ADAPT
TM
Colibri c
Installation – Commissioning – Maintenance, ADAPT Cc
Figure 1. Using a flexible duct.
20120717 / Art. No. 1545215
Installation
All connections to the duct system should be done with a straight duct of the same dimension as the box inlet and with a length > 2 * ØD. If a flexible duct is used, it should be stretched so it remains as straight as possible, see figure 1.
1. The commissioning box can be suspended from a ceiling and connected to a duct system. Use hanger system (A) or (B), see figure 2.
2. Press the ADAPT Colibri air diffuser into the outlet of the commissioning box and secure it with screws or pop rivets. The diffuser should be turned so it’s hinges
(C, figure 2) face the same direction as the inlet of the commissioning box. Readjust the hanger rods of the commissioning box if needed, so that the air diffuser is firmly positioned against the false ceiling, or the framework of the modular suspended ceiling.
3. Remove the frontplate section of the air diffuser by applying the Quick Access principle, see figure 3.
4. Connect the air diffuser connector to the appropriate contact in the upper surface of the diffuser face plate.
5. Flip the diffuser face plate up to close it.
A B
C
Figure 2. ADAPT Colibri, installation, make sure the diffuser is turned with it’s hinges (C) facing the same direction as the inlet of the commissioning box.
Figure 3. Quick Access.
1
WISE
Figure 4. Lighting fixtures or similar objects must not be installed beneaht the diffuser as this disrupts the presence detection and room temperature measurement.
Commissioning
All the ADAPT Air terminals are delivered preset into commissioning mode, which means that the air diffuser is set to max. airflow by force control.
When the ADAPT air diffuser is in commissioning mode, the light-emitting diode shines orange. The different LED indications:
• Steady green LED: Normal operation, the air diffuser is operating normally.
• Flashing green LED: The air diffuser has just been energised and calibration is in progress.
• Steady red LED: Function failure, see separate documentation for TUNE Adapt.
• Steady orange LED: The commissioning mode, max. airflow
• Flashing orange LED: Other commissioning modes and all the forced control situations of the feed-back control system.
More information about the commissioning process itself can be read in the Project Manual for the Wise system and in the documentation for TUNE Adapt.
2
Swegon reserves the right to alter specifications.
Maintenance
The exterior surface of the ADAPT air diffusers can be cleaned whenever necessary using lukewarm water with dishwashing detergent added. Normally the best method of cleaning is vacuuming with a brush nozzle.
The duct system is accessible through the air diffuser and the commissioning box.
20120717 www.swegon.com
WISE
24 V
Modbus
Figure 5. Commissioning with TUNE Adapt.
Electrical connections.
All the connections are wired to the CONNECT Adapt junction box. From there, the Master air diffuser is connected by means of the LINK Adapt (RJ45) cable included in the delivery. The slave air diffusers, if required, are connected by means of the same type of cable to their respective slave contacts. If there are more than 2 slave air diffusers, a SPLIT
Link Adapt should be used for further connection to the last slave air diffuser. See Figure 7. If SPLIT Link Adapt is used, the maximum length of LINK Adapt from the junction box to the last air diffuser is 15 meters. If ADAPT is to be connected through Modbus communication, this should be done with the LINK Modbus (RJ12) cable. The maximum length of
SPLIT Link Modbus is 10 meters from the junction box to the last air diffuser. Use double CONNECT Adapts if longer distances are required. All cables and contacts are different so that they will not be confused or incorrectly connected.
Electrical data
ADAPT is supplied with power via the junction box. See the wiring diagram in figure 7 or relevant diagram from the
Swegon Templates application, containing details for the specific installation. It is important that cables with appropriate cross-sectional area, transformers of correct size and power supply cables of correct length are selected. This can for example be carried out with the dimensioning tool
“Cable and Transformer Design”, available for download from www.swegon.com (the application is available in english and swedish language versions).
Supply voltage
Max. power consumption (controller only)
24 V AC ±10 %
3 VA
Cable rating (controller only)
Ambient temperature
0,6 A
0 °C - +50 °C
1
3
2
Figure 6. Air diffuser connections.
1. Connection for LINK Adapt cable (RJ45)
2. Connection for the LINK Modbus cable (RJ12).
3. Direct 24 V connection if a junction box is not used and the air diffuser will be completely “stand alone”.
3
Swegon reserves the right to alter specifications. 20120717 www.swegon.com
7
4
12
6
11
3
1
5
2
5 5
2
6
20
Master
21
Slave
22
Slave
23
Modbus
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
5
2
- + C
10
7
G
OUT1
G0
5
1
6
A1 A2 1 3
9
8
Figure 7. Wiring of Master/Slave air diffusers and accessories.
1. ADAPT Master air diffuser
2. ADAPT Slave air diffusers
3. CONNECT Adapt, wiring terminals
4. 230-24 V AC Transformer
5. LINK Adapt (5 m long RJ45 cable)
6. LINK Modbus (5 m long RJ12 cable)
7. DETECT Quality (3 VA) or TUNE Temp (1 VA)
8. ACTUATOR, Radiator control (max 3 valves at 6 VA)
9. ADAPT Relay, relay for lighting
10.Connection to main control system (Modbus RTU)
11. SPLIT Link RJ45
12. SPLIT Modbus RJ12, max. stab length, 10 m.
4