluated during the national
approval process.
N
4.3.13
Equipment with lasers is required to meet Code
of Federal Regulations 21 CFR 1040 (and the
Canadian Radiation Emitting Devices Act, REDR
C1370).
N
4.7
For computer room applications, automated
Not such an application.
information storage systems with combustible
media greater than 27 cubic feet are required to
have a provision for connection of either
automatic sprinklers or a gaseous agent
extinguishing system with an extended discharge.
N
4.7.3.1
For computer room applications, enclosures with Not such an application.
combustible material measuring greater than 0.9
m² or a single dimension greater than 1.8 m are
required to have a flame spread rating of 50 or
less. For other applications, enclosures with the
same dimensions require a flame spread rating of
200 or less.
N
Annex H
Equipment that produces ionizing radiation is
required to comply with the Code of Federal
Regulations, 21 CFR 1020 (and the Canadian
Radiation Emitting Devices Act, REDR C1370).
N
No laser contained.
Verdict
N
Other differences
1.5.1
Components of equipment must be suitable for
the application, and must comply with the
requirements of the equipment standard and the
applicable national (Canadian and/or U.S.)
component or material standards, as far as they
may apply.
Refer to table 1.5.1.
The acceptance will be based on the following:
A) A component Certified by a Canadian or U.S.
National Certification Body (NCB) to a
Canadian or U.S. component standard will be
checked for correct application and use in
accordance with its specified rating. Where
necessary, it will also be subject to the
applicable tests of the equipment standard.
B) A component, which has a CB Test
Certificate for compliance with a relevant IEC
component standard, will be checked for
correct application and use in accordance
Korean National Differences according to CB Bulletin No. 107A, May 2004
P
<11003268 001>
Page 65 of 70
National Differences
Clause
Requirement − Test
Result – Remark
Verdict
with its specified ratings. Where necessary, it
will also be subject to the applicable tests of
the equipment standard, and to the
applicable tests of the Canadian and/or U.S.
component or material standard, under the
conditions occurring in the equipment.
C) A component, which has no approval as in A)
or B) above or which is used not in
accordance with its specified ratings, will be
subject to the applicable tests of the
equipment standard, and to the applicable
tests of the Canadian and/or U.S. component
or material standard, under the conditions
occurring in the equipment.
D) Some components may require annual retesting, which may be carried out by the
manufacturer, CSA International or another
laboratory
2.3.1
For TNV-2 and TNV-3 circuits with other than
No TNV circuits.
ringing signals and with voltages exceeding
42.4 Vpeak or 60 Vd.c., the maximum acceptable
current through a 2000 ohm resistor (or greater)
connected across the voltage source with other
loads disconnected is 7.1 mA peak or 30 mAd.c.
under normal operating conditions.
N
2.3.2
In the event of a single fault, the limits of 2.2.3
No TNV circuits.
apply to SELV Circuits and accessible conductive
parts.
N
2.6.3.3
When subject to impedance testing, protective
earthing and bonding are required to be
subjected to the additional test conditions
specified.
N
3.2.1.2
Equipment connected to a centralized d.c. power Not applicable for this
system, and having one pole of the DC mains
equipment.
input terminal connected to the main protective
earthing terminal in the equipment, is required to
comply with special earthing, writing, marking and
installation instruction requirements.
N
4.2.8.1
Enclosures around CRTs with a face diameter of Not applicable for this
160mm or more are required to reduce the risk of equipment.
injury due to the implosion of the CRT.
N
4.3.2
Equipment with handles is required to comply
with special loading tests.
Not applicable for this
equipment.
N
5.1.8.3
Equipment intended to receive
Not applicable for this
telecommunication ringing signals is required to
equipment.
comply with a special touch current measurement
tests.
N
Not applicable for this Class II
equipment.
Korean National Differences according to CB Bulletin No. 107A, May 2004
Page 66 of 70
<11003268 001>
National Differences
Clause
Requirement − Test
Result – Remark
6.2.1
Enamel coating on winding wire not considered
electrical separation unless subjected to special
investigation.
Enamel coating not
considered as electrical
separation.
6.4
Equipment intended for connection to
No TNV circuits.
telecommunication network outside plant cable is
required to be protected against overvoltage from
power line crosses in accordance with 6.4 and
Annex NAC.
N
6.5
Equipment connected to a telecommunications
network and supplied with an earphone intended
to be held against, or in the ear is required to
comply with special acoustic pressure tests.
No TNV circuits.
N
M.2
Continuous ringing signals up to 16 mA only are
permitted if the equipment is subjected to special
installation and performance restrictions.
No TNV circuits.
N
APPENDIX Korean National Differences according to CB Bulletin No. 107A, May 2004
(K60950)
Verdict
N
P
(IEC Publication 60950-1:2001)
EXPLANATION FOR ABBREVIATIONS
P=Pass, F=Fail, N=Not applicable. Placed in the column to the right.
1.5.101
Addition:
Plugs for the connection of the apparatus to the
supply mains shall comply with the Korean
requirement (KSC 8305).
7
Addition: EMC
The apparatus shall comply with the relevant
CISPR standards.
Added. No power cord set
provided.
N
To be evaluated when
submitted for national
approval.
N
Korean National Differences according to CB Bulletin No. 107A, May 2004
Page 67 of 70
<11003268 001>
National Differences
Clause
Requirement − Test
Result – Remark
APPENDIX US National Differences according to CB Bulletin No. 107A, May 2004
(UL 60950-1)
Verdict
P
(IEC Publication 60950-1:2001)
Special National Conditions
1.1.1
All equipment is to be designed to allow
Overall acceptance has to be
installations in accordance with the National
evaluated during the national
Electrical Code (NEC), ANSI/NFPA 70,the
approval process.
Canadian Electrical Code (CEC), Part I,
CAN/CSA C22.1, and when applicable, the
National Electrical Safety Code, IEEE C2. Also,
unless marked or otherwise identified, installation
is allowed per the Standard for the Protection of
Electronic Computer/Data-Processing
Equipment, ANSI/NFPA 75.
N
1.4.14
For Pluggable Equipment Type A, the protection
in the installation is assumed to be 20A.
Considered.
P
1.5.5
For lengths exceeding 3.05 m, external
interconnecting flexible cord and cable
assemblies are required to be a suitable cable
type (e.g. DP, CL2) specified in the NEC.
No power cord set provided.
For the interconnection cables
is to be evaluated when
submitted for national
approval.
N
Single-phase equipment.
N
For lengths 3.05 m or less, external
interconnecting flexible cord and cable
assemblies that are not types specified in the
NEC are required to have special construction
features and identification markings.
1.7.1
Equipment for use on a.c. mains supply systems
with a neutral and more than one phase
conductor (e.g. 120/240 V, 3-wire) require a
special marking format for electrical ratings.
A voltage rating that exceeds an attachment plug
cap rating is only permitted if it does not exceed
the extreme operating conditions in Table 2 of
CAN/CSA C22.2 No. 235, and if it is part of a
range that extends into the Table 2 “Normal
Operating Conditions.” Likewise, a voltage rating
shall not be lower than the specified “Normal
Operating Conditions,” unless it is part of a range
that extends into the “Normal Operating
Conditions.”
2.5
Where a fuse is used to provide Class 2, Limited No such fuse provided.
Power Source, or TNV current limiting, it shall not
be operator-accessible unless it is not
interchangeable.
N
2.7.1
Suitable NEC/CEC branch circuit protection rated No such components
at the maximum circuit rating is required for all
provided.
standard supply outlets, receptacles and
medium-base or smaller lampholders if the
supply branch circuit protection is not suitable.
N
US National Differences according to CB Bulletin No. 107A, May 2004
<11003268 001>
Page 68 of 70
National Differences
Clause
Requirement − Test
Result – Remark
Verdict
Power distribution transformers distributing power
at 100 volts or more, and rated 10 kVA or more,
require transformer overcurrent protection.
3.2
Wiring methods (terminals, leads, etc.) used for
the connection of the equipment to the mains
shall be in accordance with the NEC/CEC.
3.2.1
Power supply cords are required to have
No cords provided.
attachment plugs rated not less than 125 percent
of the rated current of the equipment.
N
3.2.3
Permanent connection of equipment to the mains Pluggable type equipment.
supply by a power supply cord is not permitted,
except for certain equipment, such as ATMs.
N
3.2.5
Power supply cords are required to be no longer
than 4.5 m in length.
No cords provided.
N
Pluggable type equipment.
N
Appliance inlet is provided..
N
Flexible power supply cords are required to be
compatible with Article 400 of the NEC, and
Tables 11 and 12 of the CEC.
3.2.9
Permanently connected equipment is required to
have a suitable wiring compartment and wire
bending space.
3.3
Wiring terminals and associated spacings for field No terminals provided.
wiring connections shall comply with CSA C22.2
No. 0.
N
3.3.3
Wire binding screws are not permitted to attach
conductors larger than 10 AWG (5.3 mm²).
N
3.3.4
Terminals for permanent wiring, including
No terminals provided.
protective earthing terminals, are required to be
suitable for U.S./Canadian wire gauge sizes,
rated 125 percent of the equipment rating, and be
specially marked when specified (1.7.7).
N
3.4.2
Motor control devices are required for cordEquipment is not such a
connected equipment with a motor if the
device.
equipment is rated more than 12A, or if the motor
has a nominal voltage rating greater than 120V,
or is rated more than 1/3 hp (locked rotor current
over 43 A)
N
3.4.8
Vertically-mounted disconnect switches and
circuit breakers are required to have the ”on”
position indicated by the handle in the up
position.
No such devices incorporated.
N
3.4.11
For computer room applications, equipment with
battery systems capable of supplying 750 VA for
five minutes are required to have a battery
disconnect means that may be connected to the
computer room remote power-off circuit.
Not such an application.
N
No screws provided.
US National Differences according to CB Bulletin No. 107A, May 2004
<11003268 001>
Page 69 of 70
National Differences
Clause
Requirement − Test
4.3.12
The maximum quantify of flammable liquid stored Overall acceptance has to be
in equipment is required to comply with NFPA 30. evaluated during the national
approval process.
N
4.3.13
Equipment with lasers is required to meet Code
of Federal Regulations 21 CFR 1040 (and the
Canadian Radiation Emitting Devices Act, REDR
C1370).
N
4.7
For computer room applications, automated
Not such an application.
information storage systems with combustible
media greater than 27 cubic feet are required to
have a provision for connection of either
automatic sprinklers or a gaseous agent
extinguishing system with an extended discharge.
N
4.7.3.1
For computer room applications, enclosures with Not such an application.
combustible material measuring greater than 0.9
m² or a single dimension greater than 1.8 m are
required to have a flame spread rating of 50 or
less. For other applications, enclosures with the
same dimensions require a flame spread rating of
200 or less.
N
Annex H
Equipment that produces ionizing radiation is
required to comply with the Code of Federal
Regulations, 21 CFR 1020 (and the Canadian
Radiation Emitting Devices Act, REDR C1370).
N
Result – Remark
No laser contained.
Verdict
Other differences
1.5.1
Some components and materials associated with Refer to table 1.5.1.
the risk of fire, electric shock, or personal injury
are required to have component or material
ratings in accordance with the applicable national
(U.S. and Canadian) component or material
requirements. These components include:
attachment plugs, battery packs (rechargeable
type, used with transportable equipment),
cathode ray tubes, circuit breakers,
communication circuit accessories, connectors
(used for current interruption of non-LPS circuits),
cord sets and power supply cords, direct plug-in
equipment, enclosures (outdoor), flexible cords
and cables, fuses (branch circuit), fuseholders,
ground-fault current interrupters, industrial control
equipment, insulating tape, interconnecting
cables, lampholders, limit controls, printed wiring,
protectors for communications circuits,
receptacles, solid state controls, supplementary
protectors, surge suppressors, switches
(including interlock switches), thermal cut-offs,
thermostats, multi-layer transformer winding
wire, tubing, wire connectors, and wire and
cables.
US National Differences according to CB Bulletin No. 107A, May 2004
P
<11003268 001>
Page 70 of 70
National Differences
Clause
Requirement − Test
2.3.1
For TNV-2 and TNV-3 circuits with other than
No TNV circuits.
ringing signals and with voltages exceeding
42.4 Vpeak or 60 Vd.c., the maximum acceptable
current through a 2000 ohm resistor (or greater)
connected across the voltage source with other
loads disconnected is 7.1 mA peak or 30 mA d.c.
under normal operating conditions.
N
2.3.2
In the event of a single fault, the limits of 2.2.3
No TNV circuits.
apply to SELV Circuits and accessible conductive
parts.
N
2.6.3.3
When subject to impedance testing, protective
earthing and bonding are required to be
subjected to the additional test conditions
specified.
N
3.2.1.2
Equipment connected to a centralized d.c. power Not applicable for this
system, and having one pole of the DC mains
equipment.
input terminal connected to the main protective
earthing terminal in the equipment, is required to
comply with special earthing, writing, marking and
installation instruction requirements.
N
4.2.8.1
Enclosures around CRTs with a face diameter of Not applicable for this
160mm or more are required to reduce the risk of equipment.
injury due to the implosion of the CRT.
N
4.3.2
Equipment with handles is required to comply
with special loading tests.
Not applicable for this
equipment.
N
5.1.8.3
Equipment intended to receive
Not applicable for this
telecommunication ringing signals is required to
equipment.
comply with a special touch current measurement
tests.
N
6.2.1
Enamel coating on winding wire not considered
electrical separation unless subjected to special
investigation.
N
6.4
Equipment intended for connection to
No TNV circuits.
telecommunication network outside plant cable is
required to be protected against overvoltage from
power line crosses in accordance with 6.4 and
Annex NAC.
N
6.5
Equipment connected to a telecommunications
network and supplied with an earphone intended
to be held against, or in the ear is required to
comply with special acoustic pressure tests.
No TNV circuits.
N
M.2
Continuous ringing signals up to 16 mA only are
permitted if the equipment is subjected to special
installation and performance restrictions.
No TNV circuits.
N
Result – Remark
Not applicable for this Class II
equipment.
Enamel coating not
considered as electrical
separation.
US National Differences according to CB Bulletin No. 107A, May 2004
Verdict
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertisement