Specification Sheet T12 High Output Rapid Start Parallel Lamp Operation escent Ballast Project:

Specification Sheet T12 High Output Rapid Start Parallel Lamp Operation escent Ballast Project:
EP2/110RS/MV/SC
Specification Sheet
Electronic Fluorescent Ballast
7/21/2014
Project:
2 Lamp
Standard Ballast Factor
Multi-volt
Catalog#:
Approved by:
T12 High Output Rapid Start Parallel Lamp Operation
Lamp Type
No. Of
Lamps
Lamp
Watts
Line
Voltage
Ballast
Factor
Input
Watts
Input
Current
(amps)
Power
Factor
THD
Ballast
Efficacy
Factor
Min. Start
Temp. (F/C)
2*
110
120
0.88
185
1.54
0.98
<10%
0.48
-20/-29
2*
110
277
0.88
180
0.66
0.97
<10%
0.49
-20/-29
1
110
120
0.91
96
0.80
0.98
<10%
0.95
-20/-29
1
110
277
0.91
95
0.37
0.90
<15%
0.96
-20/-29
2
95
120
0.88
165
1.38
0.98
<10%
0.53
60/16
2
95
277
0.88
162
0.60
0.97
<10%
0.54
0/-18
1
95
120
0.91
88
0.74
0.98
<10%
1.03
60/16
1
95
277
0.91
86
0.32
0.90
<15%
1.04
0/-18
2
85
120
0.85
140
1.17
0.98
<10%
0.61
0/-18
2
85
277
0.85
137
0.50
0.97
<10%
0.62
0/-18
F96T12/HO
F96T12/HO/ES
F72T12/HO
F60T12/HO
F48T12/HO
2
75
120
0.82
117
0.98
0.98
<10%
0.70
0/-18
2
75
277
0.82
114
0.42
0.97
<10%
0.71
0/-18
2
60
120
0.83
96
0.80
0.98
<10%
0.86
0/-18
2
60
277
0.83
94
0.34
0.97
<10%
0.87
0/-18
* Primary Lamp Design
Ballast Specifications
• Ballast shall have a five-year warranty
• Ballast shall be UL & cUL Listed
• Ballast shall have OCV 387V
• Ballast shall be sound rated Class A
• Ballast shall be Class P Type 1 Outdoor
• Ballast shall contain no PCBs
• Ballast shall be Type HL, Type CC
• Ballast shall have a Lamp Current Crest Factor of <1.7
• Ballast shall meet ANSI Standards C82.11-2005 & C62.41-2002
• Ballast shall comply with the limits of FCC Part 18 Class A
• Ballast shall have a -20oF minimum lamp starting temperature for primary lamp
• Ballast shall be Rapid Start with Active Power Factor Correction
• Ballast shall be Series Lamp Operation
• Ballast shall have minimum Power Factor of 97% for primary Lamp operation
• Ballast shall operate within +/- 10% of the ballast specified line voltage at 60 Hz
• Ballast shall have a maximum case hot spot temperature of 90oC
Side Ballast View
Wiring Diagram
BLACK
WHITE
BALLAST
LAMP
LAMP
Note: For one lamp operation, cap yellow lead.
Dimensions
Bottom Ballast View
H
W
BLUE
BLUE
RED
RED
YELLOW
YELLOW
0.31
M
L
• Specifications are subject to change without notice.
Howard Lighting Products | 580 Eastview Drive | Laurel, MS 39443
(toll free) 800.956.3456 | (direct) 601.422.0033 | (fax) 601.422.1652
www.HowardLightingProducts.com
W
L: 11.8”
W: 2.15”
H: 1.6”
M: 11.0”
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertisement