B315-029-150 LRB24-SR

B315-029-150 LRB24-SR
B315-029-150, 6-Way, Characterized Control Valve
Chrome Plated Brass Ball and Nickel Plated Stem, 1/2“, NPT female ends
Application
The 6-way characterized control valve is ideal for chilled beams, radiant ceilings,
and Fan Coil Units offering reduced wiring by using a single actuator instead
of two. It eliminates the need for a change over valve and enables the use of a
single coil for heating and cooling.
Operation
A loop pressure relief is designed into port number two (2). This allows the
increased pressure to dissipate to the supply loop on port number one (1). This
is intended to release any pressure build up in the loop (coil) when the valve
is in the closed position and is isolated from the system expansion vessel. The
change in pressure occurs due to a change in the media temperature in the coil
while isolated from the pressure vessel. The pressure relief does not affect the
effi ciency of the system because cross-fl ow cannot occur between the heating
and cooling loops. The system loops (heating/cooling) should share a common
expansion vessel to keep the system pressure and volume balanced.
Date created, 05/11/2015 - Subject to change. © Belimo Aircontrols (USA), Inc.
Dimensions (Inches [mm])
Size [mm]
End Fitting
Body
Ball
Stem
Stem Packing
Seat
Seat O-ring
Characterized Disc
Body Pressure Rating [psi]
Media Temperature Range
(Water)
Max Differential Pressure (Water) 15 psi for typical applications
Close-Off Pressure
Leakage
H1
H2
D
C
G
M4
E
F
0.47” [12 mm]
97483
chilled , hot water, up to 60% glycol
linear
Sequence 1 - (0° to 30° angle)¹, Dead
zone - (30° to 60°), Sequence - 2 (60° to
90° angle)²
0.5“ [15]
NPT female ends
nickel plated brass
chrome plated brass
nickel plated brass
EPDM (lubricated)
Teflon® PTFE
EPDM
chrome plated steel
230
43°F to 180°F [6°C to 82°C]
0.87” [22 mm]
Technical Data
Service
Flow characteristic
Controllable Flow Range
1.26”
[32 mm]
B
A
1.69” [43 mm]
A
7.17“
[182]
B
3.11“
[79]
C
7.93“
[201] D
6.83“
[173]
E
1.58“
[40]
F
1.56“
[40]
G
1.73“
[44]
H1
1.18“
[30]
H2
0.5“
[15]
Application Notes
50 psi
0%
If assembled with a MFT actuator, it must be programmed for proportional
control only.
The control valve can be mounted either vertically or horizontally. Do not install
the valve with the stem pointing downwards.
Flow Patterns
Sequence 1
Sequence 2
Supply
To Coil
To Coil
Supply
Return
To Source
Return
From Coil
Return
From Coil
Return
To Source
800-543-9038 USA
A single expansion tank is recommended to ensure same pressure on
the heating and cooling loops, this helps to maintain energy efficiency by
eliminating migration of water from the cooling to the heating loop.
Maintenance: 6-Way characterized control valves and rotary actuators are
maintenance free.
Before any kind of service work is carried out, it is essential to isolate the
actuator from the power supply (by disconnecting the power).
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
LRB24-SR
Proportional, Non-Spring Return, 24 V, for 2 to 10 VDC or 4 to 20 mA
Wiring Diagrams
INSTALLATION NOTES
Actuators may be connected in parallel. Power consumption and input
impedance must be observed.
Actuators may also be powered by 24 VDC.
Only connect common to negative (-) leg of control circuits.
A 500 Ω resistor (ZG-R01) converts the 4 to 20 mA control signal to 2 to 10
VDC.
APPLICATION NOTES
Meets cULus requirements without the need of an electrical ground
connection.
Technical Data
Power Supply
Power Consumption Running
Power Consumption Holding
Transformer Sizing
Electrical Connection
Date created, 05/11/2015 - Subject to change. © Belimo Aircontrols (USA), Inc.
Overload Protection
Operating Range Y
Input Impedance
Feedback Output U
Angle of Rotation
Direction of Rotation (Motor)
Position Indication
Manual Override
Running Time (Motor)
Humidity
Ambient Temperature Range
Storage Temperature Range
Housing
Housing Material
Agency Listings†
Noise Level (Motor)
Servicing
Quality Standard
Weight
2271
!
24 VAC ± 20%, 50/60 Hz, 24 VDC ± 10%
1.5 W 0.4 W 3 VA (class 2 power source)
3 ft., 18 GA plenum cable with 1/2” conduit
connector
electronic thoughout 0° to 90° rotation
2 to 10 VDC, 4 to 20 mA (default)
WARNING! LIVE ELECTRICAL COMPONENTS!
During installation, testing, servicing and troubleshooting of this product, it
may be necessary to work with live electrical components. Have a qualified
licensed electrician or other individual who has been properly trained in
handling live electrical components perform these tasks. Failure to follow
all electrical safety precautions when exposed to live electrical components
could result in death or serious injury.
100 k  for 2 to 10 VDC (0.1 mA), 500  for 4 to
20 mA
2 to 10 VDC
90°, adjustable with mechanical stop
reversible with built-in switch
integrated into handle
external push button
90 seconds
5 to 95% RH non condensing (EN 60730-1)
-22°F to +122°F [-30°C to +50°C]
-40°F to +176°F [-40°C TO +80°C]
NEMA 2, IP42, UL enclosure type 2
UL94-5VA
cULus acc. to UL60730-1A/-2-14, CAN/CSA
E60730-1:02, CE acc. to 2004/108/EC and
2006/95/EC
<35 dB (A) maintenance free
ISO 9001
2.2 lb [1 kg]
2 to 10 VDC / 4 to 20 mA Control
24 VAC Transformer
Blk
Line
Volts
Control Signal (–)
VDC/mA (+)
2 to 10 VDC (–)
Feedback Signal (+)
(1)
Common
Red (2)
+ Hot
Wht (3)
Y Input, 2 to 10V
Org (5)
U Output
Ω
500 Ω
†Rated Impulse Voltage 800V, Type action 1.B , Control Pollution Degree 3.
800-543-9038 USA
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN