Control Systems

Control Systems
Rourkela
PCEC4303–CONTROL SYSTEM ENGINEERING
Module ‐1.............................................................................................................................................. 4 Basic Concepts of Control Systems, Open loop and closed loop systems ........................................ 4 Open‐loop systems:....................................................................................................................... 4 Closed‐loop systems ...................................................................................................................... 4 Transfer Function........................................................................................................................... 6 Differential Equations of Physical Systems: Mechanical, Translational Systems ............................. 7 Rotational systems, Gear Trains, Electrical Systems....................................................................... 10 Derivation of Transfer functions, Block Diagram Algebra............................................................... 16 Signal flow Graphs, Mason’s Gain Formula. ................................................................................... 25 Feedback characteristics of Control Systems: Effect of negative feedback on sensitivity. ............ 27 Bandwidths, Disturbance, linearizing effect of feedback, Regenerative feedback ........................ 28 A.C. Tachometer, Synchro, Stepper Motors. .................................................................................. 31 Module ‐2............................................................................................................................................ 42 Time response Analysis: Standard Test Signals............................................................................... 42 Time response of first order systems to unit step and unit ramp inputs ....................................... 45 Time Response of Second order systems to unit step input .......................................................... 46 Time Response specifications, Steady State Errors. ....................................................................... 49 Static Error Constants of different types of systems. Generalized error series and generalized error coefficients............................................................................................................................. 50 Stability and Algebraic Criteria, concept of stability, Necessary conditions of stability................. 51 Hurwitz stability criterion, Routh stability criterion, Application of the Routh stability. ............... 53 Root locus Technique: Root locus concepts, Rules of Construction of Root locus......................... 56 Systems with transportation lag, Phase‐Lead Compensation, phase‐Lag Compensation.............. 58 Phase‐Lag –Lead Compensation, Feedback Compensation............................................................ 61 Module ‐3............................................................................................................................................ 63 Frequency Response Analysis: Frequency domain specifications .................................................. 63 Procedure for drawing the bode plots. Determination of Gain Margin and Phase Margin from Bode plot ......................................................................................................................................... 72 1. Introduction to Control Systems: Basic elements of control system
• Open loop and closed loop systems
• Tracking System, Regulators
• Differential equation
• Transfer function
2. Modeling of electric systems: Translational and rotational mechanical systems
• Block diagram reduction techniques.
• Signal flow graph, Mason’s Gain Formula.
3. Feedback characteristics of Control Systems: Effect of negative feedback on sensitivity.
• Bandwidth, Disturbance.
• Linearizing effect of feedback, Regenerative feedback.
4. Control Components: D.C. Servomotors, A.C. Servomotors.
• A.C. Tachometer.
• Synchros, Stepper Motors. Module‐II
5. Time response Analysis: Standard Test Signals • Time response of first order systems to unit step and unit ramp inputs.
• Time Response of Second order systems to unit step input.
• Time Response specifications, Steady State Errors.
• Generalised error series and Gensalised error coefficients.
6. Stability Theory: Stability and Algebraic Criteria • Concept of stability, Necessary conditions of stability.
• Hurwitz stability criterion, Routh stability criterion.
• Application of the Routh stability criterion to linear feedback system.
• Relative stability by shifting the origin in s‐plane.
7. Root locus Technique: Root locus concepts, Rules of Construction of Root locus • Determination of Roots from Root locus for a specified open loop gain.
• Effect of adding open loop poles and zeros on Root locus.
• Root contours.
8. Compensation Technique: Systems with transportation lag.
• Lead compensation.
• Lag compensation
• Lead-Lag compensation
Module‐III
9. Frequency Response Analysis: Frequency domain specifications • Correlation between Time and Frequency Response with 10. Stability in frequency domain: Principle of argument, Nyquist stability criterion.
• Application of Nyquist stability criterion for linear feedback system.
• Constant Mcircles.
• Constant N‐Circles.
• Nichol’s chart.
11. Controllers: Concept of Proportional, Derivative and Integral Control actions.
• P, PD, PI, PID controllers.
• Zeigler‐Nichols method of tuning PID controllers.
Control Systems Module ‐1 Introduction to Control Systems: Basic elements of control system Open loop and closed loop systems, Tracking System, Regulators, and Differential equation, Transfer function. Modeling of electric systems ‐ Translational and rotational mechanical systems. Block diagram reduction techniques. Signal flow graph, Mason’s Gain Formula. Feedback characteristics of Control Systems: Effect of negative feedback on sensitivity. Bandwidth, Disturbance. Linearizing effect of feedback, Regenerative feedback. Control Components: D.C. Servomotors, A.C. Servomotors. A.C. Tachometer, Synchros, Stepper Motors. Lecture‐1 Basic Concepts of Control Systems, Open loop and closed loop systems 1. Basic elements of control system: In recent years, control systems have gained an increasingly importance in the development and advancement of the modern civilization and technology. Figure shows the basic components of a control system. Disregard the complexity of the system; it consists of an input (objective), the control system and its output (result). Practically day‐to‐day activities are affected by some type of control systems. There are two main branches of control systems: 1) Open‐loop systems and 2) Closed‐loop systems. Open-loop systems:
The open‐loop system is also called the non‐feedback system. This is the simpler of the two systems. A simple example is illustrated by the speed control of an automobile as shown in Figure 1‐2. In this open‐
loop system, there is no way to ensure the actual speed is close to the desired speed automatically. The actual speed might be way off the desired speed because of the wind speed and/or road conditions, such as uphill or downhill etc. Example‐Automatic washing Machine, immersion rod, A field control d.c motor and automatic control of traffic lamp.
.
(Fig1.2 Basic open-loop system)
Closed-loop systems:
The closed‐loop system is also called the feedback system. A simple closed‐system is shown in Figure 1‐3. It has a mechanism to ensure the actual speed is close to the desired speed automatically. In closed loop control systems the control action is dependent on desired output .If any system having one or more feedback paths forming a closed loop system. Example‐air conditioners are provided with thermostat.
BPUT Page 4 Control Systems BPUT Page 5 Control Systems Lecture‐2
Servo Mechanism/Tracking System, Regulators.
Transfer Function
A simpler system or element may be governed by first order or second order differential equation. When several elements are connected in sequence, say ”n” elements, each one with first order, the total order of the system will be nth order. In general, a collection of components or system shall be represented by nth order differential equation In control systems, transfer function characterizes the input output relationship of components or systems that can be described by Liner Time Invariant Differential Equation. In the earlier period, the input output relationship of a device was represented graphically. In a system having two or more components in sequence, it is very difficult to find graphical relation between the input of the first element and the output of the last element. This problem is solved by transfer function. Definition of Transfer Function
Transfer function of a LTIV system is defined as the ratio of the Laplace Transform of the output variable to the Laplace Transform of the input variable assuming all the initial condition as zero. Properties of Transfer Function
• The transfer function of a system is the mathematical model expressing the differential equation that relates the output to input of the system. • The transfer function is the property of a system independent of magnitude and the nature of the input. • The transfer function includes the transfer functions of the individual elements. But at the same time, it does not provide any information regarding physical structure of the system. • The transfer functions of many physically different systems shall be identical. • If the transfer function of the system is known, the output response can be studied for various types of inputs to understand the nature of the system. • If the transfer function is unknown, it may be found out experimentally by applying known inputs to the device and studying the output of the system. How you can obtain the transfer function (T. F.)
• Write the differential equation of the system. • Take the L. T. of the differential equation, assuming all initial condition to be zero. • Take the ratio of the output to the input. This ratio is the T. F. Mathematical Model of control systems
A control system is a collection of physical object connected together to serve an objective. The mathematical model of a control system constitutes a set of differential equation. BPUT Page 6 Control Systems Lecture-3
Differential Equations of Physical Systems: Mechanical, Translational Systems.
2. Modeling of electric systems:‐ Mechanical Translational systems The model of mechanical translational systems can obtain by using three basic elements mass, spring and dashpot. When a force is applied to a translational mechanical system, it is opposed by opposing forces due to mass, friction and elasticity of the system. The force acting on a mechanical body is governed by Newton‘s second law of motion. For translational systems it states that the sum of forces acting on a body is zero. Force balance equations of idealized elements Consider an ideal mass element shown in fig. which has negligible friction and elasticity. Let a force be applied on it. The mass will offer an opposing force which is proportional to acceleration of a body. Let
= applied force
= opposing force due to mass
Here
By Newton‘s second law,
Consider an ideal frictional element dash‐pot shown in fig. which has negligible mass and elasticity. Let a force be applied on it. The dashpot will be offer an opposing force which is proportional to velocity of the body. Let
= applied force
= opposing force due to friction
Here,
By Newton‘s second law,
Consider an ideal elastic element spring shown in fig. which has negligible mass and friction. BPUT Page 7 Control Systems Let = applied force
= opposing force due to elasticity
Here,
By Newton‘s second law,
Mechanical Rotational Systems The model of rotational mechanical systems can be obtained by using three elements, moment of inertia [J] of mass, dash pot with rotational frictional coefficient [B] and torsion spring with stiffness[k].When a torque is applied to a rotational mechanical system, and it is opposed by opposing torques due to moment of inertia, friction and elasticity of the system. The torque acting on rotational mechanical bodies is governed by Newton‘s second law of motion for rotational systems. Torque balance equations of idealized elements Consider an ideal mass element shown in fig. which has negligible friction and elasticity. The opposing torque due to moment of inertia is proportional to the angular acceleration.
Let T = applied torque
T j =opposing torque due to moment of inertia of the body
Here, T j α d2 θ/dt2
By Newton‘s law
T= T j = J d2θ/dt2
Consider an ideal frictional element dash pot shown in fig. which has negligible moment of inertia and elasticity. Let a torque be applied on it. The dash pot will offer an opposing torque is proportional to angular velocity of the body. Let T = applied torque
Tb =opposing torque due to friction
Here
BPUT Page 8 Control Systems By Newton‘s law
Consider an ideal elastic element, torsion spring as shown in fig. which has negligible moment of inertia and friction. Let a torque be applied on it. The torsion spring will offer an opposing torque which is proportional to angular displacement of the body. Let T = applied torque
=opposing torque due to friction
Here,
By Newton‘s law BPUT Page 9 Control Systems Lecture‐4 Rotational systems, Gear Trains, Electrical Systems. Modeling of electrical system
• Electrical circuits involving resistors, capacitors and inductors are considered. The behavior of
such systems is governed by Ohm‘s law and Kirchhoff‘s laws.
• Resistor: Consider a resistance of ‘R‘ carrying current ‘I‘ Amps as shown in Fig (a), then the
voltage drop across it is v = R I
•
Inductor: Consider an inductor “L‘ H carrying current ‘I‘ Amps as shown in Fig (a), then the
voltage drop across it can be written as
•
Capacitor: Consider a capacitor “C‘ F carrying current “I‘ Amps as shown in Fig (a), then the
voltage drop across it can be written as
Steps for modeling of electrical system
• Apply Kirchhoff‘s voltage law or Kirchhoff‘s current law to form the differential equations
describing electrical circuits comprising of resistors, capacitors, and inductors.
• Form Transfer Functions from the describing differential equations.
• Then simulate the model.
Example
BPUT Page 10 Control Systems Electrical systems
LRC circuit. Applying Kirchhoff‘s voltage law to the system shown. We obtain the following equation
Resistance circuit
(1)
(2)
Equation (1) & (2) give a mathematical model of the circuit. Taking the L.T. of equations (1) & (2),
assuming zero initial conditions, we obtain
The transfer function
Armature-Controlled dc motors
The dc motors have separately excited fields. They are either armature‐controlled with fixed field or field‐controlled with fixed armature current. For example, dc motors used in instruments employ a fixed permanent‐magnet field, and the controlled signal is applied to the armature terminals. Consider the armature‐controlled dc motor shown in the following figure Ra = armature-winding resistance, ohms
La = armature-winding inductance, henrys
I a = armature-winding current, amperes
I f = field current, a-pares
E a = applied armature voltage, volt
E b = back emf, volts
θ = angular displacement of the motor shaft, radians
T = torque delivered by the motor, Newton*meter
J = equivalent moment of inertia of the motor and load referred to the motor shaft kg .m2
f = equivalent viscous-friction coefficient of the motor and load referred to the motor shaft. Newton*m/rad/s
T = k1 I a ψ where ψ is the air gap flux, ψ = k f I f, k1 is constant
BPUT Page 11 Control Systems For the constant flux
(1)
Where Kb is a back emf constant
The differential equation for the armature circuit
(2)
The armature current produces the torque which is applied to the inertia and friction; hence
(3)
Assuming that all initial conditions are condition are zero/and taking the L.T. of equations (1), (2) & (3), we
obtain
The T.F can be obtained is
BPUT Page 12 Control Systems Lecture‐5 Analogy between Mechanical and electrical quanties, Thermal systems, fluid systems.
Analogous Systems
Let us consider a mechanical (both translational and rotational) and electrical system as shown in the
fig.
From the fig (a)
We get
From the fig (b)
(1)
We get
From the fig (c)
(2)
(3)
We get
Where
They are two methods to get analogous system. These are (i) force- voltage (f-v) analogy and (ii) forcecurrent (f-c) analogy
(i)Force –Voltage (f-v) Analogy
Translational
Force (F)
Mass (M)
Damper (D)
Spring (K)
Displacement (x)
Velocity (u)
Electrical
Voltage (V)
Inductance (L)
Resistance (R)
Elastance (1/C)
Charge (q)
Current (I)
(ii)Force – Current (f-c) Analogy
Translational
Electrical
Force (F)
Current (I)
Mass (M)
Capacitance (C)
Damper (D)
Reciprocal of Inductance (1/L)
Spring (K)
Conductance (1/K)
Displacement (x)
Flux Linkage ( )
Velocity
BPUT Voltage
Rotational
Torque (T)
Inertia (J)
Damper (D)
Spring (K)
Displacement ( )
Velocity ( )
Rotational
Torque (T)
Inertia (J)
Damper (D)
Spring (K)
Displacement (
)
Velocity
Page 13 Control Systems Problem
Find the system equation for system shown in the fig. And also determine f-v and f-i analogies
For free body diagram M1
(1)
For free body diagram M2
(2)
Force –voltage analogy
From Eq. (1) we get
(3)
From Eq. (2) we get
(4)
From Eq. (3) and (4) we can draw f-v analogy
Force–current analogy BPUT Page 14 Control Systems From Eq. (1) we get
(5)
From eq (2) we get
(6)
From eq (5) and (6) we can draw force-current analogy
BPUT Page 15 Control Systems Lecture-6
Derivation of Transfer functions, Block Diagram Algebra.
The system can be represented in two forms: • Block diagram representation • Signal flow graph Block diagram A pictorial representation of the functions performed by each component and of the flow of signals Basic elements of a block diagram • Blocks • Transfer functions of elements inside the blocks • Summing points • Take off points • Arrow Block diagram A control system may consist of a number of components. A block diagram of a system is a pictorial representation of the functions performed by each component and of the flow of signals. The elements of a block diagram are block, branch point and summing point. Block In a block diagram all system variables are linked to each other through functional blocks. The functional block or simply block is a symbol for the mathematical operation on the input signal to the block that produces the output. Summing point Although blocks are used to identify many types of mathematical operations, operations of addition and subtraction are represented by a circle, called a summing point. As shown in Figure a summing point may have one or several inputs. Each input has its own appropriate plus or minus sign. A summing point has only one output and is equal to the algebraic sum of the inputs. BPUT Page 16 Control Systems A takeoff point is used to allow a signal to be used by more than one block or summing point. The transfer function is given inside the block • The input in this case is E(s) • The output in this case is C(s) • C(s) = G(s) E(s) • Functional block – each element of the practical system represented by block with its • Branches – lines showing the connection between the blocks • Arrow – associated with each branch to indicate the direction of flow of signal • Closed loop system • Summing point – comparing the different signals • Take off point – point from which signal is taken for feed back Advantages of Block Diagram Representation • Very simple to construct block diagram for a complicated system • Function of individual element can be visualized • Individual & Overall performance can be studied • Over all transfer function can be calculated easily Disadvantages of Block Diagram Representation • No information about the physical construction • Source of energy is not shown BPUT Page 17 Control Systems Simple or Canonical form of closed loop system R(s) – Laplace of reference input r(t) C(s) – Laplace of controlled output c(t) E(s) – Laplace of error signal e(t) B(s) – Laplace of feedback signal b(t) G(s) – Forward path transfer function H(s) – Feedback path transfer function Block diagram reduction technique Because of their simplicity and versatility, block diagrams are often used by control engineers to describe all types of systems. A block diagram can be used simply to represent the composition and interconnection of a system. Also, it can be used, together with transfer functions, to represent the cause‐
and‐effect relationships throughout the system. Transfer Function is defined as the relationship between an input signal and an output signal to a device Block diagram rules Cascaded blocks Moving a summer beyond the block moving BPUT Page 18 Control Systems Moving a summer ahead of block Moving a pick‐off ahead of block Moving a pick‐off beyond a block Eliminating a feedback loop Cascaded Subsystems BPUT Page 19 Control Systems Parallel Subsystems Feedback Control System
Procedure to solve Block Diagram Reduction Problems • Step 1: Reduce the blocks connected in series • Step 2: Reduce the blocks connected in parallel • Step 3: Reduce the minor feedback loops • Step 4: Try to shift take off points towards right and Summing point towards left • Step 5: Repeat steps 1 to 4 till simple form is obtained • Step 6: Obtain the Transfer Function of Overall System BPUT Page 20 Control Systems Problem 1 Obtain the Transfer function of the given block diagram Combine G1, G2 which are in series Combine G3, G4 which are in Parallel
BPUT Page 21 Control Systems Reduce minor feedback loop of G1, G2 and H1
Transfer function 2. Obtain the transfer function for the system shown in the fig BPUT Page 22 Control Systems 3. Obtain the transfer function C/R for the block diagram shown in the fig The take‐off point is shifted after the block G2 Reducing the cascade block and parallel block Replacing the internal feedback loop BPUT Page 23 Control Systems Equivalent block diagram Transfer function BPUT Page 24 Control Systems Lecture-7
Signal flow Graphs, Mason’s Gain Formula.
Signal Flow Graph Representation
Signal Flow Graph Representation of a system obtained from the equations, which shows the flow of the signal Signal flow graph A signal flow graph is a diagram that represents a set of simultaneous linear algebraic equations. By taking Laplace transfer, the time domain differential equations governing a control system can be transferred to a set of algebraic equation in s‐domain. A signal‐flow graph consists of a network in which nodes are connected by directed branches. It depicts the flow of signals from one point of a system to another and gives the relationships among the signals. Basic Elements of a Signal flow graph •
•
•
•
•
Node ‐ a point representing a signal or variable. Branch – unidirectional line segment joining two nodes. Path – a branch or a continuous sequence of branches that can be traversed from one node to another node. Loop – a closed path that originates and terminates on the same node and along the path no node is met twice. Nonteaching loops – two loops are said to be non touching if they do not have a common node. Mason’s gain formula The relationship between an input variable and an output variable of signal flow graph is given by the net gain between the input and the output nodes is known as overall gain of the system. Mason‘s gain rule for the determination of the overall system gain is given below. Where = gain between X in and X out =output node variable = input node variable = total number of forward paths = path gain of the k th forward path Δ = 1‐(sum of loop gains of all individual loop) + (sum of gain product of all possible combinations of two non touching loops) – (sum of gain products of all possible combination of three non touching loops) BPUT Page 25 Control Systems Problem Forward path gain: Closed loop gain 1.
2.
3.
4.
Non touching loops taken two at a time 5. Loop 1 and loop 2: 6. Loop 1 and loop 3: 7. Loop 2 and loop 3: Non touching loops taken three at a time 8. Loop 1, 2, 3: Now, Portion of not touching the forward path Hence, BPUT Page 26 Control Systems Lecture-8
Feedback characteristics of Control Systems: Effect of negative feedback on sensitivity.
3.Feedback characteristics of Control Systems: In control system ,the feedback reduces the error, also reduces the sensitivity of the system to parameter variations .The parameter may vary due to some change in conditions .The variation in parameter affects the performance of the system. So it is necessary to make the system in sensitive to such parameter variations. Effect of feedback on sensitivity The parameters of any control system changes with the change environment conditions. Also these parameters cannot be constant throughout the life. These parameter variations affect the performance of the system. For example, the resistance of winding of a motor changes due to change in temperature during its operation. • Sensitivity to model uncertainties Open loop: Closed‐loop: → Reduced below that of the open‐loop sys by increasing G*H (>>1.0). * if GH >>1.0 → Feedback components should not be varied with environmental changes →change in H(s) directly affects output response BPUT Page 27 Control Systems Lecture-9
Bandwidths, Disturbance, linearizing effect of feedback, Regenerative feedback
Find transfer function of a feedback control system ‐ Closed‐ loop control •
Has ability to reduce system sensitivity •
If for all complex frequency of interest, then: •
By increasing the gain of it reduces the effect of parameters of the process, •
But, making When – Process, on the input variation of the , is reduced can lead to highly oscillatory and even unstable response , is changed Open loop – Closed loop – Then the change in the output is BPUT Page 28 Control Systems , as is often the case, we have when Change of the output is reduced by Disturbance in a system State Variable Model The transfer function T.F from the control Input BPUT T.F from D(s) to the Page 29 Control Systems M(s) to the output
output Disturbance in a closed‐loop system: Where The loop gain must be made large to reduce the system sensitivity Reducing Disturbance •
Reduce the gain •
Increase the loop gain •
Reduce the disturbance d(t) •
Feed forward method if the disturbance can be measured BPUT (Choice of ) Page 30 Control Systems Lecture-10
A.C. Tachometer, Synchro, Stepper Motors.
4.Control Components: SYNCHROS: A synchro is a type of rotary electrical transformer that is used for measuring the angle of a rotating machine such as an antenna platform. In its general physical construction, it is much like an electric motor. The primary winding of the transformer, fixed to the rotor, is excited by an alternating current, which by electromagnetic induction, causes currents to flow in three star‐connected secondary windings fixed at 120 degrees to each other on the stator. The relative magnitudes of secondary currents are measured and used to determine the angle of the rotor relative to the stator, or the currents can be used to directly drive a receiver synchro that will rotate in unison with the synchro transmitter Synchro Operation: On a practical level, Synchro resembles motors, in that there is a rotor, stator, and a shaft. Ordinarily, slip rings and brushes connect the rotor to external power. A synchro transmitter's shaft is rotated by the mechanism that sends information, while the synchro receiver's shaft rotates a dial, or operates a light mechanical load. Single and three‐phase units are common in use, and will follow the other's rotation when connected properly. One transmitter can turn several receivers; if torque is a factor, the transmitter must be physically larger to source the additional current. Uses of Synchro: • Synchro systems were first used in the control system of the Panama Canal in the early 1900s to transmit lock gate and valve stem positions and water levels to the control desks • Fire‐control system designs developed during World War II used synchros extensively, to transmit angular information from guns and sights to an analog fire control computer, and to transmit the desired gun position back to the gun location. BPUT Page 31 Control Systems Tachometers Tachometer is an electromechanical unit which generates an electrical output proportional to the speed of the shaft. In automatic control system tachometer performs two main functions: •
•
Stabilization of system Computation of closed loops in a control system AC Tachometer: The AC tachometer is a device, which is similar to a two phase induction motor, in which two stator windings are placed in quadrature with each other and rotor is short circuited. In AC Tachometer, a sinusoidal voltage of rated value is applied to the primary winding, which is known as reference winding, the secondary winding is placed 90 degrees apart from primary winding. The magnitude of sinusoidal output voltage is directly proportional to the speed of rotor. D.C. Tachometer
In control systems most common type of tachometers are d.c. tachometers .D.C. Tachometer contains an iron core rotor and permanent magnet. The magnetic field is provided by the permanent magnet and no external supply voltage is necessary. The input to the tachometer is the speed of the shaft and the output is voltage which is proportional to the angular speed of the shaft. Where e = tachometer generator voltage K =tachometer sensitivity = angular speed of shaft Laplace transform of equation, Hence transfer function of tachometer is BPUT Page 32 Control Systems In d.c tachometer the winding on rotor are connected to the commutator and the output voltage is taken across the brushes. The permanent magnet tachometers are compact and reliable but having high inertia. For reducing the voltage drop across the brushes, metal brushes with silver tips are used.
BPUT Page 33 Control Systems Lecturer-11
Stepper motors, Amplidyne
Stepper Motors: In stepper motors, the movement of rotor is in discrete steps. A stepper motor is electromechanical device. There are three types of stepper motors. 1. Variable reluctance motors 2. Permanent magnet motors 3. Hybrid type •
•
•
•
Conventional servo motors are classified as continuous rotation motors Stepper motors rotate through a specific number of degrees, or steps, then stop Each incoming pulse results in the shaft turning a specific angular distance Stepper motors can control velocity, distance, and direction of mechanical load Permanent Magnet Stepper Motor: •
•
•
BPUT PM stepper motors have rotor teeth made of permanent magnets Reaction of the rotor teeth to stator fields provides torque for the motor. Signals are applied to the stator to determine direction and step rate of the rotor. Page 34 Control Systems Stepper Motor Speed Stepper motor speed depends upon the step angle and stepping rate N=(Y×S)/6 Where n= speed in RPM Y=step angle in degrees S= Steps per second 6= Formula constant Amplidyne:‐ An Amplidyne is a rotating amplifier. It is a prime‐mover‐driven d.c. generator whose output power can be controlled by a small field power input. An amplidyne is capable of giving a controlled power output in the range of a few hundred to few thousand watts with a power amplification of the order of 10,000 or more and hence finds wide application in feedback control system. Study of amplidyne whose output power can be controlled by a small field power input. For studying the characteristics. (i) We plot a graph of Output voltage against effective field current with no load, full load (500W), and without compensation winding effect (ii) We draw the schematic diagram of an amplidyne system BPUT Page 35 Control Systems BPUT Page 36 Control Systems Lecture‐12 D.C. Servomotors, A.C. Servomotors. Servomotor: The servo system is the one, in which the output is some mechanical variable such as position, velocity or acceleration. The motors used in the servo systems are called servomotors. These motors are usually coupled to the output shaft for power matching. There are two types of servo motors. 1. DC Servomotors 2. AC Servomotors 1. DC Servomotors: D.C. servomotors are separately excited or permanent magnet d.c. servomotor .The armature of d.c servomotor has a large resistance, therefore torque speed characteristics is linear. The torque speed characteristics Shows in fig(c) and fig(a) shows the schematic diagram of separately excited d.c. servomotor. •
DC servo motors are controlled by DC command signals applied directly to coils. Time constant for field circuit is large, due to large time constant, the Response is slow and therefore they are not commonly used. • The magnetic fields that are formed interact with permanent magnets and cause the rotating member to turn. • One type of PM uses a wound armature and brushes like a conventional DC motor, but uses magnets as pole pieces • Another type uses wound field coils and a permanent magnet rotor. 2. AC Servomotors: ‐ These motor having two parts namely stator and rotor. A.C. Servomotors are two phase induction motor. The stator has two distributed windings. These windings are displayed from each other by 900. One winding is called main winding or reference winding. The reference winding is excited by constant a.c. voltage. Other winding is called control winding, these winding is excited by variable control voltage of the same frequency as the reference winding but having a phase displacement of 900 electrical. The variable control voltage for control winding is obtained from a servo amplifier. The rotor of a.c. servomotors are of two types (a)squirrel cage rotor (b)drag cup type rotor .The squirrel cage rotor having large length and small diameter, so its resistance is very high. The air gap of squirrel cage is kept small. In drag cup type there are two air gaps. BPUT Page 37 Control Systems For the rotor a cup of nonmagnetic conducting material is used. A stationary iron core is placed between the conducting cup to complete the magnetic circuit .The resistance of drag cup type is high and having high starting torque .Fig(a) shows the schematic diagram of two phase a.c. servomotor and fig(b) shows the two types of rotor. Fig(a) Fig(b) • Controlled by AC command signals applied to the coils. • AC Brushless Servo Motor Operates on the same principle as single‐phase induction motor. Torque speed characteristic: BPUT Page 38 Control Systems Application of servomotors: Servomotor is widely used in radars, electromechanical actuators, computers, machine tools, tracking and guidance system, process controllers and robots. UNIT I
CONTROL SYSTEM MODELLING
1. What is control system? A system consists of a number of components connected together to perform a specific function. In a system when the output quantity is controlled by varying the input quantity then the system is called control system. 2. What are the two major types of control system? The two major types of control system are open loop and closed loop. 3. Define open loop control system. The control system in which the output quantity has no effect upon the input quantity is called open loop control system. This means that the output is not feedback to the input for correction. 4. Define closed loop control system. The control system in which the output has an effect upon the input quantity so as to maintain the desired output values are called closed loop control system. 5. What are the components of feedback control system? The components of feedback control system are plant, feedback path elements, error detector and controller. 6. Define transfer function. The T.F of a system is defined as the ratio of the Laplace transform of output to Laplace transform of input with zero initial conditions. 7. What are the basic elements used for modeling mechanical translational system. Mass, spring and dashpot 8. What are the basic elements used for modeling mechanical rotational system? Moment of inertia J, dashpot with rotational frictional coefficient B and torsion spring with stiffness K 9. Name two types of electrical analogous for mechanical system. The two types of analogies for the mechanical system are ‐ Force voltage and force current analogy. 10. What is block diagram? A block diagram of a system is a pictorial representation of the functions performed by each component of the system and shows the flow of signals. The basic elements of block diagram arrow block, branch point and summing point. 11. What is the basis for framing the rules of block diagram reduction technique? The rules for block diagram reduction technique are framed such that any modification made on the diagram does not alter the input output relation. 12. What is a signal flow graph? BPUT Page 39 Control Systems A signal flow graph is a diagram that represents a set of simultaneous algebraic equations .By taking L.T the time domain differential equations governing a control system can be transferred to a set of algebraic equations in s‐domain. 13. What is transmittance? The transmittance is the gain acquired by the signal when it travels from one node to another node in signal flow graph. 14. What is sink and source? Source is the input node in the signal flow graph and it has only outgoing branches. Sink is an output node in the signal flow graph and it has only incoming branches. 15. Define non touching loop. The loops are said to be non touching if they do not have common nodes. 16. Write Masons Gain formula. Masons Gain formula states that the overall gain of the system is and Where M = gain between = output node variable = input node variable N = total number of forward paths = path gain of the k the forward path Δ =1‐(sum of loop gains of all individual loop) + (sum of gain product of all possible combinations of two non touching loops) – (sum of gain products of all possible combination of three non touching loops) 17. Write the analogous electrical elements in force voltage analogy for the elements of mechanical translational system. Force ‐ voltage e Velocity v‐ current i Displacement x‐ charge q Frictional coefficient B‐ Resistance R Mass M‐ Inductance L Stiffness K‐ Inverse of capacitance 1/C 18. Write the analogous electrical elements in force current analogy for the elements of mechanical translational system. Force ‐ current i Velocity v ‐ voltage v Displacement x‐ flux Frictional coefficient B‐ conductance 1/R Mass M ‐ capacitance C Stiffness K ‐ Inverse of inductance 1/L 19. Write the force balance equation of ideal mass element. BPUT Page 40 Control Systems 20. Write the force balance equation of ideal dashpot element. 21. Write the force balance equation of ideal spring element. 22. Distinguish between open loop and closed loop system Open loop and Closed loop • Inaccurate • Simple and economical • The changes in output due to external disturbance are not corrected. • They are generally stable • Accurate • Complex and costlier • The changes in output due to external disturbances are corrected automatically. • Great efforts are needed to design a stable system. 23. What is servomechanism? The servomechanism is a feedback control system in which the output is mechanical position (or time derivatives of position velocity and acceleration). BPUT Page 41 Control Systems Module ‐2 Lecture-13
Time response Analysis: Standard Test Signals.
5.Time response Analysis: Introduction
•
•
•
•
•
•
After deriving a mathematical model of a system, the system performance analysis can be done in various methods. In analyzing and designing control systems, a basis of comparison of performance of various control systems should be made. This basis may be set up by specifying particular test input signals and by comparing the responses of various systems to these signals. The system stability, system accuracy and complete evaluation are always based on the time response analysis and the corresponding results Next important step after a mathematical model of a system is obtained. To analyze the system‘s performance. Normally use the standard input signals to identify the characteristics of system‘s response 1. Step function 2. Ramp function 3. Impulse function 4. Parabolic function 5. Sinusoidal function It is an equation or a plot that describes the behavior of a system and contains much information about it with respect to time response specification as Over shooting, settling time, peak time, rise time and steady state error. Time response is formed by the transient response and the steady state response. Time response = Transient response + Steady state response Transient time response (Natural response) describes the behavior of the system in its first short time until arrives the steady state value and this response will be our study focus. If the input is step function then the output or the response is called step time response and if the input is ramp, the response is called ramp time response ... etc. Classification of Time Response Transient response Steady state response y(t) = yt(t) + yss(t) Transient Response The transient response is defined as the part of the time response that goes to zero as time becomes very large. Thus yt(t) has the property Lim yt(t) = 0 t ‐‐>∞ BPUT Page 42 Control Systems The time required to achieve the final value is called transient period. The transient response may be exponential or oscillatory in nature. Output response consists of the sum of forced response (form the input) and natural response (from the nature of the system).The transient response is the change in output response from the beginning of the response to the final state of the response and the steady state response is the output response as time is approaching infinity (or no more changes at the output). Steady State Response: The steady state response is the part of the total response that remains after the transient has died out. For a position control system, the steady state response when compared to with the desired reference position gives an indication of the final accuracy of the system. If the steady state response of the output does not agree with the desired reference exactly, the system is said to have steady state error. Time response = Transient response + Steady state response Typical Input Signals 1. Impulse Signal 2. Step Signal 3. Ramp Signal 4. Parabolic Signal BPUT Page 43 Control Systems Time Response Analysis & Design •
•
•
•
•
Two types of inputs can be applied to a control system Command Input or Reference Input yr(t) Disturbance Input w(t) (External disturbances w(t) are typically uncontrolled variations in the load on a control system) In systems controlling mechanical motions, load disturbances may represent forces. In voltage regulating systems, variations in electrical load area major source of disturbances. Test Signals 1. Input r(t) R(S) 2. Step input A A/S 3. Ramp input At A/S2 4. Parabolic input At2/2 A/S3 5. Impulse input δ(t) 1 BPUT Page 44 Control Systems Lecture‐14 Time response of first order systems to unit step and unit ramp inputs First‐order system time response • Transient • Steady‐state First Order System Step Response of First Order System Evolution of the transient response is determined by the pole of the transfer function at s=‐1/t where t is the time constant Also, the step response can be found: Impulse response Exponential Step response Step, Exponential Ramp response BPUT Ramp, Step, Exponential Page 45 Control Systems Lecture‐15 Time Response of Second order systems to unit step input Second-order systems: LTI second-order system
Second-Order Systems
Second order system responses
Over damped response:
Poles: Two real at
BPUT -σ1 -σ2
Page 46 Control Systems Natural response: Two exponentials with time constants equal to the reciprocal of the pole location
Under damped response:
Poles: two complexes at Natural response: Damped sinusoid with an exponential envelope whose time constant is equal to the reciprocal of the pole‘s radian frequency of the sinusoid, the damped frequency of oscillation, is equal to the imaginary part of the poles Un-damped response:
Poles: Two imaginary at Natural response: Undammed sinusoid with radian frequency equal to the imaginary part of the poles Critically damped responses:
Poles: Two real at
Natural response: One term is an exponential whose time constant is equal to the reciprocal of the pole location. Another term product of time and an exponential with time constant equal to the reciprocal of the pole location Second order system responses damping cases
BPUT Page 47 Control Systems Second‐ order step response Complex poles BPUT Page 48 Control Systems Lecture-16
Time Response specifications, Steady State Errors.
Steady State Error:
- Consider a unity feedback system
- Transfer function between e(t) and r(t)
Steady state error is
BPUT Page 49 Control Systems Lecture-17 ,18
Static Error Constants of different types of systems. Generalized error series and generalized error coefficients Error constants Steady state error Type of system Unit step input Unit ramp input Unit parabolic input
0 K 0 0 1/(1+K) 1 K 0 2 3 0 1/K K 0 0 1/K 0 0 0 Output Feedback Control Systems
Feedback only the output signal
– Easy access
– Obtainable in practice
6.Stability Theory: Stability and Algebraic Criteria:‐ A system is stable if any bounded input produces a
bounded output for all bounded initial conditions.
BPUT Page 50 Control Systems Lecture-19 Stability and Algebraic Criteria, concept of stability, Necessary conditions of stability. Basic concept of stability
Stability of the system and roots of characteristic equations
Characteristic Equation
BPUT Page 51 Control Systems Consider an nth-order system whose the characteristic equation (which is also the denominator of the transfer
function) is
BPUT Page 52 Control Systems Lecture‐20,21 Hurwitz stability criterion, Routh stability criterion, Application of the Routh stability. Routh Hurwitz Criterion
•
•
•
Goal: Determining whether the system is stable or unstable from a characteristic equation in
polynomial form without actually solving for the roots
Routh’s stability criterion is useful for determining the ranges of coefficients of polynomials
for stability, especially when the coefficients are in symbolic (non numerical) form
To find Kmar & ω
A necessary condition for Routh’s Stability
•
•
•
•
A necessary condition for stability of the system is that all of the roots of its characteristic
equation have negative real parts, which in turn requires that all the coefficients be positive.
A necessary (but not sufficient) condition for stability is that all the coefficients of the
polynomial characteristic equation are positive & none of the co-efficient vanishes.
Routh’s formulation requires the computation of a triangular array that is a function of the
coefficients of the polynomial characteristic equation.
A system is stable if and only if all the elements of the first column of the Routh array are
positive
Method for determining the Routh array
Consider the characteristic equation
Routh array method
Then add subsequent rows to complete the Routh array
Compute elements for the 3rd row:
…
BPUT Page 53 Control Systems Given the characteristic equation, Is the system described by this characteristic equation stable?
Answer:
•
•
All the coefficients are positive and nonzero
Therefore, the system satisfies the necessary condition for stability
• We should determine whether any of the coefficients of the first column of the Routh array are
negative S6: 1 3 1 4 S5: 4 2 4 0 S4: 2.5 0 4 S3: 2 ‐2.4 0 S2: 3 4 S1: ‐1.6 0 S0: 4 The elements of the 1st column are not all positive. Then the system is unstable.
Special cases of Routh’s criteria
Case 1: All the elements of a row in a RA are zero
•
Form Auxiliary equation by using the co-efficient of the row which is just above the row of zeros
•
Find derivative of the A.E.
•
Replace the row of zeros by the co-efficient of dA(s)/ds
•
complete the array in terms of these coefficients
•
analyze for any sign change, if so, unstable
•
no sign change, find the nature of roots of AE
•
non-repeated imaginary roots - marginally stable
•
repeated imaginary roots – unstable
Case 2: First element of any of the rows of RA is
BPUT Page 54 Control Systems •
•
Zero and the same remaining row contains at least one non-zero element
Substitute a small positive no. “ε‘ in place of zero and complete the array.
•
Examine the sign change by taking Lt ε = 0
BPUT Page 55 Control Systems Lecture-22, 23
Root locus Technique: Root locus concepts, Rules of Construction of Root locus
7.Root locus Technique: •
•
Introduced by W. R. Evans in 1948 Graphical method, in which movement of poles in the s‐plane is sketched when some parameter is varied • The path taken by the roots of the characteristic equation when open loop gain K is varied from 0 to ∞ are called root loci • Direct Root Locus = 0 < k < ∞ • Inverse Root Locus = ‐ ∞ < k < 0 Root Locus Analysis: •
•
The roots of the closed‐loop characteristic equation define the system characteristic responses Their location in the complex s‐plane lead to prediction of the characteristics of the time domain responses in terms of: o damping ratio, ζ o natural frequency, w n o damping constant, σ → first‐order modes o Consider how these roots change as the loop gain is varied from 0 to ∞ Basics of Root Locus: •
•
•
•
•
•
•
•
Symmetrical about real axis RL branch starts from OL poles and terminates at OL zeroes No. of RL branches = No. of poles of OLTF Centroid is common intersection point of all the asymptotes on the real axis Asymptotes are straight lines which are parallel to RL going to ∞ and meet the RL at ∞ No. of asymptotes = No. of branches going to ∞ At Break Away point , the RL breaks from real axis to enter into the complex plane At BI point, the RL enters the real axis from the complex plane Constructing Root Locus: •
•
•
•
•
Locate the OL poles & zeros in the plot Find the branches on the real axis Find angle of asymptotes & centroid Φ a= ±180º(2q+1) / (n‐m) σa = (Σ poles – Σ zeroes) / (n‐m) •
Find BA and BI points • Find Angle Of departure (AOD) and Angle Of Arrival (AOA) • AOD = 180º‐ (sum of angles of vectors to the complex pole from all other poles) + (Sum of angles of vectors to the complex pole from all zero) BPUT Page 56 Control Systems •
AOA = 180º‐ (sum of angles of vectors to the complex zero from all other zeros) + (sum of angles of vectors to the complex zero from poles) • Find the point of intersection of RL with the imaginary axis. Application of the Root Locus Procedure: Step 1: Write the characteristic equation as Step 2: Rewrite preceding equation into the form of poles and zeros as follows Step 3: • Locate the poles and zeros with specific symbols, the root locus begins at the open‐loop poles and ends at the open loop zeros as K increases from 0 to infinity • If open‐loop system has n‐m zeros at infinity, there will be n‐m branches of the root locus approaching the n‐m zeros at infinity Step 4: • The root locus on the real axis lies in a section of the real axis to the left of an odd number of real poles and zeros Step 5: • The number of separate loci is equal to the number of open‐loop poles Step 6: • The root loci must be continuous and symmetrical with respect to the horizontal real axis Step 7: • The loci proceed to zeros at infinity along asymptotes centered at centroid and with angles Step 8: •
The actual point at which the root locus crosses the imaginary axis is readily evaluated by using Routh‘s criterion Step 9: • Determine the breakaway point d (usually on the real axis) Step 10: • Plot the root locus that satisfy the phase criterion Step 11: • Determine the parameter value K1 at a specific root using the magnitude criterion BPUT Page 57 Control Systems Lecture-24, 25
Systems with transportation lag, Phase‐Lead Compensation, phase‐Lag Compensation 8.Compensation Technique:
Series Compensation or Cascade Compensation
• This is the most commonly used system where the controller is placed in series with the controlled
process.
• Figure shows the series compensation
Feedback Compensation or Parallel Compensation
Series-Feedback Compensation
Lead Compensator
It has a zero and a pole with zero closer to the origin. The general form of the transfer function of the load
compensator is
BPUT Page 58 Control Systems Here, Subsisting
;
Transfer function
Lag Compensator
It has a zero and a pole with the zero situated on the left of the pole on the negative real axis. The general
form of the transfer function of the lag compensator is
Therefore, the frequency response of the above transfer function will be
BPUT Page 59 Control Systems Now comparing with
Therefore
BPUT Page 60 Control Systems Lecture-26, 27
Phase‐Lag –Lead Compensation, Feedback Compensation Lag-Lead Compensator
The lag-lead compensator is the combination of a lag compensator and a lead compensator. The lag section is
provided with one real pole and one real zero, the pole being to the right of zero, where as the lead section
has one real pole and one real came with the zero being to the right of the pole.
The transfer function of the lag-lead compensator will be
The figure shows lag lead compensator
Where
BPUT Page 61 Control Systems The above transfer functions are comparing with
Then
Therefore
Where
BPUT Page 62 Control Systems Module ‐3 Lecture-28, 29
Frequency Response Analysis: Frequency domain specifications
What is Frequency Response? Consider a system with a sinusoidal input Under steady state, the system output as well as signals at all other points in the system are sinusoidal. The steady state output may be written as The magnitude and phase relationship between the sinusoidal input and the steady state output of a system is termed as frequency response. In linear time‐invariant systems, the frequency response is independent of the amplitude and phase of the input signal. Advantages of Frequency Response Analysis: The frequency response test on a system or a component is normally performed by keeping the amplitude A fixed and determining B and for a suitable range of frequencies. Signal generators and precise measuring instruments are readily available for various ranges of frequencies and amplitudes. BPUT Page 63 Control Systems •
•
•
•
Whenever it is not possible to obtain the form of the transfer function of a system through analytical techniques, the necessary information to compute the transfer function can be extracted by performing the frequency response test on the system. The design and parameter adjustment of the open loop transfer function of a system for specified closed loop performance is carried out somewhat more easily in frequency domain than in time domain. The effect of noise disturbance and parameter variations are relatively easy to visualize and assess through frequency response. The Nyquist Stability criterion is a powerful frequency domain method of extracting the information regarding stability as well as relative stability of a system without the need to find roots of the characteristic equation. How to obtain Steady‐State Outputs to Sinusoidal Inputs? The Laplace Transform of the output of a linear single‐input, single‐output system with transfer function G(s) can be expressed in terms of the input as We know, in general that
. However, it will be shown here that, for sinusoidal steady‐state analysis, we shall replace s by its imaginary component only, since in steady state, the contribution of the real part will disappear for a stable system. Consider the stable, linear system shown below. r(t) G(s) R(s
c C(s
Let us assume that the input signal
. Suppose that the transfer function G(s) of the system can be written as a ratio of two polynomials in s as The Laplace Transform of the output of the system is then
Transform of the input r(t). , where R(s) is the Laplace Where, BPUT is the conjugate of . The inverse Laplace of the above equation yields Page 64 Control Systems For a stable system, a, b, c have positive real parts. Hence, as t approaches at steady state, all the terms in the expression for c(t) will vanish except the last two terms. Thus at steady state, the response becomes Regardless of whether there are simple or multiple poles of G(s), the contribution due to them to the steady state response will zero. Where the constant K can be evaluated as follows: |s=‐jw |s=jw Since is a complex quantity, it can be written in the form
Where represents the magnitude and represents the angle of
∠ , . Similarly, . We can now write, Where =AM Hence, for a stable, LTI system, subjected to sinusoidal input, the amplitude of the output is given by the product of that of the input and
, while the phase angle differs from that of the input by an amount ∠ . A positive phase angle is called phase lead where as a negative phase angle is called phase lag. BPUT Page 65 Control Systems Input sinusoid Frequency Domain parameters of prototype 2nd order systems: The closed loop transfer function of a prototype 2nd order system is given by is the damping factor and Where is the undamped natural frequency. The sinusoidal transfer function of the system is obtained by substituting s=
. Hence, Where, is the normalized driving signal frequency ∠
It is seen that when BPUT Page 66 Control Systems The Magnitude and Phase angle characteristics for normalized frequency shown below. for certain values of are 1 The frequency where M has a peak value is known as Resonant Frequency. At this frequency, slope of the Magnitude curve is zero. Let frequency. Then be the resonant frequency and
be the normalized resonant BPUT Page 67 Control Systems (1)
or, The maximum value of the magnitude, known as the Resonant Peak is given by (2)
The phase angle of at the resonant frequency is given by From Eqn. (1) and Eqn. (2), it is seen that as ξ approaches zero, approaches infinity. For 0 < ξ , the resonant frequency always has a value less than has a value greater than 1. and approaches and the resonant peak For ξ >1/ , it is seen that , slope of the magnitude curve does not become zero for any real value of . For this range of ξ, the magnitude of M decreases monotonically from M=1 at u=0 with increasing u, as shown in the above figure. It therefore follows that for ξ >1/
the greatest value of M equals 1. , there is no resonant peak and as such As is evident from the above equations, for a second order system, the resonant peak of its frequency response is indicative of its damping factor ξ for 0 < ξ 1/ , and the resonant frequency of the frequency response is indicative of its natural frequency for a given ξ and hence indicative of its speed of response (as .
and of the frequency response could thus be used as performance indices for a second order system. For
, M decreases monotonically. The frequency at which M has a value 1/ is of special significance and is called the cut‐off frequency . The signal frequencies above the cut‐off frequency are greatly attenuated in passing through a system. For feedback control systems, the range of frequencies over which M is equal to or greater than 1/ is defined as the bandwidth . Control systems being low‐pass filters (At zero frequency, M=1), the bandwidth is equal to the cut‐off frequency . In general, the bandwidth of a control system indicates the noise‐filtering characteristic of the system. Also, the bandwidth gives a measure of the transient response properties as observed below. BPUT Page 68 Control Systems Mr
M(
1
Bandwidth
Magnitude M(
wr
wc
Frequency,
The normalized bandwidth as follows: of the second order system under consideration can be determined Solving for , we get, It can be approximated in linear form as We thus observe that the normalized bandwidth is a function of damping only. The de‐normalized bandwidth can be written as Correlation between Time Domain and Frequency Domain: Let us consider the step response of the second order system. The peak overshoot for 0 < ξ BPUT of the step response 1 is Page 69 Control Systems The comparison of and plots is shown below. It shows that for 0 < ξ 1/ , the two performance indices are correlated as both are functions of the system damping factor ξ only. It means that a system with a given value of a step input. For ξ of its frequency response, must exhibit a corresponding value of 1/
, the resonant peak if subjected to does not exist and the correlation breaks down. Similarly, the expression for damped natural frequency for a second order system is given as Thus, there exists definite correlation between oscillation of the step response. of the frequency response and damped frequency of It is further observed that the bandwidth, a frequency domain concept, is indicative of the un‐damped natural frequency of a system for a given , and therefore indicative of the speed of response
a time‐domain concept. Commonly used frequency response analysis Methods: Commonly used frequency response analysis Methods are: • Bode plot BPUT Page 70 , Control Systems BPUT •
•
Nyquist plot Nichols chart Page 71 Control Systems Lecture-30, 31
Procedure for drawing the bode plots. Determination of Gain Margin and Phase Margin from Bode plot
Bode plot consists of two simultaneous graphs: • Magnitude in dB [(20 log |G(jω)|)(Base 10)] vs. frequency (in log ω) • Phase (in degrees) vs. frequency (in log ω) In the logarithmic representation, the curves are drawn on semilog paper, using the log scale for frequency and the linear scale for either magnitude (in Decibels) or phase angle (in degrees). Advantages of Bode Plot: •
Multiplication of Magnitudes can be converted into addition •
A simple method of sketching Bode Plot is based on asymptotic approximations. Such information on straight line asymptotes is sufficient if only rough information on frequency‐ response characteristics is needed. • Should the exact curve be desired, corrections can be made easily to these basic asymptotic plots. • Low frequency response contains sufficient information about the physical characteristics of most of the practical systems. • Experimental determination of a transfer function is possible through Bode plot analysis. Bode Diagrams In Bode diagrams, frequency ratios are expressed in terms of: • Octave: it is a frequency band from ω1 to 2ω1. • Decade: it is a frequency band from ω1 to 10ω1, where ω1 is any frequency value. The basic factors which occur frequently in an arbitrary transfer function are: • Gain K • Integral and derivatives: ( jω)±1 • First order factors: • Quadratic Factors: Bode Diagrams ±
1
(1 + jωT ) ±1 , T = 1a • For Constant Gain K, log‐magnitude curve is a horizontal straight line at the magnitude of (20 log K) dB and phase angle is 0 deg. • Varying the gain K, raises or lowers the log‐magnitude curve of the transfer function by the BPUT Page 72 Control Systems corresponding constant amount, but has no effect on the phase curve • Logarithmic representation of the frequency‐response curve of factor ( j (ω / a) +1) can be approximated by two straight‐line asymptotes • Frequency at which the two asymptotes meet is called the corner frequency or break frequency. The Gain K: Magnitude Response: Log Magnitude = 20 log K As a number increases by a factor of 10, the corresponding value increases by a factor of 20. This may be seen from the following: Again, when expressed in decibels, the reciprocal of a number differs from its value only in sign, i.e., for the number K, Integral and Derivative Factors Log Magnitude Plot: Log Magnitude of is Phase Plot: The phase angle of is constant and equal to ‐90°. is plotted on a logarithmic, scale, it is a straight line. To draw this straight If the log magnitude line, we need to locate one point (0 dB, on it. Since The slope of the line is ‐20 dB/decade or ‐6 dB/octave. Similarly, Log Magnitude of is The phase angle of is constant and equal to 90°. It can be seen that the differences in the frequency responses of magnitude curves and in the signs of the phase angles. BPUT and lie in the slopes of the log‐
Page 73 Control Systems If the transfer function contains the factor or
, the log magnitude becomes respectively, 20 log 20 log or The slopes of the log‐magnitude curve for the factors dB /decade respectively. The phase angle of where as that of point (0 dB, is 90°
and are thus ‐20
is equal to ‐90°
dB/decade and 20
over the entire frequency range, over the entire frequency range. The magnitude curve will pass through the : First‐Order Factors
Log‐Magnitude Curve: The log magnitude of the first order factor For low frequencies, such that ‐20 log is 20 log = ‐20 log dB , the log magnitude may be approximated by = ‐20 log 1=0 dB. Thus, the log magnitude curve at low frequencies is the constant 0‐dB line. For high frequencies, such that
, ‐20 log ‐20 log = ‐20 log , the log magnitude equals 0 dB; at At
decreases by 20 dB for every decade of ‐20 log dB. , the log magnitude is ‐20 dB. Thus, the value of ‐20 log . For , the log‐magnitude curve is thus a straight line with a slope of ‐20 dB/ decade (or ‐6 dB/octave). Our analysis shows that the logarithmic representation of the frequency‐response curve for the factor 1/
can be approximated by two straight‐line asymptotes, one a straight‐line at 0 dB for the frequency range and the other a straight line with slope ‐20 dB/decade for the frequency range The frequencies at which the two asymptotes meet is called the Corner Frequency or the Break Frequency. For the factor
, is the corner frequency. The corner frequency thus divides the frequency‐
response curve into two regions: The low frequency region and the high frequency region. BPUT Page 74 Control Systems Phase Plot: The exact phase angle of the factor 1/
is At zero frequency, the phase angle is 0°. At the corner frequency, the phase angle is At infinite frequency, the phase angle becomes ‐90°. Since the phase angle is given by an inverse tangent function, it is skew‐symmetric about the inflection point at . Error in the Magnitude curve: The error in the Magnitude curve caused by the use of asymptotes can be calculated. Error at a particular frequency = Actual value – Approximate value of the log‐magnitude curve at that frequency The maximum error occurs at the corner frequency Actual value = ‐20 log Approximate value = ‐20 log 1=0 dB. Thus, error at corner frequency = ‐3 dB. The error at one octave below the corner frequency, i.e., at is The error at one octave above the corner frequency, i.e., at is ‐20 log Thus, the error at one octave avove or below the corner frequency is approximately ‐1 dB. The transfer function has the characteristics of a low‐pass filter. For frequencies above log‐magnitude falls of rapidly towards ‐
BPUT . Page 75 , the Control Systems : Quadratic Factors When there are complex conjugate zeroes, the prototype 2nd order systems will have the transfer function , When there are complex conjugate poles, the prototype 2nd order systems will have the transfer function , For the complex conjugate poles, Log Magnitude Curve: BPUT Page 76 Control Systems Log magnitude=
For low frequencies, i.e., , Log magnitude becomes ‐20 log 1= 0 dB The low frequencies asymptote is thus a horizontal line at 0 dB. For high frequencies i.e., , = ‐40 log Log magnitude becomes ‐20 log dB = ‐40 – 40 log dB. The high frequency asymptote is thus a straight line having the slope ‐40 dB/ decade. The high frequency asymptote intersects the low‐frequency one at , the corner frequency. The two asymptotes derived are independent of . The resonant peak occurs near the frequency The damping ration determines the magnitude of this resonant peak. The magnitude of errors caused by the straight line asymptotes depend on the value of It is large for small values of Phase Plot: The phase angle of the quadratic factor is The phase angle is a function of both and . , The phase angle curve is skew‐symmetric about the inflection point where . The frequency response for the factor Can be obtained by merely reversing the sign of the log magnitude and that of the phase angle for the factor BPUT Page 77 Control Systems Relationship between System Type and Log‐Magnitude Curve: For a unity feedback system the static position, velocity and acceleration error constants describe the low‐
frequency behavior of type 0, type 1, and type 2 systems respectively. For a given system, only one of the static error constants is finite and significant. (The larger the value of the finite static error constant, the higher the loop gain is as approaches zero.) The type of the system determines the slope of the log‐magnitude curve at low frequencies. Thus, information concerning the existence and magnitude of the steady‐state error of a control system to a given input can be determined from the observation of the low‐frequency region of the log‐magnitude curve. Determination of Static Error constants: Assume that the open loop transfer function of a unity feedback system is given by Or BPUT Page 78 Control Systems Static Position Error constant: The figure shown below shows an example of the log‐magnitude plot of a type 0 system. In such a system, equals the magnitude of at low frequencies, or dB
20 log Kp
-20 dB/decade
-40 dB/decade
0
In log scale
Static Velocity Error constant: The figure given below shows an example of the log‐magnitude of a type 1 unity feedback system. The intersection of the initial ‐20 dB/decade segment (or its extension) with the line 20 log . This may be seen as follows. has the magnitude In a type‐1 system, Thus, BPUT Page 79 Control Systems The intersection of the initial ‐20 dB/decade segment (or its extension) with the 0‐dB line has a frequency numerically equal to , i.e., if the frequency at this intersection is , then or, Static Acceleration Error constant: The figure given below shows an example of the log‐magnitude of a type 2 unity feedback system. The intersection of the initial ‐40 dB/decade segment (or its extension) with the line 20 log . This may be seen as follows. has the magnitude Since at low frequencies, It follows that The frequency at the intersection of the initial ‐40 dB/decade segment (or its extension) with the 0‐dB line gives the square root of numerically. This can be seen from the following. Which yields BPUT Page 80 Control Systems Phase Margin (PM): Phase margin is that amount of additional phase lag at the gain crossover frequency required to bring the system to the verge of instability. Gain Crossover Frequency: Gain crossover frequency is that frequency at which, function is unity. The Phase margin PM is 180° plus the phase angle crossover frequency. , the magnitude of the open loop transfer of the open loop transfer function at the gain Gain Margin (PM): Gain Margin is the reciprocal of the magnitude at the Phase crossover frequency. Phase Crossover Frequency: Phase crossover frequency is that frequency at which, function equals ‐180°. , the phase angle of the open loop transfer Thus, Gain Margin, In terms of decibels, A Few Comments on Phase and Gain Margins: •
•
•
•
BPUT For a stable non‐minimum phase system, the gain margin indicates how much the gain can be increased before the system becomes unstable. For an unstable system, the gain margin indicates how much the gain can be decreased before the system becomes stable. The Gain Margin of a first and Second order system is infinite since the polar plot of such systems does not cross the real axis. Thus, theoretically, the 1st and 2nd order systems cannot be unstable. It is important to point out that conditionally stable systems will have two or more phase crossover frequencies and some higher order systems with complicated numerator dynamics may also have two or more gain crossover frequencies. For stable systems having two or more gain crossover frequencies, the Phase Margin is measured at the highest Gain Cross‐over Frequency. Either the Gain Margin alone or the Phase Margin alone does not give a sufficient indication of the relative stability. Both should be given for determination of stability. Page 81 Control Systems •
•
For satisfactory performance, PM should be between 30° and 60° and the GM should be greater than 6 dB. The requirement that the PM be between 30° and 60° means that in Bode diagram, the slope of the log‐magnitude curve at the gain crossover frequency should be more gradual than ‐40 dB/ decade. In most practical cases, a slope of ‐20 dB/decade is desirable. If the slope at the gain crossover frequency is ‐60 dB/ decade or steeper, the system is most likely unstable. PHASE AND GAIN MARGIN THROUGH BODE PLOTS: BPUT Page 82 Control Systems Lecture-31
Polar plots. Polar plots of some standard type function
A sinusoidal transfer function is a complex function and is given by Or, It is seen that can be represented as a phasor of magnitude M and phase angle positively in counter‐clockwise direction). As the input frequency is varied from 0 to M and the phase angle change and hence the tip of the phasor plane. The locus thus obtained is known as ‘Polar Plot’ as shown below. (Measured , the magnitude traces a locus in the complex Procedure for Sketching of the Polar Plot: To sketch the Polar Plot of of a given Open Loop Transfer Function over the entire frequency range, •
Express the given expression for the OLTF in (1+sT) form. •
•
Substitute in the expression for Find out the expressions for and •
Tabulate various values of magnitude and phase angle for different values of . There are usually four key points to be known. •
(a) The starting of the plot where (b) The end of the plot where and get . (c) The point where the Polar plot crosses the real axis, i.e.,
(d) The point where the Polar plot crosses the imaginary axis, i.e.,
BPUT starting from 0 to Page 83 Control Systems •
Fix all points in a polar graph sheet and join the points. (Polar graph sheet has concentric circles and radial lines. The concentric circles represent the magnitude and the radial lines represent the phase angles. In polar sheet, + ve phase angle is measured in ACW from 00 and ‐ve phase angle is measured in CW from 00 Examples: Polar Plot of
: Consider a 1st order system with transfer function The sinusoidal transfer function is and
When real axis. As Therefore, the phasor at has unit length and lies along the positive increases, M decreases and phase angle increases negatively. When As , M becomes zero and , is ‐90 This is represented by a phasor of zero length directed along the ‐90 axis in the complex plane. In fact, the locus of semicircle. can be shown to be a Im
270º
1
-180º
45º
increasing
1/
-90º
Polar Plot of
Polar Plot of 1/ (1+j T)
: Consider now the transfer function BPUT and Page 84 Control Systems This transfer function may be rearranged as The general shape of this transfer function is shown below. The plot is asymptotic to the vertical line passing through the point (‐T, 0). Polar Plot of
: The low and high frequency regions of the polar plot of the following sinusoidal transfer function are given respectively by and The Polar plot of this sinusoidal transfer function starts at from zero to infinity. Thus, the high frequency portion of BPUT and ends at as increases is a tangent to the negative real axis. Page 85 Control Systems The exact shape of a polar plot depends on the value of the damping ratio same for both overdamped and underdamped case. For the under‐damped case, at , we have Therefore, it can be seen that the frequency at which the undamped natural frequency vector at the resonant frequency . The peak value of Thus the general shape is , and the phase angle at is ‐90°. locus intersects the imaginary axis is the is obtained as the ratio of magnitude of the to the magnitude of the vector at For the over‐damped case, as increases well beyond unity, the locus approaches a semi‐circle.. This may be seen from the fact that, for a heavily damped system, the characteristic roots are real, and one is much smaller than the other. Since, for sufficiently large , the effect of the larger root (larger in absolute value) on the response becomes very small, the system behaves like a 1st order one. BPUT Page 86 Control Systems Example: Obtain the Polar Plot of the following transfer function: Since can be written as The magnitude and phase angle are respectively And Im
1
Re
Since the magnitude decreases from unity monotonically, and the phase angle also decreases monotonically, and indefinitely, the polar plot of the given transfer function is a spiral, as shown in the above figure. General Nature of Nyquist Plots: The polar plots of a transfer function of the form Where, or the degree of the denominator polynomial is greater than that of the numerator will have the following shapes. BPUT Page 87 Control Systems General shapes of the polar plots of some important functions The general shapes of the polar plots of some important functions are shown below. From the figures, following observations are made. Addition of a non‐zero pole to a transfer function results in further rotation of the polar plot through an angle of •
•
as Addition of a pole at the origin to the transfer function rotates the polar plot at zero and infinite frequencies by a further angle of . The effect of addition of a zero to the transfer function is to rotate the high frequency portion of the polar plot by •
•
BPUT in the counter‐clockwise direction. If degree of the denominator polynomial is greater than that of the numerator, the loci will converge to the origin clockwise. Any complicated shape of the polar plot curves are caused by the numerator dynamics, which is by the time constants in the numerator of the transfer function. Page 88 Control Systems General shapes of the polar plots of some other important functions RELATIVE STABILITY ANALYSIS: In designing a control system, we require that the system be stable. We also require that the system has adequate relative stability. The closeness of approach of the locus to the ‐1+j0 point is an indication of the relative stability of a stable system. In general, we may expect that the closer the locus is to the 1+j0 point, the larger is the maximum overshoot in the transient response and the larger it takes to damp out. When the locus passes through the 1+j0 point, the system is on the verge of instability and exhibits sustained oscillations. The measures of relative stability in the frequency domain are the Gain Margin and the Phase Margin. BPUT Page 89 Control Systems Lecture - 33, 34
Stability in frequency domain : Principle of argument, Nyquist stability criterion
10.Stability in frequency domain: A stability test for time invariant linear systems can also be derived in the frequency domain. It is known as Nyquist stability criterion. It is based on the complex analysis result known as Cauchy’s principle of argument. Note that the system transfer function is a complex function. By applying Cauchy’s principle of argument to the open‐loop system transfer function, we will get information about stability of the closed‐loop system transfer function and arrive at the Nyquist stability criterion (Nyquist, 1932). The importance of Nyquist stability lies in the fact that it can also be used to determine the relative degree of system stability by producing the so‐called phase and gain stability margins. These stability margins are needed for frequency domain controller design techniques. We present Only the Essence of the Nyquist stability Criterion and Define the Phase and Gain stability margins. The Nyquist Method is used for studying the stability of linear Systems with Pure time delay. For a SISO feedback System the closed‐loop transfer function is given by: where
represents the system and is the feedback element. Since the system poles are determined as those values at which its transfer function becomes infinity, it follows that the closed‐loop system poles are obtained by solving the following equation which, in fact, represents the System characteristic equation. In the following we consider the complex function Whose zeros are the closed‐loop poles of the transfer function. In addition, it is easy to see that the poles of are the zeros of . At the same time the poles of are the open‐loop control system poles since they are contributed by the poles of , which can be considered as the open‐loop control system transfer function‐ obtained when the feedback loop is open at some point. The Nyquist stability test is obtained by applying the Cauchy principle of argument to the complex function
Cauchy’s principle of argument. . First, we state Cauchy’s principle of argument Let be an analytic function in a closed region of the complex plane finite number of points (namely, the poles of the contour. Then, as function Figure 4.6), with BPUT ). It is also assumed that travels around the contour in the encircles the origin in the given in Figure below except at a is analytic at every point on plane in the clockwise direction, the ‐plane in the same direction times (see given by Page 90 Control Systems Where and stand for the number of zeros and poles (including their multiplicities) of the function inside the contour. The above result can be also written as Which justifies the terminology used, “the principle of argument”. Figure 1. Cauchy's principle of argument
Nyquist Plot The Nyquist plot is a polar plot of the function When travels around the contour given in Figure below. Figure 2. Contour in S‐ plane
The contour in this figure covers the whole unstable half plane of the complex plane
function the poles of ,
. Since the , according to Cauchy’s principle of argument, must be analytic at every point on the contour, on the imaginary axis must be encircled by infinitesimally small semicircles. Nyquist Stability Criterion It states that the number of unstable closed‐loop poles is equal to the number of unstable open‐loop poles plus the number of encirclements of the origin of the Nyquist plot of the complex function. This can be easily justified by applying Cauchy’s principle of argument to the function with the ‐plane contour given in Figure 2. Note that and represent the numbers of zeros and poles, respectively, of in the unstable part of the complex plane. At the same time, the zeros of are the closed‐loop system poles, and the poles of are the open‐loop system poles (closed‐loop zeros). The above criterion can be slightly simplified if instead of plotting the function, we plot only the function and count encirclement of the Nyquist plot of around the point, so that the modified Nyquist criterion has the following form. BPUT Page 91 Control Systems Stability via the Nyquist Diagram We now use the Nyquist diagram to determine a system's stability, using the simple equation. The values of P, the number of open‐loop poles of G(s)H(s) enclosed by the contour, and N, the number of encirclements the Nyquist diagram makes about — 1, are used to determine Z, the number of right‐half‐plane poles of the closed‐loop system. If the closed‐loop system has a variable gain in the loop, one question we would like to ask is, "For what range of gain is the system stable?" The general approach is to set the loop gain equal to unity and draw the Nyquist diagram. Since gain is simply a multiplying factor, the effect of the gain is to multiply the resultant by a constant anywhere along the Nyquist diagram. Figure 3. Nyquist stability contour and diagram
As the gain is varied, we can visualize the Nyquist diagram is expanding (increased gain) or shrinking (decreased gain) like a balloon. This motion could move the Nyquist diagram past the —1 point, changing the stability picture. For this system, since P = 2, the critical point must be encircled by the Nyquist diagram to yield N = 2 and a stable system. A reduction in gain would place the critical point outside the Nyquist diagram where N = 0, yielding Z = 2, an unstable system. If the Nyquist diagram intersects the real axis at —1, then . From root locus concepts, when G(s)H(s) = —1, the variable s is a closed‐loop pole of the system. Thus, the frequency at which the Nyquist diagram intersects —1 is the same frequency at which the root locus crosses the /co‐axis. Hence, the system is marginally stable if the Nyquist diagram intersects the real axis at —1. In summary, then, if the open‐loop system contains a variable gain, K, set K = 1 and sketch the Nyquist diagram. Consider the critical point to be at ‐1/K rather than at ‐ 1 . Adjust the value of K to yield stability, based upon the Nyquist criterion. BPUT Page 92 Control Systems PROBLEM: For the unity feedback system, where G(s) = K/[s(s + 3)( s + 5)], find the range of gain, K, for stability, instability, and the value of gain for marginal stability. For marginal stability also find the frequency of oscillation. Use the Nyquist criterion.
SOLUTION: First set K = 1 and sketch the Nyquist diagram for the system –
Figure 4. Nyquist conture and stability diagram
For all points on the imaginary axis, ,
At
Next find the point where the Nyquist diagram intersects the negative real axis. Setting the imaginary part of Eq. (1) equal to zero, we find . back into Eq. (1) yields the real part of ‐0.0083. Finally, at , Substituting this value of From the contour of Figure, P = 0; for stability N must then be equal to zero. From Figure, the system is stable if the critical point lies outside the contour (N = 0), so that Z = P — N = 0. Thus, K can be increased by 1/0.0083 = 120.5 before the Nyquist diagram encircles — 1. Hence, for stability, K < 120.5. For marginal stability K = 120.5. At this gain the Nyquist diagram intersects — 1, and the frequency of oscillation is rad/s BPUT Page 93 Control Systems Axis Stability via Mapping Only the Positive Once the stability of a system is determined by the Nyquist criterion, continued evaluation of the system can be simplified by using just the mapping of the positive ‐axis. Figure 5. Contour and root locus of system that is stable for small gain and unstable for large gain Consider the system shown in above Figure, which is stable at low values of gain and unstable at high values of gain. Since the contour does not encircle open‐loop poles, the Nyquist criterion tells us that we must have no encirclements of —1 for the system to be stable. We can see from the Nyquist diagram that the encirclements of the critical point can be determined from the mapping of the positive
‐axis alone. If the gain is small, the mapping will pass to the right of —1, and the system will be stable. If the gain is high, the mapping will pass to the left of —1, and the system will be unstable. Thus, this system is stable for the range of loop gain, K, that ensures that the open‐loop magnitude is less than unity at that frequency where the phase angle is 180° (or, equivalently, —180°). This statement is thus an alternative to the Nyquist criterion for this system. Figure 6. Contour and root locus of system that is unstable for small gain and stable for large gain
Now consider the system shown in above Figure, which is unstable at low values of gain and stable at high values of gain. Since the contour encloses two open‐loop poles, two counter clockwise encirclements of the critical point are required for stability. Thus, for this case the system is stable if the open‐loop magnitude is greater than unity at that frequency where the phase angle is 180° (or, equivalently, —180°). In summary, first determine stability from the Nyquist criterion and the Nyquist diagram. Next interpret the Nyquist criterion and determine whether the mapping of just the positive imaginary axis should have a gain BPUT Page 94 Control Systems of less than or greater than unity at 180°. If the Nyquist diagram crosses ±180° at multiple frequencies, determine the interpretation from the Nyquist criterion. PROBLEM: Find the range of gain for stability and instability, and the gain for marginal stability, for the unity feedback system, where G(s) = K/[(s2 + 2s + 2)(s + 2)]. For marginal stability find the radian frequency of oscillation. Use the Nyquist criterion and the mapping of only the positive imaginary axis.
SOLUTION: Since the open‐loop poles are only in the left‐half‐plane, the Nyquist criterion tells us that we want no encirclements of ‐ 1 for stability. Hence, a gain less than unity at ±180° is required. Begin by letting K = 1 and draw the portion of the contour along the positive imaginary axis as shown in Figure.
Figure 7. Nyquist diagram of Mapping of positive imaginary axis
In Figure, the intersection with the negative real axis is found by letting 5 = jco in G(s)H(s), setting the imaginary part equal to zero to find the frequency, and then substituting the frequency into the real part of G(jco)H{jco). Thus, for any point on the positive imaginary axis, Setting the imaginary part equal to zero, we find . Substituting this value back into equation yields the real part, This closed‐loop system is stable if the magnitude of the frequency response is less than unity at 180°. Hence, the system is stable for K < 20, unstable for K > 20, and marginally stable for K = 20. When the system is marginally stable, the radian frequency of oscillation is . Example:1 Consider the following transfer function Putting the value of in above equation, we obtain The magnitude and phase angle equations: BPUT Page 95 Control Systems Evaluating magnitude and phase response at At At and PHASE AND GAIN MARGIN THROUGH NYQUIST PLOTS: BPUT Page 96 Control Systems BPUT Page 97 Control Systems Lecturer - 35, 36
Closed loop frequency response: Constant M circles. Constant N‐Circles, Nichol’s chart
The closed‐loop frequency response is the locus of the closed‐loop magnitude frequency response for unity feedback system. If the frequency response of an open loop system is plotted in polar coordinates, and superimposed on the top of M‐circles, then the closed‐loop magnitude frequency response is determined by each intersection of this polar plot with the constant M‐circles. M‐circles are contours of constant closed‐loop magnitude on Nyquist plane. Let . Then . Hence, Then two cases are possible: , so we get: Constant M‐circles are the circles in the complex plane with radius
centered at BPUT Page 98 Control Systems Figure 8. Constant M circles
Constant N‐circles Therefore For a constant value of is also constant. Rearranging the equation we get, centered at (−1/2, 1/2N) (see constant N‐circles are the circles in the complex plane with radius figure 2). Constant N‐circles are the locus of the closed‐loop phase frequency response. Similarly to M‐
circles, if the frequency response of an open loop system is plotted in polar coordinates, and superimposed on the top of N‐circles, then the closed‐loop phase frequency response is determined by each intersection of this polar plot with the constant N‐circles. All the constant N‐circles pass through the origin and (‐1+j0) point regardless of the value of N. BPUT Page 99 Control Systems Figure 9. Constant N circles
Example 1- Closed-loop frequency response from open-loop frequency response
Find the closed‐loop frequency response of the unity feedback system with open‐loop transfer function
using the open‐loop polar frequency response curve, constant M‐circles, and constant N‐circles. Solution
Open‐loop frequency response is Polar plot of BPUT is shown superimposed over the M‐ and N‐circles in figure 3. Page 100 Control Systems Figure 10. Constant N and M circles
The closed‐loop magnitude frequency response can be obtained by finding the intersection of each point of with the M‐circles, and the closed‐loop phase frequency response can be obtained by finding the the intersection of each point of the with the N‐circles. BPUT Page 101 Control Systems Figure 11. Closed loop frequency response
Nichols Charts Since it is easier to construct a bode plot than a polar plot, it is preferable to have constant‐M and constant‐
contours constructed on logarithmic gain and phase coordinates. N.B. Nichols transformed the constant‐
M and constant‐ contours constructed on logarithmic gain and phase coordinate and the resulting chart is known as the Nichols chart. It displays magnitude response in decibels, so that changes in gain are as simple to handle as in the Bode plot. Nichols chart is a plot of open‐loop magnitude in dB vs. open‐loop phase. Every point on the constant M‐ and N‐circles is transferred to the Nichols chart (see figure 4). The intersection of the
with the Nichols chart yields the frequency response of the closed‐loop system. BPUT Page 102 Control Systems Example 2‐ Closed‐loop frequency response from open‐loop frequency response using Nichols chart Consider a unity feedback system with the following open‐loop transfer function Find the closed‐loop frequency response using Nichols chart. Solution Superimposing the open‐loop frequency response for K = 1 on the Nichols chart, we obtain the plot shown in figure 5. Figure 5: Nichols chart for Example 2
The intersection of the plot of with the Nichols chart yields the frequency response of the closed‐loop system If the gain is increased by 10 dB, one should simply raise the curve for K = 1 by 10 dB to obtain the curve for K = 3.16 (10 dB) (see figure 5). BPUT Page 103 Control Systems Nichols Chart for elementary systems
Bode
Nyquist
Nichols
BPUT Page 104 Control Systems Lecture - 37, 38
Controllers : Concept of Proportional, Derivative, Integral Control actions, P, PD
11.Controllers: Concept of Proportional, Derivative and Integral Control actions: A variety of controls are used to manipulate processes, however the most simple and often most effective is the PID controller. Much more practical than the typical on/off controller, PID controllers allow for much better adjustments to be made in the system. While this is true, there are some advantages to using an on/off controller: • Relatively simple to design and execute • Binary sensors and actuators (such as an on/off controller) are generally more reliable and less expensive Although there are some advantages, there are large disadvantages to using an on/off controller scheme: • Inefficient (using this control is like driving with full gas and full breaks) • Can generate noise when seeking stability (can dramatically overshoot or undershoot a set‐point) • Physically wearing on valves and switches (continuously turning valves/switches fully on and fully off causes them to become worn out much quicker) To allow for much better control and fine‐tuning adjustments, most industrial processes use a PID controller scheme. The controller attempts to correct the error between a measured process variable and desired set‐point by calculating the difference and then performing a corrective action to adjust the process accordingly. A PID controller controls a process through three parameters: Proportional (P), Integral (I), and Derivative (D). These parameters can be weighted, or tuned, to adjust their effect on the process. The following section will provide a brief introduction on PID controllers. The Process Gain (K) is the ratio of change of the output variable (responding variable) to the change of the input variable (forcing function). It specifically defines the sensitivity of the output variable to a given change in the input variable. Gain can only be described as a steady state parameter and give no knowledge about the dynamics of the process and is independent of the design and operating variables. A gain has three components that include the sign, the value, and the units. The sign indicates how the output responds to the process input. A positive sign shows that the output variable increases with an increase in the input variable and a negative sign shows that the output variable decreases with an increase in the input variable. The units depend on the process considered that depend on the variables mentioned. As previously mentioned, controllers vary in the way they correlate the controller input (error) to the controller output (actuating signal). The most commonly used controllers are the proportional‐ integral‐
BPUT Page 105 Control Systems derivative (PID) controllers. PID controllers relate the error to the actuating signal either in a proportional (P), integral (I), or derivative (D) manner. PID controllers can also relate the error to the actuating signal using a combination of these controls. Proportional (P) Control Proportional control is the simplest form of continuous control that can be used in a closed‐looped system. P‐only control minimizes the fluctuation in the process variable, but it does not always bring the system to the desired set point. This deviation is known as the offset, and it is usually not desired in a process. The existence of an offset implies that the system could not be maintained at the desired set point at steady state. It is analogous to the systematic error in a calibration curve, where there is always a set, constant error that prevents the line from crossing the origin. The offset can be minimized by combining P‐only control with another form of control, such as I‐ or D‐ control. Mathematical Equations P‐control linearly correlates the controller output (actuating signal) to the error (difference between measured signal and set point). This P‐control behavior is mathematically illustrated in Equation 1. c(t) = Kce(t)+b
(1)
As can be seen from the above equation, P‐only control provides a linear relationship between the error of a system and the controller output of the system. . Combined with the bias, this algorithm determines the action that the controller should take. A graphical representation of the P‐controller output for a step increase in input at time t0 is shown below in Figure 2. This graph is exactly similar to the step input graph itself.
BPUT Page 106 Control Systems Figure 2. P-controller output for step input.
Integral (I) Control Integral control is a second form of feedback control. It is often used because it is able to remove any deviations that may exist. Thus, the system returns to both steady state and its original setting. A negative error will cause the signal to the system to decrease, while a positive error will cause the signal to increase. However, I‐only controllers are much slower in their response time than P‐only controllers because they are dependent on more parameters. If it is essential to have no offset in the system, then an I‐only controller should be used, but it will require a slower response time. This slower response time can be reduced by combining I‐only control with another form, such as P or PD control. The philosophy behind the integral control is that deviations will be affected in proportion to the cumulative sum of their magnitude. The key advantage of adding a I‐control to your controller is that it will eliminate the offset. The disadvantages are that it can destabilize the controller, and there is an integrator windup, which increases the time it takes for the controller to make changes. Mathematical Equations
I‐control correlates the controller output to the integral of the error. The integral of the error is taken with respect to time. It is the total error associated over a specified amount of time. This I‐control behavior is mathematically illustrated in Equation 2. (2)
BPUT Page 107 Control Systems Steady state error for a Step input -
In this equation, the integral time is the amount of time that it takes for the controller to change its output by a value equal to the error. The controller output before integration is equal to either the initial output at time t=0, or the controller output at the time one step before the measurement. As expected, this graph represents the area under the step input graph. Figure 3. I-controller output for step input.
Derivative (D) Control Unlike P‐only and I‐only controls, D‐control is a form of feed forward control. D‐control anticipates the process conditions by analyzing the change in error. It functions to minimize the change of error, thus keeping the system at a consistent setting. The primary benefit of D controllers is to resist change in the system, the most important of these being oscillations. The control output is calculated based on the rate of change of the error with time. The larger the rate of the change in error, the more pronounced the controller response will be. Unlike proportional and integral controllers, derivative controllers do not guide the system to a steady state. Because of this property, D controllers must be coupled with P, I or PI controllers to properly control the system. Mathematical Equations
BPUT Page 108 Control Systems D‐control correlates the controller output to the derivative of the error. The derivative of the error is taken with respect to time. It is the change in error associated with change in time. This D‐control behavior is mathematically illustrated in Equation 3. (3)
A graphical representation of the D‐controller output for a step increase in input at time t0 is shown below in Figure 4. As expected, this graph represents the derivative of the step input graph. Figure 4. D-controller output for step input.
BPUT Page 109 Control Systems Lecture - 39, 40
PI, PID controllers, Zeigler‐Nichols method of tuning PID controllers
Proportional-Integral (PI) Control
One combination is the PI‐control, which lacks the D‐control of the PID system. PI control is a form of feedback control. It provides a faster response time than I‐only control due to the addition of the proportional action. PI control stops the system from fluctuating, and it is also able to return the system to its set point. Although the response time for PI‐control is faster than I‐only control, it is still up to 50% slower than P‐only control. Therefore, in order to increase response time, PI control is often combined with D‐only control. Mathematical Equations
PI‐control correlates the controller output to the error and the integral of the error. This PI‐control behavior is mathematically illustrated in Equation 4. (4)
In this equation, the integral time is the time required for the I‐only portion of the controller to match the control provided by the P‐only part of the controller. BPUT Page 110 Control Systems The PI‐controller can also be seen as a combination of the P‐only and I‐only control equations. The bias term in the P‐only control is equal to the integral action of the I‐only control. The P‐only control is only in action when the system is not at the set point. When the system is at the set point, the error is equal to zero, and the first term drops out of the equation. The system is then being controlled only by the I‐only portion of the controller. Should the system deviate from the set point again, P‐only control will be enacted. A graphical representation of the PI‐controller output for a step increase in input at time is shown below in Figure 5. Figure 5. PI-controller output for step input.
Effects of Kc and Ti
With a PI control system, controller activity (aggressiveness) increases as Kc and Ti decreases, however they can act individually on the aggressiveness of a controller’s response. Consider Figure 6 below with the center graph being a linear second order system base case. BPUT Page 111 Control Systems Figure 6. Effects of Kc and Ti [2]
The plot depicts how Ti and Kc both affect the performance of a system, whether they are both affecting it or each one is independently doing so. Regardless of integral time, increasing controller gain (moving form bottom to top on the plot) will increase controller activity. Similarly, decreasing integral time (moving right to left on the plot) will increase controller activity independent of controller gain. As expected, increasing Kc and decreasing Ti would compound sensitivity and create the most aggressive controller scenario. Another noteworthy observation is the plot with a normal Kc and double Ti. The plot depicts how the proportional term is practical but the integral is not receiving enough weight initially, causing the slight oscillation before the integral term can finally catch up and help the system towards the set point. Proportional-Derivative (PD) Control
BPUT Page 112 Control Systems Another combination of controls is the PD‐control, which lacks the I‐control of the PID system. PD‐control is combination of feed‐forward and feedback control, because it operates on both the current process conditions and predicted process conditions. In PD‐control, the control output is a linear combination of the error signal and its derivative. PD‐control contains the proportional control’s damping of the fluctuation and the derivative control’s prediction of process error. Mathematical Equations
As mentioned, PD‐control correlates the controller output to the error and the derivative of the error. This PD‐control behavior is mathematically illustrated in Equation 5. (5)
The equation indicates that the PD‐controller operates like a simplified PID‐controller with a zero integral term. Alternatively, the PD‐controller can also be seen as a combination of the P‐only and D‐only control equations. In this control, the purpose of the D‐only control is to predict the error in order to increase stability of the closed loop system. P‐D control is not commonly used because of the lack of the integral term. Without the integral term, the error in steady state operation is not minimized. P‐D control is usually used in batch pH control loops, where error in steady state operation does not need to be minimized. In this application, the error is related to the actuating signal both through the proportional and derivative term. A graphical representation of the PD‐controller output for a step increase in input at time t0 is shown below in Figure 6. Again, this graph is a combination of the P‐only and D‐only graphs, as expected. BPUT Page 113 Control Systems Figure 12. PD-controller output for step input.
Proportional‐Integral‐Derivative (PID) Control Proportional‐integral‐derivative control is a combination of all three types of control methods. PID‐control is most commonly used because it combines the advantages of each type of control. This includes a quicker response time because of the P‐only control, along with the decreased/zero offset from the combined derivative and integral controllers. This offset was removed by additionally using the I‐control. The addition of D‐control greatly increases the controller's response when used in combination because it predicts disturbances to the system by measuring the change in error. On the contrary, as mentioned previously, when used individually, it has a slower response time compared to the quicker P‐only control. However, although the PID controller seems to be the most adequate controller, it is also the most expensive controller. Therefore, it is not used unless the process requires the accuracy and stability provided by the PID controller. Mathematical Equations
PID‐control correlates the controller output to the error, integral of the error, and derivative of the error. This PID‐control behavior is mathematically illustrated in Equation 6. (6)
BPUT Page 114 Control Systems As shown in the above equation, PID control is the combination of all three types of control. In this equation, the gain is multiplied with the integral and derivative terms, along with the proportional term, because in PID combination control, the gain affects the I and D actions as well. Because of the use of derivative control, PID control cannot be used in processes where there is a lot of noise, since the noise would interfere with the predictive, feed‐forward aspect. A graphical representation of the PID‐controller output for a step increase in input at time t0 is shown below in Figure 7. This graph resembles the qualitative combination of the P‐only, I‐only, and D‐only graphs. Figure 7. PID-controller output for step input.
In addition to PID‐control, the P‐, I‐, and D‐ controls can be combined in other ways. These alternative combinations are simplifications of the PID‐control. Summary Tables A summary of the advantages and disadvantages of the three controls is shown below is shown in Table 1.
Table 1. Advantages and disadvantages of controls
Proportional (P)
Integral (I)
BPUT Derivative (D)
Page 115 Control Systems Advantages
Fast response time
Reduces
error.
steady
state Improves stability
Minimizes fluctuation
Disadvantages Contains large offset
Slow response time
Does not bring system to Reduces stability margins
desired set point
Controls
process
with
rapidly changing outputs
Highly sensitive to noise
Requires combined use
with another controller
Effects of Coefficients: Parameter Speed of Response Stability Accuracy Increasing K Increases Deteriorate Improves Increasing Ki Decreases Deteriorate Improves Increasing Kd Increases Improves No impact What is tuning? Tuning is adjustment of control parameters to the optimum values for the desired control response. Stability is a basic requirement. However, different systems have different behavior, different applications have different requirements, and requirements may conflict with one another. Ziegler–Nichols tuning method:
This method was introduced by John G. Ziegler and Nathaniel B. Nichols in the 1940s. The Ziegler‐
Nichols’ closed loop method is based on experiments executed on an established control loop (a real system or a simulated system). Closed Loop (Feedback Loop) 1. Remove integral and derivative action. Set integral time (Ti) to 999 or its largest value and set the derivative controller (Td) to zero. 2. Create a small disturbance in the loop by changing the set point. Adjust the proportional, increasing and/or decreasing, the gain until the oscillations have constant amplitude. 3. Record the gain value (Ku) and period of oscillation (Pu). 4. Plug these values into the Ziegler‐Nichols closed loop equations and determine the necessary settings for the controller. BPUT Page 116 Control Systems Figure 1. System tuned using the Ziegler-Nichols closed-loop tuning method
P
PI
PID
Advantages 1. Easy experiment; only need to change the P controller 2. Includes dynamics of whole process, which gives a more accurate picture of how the system is behaving Disadvantages 1. Experiment can be time consuming 2. Can venture into unstable regions while testing the P controller, which could cause the system to become out of control BPUT Page 117 Control Systems Ziegler‐Nichols Open‐Loop Tuning Method or Process Reaction Method ‐ This method remains a popular technique for tuning controllers that use proportional, integral, and derivative actions. The Ziegler‐Nichols open‐loop method is also referred to as a process reaction method, because it tests the open‐loop reaction of the process to a change in the control variable output. This basic test requires that the response of the system be recorded, preferably by a plotter or computer. Once certain process response values are found, they can be plugged into the Ziegler‐Nichols equation with specific multiplier constants for the gains of a controller with either P, PI, or PID actions. In this method, the variables being measured are those of a system that is already in place. A disturbance is introduced into the system and data can then be obtained from this curve. First the system is allowed to reach steady state, and then a disturbance, Xo, is introduced to it. The percentage of disturbance to the system can be introduced by a change in either the set point or process variable. For example, if you have a thermometer in which you can only turn it up or down by 10 degrees, then raising the temperature by 1 degree would be a 10% disturbance to the system. These types of curves are obtained in open loop systems when there is no control of the system, allowing the disturbance to be recorded. The process reaction curve method usually produces a response to a step function change for which several parameters may be measured which include: transportation lag or dead time, τdead, the time for the response to change, τ, and the ultimate value that the response reaches at steady‐state, Mu. τdead = transportation lag or dead time: the time taken from the moment the disturbance was introduced to the first sign of change in the output signal τ = the time for the response to occur Xo = the size of the step change Mu = the value that the response goes to as the system returns to steady‐state An example for determining these parameters for a typical process response curve to a step change is shown below. In order to find the values for τdead and τ, a line is drawn at the point of inflection that is tangent to the response curve and then these values are found from the graph. BPUT Page 118 Control Systems To use the Ziegler‐Nichols open‐loop tuning method, you must perform the following steps: 1. Make an open loop step test 2. From the process reaction curve determine the transportation lag or dead time, τdead, the time constant or time for the response to change, τ, and the ultimate value that the response reaches at steady‐state, Mu, for a step change of Xo. 3. Determine the loop tuning constants. Plug in the reaction rate and lag time values to the Ziegler‐
Nichols open‐loop tuning equations for the appropriate controller—P, PI, or PID—to calculate the controller constants. Use the table below. Table 2. Open-Loop Calculations of Kc, Ti, Td
P
PI
PID
BPUT Page 119 Control Systems Advantages
1. Quick and easier to use than other methods 2. It is a robust and popular method 3. Of these two techniques, the Process Reaction Method is the easiest and least disruptive to implement Disadvantages
1. It depends upon purely proportional measurement to estimate I and D controllers. 2. Approximations for the Kc, Ti, and Td values might not be entirely accurate for different systems. 3. It does not hold for I, D and PD controllers Example 1 Problem You're a controls engineer working for Flawless Design company when your optimal controller breaks down. As a backup, you figure that by using coarse knowledge of a classical method, you may be able to sustain development of the product. After adjusting the gain to one set of data taken from a controller, you find that your ultimate gain is 4.3289. From the adjusted plot below, determine the type of loop this graph represents; then, please calculate Kc, Ti, and Td for all three types of controllers. Solution From the fact that this graph oscillates and is not a step function, we see that this is a closed loop. Thus, the values will be calculated accordingly. BPUT Page 120 Control Systems We're given the Ultimate gain, Ku = 4.3289. From the graph below, we see that the ultimate period at this gain is Pu = 6.28 From this, we can calculate the Kc, Ti, and Td for all three types of controllers. The results are tabulated below. (Results were calculated from the Ziegler‐Nichols closed‐loop equations.) 4.3289
6.28
P 2.1645
PI 1.9677 5.2333
PID 2.5464 3.14 0.785
Example 2 Problem Your partner finds another set of data after the controller breaks down and decides to use the Cohen‐Coon method because of the slow response time for the system. They also noticed that the control dial, which goes from 0‐8, was set at 3 instead of 1. Luckily the response curve was obtained earlier and is illustrated below. From this data he wanted to calculate Kc, Ti and Td. Help him to determine these values. Note that the y‐axis is percent change in the process variable. BPUT Page 121 Control Systems Solution In order to solve for Kc, Ti and Td, you must first determine L, ΔCp, and T. All of these values may be calculated by the reaction curve given. From the process reaction curve we can find that: L = 3 T = 11 ΔCp = 0.55 (55%) Now that these three values have been found N and R may be calculated using the equations below.
BPUT Page 122 Control Systems Using these equations you find that N = .05 R = 0.27 We also know that since the controller was moved from 1 to 3, so a 200% change. P = 2.00 We use these values to calculate Kc, Ti, and Td, for the three types of controllers P 14.53
PI 12.3 6.42
PID 18.68 6.65 1.04
BPUT Page 123 