: Efficient solutions for motor control Product information Motor contactors DIL M

: Efficient solutions for motor control Product information Motor contactors DIL M
: Efficient solutions
for motor control
The complete range of contactors, efficient motor-starters
and controlled drives for the
motor circuit. New simple to
install solutions based on
clever communication.
Contactors DIL
Product information
Motor contactors DIL M
Motor-protective
circuit-breakers PKZ
Motor-starters MSC
Motor-protective
circuit-breakers PKZ
Motor-starters MSC
Softstarters DS 4
Drives
Rapid Link
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616
xStart is the intelligent solution:
easier engineering, faster fitting
1
2
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616
“We need a partner we can rely on.
Moeller satisfies all of our needs.“
Both trade and industry expect innovations in
electrical engineering to bring them clear
advantages by making processes more efficient
– all the way from the planning stage through
engineering to fitting and installation. The new
xStart range from Moeller does just that.
With Moeller you can meet any
challenge!
Moeller has proved its competence as
a partner with high-quality, efficient
motor-related solutions for more than
a century. xStart now offers you the
complete range of products needed for
switching, protecting, starting, running
up and controlling motors. You can rely
on our competence in each of these
areas, and we can meet any challenge
from contactors to drive control.
1
The latest innovation is the new
MSC motor-starter: a combination of standard components, i.e.
the new DIL M motor contactors
and the optimised PKZ motorprotective circuit-breakers.
Just four slim starter modules
up to 170 A, each with the same
dimensions for AC and DC,
significantly simplify planning
and engineering.
2
The newly developed DIL M
motor contactors can switch
motors up to 170 A. Their significantly improved performance
criteria such as pick-up and
sealing consumption, space
saving foot-prints and ease of
installation make these contactors state-of-the-art, top-class
product.
Tested quality
Every single one of our products is built
and tested to the latest national and
international standards. Having attained
all the major approvals, they are perfectly
suited to the world's market.
2
3
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616
Motor-protective
circuit-breakers PKZ:
now better than ever
A!
p to 32
!
Now u
to 12 A
p
u
A
150 k
A!
p to 32
50 kA u
Motor-protective
circuit-breakers PKZ
from Moeller have
long set the benchmark for quality. And
now, for inclusion in
the xStart concept,
these products have
been updated once
again, and enhanced
in terms of their technical specification.
The PKZM 0 now switches motors up
to 32 A. At the same time, its shortcircuit switching capacity is significantly
increased: the short-circuit rating
(400 V) is now 150 kA up to 10 A and
50 kA up to 32 A. The PKZM 4 also has
a switching capacity of 50 kA. This simplifies the engineering of safety and
reliability, with current limiters becoming
virtually obsolete. PKZM 01 is a completely new product with push-button
operation for switching motors up to
25 A (50 kA/400 V).
“Motor-protective circuit-breakers PKZ
are, and always will be, the epitome
of safety, reliability and quality in
motor protection.“
4
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616
1
2
3
5
6
45 mm
55 mm
4
Common accessories throughout the
system
Whether PKZM 0, PKZM 01 or PKZM 4,
the accessories are always the same.
Whether On or Off, overload or short
circuit, differential indication helps to
locate the cause of tripping without
delay, every time. The auxiliary contacts
can be fitted without tools and are failsafe in the way they signal every switching state. One particularly convenient
component is the NHI-E front auxiliary
contact that can be optionally built into
already installed and wired circuitbreakers. It goes without saying that all
the auxiliary contacts and releases are
worldmarket devices, for all the customary mains voltages.
1
Shunt trips and undervoltage
trips
2
Motor-protective circuit-breakers
PKZM 0: from 0 to 32 A
3
Motor-protective circuit-breakers
PKZM 4 from 10 to 65 A
4
5
6
The optionally integrable front
auxiliary contact indicates the
switching position of 1 NO and
NC contact or 1 NO contact
Trip-indicating contacts: two
contacts provide differential indication of short circuit or overload
Standard auxiliary contacts with
up to three contacts for the
On/Off switching position
The door coupling handle (IP 65) has a
tripped position in addition to the On
and Off positions.
Motor-protective circuit-breakers
PKZM 01 easy to operate by pressing
or hitting a button
The new motor-protective circuitbreakers PKZM 01 for motors up to
25 A are ideally suited to small machines
and applications where operation by
pressing or even hitting a button is
preferred. In addition to the auxiliary
contacts from the PKZM 0 range, special
enclosures with ingress protection IP 65
or IP 40 and the appropriate EmergencyStop buttons are available for these
new components. Their short-circuit
switching capacity is 50 kA.
5
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616
AC and DC contactors:
both the same frame size –
simplifies engineering
Great efficiency in
planning and engineering with AC and
DC contactors is
achieved by them
being the same dimensions. With only four
component sizes
covering the rating
range up to 170 A
engineering is further
simplified.
Definitely useful: up to 32 A, the auxiliary
contact is already built in, and the DC
contactors include a suppressor circuit up
to 170 A. From 12 A, the DC contactors
have an electronic drive that removes
the need for coupling relays. With all
these extras already included in the contactors, your costs are clearly reduced.
DC
DC
AC
DC contactors now are no bigger
than AC contactors
The new contactors DIL are significantly
more compact than their predecessors,
even though, up to 32 A, the auxiliary
contact is included. The advantage of
this is particularly striking with the DC
contactors that now are the same size
as their AC counterparts. This makes
everything easier, i.e. planning, engineering and fitting, without having to
alter the control system, even if the control current has to change for another
customer.
6
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616
a sealing consumption of only 0.5 Watt,
even those at 170 A only use 1.5 Watt.
This also results in lower power consumption for the whole installation.
2
“With these new motor contactors,
Moeller is definitely on to a winner.
They bring real advantages from the
planning all the way to the fitting
costs.”
1
This reduces the cost of your
control panel
The space-saving is achieved not just by
the reduced component dimensions,
but also due to the lower heat dissipation that, particularly with the DC contactors, helps keep the cabinet size
down and saves the cost of a fan. The
significantly reduced sealing consumption achieved by innovative, electronic
drives makes this possible. The Moeller
DC contactors from 17 up to 72 A have
No compromise where termination reliability is concerned
DIL contactors up to 170 A have box
terminals with two clamping chambers,
allowing unequal cable cross-sections
to be terminated absolutely securely,
even in strongly vibrating machines.
This makes wiring easier and cuts down
on associated errors.
3
1
The benefits of the electronically controlled drive
All DC motor contactors from DIL M17
have an electronically controlled drive
that offers the following advantages:
• Significantly less heat dissipation due
to reduced sealing consumption
• Smaller control transformers because
of lower pick-up consumption
• Direct actuation from the PLC without
coupling contactors up to 32 A.
2
3
4
5
4
5
The new auxiliary contacts DIL A
perfectly complement the new
motor contactors DIL M.
Overload relays Z protect the
motor against phase failure or
overload. Their auxiliary contacts
switch the motor contactor off,
and signal the fault. These relays
are suitable for protecting EEx
e-motors according to ATEX 100
a guideline.
7
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616
The simplicity of it! –
Toolless plug connection!
8
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616
Using the new xStart
motor-starter combinations it is possible to
create the best solutions from standard
products even more
easily and efficiently.
Moeller has optimised the DIL and PKZ
standard products in such a way that,
by using simple toolless plug connectors,
they can be assembled to form reliable
motor-starters. Without the need for
tools! The motor-starter combinations
MSC can also be supplied as complete
devices. Costs for fitting and wiring can
be considerably reduced in this way.
Costs for testing are cut and errors are
prevented from the start. Another advantage lies in increased safety during
maintenance work where removal of
the combination plug connector produces a visible isolating gap. This Moeller
technology is available on our direct-online and reversing starters up to 15.5 A.
Slim solutions: DOL starters from
standard components
The new direct-on-line starters built
from standard components are available
in four slim frame sizes. The contactor
and the protective switch are of the
same compact width dimension. Thus
you lose not a millimetre of control panel
space. The convenient MSC motorstarters using toolless plug connection
technology are available up to 15.5 A and
require only a top-hat rail for mounting.
The mechanical connector ensures a
secure hold and the electrical connector
provides optimum reliability and safety.
Complete mounting connectors are
offered for DOL and reversing starters
from 17 up to 32 A. This prevents fitting
errors and cuts down on wiring time.
Plug and go: reversing starters from
standard components
The reversing starters offer distinct advantages to the assembler. Instead of
laboriously having to tighten up 21
screws, a small number of components
simply plug together. This of course
speeds up fitting work, and means fewer
errors and a very clearly laid out
switching installation.
Speedier wiring using spring-loaded
terminations
“The toolless plug connection is
very quick to fit – just what I need
to reduce costs.”
Moeller provides proven quality with
tension clamp terminals. Numerous
tests have proved that contactors and
motor-protective circuit-breakers are
just as securely wired in this way as by
screw connection – even in strongly
vibrating machines. But wiring work
using tension clamp terminals is very
much quicker to do. The main current
paths on PKZM 0 and motor contactors
up to 12 A all use spring-loaded terminals. The sundries for termination are
always available for both screw and
tension clamp connection.
9
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616
Reversing starters
with mechanical interlock –
as compact as it gets!
Reversing starters and star-delta
combinations up tp 15.5 A can be
combined without tools.
up to 12 A
Moeller has significantly reduced the
wiring costs with reversing and stardelta combinations using tool-less plug
connections. Moeller DIL M contactors
up to 15.5 A feature sockets in which
the connection elements are simply
plugged in as standard and without
additional expense. Thus, costs
associated with operations such as
cutting wires to length, stripping of
insulation, work on the wire ends and
provision of conductors with markings,
as well as application of defined torques
when tightening screws, have been
totally eliminated. Inspection of 21
electrical connections between the
mains and the star and delta contactor
are reduced to a simple visual inspection.
A measurement with test device probes
can be undertaken without having to
remove the connection elements.
up to 32 A
up to 65 A
up to 150 A
Precious space is provided in the
control panel by the narrow widths of
just 55 mm on contactors up to 65 A.
The mechanical interlocks which are
usually found on reversing contactor
combinations do not require any
additional space from Moeller. The
smart, patented solution is a plastic
sphere. It is simply inserted into
the side cavities provided on both
contactors and reliably prevents
simultaneous switch on. Furthermore,
a lateral clearance between the
contactors is not required –
the contactors can be mounted and
wired side-by-side.
Generally, DC contactors in the range
up to 65 A have a longer depth than
AC contactors. However, with xStart –
thanks to electronically supported
magnet systems – all dimensions of
the DC variants are identical to those
of the AC variants. If the manufacturer
of mass produced machines uses
differing control voltages, the testing
of the control panel layout is now
eliminated, the DC contactors are
simply positioned on the top-hat rail
or mounting plate in the same manner
as the AC variants.
The heat dissipation limits the packing
density in control panels. Solutions
which are possible from a purely
mechanical viewpoint cannot be
implemented due to heat dissipation
considerations. The extremely low
holding power of just 0.5 W with
Moeller DC contactors now enables
solutions which were previously
impossible.
10
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616
Mounting rail adapter with new
flexibility
Optimum compatibility:
Starters and busbar adapters
The switchgear interconnected with
the three phase commoning links is
generally snapped onto a mounting rail.
The result is an additional benefit where
components can be easily removed from
an interconnected group by offsetting
the adapter mounting rail without
having to disassemble the entire three
phase commoning link.
The xStart system has been extended
by the new busbar adapter, which is
compatible with the busbar system and
the system accessories from Wöhner,
the market leader in this field.
Conformity to the standard ensures
that busbar adapters for 60 mm busbar
clearances fit all similar manufacturers
systems. An additional benefit is that
the busbar adapter material used
worldwide is a standard copper profile.
Prefabricated connectors or the new
tool-less plug connections are available
for establishing connections between
circuit-breakers and contactors.
With large and uniform requirements,
Moeller supplies the adapter fitted
complete with switchgear for DOL and
reversing starters.
Simply select tested motor starters to approval types I and II
The DOL starter (complete unit) consists
of a Motor-protective circuit-breaker
PKMZ 0 and a contactor DILM.
Moeller provides a PC-based electronic
selection program for motor starters in
addition to the comprehensive selection
page in the Moeller main catalogue.
This program considers various
operating voltages, short-circuit ratings
and coordination types, as well as
fuseless and fused combinations.
This small program is available from
Moeller free of charge on the Internet.
Moeller has provided the practicallyminded with a carton selection slider
for a number of years.
www.moeller.net/select
11
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616
Contactors DIL M7 – 170
Contactor relays DILA
DILM basic units
AC-3
DILM17 – DILM32
Ith =
Ie
Ie
P
A
A
kW
7
3
7
3
9
4
9
4
12
5.5
12
5.5
15.5
7.5
15.5
7.5
4-pole
–
–
5
2
5
3-pole
18
7.5
35
18
7.5
35
25
11
40
25
11
40
32
15
40
32
15
40
40
18.5
50
50
22
65
65
30
80
72
37
80
80
37
110
95
45
115
55
150
75
170
90
5
2
5
4
3
3
20
DILM40 – DILM170
1
1
1
1
Open
380 V 380 V
400 V 400 V
3-pole
DILM7 – DILM12
AC-3
4
1. Basic units
2. Suppressor 1)
3. Auxiliary contact modules, 2-pole
4. Auxiliary contact modules, 4-pole
5. Overload relays
1)
For AC operated contactors 50-60 Hz;
in DC operated contactors, the suppressor circuit is incorporated.
Note drop-out delay
12
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616
160
185
Contacts
Can be combined
with auxiliary
contact
AC operation
DC actuation
Part no.
Article no.
230 V 50 Hz
240 V 60 Hz
Part no.
Article no.
230V 50/60 Hz
Part no.
Article no.
24 V 50/60 Hz
Part no.
Article no..
110 V 50 Hz,
120 V 60 Hz
Part no.
Article no.
110V 50/60Hz
Part no.
Article no.
24 V DC
1 N/O
DILM32-XHI..
DILA-XHI(V)..
DILM7-10(...)
276550
DILM7-10(...)
276558
DILM7-10(...)
276554
DILM7-10(...)
276547
DILM7-10(...)
276556
DILM7-10(24VDC)
276565
1 N/C
DILA-XHI(V)..
DILM7-01(...)
276585
DILM7-01(...)
276593
DILM7-01(...)
276589
DILM7-01(...)
276582
DILM7-01(...)
276591
DILM7-01(24VDC)
276600
1 N/O
DILM32-XHI..
DILA-XHI(V)..
DILM9-10(...)
276690
DILM9-10(...)
276698
DILM9-10(...)
276694
DILM9-10(...)
276687
DILM9-10(...)
276696
DILM9-10(24VDC)
276705
1 N/C
DILA-XHI(V)..
DILM9-01(...)
276725
DILM9-01(...)
276733
DILM9-01(...)
276729
DILM9-01(...)
276722
DILM9-01(...)
276731
DILM9-01(24VDC)
276740
1 N/O
DILM32-XHI..
DILA-XHI(V)..
DILM12-10(...)
276830
DILM12-10(...)
276838
DILM12-10(...)
276834
DILM12-10(...)
276827
DILM12-10(...)
276836
DILM12-10(24VDC)
276845
1 N/C
DILA-XHI(V)..
DILM12-01(...)
276865
DILM12-01(...)
276873
DILM12-01(...)
276869
DILM12-01(...)
276862
DILM12-01(...)
276871
DILM12-01(24VDC)
276880
1 N/O
DILM32-XHI..
DILA-XHI(V)..
DILM15-10(...)
290058
DILM15-10(...)
290066
DILM15-10(...)
290062
DILM15-10(...)
290055
–
DILM15-10(24VDC)
290073
1 N/C
DILA-XHI(V)..
DILM15-01(...)
290093
DILM15-01(...)
290101
DILM15-01(...)
290097
DILM15-01(...)
290090
–
DILM15-01(24VDC)
290108
–
DILM32-XHI..
DILA-XHI(V)..
DILMP20(...)
276970
DILMP20(...)
276978
DILMP20(...)
276974
DILMP20(...)
276967
–
DILMP20(24VDC)
276985
1 N/O
DILM32-XHI..
DILA-XHI(V)..
DILM17-10(...)
277004
DILM17-10(...)
277012
DILM17-10(...)
277008
DILM17-10(...)
277001
DILM17-10(...)
277010
DILM17-10(RDC24)
277018
1 N/C
DILA-XHI(V)..
DILM17-01(...)
277036
DILM17-01(...)
277044
DILM17-01(...)
277040
DILM17-01(...)
277033
DILM17-01(...)
277042
DILM17-01(RDC24)
277050
1 N/O
DILM32-XHI..
DILA-XHI(V)..
DILM25-10(...)
277132
DILM25-10(...)
277140
DILM25-10(...)
277136
DILM25-10(...)
277129
DILM25-10(...)
277138
DILM25-10(RDC24)
277146
1 N/C
DILA-XHI(V)..
DILM25-01(...)
277164
DILM25-01(...)
277172
DILM25-01(...)
277168
DILM25-01(...)
277161
DILM25-01(...)
277170
DILM25-01(RDC24)
277178
1 N/O
DILM32-XHI..
DILA-XHI(V)..
DILM32-10(...)
277260
DILM32-10(...)
277268
DILM32-10(...)
277264
DILM32-10(...)
277257
DILM32-10(...)
277266
DILM32-10(RDC24)
277274
1 N/C
DILA-XHI(V)..
DILM32-01(...)
277292
DILM32-01(...)
277300
DILM32-01(...)
277296
DILM32-01(...)
277289
DILM32-01(...)
277298
DILM32-01(RDC24)
277306
–
DILM150-XHI(V)..
DILM1000-XHI(V)..
DILM40(...)
277766
DILM40(...)
277774
DILM40(...)
277770
DILM40(...)
277763
DILM40(...)
277772
DILM40(RDC24)
277780
–
DILM50(...)
277830
DILM50(...)
277838
DILM50(...)
277834
DILM50(...)
277827
DILM50(...)
277836
DILM50(RDC24)
277844
–
DILM65(...)
277894
DILM65(...)
277902
DILM65(...)
277898
DILM65(...)
277891
DILM65(...)
277900
DILM65(RDC24)
277908
–
DILM72(...)
107670
–
–
–
–
DILM72(RDC24)
107671
–
DILM80(...)
239402
DILM80(...)
239414
DILM80(...)
239406
DILM80(...)
239399
DILM80(...)
239408
DILM80(RDC24)
239416
–
DILM95(...)
239480
DILM95(...)
239488
DILM95(...)
239484
DILM95(...)
239477
DILM95(...)
239486
DILM95(RDC24)
239510
–
DILM115(RAC240)
239548
DILM115(RAC240) DILM115(RAC24)
239548
239545
DILM115(RAC120) DILM115(RAC120)
239547
239547
DILM115(RDC24)
239555
–
DILM150(RAC240)
239588
DILM150(RAC240) DILM150(RAC24)
239588
239585
DILM150(RAC120) DILM150(RAC120)
239587
239587
DILM150(RDC24)
239591
–
DILM170(RAC240)
107013
DILM170(RAC240) DILM170(RAC24)
107013
107010
DILM170(RAC120) DILM170(RAC120)
107012
107012
DILM170(RDC24)
107016
The listed auxiliary and main contacts up to 12 A are available with springloaded terminals.
The auxiliary contact modules listed for the DILA contactor relay can also be used for the DILM contactors up to 32 A.
Auxiliary contact members: DILA-XHI to EN 50005, DILM32-XHI to DIN 50012
The 2- and 4-pole DILM32-XHI... auxiliary contact modules can not be combined with DILM...-01 contactors.
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616
13
Auxiliary contact modules2)
Ith = Ie
Contacts
Can be combined
with basic units
open
A
2-pole
10
1 N/O
1 N/C
2 N/C
4-pole
2 N/O
2 N/C
2-pole
2 N/O
–
1 N/O
1 N/C
–
2 N/C
2-pole
4-pole
–
2-pole
10
Article no.
N/CE = Early-make contacts
N/OL = Late-break contacts
–
4-pole
Part no.
DILM7-10...
DILM9-10...
DILM12-10...
DILM15-10...
DILM17-10...
DILM25-10...
DILM32-10...
DILM7...
DILM9...
DILM12...
DILM15...
DILM17...
DILM25...
DILM32...
DILM32-XHI11
277376
DILM32-XHI02
277375
DILM32-XHI22
277377
DILA-XHI20
276422
DILA-XHI11
276421
DILA-XHI02
276420
1 N/OE
1 N/CL
4 N/O
–
3 N/O
1 N/C
2 N/O
2 N/c
1 N/O
3 N/C
DILA-XHI13
276425
–
4 N/C
DILA-XHI04
276424
1 N/O, 1 N/OE
1 N/C, 1 N/CL
2 N/O
–
1 N/O
1 N/C
DILM40...
DILM50...
DILM65...
DILM80...
DILM95...
DILM115...
DILM150...
DILA-XHIV11
276423
DILA-XHI40
276428
DILA-XHI31
276427
DILA-XHI22
276426
DILA-XHIV22
276429
DILM150-XHI20
277945
DILM150-XHI11
277946
DILM150-XHI02
277947
DILM150-XHI40
277948
DILM150-XHI31
277949
DILM150-XHI22
277950
–
2 N/C
4 N/O
–
3 N/O
1 N/C
2 N/O
2 N/C
1 N/O
3 N/C
DILM150-XHI13
277951
–
4 N/C
DILM150-XHI04
277952
1 N/O, 1 N/OE
1 N/C, 1 N/CL
DILM150-XHIV22
277953
1 N/O
1 N/C
DILM1000-XHI11-SI
278425
1 N/O
1 N/C
DILM150-XHIA111)
283463
The listed auxiliary and main contacts up to 12 A are available with springloaded terminals.
The auxiliary contact modules listed for the DILA contactor relay can also be used for the DILM contactors up to 32 A.
Auxiliary contact members: DILA-XHI to EN 50005, DILM32-XHI to DIN 50012
The 2- and 4-pole DILM32-XHI... auxiliary contact modules can not be combined with DILM...-01 contactors.
1)
NEW: Also available as 4-pole version DILM150-XHIA22 with terminal markings 53/54, 61/62, 71/72 and 83/84
(Article no. 283464) in order to avoid duplication of terminal markings on combinations with auxiliary contact on the side.
2)
The following applies for all auxiliary contact modules: Ie=3 A for AC-15 at 380 V, 400 V, 415 V
14
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616
Accessories
Us
V AC
For use with
Part no.
Article no.
Notes
Suppressor
24 – 48
DILM12-XSPV48
281208
Varistor suppressor
48 – 130
DILM7 – DILM15
DILMP20
DILA
DILM12-XSPV130
281209
DILM12-XSPV240
281210
For AC operated contactors,
50-60 Hz,
DC operated contactors
have an integrated suppressor
Note drop-out delay
DILM12-XSPV500
281211
130 – 240
240 – 500
DILM32-XSPV48
281212
48 – 130
DILM32-XSPV130
281213
130 – 240
DILM32-XSPV240
281214
240 – 500
DILM32-XSPV500
281215
24 – 48
A1
DILM17 – DILM32
A2
DILM95-XSPV48
281216
48 – 130
DILM95-XSPV130
281217
130 – 240
DILM95-XSPV240
281218
240 – 500
DILM95-XSPV500
281219
DILM12-XSPVL48
281220
DILM12-XSPVL240
281221
DILM32-XSPVL48
281222
DILM32-XSPVL240
281223
DILM95-XSPVL48
281224
DILM95-XSPVL240
281225
DILM12-XSPR48
281199
DILM12-XSPR240
281200
DILM12-XSPR500
281201
DILM32-XSPR48
281202
DILM32-XSPR240
281203
DILM32-XSPR500
281204
DILM95-XSPR48
281205
110 – 240
DILM95-XSPR240
281206
240 – 500
DILM95-XSPR500
281207
DILM7 – DILM65
DILA
DILM32-XVB
281227
DILM80 – DILM150
DILM7 – DILM15
DILMP20
DILA
DILM150-XVB
281226
DILM12-XMV
281196
DILM17 – DILM32
DILM32-XMV
281197
DILM40 – DILM65
DILM65-XMV
281198
DILM80 – DILM150
DILM150-XMV
240081
24 – 48
Varistor suppressors with
built-in LED
DILM40 – DILM95
24 – 48
130 – 240
24 – 48
DILM7 – DILM15
DILMP20
DILA
DILM17 – DILM32
130 – 240
A1
A2
24 – 48
DILM40 – DILM95
130 – 240
RC suppressor
24 – 48
130 – 240
DILM7 – DILM15
DILMP20
DILA
240 – 500
24 – 48
DILM17 – DILM32
110 – 240
A1
240 – 500
24 – 48
A2
Connector
For the mechanical
connection of contactors
to groups of components
Mechanical
interlock
DILM40 – DILM95
For AC operated contactors,
50-60 Hz,
DC operated contactors
have an integrated suppressor
Note drop-out delay
For AC operated contactors,
50-60 Hz,
DC operated contactors
have an integrated suppressor
Note drop-out delay
0 mm distance between contactors
For two contactors with AC or DC
operation, distance between
contactors 0 mm, mechanical
lifespan 2.5 X 10 6 switching
operations, additional auxiliary
contact modules can be fitted
15
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616
Technical data
DIL M7
DIL M9
DIL M12
DIL M15
10
10
10
10
General
Lifespan, mechanical
AC operated
DC operated
Operations
x 106
Operations
6
x 10
10
10
10
10
open
°C
–25/60
–25/60
–25/60
–25/60
Make contact
g
10
10
10
10
Make contact
g
7
7
7
7
Break contact
g
5
5
5
5
AC operated
kg
0.23
0.23
0.23
0.23
DC operated
kg
0.28
0.28
0.28
0.28
Ambient temperature
Mechanical shock resistance (IEC/EN 60068-2-27)
Half-sinusoidal shock
Main contacts
Auxiliary contacts
Weight
Terminal capacity, screwed
Terminal capacity, main contacts
mm2
Solid
1 x (0.75 – 4)
2 x (0.75 – 2.5)
2
Flexible with ferrule
mm
1 x (0.75 – 4)
2 x (0.75 – 2.5)
mm2
Stranded
Solid or stranded
Flat conductor
Number of layers
–
–
–
–
AWG
18 – 10
18 – 10
18 – 10
18 – 10
mm
–
–
–
–
x width x thickness
Terminal capacity, auxiliary contacts
mm2
Solid
1 x (0.75 – 4)
2 x (0.75 – 2.5)
Flexible with ferrule
mm2
Solid or stranded
AWG
18 – 10
18 – 10
18 – 10
18 – 10
690
690
690
690
1 x (0.75 – 2.5)
2 x (0.75 – 2.5)
Main contacts
Rated insulation voltage
Ui
V AC
Rated operational voltage
Ue
V AC
690
690
690
690
A
112
112
144
155
220/230 V
A
70
90
120
124
380/400 V
A
70
90
120
124
500 V
A
50
70
100
100
660/690 V
A
40
50
70
70
Making capacity (cos v to IEC/EN 60947) to 690 V
Breaking capacity
16
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616
Technical data
DIL M17
DIL M25
DIL M32
DIL M40
DIL M50
DIL M65
DIL M72
DIL M80
DIL M95
DIL M115
DIL M150
DIL M170
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
–25/60
–25/60
–25/60
–25/60
–25/60
–25/60
–25/60
–25/60
–25/60
–25/60
–25/60
10
10
10
10
10
10
10
10
10
10
10
7
7
7 7
7
7
7
7
7
7
7
7
5
5
5 5
5
5
5
5
5
5
5
5
0.42
0.42
0.42
0.9
0.9
0.9
2
2
2
2
2
0.48
0.48
0.48
1.1
1.1
1.1
2.1
2.1
2.1
2.1
2.1
1 x (0.75 – 16)
1 x (2.5 – 16)
2 x (0.75 – 10)
2 x (2.5 – 16)
–
1 x (0.75 – 16)
1 x (2.5 – 35)
1 x (4 – 70)
1 x (10 – 95)
2 x (0.75 – 10)
2 x (2.5 – 25)
2 x (4 – 50)
2 x (10 – 70)
1 x (16 – 50)
1 x (16 – 95)
1 x (16 – 120)
2 x (16 – 35)
2 x (16 – 70)
2 x (16 – 95)
1 x 16
18 – 6
18 – 6
18 – 6
–
–
–
12 – 2
12 – 2
12 – 2
8 – 3/0
2 x (6 x 9 x 0.8)
8 – 3/0
8 – 3/0
8 – 3/0
8 – 3/0
2 x (6 x 16 x 0.8)
1 x (0.75 – 4)
1 x (0.75 – 4)
2 x (0.75 – 4)
2 x (0.75 – 2.4)
1 x (0.75 – 2.5)
1 x (0.75 – 2.5)
2 x (0.75 – 2.5)
2 x (0.75 – 2.5)
18 – 14
18 – 14
18 – 14
18 – 14
18 – 14
18 – 14
18 – 14
18 – 14
18 – 14
18 – 14
18 – 14
690
690
690
690
690
690
1000
1000
1000
1000
1000
690
690
690
690
690
690
1000
1000
1000
1000
1000
238
350
384
560
700
910
1120
1330
1610
2100
2100
170
250
320
400
500
650
800
950
1150
1500
1500
170
250
320
400
500
650
800
950
1150
1500
1500
170
250
320
400
500
650
800
950
1150
1500
1500
120
150
180
250
320
370
650
800
1100
1200
1320
17
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616
Technical data
DIL M7
DIL M9
DIL M12
DIL M15
AC
AC-1 actuation
Conventional free air thermal
Open
Current 3-pole 50 – 60 Hz
at 40 °C
A
22
22
22
22
at 60 °C
A
20
20
20
20
AC actuation
Rated operational current, AC-3
220/230 V
Ie
A
7
9
12
15.5
open, 50 – 60 Hz, 3-pole
380/400 V
Ie
A
7
9
12
15.5
500 V
Ie
A
5
7
10
12.5
660/690 V
Ie
A
4
5
7
9
220/230 V
P
kW
2.2
2.5
3.5
4
380/400 V
P
kW
3
4
5.5
7.5
500 V
P
kW
3.5
4.5
7
7.5
660/690 V
P
kW
3.5
4.5
6.5
7
AC operated
Pick-up
x Uc
0.8 – 1.1
0.8 – 1.1
0.8 – 1.1
0.8 – 1.1
DC operated
Pick-up
x Uc
0.8 – 1.1
0.8 – 1.1
0.8 – 1.1
0.8 – 1.1
Pick-up
VA
24
30
24
30
24
30
24
30
Sealing
VA
3.4
4.4
3.4
4.4
3.4
4.4
3.4
4.4
W
1.2
1.4
1.2
1.4
1.2
1.4
1.2
1.4
Pick-up
W
3
3
4.5
4.5
Sealing
W
3
3
4.5
4.5
Motor rating
Magnet systems
Pick-up and drop-out values
Coil consumption from cold and 1.0 x Uc
AC operated
50 Hz coil
60 Hz coil
DC operated
Dimensions
DIL M7 – DIL M15, DILA with auxiliary contact module
DIL M17 – DIL M32 basic unit with auxiliary contact module
(5.1)
71
85
68
38
45
45
18
8.7 8.7 8.7 8.7
60.4
36
3.2
4.5
4.8
6.5
17.7
75
(6.4)
116.3
11.6 11.6 10.6
45
4.5
6.5
97.4
138.7
18
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616
Technical data
DIL M17
DIL M25
DIL M32
DIL M40
DIL M50
DIL M65
DIL M72
DIL M80
DIL M95
DIL M115
DIL M150
DIL M170
40
45
45
60
80
98
110
130
160
190
225
35
40
40
50
65
80
90
110
130
160
185
18
25
32
40
50
65
72
80
95
115
150
170
18
25
32
40
50
65
72
80
95
115
150
170
18
25
32
40
50
65
72
80
95
115
150
170
12
25
18
25
32
37
37
65
80
93
100
150
5
7.5
10
12.5
15.5
20
22
25
30
37
48
52
7.5
11
15
18.5
22
30
37
37
45
55
75
90
12
17.5
23
28
36
47
45
58
70
85
110
120
11
14
17
23
30
35
35
63
75
90
96
140
0.8 – 1.1
0.8 – 1.1
0.8 – 1.1
0.8 – 1.1
0.8 – 1.1
0.8 – 1.1
0.8 – 1.1
0.8 – 1.1
0.8 – 1.1
0.8 – 1.1
0.8 – 1.1
0.7 – 1.2
0.7 – 1.2
0.7 – 1.2
0.7 – 1.2
0.7 – 1.2
0.7 – 1.2
0.7 – 1.2
0.7 – 1.2
0.7 – 1.2
0.7 – 1.2
0.7 – 1.2
52
67
52
67
52
67
149
178
149
178
149
178
310
345
310
345
180
170
180
170
180
170
7.1
8.7
7.1
8.7
7.1
8.7
16.0
19.0
16.0
19.0
16.0
19.0
26.0
30.0
26.0
30.0
3.1
3.1
3.1
3.1
3.1
3.1
2.1
2.6
2.1
2.6
2.1
2.6
4.3
5.3
4.3
5.3
4.3
5.3
5.8
7.1
5.8
7.1
2.1
2.1
2.1
2.1
2.1
2.1
12 at 24 V
12 at 24 V
12 at 24 V
24 at 24 V
24 at 24 V
24 at 24 V
90 at 24 V
90 at 24 V
149 at 24 V
149 at 24 V
149 at 24 V
0.5 at 24 V
0.5 at 24 V
0.5 at 24 V
0.5 at 24 V
0.5 at 24 V
0.5 at 24 V
1.3 at 24 V
1.3 at 24 V
2.1 at 24 V
2.1 at 24 V
2.1 at 24 V
Dimensions
DIL M80 – DIL M170 basic unit with auxiliary contact module
55
170
156
57
34.4
76.5
104
57
86.4
DIL M40 – DIL M72 basic unit with auxiliary contact module
4.7
6.9
113.8
132.1
146.75
90
82.5
111
85.5
142
160
19
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616
DILA contactor relays
Contacts
Can be combined AC operation
with auxiliary
Part no.
contact
AC-15
380 V
400 V
415 V
Basic units with
interlocked
opposing contacts
Ie
Ith
A
A
DC operation
Part no.
Part no.
Article no.
Article no.
Article no.
230 V 50 Hz
240 V 60 Hz
24 V 50/60 Hz
110 V 50 Hz
120 V 60 Hz
24 V DC
4 N/O
–
4
10
DILA-XHI(V)...
DILA-40(...)
276329
DILA-40(...)
276333
DILA-40(...)
276326
DILA-40(...)
276344
3 N/O
1 N/C
4
10
DILA-XHI(V)...
DILA-31(...)
276364
DILA-31(...)
276368
DILA-31(...)
276361
DILA-31(...)
276379
2 N/O
2 N/C
4
10
DILA-XHI(V)...
DILA-22(...)
276399
DILA-22(...)
276403
DILA-22(...)
276396
DILA-22(...)
276414
The listed auxiliary and main contacts up to 12 A are available with springloaded terminals.
The auxiliary contact modules listed for the DILA contactor relay can also be used for the DILM contactors up to 32 A.
Auxiliary contact members: DILA-XHI to EN 50005, DILM32-XHI to DIN 50012
The DILA-22 contactor relay can not be combined with the 4-pole auxiliary contact module.
DILA auxiliary contact modules
Contacts
Rated operating
current
Conventional current,
open at 60 °C
Can be combined
with basic unit
Part no.
Article no.
DILA...
DILA-XHI02
276420
AC-15
N/CE = Early-make contacts
N/OL = Late-break contacts
2-pole
–
4-pole
2 N/C
380 V
400 V
415 V
Ie
Ith
A
A
3
16
DILM7...
DILM9...
DILM12...
DILM15...
DILM17...
DILM25...
DILM32...
1 N/O
1 N/C
2 N/O
–
1 N/OE
1 N/CL
–
4 N/C
DILA-40...
DILA-31...
DILA-XHI04
276424
1 N/O
3 N/C
DILA-XHI13
276425
2 N/O
2 N/C
3 N/O
1 N/C
DILM7...
DILM9...
DILM12...
DILM15...
DILM17...
DILM25...
DILM32...
4 N/O
–
DILA-XHI40
276428
1 N/O, 1 N/OE
1 N/C, 1 N/CL
DILA-XHIV22
276429
DILA-XHI11
276421
DILA-XHI20
276422
DILA-XHIV11
276423
DILA-XHI22
276426
DILA-XHI31
276427
a Dimensions Page 18
20
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616
Technical data
DIL A
DIL A-XHI...
General
Lifespan, mechanical
Operations
x 106
20
10
Operations
6
x 10
20
10
°C
–25/60
–25/60
AC operated
kg
0.23
0.05
DC operated
kg
0.28
0.05
Solid
mm2
1 x (0.75 – 4)
Flexible with ferrule
mm2
Solid or stranded
AWG
18 – 14
AC operated
DC operated
Ambient temperature
open
Weight
Terminal capacity
Screw terminals
2 x (0.75 – 2.5)
1 x (0.75 – 2.5)
2 x (0.75 – 2.5)
Contacts
Rated insulation voltage
Ui
V AC
690
690
Rated operational voltage
Ue
V AC
690
500
220/240 V
Ie
A
6
6
380/415 V
Ie
A
4
3
500 V
Ie
A
1.5
–
10
Rated operational current
AC-15
DC-13 1)
DC-13 L/R F 15 ms
Contacts in series:
1
Fault frequency at Ue = 24 V DC, Umin = 17 V, Imin = 5.4 mA
24 V
A
10
Fault rate
HF
< 10-8, < 1 failure to 100 million switching operations
Magnet systems
Pick-up and drop-out values
AC operated
DC operated
50 Hz single-voltage coil and 50/60 Hz dual-voltage coil
Pick-up
x Uc
0.8 – 1.1
–
Dual-frequency coil 50/60 Hz
Pick-up
x Uc
0.8 – 1.1
–
Pick-up voltage
Pick-up
x Uc
0.8 – 1.1
–
Without auxiliary contact module (40 °C)
Pick-up
x Uc
0.7 – 1.3
–
2)
Power consumption
50 Hz single-voltage coil and 50/60 Hz dual-voltage coil
Pick-up
VA
24
–
50 Hz single-voltage coil and 50/60 Hz dual-voltage coil
Sealing
VA
4
–
Sealing
W
1.2
–
Pick-up = Sealing
W
3
–
DC operated
Notes
1)
2)
Making and breaking currents to DC-13 time constant as stated
Smoothed DC or three-phase bridge rectifier
21
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616
ZB overload relays
Overload release
setting range
Short-circuit
protection
Coordination type
gG/gL
A
“1“
“2“
Part no.
Article no.
25
0.5
ZB12-0,16
278431
1
ZB12-0,24
278432
2
ZB12-0,4
278433
4
ZB12-0,6
278434
4
ZB12-1,0
278435
6
ZB12-1,6
278436
10
ZB12-2,4
278437
2.4 – 4
16
ZB12-4
278438
4–6
20
ZB12-6
278439
25
ZB12-10
278440
9 – 12
ZB12-12
278441
12 – 16
ZB12-16
290168
0.5
ZB32-0,16
278442
1
ZB32-0,24
278443
DIULM17,
DIULM25,
DIULM32
2
ZB32-0,4
278444
4
ZB32-0,6
278445
SDAINLM30,
SDAINLM45,
SDAINLM55
4
ZB32-1,0
278446
6
ZB32-1,6
278447
1.6 – 2.4
10
ZB32-2,4
278448
2.4 – 4
16
ZB32-4
278449
For use with
Ir
A
ZB12 overload relays
Single-phasing sensitivity to
IEC/EN 60947,
VDE 0660 Part 102
Direct fitting
0.1 – 0.16
0.16 – 0.24
0.24 – 0.4
0.4 – 0.6
0.6 – 1
1 – 1.6
1.6 – 2.4
97 95
2
4
6
0.1 – 0.16
0.16 – 0.24
0.24 – 0.4
0.4 – 0.6
0.6 – 1
1 – 1.6
6
SDAINLM12,
SDAINLM16,
SDAINLM22
50
DILM17,
DILM25,
DILM32,
25
4–6
97 95
4
DIULM7,
DIULM9,
DIULM12,
6 – 10
98 96 A2 14/
22
ZB32 overload relays
Single-phasing sensitivity to
IEC/EN 60947,
VDE 0660 Part 102
Direct fitting
2
DILM7,
DILM9,
DILM12,
DILM15,
98 96 14/
22
ZB65 overload relays
Single-phasing sensitivity to
IEC/EN 60947,
VDE 0660 Part 102
Direct fitting
Overload release:
tripping class 10 A
Short-circuit protection:
when fitting directly, note
maximum admissible fuse for the
contactor.
Suitable for the protection of EEx
e-motors. EU prototype test
certificate available on request.
Overload release:
tripping class 10 A
Short-circuit protection:
when fitting directly, note
maximum admissible fuse for the
contactor.
Suitable for the protection of EEx
e-motors. EU prototype test
certificate available on request.
20
ZB32-6
278450
6 – 10
50
25
ZB32-10
278451
10 – 16
63
35
ZB32-16
278452
16 – 24
100
35
ZB32-24
278453
24 – 32
125
63
ZB32-32
278454
DILM40,
DILM50,
DILM65,
50
25
ZB65-10
278455
63
35
ZB65-16
278456
DIULM40,
DIULM50,
DIULM65
63
50
ZB65-24
278457
125
63
ZB65-40
278458
SDAINLM70,
SDAINLM90,
SDAINLM115
160
80
ZB65-57
278459
160
100
ZB65-65
278460
Suitable for the protection of EEx
e-motors. EU prototype test
certificate available on request.
DILM80,
DILM95,
DILM115,
DILM150,
DILM170,
125
100
ZB150-35
278461
160
125
ZB150-50
278462
Overload release:
tripping class 10 A
250
160
ZB150-70
278463
DIULM80,
DIULM95,
DIULM115,
DIULM150,
315
200
ZB150-100
278464
315
250
ZB150-125
278465
315
250
ZB150-150
278466
315
250
ZB150-175
107316
6 – 10
10 – 16
16 – 24
24 – 40
40 – 57
50 – 65
Overload release:
tripping class 10 A
Short-circuit protection:
when fitting directly, note
maximum admissible fuse for the
contactor.
97 95
2
4
6
98 96
ZB150 overload relays
Single-phasing sensitivity to
IEC/EN 60947,
VDE 0660 Part 102
Direct fitting
25-35
35-50
50-70
70-100
95-125
120-142
97 95
2
4
6
SDAINLM140,
SDAINLM165,
SDAINLM200,
SDAINLM260
Short-circuit protection:
when fitting directly, note
maximum admissible fuse for the
contactor.
Suitable for the protection of EEx
e-motors. EU prototype test
certificate available on request.
98 96
22
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616
Overload relay technical data
ZB12, ZB32
ZB65
ZB150 (kk)
General
Standards and regulations
IEC/EN 60947, VDE 0660, UL, CSA
Ambient temperature
open1)
°C
–25/55
–25/55
–25/55
enclosed1)
°C
–25/40
–25/40
–25/40
V AC
690
690
1000
Solid
mm2
2 x (1 – 6)
2 x (1 – 16)
2 x (4 – 16)
Flexible with ferrule
mm2
2 x (1 – 4)
1 x 25
Main contacts
Rated operational voltage
Ue
Terminal capacity
2 x (1 – 6)
Solid or stranded
2)
2 x (1 – 10)
1 x (4 – 70)
3)
2 x (4 – 50)
AWG
14 – 8
14 – 2
2/0
Ith
A
6
6
6
240 V
Ie
A
1.5
1.5
1.5
415 V
Ie
A
0.5
0.5
0.5
500 V
Ie
A
0.5
0.5
0.5
Break contact 240 V
Ie
A
1.5
1.5
1.5
415 V
Ie
A
0.9
0.9
0.9
500 V
Ie
A
0.8
0.8
0.8
24 V
Ie
A
0.9
0.9
0.9
60 V
Ie
A
0.75
0.75
0.75
110 V
Ie
A
0.4
0.4
0.4
220 V
Ie
A
0.2
0.2
0.2
Auxiliary circuits and control circuits
Conventional free air thermal current
Rated operational current
AC-15
Make contact
DC-13 L/R F 15 ms4)
1)
Ambient temperature: operating range to IEC/EN 60947, PTB: –5 °C to +50 °C
6 mm2 flexible with ferrule to DIN 46228
3)
Terminal capacity of main contacts solid and flexible with ferrule:
when using 2 conductor of equal cross-section
4)
Rated operational current: making and breaking currents to DC-13, time constant as stated
Notes
2)
Dimensions
ZB12/ZB32
ZB150
45
35.5
80
73
48
29.5
39.5
99
65
138
83
ZB65
20.3
79.2
74
51.5
95
100
118
60
63
129
134
95.5
102
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616
23
Motor-protective circuit-breaker
PKZ
1
5
2
6
4
7
3
1. Motor-protective circuit-breaker PKZM 01
2. Motor-protective circuit-breaker PKZM 0
3. Motor-protective circuit-breaker PKZM 4
4. Door coupling rotary handle IP65
5. Voltage release
6. Trip-indicating auxiliary contact
7. Auxiliary contacts
24
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616
7
PKZM0, PKZM4 motor-protective circuit-breakers
Max. motor rating
Rated uninterrupted
current
AC-3
Setting range
Screw terminals
Overload releases
Short-circuit release
Part no.
Article no.
380 V 400 V 415 V
Iu
Ir
Irm
P
A
A
A
–
0.16
0.1 – 0.16
2.2
PKZM0-0,16
072730
0.06
0.25
0.16 – 0.25
3.5
PKZM0-0,25
072731
0.09
0.4
0.25 – 0.4
5.6
PKZM0-0,4
072732
0.12
0.63
0.4 – 0.63
8.8
PKZM0-0,63
072733
0.25
1
0.63 – 1
14
PKZM0-1
072734
0.55
1.6
1 – 1.6
22
PKZM0-1,6
072735
0.75
2.5
1.6 – 2.5
35
PKZM0-2,5
072736
1.5
4
2.5 – 4
56
PKZM0-4
072737
2.2
6.3
4 – 6.3
88
PKZM0-6,3
072738
4
10
6.3 – 10
140
PKZM0-10
072739
5.5
12
8 – 12
168
PKZM0-12
278486
7.5
16
10 – 16
224
PKZM0-16
046938
9
20
16 – 20
280
PKZM0-20
046988
12.5
25
20 – 25
350
PKZM0-25
046989
15
32
25 – 32
448
PKZM0-32
278489
7.5
16
10 – 16
224
PKZM4-16
222350
12.5
25
16 – 25
350
PKZM4-25
222352
15
32
25 – 32
448
PKZM4-32
222353
20
40
32 – 40
560
PKZM4-40
222354
25
50
40 – 50
700
PKZM4-50
222355
30
58
50 – 58
812
PKZM4-58
222394
34
65
55 – 65
882
PKZM4-63
222413
kW
Motor-protective circuit-breakers,
coordination type “1“ and “2“
Motor-protective circuit-breaker,
coordination type “1“ and “2“
Note
Three-phase motors (approximate values for squirrel-cage rotors)
25
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616
PKZM01 motor-protective circuit-breaker
Motor-protective circuit-breakers,
coordination type “1“ and “2“
Note Three-phase motors (approximate
values for squirrel-cage rotors)
Max. motor rating
Rated uninterrupted
current
Setting range
Screw terminals
AC-3
380 V 400 V 415 V
P
kW
Iu
A
Overload releases
Ir
A
Short-circuit releases
Irm
A
Part no.
Article no.
–
0.16
0.1 – 0.16
2.2
PKZM01-0,16
278475
0.06
0.25
0.16 – 0.25
3.5
PKZM01-0,25
278476
0.09
0.4
0.25 – 0.4
5.6
PKZM01-0,4
278477
0.12
0.63
0.4 – 0.63
8.8
PKZM01-0,63
278478
0.25
1
0.63 – 1
14
PKZM01-1
278479
0.55
1.6
1 – 1.6
22
PKZM01-1,6
278480
0.75
2.5
1.6 – 2.5
35
PKZM01-2,5
278481
1.5
4
2.5 – 4
56
PKZM01-4
278482
2.2
6.3
4 – 6.3
88
PKZM01-6,3
278483
4
10
6.3 – 10
140
PKZM01-10
278484
5.5
12
8 – 12
168
PKZM01-12
278485
7.5
16
10 – 16
224
PKZM01-16
283390
9
20
16 – 20
280
PKZM01-20
283383
12,5
25
20 – 25
350
PKZM01-25
288893
Insulated enclosures
Insulated enclosures for surface
mounting
Insulated enclosures for flush mounting
Protection
type
For use with
Part no.
Article no.
–
IP40
NEMA Type 1
PKZM01+NHI-E or VHI-PKZ01+U
or A or NHI+L (2 off)
CI-PKZ01
281403
With actuating diaphragm
IP65
NEMA 4X
PKZM01+NHI-E or VHI-PKZ01+U
or A or NHI+L (2 off)
CI-PKZ01-G
281404
Lockable in the Off position
IP65
NEMA 4X
PKZM01+NHI-E+U or A (undervoltage
or shunt release)+L (2 off)
CI-PKZ01-SVB
281405
Lockable in the Off position,
in conjunction with VHI-PKZ01
IP65
NEMA 4X
PKZM01+NHI-E or VHI-PKZ01+U or A
CI-PKZ01-SVB-V
(undervoltage or shunt release)+L (2 off) 281944
With stay-put Emergency-Stop
mushroom button
IP65
NEMA 4X
PKZM01+NHI-E or VHI-PKZ01+U or A
CI-PKZ01-PVT
(undervoltage or shunt release)+L (2 off) 281406
With key-release Emergency-Stop
mushroom button
IP65
NEMA 4X
PKZM01+NHI-E or VHI-PKZ01+U or A
CI-PKZ01-PVS
(undervoltage or shunt release)+L (2 off) 281407
–
Front IP40
NEMA Type 1
PKZM01+NHI-E orVHI-PKZ01+U
or A or NHI+L (2 off)
E-PKZ01
281633
With actuating diaphragm
Front IP65
NEMA 4X
PKZM01+NHI-E or VHI-PKZ01+U
or A or NHI+L (2 off)
E-PKZ01-G
281634
Lockable in the Off position
Front IP65
NEMA 4X
PKZM01+NHI-E or VHI-PKZ01+U or A
E-PKZ01-SVB
(undervoltage or shunt release)+L (2 off) 281635
Lockable in the Off position,
in conjunction with VHI-PKZ01
Front IP65
NEMA 4X
PKZM01+NHI-E or VHI-PKZ01+U or A
E-PKZ01-SVB-V
(undervoltage or shunt release)+L (2 off) 281943
With stay-put Emergency-Stop
mushroom button
Front IP65
NEMA 4X
PKZM01+NHI-E or VHI-PKZ01+U or A
E-PKZ01-PVT
(undervoltage or shunt release)+L (2 off) 281636
With key-release Emergency-Stop
mushroom button
Front IP65
NEMA 4X
PKZM01+NHI-E or VHI-PKZ01+U or A
E-PKZ01-PVS
(undervoltage or shunt release)+L (2 off) 281637
26
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616
Accessories
Contacts
–
Trip-indicating auxiliary contact 2 x 1 N/O
Type of current AC/DC
For use with
–
–
Part no.
Article no.
when ordered separately
–
PKZM0
PKZM4
AGM2-10-PKZ0
072898
–
2 x 1 N/C
–
PKZM01
AGM2-01-PKZ0
072899
Early-make auxiliary contacts
2 N/O
–
–
PKZM0
VHI20-PKZ0
203595
–
2 N/O
–
–
PKZM01
VHI20-PKZ01
278495
Shunt release
–
–
AC operation
PKZM0
A-PKZ0(230V50HZ)
073187
PKZM4
–
–
DC operation
PKZM01
A-PKZ0(24VDC)
073200
Undervoltage release
–
–
AC operation
PKZM0
PKZM4
PKZM01
U-PKZ0(230V50HZ)
4073135
Standard auxiliary contact
1 N/O
1 N/C
–
PKZM0
NHI11-PKZ0
072896
PKZM4
Standard auxiliary contact
1 N/O
2 N/C
–
2 N/O
1 N/C
–
NHI21-PKZ0
072894
1 N/O
1 N/C
–
NHI-E-11-PKZ0
082882
1 N/O
–
–
NHI-E-10-PKZ0
082884
PKZM01
NHI12-PKZ0
072895
27
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616
Technical data basic units
PKZM01...
PKZM0-...
PKZM4
°C
–25/55
–25/55
–25/55
Solid
mm2
1 x (1 – 6)
2 x (1 – 6)
1 x (1 – 6)
2 x (1 – 6)
1 x (1 – 50)
2 x (1 – 35)
Flexible with ferrule
mm2
1 x (1 – 6)
2 x (1 – 6)
1 x (1 – 6)
2 x (1 – 6)
1 x (1 – 35)
2 x (1 – 35)
Solid or stranded
AWG
18 – 10
18 – 10
14 – 2
Main contacts
Nm
1.7
1.7
3
Auxiliary contacts
Nm
1
1
1
General
Ambient temperature
open
Terminal capacity
Tightening torque, terminal screws
Main contacts
Rated operational voltage
Ue
V AC
690
690
690
Rated uninterrupted current =
rated operational current
Iu = I e
A
16 or setting current of
overcurrent release
32 or setting current of
overcurrent release
65 open
63 enclosed
or setting current of
overcurrent release
Lifespan, mechanical
Operations
x 106
0.05
0.1
0.03
Operations
6
0.05
0.1
0.03
S/h
40
40
40
to IEC/EN 60947, VDE 0660
°C
–5/40
–5/40
–5/40
Operating range
Lifespan, electric (AC-3 at 400 V)
Maximum operating frequency
x 10
Releases
Temperature compensation
°C
–25/55
–25/55
–25/55
Setting range, overload release
x Iu
0.6 – 1
0.6 – 1
0.6 – 1
Short-circuit release fixed
x Iu
14
14
14
IEC/EN 60947-4-1,
VDE 0660 Part 102
IEC/EN 60947-4-1,
VDE 0660 Part 102
IEC/EN 60947-4-1,
VDE 0660 Part 102
Phase-failure sensitivity
Technical data auxiliary contacts
NHI...PKZ0
NHI-E-...PKZ0
VHI...PKZ0
AGM
Terminal capacity
Solid or flexible with ferrule
mm2
0.75 – 2.5
0.75 – 1.5
0.75 – 1.5
0.75 – 2.5
Solid or stranded
AWG
18 – 14
18 – 16
18 – 16
18 – 14
28
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616
PKZM, dimensions
Motor-protective circuit-breaker with early-make auxiliary contact
Motor-protective circuit-breakers
PKZM0-…+VHI-…-PKZ0
PKZM0-…(+NHI-E-..-PKZ0)
80
45
93
45
55
93
55
4.5
70
VHI...-PKZ0
NHI-E-..-PKZ0
VHI...-PKZ0
NHI-E-..-PKZ0
50
25
68
76
45
50
45
68
U/A-PKZ0
9
26
68
90
45
90
45
26
9
36
Voltage release
AGM2-…-PKZ0
36
Trip-indicating auxiliary contact
NHI…-PKZ0
36
Standard auxiliary contact
18
45
90
86
49
68
68
Motor-protective circuit-breakers
45
93
PKZM01
45
5.5
44
74
85
Switching capacity with coordination type “1“ and “2“
PKZM0
PKZM01
Iu
A
400 V
Iq
kA
Icu
kA
Ics
kA
0.16 – 1
1.6
2.5
4
6.3
10
12
16
20
25
32
150
150
150
150
150
150
50
50
50
50
50
150
150
150
150
150
150
50
50
50
50
50
150
150
150
150
150
150
10
10
10
10
10
A1)
400 V
Iq
kA
Icu
kA
Ics
kA
A2)
N
N
N
N
N
N
50
50
50
50
50
0
50
50
50
50
50
50
50
–
–
–
50
50
50
50
50
50
50
50
–
–
–
50
50
50
50
50
50
10
10
–
–
–
50
50
50
50
50
50
50
50
–
–
–
Rated uninterrupted current Iu
Rated conditional short-circuit current Iq IEC/EN 60947-4-1
Rated ultimate short-circuit breaking capacity Icu
IEC/EN 60947-2
Rated breaking capacity Ics
1)
Required back-up fuse, if the short-circuit current
exceeds the rated conditional short-circuit current of the devices (Icc Iq).
2)
Fuse (A gG/gL) to raise the switching capacity of the motor-protective
circuit-breaker to 100 kA
N
Not required
No upstream protective device necessary,
since inherently protected range ( (100/150 kA)
29
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616
Direct-on-line starter, 400/415 V
Motor starter Coordination type “1“
Motor data
AC-3
380 V
400 V
415 V
Complete units
PKZ and DILM
Components
PKZM4 and DILM
30
Setting range
Actuating voltage
230 V 50 Hz
240 V 60 Hz
Actuating voltage
24 V DC
Part no.
Article no.
Part no.
Article no.
Rated
operational
current
400 V
Rated shortcircuit current
380 – 415 V
Overload
release
P
Ie
Iq
Ir
Irm
kW
A
kA
A
A
0.06
0.21
150 (50)1)
0.16 – 0.25
3.5
MSC-D-0,25-M7 (...)
281925
MSC-D-0,25-M7 (...)
283154
0.09
0.31
150 (50)1)
0.25 – 0.4
5.6
MSC-D-0,4-M7 (...)
281926
MSC-D-0,4-M7 (...)
283155
0.12
0.41
150 (50)1)
0.40 – 0.63
8.82
MSC-D-0,63-M7 (...)
281927
MSC-D-0,63-M7 (...)
283156
0.18
0.6
150 (50)1)
0.40 – 0.63
8.82
MSC-D-0,63-M7 (...)
281927
MSC-D-0,63-M7 (...)
283156
0.25
0.8
150 (50)1)
0.63 – 1
14
MSC-D-1-M7 (...)
281929
MSC-D-1-M7 (...)
283158
0.37
1.1
150 (50)1)
1.00 – 1.6
22.4
MSC-D-1,6-M7 (...)
283140
MSC-D-1,6-M7 (...)
283159
0.55
1.5
150 (50)1)
1.00 – 1.6
22.4
MSC-D-1,6-M7 (...)
283140
MSC-D-1,6-M7 (...)
283159
0.75
1.9
150 (50)1)
1.60 – 2.5
35
MSC-D-2,5-M7 (...)
283142
MSC-D-2,5-M7 (...)
283161
1.1
2.6
150 (50)1)
2.50 – 4
56
MSC-D-4-M7 (...)
283143
MSC-D-4-M7 (...)
283162
1.5
3.6
150 (50)1)
2.50 – 4
56
MSC-D-4-M7 (...)
283143
MSC-D-4-M7 (...)
283162
2.2
5
150 (50)1)
4.00 – 6.3
88.2
MSC-D-6,3-M7 (...)
283145
MSC-D-6,3-M7 (...)
283164
3
6.6
150 (50)1)
6.30 – 10
140
MSC-D-10-M7 (...)
283146
MSC-D-10-M7 (...)
283165
4
8.5
150 (50)1)
6.30 – 10
140
MSC-D-10-M9 (...)
283147
MSC-D-10-M9 (...)
283166
5.5
11.3
50
8 – 12
168
MSC-D-12-M12 (...)
283148
MSC-D-12-M12 (...)
283167
7.5
16 (15.52))
50
10 – 16
224
MSC-D-16-M15 (...)
100414
MSC-D-16-M15 (...)
100415
7.5
16
50
10 – 16
224
MSC-D-16-M17 (...)
283150
MSC-D-16-M17 (...)
283168
11
21.7
50
20 – 25
350
MSC-D-25-M25 (...)
283151
MSC-D-25-M25 (...)
283169
15
29.3
50
25 – 32
448
MSC-D-32-M32 (...)
283152
MSC-D-32-M32 (...)
283170
5.5
11.3
50
10 - 16
224
-
-
7.5
16
50
10 - 16
224
-
-
11
21.7
50
20 - 25
350
-
-
15
29.3
50
25 - 32
448
-
-
18.5
36
50
32 - 40
560
-
-
22
41
50
40 - 50
700
-
-
30
55
50
50 - 58
812
-
-
34
63
50
55 - 65
910
-
-
1)
For coordination type “2“
2)
Short-circuit
release
IF DILM15-... is used
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616
Direct-on-line starter, 400/415 V
Motor-protective
circuit-breake
Contactor
DOL starter set
Coordination type Mechanical
“1“
connection element +
Contactor
DOL starter set
Coordination type Mechanical
“2“
connection element +
Electrical
contact element
Electrical
contact element
Part no.
Article no.
Part no.3)
Part no.
Article no.
Part no.3)
Part no.
Article no.
PKZM0-0,25
072731
DILM7-...
PKZM0-XD M12
283149
DILM7-...
PKZM0-XD M12
283149
PKZM0-0,4
072732
DILM7-...
PKZM0-XD M12
283149
DILM7-...
PKZM0-XD M12
283149
PKZM0-0,63
072733
DILM7-...
PKZM0-XD M12
283149
DILM7-...
PKZM0-XD M12
283149
PKZM0-0,63
072733
DILM7-...
PKZM0-XD M12
283149
DILM7-...
PKZM0-XD M12
283149
PKZM0-1
072734
DILM7-...
PKZM0-XD M12
283149
DILM7-...
PKZM0-XD M12
283149
PKZM0-1,6
072735
DILM7-...
PKZM0-XD M12
283149
DILM7-...
PKZM0-XD M12
283149
PKZM0-1,6
072735
DILM7-...
PKZM0-XD M12
283149
DILM7-...
PKZM0-XD M12
283149
PKZM0-2,5
072736
DILM7-...
PKZM0-XD M12
283149
DILM7-...
PKZM0-XD M12
283149
PKZM0-4
072737
DILM7-...
PKZM0-XD M12
283149
DILM7-...
PKZM0-XD M12
283149
PKZM0-4
072737
DILM7-...
PKZM0-XD M12
283149
DILM7-...
PKZM0-XD M12
283149
PKZM0-6,3
072738
DILM7-...
PKZM0-XD M12
283149
DILM7-...
PKZM0-XD M12
283149
PKZM0-10
072739
DILM7-...
PKZM0-XD M12
283149
DILM17-...
PKZM0-XD M32
283153
PKZM0-10
072739
DILM9-...
PKZM0-XD M12
283149
DILM17-...
PKZM0-XD M32
283153
PKZM0-12
278486
DILM12-...
PKZM0-XD M12
283149
DILM17-...
PKZM0-XD M32
283153
PKZM0-16
046938
DILM15-...
PKZM0-XD M12
283149
DILM17-...
PKZM0-XD M32
283153
PKZM0-16
046938
DILM17-...
PKZM0-XD M32
283153
DILM17-...
PKZM0-XD M32
283153
PKZM0-25
046989
DILM25-...
PKZM0-XD M32
283153
DILM25-...
PKZM0-XD M32
283153
PKZM0-32
278489
DILM32-...
PKZM0-XD M32
283153
DILM32-...
PKZM0-XD M32
283153
PKZM4-16
222350
DIL M17-...
-
DIL M17-...
-
PKZM4-16
222350
DIL M17-...
-
DIL M17-...
-
PKZM4-25
222352
DIL M25-...
-
DIL M25-...
-
PKZM4-32
222353
DIL M32-...
-
DIL M32-...
-
PKZM4-40
222354
DIL M40
-
DIL M40
-
PKZM4-50
222355
DIL M50
-
DIL M50
-
PKZM4-58
222394
DIL M65
-
DIL M65
-
PKZM4-63
222413
DIL M65
-
DIL M65
-
3)
Notes
The direct-on-line starters (complete units) consist of
a PKZM0 motor-protective circuit-breaker and a DILM
contactor.
Up to 15.5 A, starters are mounted without adapter
plates, with only the motor-protective circuit-breaker
being secured to the top-hat rail. The contactors
receive their mechanical hold via a mechanical
connection module.
From 16 A, motor-protective circuit-breakers and
contactors are mounted on top-hat-rail adapter plates.
The connection of the main contacts between PKZ
and contactor is effected via an electrical contact
module.
Please find the order number in the Industrial Switchgear main catalogue to suit the actuation voltage
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616
31
Reversing starter 400/415 V
Motor starter Coordination type “1“
Motor data
Complete units
PKZ and DILM
Components
PKZM4 and DILM
32
Setting range
Actuating voltage
230 V 50 Hz
240 V 60 Hz
Actuating voltage
24 V DC
Part no.
Article no.
Part no.
Article no.
AC-3
380 V
400 V
415 V
Rated
operational
current
400 V
Rated shortcircuit current
380 – 415 V
Overload
release
P
Ie
Iq
Ir
Irm
kW
A
kA
A
A
0.06
0.21
150 (50)1)
0.16 – 0.25
3.5
MSC-R-0,25-M7 (...)
283171
MSC-R-0,25-M7 (...)
283190
0.09
0.31
150 (50)1)
0.25 – 0.4
5.6
MSC-R-0,4-M7 (...)
283172
MSC-R-0,4-M7 (...)
283191
0.12
0.41
150 (50)1)
0.40 – 0.63
8.82
MSC-R-0,63-M7 (...)
283173
MSC-R-0,63-M7 (...)
283192
0.18
0.6
150 (50)1)
0.40 – 0.63
8.82
MSC-R-0,63-M7 (...)
283173
MSC-R-0,63-M7 (...)
283192
0.25
0.8
150 (50)1)
0.63 – 1
14
MSC-R-1-M7 (...)
283175
MSC-R-1-M7 (...)
283194
0.37
1.1
150 (50)1)
1.00 – 1.6
22.4
MSC-R-1,6-M7 (...)
283176
MSC-R-1,6-M7 (...)
283195
0.55
1.5
150 (50)1)
1.00 – 1.6
22.4
MSC-R-1,6-M7 (...)
283176
MSC-R-1,6-M7 (...)
283195
0.75
1.9
150 (50)1)
1.60 – 2.5
35
MSC-R-2,5-M7 (...)
283178
MSC-R-2,5-M7 (...)
283197
1.1
2.6
150 (50)1)
2.50 – 4
56
MSC-R-4-M7 (...)
283179
MSC-R-4-M7 (...)
283198
1.5
3.6
150 (50)1)
2.50 – 4
56
MSC-R-4-M7 (...)
283179
MSC-R-4-M7 (...)
283198
2.2
5
150 (50)1)
4.00 – 6.3
88.2
MSC-R-6,3-M7 (...)
283181
MSC-R-6,3-M7 (...)
283200
3
6.6
150 (50)1)
6.30 – 10
140
MSC-R-10-M7 (...)
283182
MSC-R-10-M7 (...)
283201
4
8.5
150 (50)1)
6.30 – 10
140
MSC-R-10-M9 (...)
283183
MSC-R-10-M9 (...)
283202
5.5
11.3
50
8 – 12
168
MSC-R-12-M12 (...)
283184
MSC-R-12-M12 (...)
283203
7.5
16 (15.52))
50
10 - 16
224
-
-
7.5
16
50
10 – 16
224
MSC-R-16-M17 (...)
283186
MSC-R-16-M17 (...)
283204
11
21.7
50
20 – 25
350
MSC-R-25-M25 (...)
283187
MSC-R-25-M25 (...)
283205
15
29.3
50
25 – 32
448
MSC-R-32-M32 (...)
283188
MSC-R-32-M32 (...)
283206
5.5
11.3
50
10 - 16
224
-
-
7.5
16
50
10 - 16
224
-
-
11
21.7
50
20 - 25
350
-
-
15
29.3
50
25 - 32
448
-
-
18.5
36
50
32 - 40
560
-
-
22
41
50
40 - 50
700
-
-
30
55
50
50 - 58
812
-
-
34
63
50
55 - 65
910
-
-
1)
For coordination type “2“
2)
Short-circuit
releases
IF DILM15-... is used
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616
Reversing starter 400/415 V
Motor-protective
circuit-breakers
Contactor
DOL starter set
Coordination type Mechanical
“1“
connection element +
Contactor
DOL starter set
Coordination type Mechanischer
“2“
connection element +
Electrical
contact element
Electrical
contact element
Part no.
Article no.
Part no.3)
Part no.
Article no.
Part no.3)
Part no.
Article no.
PKZM0-0,25
072731
2 X DILM7-01
PKZM0-XR M12
283185
2 x DILM7-01
PKZM0-XR M12
283185
PKZM0-0,4
072732
2 x DILM7-01
PKZM0-XR M12
283185
2 x DILM7-01
PKZM0-XR M12
283185
PKZM0-0,63
072733
2 x DILM7-01
PKZM0-XR M12
283185
2 x DILM7-01
PKZM0-XR M12
283185
PKZM0-0,63
072733
2 x DILM7-01
PKZM0-XR M12
283185
2 x DILM7-01
PKZM0-XR M12
283185
PKZM0-1
072734
2 x DILM7-01
PKZM0-XR M12
283185
2 x DILM7-01
PKZM0-XR M12
283185
PKZM0-1,6
072735
2 x DILM7-01
PKZM0-XR M12
283185
2 x DILM7-01
PKZM0-XR M12
283185
PKZM0-1,6
072735
2 x DILM7-01
PKZM0-XR M12
283185
2 x DILM7-01
PKZM0-XR M12
283185
PKZM0-2,5
072736
2 x DILM7-01
PKZM0-XR M12
283185
2 x DILM7-01
PKZM0-XR M12
283185
PKZM0-4
072737
2 x DILM7-01
PKZM0-XR M12
283185
2 x DILM7-01
PKZM0-XR M12
283185
PKZM0-4
072737
2 x DILM7-01
PKZM0-XR M12
283185
2 x DILM7-01
PKZM0-XR M12
283185
PKZM0-6,3
072738
2 x DILM7-01
PKZM0-XR M12
283185
2 x DILM7-01
PKZM0-XR M12
283185
PKZM0-10
072739
2 x DILM7-01
PKZM0-XR M12
283185
2 x DILM17-01
PKZM0-XR M32
283189
PKZM0-10
072739
2 x DILM9-01
PKZM0-XR M12
283185
2 x DILM17-01
PKZM0-XR M32
283189
PKZM0-12
278486
2 x DILM12-01
PKZM0-XR M12
283185
2 x DILM17-01
PKZM0-XR M32
283189
PKZM0-16
046938
2 x DILM15-01
PKZM0-XR M12
283185
2 x DILM17-01
PKZM0-XR M32
283189
PKZM0-16
046938
2 x DILM17-01
PKZM0-XR M32
283189
2 x DILM17-01
PKZM0-XR M32
283189
PKZM0-25
046989
2 x DILM25-01
PKZM0-XR M32
283189
2 x DILM25-01
PKZM0-XR M32
283189
PKZM0-32
278489
2 x DILM32-01
PKZM0-XR M32
283189
2 x DILM32-01
PKZM0-XR M32
283189
PKZM4-16
222350
2 X DIL M17-..
-
2 X DIL M17-..
-
PKZM4-16
222350
2 X DIL M17-..
-
2 X DIL M17-..
-
PKZM4-25
222352
2 X DIL M25-..
-
2 X DIL M25-..
-
PKZM4-32
222353
2 X DIL M32-..
-
2 X DIL M32-..
-
PKZM4-40
222354
2 X DIL M40
-
2 X DIL M40
-
PKZM4-50
222355
2 X DIL M50
-
2 X DIL M50
-
PKZM4-58
222394
2 X DIL M65
-
2 X DIL M65
-
PKZM4-63
222413
2 X DIL M65
-
2 X DIL M65
-
3)
Notes
The reversing starters (complete units) consist of a
PKZM0 motor-protective circuit-breaker and two
DILM contactors. Up to 12 A, starters are mounted
without adapter plates, with only the motor-protective circuit-breaker being secured to the top-hat rail.
The contactors receive their mechanical hold via a
mechanical connection module.
From 16 A, motor-protective circuit-breakers and contactors are mounted on top-hat-rail adapter plates.
The connection of the main contacts between PKZ
and contactor is effected via an electrical contact
module.
Complete units with mechanical interlock, starters
up to 12 A also with electrical interlock.
Please find the order number in the Industrial Switchgear main catalogue to suit the actuation voltage
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616
33
Reversing combinations
Rated operational current
Max. three-phase motor rating
at 50-60 Hz
AC-3
380 V
400 V
AC-3
220 V
230 V
380 V
400 V
660 V
690 V
AC-4
220 V
230 V
380 V
400 V
660 V
690 V
Ie
P
P
P
P
P
P
Part no.
A
kW
kW
kW
kW
kW
kW
Article no.
7
2.2
3
3.5
1
2.4
2.9
DIULM7/21(230V50HZ)
278061
9
2.5
4
4.5
1.5
2.5
3.6
DIULM9/21(230V50HZ)
278086
12
3.5
5.5
6.5
2
3
4.4
DIULM12/21(230V50HZ)
278111
18
5
7.5
11
2.5
4.5
6.5
DIULM17/21(230V50HZ)
278136
25
7.5
11
14
3.5
6
8.5
DIULM25/21(230V50HZ)
278161
32
10
15
17
4
7
10
DIULM32/21(230V50HZ)
278186
40
12.5
18.5
23
5
9
12
DIULM40/11(230V50HZ)
278211
50
15.5
22
30
6
10
14
DIULM50/11(230V50HZ)
278236
65
20
30
35
7
12
17
DIULM65/11(230V50HZ)
278261
1
5
3
1
3
5
2
4
6
K2M
K1M
2
4
U
M1
6
V
W
M
3
34
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616
Reversing combinations
Individual combination components
Free auxiliary switch
Mechanical
interlock
Contactor K1M
Contactor K2M
K1M
K2M
Part no.
Part no.
DILM7-01
+ DILA-XHI20
DILM7-01
+ DILA-XHI20
1 N/O
1 N/O
+
DILM9-01
+ DILA-XHI20
DILM9-01
+ DILA-XHI20
1 N/O
1 N/O
+
DILM12-01
+ DILA-XHI20
DILM12-01
+ DILA-XHI20
1 N/O
1 N/O
+
21
0
22
22
21
II
22
21
13
14
I
DILM17-01
+ DILA-XHI20
DILM17-01
+ DILA-XHI20
1 N/O
1 N/O
+
DILM25-01
+ DILA-XHI20
DILM25-01
+ DILA-XHI20
1 N/O
1 N/O
+
DILM32-01
+ DILA-XHI20
DILM32-01
+ DILA-XHI20
1 N/O
1 N/O
+
DILM40
+ DILM150-XHI11
DILM40
+ DILM150-XHI11
-
-
+
DILM50
+ DILM150-XHI11
DILM50
+ DILM150-XHI11
-
-
+
DILM65
+ DILM150-XHI11
DILM65
+ DILM150-XHI11
-
13
54
K1M
53
54
K2M
22
K2M
21
A1
K1M
14
53
22
K1M
21
A1
K2M
A2
A2
21
0
22
-
+
22
21
II
21
22
14
13
13
14
I
14
14
K2M
K1M
13
13
22
K2M
22
K1M
21
A1
21
A1
K1M
(-)N
K2M
A2
A2
35
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616
Star-delta combinations
Rated operational current
Max. three-phase motor rating
at 50-60 Hz
AC-3
380 V
400 V
AC-3
220 V
230 V
380 V
400 V
500 V
660 V
690 V
Ie
P
P
P
P
A
kW
kW
kW
kW
s
Article no.
12
3
5.5
5.5
5.5
20
SDAINLM12(230V50HZ)
278286
16
4
7.5
7.5
7.5
20
SDAINLM16(230V50HZ)
278311
22
5.5
11
11
11
20
SDAINLM22(230V50HZ)
278336
30
7.5
15
18.5
18.5
20
SDAINLM30(230V50HZ)
278361
45
11
22
30
22
20
SDAINLM45(230V50HZ)
278386
55
15
30
37
30
20
SDAINLM55(230V50HZ)
278411
70
18.5
37
45
37
20
SDAINLM70(230V50HZ)
239895
90
22
45
55
45
20
SDAINLM90(230V50HZ)
239937
115
30
55
75
55
20
SDAINLM115(230V50HZ)
239963
140
37
75
90
90
20
SDAINLM140(230V50HZ)
240009
165
45
90
110
132
20
SDAINLM165(230V50HZ)
240035
200
55
110
132
160
20
SDAINLM200(230V50HZ)
101010
260
75
132
160
200
20
SDAINLM260(230V50HZ)
101031
Switchover time up to
s
Part no.
for SDAINL M12-M55
B
21
0
22
S11
K1M
1 3 5
K5M
2 4 6
1 3 5
K3M
2 4 6
A
1 3 5
I
2 4 6
13
K1M
14
K1M
C
14
13
54
K3M
53
54
K5M
53
54
17
K1T
53
17
K1T
18
22
K5M
28
22
K3M
21
A1
U1
V1
W1
M1
3
A1
A2
N
A1
K3M
K1T
K1M
V2
W2
U2
21
A2
A1
K5M
A2
A2
N
M1
for SDAINL M70-M260
21
0
22
S11
I
13
K1M
14
K1M
14
13
44
K3M
43
14
K5M
13
14
17
K1T
13
17
K1T
18
22
K5M
28
22
K3M
21
A1
A1
A2
A1
K3M
K1T
K1M
N
21
A2
N
36
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616
A1
K5M
A2
A2
Star-delta combinations
Individual combination components
Free auxiliary switch
Mains contactor
Delta contactor
K1M
K3M
K5M
K1M
K5M
K3M
Part no.
Part no.
Part no.
Part no.
DILM7-10
+ DILA-XHI20
DILM7-01
+ DILA-XHI20
DILM7-01
+ DILA-XHI20
ETR4-51
1 N/O
1 N/O
1 N/O
DILM9-10
+ DILA-XHI20
DILM9-01
+ DILA-XHI20
DILM9-01
+ DILA-XHI20
ETR4-51
1 N/O
1 N/O
1 N/O
DILM12-10
+ DILA-XHI20
DILM12-01
+ DILA-XHI20
DILM12-01
+ DILA-XHI20
ETR4-51
1 N/O
1 N/O
1 N/O
DILM17-10
+ DILA-XHI20
DILM17-01
+ DILA-XHI20
DILM17-01
+ DILA-XHI20
ETR4-51
1 N/O
1 N/O
1 N/O
DILM25-10
+ DILA-XHI20
DILM25-01
+ DILA-XHI20
DILM17-01
+ DILA-XHI20
ETR4-51
1 N/O
1 N/O
1 N/O
DILM32-10
+ DILA-XHI20
DILM32-01
+ DILA-XHI20
DILM25-01
+ DILA-XHI20
ETR4-51
1 N/O
1 N/O
1 N/O
DIL M40
+ DIL M150-XHI31
DIL M40
+ DIL M150-XHI11
DIL M40
+ DIL M150-XHI11
ETR4-51
1 N/C 1 N/O
-
-
DIL M50
+ DIL M150-XHI31
DIL M50
+ DIL M150-XHI11
DIL M40
+ DIL M150-XHI11
ETR4-51
1 N/C 1 N/O
-
-
DIL M65
+ DIL M150-XHI31
DIL M65
+ DIL M150-XHI11
DIL M40
+ DIL M150-XHI11
ETR4-51
1 N/C 1 N/O
-
-
DIL M80
+ DIL M150-XHI31
DIL M80
+ DIL M150-XHI11
DIL M50
+ DIL M150-XHI11
ETR4-51
1 N/C 1 N/O
-
-
DIL M95
+ DIL M150-XHI31
DIL M95
+ DIL M150-XHI11
DIL M65
+ DIL M150-XHI11
ETR4-51
1 N/C 1 N/O
-
-
DIL M115
+ DIL M150-XHI31
DIL M115
+ DIL M150-XHI11
DIL M80
+ DIL M150-XHI11
ETR4-51
1 N/C 1 N/O
-
-
DIL M150
+ DIL M150-XHI31
DIL M150
+ DIL M150-XHI11
DIL M80
+ DIL M150-XHI11
ETR4-51
1 N/C 1 N/O
-
-
Overload relay settings
Star contactor
Timing relay
Starting
A: IN x 0.58
≤15 s
Protection of the motor in Y and d configuration
15-40 s
B: IN x 1
In Y configuration only conditional motor protection
C: IN x 0.58
No motor protection in Y configuration
> 40 s
Timing relay setting to approx. 10 s
Main circuit:
Depending on the aspired co-ordination type “1” or “2”, it is necessary to verify if
the fusing and the incomer to the mains and delta contactor can be used together,
or if they must be used separately.
37
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616
Busbar adapter
38
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616
Busbar adapter, 3-pole1
Version
Busbar adapter
25 A
Busbar adapter
32 A
Busbar adapter
63 A
Side module plugin on both sides
Rated
operational
voltage
Rated
operational
current
Conductor
crosssection
Adapter
width
Adapter
length
Moun- For use with
ting rail
Ue
V
Ie
A
mm
mm
690
25
AWG 12
(4 mm2)
45
200
1
PKZM0 +
DIL M 7 contactor
DIL M 9 contactor
DIL M 12 contactor
DIL M 15 contactor
690
25
AWG 12
(4 mm2)
90
200
1
PKZM0 +
BBA0R-25
2 x DIL M 7-01contactor 101453
2 x DIL M 9-01contactor
2 x DIL M 12-01contactor
PKZM0 and
2 x contactor
DIL M 7..M9..M12
via PKZM0-XRM12
690
32
AWG 10
(6 mm2)
45
200
2
PKZM0 +
DIL M 17 contactor
DIL M 25 contactor
DIL M 32 contactor
PKZM0 and contactor
DIL M17..M25..M32
via PKZ0-XM32DE
690
32
AWG 10
(6 mm2)
90
200
2
PKZM0 +
BBA0R-32
2 x DIL M 17-01contactor 101454
2 x DIL M 25-01contactor
2 x DIL M 32-01contactor
PKZM0 and
2 x contactor
DIL M17..M25..M32
via DILM32-XRL
PKZM0-XM32DE
690
40
AWG 8
(10 mm2)
72
260
2
PKZ2 +
DIL M 7 contactor
DIL M 9 contactor
DIL M 12 contactor
DIL M 17 contactor
DIL M 25 contactor
DIL M 32 contactor
DIL M 40 contactor
BBA2L-63
101480
PKZ2 and contactor
DIL M7..M9..M12
via flexible
connectors
MVS-LB0-00M-G
(AWG 12)
DIL M17..M25..M32
via flexible
connectors
MVS-LB0-0M-G
(AWG 10)
690
40
AWG 8
(10 mm2)
72
200
1
PKZ2
BBA2-63
101458
690
63
AWG 8
(10 mm2)
54
260
2
PKZM4 +
DIL M 17 contactor
DIL M 25 contactor
DIL M 32 contactor
DIL M 40 contactor
DIL M 50 contactor
DIL M 65 contactor
BBA4L-63
101459
690
63
AWG 8
(10 mm2)
54
200
1
PKZM4
BBA4-63
101457
9
200
4
Electrical
connections
Part no.
Article no.
Connection
elements
1
Notes
BBA0-25
101451
BBA0-32
101452
BBA-XSM
101484
PKZM0 and
contactor DIL
M7..M9..M12..M15
via PKZM0-XDM12
PKZM4 and contactor
DIL M 17..M25..M32
via flexible
connectors
MVS-LB0-0M-G
(AWG 10)
DIL M40..M50..M65
via contact module
PKZM4-XM65 DE
Can be grouped on
AD... for expansion of
the mounting width
PKZM0-XCM
239359
Can be used in all 60 mm systems. Suitable for 5 and 10 mm rail thickness' via combination foot
Mounting by snap fitting onto the voltage-free busbar
39
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616
Moeller addresses worldwide:
www.moeller.net/address
E-Mail: [email protected]
© 2005 by Moeller GmbH
Subject to alterations
W1200+2100-7548GB MDS/DFS 02/07
Printed in the Federal Republic of Germany (03/07)
Article No.: 284765
Xtra Combinations
Xtra Combinations from Moeller offers a range of products
and services, enabling the best possible combination options
for switching, protection and control in power distribution
and automation.
Using Xtra Combinations enables you to find more efficient
solutions for your tasks while optimising the economic
viability of your machines and systems.
It provides:
■ flexibility and simplicity
■ great system availability
■ the highest level of safety
All the products can be easily combined with one another
mechanically, electrically and digitally, enabling you to arrive
at flexible and stylish solutions tailored to your application –
quickly, efficiently and cost-effectively.
The products are proven and of such excellent quality that
they ensure a high level of operational continuity, allowing
you to achieve optimum safety for your personnel, machinery,
installations and buildings.
Thanks to our state-of-the-art logistics operation, our comprehensive dealer network and our highly motivated service
personnel in 80 countries around the world, you can count
on Moeller and our products every time. Challenge us!
We are looking forward to it!
For Moeller Electric Sales and Support call KMparts.com (866) 595-9616
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project