ADAPTCc

ADAPTCc
ADAPT Colibri c
TM
Installation – Commissioning – Maintenance, ADAPT Cc
20120717 / Art. No. 1545215
Installation
All connections to the duct system should be done with a
straight duct of the same dimension as the box inlet and
with a length > 2 * ØD. If a flexible duct is used, it should be
stretched so it remains as straight as possible, see figure 1.
1.The commissioning box can be suspended from a
ceiling and connected to a duct system. Use hanger
system (A) or (B), see figure 2.
2.Press the ADAPT Colibri air diffuser into the outlet of
the commissioning box and secure it with screws or
pop rivets. The diffuser should be turned so it’s hinges
(C, figure 2) face the same direction as the inlet of the
commissioning box. Readjust the hanger rods of the
commissioning box if needed, so that the air diffuser is
firmly positioned against the false ceiling, or the framework of the modular suspended ceiling.
3.Remove the frontplate section of the air diffuser by
applying the Quick Access principle, see figure 3.
4.Connect the air diffuser connector to the appropriate
contact in the upper surface of the diffuser face plate.
5.Flip the diffuser face plate up to close it.
Figure 1. Using a flexible duct.
A
B
C
Figure 3. Quick Access.
Figure 2. ADAPT Colibri, installation, make sure the diffuser is
turned with it’s hinges (C) facing the same direction as the inlet
of the commissioning box.
1
WISE
Figure 4. Lighting fixtures or similar objects must not be installed
beneaht the diffuser as this disrupts the presence detection and
room temperature measurement.
Commissioning
Maintenance
All the ADAPT Air terminals are delivered preset into commissioning mode, which means that the air diffuser is set to
max. airflow by force control.
The exterior surface of the ADAPT air diffusers can be
cleaned whenever necessary using lukewarm water with
dishwashing detergent added. Normally the best method
of cleaning is vacuuming with a brush nozzle.
When the ADAPT air diffuser is in commissioning mode,
the light-emitting diode shines orange. The different LED
indications:
The duct system is accessible through the air diffuser and
the commissioning box.
• Steady green LED: Normal operation, the air diffuser is
operating normally.
• Flashing green LED: The air diffuser has just been energised and calibration is in progress.
• Steady red LED: Function failure, see separate documentation for TUNE Adapt.
• Steady orange LED: The commissioning mode, max.
airflow
• Flashing orange LED: Other commissioning modes
and all the forced control situations of the feed-back
control system.
More information about the commissioning process itself
can be read in the Project Manual for the Wise system and
in the documentation for TUNE Adapt.
2
Swegon reserves the right to alter specifications.
20120717
www.swegon.com
WISE
24 V
Modbus
Figure 5. Commissioning with TUNE Adapt.
Electrical connections.
All the connections are wired to the CONNECT Adapt junction box. From there, the Master air diffuser is connected
by means of the LINK Adapt (RJ45) cable included in the
delivery. The slave air diffusers, if required, are connected
by means of the same type of cable to their respective slave
contacts. If there are more than 2 slave air diffusers, a SPLIT
Link Adapt should be used for further connection to the last
slave air diffuser. See Figure 7. If SPLIT Link Adapt is used, the
maximum length of LINK Adapt from the junction box to
the last air diffuser is 15 meters. If ADAPT is to be connected
through Modbus communication, this should be done with
the LINK Modbus (RJ12) cable. The maximum length of
SPLIT Link Modbus is 10 meters from the junction box to
the last air diffuser. Use double CONNECT Adapts if longer
distances are required. All cables and contacts are different
so that they will not be confused or incorrectly connected.
3
2
1
Electrical data
ADAPT is supplied with power via the junction box. See
the wiring diagram in figure 7 or relevant diagram from the
Swegon Templates application, containing details for the
specific installation. It is important that cables with appropriate cross-sectional area, transformers of correct size and
power supply cables of correct length are selected. This
can for example be carried out with the dimensioning tool
“Cable and Transformer Design”, available for download
from www.swegon.com (the application is available in
english and swedish language versions).
Supply voltage
24 V AC ±10 %
Max. power consumption (controller only)
3 VA
Cable rating (controller only)
0,6 A
Ambient temperature
Swegon reserves the right to alter specifications.
Figure 6. Air diffuser connections.
1. Connection for LINK Adapt cable (RJ45)
2. Connection for the LINK Modbus cable (RJ12).
3. Direct 24 V connection if a junction box is not used and the air
diffuser will be completely “stand alone”.
0 °C - +50 °C
20120717
www.swegon.com
3
WISE
6
12
11
1
5
2
5
2
5
5
2
6
3
10
20
Master
4
1
3 4
5
6
7
22
Slave
8
23
Modbus
9 10 11 12 13 14 15 16
5
1
6
7
7
2
21
Slave
- +C
9
A1 A2 1 3
G
OUT1
G0
8
Figure 7. Wiring of Master/Slave air diffusers and accessories.
1. ADAPT Master air diffuser
2. ADAPT Slave air diffusers
3. CONNECT Adapt, wiring terminals
4. 230-24 V AC Transformer
5. LINK Adapt (5 m long RJ45 cable)
6. LINK Modbus (5 m long RJ12 cable)
7. DETECT Quality (3 VA) or TUNE Temp (1 VA)
8. ACTUATOR, Radiator control (max 3 valves at 6 VA)
9. ADAPT Relay, relay for lighting
10.Connection to main control system (Modbus RTU)
11. SPLIT Link RJ45
12. SPLIT Modbus RJ12, max. stab length, 10 m.
4
Swegon reserves the right to alter specifications.
20120717
www.swegon.com
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertisement