Fireye Amplifier Modules Owner's Manual
Advertisement
Advertisement
MAMP-1
APRIL 3, 2013
MEUV1, MEUV4,MEUVS1,
MEUVS4, MEIR1, MEIR4,
MERT1, MERT4,
MECD1 and MECD4
AMPLIFIER MODULES FOR USE WITH THE
FIREYE
®
MODULAR MicroM™ CONTROL
APPROVED
DESCRIPTION
The Fireye MEUV1, MEUV4, MEUVS1, MEUVS4, MERT1, MERT4, MEIR1, MEIR4, MECD1 and MECD4 are Amplifier Modules used with the Fireye Modular MicroM control. These amplifier modules provide flame scanning capabilities using any of the Fireye standard ultraviolet scanners, self-check scanners, infrared scanners, cadmium sulfide scanners and flame rods. The Flame Failure
Response Time (FFRT) of the control is determined by the selection of the amplifier module (see
Ordering Information). Test jacks are provided on the amplifier modules to permit flame signal measurement during operation and is a uniform 0-10 vdc for all models.
After scanner selection, the proper amplifier module must be used in the Modular MicroM chassis
(see Ordering Information). The amplifier module incorporates a plug-in design for ease of installation.
The programmer module determines the operational characteristics of the control (e.g. relight, purge timing, etc.).
For proper and safe application of this product, you must refer to bulletin MC-5000 for a detailed description of the operation of the Modular MicroM control, including installation instructions, operating sequences for the programmer modules, etc. Also follow the scanner installation and wiring instructions found in bulletins MC-5000 for proper flame scanning operation.
WARNING: Selection of this control for a particular application should be made by a competent professional, licensed by a state or other government agency. Inappropriate application of this product could result in an unsafe condition hazardous to life and property. Installation should not be considered complete until pilot turndown and other appropriate performance tests have been successfully completed.
1
ORDERING INFORMATION
Flame Amplifier Selection
:
MEUV1
MEUV4
MEUVS1
MEUVS4
MERT1
MERT4
MEIR1
MEIR4
MECD1
MECD4
MicroM Amplifier Models:
UV amplifier,0.8 second FFRT, uses UV1A, UV2, UV8A and 45UV3-1050 scanners.
UV amplifier, 4 second (max) FFRT, uses UV1A, UV2, UV8A and 45UV3-1050 scanners.
UV Self-Check amplifier,0.8 second FFRT, uses 45UV5-1009 scanner.
UV Self-Check amplifier, 4 second (max) FFRT, uses 45UV5-1009 scanner.
Flame Rod / Photocell amplifier,0.8 second FFRT, uses 69ND1 or 45CM1 (obsolete).
Flame Rod / Photocell amplifier, 4 second (max) FFRT, uses 69ND1 or 45CM1 (obsolete).
Infrared amplifier0,.8 second FFRT, uses 48PT2 scanner.
Infrared amplifier, 4 second (max) FFRT, uses 48PT2 scanner.
Cadmium sulfide amplifier,0.8 second FFRT, uses CS1A5 scanner.
Cadmium sulfide amplifier, 4 second (max) FFRT, uses CS1A5 scanner.
FLAME SCANNERS
2
CAUTION: The UV1, UV2, UV8A, UV90 and 45UV3 ultra-violet flame scanners and associated amplifier modules are non self-checking UV systems and should be applied only to burners that cycle often (e.g.: a minimum of once per 12 hours) in order for the safety checking circuit to be exercised. If component checking is required during burner operation for constantly fired burners, utilize the self-checking ultra-violet flame scanners (45UV5) with associated amplifier module
(MEUVS1, MEUVS4) or the infrared flame scanner (48PT2) with associated Auto Check amplifier
(MEIR1, MEIR4).
UV1A3
UV1A6
UV2
UV8A
UV SCANNERS:
1/2” NPT connector, 3 ft. (914mm) TC-ER cable, non self-checking.
1/2” NPT connector, 6 ft. (1828mm) TC-ER cable, non self-checking.
3/8” NPT connector, 3 ft. (914mm) TC-ER cable, non self-checking.
1/2” NPT 90° head, 6 ft. unshielded leads.
45UV3-1050 3/4” sleeve/set screw mount. Non self-checking.
45UV5-1009 UV self-check scanner 8 ft. (2400mm) leads. 1” NPT threads.
120 VAC shutter. Use with MEUVS type amplifier.
UV90-3
UV90-6
UV90-9
UV, 90° lateral view, 3 ft. (914mm) flex conduit
UV, 90° lateral view, 6 ft. (1828mm) flex conduit
UV, 90° lateral view, 9 ft. (2742mm) flex conduit
45CM1-1000
45CM1-1000Y
FLAME DETECTORS:
Photocell with filter.
Photocell without filter.
69ND1-1000K4 12 inch flame rod, 1/2” NPT connector.
69ND1-1000K6 18 inch flame rod, 1/2” NPT connector.
69ND1-1000K8 24 Inch flame rod, 1/2” NPT connector.
BULLETIN
SC-102
SC-102
SC-102
SC-102
SC-102
SC-101
SC-102
SC-102
SC-102
BULLETIN
OBSOLETE
OBSOLETE
SC-103
SC-103
SC-103
48PT2-1003
48PT2-1007
48PT2-9003
48PT2-9007
48PT2-9007W
INFRARED SCANNERS:
Infrared scanner 8 ft. (2400mm) TC-ER cable, straight head.
Infrared scanner 4 ft. (1200mm) TC-ER cable, straight head.
Infrared scanner 8 ft. (2400mm) TC-ER cable, 90° head.
Infrared scanner 4 ft. (1200mm) TC-ER cable, 90° head.
Infrared scanner 4 ft. (1200mm) shielded cable, 90° head, water repellent. OBSOLETE, Replaced by 48PT2-9007
BULLETIN
SC-103
SC-103
SC-103
SC-103
SC-103
CS1A5
Parts and Accessories
Part Number
4-263-1
4-314-1
10-88
19-30
35-69
35-75
35-127-1
46-38
46-56
46-58
60-302
60-801
60-1199-1
60-1199-2
60-1257
60-1290
60-1664-3
61-436
61-2914
61-3263
82-95
92-45
92-48
124-13
124-14
CADMIUM SULPHIDE:
Cadmium sulfide 5’, with mounting bracket
Description
Firetron cell for 48PT2 only.
UV tube for 45UV5-1005-1009, 45UV2, 45UV3.
Set of 3 orifice plugs (
1
/
16
'',
1
/
8
'',
3
/
16
'') for 48PT1, 48PT2.
Pyrex window for 60-801 union.
Heat insulator,
1
/
2
" connection for 48PT, UV1A.
Water cooled adapter for 48PT, UV1A.
Heat insulator. 1" NPT for 45UV5.
Replacement lens (1.25" dia.) for 45UV5,.
Quartz magnifying lens for 45UV3, (1" dia.).
Quartz (1”dia.) lens for 60-1290 union.
Swivel mtg. adapter,
1
/
2
" NPT for 48PT1, 48PT2, UV1A.
1
/
2
" union with Pyrex window for 48PT1, 48PT2.
Coupling with quartz window, 1" NPT for 45UV2, 45UV3, 45UV5.
Coupling with quartz window, 1" BSP for 45UV2, 45UV3, 45UV5.
Union with quartz window,
1
/
2
" NPT for UV1A.
Union with quartz lens,
1
/
2
" NPT for UV1A.
Swivel mount adapter, 1" NPT for 45UV5 scanners.
Lens cap (standard) for 48PT scanners.
Shutter and bracket assembly only for 45UV5-1009.
Shutter, bracket and lens assembly with lens holder and gasket for 45UV5-1005-1009,
1105 (includes a 61-2914).
Lens holder for 45UV5 scanner.
Quartz window used in 45UV3-1050 and 60-1237 union.
Quartz window used in 60-1199 union.
“O” Ring used in 60-1199 union.
“O” Ring used in 60-801, 60-1257, 60-1290.
Remove power from the control and remove the control from its wiring base before proceeding.
3
INSTALLATION
The amplifier modules are used with the Fireye
Modular MicroM Base Chassis (P/N MEC120,
MEC120C, MEC120R, MEC120D, MEC120RC for 120VAC, P/N MEC230, for 230VAC). They are installed in the chassis by grabbing hold of the amplifier module by the edges of its printed circuit board, aligning the module with the guide slots on the opening in the middle of the chassis, and inserting the module into the pin connectors.
The amplifier modules are designed to fit in the proper slot only. DO NOT FORCE THEM.
4
3
2
6
5
1
0
9
8
7
12
11
10
CORRELATION BETWEEN
AMPLIFIER TEST JACK
VOLTAGE AND OPTIONAL
ED510 REMOTE DISPLAY
FLAME SIGNAL READING
6 16 20 24 28 32 36 40
ED510 DISPLAY FLAME SIGNAL
WARRANTIES
FIREYE guarantees for one year from the date of installation or 18 months from date of manufacture of its products to replace, or, at its option, to repair any product or part thereof (except lamps, electronic tubes and photocells) which is found defective in material or workmanship or which otherwise fails to conform to the description of the product on the face of its sales order. THE FOREGOING IS IN LIEU OF ALL OTHER WARRANTIES AND FIREYE MAKES NO WAR-
RANTY OF MERCHANTABILITY OR ANY OTHER WARRANTY, EXPRESS OR IMPLIED. Except as specifically stated in these general terms and conditions of sale, remedies with respect to any product or part number manufactured or sold by Fireye shall be limited exclusively to the right to replacement or repair as above provided. In no event shall Fireye be liable for consequential or special damages of any nature that may arise in connection with such product or part.
FIREYE
3 Manchester Road
Derry, New Hampshire 03038 USA www.fireye.com
MAMP-1
APRIL 3, 2013
Supersedes September 10, 2012
4

Download
Advertisement