Flame Detectors IR + UV
FLV45 FLV45A FLV45A-AL
INFORMAZIONI TECNICHE
TECHNICAL ADVANTAGES
• high speed of intervention
• wide area surveillance
• immunity to false alarms
• possibility of safe operation
in environments with large perturbations
in the visual field
APPLICATIONS
• fire detection in fuel stores (petrol, oil,
kerosene,etc.).
• flammable chemicals
• storage of paints
• storage of paper products
• timber storage
• chemical laboratories
• deposits of flammable gases
The flame detectors FLV-45 are suited for electronic fire
detection systems where the speed response is of primary
importance. They are able to detect the presence of a flame (target
flame - see the technical data below) up to 25 m, easy to install
and are very reliable.
These detectors find particular application in the places where it
is presumed that a fire may develop quickly, such as in warehouses
of petroleum products, paints, plastics, alcohols, etc. The
principle of operation of these detectors is the detection of the
infrared IR and ultraviolet UV components of the flame. The flame
emits a very broad spectrum of radiation ranging from ultraviolet
to infrared range.
The detection of both infrared and ultraviolet components is a
clear evidence of the presence of the flame.
Two special UV and IR sensors, through a suitable window of
vision, “watch “ the supervised area . When inside this is generated
a flame due to start of fire, the IR and UV radiation emitted by
the flame itself, are readily detected by the sensor which , through
appropriate associated electronics, will trigger an output relay
for sending the alarm signal.
The electronic board is accompanied by special algorithms to
give the detector a high immunity to false alarms.
The detector has a sensitivity adjustment independent for the two
channels IR and UV in order to allow a perfect adaptation to the
environmental conditions.
TECHNICAL DATA
• supply voltage: 12 or 24 VDC
• protection against reverse polarity
• current: 100 mA
• maximum detection distance: 25m (referred to hydrocarbons
target flame - height 20 cm - tray 33x33x5 cm)
• viewing angle: 120 °
• sensitivity adjustment: channel IR and UV-independent
• adjustable time delay: 5-10-20-30sec with dip-switch
• equipped with a swivel mounting bracket for wall or ceiling
for easy orientation (FLV45A and FLV45A-AL)
• analog output: 0-5V
• OC output (Open Collector) Alarm
• OC output (Open Collector) Fault
• relay output: 0.5 A/24Vcc - full exchange
• LEDs: Alarm, Fault, IR and UV (active)
• plastic enclosure
• protection: IP65
• electromagnetic immunity: conforms to standards EN50130
The detectors can be supplied in 3 models:
• FLV45 - basic version - without bracket
• FLV45A - model equipped with swivel bracket that allows
the proper orientation and installation on wall or ceiling
• FLV45A-AL - how FLV45A model but with box made of
aluminum alloy
• dimensions: FLV45=142x82x54
FLV45A=142x82x148
FLV45A-AL=142x82x150mm
• weights: FLV45=350gr FLV45A=400gr FLV45A-AL=1,2kg
EDS - V. Ca' Nova Zampieri 6 - 37057 S. G. Lupatoto - VERONA - Tel. 0039045547529 - Fax. 00390458750065 - Email: [email protected] - Web: www.eds.eu
FLV45A-AL
FLV45A-AL PROTECTION AREA
25[m]
15
20
10
5
5
10
15
20
25[m]
5
25
10
60
60
50
15
50
50
45
20
45
40
35
35
20
25
20
10
distanza [m]
distance [m]
75
40
0
[gradi]
[degree]
DS1954
100%
10
sensibilità
sensitivity
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertisement