awassie-01

awassie-01
Analog Digital Converter
AWA/SSI/12
12 Bit
Version 2
Digitronic Automationsanlagen GmbH
Steinbeisstraße 3 • D - 72636 Frickenhausen • Tel. (+49)7022/40590-0 • Fax -10
Auf der Langwies 1 • D - 65510 Hünstetten-Wallbach • Tel.(+49)6126/9453-0 • Fax -42
Internet: http://www.digitronic.com • E-Mail: [email protected]
2 rue René Laennec 51500 Taissy France
Fax: 03 26 85 19 08, Tel : 03 26 82 49 29
E-mail:[email protected]
Site web : www.hvssystem.com
Digitronic
Automationsanlagen GmbH
Analog Digital Converter
AWA/SSI/12
Notification
This handbook corresponds with the unit version of 18.3.2002. The company Digitronic
Automationsanlagen GmbH reserves the right to implement changes that result in an improvement of
the quality and the functions of the device at any time and without any announcements.
This instructions manual was created with a maximum of care, but mistakes are not out of the
question. We are thankful for any comments, regarding possible mistakes in the instruction manual.
UP-date
You can also obtain this instruction manual on the Internet at http://www.digitronic.com in the latest
version as PDF file.
Qualified personal only
Commissioning and operation of the device may only be carried out by qualified personal. Qualified
personal are persons, authorized with commissioning, grounding and labeling devices, systems and
electrical circuits according to the applicable standards of security
Liability
(1) The salesperson is liable for any damages for which he or the rightful owner is responsible up to
the amount of the actual salesprice. Liability concerning missed profits, failed-to-appear savings,
indirect damages and consequential damage is excluded.
(2) The liability restrictions above are not valid concerning assured characteristics and damages,
which are caused by intention or coarse negligence.
Protection
The device AWA/SSI/12 and this instruction manual are protected by copyright. All rights are
reserved. Neither the device AWA/SSI/12, nor this document may be copied as a whole or partially,
photocopied, reproduced, translated or transferred to electronic media of any kind or into machine
readable format without prior written permission by the company Digitronic Automationsanlagen
GmbH.
Note:
The products of Digitronic are so well constructed that they will not be effected by the
millenium.
Note:
This device fulfills the following norms according to electromagneticalcompatibility:
EN 55011, EN 55022, EN 55024 Teil 2, EN 50082 Teil 2, ENV 50140, VDE 0843
Teil 2, VDE 0843 Teil 4, VDE 0871, VDE 0875 Teil 3 ("N"), VDE 0875 Teil 11,
VDE 0877 Teil 2, IEC 801 Teil 3, IEC 801 Teil 2, IEC 801 Teil 4, IEC 801 Teil 5.
(c) Copyright 1992 - 2004 / Datei: AWASSIE.DOC
Digitronic Automationsanlagen GmbH
Auf der Langwies 1
D-65510 Hünstetten - Wallbach
Tel. (+49)6126/9453-0 Fax. (+49)6126/9453-42
Internet: http://www.digitronic.com / E-Mail: [email protected]
Edition: Aug. 04
Page: 2
2 rue René Laennec 51500 Taissy France
Fax: 03 26 85 19 08, Tel : 03 26 82 49 29
E-mail:[email protected]
Site web : www.hvssystem.com
Digitronic
Automationsanlagen GmbH
Analog Digital Converter
AWA/SSI/12
Table of contents:
1. Introduction .................................................................................................................................... 3
1.1. Data format at the synchronous serial interface........................................................................... 3
2. Assembly ....................................................................................................................................... 3
3. Terminal alllocation........................................................................................................................ 4
3.1. Terminal allocation of the power supply....................................................................................... 4
3.2. SSI interface ............................................................................................................................... 4
3.3. Terminal allocation of the analog input ........................................................................................ 4
3.4. An example for terminal allocation of the CamCon...................................................................... 4
4. Configuration ................................................................................................................................. 4
4.1. Change the input - signal level .................................................................................................... 4
4.2. Reference voltage supply............................................................................................................ 5
4.3. Calibration................................................................................................................................... 5
4.3.1. Calibration during power input .................................................................................................. 5
4.3.2. Calibration during voltage-input 0 - +10V.................................................................................. 5
5. Dimensions .................................................................................................................................... 6
6. Technical data................................................................................................................................ 6
1. Introduction
The analog - digital - converter AWA/SSI/12 of the next generation offers the possibilty to meassure
voltages from 0 to +10 Volt or from 0 to 20mA with a resolution of 12 Bit. The enclosed pre-resistor
enables adjusting and configuring the measuring range. The measured value is read out via the serial
synchronous interface.
1.1. Data format at the synchronous serial interface
Tp
=
Tmono
Err
=
=
Data format
clock impulse
maximum 1MHz
minimum 100kHz
Monoflop time minimum 25µs
SSI Errorbit
always low
Graycode, according to Stegmann Tannenbaum, compatible to the singleturn encoder
with 4096 steps.
2. Assembly
The device is clip-locked onto an "EN carrier rail" in the switchboard (see also chapter "5.
Dimensions" on page 6). The grounding pins and cable mantlings are to be put on the shortest way
possible onto serial grounding clip next to the device. The grounded assembly plate and its electrical
connection to the "EN carrier rail" allow an excelent grounding of the disturbances onto the covering.
All cable connections are to be switched in a cold state!! The SSI data lines of the external interface
are galvanically separated with an optical couplerthey have to be shielded, wired as pairs and the
shield has to be laid on ground with both cable ends. Analog signals have to be placed and covered
separately and the cover has to be grounded on one end. The supply voltage measures 24V DC +/20%.
Edition: Aug. 04
Page: 3
2 rue René Laennec 51500 Taissy France
Fax: 03 26 85 19 08, Tel : 03 26 82 49 29
E-mail:[email protected]
Site web : www.hvssystem.com
Digitronic
Automationsanlagen GmbH
Analog Digital Converter
AWA/SSI/12
3. Terminal alllocation
.
3.1. Terminal allocation of the power supply
Terminal
Terminal
Terminal
Terminal
1
2
3
4
0V voltage supply
0V voltage supply
+24V voltage supply
+24V voltage supply
3.2. SSI interface
DSUB Pin 5
DSUB Pin 9
DSUB Pin 8
DSUB Pin 3
SSI Data
SSI Data
SSI Clock
SSI Clock
+
+
-
3.3. Terminal allocation of the analog input
Terminal 5
Terminal 6
Terminal 7
Signal ground GND
Analog IN
reference voltage
3.4. An example for terminal allocation of the CamCon
CamCon
AWA/SSI/12U
3
7 V-REF
1
PIN 8
6 SIGNAL
PIN 3
PIN 5
5 GND
PIN 9
Attention:
At the CamCon an SSI-singleturn encoder with 4096 steps, Gray has to be chosen
as the measuring system at this AWA/SSI version 2.
4. Configuration
.
4.1. Change the input - signal level
The analog inputs' signal level can be changed by solding bridges on the solder side of the
AWA/2X12B's printed circuit board.
The following input signals can be set: "0-20mA" or "0 - +10V".".
The adjusted signal level is marked for every input by with a cross on the metal cap.
To change the input level, detach all cable connections from the device.,
remove the device from the switch chest, open the floor part at
the devices side using a screwdriver and pull the printed circuit
board out of the floor part. On the solding side of the printed
circuit board are to solding bridges for signal input 1 and 2 which
are called SJ1 to SJ4. For the measuring of a currency signal
the soldingbridge SJ" has to be closed. To measure a voltage
signal, it has to be openened.
Note:
Having adjusted the desired signal level, the input switching has
to be equalized anew. See also chapter "4.3. Calibration".
Edition: Aug. 04
Page: 4
2 rue René Laennec 51500 Taissy France
Fax: 03 26 85 19 08, Tel : 03 26 82 49 29
E-mail:[email protected]
Site web : www.hvssystem.com
Digitronic
Automationsanlagen GmbH
Analog Digital Converter
AWA/SSI/12
4.2. Reference voltage supply
Two intern voltages (+4.096 and +5V) are avaible, an external voltage source may
be enabled by switching them both of. The choice is made via a jumper ledge on the
component side of the printed circuit board. To change the reference voltage,
remove the cap by unscrewing the four cap nuts and choose your voltage source at
jumper JP1.
Bridge at 1+2
Bridge at 2+3
= +5V
= +4.096V
Bridge open
= external
Note:
Ref. voltage from the operating voltage.
Ref. voltage by precission voltage controller
(default).
Ref. voltage external by at least +1V to a maximum of +5V.
If the source of reference voltage is changed, the input switching has to be equilibrated
anew. (see also chapter "4.3. Calibration").
4.3. Calibration
If the AWA/2X12B module has to be eliquibrated anew,
remove the case's top by unscrewing the four cap nuts,
to get to the pontentiometer. Four multi-gear trimmer
called R36 is provided for this purpose.
4.3.1. Calibration during power input
Set a constant power source to the terminals 5 and 6.
The value of currency has to be known with great
accuracy. It should be in the range of 15 to 20 mA. Now
choose the menu in which this value is displayed in the
device (CamCon). You are able to increase this
displayed value by turning to the left at the R36 (input 1)
or R39 (input 2) or de-crease it by turning to the right.
Set the now present current or it's corresponding value
and seal the potentiometer with sealing wax.
4.3.2. Calibration during voltage-input 0 - +10V
Set a voltage source to the terminals 5 and 6. The value of voltage has to be known with great
accuracy. It should be in the range o+5 to +10 Volt. Now choose the menu in which this value is
displayed in the device (CamCon).You are able to increase this displayed value by turning to the left
at the R36 (input 1) or R39 (input 2) or de-crease it by turning to the right. Set the now present
voltage or it's corresponding value and seal the potentiometer with sealing wax.
Edition: Aug. 04
Page: 5
2 rue René Laennec 51500 Taissy France
Fax: 03 26 85 19 08, Tel : 03 26 82 49 29
E-mail:[email protected]
Site web : www.hvssystem.com
Digitronic
Automationsanlagen GmbH
Analog Digital Converter
AWA/SSI/12
5. Dimensions
The following mounting rails may be used to assemble the case:
NS 35 / 7.5 (DIN 50022), NS 35 / 15 (DIN 50022) oder NS 32 (DIN 50035)
6. Technical data
Voltage supply: ......................................................24VDC +-20%
Power conssumption: .............................................150 mA
Input ranges: .........................................................."0 - +10V" oder "0 - 20mA"
Input resistance:
at voltage input: .....................................................RL = 10 kOhm
at power input: .......................................................RL = 220 Ohm
Resolution:.............................................................12 Bit
Reference voltage source: .....................................+4.096V (standard), +5V oder external.
Data output: ...........................................................synchronous serial RS422, Graycode
corresponding to Stegmann "Tannenbaum".
Clock frequency: ....................................................maximum 1 MHz
minimum 100 kHz
Monoflop i.e. transforming time:.............................minimum 250 µs
Grounding: .............................................................via 4 * 6.3mm Flatplugs directly to be laid on rowgrounding pin.
Assembling: ...........................................................simply clamp upon carrier rail
according to EN 50 022, may be set in rows.
The following mounting rails may be used to
fasten the case: NS 35 / 7.5 (DIN 50022) NS 35 /
15 (DIN 50022) NS 32 (DIN 50035)
Disassembly:..........................................................by pulling back the snapping bars.
Protection: .............................................................Type of case: Phoenix UM corresponds to IP20
and cap made of 1mm galvanized tin
Dimensions: ...........................................................See also chapter 5. Dimensions.
Working temperaturer: ...........................................0°C ... + 50° C
Weight: ..................................................................approximately 400g
Edition: Aug. 04
Page: 6
2 rue René Laennec 51500 Taissy France
Fax: 03 26 85 19 08, Tel : 03 26 82 49 29
E-mail:[email protected]
Site web : www.hvssystem.com