B315-029-029 LRX24-MFT

B315-029-029 LRX24-MFT
B315-029-029, 6-Way, Characterized Control Valve
Chrome Plated Brass Ball and Nickel Plated Stem, 1/2“, NPT female ends
Application
The 6-way characterized control valve is ideal for chilled beams, radiant ceilings,
and Fan Coil Units offering reduced wiring by using a single actuator instead
of two. It eliminates the need for a change over valve and enables the use of a
single coil for heating and cooling.
Operation
A loop pressure relief is designed into port number two (2). This allows the
increased pressure to dissipate to the supply loop on port number one (1). This
is intended to release any pressure build up in the loop (coil) when the valve
is in the closed position and is isolated from the system expansion vessel. The
change in pressure occurs due to a change in the media temperature in the coil
while isolated from the pressure vessel. The pressure relief does not affect the
effi ciency of the system because cross-fl ow cannot occur between the heating
and cooling loops. The system loops (heating/cooling) should share a common
expansion vessel to keep the system pressure and volume balanced.
Date created, 05/11/2015 - Subject to change. © Belimo Aircontrols (USA), Inc.
Dimensions (Inches [mm])
Size [mm]
End Fitting
Body
Ball
Stem
Stem Packing
Seat
Seat O-ring
Characterized Disc
Body Pressure Rating [psi]
Media Temperature Range
(Water)
Max Differential Pressure (Water) 15 psi for typical applications
Close-Off Pressure
Leakage
H2
D
C
G
M4
E
F
1.26”
[32 mm]
B
A
1.69” [43 mm]
A
7.17“
[182]
B
3.11“
[79]
C
7.93“
[201] D
6.83“
[173]
E
1.58“
[40]
F
1.56“
[40]
G
1.73“
[44]
H1
1.18“
[30]
H2
0.5“
[15]
Application Notes
50 psi
0%
If assembled with a MFT actuator, it must be programmed for proportional
control only.
Please dispose of this device in a safe and environmentally responsible manner, according to any locally
valid regulations and requirements.
Flow Patterns
Sequence 1
H1
0.47” [12 mm]
97479
chilled , hot water, up to 60% glycol
linear
Sequence 1 - (0° to 30° angle)¹, Dead
zone - (30° to 60°), Sequence - 2 (60° to
90° angle)²
0.5“ [15]
NPT female ends
nickel plated brass
chrome plated brass
nickel plated brass
EPDM (lubricated)
Teflon® PTFE
EPDM
chrome plated steel
230
43°F to 180°F [6°C to 82°C]
0.87” [22 mm]
Technical Data
Service
Flow characteristic
Controllable Flow Range
Sequence 2
The control valve can be mounted either vertically or horizontally. Do not install
the valve with the stem pointing downwards.
A single expansion tank is recommended to ensure same pressure on
the heating and cooling loops, this helps to maintain energy efficiency by
eliminating migration of water from the cooling to the heating loop.
Maintenance: 6-Way characterized control valves and rotary actuators are
maintenance free.
Supply
To Coil
To Coil
Supply
Return
To Source
Return
From Coil
Return
From Coil
Return
To Source
800-543-9038 USA
Before any kind of service work is carried out, it is essential to isolate the
actuator from the power supply (by disconnecting the power).
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
LRX24-MFT
Proportional, Non-Spring Return, 24 V, Multi-Function Technology®
Wiring Diagrams
INSTALLATION NOTES
Actuators may be connected in parallel. Power consumption and input
impedance must be observed.

Actuators may also be powered by 24 VDC.
Actuators Hot wire must be connected to the control board common. Only
connect common to neg. (-) leg of control circuits. Only connect common to
neg. (-) leg of control circuits. Terminal models (-T) have no-feedback.
A 500 Ω resistor (ZG-R01) converts the 4 to 20 mA control signal to 2 to 10
VDC.
Technical Data
Power Supply
Power Consumption Running
Power Consumption Holding
Transformer Sizing
Electrical Connection
Overload Protection
Operating Range Y
Input Impedance
Date created, 05/11/2015 - Subject to change. © Belimo Aircontrols (USA), Inc.
Feedback Output U
Angle of Rotation
Position Indication
Manual Override
Running Time (Motor)
Control signal may be pulsed from either the Hot (Source) or Common (Sink)
24 VAC line.
2260
For triac sink the common connection from the actuator must be connected
to the hot connection of the controller. Contact closures A & B also can be
triacs. A & B should both be closed for the triac source and open for triac
sink.
24 VAC ± 20%, 50/60 Hz, 24 VDC ± 10%
2.5 W 
1.2 W 
3.5 VA (class 2 power source)
3 ft., 18 GA plenum cable with 1/2” conduit
connector
APPLICATION NOTES
electronic thoughout 0° to 90° rotation
2 to 10 VDC, 4 to 20 mA (default), variable (VDC,
floating point, on/off)
100 k  for 2 to 10 VDC (0.1 mA), 500  for 4 to
20 mA, 1500  for PWM and on/off
2 to 10 VDC, 0.5 mA max, VDC variable
90°, adjustable with mechanical stop
integrated into handle
external push button
150 seconds (default), variable (35 to 150 seconds)
Humidity
Ambient Temperature Range
Storage Temperature Range
Housing
Housing Material
Agency Listings†
5 to 95% RH non condensing (EN 60730-1)
-22°F to +122°F [-30°C to +50°C]
-40°F to +176°F [-40°C TO +80°C]
NEMA 2, IP42, UL enclosure type 2
UL94-5VA
cULus acc. to UL60730-1A/-2-14, CAN/CSA
E60730-1:02, CE acc. to 2004/108/EC and
2006/95/EC
Noise Level (Motor)
Servicing
Quality Standard
Weight
<35 dB (A) 
maintenance free
ISO 9001
2.2 lb [1 kg]
Meets cULus requirements without the need of an electrical ground
connection.
WARNING! LIVE ELECTRICAL COMPONENTS!
!
During installation, testing, servicing and troubleshooting of this product, it
may be necessary to work with live electrical components. Have a qualified
licensed electrician or other individual who has been properly trained in
handling live electrical components perform these tasks. Failure to follow
all electrical safety precautions when exposed to live electrical components
could result in death or serious injury.
Floating Point
24 VAC Transformer (AC Only)
1
10
11
Blk (1) Common
Line
Volts
Red (2) + Hot
Wht (3) Y1 Input
Pnk (4) Y2 Input
(–)
Position Feedback VDC (+)
Org (5) U Output
VDC/mA Control
†Rated Impulse Voltage 800V, Type action 1.B , Control Pollution Degree 3.
24 VAC Transformer
On/Off
1
1
3
11
Line
Blk (1) Common
Volts
Red (2) + Hot
(–)
Position
Feedback VDC (+)
800-543-9038 USA
Control Signal (–)
VDC / mA (+)
5
11
Blk (1) Common
Line
Volts
24 VAC Transformer
3
Red (2) + Hot
500 Ω
Ω 1/4
watt
Wht (3) Y1 Input
7
Pnk (4) Y2 Input
Org (5) U Output
Wht (3) Y1 Input
Pnk (4) Y2 Input
Org (5) U Output
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
LRX24-MFT
Proportional, Non-Spring Return, 24 V, Multi-Function Technology®
PWM Control
24 VAC Transformer (AC only)
1
8
11
Line
Blk (1)
Common
Volts
Red (2)
+ Hot
Wht (3)
Y1 Input
Position (–)
Pnk (4)
Y2 Output
Feedback VDC (+)
Org (5)
U Output
Override Control
A
24 VAC Transformer (AC Only)
1
5
Blk (1) Common
Line
Volts
Ω
(–)
Control Signal
VDC / mA (+)
C
7
Min
Mid
A
B
12
Red (2) + Hot
Wht (3) Y1 Input
Pnk (4) Y2 Input
Org (5) U Output
Functions
0%
a
b
c
50%
Max
800-543-9038 USA
Date created, 05/11/2015 - Subject to change. © Belimo Aircontrols (USA), Inc.