Сервис мануал fdkn
FDTN-C
CEILING RECESSED TYPE
PACKAGED AIR CONDITIONER
Split system, Air cooled
Cooling only type
(
)
FDTN208CEN-S,
FDTN208CEN,
FDTN258CEN-S,
FDTN258CEN,
FDTN308CEN,
FDTN308CES,
FDTN508CES,
FDTN208CEP-S
FDTN208CEP
FDTN258CEP-S
FDTN258CEP
FDTN308CEP
FDTN408CES
FDTN508CEM
FDT208CEN-S,
FDT308CEN,
FDT408CES,
FDT258CEN-S
FDT308CES
FDT508CES
FDTN-C
7.
285
FDTN-C
CONTENTS
7.1
GENERAL INFORMATION ........................................................................ 287
7.1.1
Specific features ................................................................................. 287
7.1.2
How to read the model name ............................................................. 287
7.2
SELECTION DATA..................................................................................... 288
7.2.1
Specifications ...................................................................................... 288
7.2.2
Range of usage & limitations ............................................................. 308
7.2.3
Exterior dimensions............................................................................ 309
7.2.4
Exterior appearance............................................................................ 318
7.2.5
Piping system ...................................................................................... 319
7.2.6
Selection chart .................................................................................... 320
7.2.7
Noise level ........................................................................................... 323
7.3
ELECTRICAL DATA .................................................................................. 325
7.3.1
Electrical wiring .................................................................................. 325
7.4
OUTLINE OF OPERATION CONTROL BY MICROCOMPUTER ............. 330
7.5
APPLICATION DATA ................................................................................. 330
7.6
MAINTENANCE DATA............................................................................... 330
286
FDTN-C
7.1
GENERAL INFORMATION
7.1.1
Specific features
(1)
Less refrigerant charge amount due to use of double phase refrigerant flow system. The total refrigerant charge amount has
been reduced by more than 50%.
(2)
The indoor outdoor interconnection signal wiring has been done away with. The microcomputer chip is installed in the
indoor unit. There is no need for the unit to communicate between the outdoor and indoor units so the unit is more resistant
to electromagnetic noise thus the incidence of microcomputer malfunction has been reduced. The compressor in the outdoor
unit has its own self protection function, that reacts according to abnormal high pressure and excessive high temperature.
(3)
There are only four power lines between the outdoor and indoor unit. As no signal wire is used there is no need to separate the
power line from the signal line. One cab tyre cable with 4 wires encased in one sheath is enough for conducting the wiring
work between the outdoor unit and the indoor unit. This contributes to simpler wiring work in the field.
(4)
All air supply ports have auto swing louvers. The indoor fan motor has two speeds of high and low.
(5)
All models have control valves protruding from the outdoor unit for faster flare connection work in the field.
(6) Low sound level
Operating noise has been remarkably reduced due to adoption of the crescent turbo fan which cuts off wind-blowing noise
and also console type of cabinet which is highly effective to protect vibration.
(7) 700mm high drain head
Adoption of drain pump with high drain head and high capacity (600cc/min) has made it possible to have maximum 700
mm(form below ceiling drain head.[In case 700mm drain head is required, set it up close to the unit. It is impossible to do
piping on down slope.]
How to read the model name
Exampie: FDTN 30 8 C
EN
FDTN-C
7.1.2
Applicable power source ... See the specifications
Cooling only type
Series No.
Nominal capacity
FDTN : Ceiling recessed type unit with
wireless remote controller
Model name
FDT : Ceiling recessed type unit with
wired remote controller
FDC : Outdoor unit
287
FDTN-C
7.2
SELECTION DATA
7.2.1
Specifications
(a) Wireless remote controller type
Model FDTN208CEN-S
FDTN208CEN-S
Model
Item
FDTN208C
Nominal cooling capacity(1)
FDC208CEN3
5000
W
Power source
Operation data(3)
Cooling input
1 Phase, 220/240V, 50Hz
kW
1.78/1.87
Running current (Cooling)
A
8.3/8.1
Power factor (Cooling)
%
97/96
Inrush current (L.R.A)
A
Noise level(4)
Exterior dimensions
Height × Width × Depth
dB(A)
Net weight
Refrigerant equipment
Compressor type & Q’ty
kg
mm
44
Hi:38 Lo:33
Unit 215 × 700 × 700
Panel 26 × 800 × 800
52
690 × 880 × 290
23 (Unit:18 Panel:5)
49
–
RM5523GNE4 × 1
–
1.6
–
Line starting
Heat exchanger
Louver fins & inner grooved tubing
Slitted fines & bare tubing
Refrigerant control
Capillary tube
Motor
kW
Starting method
Capillary tube
Refrigerant
R22
Quantity
Refrigerant oil
kg
Holding charged
r
–
0.9 [Pre-charged up to the piping length of 0m]
0.7 (BARREL FREEZE 32 SAM)
High pressure control
–
Air handling equipment
Turbo fan × 1
Fan type & Q’ty
Motor
W
Starting method
Air flow (Standard)
CMM
Fresh air intake
Air filter, Q’ty
Shock & vibration absorber
Electric heater
Operation control
Operation switch
Safety equipment
Installation data
Refrigerant piping size
30 × 1
55 × 1
Line starting
Line starting
Hi:14 Lo:10
56
Available
–
Long life filter × 1 (washable)
–
Rubber sleeve (for fan motor)
Rubber mount (for compressor)
–
20 (Crank case heater)
Wireless remote control switch
– (Indoor unit side)
W
Room temperature control
Propeller fan × 1
Thermostat by electronics
–
Internal thermostat for fan motor.
Frost protection thermostat.
Internal thermostat for fan motor.
Thermostat for discharge temperature.
mm
(in)
Liquid line: φ6.35 (1/4″) Gas line: φ15.88 (5/8″)
Connecting method
Drain hose
Flare piping
(Connectable with VP25)
Insulation for piping
Accessories
–
Necessary (both Liquid & Gas lines)
Mounting kit. Wireless remote controller.
Optional parts
Notes (1) The data are measured at the following conditions.
Item
Indoor air temperature
Operation
DB
WB
Cooling
27˚C
19˚C
Decorative Panel
Outdoor air temperature
DB
WB
35˚C
24˚C
(2) This packaged air conditioner is manufactured and tested in conformity with the following standard.
JIS B8616 “UNITARY AIR CONDITIONERS”
(3) The operation data indicate when the air conditioner is operated at 220V and 240V respectively.
(4) Indicates the value at mild mode.
288
Standards
ISO-T1, JIS B8616
FDTN-C
Model
FDTN208CEP-S
FDTN208CEP-S
Model
Item
FDTN208C
Nominal cooling capacity(1)
FDC208CEP3
5200
W
Cooling input
1 Phase, 220V, 60Hz
kW
1.78
Running current (Cooling)
A
8.4
Power factor (Cooling)
%
96
Inrush current (L.R.A)
A
Noise level(4)
Exterior dimensions
Height × Width × Depth
dB(A)
Net weight
Refrigerant equipment
Compressor type & Q’ty
kg
mm
52
Hi:38 Lo:33
Unit 215 × 700 × 700
Panel 26 × 800 × 800
52
690 × 880 × 290
23 (Unit:18 Panel:5)
49
–
RM5520GP4 × 1
–
1.6
–
Line starting
Heat exchanger
Louver fins & inner grooved tubing
Slitted fines & bare tubing
Refrigerant control
Capillary tube
Motor
kW
Starting method
Capillary tube
Refrigerant
R22
Quantity
Refrigerant oil
kg
Holding charged
r
–
0.9 [Pre-charged up to the piping length of 0m]
0.7 (BARREL FREEZE 32 SAM)
High pressure control
–
Air handling equipment
Turbo fan × 1
Fan type & Q’ty
Motor
W
Starting method
Air flow (Standard)
CMM
Fresh air intake
Air filter, Q’ty
Shock & vibration absorber
Electric heater
Operation control
Operation switch
Safety equipment
Installation data
Refrigerant piping size
30 × 1
55 × 1
Line starting
Line starting
Hi:14 Lo:10
56
Available
–
Long life filter × 1 (washable)
–
Rubber sleeve (for fan motor)
Rubber mount (for compressor)
–
20 (Crank case heater)
Wireless remote control switch
– (Indoor unit side)
W
Room temperature control
Propeller fan × 1
Thermostat by electronics
–
Internal thermostat for fan motor.
Frost protection thermostat.
Internal thermostat for fan motor.
Thermostat for discharge temperature.
mm
(in)
Liquid line: φ6.35 (1/4″) Gas line: φ15.88 (5/8″)
Connecting method
Drain hose
Flare piping
(Connectable with VP25)
Insulation for piping
Accessories
–
Necessary (both Liquid & Gas lines)
Mounting kit. Wireless remote controller.
Optional parts
Notes (1) The data are measured at the following conditions.
Item
Indoor air temperature
Operation
DB
WB
Cooling
27˚C
19˚C
Decorative Panel
Outdoor air temperature
DB
WB
35˚C
24˚C
Standards
ISO-T1, JIS B8616
(2) This packaged air conditioner is manufactured and tested in conformity with the following standard.
JIS B8616 “UNITARY AIR CONDITIONERS”
(3) The operation data indicate when the air conditioner is operated at 220V.
(4) Indicates the value at mild mode.
289
FDTN-C
Operation data(3)
Power source
FDTN-C
Model
FDTN258CEN-S
FDTN258CEN-S
Model
Item
FDTN258C
Nominal cooling capacity(1)
FDC258CEN3
5700
W
Power source
Operation data(3)
Cooling input
1 Phase, 220/240V, 50Hz
kW
2.05/2.16
Running current (Cooling)
A
9.4/9.4
Power factor (Cooling)
%
99/96
Inrush current (L.R.A)
A
Noise level(4)
Exterior dimensions
Height × Width × Depth
dB(A)
Net weight
Refrigerant equipment
Compressor type & Q’ty
kg
mm
51
Hi:39 Lo:35
Unit 260 × 840 × 840
Panel 30 × 950 × 950
52
845 × 880 × 340
30 (Unit:24 Panel:6)
55
–
RM5526GNE4 × 1
–
1.9
–
Line starting
Heat exchanger
Louver fins & inner grooved tubing
Slitted fines & bare tubing
Refrigerant control
Capillary tube
Motor
kW
Starting method
Capillary tube
Refrigerant
R22
Quantity
Refrigerant oil
kg
Holding charged
r
–
1.05 [Pre-charged up to the piping length of 5m]
0.7 (BARREL FREEZE 32 SAM)
High pressure control
–
Air handling equipment
Turbo fan × 1
Fan type & Q’ty
Motor
W
Starting method
Air flow (Standard)
CMM
Fresh air intake
Air filter, Q’ty
Shock & vibration absorber
Electric heater
Operation control
Operation switch
Safety equipment(4)
Installation data
Refrigerant piping size
25 × 1
55 × 1
Line starting
Line starting
Hi:16 Lo:11
56
Available
–
Long life filter × 1 (washable)
–
Rubber sleeve (for fan motor)
Rubber mount (for compressor)
–
20 (Cank case heater)
Wireless remote control switch
– (Indoor unit side)
W
Room temperature control
Propeller fan × 1
Thermostat by electronics
–
Internal thermostat for fan motor.
Frost protection thermostat.
Internal thermostat for fan motor.
Thermostat for discharge temperature.
mm
(in)
Liquid line: φ9.52 (3/8″) Gas line: φ15.88 (5/8″)
Connecting method
Drain hose
Flare piping
(Connectable with VP25)
Insulation for piping
Accessories
–
Necessary (both Liquid & Gas lines)
Mounting kit. Wireless remote controller.
Optional parts
Notes (1) The data are measured at the following conditions.
Item
Indoor air temperature
Operation
DB
WB
Cooling
27˚C
19˚C
Decorative Panel
Outdoor air temperature
DB
WB
35˚C
24˚C
(2) This packaged air conditioner is manufactured and tested in conformity with the following standard.
JIS B8616 “UNITARY AIR CONDITIONERS”
(3) The operation data indicate when the air conditioner is operated at 220V and 240V respectively.
(4) Indicates the value at mild mode.
290
Standards
ISO-T1, JIS B8616
FDTN-C
Model
FDTN258CEP-S
FDTN258CEP-S
Model
Item
FDTN258C
Nominal cooling capacity(1)
FDC258CEP3
6200
W
Operation data(3)
Power source
Cooling input
1 Phase, 220V, 60Hz
kW
2.77
Running current (Cooling)
A
12.8
Power factor (Cooling)
%
98
Inrush current (L.R.A)
A
Noise level(4)
Exterior dimensions
Height × Width × Depth
dB(A)
Net weight
Refrigerant equipment
Compressor type & Q’ty
kg
mm
71
Hi:39 Lo:35
Unit 260 × 840 × 840
Panel 30 × 950 × 950
52
845 × 880 × 340
30 (Unit:24 Panel:6)
55
–
RM5526GP4 × 1
–
1.9
–
Line starting
Heat exchanger
Louver fins & inner grooved tubing
Slitted fines & bare tubing
Refrigerant control
Capillary tube
Motor
kW
Starting method
Capillary tube
Refrigerant
R22
Quantity
Refrigerant oil
kg
Holding charged
r
–
1.13 [Pre-charged up to the piping length of 5m]
0.7 (BARREL FREEZE 32 SAM)
High pressure control
–
Air handling equipment
Turbo fan × 1
Fan type & Q’ty
Motor
W
Starting method
Air flow (Standard)
CMM
Fresh air intake
Air filter, Q’ty
Shock & vibration absorber
Electric heater
Operation control
Operation switch
Safety equipment
Installation data
Refrigerant piping size
25 × 1
55 × 1
Line starting
Line starting
Hi:16 Lo:11
56
Available
–
Long life filter × 1 (washable)
–
Rubber sleeve (for fan motor)
Rubber mount (for compressor)
–
20 (Cank case heater)
Wireless remote control switch
– (Indoor unit side)
W
Room temperature control
Propeller fan × 1
Thermostat by electronics
–
Internal thermostat for fan motor.
Frost protection thermostat.
Internal thermostat for fan motor.
Thermostat for discharge temperature.
mm
(in)
Liquid line: φ9.52 (3/8″) Gas line: φ15.88 (5/8″)
Connecting method
Drain hose
Flare piping
(Connectable with VP25)
Insulation for piping
Accessories
–
Necessary (both Liquid & Gas lines)
Mounting kit. Wireless remote controller.
Optional parts
Notes (1) The data are measured at the following conditions.
Item
Indoor air temperature
Operation
DB
WB
Cooling
27˚C
19˚C
Decorative Panel
Outdoor air temperature
DB
WB
35˚C
24˚C
Standards
ISO-T1, JIS B8616
(2) This packaged air conditioner is manufactured and tested in conformity with the following standard.
JIS B8616 “UNITARY AIR CONDITIONERS”
(3) The operation data indicate when the air conditioner is operated at 220V.
(4) Indicates the value at mild mode.
291
FDTN-C
Model
FDTN208CEN
FDTN208CEN
Model
Item
FDTN208C
Nominal cooling capacity(1)
ISO-T1
ISO-T3
W
ISO-T1
kW
A
%
kW
A
%
A
dB(A)
ISO-T3
Operation data(3)
Power source
Cooling input
Running current (Cooling)
Power factor (Cooling)
Cooling input
Running current (Cooling)
Power factor (Cooling)
Inrush current (L.R.A)
Noise level(4)
Exterior dimensions
Height × Width × Depth
Net weight
Refrigerant equipment
Compressor type & Q’ty
Motor
Starting method
Heat exchanger
Refrigerant control
Refrigerant
Quantity
Refrigerant oil
High pressure control
Air handling equipment
Fan type & Q’ty
Motor
Starting method
Air flow (Standard)
Fresh air intake
Air filter, Q’ty
Shock & vibration absorber
Electric heater
Operation control
Operation switch
Room temperature control
Safety equipment
FDC206CEN3
5000
4100
1 Phase, 220/240V, 50Hz
2.09/2.12
10.0/9.8
95/90
2.35/2.37
11.1/10.9
96/91
47
Hi:38 Lo:33
Unit 215 × 700 × 700
Panel 26 × 800 × 800
23 (Unit:18 Panel:5)
615 × 850 × 290 + 30
–
RC5520ENE1 × 1
kW
–
–
Louver fins & inner grooved tubing
Capillary tube
1.49
Line starting
Slitted fines & bare tubing
Capillary tube
kg
r
Holding charged
–
mm
kg
59
55
R22
W
CMM
W
0.9 [Pre-charged up to the piping length of 5m]
1.63 (SUNISO 3GS)
High pressure regulator valve
Turbo fan × 1
Propeller fan × 1
30 × 1
Line starting
Hi:14 Lo:10
Available
Long life filter × 1 (washable)
Rubber sleeve (for fan motor)
–
55 × 1
Line starting
42
–
–
Rubber mount (for compressor)
–
Wireless remote control switch
Thermostat by electronics
– (Indoor unit side)
–
Internal protector for compressor.
Internal thermostat for fan motor.
Internal Pressure relief valve for compressor.
Internal thermostat for fan motor.
Frost protection thermostat.
Installation data
Refrigerant piping size
Connecting method
Drain hose
Insulation for piping
Accessories
mm
(in)
Liquid line: φ6.35 (1/4″) Gas line: φ15.88 (5/8″)
Flare piping
(Connectable with VP25)
Necessary (both Liquid & Gas lines)
Mounting kit. Wireless remote controller.
Optional parts
–
Decorative Panel
Notes (1) The data are measured at the following conditions.
Item
Operation
Cooling
Indoor air temperature
Outdoor air temperature
WB
19˚C
DB
35˚C
WB
24˚C
ISO-T1, JIS B8616
29˚C
19˚C
46˚C
24˚C
ISO-T3, SASO
(2) This packaged air conditioner is manufactured and tested in conformity with the following standard.
JIS B8616 “UNITARY AIR CONDITIONERS”
(3) The operation data indicate when the air conditioner is operated at 220V and 240V respectively.
(4) Indicates the value at mild mode.
292
Standards
DB
27˚C
FDTN-C
FDTN208CEP
FDTN208CEP
Model
Item
FDTN208C
Nominal cooling capacity(1)
ISO-T1
ISO-T3
W
ISO-T1
kW
A
%
kW
A
%
A
dB(A)
ISO-T3
Operation data(3)
Power source
Cooling input
Running current (Cooling)
Power factor (Cooling)
Cooling input
Running current (Cooling)
Power factor (Cooling)
Inrush current (L.R.A)
Noise level(4)
Exterior dimensions
Height × Width × Depth
Net weight
Refrigerant equipment
Compressor type & Q’ty
Motor
Starting method
Heat exchanger
Refrigerant control
Refrigerant
Quantity
Refrigerant oil
High pressure control
Air handling equipment
Fan type & Q’ty
Motor
Starting method
Air flow (Standard)
Fresh air intake
Air filter, Q’ty
Shock & vibration absorber
Electric heater
Operation control
Operation switch
Room temperature control
Safety equipment
FDC206CEP3
5200
4500
1 Phase, 220V, 60Hz
2.08
9.7
97
2.34
11.0
97
50
Hi:38 Lo:33
Unit 215 × 700 × 700
Panel 26 × 800 × 800
23 (Unit:18 Panel:5)
615 × 850 × 290 + 30
–
RC5520EPE1 × 1
kW
–
–
Louver fins & inner grooved tubing
Capillary tube
1.31
Line starting
Slitted fines & bare tubing
Capillary tube
kg
r
Holding charged
–
mm
kg
59
55
R22
W
CMM
W
1.15 [Pre-charged up to the piping length of 5m]
1.63 (SUNISO 3GS)
High pressure regulator valve
Turbo fan × 1
Propeller fan × 1
30× 1
Line starting
Hi:14 Lo:10
Available
Long life filter × 1 (washable)
Rubber sleeve (for fan motor)
–
55 × 1
Line starting
44
–
–
Rubber mount (for compressor)
–
Wireless remote control switch
Thermostat by electronics
– (Indoor unit side)
–
Internal protector for compressor.
Internal thermostat for fan motor.
Internal Pressure relief valve for compressor.
Internal thermostat for fan motor.
Frost protection thermostat.
Installation data
Refrigerant piping size
Connecting method
Drain hose
Insulation for piping
Accessories
mm
(in)
FDTN-C
Model
Liquid line: φ6.35 (1/4″) Gas line: φ15.88 (5/8″)
Flare piping
(Connectable with VP25)
Necessary (both Liquid & Gas lines)
Mounting kit. Wireless remote controller.
Optional parts
–
Decorative Panel
Notes (1) The data are measured at the following conditions.
Item
Operation
Cooling
Indoor air temperature
Outdoor air temperature
Standards
DB
27˚C
WB
19˚C
DB
35˚C
WB
24˚C
ISO-T1, JIS B8616
29˚C
19˚C
46˚C
24˚C
ISO-T3, SASO
(2) This packaged air conditioner is manufactured and tested in conformity with the following standard.
JIS B8616 “UNITARY AIR CONDITIONERS”
(3) The operation data indicate when the air conditioner is operated at 220V.
(4) Indicates the value at mild mode.
293
FDTN-C
Model
FDTN258CEN
FDTN258CEN
Model
Item
FDTN258C
Nominal cooling capacity(1)
ISO-T1
ISO-T3
W
ISO-T1
kW
A
%
kW
A
%
A
dB(A)
ISO-T3
Operation data(3)
Power source
Cooling input
Running current (Cooling)
Power factor (Cooling)
Cooling input
Running current (Cooling)
Power factor (Cooling)
Inrush current (L.R.A)
Noise level(4)
Exterior dimensions
Height × Width × Depth
Net weight
Refrigerant equipment
Compressor type & Q’ty
Motor
Starting method
Heat exchanger
Refrigerant control
Refrigerant
Quantity
Refrigerant oil
High pressure control
Air handling equipment
Fan type & Q’ty
Motor
Starting method
Air flow (Standard)
Fresh air intake
Air filter, Q’ty
Shock & vibration absorber
Electric heater
Operation control
Operation switch
Room temperature control
Safety equipment
FDC256CEN3
5900
4900
1 Phase, 220/240V, 50Hz
2.59/2.63
12.6/13.2
93/83
2.77/2.81
13.4/14.0
94/84
64
Hi:39 Lo:35
Unit 260 × 840 × 840
Panel 30 × 950 × 950
30 (Unit:24 Panel:6)
615 × 850 × 290 + 30
–
RC5527ENE1 × 1
kW
–
–
Louver fins & inner grooved tubing
Capillary tube
1.87
Line starting
Slitted fines & bare tubing
Capillary tube
kg
r
Holding charged
–
mm
kg
59
56
R22
W
CMM
W
1.35 [Pre-charged up to the piping length of 5m]
1.63 (SUNISO 3GS)
High pressure regulator valve
Turbo fan × 1
Propeller fan × 1
25× 1
Line starting
Hi:16 Lo:11
Available
Long life filter × 1 (washable)
Rubber sleeve (for fan motor)
–
55 × 1
Line starting
42
–
–
Rubber mount (for compressor)
–
Wireless remote control switch
Thermostat by electronics
– (Indoor unit side)
–
Internal protector for compressor.
Internal thermostat for fan motor.
Internal Pressure relief valve for compressor.
Internal thermostat for fan motor.
Frost protection thermostat.
Installation data
Refrigerant piping size
Connecting method
Drain hose
Insulation for piping
Accessories
mm
(in)
Liquid line: φ9.52 (3/8″) Gas line: φ15.88 (5/8″)
Flare piping
(Connectable with VP25)
Necessary (both Liquid & Gas lines)
Mounting kit. Wireless remote controller.
Optional parts
–
Decorative Panel
Notes (1) The data are measured at the following conditions.
Item
Operation
Cooling
Indoor air temperature
Outdoor air temperature
WB
19˚C
DB
35˚C
WB
24˚C
ISO-T1, JIS B8616
29˚C
19˚C
46˚C
24˚C
ISO-T3, SASO
(2) This packaged air conditioner is manufactured and tested in conformity with the following standard.
JIS B8616 “UNITARY AIR CONDITIONERS”
(3) The operation data indicate when the air conditioner is operated at 220V and 240V respectively.
(4) Indicates the value at mild mode.
294
Standards
DB
27˚C
FDTN-C
FDTN258CEP
FDTN258CEP
Model
Item
FDTN258C
Nominal cooling capacity(1)
ISO-T1
ISO-T3
W
ISO-T1
kW
A
%
kW
A
%
A
dB(A)
ISO-T3
Operation data(3)
Power source
Cooling input
Running current (Cooling)
Power factor (Cooling)
Cooling input
Running current (Cooling)
Power factor (Cooling)
Inrush current (L.R.A)
Noise level(4)
Exterior dimensions
Height × Width × Depth
Net weight
Refrigerant equipment
Compressor type & Q’ty
Motor
Starting method
Heat exchanger
Refrigerant control
Refrigerant
Quantity
Refrigerant oil
High pressure control
Air handling equipment
Fan type & Q’ty
Motor
Starting method
Air flow (Standard)
Fresh air intake
Air filter, Q’ty
Shock & vibration absorber
Electric heater
Operation control
Operation switch
Room temperature control
Safety equipment
FDC256CEP3
6200
5200
1 Phase, 220V, 60Hz
2.68
12.4
98
3.06
14.4
97
66
Hi:39 Lo:35
Unit 260 × 840 × 840
Panel 30 × 950 × 950
30 (Unit:24 Panel:6)
615 × 850 × 290 + 30
–
RC5528EPE1 × 1
kW
–
–
Louver fins & inner grooved tubing
Capillary tube
1.68
Line starting
Slitted fines & bare tubing
Capillary tube
kg
r
Holding charged
–
mm
kg
59
56
R22
W
CMM
W
1.35 [Pre-charged up to the piping length of 5m]
1.63 (SUNISO 3GS)
High pressure regulator valve
Turbo fan × 1
Propeller fan × 1
25 × 1
Line starting
Hi:16 Lo:11
Available
Long life filter × 1 (washable)
Rubber sleeve (for fan motor)
–
55 × 1
Line starting
44
–
–
Rubber mount (for compressor)
–
Wireless remote control switch
Thermostat by electronics
– (Indoor unit side)
–
Internal protector for compressor.
Internal thermostat for fan motor.
Internal Pressure relief valve for compressor.
Internal thermostat for fan motor.
Frost protection thermostat.
Installation data
Refrigerant piping size
Connecting method
Drain hose
Insulation for piping
Accessories
mm
(in)
FDTN-C
Model
Liquid line: φ9.52 (3/8″) Gas line: φ15.88 (5/8″)
Flare piping
(Connectable with VP25)
Necessary (both Liquid & Gas lines)
Mounting kit. Wireless remote controller.
Optional parts
–
Decorative Panel
Notes (1) The data are measured at the following conditions.
Item
Operation
Cooling
Indoor air temperature
Outdoor air temperature
Standards
DB
27˚C
WB
19˚C
DB
35˚C
WB
24˚C
ISO-T1, JIS B8616
29˚C
19˚C
46˚C
24˚C
ISO-T3, SASO
(2) This packaged air conditioner is manufactured and tested in conformity with the following standard.
JIS B8616 “UNITARY AIR CONDITIONERS”
(3) The operation data indicate when the air conditioner is operated at 220V.
(4) Indicates the value at mild mode.
295
FDTN-C
Model
FDTN308CEN
FDTN308CEN
Model
Item
FDTN308C
Nominal cooling capacity(1)
ISO-T1
ISO-T3
W
ISO-T1
kW
A
%
kW
A
%
A
dB(A)
ISO-T3
Operation data(3)
Power source
Cooling input
Running current (Cooling)
Power factor (Cooling)
Cooling input
Running current (Cooling)
Power factor (Cooling)
Inrush current (L.R.A)
Noise level(4)
Exterior dimensions
Height × Width × Depth
Net weight
Refrigerant equipment
Compressor type & Q’ty
Motor
Starting method
Heat exchanger
Refrigerant control
Refrigerant
Quantity
Refrigerant oil
High pressure control
Air handling equipment
Fan type & Q’ty
Motor
Starting method
Air flow (Standard)
Fresh air intake
Air filter, Q’ty
Shock & vibration absorber
Electric heater
Operation control
Operation switch
Room temperature control
Safety equipment
FDC306CEN3
7100
5700
1 Phase, 220/240V, 50Hz
3.07/3.11
15.6/16.3
89/79
3.26/3.30
16.6/17.3
89/79
89
Hi:41 Lo:35
Unit 260 × 840 × 840
Panel 30 × 950 × 950
30 (Unit:24 Panel:6)
844 × 950 × 340
–
RC5532ENE1 × 1
kW
–
–
Louver fins & inner grooved tubing
Capillary tube
2.24
Line starting
Slitted fines & bare tubing
Capillary tube
kg
r
Holding charged
–
mm
kg
56
67
R22
W
CMM
W
1.3 [Pre-charged up to the piping length of 5m]
1.63 (SUNISO 3GS)
High pressure regulator valve
Turbo fan × 1
Propeller fan × 1
30× 1
Line starting
Hi:17 Lo:12
Available
Long life filter × 1 (washable)
Rubber sleeve (for fan motor)
–
60 × 1
Line starting
54
–
–
Rubber mount (for compressor)
–
Wireless remote control switch
Thermostat by electronics
– (Indoor unit side)
–
Internal protector for compressor.
Internal thermostat for fan motor.
Internal Pressure relief valve for compressor.
Internal thermostat for fan motor.
Frost protection thermostat.
Installation data
Refrigerant piping size
Connecting method
Drain hose
Insulation for piping
Accessories
mm
(in)
Liquid line: φ9.52 (3/8″) Gas line: φ15.88 (5/8″)
Flare piping
(Connectable with VP25)
Necessary (both Liquid & Gas lines)
Mounting kit. Wireless remote controller.
Optional parts
–
Decorative Panel
Notes (1) The data are measured at the following conditions.
Item
Operation
Cooling
Indoor air temperature
Outdoor air temperature
WB
19˚C
DB
35˚C
WB
24˚C
ISO-T1, JIS B8616
29˚C
19˚C
46˚C
24˚C
ISO-T3, SASO
(2) This packaged air conditioner is manufactured and tested in conformity with the following standard.
JIS B8616 “UNITARY AIR CONDITIONERS”
(3) The operation data indicate when the air conditioner is operated at 220V and 240V respectively.
(4) Indicates the value at mild mode.
296
Standards
DB
27˚C
FDTN-C
FDTN308CEP
FDTN308CEP
Model
Item
FDTN308C
Nominal cooling capacity(1)
ISO-T1
ISO-T3
W
ISO-T1
kW
A
%
kW
A
%
A
dB(A)
ISO-T3
Operation data(3)
Power source
Cooling input
Running current (Cooling)
Power factor (Cooling)
Cooling input
Running current (Cooling)
Power factor (Cooling)
Inrush current (L.R.A)
Noise level(4)
Exterior dimensions
Height × Width × Depth
Net weight
Refrigerant equipment
Compressor type & Q’ty
Motor
Starting method
Heat exchanger
Refrigerant control
Refrigerant
Quantity
Refrigerant oil
High pressure control
Air handling equipment
Fan type & Q’ty
Motor
Starting method
Air flow (Standard)
Fresh air intake
Air filter, Q’ty
Shock & vibration absorber
Electric heater
Operation control
Operation switch
Room temperature control
Safety equipment
FDC306CEP3
7100
5700
1 Phase, 220V, 60Hz
3.03
14.1
98
3.26
15.2
97
78
Hi:41 Lo:35
Unit 260 × 840 × 840
Panel 30 × 950 × 950
30 (Unit:24 Panel:6)
844 × 950 × 340
–
RC5533EPE1 × 1
kW
–
–
Louver fins & inner grooved tubing
Capillary tube
1.87
Line starting
Slitted fines & bare tubing
Capillary tube
kg
r
Holding charged
–
mm
kg
59
67
R22
W
CMM
W
1.3 [Pre-charged up to the piping length of 5m]
1.63 (SUNISO 3GS)
High pressure regulator valve
Turbo fan × 1
Propeller fan × 1
30 × 1
Line starting
Hi:17 Lo:12
Available
Long life filter × 1 (washable)
Rubber sleeve (for fan motor)
–
60 × 1
Line starting
56
–
–
Rubber mount (for compressor)
–
Wireless remote control switch
Thermostat by electronics
– (Indoor unit side)
–
Internal protector for compressor.
Internal thermostat for fan motor.
Internal Pressure relief valve for compressor.
Internal thermostat for fan motor.
Frost protection thermostat.
Installation data
Refrigerant piping size
Connecting method
Drain hose
Insulation for piping
Accessories
mm
(in)
FDTN-C
Model
Liquid line: φ9.52 (3/8″) Gas line: φ15.88 (5/8″)
Flare piping
(Connectable with VP25)
Necessary (both Liquid & Gas lines)
Mounting kit. Wireless remote controller.
Optional parts
–
Decorative Panel
Notes (1) The data are measured at the following conditions.
Item
Operation
Cooling
Indoor air temperature
Outdoor air temperature
Standards
DB
27˚C
WB
19˚C
DB
35˚C
WB
24˚C
ISO-T1, JIS B8616
29˚C
19˚C
46˚C
24˚C
ISO-T3, SASO
(2) This packaged air conditioner is manufactured and tested in conformity with the following standard.
JIS B8616 “UNITARY AIR CONDITIONERS”
(3) The operation data indicate when the air conditioner is operated at 220V.
(4) Indicates the value at mild mode.
297
FDTN-C
Model
FDTN308CES
FDTN308CES
Model
Item
FDTN308C
Nominal cooling capacity(1)
ISO-T1
ISO-T3
W
ISO-T1
kW
A
%
kW
A
%
A
dB(A)
ISO-T3
Operation data(3)
Power source
Cooling input
Running current (Cooling)
Power factor (Cooling)
Cooling input
Running current (Cooling)
Power factor (Cooling)
Inrush current (L.R.A)
Noise level(4)
Exterior dimensions
Height × Width × Depth
Net weight
Refrigerant equipment
Compressor type & Q’ty
Motor
Starting method
Heat exchanger
Refrigerant control
Refrigerant
Quantity
Refrigerant oil
High pressure control
Air handling equipment
Fan type & Q’ty
Motor
Starting method
Air flow (Standard)
Fresh air intake
Air filter, Q’ty
Shock & vibration absorber
Electric heater
Operation control
Operation switch
Room temperature control
Safety equipment
FDC306CES3
7100/7700
5700/6000
3 Phase, 380-415V 50Hz or 380V 50Hz/415V 50Hz, 380V 60Hz
2.83/2.84/3.35
5.3/5.3/6.0
81/75/85
3.02/3.03/3.58
5.7/5.7/6.5
80/74/84
43
Hi:41 Lo:35
59
Unit 260 × 840 × 840
844 × 950 × 340
Panel 30 × 950 × 950
30 (Unit:24 Panel:6)
67
mm
kg
–
RC5538ESE1 × 1
kW
–
–
Louver fins & inner grooved tubing
Capillary tube
2.24
Line starting
Slitted fines & bare tubing
Capillary tube
kg
r
Holding charged
–
R22
W
CMM
W
1.3 [Pre-charged up to the piping length of 5m]
1.63 (SUNISO 3GS)
High pressure regulator valve
Turbo fan × 1
Propeller fan × 1
30 × 1
Line starting
Hi:17 Lo:12
Available
Long life filter × 1 (washable)
Rubber sleeve (for fan motor)
–
60 × 1
Line starting
54/56
–
–
Rubber mount (for compressor)
–
Wireless remote control switch
Thermostat by electronics
- (Indoor unit side)
–
Internal protector for compressor.
Internal thermostat for fan motor.
Internal Pressure relief valve for compressor.
Internal thermostat for fan motor.
Frost protection thermostat.
Installation data
Refrigerant piping size
Connecting method
Drain hose
Insulation for piping
Accessories
mm
(in)
Liquid line: φ9.52 (3/8″) Gas line: φ15.88 (5/8″)
Flare piping
(Connectable with VP25)
Necessary (both Liquid & Gas lines)
Mounting kit. Wireless remote controller.
Optional parts
–
Decorative Panel
Notes (1) The data are measured at the following conditions.
Item
Operation
Cooling
Indoor air temperature
Outdoor air temperature
DB
WB
DB
WB
27˚C
29˚C
19˚C
19˚C
35˚C
46˚C
24˚C
24˚C
(2) This packaged air conditioner is manufactured and tested in conformity with the following standard.
JIS B8616 “UNITARY AIR CONDITIONERS”
(3) The operation data indicate when the air conditioner is operated at 380/415V 50Hz and 380V 60Hz respectively.
(4) Indicates the value at mild mode.
298
Standards
ISO-T1, JIS B8616
ISO-T3, SASO
FDTN-C
Model
FDTN408CES
FDTN408CES
Model
Item
FDTN408C
Nominal cooling capacity(1)
ISO-T1
ISO-T3
W
ISO-T1
kW
A
%
kW
A
%
A
dB(A)
ISO-T3
Operation data(3)
Power source
Cooling input
Running current (Cooling)
Power factor (Cooling)
Cooling input
Running current (Cooling)
Power factor (Cooling)
Inrush current (L.R.A)
Noise level(4)
Exterior dimensions
Height × Width × Depth
Net weight
Refrigerant equipment
Compressor type & Q’ty
Motor
Starting method
Heat exchanger
Refrigerant control
Refrigerant
Quantity
Refrigerant oil
High pressure control
Air handling equipment
Fan type & Q’ty
Motor
Starting method
Air flow (Standard)
Fresh air intake
Air filter, Q’ty
Shock & vibration absorber
Electric heater
Operation control
Operation switch
Room temperature control
Safety equipment
FDC406CES3
10200/11300
8900/9900
3 Phase, 380-415V 50Hz or 380V 50Hz/415V 50Hz, 380V 60Hz
3.78/3.78/4.65
7.5/7.5/8.8
77/70/80
4.12/4.12/5.15
8.1/8.1/9.5
77/71/82
45
Hi:48 Lo:40
57
Unit 320 × 840 × 840
1250 × 950 × 340
Panel 30 × 950 × 950
34 (Unit:28 Panel:6)
80
mm
kg
–
RC5547ESE1 × 1
kW
–
–
Louver fins & inner grooved tubing
Capillary tube
2.61
Line starting
Slitted fines & bare tubing
Capillary tube
kg
r
Holding charged
–
R22
W
CMM
W
1.55 [Pre-charged up to the piping length of 5m]
1.63 (SUNISO 3GS)
High pressure regulator valve
Turbo fan × 1
Propeller fan × 2
80 × 1
Line starting
Hi:26 Lo:19
Available
Long life filter × 1 (washable)
Rubber sleeve (for fan motor)
–
60 × 2
Line starting
100/110
–
–
Rubber mount (for compressor)
–
Wireless remote control switch
Thermostat by electronics
– (Indoor unit side)
–
Internal protector for compressor.
Internal thermostat for fan motor.
Internal Pressure relief valve for compressor.
Internal thermostat for fan motor.
Frost protection thermostat.
Installation data
Refrigerant piping size
Connecting method
Drain hose
Insulation for piping
Accessories
mm
(in)
Liquid line: φ9.52 (3/8″) Gas line: φ19.05 (3/4″)
Flare piping
(Connectable with VP25)
Necessary (both Liquid & Gas lines)
Mounting kit. Wireless remote controller.
Optional parts
–
Decorative Panel
Notes (1) The data are measured at the following conditions.
Item
Operation
Cooling
Indoor air temperature
Outdoor air temperature
DB
WB
DB
WB
27˚C
29˚C
19˚C
19˚C
35˚C
46˚C
24˚C
24˚C
Standards
ISO-T1, JIS B8616
ISO-T3, SASO
(2) This packaged air conditioner is manufactured and tested in conformity with the following standard.
JIS B8616 “UNITARY AIR CONDITIONERS”
(3) The operation data indicate when the air conditioner is operated at 380/ 415V 50Hz and 380V 60Hz respectively.
(4) Indicates the value at mild mode.
299
FDTN-C
Model
FDTN508CES
FDTN508CES
Model
Item
FDTN508C
Nominal cooling capacity(1)
ISO-T1
ISO-T3
W
kW
A
%
kW
A
%
A
dB(A)
ISO-T3 ISO-T1
Operation data(3)
Power source
Cooling input
Running current (Cooling)
Power factor (Cooling)
Cooling input
Running current (Cooling)
Power factor (Cooling)
Inrush current (L.R.A)
Noise level(4)
Exterior dimensions
Height × Width × Depth
Net weight
Refrigerant equipment
Compressor type & Q’ty
Motor
Starting method
Heat exchanger
Refrigerant control
Refrigerant
Quantity
Refrigerant oil
High pressure control
Air handling equipment
Fan type & Q’ty
Motor
Starting method
Air flow (Standard)
Fresh air intake
Air filter, Q’ty
Shock & vibration absorber
Electric heater
Operation control
Operation switch
Room temperature control
Safety equipment
FDC506CES3
12500/14000
10600/11900
3 Phase, 380-415V 50Hz or 380V 50Hz/415V 50Hz, 380V 60Hz
4.87/4.87/5.83
10.0/10.0/11.0
74/68/81
5.42/5.42/6.43
11.3/11.3/12.0
73/67/81
68
Hi:49 Lo:43
59
Unit 320 × 840 × 840
1250 × 950 × 340
Panel 30 × 950 × 950
36 (Unit:30 Panel:6)
85
mm
kg
–
RC5563ESE2 × 1
kW
–
–
Louver fins & inner grooved tubing
Capillary tube
3.73
Line starting
Slitted fines & bare tubing
Capillary tube
kg
r
Holding charged
–
R22
W
CMM
W
1.85 [Pre-charged up to the piping length of 5m]
2.07 (SUNISO 3GS)
High pressure regulator valve
Turbo fan × 1
Propeller fan × 2
130 × 1
Line starting
Hi:28 Lo:20
Available
Long life filter × 1 (washable)
Rubber sleeve (for fan motor)
–
60 × 2
Line starting
100/110
–
–
Rubber mount (for compressor)
40 (Crank case heater)
Wireless remote control switch
Thermostat by electronics
– (Indoor unit side)
–
Internal protector for compressor.
Internal thermostat for fan motor.
Internal Pressure relief valve for compressor.
Internal thermostat for fan motor.
Frost protection thermostat.
Installation data
Refrigerant piping size
Connecting method
Drain hose
Insulation for piping
Accessories
mm
(in)
Liquid line: φ9.52 (3/8″) Gas line: φ19.05 (3/4″)
Flare piping
(Connectable with VP25)
Necessary (both Liquid & Gas lines)
Mounting kit. Wireless remote controller.
Optional parts
–
Decorative Panel
Notes (1) The data are measured at the following conditions.
Item
Operation
Cooling
Indoor air temperature
Outdoor air temperature
WB
19˚C
DB
35˚C
WB
24˚C
ISO-T1, JIS B8616
29˚C
19˚C
46˚C
24˚C
ISO-T3, SASO
(2) This packaged air conditioner is manufactured and tested in conformity with the following standard.
JIS B8616 “UNITARY AIR CONDITIONERS”
(3) The operation data indicate when the air conditioner is operated at 380/415V 50Hz and 380V 60Hz respectively.
(4) Indicates the value at mild mode.
300
Standards
DB
27˚C
FDTN-C
Model
FDTN508CEM
FDTN508CEM
Model
Item
FDTN508C
ISO-T1
ISO-T3
W
ISO-T1
kW
A
%
kW
A
%
A
dB(A)
ISO-T3
Operation data(3)
Power source
Cooling input
Running current (Cooling)
Power factor (Cooling)
Cooling input
Running current (Cooling)
Power factor (Cooling)
Inrush current (L.R.A)
Noise level(4)
Exterior dimensions
Height × Width × Depth
Net weight
Refrigerant equipment
Compressor type & Q’ty
Motor
Starting method
Heat exchanger
Refrigerant control
Refrigerant
Quantity
Refrigerant oil
High pressure control
Air handling equipment
Fan type & Q’ty
Motor
Starting method
Air flow (Standard)
Fresh air intake
Air filter, Q’ty
Shock & vibration absorber
Electric heater
Operation control
Operation switch
Room temperature control
Safety equipment
FDC506CEM3
12500/14000
11900
3 Phase, 230V 50Hz, 220V 60Hz
4.62/5.56
15.0/16.4
77/89
6.08
17.7
90
108
Hi:49 Lo:43
59
Unit 320 × 840 × 840
1250 × 950 × 340
Panel 30 × 950 × 950
36 (Unit:30 Panel:6)
85
mm
kg
–
RC5559EME2 × 1
kW
–
–
Louver fins & inner grooved tubing
Capillary tube
3.36
Line starting
Slitted fines & bare tubing
Capillary tube
kg
r
Holding charged
–
R22
W
CMM
W
1.8 [Pre-charged up to the piping length of 5m]
2.07 (SUNISO 3GS)
High pressure regulator valve
Turbo fan × 1
Propeller fan × 2
130 × 1
Line starting
Hi:28 Lo:20
Available
Long life filter × 1 (washable)
Rubber sleeve (for fan motor)
–
60 × 2
Line starting
100/110
–
–
Rubber mount (for compressor)
40 (Crank case heater)
Wireless remote control switch
Thermostat by electronics
– (Indoor unit side)
–
Internal protector for compressor.
Internal thermostat for fan motor.
Internal Pressure relief valve for compressor.
Internal thermostat for fan motor.
Frost protection thermostat.
Installation data
Refrigerant piping size
Connecting method
Drain hose
Insulation for piping
Accessories
mm
(in)
FDTN-C
Nominal cooling capacity(1)
Liquid line: φ9.52 (3/8″) Gas line: φ19.05 (3/4″)
Flare piping
(Connectable with VP25)
Necessary (both Liquid & Gas lines)
Mounting kit. Wireless remote controller.
Optional parts
–
Decorative Panel
Notes (1) The data are measured at the following conditions.
Item
Operation
Cooling
Indoor air temperature
Outdoor air temperature
Standards
DB
27˚C
WB
19˚C
DB
35˚C
WB
24˚C
ISO-T1, JIS B8616
29˚C
19˚C
46˚C
24˚C
ISO-T3, SASO
(2) This packaged air conditioner is manufactured and tested in conformity with the following standard.
JIS B8616 “UNITARY AIR CONDITIONERS”
(3) The operation data indicate when the air conditioner is operated at 230V,50Hz and 220V,60Hz respectively.
(4) Indicates the value at mild mode.
301
FDTN-C
(b) Wired remote controller type
Model FDT208CEN-S
FDT208CEN-S
Model
Item
FDT208
Nominal cooling capacity(1)
FDC208CEN3
5000
W
Power source
Operation data(3)
Cooling input
1 Phase, 220/240V, 50Hz
kW
1.78/1.87
Running current (Cooling)
A
8.3/8.1
Power factor (Cooling)
%
97/96
Inrush current (L.R.A)
A
Noise level(4)
Exterior dimensions
Height × Width × Depth
dB(A)
Net weight
Refrigerant equipment
Compressor type & Q’ty
kg
mm
44
Hi:38 Lo:33
Unit 215 × 700 × 700
Panel 26 × 800 × 800
52
690 × 880 × 290
23 (Unit:18 Panel:5)
49
–
RM5523GNE4 × 1
–
1.6
–
Line starting
Heat exchanger
Louver fins & inner grooved tubing
Slitted fines & bare tubing
Refrigerant control
Capillary tube
Motor
kW
Starting method
Capillary tube
Refrigerant
R22
Quantity
Refrigerant oil
kg
Holding charged
r
–
0.9 [Pre-charged up to the piping length of 0m]
0.7 (BARREL FREEZE 32 SAM)
High pressure control
–
Air handling equipment
Turbo fan × 1
Fan type & Q’ty
Motor
W
Starting method
Air flow (Standard)
CMM
Fresh air intake
Air filter, Q’ty
Shock & vibration absorber
Electric heater
Operation control
Operation switch
W
Room temperature control
Safety equipment
Installation data
Refrigerant piping size
Propeller fan × 1
30 × 1
55 × 1
Line starting
Line starting
Hi:14 Lo:10
56
Available
–
Long life filter × 1 (washable)
–
Rubber sleeve (for fan motor)
Rubber mount (for compressor)
–
Wired remote control switch
(Optional:RCD-C-S-E)
20 (Crank case heater)
–
Internal thermostat for fan motor.
Frost protection thermostat.
Internal thermostat for fan motor.
Thermostat for discharge temperature.
mm
(in)
Liquid line: φ6.35 (1/4″) Gas line: φ15.88 (5/8″)
Connecting method
Drain hose
– (Indoor unit side)
Thermostat by electronics
Flare piping
(Connectable with VP25)
Insulation for piping
Accessories
–
Necessary (both Liquid & Gas lines)
Mounting kit.
Optional parts
Notes (1) The data are measured at the following conditions.
Item
Indoor air temperature
Operation
DB
WB
Cooling
27˚C
19˚C
Decorative Panel
Outdoor air temperature
DB
WB
35˚C
24˚C
(2) This packaged air conditioner is manufactured and tested in conformity with the following standard.
JIS B8616 “UNITARY AIR CONDITIONERS”
(3) The operation data indicate when the air conditioner is operated at 220V and 240V respectively.
(4) Indicates the value at mild mode.
302
Standards
ISO-T1, JIS B8616
FDTN-C
Model
FDT258CEN-S
FDT258CEN-S
Model
Item
FDT258
Nominal cooling capacity(1)
FDC258CEN3
5700
W
Operation data(3)
Power source
Cooling input
1 Phase, 220/240V, 50Hz
kW
2.05/2.16
Running current (Cooling)
A
9.4/9.4
Power factor (Cooling)
%
99/96
Inrush current (L.R.A)
A
Noise level(4)
Exterior dimensions
Height × Width × Depth
dB(A)
Net weight
Refrigerant equipment
Compressor type & Q’ty
kg
mm
51
Hi:39 Lo:35
Unit 260 × 840 × 840
Panel 30 × 950 × 950
52
845 × 880 × 340
30 (Unit:24 Panel:6)
55
–
RM5526GNE4 × 1
–
1.9
–
Line starting
Heat exchanger
Louver fins & inner grooved tubing
Slitted fines & bare tubing
Refrigerant control
Capillary tube
Motor
kW
Starting method
Capillary tube
Refrigerant
R22
Quantity
Refrigerant oil
kg
Holding charged
r
–
1.05 [Pre-charged up to the piping length of 5m]
0.7 (BARREL FREEZE 32 SAM)
High pressure control
–
Air handling equipment
Turbo fan × 1
Fan type & Q’ty
Motor
W
Starting method
Air flow (Standard)
CMM
Fresh air intake
Air filter, Q’ty
Shock & vibration absorber
Electric heater
Operation control
Operation switch
W
Room temperature control
Safety equipment(4)
Installation data
Refrigerant piping size
Propeller fan × 1
25 × 1
55 × 1
Line starting
Line starting
Hi:16 Lo:11
56
Available
–
Long life filter × 1 (washable)
–
Rubber sleeve (for fan motor)
Rubber mount (for compressor)
–
Wired remote control switch
(Optional:RCD-C-S-E)
20 (Cank case heater)
–
Internal thermostat for fan motor.
Frost protection thermostat.
Internal thermostat for fan motor.
Thermostat for discharge temperature.
mm
(in)
Liquid line: φ9.52 (3/8″) Gas line: φ15.88 (5/8″)
Connecting method
Drain hose
– (Indoor unit side)
Thermostat by electronics
Flare piping
(Connectable with VP25)
Insulation for piping
Accessories
–
Necessary (both Liquid & Gas lines)
Mounting kit.
Optional parts
Notes (1) The data are measured at the following conditions.
Item
Indoor air temperature
Operation
DB
WB
Cooling
27˚C
19˚C
Decorative Panel
Outdoor air temperature
DB
WB
35˚C
24˚C
Standards
ISO-T1, JIS B8616
(2) This packaged air conditioner is manufactured and tested in conformity with the following standard.
JIS B8616 “UNITARY AIR CONDITIONERS”
(3) The operation data indicate when the air conditioner is operated at 220V and 240V respectively.
(4) Indicates the value at mild mode.
303
FDTN-C
Model
FDT308CEN
FDT308CEN
Model
Item
FDT308
Nominal cooling capacity(1)
ISO-T1
ISO-T3
W
ISO-T1
kW
A
%
kW
A
%
A
dB(A)
ISO-T3
Operation data(3)
Power source
Cooling input
Running current (Cooling)
Power factor (Cooling)
Cooling input
Running current (Cooling)
Power factor (Cooling)
Inrush current (L.R.A)
Noise level(4)
Exterior dimensions
Height × Width × Depth
Net weight
Refrigerant equipment
Compressor type & Q’ty
Motor
Starting method
Heat exchanger
Refrigerant control
Refrigerant
Quantity
Refrigerant oil
High pressure control
Air handling equipment
Fan type & Q’ty
Motor
Starting method
Air flow (Standard)
Fresh air intake
Air filter, Q’ty
Shock & vibration absorber
Electric heater
Operation control
Operation switch
Room temperature control
Safety equipment
FDC306CEN3
7100
5700
1 Phase, 220/240V, 50Hz
3.07/3.11
15.6/16.3
89/79
3.26/3.30
16.6/17.3
89/79
89
Hi:41 Lo:35
Unit 260 × 840 × 840
Panel 30 × 950 × 950
30 (Unit:24 Panel:6)
844 × 950 × 340
–
RC5532ENE1 × 1
kW
–
–
Louver fins & inner grooved tubing
Capillary tube
2.24
Line starting
Slitted fines & bare tubing
Capillary tube
kg
r
Holding charged
–
mm
kg
56
67
R22
W
CMM
W
1.3 [Pre-charged up to the piping length of 5m]
1.63 (SUNISO 3GS)
High pressure regulator valve
Turbo fan × 1
Propeller fan × 1
30× 1
Line starting
Hi:17 Lo:12
Available
Long life filter × 1 (washable)
Rubber sleeve (for fan motor)
–
Wired remote control switch
(Optional:RCD-C-S-E)
Thermostat by electronics
60 × 1
Line starting
54
–
–
Rubber mount (for compressor)
–
Internal thermostat for fan motor.
Frost protection thermostat.
Installation data
Refrigerant piping size
Connecting method
Drain hose
Insulation for piping
Accessories
Optional parts
mm
(in)
– (Indoor unit side)
–
Internal protector for compressor.
Internal thermostat for fan motor.
Internal Pressure relief valve for compressor.
Liquid line: φ9.52 (3/8″) Gas line: φ15.88 (5/8″)
Flare piping
(Connectable with VP25)
Necessary (both Liquid & Gas lines)
Mounting kit.
Decorative Panel
–
Notes (1) The data are measured at the following conditions.
Item
Operation
Cooling
Indoor air temperature
Outdoor air temperature
WB
19˚C
DB
35˚C
WB
24˚C
ISO-T1, JIS B8616
29˚C
19˚C
46˚C
24˚C
ISO-T3, SASO
(2) This packaged air conditioner is manufactured and tested in conformity with the following standard.
JIS B8616 “UNITARY AIR CONDITIONERS”
(3) The operation data indicate when the air conditioner is operated at 220V and 240V respectively.
(4) Indicates the value at mild mode.
304
Standards
DB
27˚C
FDTN-C
Model
FDT308CES
FDT308CES
Model
Item
FDT308
ISO-T1
ISO-T3
W
ISO-T1
kW
A
%
kW
A
%
A
dB(A)
ISO-T3
Operation data(3)
Power source
Cooling input
Running current (Cooling)
Power factor (Cooling)
Cooling input
Running current (Cooling)
Power factor (Cooling)
Inrush current (L.R.A)
Noise level(4)
Exterior dimensions
Height × Width × Depth
Net weight
Refrigerant equipment
Compressor type & Q’ty
Motor
Starting method
Heat exchanger
Refrigerant control
Refrigerant
Quantity
Refrigerant oil
High pressure control
Air handling equipment
Fan type & Q’ty
Motor
Starting method
Air flow (Standard)
Fresh air intake
Air filter, Q’ty
Shock & vibration absorber
Electric heater
Operation control
Operation switch
Room temperature control
Safety equipment
FDC306CES3
7100/7700
5700/6000
3 Phase, 380-415V 50Hz or 380V 50Hz/415V 50Hz, 380V 60Hz
2.83/2.84/3.35
5.3/5.3/6.0
81/75/85
3.02/3.03/3.58
5.7/5.7/6.5
80/74/84
43
Hi:41 Lo:35
59
Unit 260 × 840 × 840
844 × 950 × 340
Panel 30 × 950 × 950
30 (Unit:24 Panel:6)
67
mm
kg
–
RC5538ESE1 × 1
kW
–
–
Louver fins & inner grooved tubing
Capillary tube
2.24
Line starting
Slitted fines & bare tubing
Capillary tube
kg
r
Holding charged
–
R22
W
CMM
W
1.3 [Pre-charged up to the piping length of 5m]
1.63 (SUNISO 3GS)
High pressure regulator valve
Turbo fan × 1
Propeller fan × 1
30 × 1
Line starting
Hi:17 Lo:12
Available
Long life filter × 1 (washable)
Rubber sleeve (for fan motor)
–
Wired remote control switch
(Optional:RCD-C-S-E)
Thermostat by electronics
60 × 1
Line starting
54/56
–
–
Rubber mount (for compressor)
–
Internal thermostat for fan motor.
Frost protection thermostat.
Installation data
Refrigerant piping size
Connecting method
Drain hose
Insulation for piping
Accessories
Optional parts
mm
(in)
- (Indoor unit side)
–
Internal protector for compressor.
Internal thermostat for fan motor.
Internal Pressure relief valve for compressor.
FDTN-C
Nominal cooling capacity(1)
Liquid line: φ9.52 (3/8″) Gas line: φ15.88 (5/8″)
Flare piping
(Connectable with VP25)
Necessary (both Liquid & Gas lines)
Mounting kit.
Decorative Panel
–
Notes (1) The data are measured at the following conditions.
Item
Operation
Cooling
Indoor air temperature
Outdoor air temperature
DB
WB
DB
WB
27˚C
29˚C
19˚C
19˚C
35˚C
46˚C
24˚C
24˚C
Standards
ISO-T1, JIS B8616
ISO-T3, SASO
(2) This packaged air conditioner is manufactured and tested in conformity with the following standard.
JIS B8616 “UNITARY AIR CONDITIONERS”
(3) The operation data indicate when the air conditioner is operated at 380/415V 50Hz and 380V 60Hz respectively.
(4) Indicates the value at mild mode.
305
FDTN-C
Model
FDT408CES
FDT408CES
Model
Item
FDT408
Nominal cooling capacity(1)
ISO-T1
ISO-T3
W
ISO-T1
kW
A
%
kW
A
%
A
dB(A)
ISO-T3
Operation data(3)
Power source
Cooling input
Running current (Cooling)
Power factor (Cooling)
Cooling input
Running current (Cooling)
Power factor (Cooling)
Inrush current (L.R.A)
Noise level(4)
Exterior dimensions
Height × Width × Depth
Net weight
Refrigerant equipment
Compressor type & Q’ty
Motor
Starting method
Heat exchanger
Refrigerant control
Refrigerant
Quantity
Refrigerant oil
High pressure control
Air handling equipment
Fan type & Q’ty
Motor
Starting method
Air flow (Standard)
Fresh air intake
Air filter, Q’ty
Shock & vibration absorber
Electric heater
Operation control
Operation switch
Room temperature control
Safety equipment
FDC406CES3
10200/11300
8900/9900
3 Phase, 380-415V 50Hz or 380V 50Hz/415V 50Hz, 380V 60Hz
3.78/3.78/4.65
7.5/7.5/8.8
77/70/80
4.12/4.12/5.15
8.1/8.1/9.5
77/71/82
45
Hi:48 Lo:40
57
Unit 320 × 840 × 840
1250 × 950 × 340
Panel 30 × 950 × 950
34 (Unit:28 Panel:6)
80
mm
kg
–
RC5547ESE1 × 1
kW
–
–
Louver fins & inner grooved tubing
Capillary tube
2.61
Line starting
Slitted fines & bare tubing
Capillary tube
kg
r
Holding charged
–
R22
W
CMM
W
1.55 [Pre-charged up to the piping length of 5m]
1.63 (SUNISO 3GS)
High pressure regulator valve
Turbo fan × 1
Propeller fan × 2
80 × 1
Line starting
Hi:26 Lo:19
Available
Long life filter × 1 (washable)
Rubber sleeve (for fan motor)
–
Wired remote control switch
(Optional:RCD-C-S-E)
Thermostat by electronics
60 × 2
Line starting
100/110
–
–
Rubber mount (for compressor)
–
Internal thermostat for fan motor.
Frost protection thermostat.
Installation data
Refrigerant piping size
Connecting method
Drain hose
Insulation for piping
Accessories
mm
(in)
– (Indoor unit side)
–
Internal protector for compressor.
Internal thermostat for fan motor.
Internal Pressure relief valve for compressor.
Liquid line: φ9.52 (3/8″) Gas line: φ19.05 (3/4″)
Flare piping
(Connectable with VP25)
Necessary (both Liquid & Gas lines)
Mounting kit.
Optional parts
–
Decorative Panel
Notes (1) The data are measured at the following conditions.
Item
Operation
Cooling
Indoor air temperature
Outdoor air temperature
DB
WB
DB
WB
27˚C
29˚C
19˚C
19˚C
35˚C
46˚C
24˚C
24˚C
(2) This packaged air conditioner is manufactured and tested in conformity with the following standard.
JIS B8616 “UNITARY AIR CONDITIONERS”
(3) The operation data indicate when the air conditioner is operated at 380/ 415V 50Hz and 380V 60Hz respectively.
(4) Indicates the value at mild mode.
306
Standards
ISO-T1, JIS B8616
ISO-T3, SASO
FDTN-C
Model
FDT508CES
FDT508CES
Model
Item
FDT508
ISO-T1
ISO-T3
W
kW
A
%
kW
A
%
A
dB(A)
ISO-T3 ISO-T1
Operation data(3)
Power source
Cooling input
Running current (Cooling)
Power factor (Cooling)
Cooling input
Running current (Cooling)
Power factor (Cooling)
Inrush current (L.R.A)
Noise level(4)
Exterior dimensions
Height × Width × Depth
Net weight
Refrigerant equipment
Compressor type & Q’ty
Motor
Starting method
Heat exchanger
Refrigerant control
Refrigerant
Quantity
Refrigerant oil
High pressure control
Air handling equipment
Fan type & Q’ty
Motor
Starting method
Air flow (Standard)
Fresh air intake
Air filter, Q’ty
Shock & vibration absorber
Electric heater
Operation control
Operation switch
Room temperature control
Safety equipment
FDC506CES3
12500/14000
10600/11900
3 Phase, 380-415V 50Hz or 380V 50Hz/415V 50Hz, 380V 60Hz
4.87/4.87/5.83
10.0/10.0/11.0
74/68/81
5.42/5.42/6.43
11.3/11.3/12.0
73/67/81
68
Hi:49 Lo:43
59
Unit 320 × 840 × 840
1250 × 950 × 340
Panel 30 × 950 × 950
36 (Unit:30 Panel:6)
85
mm
kg
–
RC5563ESE2 × 1
kW
–
–
Louver fins & inner grooved tubing
Capillary tube
3.73
Line starting
Slitted fines & bare tubing
Capillary tube
kg
r
Holding charged
–
R22
W
CMM
W
1.85 [Pre-charged up to the piping length of 5m]
2.07 (SUNISO 3GS)
High pressure regulator valve
Turbo fan × 1
Propeller fan × 2
130 × 1
Line starting
Hi:28 Lo:20
Available
Long life filter × 1 (washable)
Rubber sleeve (for fan motor)
–
Wired remote control switch
(Optional:RCD-C-S-E)
Thermostat by electronics
60 × 2
Line starting
100/110
–
–
Rubber mount (for compressor)
40 (Crank case heater)
Internal thermostat for fan motor.
Frost protection thermostat.
Installation data
Refrigerant piping size
Connecting method
Drain hose
Insulation for piping
Accessories
mm
(in)
– (Indoor unit side)
–
Internal protector for compressor.
Internal thermostat for fan motor.
Internal Pressure relief valve for compressor.
FDTN-C
Nominal cooling capacity(1)
Liquid line: φ9.52 (3/8″) Gas line: φ19.05 (3/4″)
Flare piping
(Connectable with VP25)
Necessary (both Liquid & Gas lines)
Mounting kit.
Optional parts
–
Decorative Panel
Notes (1) The data are measured at the following conditions.
Item
Operation
Cooling
Indoor air temperature
Outdoor air temperature
Standards
DB
27˚C
WB
19˚C
DB
35˚C
WB
24˚C
ISO-T1, JIS B8616
29˚C
19˚C
46˚C
24˚C
ISO-T3, SASO
(2) This packaged air conditioner is manufactured and tested in conformity with the following standard.
JIS B8616 “UNITARY AIR CONDITIONERS”
(3) The operation data indicate when the air conditioner is operated at 380/415V 50Hz and 380V 60Hz respectively.
(4) Indicates the value at mild mode.
307
FDTN-C
7.2.2
Range of usage & limitations
Models
Item
FDT(N)208, 258 (FDC208, 258 type)
FDT(N)208~508 (FDC206~506 type)
Indoor return air temperature
(Upper, lower limits)
Refer to the selection chart
Outdoor air temperature
(Upper, lower limits)
Indoor unit atmosphere (behind ceiling)
temperature and humidity
Refrigerant line (one way) length
Vertical height difference between
outdoor unit and indoor unit
Power source voltage
Dew point temperature 28˚C or less, relative humidity 80% or less
Max. 30m
Max. 20m (Outdoor unit is higher)
Max. 15m (Outdoor unit is lower)
Rating ± 10%
Voltage at starting
Min. 85% of rating
Frequency of ON-OFF cycle
Max. 10 times/h
ON and OFF interval
Min. 3 minutes
308
Max. 15m
FDTN-C
7.2.3
Exterior dimensions
(1) Indoor unit
Models FDTN208C
FDT208
Unit : mm
740 (Ceiling hole size)
Fresh air opening
for ducting
Decorative Panel
430
800
(Suspension bolts
pitch)
C
515
→
→
359
295
D
336
680 (Suspension bolts pitch)
Exhaust air opening
for ducting
570
B→
Indication board
(Only case of FDTN type)
Air outlet grille
264
300
700
VIEW A
295 ~ 325
→
215
26
141
99
Hole for wiring
A
700 or more
Liquid piping
φ6.35(1/4")
FDTN-C
Gas piping
φ15.88(5/8")
49
or more
VIEW B
Lug for Suspension bolts
Control box
Holes for
tapping screws
Holes for
tapping screws
VIEW C
37
120
100
1000
or more
110
Obstacle
90
1000
or more
90
87
50
4-φ4 140
70
35
4-φ4
Space for installation and service
80
161
Suspension bolts
(M10 or M8 × 4PCS.)
Air inlet grille
(Max. Drain up)
Drain hose(Accessories)
(Connectable with VP25)
304
VIEW D
309
FDTN-C
Models FDTN258C, 308C
FDT258, 308
Unit : mm
Decorative Panel
C
↑
Fresh air
opening for ducting
860~890 (Ceiling hole size)
950
780 (Suspension bolts pitch )
630
400
420
637
D→
422
675 (Suspension bolts pitch)
Exhaust air
opening for ducting
B→
Air inlet grille
267
Drain hose (Accessories)
(Connectable with VP25)
332
Indication boad
(Only case of FDTN type)
310
VIEW A
Air outlet grille
Liquid piping
φ9.52 (3/8")
840
Hole for wiring
260
700 or less
(Max. Drain up)
295~325
30
137
Control box
VIEW B
Holes for
tapping screws
6-φ4
Holes for
tapping screws
4-φ4
55
140
25
60
1000
or more
113
140
1000
Obstacle
or more
Hole
42
80
VIEW C
310
Hole
112
100
160
33
Space for installation and service
VIEW D
140
45 or more
95
210
FDTN-C
↑
A
Lug for
suspension bolts
187
Suspension bolts
(M10 or M8 ×4pcs.)
Gas piping
φ15.88(5/8")
FDTN-C
Models FDTN408C, 508C
FDT408, 508
Unit : mm
Decorative Panel
C
↑
Fresh air
opening for ducting
860~890 (Ceiling hole size)
950
780 (Suspension bolts pitch )
630
400
420
637
D→
422
675 (Suspension bolts pitch)
Exhaust air
opening for ducting
B→
Air inlet grille
267
Drain hose (Accessories)
(Connectable with VP25)
332
Indication boad
(Only case of FDTN type)
310
VIEW A
Air outlet grille
Liquid piping
φ9.52(3/8")
840
FDTN-C
700 or less
(Max. Drain up)
320
30
VIEW B
Holes for
tapping screws
6-φ4
Holes for
tapping screws
4-φ4
55
Space for installation and service
140
25
60
Obstacle
140
Hole
172
100
1000
or more
160
Hole
173
140
1000
93
102
137
Hole for wiring
295~325
Control box
or more
45 or more
270
95
↑
A
Lug for
suspension bolts
187
Suspension bolts
(M10 or M8 ×4pcs.)
Gas piping
φ19.05(3/4")
80
VIEW C
VIEW D
311
FDTN-C
(2) Remote controller
(a) Wireless remote controller
AUTO COOL DRY FAN HEAT
FAN HI LO
Unit: mm
FILTER
°C
ON AM
PM
TEMP
Indication board of indoor unit
ON/OFF
161.5
MODE
OFF AM
PM
RUN
20.5
60
Unit: mm
(b) Wired remote controller(Optional parts)
Wall
0.3mm2, 3cores (O.D.φ5.6)
Remote controller mounting dimensions
Wire
(Recessed)
120
LCD display
60
46
7
17
FDTN-C
47
120
89
83.5
For the passage
after wiring
Junction box
(Locally Purchased)
120
Remote controller outline
16
♦ Usable JIS box, JIS C 8336
⋅ Switch box for 1 piece (without cover)
(use of the mark hole as illustrated on the left)
⋅ Switch box for 2 pieces
(use of the mark hole as illustrated on the left)
(without cover)
(use of the mark hole as illustrated on the left)
(when installing the cover)
312
Note (1) Allowable length of remote controller
cable: 600 m
Allowable rang of wire thickness and length
Standard Within 0.3 mm2
0.5 mm2
0.75 mm2
1.25 mm2
2 mm2
× Within 100 m
× Within 200 m
× Within 300 m
× Within 400 m
× Within 600 m
FDTN-C
(3) Outdoor unit
Models FDC208CEN3, 208CEP3
Unit: mm
Liquid piping: φ6.35 (1/4⬙)
(Flare connecting)
40
53
40
Gas piping: φ15.88 (3/8⬙)
(Flare connecting)
95
Liquid piping: φ6.35 (1/4⬙)
(Flare connecting)
Terminal block
Gas piping: φ15.88 (3/8⬙)
(Flare connecting)
195
351
311
110
10
195
110
690
Opening for electric wiring
40
50
50
50
Opening for piping and
electric wiring
Opening for piping and
electric wiring
15
50
50
27
880
Electric wiring
Holes for anchor bolt
(M10 × 4 pcs.)
Opening for
electric wiring
150
50
55
50
260
335
15
15
FDTN-C
70
15
Opening for piping
and electric wiring
103
150
40
35
290
35
580
55
15
330
15
150
50
40
Holes for drain
(M20 × 3 pcs.)
Required space for maintenance and air flow
Minimum allowable space to the obstacles
Unit:mm
L3
L2
Installation
type
L4
Air
inlet
L1
Maintenance
space
1
2
3
L1
Open
Open
500
L2
300
5
Open
L3
100
150
100
L4
5
5
5
Mark
Air inlet
Air inlet
Notes
(1) Avoid the location where four sides are entirely surrounded by walls.
(2) Fix the unit by anchor bolts without fail. Restrict the protrusion length of anchor bolt to 15 mm and under.
(3) When strong wind blows against the unit, direct the discharge port at a right angle to the wind direction.
(4) Secure the space of 1 m and over at the top of unit.
(5) Make the height of obstruction wall in front of discharge port lower than the height of unit.
313
FDTN-C
Models FDC258CEN3, 258CEP3
Unit: mm
Liquid piping: ø9.52 (3/8")
(Flare connecting)
53
40
Gas piping: ø15.88 (5/8")
(Flare connecting)
40
95
Terminal block
Liquid piping: ø9.52 (3/8")
(Flare connecting)
110
195
50
50
10
195
460
110
845
Gas piping: ø15.88 (5/8")
(Flare connecting)
Opening for
electric wiring
Opening for
electric wiring
Opening for piping
and electric wiring
50
40
50
27
15
Opening for piping
and electric wiring
50
880
15
35
103
70
Opening for piping
and electric wiring
40
50
222
50
47
340
35
55
380
15
FDTN-C
Electric wiring
150
15
150
Holes for anchor bolt
(M10 × 4 pcs.)
580
150
15
50
15
50
Holes for drain
(ø9.52 × 3pcs.)
310
VIEW A
Required space for maintenance and air flow
Minimum allowable space to the obstacles
Unit:mm
L3
L2
Installation
type
L4
Air
inlet
L1
Maintenance
space
1
2
3
L1
Open
Open
500
L2
300
5
Open
L3
100
150
100
L
5
5
5
Air inlet
Air outlet
Mark
4
Notes
(1) Avoid the location where four sides are entirely surrounded by walls.
(2) Fix the unit by anchor bolts without fail. Restrict the protrusion length of anchor bolt to 15 mm and under.
(3) When strong wind blows against the unit, direct the discharge port at a right angle to the wind direction.
(4) Secure the space of 1 m and over at the top of unit.
(5) Make the height of obstruction wall in front of discharge port lower than the height of unit.
314
FDTN-C
Models FDC206CEN3, 206CEP3, 256CEN3, 256CEP3
Unit: mm
Anchor bolts
(M10×4pcs.)
19
30
307
25
30
19
170
510
345
170
33
850
30
290
Terminal block
615
65 105
Operating for
electric wiring
Gas piping: ø15.88(3/8'')
(Flare connecting)
25
128
Liquid piping: 206 type: ø6.35(1/4'') 256 type: ø9.52(3/8'')
(Flare connecting)
206 type: 125
256 type: 145
15
87
Required space for maintenance and air flow
Minimum allowable space to the obstacles
Unit:mm
Air
inlet
L3
L2
Air
inlet
Installation
type
500 mm
Obstacles
Air
Maintenance
outlet space
Mark
1
2
L1
Open
100
L2
100
Open
L3
100
500
L1
Notes
(1) Fix the unit with anchor bolts.
(2) Strong wind must not be directed to the air outlet.
(3) Free space over the unit must be larger than 1 m.
(4) The unit should not be surrounded by obstructions in all direction.
At least one direction around the unit must be free.
315
FDTN-C
Models FDC306CEN3, 306CEP3, 306CES3
580
380
Unit: mm
Required space for maintenance and air flow
Unit:mm
Air
inlet
L3
L2
Air
inlet
500 mm
Installation
type
Obstacles
Air
Maintenance
outlet space
L1
Notes
(1) Fix the unit with anchor bolts.
(2) Strong wind must not be directed to the air outlet.
(3) Free space over the unit must be larger than 1 m.
(4) The unit should not be surrounded by obstructions in all direction.
At least one direction around the unit must be free.
316
Minimum allowable space to the obstacles
1
2
3
L1
Open
Open
500
L2
300
0
Open
L3
100
150
100
Mark
FDTN-C
Models FDC406CES3, 506CES3, 506CEM3
Unit: mm
380
580
FDTN-C
1250
950
Required space for maintenance and air flow
Minimum allowable space to the obstacles
Unit:mm
L2
Installation
type
L3
1
2
L1
Open
Open
500
L2
300
0
Open
L3
150
300
150
Mark
L1
3
Notes
(1) Fix the unit with anchor bolts.
(2) Strong wind must not be directed to the air outlet.
(3) Free space over the unit must be larger than 1 m.
(4) The unit should not be surrounded by obstructions in all direction.
At least one direction around the unit must be free.
317
FDTN-C
7.2.4
(1)
Exterior appearance
Indoor unit
Models All models
Item
Type
Panel model
For wireless remote
controller
FDTN208C
TN-PSC-22W-E
FDTN258C~508C
TN-PSC-32W-E
For wired remote
controller
FDT208
T-PSA-22W-E
FDT258~508
T-PSA-32W-E
Remarks
Without swing
Pearl white
(Decorative panel)
(2) Outdoor unit
Models FDC208CEN3, 208CEP3
Models FDC258CEN3, 258CEP3
Polar white
FDTN-C
Polar white
Models FDC206CEN3, 206CEP3
256CEN3, 256CEP3
Models FDC306CEN3,306CEP3
306CES3
Polar white
Polar white
Polar white
318
Models FDC406CES3, 506CES3
506CEM3
FDTN-C
7.2.5
Piping system
Models FDTN208CEN-S, 208CEP-S, 258CEN-S, 258CEP-S
FDT208CEN-S, 258CEN-S
Check joint
Service valve
Indoor unit
Outdoor unit
(Flare connecting)
Gas line
(φ15.88)
Thermistor
(Th1–A)
Thermostat
(23Td)
Heat
exchanger
Thermistor
(Th1–R)
Heat
exchanger
Compressor
Solenoid
valve
SV
Accumulator
(
Liquid line
208:φ6.35
258:φ9.52
)
Check joint
Capillary tube
Stralner
Service valve
(Flare connecting)
Models FDTN208CEN, 208CEP, 258CEN, 258CEP, 308CEN, 308CEP, 308CES, 408CES, 508CES, 508CEM
FDT308CEN, 308CES, 408CES, 508CES
Indoor unit
FDTN-C
Outdoor unit
ø15.88
(208~308:
408, 508: ø19.05)
ø6.35
(208:
258~508: ø9.52)
Preset point of protective devices
Part name
Thermistor
(for frost prevention)
Mark
Equipped
unit
All models
ThI-R
Indoor
unit
OFF 2.5°C
ON 10°C
319
FDTN-C
7.2.6
Selection chart
Correct the cooling capacity in accordance with the conditions as follows. The net cooling capacity can be obtained in the
following way.
Net capacity = Capacity shown on specification × Correction factors as follows.
(1) Coefficient of cooling capacity in relation to temperatures
Only case of ISO-T1 models
Coefficient of cooling capacity
in relation to temperature (˚CD.B.)
(a)
FDTN-C
Cooling operation
Outdoor air D.B.
temperature (˚CD.B.)
Applicable range
ISO-T1 Standard condition
Indoor air W.B. temperature(˚CW.B.)
320
FDTN-C
FDTN-C
(b) Only case of ISO-T3 and SASO models
ISO-T1 Standard condition
Indoor air W.B. temperature (˚CW.B.)
Table of bypass factor
Item
Air flow
Model
208 type
258 type
308 type
408 type
508 type
Hi
0.112
0.050
0.065
0.076
0.025
Lo
0.073
0.030
0.030
0.050
0.013
(2) Correction of cooling capacity in relation to air flow rate control (fan speed)
Coefficient: 1.00 at High, 0.95 at Low
321
FDTN-C
(3) Correction of cooling capacity in relation to one way length of refrigerant piping
It is necessary to correct the cooling capacity in relation to the one way equivalent piping length between the indoor and outdoor
units.
(50/60Hz)
Cooling
Equivalent piping length(1) m
5
10
15
20
25
208 type
1.0
0.995
0.995/0.99
0.99/0.985
258 type
1.0
0.995
0.99
0.985
0.98
308 type
1.0
0.99
0.98/0.975
0.97/0.965
408 type
1.0
0.995/0.99
0.985/0.98
0.98/0.97
508 type
1.0
0.99/0.985
0.975/0.97 0.965/0.955
30
0.985/0.98 0.985/0.975
35
0.98/0.97
0.975
0.97
0.96/0.95
0.95/0.94
0.94/0.925
0.97/0.96
0.965/0.95 0.955/0.94
0.95/0.94
0.94/0.925 0.925/0.91
Note (1) Equivalent piping length can be obtained by calculating as follows.
208, 258, 308 series [φ15.88(5/8″)]: Equivalent piping length = Real piping length + (0.10 × Number or bends in piping)
408, 508, series [φ19.05(3/4″)]: Equivalent piping length = Real piping length + (0.15 × Number of bends in piping)
[Equivalent piping length < Limitation length of piping + 5m]
(4) When the outdoor unit is located at a lower height than the indoor unit in cooling operation, the following values
should be subtracted from the values in the above table.
Height difference between the indoor unit and
outdoor unit in the vertical height difference
5m
10m
15m
Adjustment coefficient
0.01
0.02
0.03
Piping length limitations
Item
Modei
FDT(N)208, 258(FDC208,258 type)
FDTN-C
Max.one way piping length
FDT(N)208~508(FDC206~506 type)
30m
20m(Outdoor unit is higher)
15m(Outdoor unit is lower)
Max.vertical height difference
15m
Note (1) Values in the table indicate the one way piping length between the indoor and outdoor units.
How to obtain the cooling capacity
Example : The net cooling capacity of the model FDTN308CEN with the air flow “High”, the piping length of 15m, the outdoor unit
located 5m lower than the indoor unit, indoor wet-bulb temperature at 19.0 ˚C and outdoor dry-bulb temperature 35 ˚C is
Net cooling capacity =
7100
×
FDTN308CEN
322
1.00
Air flow
“High”
×
(0.98 - 0.01)
×
Length 15m.
Height difference 5 m
1.0
=
6887 w
Factor by air
temperatures
FDTN-C
7.2.7
Noise level
Notes (1) The data are based on the following conditions.
Ambient air temperature:
Indoor unit 27˚C DB, 19˚C WB.
Outdoor unit 35˚C DB.
Outdoor unit
Measured based on JIS B 8616
Mike position: at highest noise level
in position as below
Distance from front side
1m
Height
1m
Indoor unit
Measured based on JIS B 8616
Mike position as below
Mike (center & low points)
(2) The data in the chart are measured in an unechonic room.
(3) The noise levels measured in the field are usually higher than the data because of reflection.
(1) Indoor unit
Models FDTN208C
Models FDTN258C
FDT208
Noise level 38 dB (A) at HIGH
33 dB (A) at LOW 70
70
60
60
N60
50
50
N50
40
40
N40
30
30
N30
20
125
250
500
1000
2000
60
N60
50
50
N50
40
40
N40
30
30
N30
N2
20
63
Mid octave band frequency (Hz)
125
250
500
1000
2000
70
40
40
N40
30
30
N30
N2
20
63
125
250
500
1000
2000
4000
20
8000
Mid octave band frequency (Hz)
Noise level 49 dB (A) at HIGH
43 dB (A) at LOW
70
70
70
N70
N70
60
60
N60
50
50
N50
40
40
N40
30
30
N30
N2
0
20
500
1000
2000
4000
20
8000
Sound pressure level
(Standard 0.0002µ bar) dB
Sound pressure level
(Standard 0.0002µ bar) dB
50
N50
FDT508
Noise level 48 dB (A) at HIGH
40 dB (A) at LOW
250
50
Models FDTN508C
FDT408
125
60
N60
0
20
8000
4000
60
Mid octave band frequency (Hz)
Models FDTN408C
63
70
N70
60
0
20
8000
4000
70
70
FDTN-C
63
Noise level 41 dB (A) at HIGH
35 dB (A) at LOW
N70
Sound pressure level
(Standard 0.0002µ bar) dB
Sound pressure level
(Standard 0.0002µ bar) dB
N70
N2
0
FDT308
Noise level 39 dB (A) at HIGH
35 dB (A) at LOW
Sound pressure level
(Standard 0.0002µ bar) dB
70
Models FDTN308C
FDT258
60
60
N60
50
50
N50
40
40
N40
30
30
N30
N2
0
20
63
Mid octave band frequency (Hz)
125
250
500
1000
2000
4000
20
8000
Mid octave band frequency (Hz)
(2) Outdoor unit
Model
FDC208CEN3
Model
Noise level 52 dB (A)
FDC208CEP3
Model
Noise level 52 dB (A)
70
FDC206CEN3
Noise level 59 dB (A)
70
70
70
N70
60
60
N60
50
50
N50
40
40
N40
30
30
N2
20
63
125
250
500
1000
2000
4000
60
60
N60
50
50
N50
40
40
N40
30
30
N30
N2
0
N30
0
Sound pressure level
(Standard 0.0002µ bar) dB
Sound pressure level
(Standard 0.0002µ bar) dB
N70
20
20
8000
63
125
250
500
1000
2000
4000
20
8000
Mid octave band frequency (Hz)
Mid octave band frequency (Hz)
323
FDTN-C
Model
FDC206CEP3
Model
Noise level 59 dB (A)
FDC258CEN3
Model
Noise level 52 dB (A)
70
Noise level 52 dB (A)
70
70
70
N70
60
60
Sound pressure level
(Standard 0.0002µ bar) dB
Sound pressure level
(Standard 0.0002µ bar) dB
N70
N60
50
50
N50
40
40
N40
30
30
N30
N2
0
20
63
125
250
500
1000
2000
4000
FDC258CEP3
20
8000
60
60
N60
50
50
N50
40
40
N40
30
30
N30
N2
0
20
63
Mid octave band frequency (Hz)
125
250
500
1000
2000
20
8000
4000
Mid octave band frequency (Hz)
FDC256CEN3
Model
Noise level 59 dB (A)
FDC256CEP3
Model
Noise level 59 dB (A)
70
70
Sound pressure level
(Standard 0.0002µ bar) dB
Sound pressure level
(Standard 0.0002µ bar) dB
60
N60
50
50
N50
40
40
N40
30
30
N30
N2
0
20
63
125
250
500
1000
2000
4000
70
N70
60
60
N60
50
50
N50
40
40
N40
30
30
N30
N2
0
63
125
Mid octave band frequency (Hz)
250
500
1000
2000
20
8000
4000
70
N70
60
20
20
8000
FDC306CEN3
Noise level 56 dB (A)
70
70
N70
Sound pressure level
(Standard 0.0002µ bar) dB
Model
60
60
N60
50
50
N50
40
40
N40
30
30
N30
N2
0
20
63
Mid octave band frequency (Hz)
125
250
500
1000
2000
4000
20
8000
Mid octave band frequency (Hz)
FDC306CEP3
Model
Noise level 59 dB (A)
FDC306CES3
Model
Noise level 59 dB (A)
70
50
N50
40
40
N40
30
30
N30
63
125
250
500
1000
2000
4000
20
8000
Noise level 59 dB (A)
70
70
N70
60
60
N60
50
50
N50
40
40
N40
30
30
N30
20
63
125
250
500
1000
2000
Mid octave band frequency (Hz)
324
4000
70
20
8000
N70
60
N60
50
50
N50
40
40
N40
30
30
N30
N2
20
63
125
250
500
1000
2000
Mid octave band frequency (Hz)
Models FDC506CES3, 506CEM3
0
60
0
Mid octave band frequency (Hz)
N2
Sound pressure level
(Standard 0.0002µ bar) dB
Sound pressure level
(Standard 0.0002µ bar) dB
50
20
Sound pressure level
(Standard 0.0002µ bar) dB
FDTN-C
60
N60
0
70
70
N70
60
N2
FDC406CES3
Noise level 57dB (A)
70
70
N70
4000
Sound pressure level
(Standard 0.0002µ bar) dB
Model
60
60
N60
50
50
N50
40
40
N40
30
30
N30
N2
0
20
8000
20
63
125
250
500
1000
2000
Mid octave band frequency (Hz)
4000
20
8000
1
WH
U
2
C
CC
51C
1
T
V W
R S
WH
N
RD
RD
L
2
51C
1
1
CC
WH
R
4
CM
S
BK
52C
WH
OR
OR
OR
CFO
CH
SV
CnP
CnP
52C
BR
RD
WH
Mark
Cc
CFI
CFO
CH
CM
CnA ~ W
DM
F
FMI
FMO
FS
LED1
LED2
LM
LS
NR
PC
F(3 . 15A)
Parts name
Capacitor for CM
Capacitor for FMI
Capacitor for FMO
Crankcase heater
Compressor motor
Connector
Drain motor
Fuse
Fan motor (Indoor unit)
Fan motor (Outdoor unit)
Float switch
Indication lamp (Green - Run)
Indication lamp (Yellow - Timer/Check)
Louver motor
Limit switch
Surge suppressor
Photo coupler
Meaning of marks
Only case of FDTN·FDT258 series.
CnM
(49F01)
BL
OR
CnM
FM01
BK
23Td
BK
BL BL
RD
Mark
SV
SW
SW2, 3
TB
Thc
ThI-A
Thl-R
TrI
Val
23Td
49Fo
49FI
51C
52C
X1~7
v
■
RD
WH
B
52C
A
BK
WH
TB
1
2
3
TB
1
2
3
BK
WH
RD
Parts name
Solenoid coil (for control)
Back up switch (ON/OFF)
Changeover switch
Terminal block ( mark)
Thermistor
Thermistor
Thermistor
Transformer
Varistor
Thermostat
Internal thermostat for FMo
Internal thermostat for FMI
Overcurrent relay for CM
Magnetic contactor for CM
Auxiliary relay
Terminal (F)
Connector
NR
RD
Y / GN
Outdoor Unit
Y / GN
TB
Y / GN
[
9
2
1
X5
CnJ
LM
3
CnJ
X1
Mark
BK
BL
BR
GR
OR
RD
WH
Y/GN
Color mark
L
8
X3
7
X4
WH
5
CFI
Color
Black
Blue
Brown
Gray
Orange
Red
White
Yellow/Green
CnF1
(49FI)
H UH
OR
FMI
CnF1
6
X7
X1 X4 X7
X2 X5
X3
Indoor Unit
BL
WH
WH
WH
BK
BL
BK
RD
OR
OR
WH
RD
RD
Y / GN
BR
X2
CnR
4
CnI
FS
CnI
13
VaI
SW2
SW3
OFF
1 2 3 4
OFF
ON
1 2 3 4
ON
Test
BK
CnW1
CnQ
12V
BR CnW2
Tr I
BK RD
Printed wiring board
CnR
DM
BR
WH
WH
PC
GR
RD
RD
WH
CnT
CnH
CnN
CnL
CnV
220/240V
RD
RD
Y
Z
Thc
Remote
controller
RD WH BK
X
Wireless
remote
controller
Receiver amp
2
2
Only case of FDT series.
Z
Y
X
BK
RD
WH
BK
BK LS
CnA
(3)
BK
CnS2
LED1
LED2
SW
(3)
(3)
ThI–R
ThI–A
Option
BK
CnB
CnB2
CnN
BK
BK
XR5
XR3
XR1
]
CnH2
BK BK
BK
BK
XR4
XR2
This diagram indicates the FDTN208 series. 1 is for FDTN258 series.
2 Is for FDT208 series. Sections from 1 and 2 change on the
FDT258 series.
CnS
BK
WH
WH
BL
BL
BK
WH
Electrical wiring
WH
7.3.1
BK
ELECTRICAL DATA
WH
7.3
CnB
Power source
FDTN208CEN-S, 258CEN-S
FDT208CEN-S, 258CEN-S
1 Phase 220/240V 50Hz
FDTN208CEP-S, 258CEP-S
1 Phase 220V 60Hz
FDTN-C
Models FDTN208CEN-S, 208CEP-S, 258CEN-S, 258CEP-S
FDT208CEN-S, 258CEN-S
325
WH
5
CC
4 6
3
2
1
WH
N
C CM R
(49C)
S
BK
52C
OR
CnM
FM01
(49F01)
OR
CnM
OR OR
CnM
CFO
Parts name
Capacitor for CM
Capacitor for FMI
Capacitor for FMO
Compressor motor
Connector
Drain motor
Fuse
Fan motor (Indoor unit)
Fan motor (Outdoor unit)
Float switch
Indication lamp (Green - Run)
Indication lamp (Yellow - Timer/Check)
Louver motor
Limit switch
Surge suppressor
Photo coupler
Meaning of marks
Mark
Cc
CFI
CFO
CM
CnA ~ W
DM
F
FMI
FMO
FS
LED1
LED2
LM
LS
NR
PC
WH
Exclude
FDTN208, 258, 308CEP
NR
Mark
SW
SW2, 3
TB
Thc
Thl-A
Thl-R
TrI
Val
49C
49Fo
49FI
52C
X1~7
v
■
F(3 . 15A)
A
TB
1
2
3
TB
1
2
3
Parts name
Back up switch (ON/OFF)
Changeover switch
Terminal block ( mark)
Thermistor
Thermistor
Thermistor
Transformer
Varistor
Internal thermostat for CM
Internal thermostat for FMo
Internal thermostat for FMI
Magnetic contactor for CM
Auxiliary relay
Terminal (F)
Connector
B
52C
BK
WH
RD
Y / GN
BK
WH
RD
X5
Mark
BK
BL
BR
GR
OR
RD
WH
Y/GN
Color mark
9
2
1
CnJ
LM
3
CnJ
X1
7
WH
Color
Black
Blue
Brown
Gray
Orange
Red
White
Yellow/Green
5
CnF1
(49FI)
X7
CFI
CnF1
6
H UH
OR
L
FMI
8
X3
X4
X1 X4 X7
X2 X5
X3
Indoor Unit
CnR
DM
CnR
4
X2
SW2
SW3
OFF
1 2 3 4
OFF
ON
1 2 3 4
ON
Test
BK
CnW1
CnQ
12V
BR CnW2
Tr I
BK RD
]
Printed wiring board
CnI
FS
CnI
13
Val
1 changes on
220/240V
This diagram indicates the FDTN series. Section from
the FDT series.
Y / GN
RD
RD
RD
WH
WH
RD
L
Y / GN
BK
RD
BL
BL
TB
Y / GN
BL
BL
Y / GN
BK
WH
WH
WH
BK
OR
OR
WH
WH
RD
Y / GN
BK
BK
WH
WH
BR
BR
WH
WH
PC
GR
RD
RD
WH
CnT
CnH
CnN
CnL
CnV
Outdoor Unit
[
XR4
XR2
RD
RD
XR5
Y
Z
Thc
Remote
controller
RD WH BK
X
Wireless
remote
controller
1
Receiver amp
1
Only case of FDT series.
Z
Y
X
BK
RD
WH
BK
BK LS
CnA
(3)
BK
CnS2
LED1
LED2
SW
(3)
(3)
ThI–R
ThI–A
Option
BK
CnB
CnB2
CnN
XR3
XR1
BK
BK
CnH2
BK BK
BK
BK
CnS
326
CnB
Power source
FDTN208CEN, 258CEN, 308CEN
FDT308CEN
1 Phase 220/240V 50Hz
FDTN208CEP, 258CEP, 308CEP
1 Phase 220V 60Hz
FDTN-C
Models FDTN208CEN, 208CEP, 258CEN, 258CEP, 308CEN, 308CEP
FDT308CEN
N
L3
L2
BK
52C
NR
T2
T1 CM T3
(49C)
6
5
4
3
2
1
RD
OR
OR
CnM
OR OR
CnM
(49FO)
FMO
CnM
BK
Mark
CFI
CFO
CM
CnA ~ W
DM
F
FMI
FMO
FS
LED1
LED2
LM
LS
NR
SW
CFO
WH
Parts name
Capacitor for FMI
Capacitor for FMO
Compressor motor
Connector
Drain motor
Fuse
Fan motor (Indoor unit)
Fan motor (Outdoor unit)
Float switch
Indication lamp (Green - Run)
Indication lamp (Yellow - Timer/Check)
Louver motor
Limit switch
Surge suppressor
Back up switch (ON/OFF)
Meaning of marks
BK
BL
WH
RD
Mark
PC
TB
SW2, 3
Thc
ThI-A
ThI-R
TrI
Val
49C
49Fo
49FI
52C
X1~7
v
■
F(3 . 15A)
A
TB
1
2
3
TB
1
2
3
Parts name
Photo coupler
Terminal block ( mark)
Changeover switch
Thermistor
Thermistor
Thermistor
Transformer
Varistor
Internal thermostat for CM
Internal thermostat for FMo
Internal thermostat for FMI
Magnetic contactor for CM
Auxiliary relay
Terminal (F)
Connector
B
52C
BK
BK
RD
Y / GN
TB
Y / GN
BL
RD
BK
WH
RD
X5
Mark
BK
BL
BR
GR
OR
RD
WH
Y/GN
Color mark
9
2
1
CnJ
LM
3
CnJ
X1
7
WH
Color
Black
Blue
Brown
Gray
Orange
Red
White
Yellow/Green
5
CnF1
(49FI)
X7
CFI
CnF1
6
H UH
OR
L
FMI
8
X3
X4
X1 X4 X7
X2 X5
X3
Indoor Unit
CnR
DM
CnR
4
X2
SW2
SW3
OFF
1 2 3 4
OFF
ON
1 2 3 4
ON
Test
BK
CnW1
CnQ
12V
BR CnW2
Tr I
BK RD
]
Printed wiring board
CnI
FS
CnI
13
Val
1 changes on
220/240V
This diagram indicates the FDTN series. Section from
the FDT series.
Y / GN
L1
Y / GN
BL
BL
WH
BL
WH
Y / GN
BK
WH
WH
WH
BK
OR
OR
WH
WH
RD
RD
Y / GN
BK
BK
WH
WH
BR
BR
WH
WH
PC
GR
RD
RD
WH
CnT
CnH
CnN
CnL
CnV
Outdoor Unit
[
XR4
XR2
RD
RD
XR5
Y
Z
Thc
Remote
controller
RD WH BK
X
Wireless
remote
controller
Receiver amp
1
1
Only case of FDT series.
Z
Y
X
BK
RD
WH
BK
BK LS
CnA
(3)
BK
CnS2
LED1
LED2
SW
(3)
(3)
ThI–R
ThI–A
Option
BK
CnB
CnB2
CnN
XR3
XR1
BK
BK
CnH2
BK BK
BK
BK
CnS
CnB
Power Source
3 Phase 380/415V 50Hz-380V 60Hz
FDTN-C
Models FDTN308CES
FDT308CES
327
N
L3
BK
BL
RD
T2
T1 CM T3
(49C)
6
5
4
3
2
1
BK
52C
NR
BK
OR
CFo1
Mark
CFI
CFO1,2
CH
CM
CnA ~ W
DM
F
FMI
FMO1,2
FS
LED1
LED2
LM
LS
NR
SW
OR
OR
CnM2
OR OR
CnM2
(49FO2)
FMO1
CnM2
CnP
CH
CnP
52C
BK
CFo2
WH
Parts name
Capacitor for FMI
Capacitor for FMO
Crankcase heater
Compressor motor
Connector
Drain motor
Fuse
Fan motor (Indoor unit)
Fan motor (Outdoor unit)
Float switch
Indication lamp (Green - Run)
Indication lamp (Yellow - Timer/Check)
Louver motor
Limit switch
Surge suppressor
Back up switch (ON/OFF)
Meaning of marks
OR
CnM1
OR OR
CnM1
(49FO1)
FMO1
CnM1
Only for FDT(N)508
BK
RD
BK
WH
Mark
PC
TB
SW2, 3
Thc
ThI-A
ThI-R
TrI
Val
49C
49Fo1,2
49FI
52C
X1~7
v
■
F(3 . 15A)
A
TB
1
2
3
TB
1
2
3
Parts name
Photo coupler
Terminal block ( mark)
Changeover switch
Thermistor
Thermistor
Thermistor
Transformer
Varistor
Internal thermostat for CM
Internal thermostat for FMo
Internal thermostat for FMI
Magnetic contactor for CM
Auxiliary relay
Terminal (F)
Connector
B
52C
BK
BK
RD
Y / GN
L2
BL
RD
BK
WH
RD
X5
CnJ
Mark
BK
BL
BR
GR
OR
RD
WH
Y/GN
3
X1
7
WH
5
CnF1
(49FI)
X7
CFI
CnF1
6
H UH
OR
L
FMI
8
X3
X4
Color
Black
Blue
Brown
Gray
Orange
Red
White
Yellow/Green
LM
CnJ
Color mark
9
2
1
X1 X4 X7
X2 X5
X3
Indoor Unit
CnR
DM
CnR
4
X2
SW2
SW3
OFF
1 2 3 4
OFF
ON
1 2 3 4
ON
Test
BK
CnW1
CnQ
12V
BR CnW2
Tr I
BK RD
]
Printed wiring board
Cn I
FS
Cn I
13
Val
1 changes on
220/240V
This diagram indicates the FDTN series. Section from
the FDT series.
Y / GN
RD
Y / GN
RD
TB
Y / GN
BK
WH
BL
WH
Y / GN
BK
BK
WH
WH
BL
BL
L1
Y / GN
BK
WH
WH
WH
BK
OR
OR
WH
WH
RD
Y / GN
BK
BK
WH
WH
BR
BR
WH
WH
PC
GR
RD
RD
WH
CnT
CnH
CnN
CnL
CnV
Outdoor Unit
[
XR4
XR2
RD
RD
XR5
Y
Z
Thc
Remote
controller
RD WH BK
X
Wireless
remote
controller
1
Receiver amp
1
Only case of FDT series.
Z
Y
X
BK
RD
WH
BK
BK LS
CnA
(3)
BK
CnS2
LED1
LED2
SW
(3)
(3)
Th I–R
Th I–A
Option
BK
CnB
CnB2
CnN
XR3
XR1
BK
BK
CnH2
BK BK
BK BK
CnS
328
CnB
Power Source
3 Phase 380/415V 50Hz-380V 60Hz
FDTN-C
Models FDTN408CES, 508CES
FDT408CES, 508CES
T
S
BL
WH
RD
T2
T1 CM T3
(49C)
6
5
4
3
2
1
BK
OR
OR
CnM1
OR OR
CnM1
(49FO1)
FMO1
CnM1
CFo1
Mark
CFI
CFO1,2
CH
CM
CnA ~ W
DM
F
FMI
FMO1,2
FS
LED1
LED2
LM
SW
OR
OR
CnM2
OR OR
CnM2
(49FO2)
FMO1
CnM2
CnP
CH
CnP
52C
BR
CFo2
WH
Parts name
Capacitor for FMI
Capacitor for FMO
Crankcase heater
Compressor motor
Connector
Drain motor
Fuse
Fan motor (Indoor unit)
Fan motor (Outdoor unit)
Float switch
Indication lamp (Green - Run)
Indication lamp (Yellow - Timer/Check)
Louver motor
Back up switch (ON/OFF)
Meaning of marks
52C
BK
RD
BK
RD
Mark
PC
TB
SW2, 3
ThI-A
ThI-R
TrI
Val
49FI
49C
49Fo1,2
52C
X1~7
v
■
F(3 . 15A)
A
TB
1
2
3
TB
1
2
3
Parts name
Photo coupler
Terminal block ( mark)
Changeover switch
Thermistor
Thermistor
Transformer
Varistor
Internal thermostat for FMI
Internal thermostat for CM
Internal thermostat for FMo
Magnetic contactor for CM
Auxiliary relay
Terminal (F)
Connector
B
52C
BK
BK
RD
Y / GN
Outdoor Unit
BK
WH
RD
Y / GN
R
BL
RD
X5
Mark
BK
BL
BR
GR
OR
RD
WH
Y/GN
Color mark
9
2
1
CnJ
LM
3
CnJ
X1
RD
TB
Y / GN
7
WH
Color
Black
Blue
Brown
Gray
Orange
Red
White
Yellow/Green
5
CnF1
(49FI)
X7
CFI
CnF1
6
H UH
OR
L
FMI
8
X3
X4
X1 X4 X7
X2 X5
X3
Indoor Unit
BL
BL
WH
BL
WH
Y / GN
BK
BK
WH
WH
BK
BK
WH
WH
BK
BK
OR
OR
WH
WH
RD
Y / GN
BK
BK
WH
WH
BR
X2
CnR
4
Cn I
FS
Cn I
13
Val
BK
CnW1
SW2
SW3
OFF
1 2 3 4
OFF
ON
1 2 3 4
ON
Test
12V
BR CnW2
Tr I
BK RD
CnQ
220/240V
Printed wiring board
CnR
DM
BR
WH
WH
PC
GR
RD
RD
WH
CnT
CnH
CnN
CnL
RD
RD
XR5
CnB
CnB2
CnN
XR3
XR1
CnA
(3)
Th I–R
Wireless
remote
controller
Receiver amp
Option
Th I–A
LED1
LED2
SW
(3)
(3)
BK
BK
CnH2
BK BK
BK
BK
XR4
XR2
Model
CnV
Power source
3 Phase 230V 50Hz/220V 60Hz
FDTN-C
FDTN508CEM
329
FDTN-C
7.4
OUTLINE OF OPERATION CONTROL BY MICROCOMPUTER
Except for function relating to heating, same at the unit for FDT(N) heat pump type. See page 241.
7.5
APPLICATION DATA
The application data for the cooling only models are similar to those for the heat pump models. (See page 256.)
7.6
MAINTENANCE DATA
FDTN-C
Same at the cooling /heating equipment FDT(N) heat pump type. Refer to page 271.
330