AS DC ALARM BEFORE USE .... MODEL

AS DC ALARM BEFORE USE .... MODEL
AS
INSTRUCTION MANUAL
DC ALARM
MODEL
AS
■ FRONT PANEL CONFIGURATION
BEFORE USE ....
Thank you for choosing M-System. Before use, check the
package you received as below.
If you have any problems or questions with the product,
please contact M-System’s Sales Office or representatives.
Hi Adj.
Lo Adj.
Hi Setpoint Monitor
■ PACKAGE INCLUDES:
Signal conditioner (body + base socket + input resistor) (1)
Input resistor is provided only with current input type.
■ MODEL NO.
Check that model No. described on specification label is
exactly what you ordered.
■ INSTRUCTION MANUAL
This manual describes necessary points of caution when you
use this product, installation, connection and basic maintenance procedures.
COMPONENT IDENTIFICATION
Body
Base Socket
Hi LED
Lo Setpoint Monitor
Lo LED
COM.
• Hi Adjustment: Used for adjusting Hi setpoint.
• Lo Adjustment: Used for adjusting Lo setpoint.
• Hi LED: Turns on in a tripped condition.
• Lo LED: Turns on in a tripped condition.
• Hi Setpoint Monitor (+):
Outputs 0 – 10V DC proportional to the setpoint 0 – 100%.
(ex: Set to 8V when you need output ON with input 80% or
more.)
• Lo Setpoint Monitor (+):
Outputs 0 – 10V DC proportional to the setpoint 0 – 100%.
(ex: Set to 2V when you need output ON with input 20% or
less.)
• Common (–): Used for setpoint monitors.
Specification
Label
INSTALLATION
M•UNIT
Model
Input Resistor
AS
DC ALARM
SET
HI
LO
HI
SET MONITOR
0–100%
(0–10VDC)
LO
COM
Detach the yellow clamps located at the top and bottom of
the unit for separating the body
from the base socket.
Clamp
(top & bottom)
DIN Rail
35mm wide
■ DIN RAIL MOUNTING
Set the base socket so that its
DIN rail adaptor is at the bottom. Position the upper hook
at the rear side of base socket
on the DIN rail and push in the
Spring Loaded
lower. When removing the
DIN Rail Adaptor
socket, push down the DIN rail
adaptor utilizing a screwdriver Shape and size of the base socket
are slightly different with various
(–) and pull.
socket types.
■ WALL MOUNTING
Refer to the drawings in the following page.
P. 1 / 3
EM-1611-A Rev.6
AS
TERMINAL CONNECTIONS
Connect the unit as in the diagram below or refer to the connection diagram label on the front of the unit.
When an input resistor is provided with the module, attach it together with input wiring to the input screw terminals.
■ DIMENSIONS mm (inch)
CLAMP
(top & bottom)
20
(.79)
7.8 (.31)
5
4
3
7
8
1
2
2–4.5 (.18) dia.
MTG HOLE
15 (.59) deep
8–M3.5
SCREW
50 (1.97)
6
80 (3.15)
80 (3.15)
35.4 (1.39)
DIN RAIL
35mm wide
103 (4.06)
123 (4.84)
40 (1.57)
[3.3 (.13)]
50 (1.97)
•When mounting, no extra space is needed between units.
■CONNECTION DIAGRAM
INPUT
R
–
3
*
1 +
4
2 –
INPUT RESISTOR
(model: REM)
HI OUTPUT
5 +
6
5
4
3
7
8
1
2
LO OUTPUT
6 –
12 (.47)
+
■ TERMINAL ASSIGNMENTS mm (inch)
7 U(+)
POWER
8 V(–)
*Input shunt resistor attached for current input.
Input shunt resistor attached
for current input.
P. 2 / 3
EM-1611-A Rev.6
AS
CHECKING
POINTS OF CAUTION
1) Terminal wiring: Check that all cables are correctly
connected according to the connection diagram.
2) Power input voltage: Check voltage across the terminal 7
–␣ 8 with a multimeter.
3) Input: Check that the input signal is within 0 – 100% of
the full-scale.
4) Relay operations: Confirm that the relays operate properly referring to the figure below.
5) Output load: Check the output load corresponds to the
table below.
■ GENERAL
• Before you remove the unit from its base socket or mount it,
turn off the power supply and input signal for safety.
OUTPUT
Open collector
Relay
LOAD RESISTANCE
50V DC @100mA
380V AC @100VA
125V DC @30W
60 – 280V AC @0.1 – 1A
SSR
For maximum relay life with inductive load, external
protection is recommended.
■ ENVIRONMENT
• When heavy dust or metal particles are present in the air,
install the unit inside proper housing and ventilate it.
• Do not install the unit where it is subjected to continuous
vibration. Do not apply physical impact to the unit.
• Environmental temperature must be within -5 to +60°C (23
to 140°F) with relative humidity within 30 to 90% RH in order
to ensure adequate life span and operation.
■ WIRING
• Do not install cables (power supply, input and output) close
to noise sources (relay drive cable, high frequency line, etc.).
• Do not bind these cables together with those in which noises
are present. Do not install them in the same duct.
■ AND ....
• The unit is designed to function as soon as power is
supplied, however, a warm up for 10 minutes is required for
satisfying complete performance described in the data sheet.
ALARM RELAY OPERATIONS
•Output Code : 1, 2, 4
(1–2)ON
Hi Output
Input
(%)
MAINTENANCE
(5–6)ON
Lo Output
Regular calibration procedure is explained below:
0
▲
Lo Setpoint
50
▲
Hi Setpoint
100
•Output Code : 3
(1–2)ON
Hi Output
(5–6)ON
Lo Output
Input
(%)
0
▲
Lo Setpoint
50
▲
Hi Setpoint
Trip Operation in Power Failure
•Output Code: 1, 2, 4: both relays turn OFF
•Output Code: 3: both relays turn ON
100
■ CALIBRATION
Warm up the unit for at least 10 minutes.
• Hi Setpoint
Increase the input signal from a value lower than the setpoint
and check that the trip point remains within the accuracy
described in the data sheet.
• Lo Setpoint
Decrease the input signal from a value higher than the
setpoint and check that the trip point remains within the
accuracy described in the data sheet.
When the trip points are out of tolerance, contact M-System’s
Sales Office or local representatives.
M-SYSTEM WARRANTY
M-System warrants such new M-System product which it manufactures to be free from defects in materials and workmanship during the 36-month period following the date that such
product was originally purchased if such product has been used under normal operating conditions and properly maintained, M-System's sole liability, and purchaser's exclusive remedies,
under this warranty are, at M-System's option, the repair, replacement or refund of the purchase price of any M-System product which is defective under the terms of this warranty. To
submit a claim under this warranty, the purchaser must return, at its expense, the defective M-System product to the below address together with a copy of its original sales invoice.
THIS IS THE ONLY WARRANTY APPLICABLE TO M-SYSTEM PRODUCT AND IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING ANY IMPLIED
WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. M-SYSTEM SHALL HAVE NO LIABILITY FOR CONSEQUENTIAL, INCIDENTAL OR
SPECIAL DAMAGES OF ANY KIND WHATSOEVER.