Original instructions
SIRe Advanced Air Curtains
Water
Ambient, no heat
With quick guide
SIReAA
SE .... 2
GB .... 23
ES .... 86
IT
PL .... 170
RU .... 191
.... 107
DE .... 44
FR .... 65
NL .... 128
NO .... 149
For wiring diagram, please see last pages
GB
SIRe Advanced Air Curtains Water
Quick guide/start up
Wiring diagrams
Check that all constituent parts are present
(see section Constituent parts).
The wiring diagrams are in a separate section
at the end of this manual.
When external PC board Base SIReB1X is
used, wiring between the PC board base and
the unit must be done. Please see separate
manual for SIReB1X.
Advice about location
PC board HUB SIReA1X is installed close to
the unit.
Control unit SIReUA1 has an integrated
room temperature sensor and is installed so
that it is easily accessible to the user. RJ12
(6p/6c) modular cables, which are available in
different lengths, are used to connect the PC
board and the control unit. Longer cables are
available as options. Maximum cable lengths
see section Options.
To prevent unauthorised people from accessing the Control unit it can instead be placed
in another area and an external room sensor,
SIReRTX (option), can be installed in the
premises to sense the correct temperature.
Enter ID/ Operation without control unit
The control system can control one or more
units in parallel (max 9). Each unit must get a
unique ID number (1-9) which is set in the ID
selector of the SIReB1/B2/B1EC. E.g. Unit 1:
ID=1, unit 2: ID:2
If the external control for some reason has
not been installed the unit can still be run
temporarily. The ID selector is then set to
mode 0 see the image below.
The function is half speed and heating is on.
When the ID number must be changed the
unit must be disconnected from power.
Connect the system
In control board base SIReB1(X) the unit is
connected further with RJ12 (6p/6c) modular
cable if several units are to be connected in
parallell.
If an external room temperature sensor SIReRTX (option) is used it is connected using
modular cable RJ11 (4p/4c) on HUB SIReA1X.
The actuator for water control, door switch
SIReDC and outdoor sensor SIReOTX is connected on PC Board HUB SIReA1X.
Transformer for voltage supply of the valve
actuator is connected with quick terminal
block on PC Board Base SIReB1(X) (230V)
and 24V and onward to the actuator.
If return water temp. sensor SIReWTA is
used, it is connected with modular cable RJ11
(4p/4c) on PC Board Base SIReB1(X).
Control board Base SIReB1(X) in/at the
unit and control unit SIReUA1 are connected
by PC board HUB SIReA1X with RJ12 (6p/6c)
modular cables, after the other units are powered up.
For fixed installation requirements, remove the supplied cable and plug. Perform
the installation in accordance with applicable
regulations.
3
4
5
3
6
4
5
6
7
2
7
1
8
1
8
0
9
0
9
2
Each unit should have
a unique ID on its
SIReB1X card.
To run the unit
temporarily without
external control
select mode 0.
23
GB
SIRe Advanced Air Curtains Water
Start up
SDM24
System supplied with power. At the first start
up, the start-up wizard is run and the basic
settings are made. Fan and heating steps
are tested through the test program. Then a
status window is displayed.
At the first start up alarm and error codes
can occur, these will usually be reset without
actions.
For actuator SDM24 (included in the valve
kit) to work with SIRe the setting should be as
follows:
Start-up wizard
1
Start-up wizard
5
Set language
English
2
Function test
Start test
Skip test
Screen function test
Start-up wizard
Start-up wizard
Set temp. unit
Fan step 1-5
Heating step off-1
°C
°F
3
Start-up wizard
6
Set date
2011-05-28
Start-up wizard
7
Set time
24h format
10
24
Start-up wizard
Eco / Comfort
Comfort mode
Eco mode
14:07
Checking system...
Start-up wizard
Function test
Test completed
Restart test
YYYY-MM-DD
4
Start-up wizard
Start-up wizard
Start-up finished
Proceed
Restart wizard
SIRe Advanced Air Curtains Water
GB
Contents
Quick guide/start up
Advice about location 23
Connect the system 23
Wiring diagrams
23
Enter ID/Operation without control unit
23
Start up
24
SDM2424
Constituent parts
SIReAA26
Operating modes
Door that is opened and closed
Doors that are always or often left open for longer periods
Function description of current stage
29
29
30
Control unit SIReUA1
Overview32
Statuswindow32
Main menu
Current settings
Temperature settings
Fan control
System on/off
Installer menu
33
33
33
33
33
Installer menu
Installer status screen
Week program
Fan settings
Heating settings
External filter guard (not for electric)
External control (BMS)
Filter guard settings General settings
Service menu
34
34
35
36
38
38
38
39
39
Alarm and error codes
Displaying alarm and error codes
Reset alarm
Overheat protection
Power failure
Frost protection function
40
40
40
40
40
Wiring diagrams, see last pages
25
GB
SIRe Advanced Air Curtains Water
Constituent parts
SIReAA
Integrated in the air curtain
X5
C2
SIReUA1,
control unit Competent
and Advanced
SIReA1X,
PC board HUB
Advanced
Wall unit cover
SIReOTX,
outdoor temperature
sensor
X4
C1
X3
ROOM
ACTUATOR
230V
SIReB1/B2,
integrated PC
Board Base
PE N L
SUPPLY 230V
SIReIT, internal
temperature
sensor
SIReDC,
door contact
SIReCC,
modular cable
Dimensions constituent parts
Type
Description
SIReUA1
SIReB1
SIReIT
SIReA1X
SIReOTX
SIReDC
SIReCC603
SIReCC605
Control unit Competent and Advanced
Integrated PC board Base
Internal temperature sensor
PC Board HUB Advanced
Outdoor temperature sensor
Magnetic door contact
Modular cable RJ12 (6/6)
Modular cable RJ12 (6/6)
26
HxWxD
[mm]
120x70x35
L
[m]
1
202x139x50
70x33x23
3
5
GB
SIRe Advanced Air Curtains Water
Option
SIReRTX,
external room
temperature
sensor
SIReUR, kit
for recessed
installation
SIReCJ4,
joint piece
SIReCJ6,
joint piece
SIReWTA,
SIReCC,
clamp-on sensor modular cable
Type
RSK-no.
E-no.
Description
SIReRTX
SIReUR*
SIReCJ4
SIReCJ6
SIReWTA
SIReCC603
SIReCC605
SIReCC610
SIReCC615
SIReCC403
SIReCC405
SIReCC410
SIReCC415
673 09 22
673 09 21
87 510 12
87 510 11
673 09 23
673 09 24
673 09 25
673 09 26
673 09 27
673 09 28
673 09 29
673 09 30
87 510 13
87 510 14
87 510 15
87 510 16
87 510 17
87 510 18
87 510 19
87 510 20
External room temperature sensor
Kit for recessed installation
Joint piece for two pcs. RJ11 (4/4)
Joint piece for two pcs. RJ12 (6/6)
Clamp-on sensor RJ11(4/4)
Modular cable RJ12 (6/6)
Modular cable RJ12(6/6)
Modular cable RJ12 (6/6)
Modular cable RJ12 (6/6)
Modular cable RJ11 (4/4)
Modular cable RJ11 (4/4)
Modular cable RJ11 (4/4)
Modular cable RJ11 (4/4)
HxWxD
[mm]
70x33x23
114x70x50
L
[m]
10
3
5
10
15
3
5
10
15
*) See separate manual.
Max. cable lengths
Modular cable RJ12 (6p/6c) between SIReUA1 and SIReA1X: max. 50 m.
Modular cable RJ12 (6p/6c) between SIReA1X and SIReB1(X): max. 10 m.
Modular cable RJ12 (6p/6c) between two SIReB1(X): max. 50 m.
Modular cable RJ11 (4p/4c) to room sensor SIReRTX: max. 20 m.
Cable for outdoor sensor SIReOTX (not modular): max. 50 m.
Total cable length permitted in the system is a maximum of 300 m.
27
GB
SIRe Advanced Air Curtains Water
Water control - valve kit
SDM24
VMO
TBVCM
AV
Water control - option
SDM24
VMOP
TBVCMP
AV
VAT, adjustment tool
for valve package
VMT
SDM24
TRVS
Type
RSK-no.
Description
Connection
VMO15LF
VMO15NF
VMO20
VMO25
VMOP15LF
VMOP15NF
VMOP20
VMOP25
VMT15
VMT20
VMT25
VAT
673 09 47
673 09 48
673 09 49
673 09 50
673 09 51
673 09 52
673 09 53
673 09 54
Modulating
Modulating
Modulating
Modulating
Pressure independent and modulating
Pressure independent and modulating
Pressure independent and modulating
Pressure independent and modulating
Three way valve and modulating actuator
Three way valve and modulating actuator
Three way valve and modulating actuator
Adjustment tool for valve package
DN15
DN15
DN20
DN25
DN15
DN15
DN20
DN25
DN15
DN20
DN25
28
SIRe Advanced Air Curtains Water
Operating modes
Door that is opened and closed
The control function notes whether the door
is open or closed as standard, this mode is
default set and is called Fixed flexible (the
setting is under Installer menu > Settings fan
> Door mode).
Open door
Indicates OP on the installer status screen.
Fan control runs at high speed mode and is
controlled to outdoor temperature. During
dropping outdoor temperatures during the
winter and increasing outdoor temperatures
during summer the fan speed increases. High
speed limit is set under Main Menu > Fan
control > High speed limit.
The control curves to the outdoor
temperature are set under Installer menu
> Settings fan > Fan speed increase where
temperatures for min- and max speed are set
for summer and winter modes.
Normally it is requested that heat is engaged
when the door is opened. The set point value
(Room temp. day) is then increased with
the fixed set point value difference that can
be changed under Installer menu> Settings
heating > Open door setp. diff., factory setting
3.0 K. The set point is set under Main Menu
> Temperature settings > Room temp. day.
If week program is used the night time set
point value is set under Main menu > Temp.
settings > Room temperature night. The room
temperature is regulated using the integrated
room temperature sensor or the external
room temperature sensor, SIReRTX (option).
Closed door
Indicated CL on the installer status screen.
When heating demand the fan speed runs
at low speed which is set under Main menu
> Fan speed > Speed closed door. Heating is
regulated to Room temp. Day which is set
under Main Menu > Temperature settings >
Room temp. day.
If week program is used the night time set
point value is regulated against the Room
temperature is set under Main menu > Temp.
GB
settings > Room temperature night. The room
temperature is regulated using the integrated
room temperature sensor or the external
room temperature sensor, SIReRTX (option).
When the door is closed - over run
When the door has been closed, high speed
mode remains during the fixed time that is
set under Installer menu > Settings fan >
Door over run > High speed over run and at
low speed during a fixed time under Installer
menu > Settings fan> Door over run > Low
speed over run, on the condition that it is
sufficiently warm in the premises, otherwise
the fans run until the desired temperature has
been reached.
When the door is closed, the set point value
shifts from room temperature + fixed set point
value difference for open door to Room temp.
day/night.
Over run is factory set so that the over run
times are controlled according to how often
the door is opened (Auto mode under Installer menu > Settings fan > Door over run >
Over run mode).
Doors that are always or often left open for
longer periods
If a door is always, or often, left open it is
possible to use a function called CURRENT
STAGE instead. The fan and heating steps
increase/decrease 6 or 9 steps (depending on
the type of unit) and are only controlled by
the room temperature. Actual Current stage
is shown in the status screen.
The function current stage is activated in
two ways:
Door that are always open
For a door that is always open, door mode
Fixed open > can be selected under >Settings
fan> Door mode.
Doors that are often open
For a door that is often open Auto can be
selected under Installer menu > Settings
fan > Door mode. In Auto mode, the control
29
GB
SIRe Advanced Air Curtains Water
automatically switches between Fixed flexible
and Fixed open modes depending on how
often the door has been open (when the door
has been open for longer than 300 seconds
the function changes from Fixed Flexible to
Fixed Open).
Function description of current stage
The task of the Current stage function is to
balance the room climate when a door is
always open by using the right combination of
fan and heating step.
In open mode, the room temperature is
read every 60 seconds (during the first 6
cycles, and then every 5 minutes and at each
reading any Current stage adjustments are
made, i.e. fan control and supplied output
adjusted.
Winter
When the outdoor temperature is less than
the current setting on Installer menu>
Settings fan > Outdoor temp. limit.
• If the room temperature is more than
3 degrees below the current settings, the
current stage increases by 2 steps.
•If the room temperature is between 1 and
3 degrees below the current settings, the
current stage increases by 1 step.
•If the room temperature is more than 2
degrees above the current setting, the
current stage decreases by 1 step.
Summer
When the outdoor temperature is greater
than the current setting on Installer menu>
Settings fan > Outdoor temperature limiting.
The heating is blocked.
• If the room temperature is more than
2 degrees below the current settings, the
current stage increases by 1 step.
•If the room temperature is between 1 and
2 degrees below the current settings, the
current stage decreases by 1 step.
•If the room temperature is more than 2
degrees greater than the Current settings,
current stage increases by 1 step.
•If the room temperature is between 1 and 2
30
degrees above current settings, the current
stage decreases by 1 step.
If fan control has been max. limited under
Main Menu > Fan control> High speed limit,
all current stages will be used but the fan will
be limited to the current setting.
See the table on the next page.
SIRe Advanced Air Curtains Water
GB
Table - Current stage for units with 5 fan controls Current
stage
0
1
2
3
4
5
6
7
8
Fan
0
1
2
2
3
3
4
5
5
Stepless fan 5
speeds (output)
0
30% (3V)
47% (4.7V)
47% (4.7V)
64% (6.4V)
64% (6.4V)
81% (8.1V)
100% (10V)
100% (10V)
Stepless heat (Outlet
temp.)
0
0
0
30 °C
30 °C
35 °C
35 °C
35 °C
40 °C
Table - Current stage for units with 3 fan controls
Current
stage
0
1
2
3
4
5
Fan
0
1
2
2
3
3
Stepless fan 3
speeds (output)
0
30% (3V)
60% (6V)
60% (6V)
100% (10V)
100% (10V)
Stepless heat (Outlet temp.)
0
0
0
30 °C
35 °C
40 °C
31
GB
SIRe Advanced Air Curtains Water
Control unit SIReUA1
Overview
IN
19.0
°C
Statuswindow
Out
-5 .0°C
DOOR
CL
Forward arrow
Back arrow
Rotary dial
Fan speed step
Heating step
Week program
Day
Week program
Night
Alarm Red led
Run signal Green led
OFF
Week program
Out of operation
Explanations
Statuswindow
The display shows prevailing room
temperature, outdoor temperature, fan and
heating step, door status and day or night
mode when week program is used.
Forward arrow
Confirm selection and proceed.
Rotary dial
Scroll between alternatives
Back arrow
Go back.
After three minutes the control unit goes back
to displaying the status window.
32
Statuswindow
Press forward arrow to enter the main menu.
GB
SIRe Advanced Air Curtains Water
Main menu
Fan control
Current settings
Possibility of setting high speed mode at an
open door and what speed should apply with
a closed door (3 or 5 steps depending on the
unit).
Shows the current room temperature, high
speed limit, speed closed door and week
program status.
Main menu
Main menu
Current settings
Current settings
Temperature settings
Fan control
Room temp. day
Room temp. night
High speed limit
Speed closed door
Week program
20°C
18°C
Step 5
Step 1
No program
Temperature settings
Fan control
System on/off
Main menu>Fan control
Main menu>Fan control
High speed limit
Speed closed door
High speed limit
•
Step 5
Temperature settings
Set the desired room temperatures to apply
for day respectively night mode, when the
door is closed (room temperature night is
used for week program/night reduction).
At open door these set point values automatically increase with a set point differential
that can be set under Installer menu > Heat
settings> Open door setp. diff. (Factory setting 3.0 K).
Main menu
Current settings
Temperature settings
Fan control
Main menu>Temperature
settings
Room temp. day
Room temp. night
Factory setting
Room temp. day: 20°C (5 – 35°C)
Room temp. night: 18°C (0 – 20°C)
Main menu>Fan control
Main menu>Fan control
High speed limit
Speed closed door
Speed closed door
•
Step 1
Factory setting
High speed limit: 3 resp. 5 (1-3, resp. 1-5)
Speed closed door: 1 (Off-3, resp. Off-4)
System on/off
Switch the whole unit off manually. In Off the
display goes out; as soon as a button is pushed
the display lights and shows System on/off. To
activate the unit again select On.
The unit’s safety functions are still active
when the system is switched off, which means
that the fan can continue to run for a moment
after mode Off has been selected.
Main menu
Main menu>System on/off
Fan control
System on/off
Installer menu
System on/off
ON
•
Installer menu
The installer menu is at the bottom of the
main menu, this is password protected. See
Installer menu in this manual.
Main menu
Main menu>Installer menu
Fan control
System on/off
Enter password
Installer menu
0 0 0 0
(See manual)
33
GB
SIRe Advanced Air Curtains Water
Installer menu
To enter the Installer menu, code 1932 is
entered. Select the digits using the rotary dial
and confirm using the forward arrow.
Main menu
Main menu>Installer menu
Fan control
System on/off
Enter password
Installer menu
To check which days a certain program is
active, select a week day by pressing the
forward arrow, the program is marked and
those days that the program is used will be
underlined, switch between the programs for
a particular day using the rotary wheel.
Check program
0 0 0 0
(See manual)
Mon Tue Wed Thu Fri
Installer status screen
Check the settings. The installer status screen
consists of three pages with settings, scroll
using the rotary dial.
>Installer menu
Installer status screen
Installer status screen
Week program
Fan settings
Functionality mode
Eco / Comfort mode
Door mode
Current stage
Over run mode
Program
Sat Sun
08:00 Day (1)
18:00 Night (2)
To add program step, select New program
step. Confirm your selection with the forward
arrow. Select Day, Night or Off (if the unit
should not be in operation), set the time
for switch on and then for which days the
program applies, then go to End to finish.
>Installer menu>Week
program
Adv.
Comfort
2°C
Flexible
FF
002 FF
Auto
FF
AC10
Week program on/off
New program step
Check program
New program step 7/16
Mode
Day
00:00
Tue 10:45
Mon Tue Wed Thu Fri
Tue 10:45
Sat Sun
Tue 10:45
Mon Tue Wed Thu Fri
Week program
End
Sat Sun
Tue 10:45
A new program step does not replace a set
time for Day for example, but you can instead
select to change a program step.
To change a program step, select Change
program.
Make settings for week program.
>Installer menu
Installer status screen
Week program
Fan settings
>Installer menu>Week
program
A basic program is pre-entered in SIRe.
Mon-Fri Day from 08:00, Night from 18:00
Sat Day from 10:00, Night from 16:00
Sun Day from 11:00:00, Night from 14:00
Check program
Change program
Remove program
Change program
Mon Tue Wed Thu Fri
1. 08:00
2. 18:00
3. 10:00
4. 16:00
Day
Night
Day
Night
00:00
Sat Sun
Tue 10:45
Mon Tue Wed Thu Fri
Tue 10:45
Sat Sun
Tue 10:45
Mon Tue Wed Thu Fri
To check which program is set for a particular
day, select Check program and then switch
between the days using the rotary dial.
>Installer menu>Week
program
New program step
Check program
Change program
Check program
Mon Tue Wed Thu Fri
08:00 Day (1)
18:00 Night (2)
Sat Sun
End
The program steps that should not apply
are removed in Remove program. One or all
program steps can be removed in the menu.
To return to the factory set basic program,
select Reset all.
>Installer menu>Week
program
Check program
Change program
Remove program
34
Sat Sun
Tue 10:45
Remove program
Remove single
Remove all
Reset all
GB
SIRe Advanced Air Curtains Water
Fan speed increase
Settings for outdoor temperatures for max
respectively min speed during summer
respectively winter modes.
Week program is activated by selecting On,
under Week program on/off. In On-mode,
a sun, moon or Off in the Status window
appears to indicate day, night respectively
Off-function.
>Installer menu>Week
program
>Installer menu>Week
program
Week program on/off
ON
•
Week program on/off
New program step
Check program
Installer menu>Fan
settings>Fan speed increase
Fan speed increase
Door over run
Door mode
T max speed winter
T min speed winter
T min speed summer
Factory setting
T max speed winter: -10°C (-30 – 15°C)
T min speed winter: 15°C (-10 – 22°C)
T min speed summer: 22°C (15 – 37°C)
T max speed summer: 37°C (22 – 50°C)
Fan settings
Make settings for fan mode (see also
Operating modes section).
>Installer menu
Week program
Fan settings
Heating settings
T max speed
winter
Fan speed
step
>Installer menu>Fan settings
T min speed T min speed
winter
summer
T max speed
summer
5
4
3
2
1
-15
-10
-5
0
5
10
15
20
25
30
35
40
Outdoor
temperature
[°C]
Diagram: Fan speed increase 5 step
T max speed
winter
Fan speed
step
T min speed
winter
T min speed
summer
T max speed
summer
3
2
1
-15
-10
-5
0
5
10
Diagram: Fan speed increase 3 step
15
20
25
30
35
40
Outdoor
temperature
[°C]
35
GB
SIRe Advanced Air Curtains Water
Door over run
Settings for overrun.
and Fixed open modes depending on how
often the door has been open.
>Installer menu>Fan settings
Fan speed increase
Door over run
Door mode
>Installer menu>Fan
settings>Door over run
Factory setting
Door mode:
Auto)
>Installer menu>Fan
settings>Door over run
Over run mode
High speed over run
Low speed over run
Over run mode
Auto
•
In over run mode Auto, SIRe controls the over
run time depending on how frequently the
door is opened between openings, according
to fixed preset values, according to the table.
Time between
opening [s]
t < 60
60 < t < 300
t > 300
Fixed flexible (Fixed open/
High speed over
run [s]
30
10
0
Low speed over
run [s]
90
300
180
Over run mode Fixed time is selected is one
wants fixed over run times, the times can be
changed during High speed over run and Low
speed over run.
>Installer menu>Fan
settings>Door over run
Over run mode
High speed over run
Low speed over run
Factory setting
Over run mode:
High speed over run:
Low speed over run:
Stepless fan control
Settings for stepless fan control.
Fans are controlled in 3 or 5 steps as
standard. If stepless fan control is selected,
the fans can be controlled steplessly via an
external frequency converter for example.
>Installer menu>Fan settings
Door over run
Door mode
>Installer menu>Fan settings
Stepless fan
•
OFF
Stepless fan
Factory setting
Stepless fan control: Off (On)
Heating settings
Make settings for heating.
>Installer menu>Fan
settings>Door over run
Over run mode
Fixed time
•
Auto (Set time)
30 s (0 – 180 s)
120 s (0 – 300 s)
Door mode
There are three different door modes to
choose from; Auto, Fixed flexible and Fixed
open.
>Installer menu>Fan settings
>Installer menu>Fan settings
Door over run
Door mode
Stepless fan
Door mode
Fixed flexible
•
In Fixed flexible mode, the control function
notes whether the door is open or closed.
In Fixed open mode the door is considered
always open and is only controlled according
to Current stage. In Auto mode, the control
automatically switches between Fixed flexible
36
>Installer menu
Fan settings
Heating settings
Filter guard settings
Outdoor temp. limit
Blocking heating summer time.
>Installer menu>Heating
settings
Outdoor temp. limit
Eco / Comfort
Open door setp. diff.
>Installer menu>Heating
settings
Outdoor temp. limit
15°C
•
Factory setting
Outdoor temp. limit: 15°C (5 – 30°C)
Eco / Comfort
Select between Eco and Comfort mode
depending on whether energy savings or
optimal comfort is more important. Comfort
>Installer menu>Heating
settings
Outdoor temp. limit
Eco / Comfort
Open door setp. diff.
>Installer menu>Heating
settings
Eco / Comfort
•
Comfort mode
Eco mode
GB
SIRe Advanced Air Curtains Water
mode gives faster comfort and a slightly
greater output. Comfort mode prioritises the
temperature comfort, the control system only
accepts a smaller deviation from the set room
temperature.
In Eco mode the heating adapts to the desired
level a little more slowly, when a temperature
change occurs, which gives lower energy
consumption (only valid for units with
internal temperature sensor).
In units with an internal sensor the Eco
mode outlet temperature is restricted to 32 °C
(adjustable), which further reduces the energy consumption.
To use the Eco functions it is necessary for
the valve actuator to be controlled by 0-10V.
Open door setp. diff.
Set by how much the set point value (Room
temp. day/night) is to increase when the door
is open.
>Installer menu>Heating
settings
>Installer menu>Heating
settings
Eco / Comfort
Open door setp. diff.
Sensor calibration
Open door setp. diff.
•
3.0 K
Sensor calibration
If the sensor displays the wrong values these
can be calibrated. Some display errors may
occur, but this is primarily due to the location
(cold/hot surfaces etc). The value + or – adds
to or subtracts from the measured value
(for example +2K gives an increase of the
displayed value of 2 degrees).
>Installer menu>Heating
settings>Sensor calibration
>Installer menu>Heating
settings
Open door setp. diff.
Sensor calibration
Return water temp.
Room temp. sensor
Outdoor temp. sensor
>Installer menu>Heating
settings>Sensor calibration
Room temp. sensor
•
Return water temp.
If there is a demand for the temperature
of the return water not to exceed a certain
value, this function is activated under Return
water temp. A return water temperature
sensor (proximity sensor SIReWTA, option)
must then be installed on the return water
pipe.
Install Return temp. Sensor to Connected
and select max return temperature (15-90 °C)
using the turn wheel. During operation, this
function limits the valve’s degree of opening,
which reduces the flow and the return temperature.
>Installer menu>Heating
settings
Sensor calibration
Return water temp.
Stepless heat control
Installer menu>Heating
settings>Return water temp.
Installer menu>Heating
settings>Return water temp.
Return temp. sensor
Return temp. limit
Return temp. sensor
•
Not connected
Connected
Installer menu>Heating
settings>Return water temp.
Installer menu>Heating
settings>Return water temp.
Return temp. sensor
Return temp. limit
Return temp. limit
•
OFF
Factory setting
Return temp. sensor: Not connected
(Connected)
Return temp. limit: Off (15 – 90°C)
Stepless heat control
To use Advanced fully, stepless heat control
must be used.
>Installer menu>Heating
settings
Return water temp.
Stepless heat control
Control range limit
>Installer menu>Heating
settings
Stepless heat control
•
ON
0.0 K
Factory setting
Room temperature sensor: 0.0 K (-10 K – 10
K)
Outdoor temperature sensor: 0.0 K (-10 K –
10 K)
Factory setting
Stepless heat control: ON (Off - not
selectable)
37
GB
SIRe Advanced Air Curtains Water
Control range limit
The maximum room temperature that a user
can select is limited to between 5 – 35°C.
>Installer menu>Heating
settings
Sensor calibration
Stepless heat control
>Installer menu>Heating
settings
External filter guard (not for electric)
If an external filter guard, e.g. a pressure
switch, is used, it is activated under External
filter guard, select On.
Control range limit
•
35°C
>Installer menu
Control range limit
Factory setting
Control range limit temperature: 35°C (5 –
35°C)
Filter guard settings
Filter alarm alarms when the set fixed run
time has been exceeded.
>Installer menu
Heating settings
Filter guard settings
External control
Filter timer setting
Under Filter timer setting, set the desired run
time to between 50 and 9950 hours.
>Installer menu>Filter guard
settings
Filter timer on/off
Filter timer setting
External filter guard
>Installer menu>Filter guard
settings
Filter timer setting
•
1500 h
Factory setting
Filter timer setting: 1500 h (50 - 9950 h)
Filter timer on/off
Filter alarm is activated by selecting On,
under Filter timer on/off.
>Installer menu>Filter guard
settings
Filter timer on/off
Filter timer setting
External filter guard
Factory setting
Filter timer on/off: Off (On)
Filter timer setting
External filter guard
Last filter change
Factory setting
External filter guard: Off (On)
Last filter change
To check the number of run time hours since
the last filter replacement, select Last filter
change. The time is reset when the filter
alarm is reset. If the time is to be reset before
the alarm has gone, switch the filter timer on
and off.
>Installer menu>Filter guard
settings
Filter timer setting
External filter guard
>Installer menu>Filter guard
settings
Last filter change
0h
Last filter change
External control (BMS)
BMS functions can be activated under
External control.
Activate External on/off (5-30V AC/DC
from BMS), 0-10V fan control or 0-10V
Heating control by selecting On under the
relevant one. See diagram on next page and
Connecting external control.
>Installer menu
Filter guard settings
External control
General settings
>Installer menu>External
control
External on/off
0-10V fan control
0-10V heat control
>Installer menu>External
control
External on/off
0-10V fan control
0-10V heat control
>Installer menu>External
control
External on/off
0-10V fan control
0-10V heat control
38
SIRe Advanced Air Curtains Water
GB
8,4
5
7,0
4
5,6
3
4,2
2
2,8
1
1
7,4
6,0
4,6
3,2
2
8,8
3
4
5
6
7
8
9
10
11
[V]
Diagram: Fan step at incoming 0-10V DC voltage level, 5 step
7,2
3
5,0
2
7,6
2,8
1
5,4
1
2
3,2
3
4
5
6
7
8
9
10
11
[V]
Diagram: Fan step for incoming 0-10V DC voltage level, 3-step.
General settings
Possibility of making general settings that are
also in the Start-up wizard and execute user
reset.
>Installer menu
Function test
To test the fan and heating steps, run the
function test.
External control
General settings
Support menu
>Installer menu>General
settings
Function test
Start test
Skip test
Change the date, time, language and
temperature unit.
>Installer menu>General
settings
Fan step 1-5
Heating step off-1
>Installer menu>General
settings
Set date
Set time
Set language
>Installer menu>General
settings
User reset
User reset (Room temp. day resp. night, high
speed limit, speed closed door) to factory
setting.
>Installer menu>General
settings
Function test
User reset
>Installer menu>User reset
Execute user reset?
No
Yes
Function test
Test completed
Restart test
Service menu
The service menu is password protected and
is used for support in contact with Frico or
authorised installer.
39
GB
SIRe Advanced Air Curtains Water
Alarm and error codes
SIRe has different alarms and error codes for
safe and problem free operation.
If alarms or error codes have been indicated
these must be reset in order to return to
normal operation, for example activating the
heating again. Fan mode is active even when,
for example, the over heating alarm has been
indicated.
Displaying alarm and error codes
In event of alarm or error the alarm/error
code is shown in the status window. In event
of alarm/error code the unit it applies to is
displayed.
See Table - Alarms and Table – Error codes.
Reset alarm
Note! Before resetting, check that the fault is
rectified and there is nothing to prevent the
unit from being recommissioned!
When the fault is rectified, the alarm is
reset by pressing the forward arrow and selecting Reset alarm and then confirm. If several
units give an alarm at the same time, the fact
that there are several alarms is indicated, but
only one is shown in the display. By resetting
that alarm the next alarm can be read.
At the first start up alarm and error codes
can occur, these can usually be reset without
action.
Overheat protection
Only applies to units with internal sensor.
The over heat protection maintains the
exhaust temperature at +40°C. If the
temperature should exceed +46°C e.g. in the
event of a faulty valve or actuator, the fan
starts to speed up to keep the temperature
down. At the same time there is an over
heating alarm A2. At internal temperatures of
+50°C the fan runs at maximum speed.
If the unit cools, heating is automatically
reengaged. The alarm remains in the control
unit’s display. If the unit overheats twice
within an hour, the fan operates until the
alarm is reset.
40
Power failure
Note that in case of power failure the time
settings need to be checked, if the time is not
set correctly week program will be affected.
Frost protection function
Only applies to units with internal sensor.
The frost protection function is intended to
prevent the water coil from freezing.
When the fan is in operation the valve
actuator opens the valve at an internal temperature below +15°C regardless of whether
there is a heating requirement. If the internal
unit temperature continues to drop, e.g. at
low ambient temperatures, insufficient flow
line temperatures, low flow or fault valve
function, the frost protection alarm A3 will be
triggered when the internal unit temperature
drops +5°C. The fan then also stops and when
the mixing cabinet is used the dampers is also
closed.
With return temp. sensor SIReWTA connected an advanced alarm function occurs. At
return temperatures less than +15°C the actuator will open regardless of the heat demand.
Alarm is triggered at return temperature +7°C
and the fan also stops.
When the fan is not running there is a heat
retention function that opens the valve when
the water’s return temperature falls below
+25°C regardless of heat demand.
Note! In event of repeated alarms, overheating alarms and frost protection alarms, carry
out a thorough check and if the fault cause
cannot be found contact authorised installer
or Frico.
SIRe Advanced Air Curtains Water
Alarm
Cause
Action
A1
Motor alarm
A2
Over heating alarm The temperature in the unit has
exceeded the alarm limit for
overheating.
(Only applies to units with
internal unit temperature.)
A3
Frost protection
alarm
The temperature in the unit has
fallen below the alarm limit for frost
protection. (Only applies to units with
internal unit temperature.)
Make sure that the ambient temperature
where the unit is installed exceeds +5°C.
Check the flow temperature, the flow of
hot water and the function of the actuator
and valve. In event of an alarm there a
risk that the battery is damaged, check
carefully for leakage and replace the
battery if damaged.
A4
Filter alarm
Fixed run time before the filter alarm
has been reached.
or the external filter alarm has been
activated.
Replace or clean the filter, adjust any
alarm time based on how dirty the filter
was and reset the alarm.
A5
Ext. alarm
Thermal switch has deployed. One
or several motors have overheated.
(Only units with withdrawn thermal
switches.)
GB
External alarm input on SIReA1X
has been activated.
Check that nothing is obstructing the
unit’s air intake and exhaust. When the
overheated motor has cooled the thermal
switch shuts again and the alarm can be
reset. At repeated alarms, check the motors,
replace damaged motors.
Check that nothing is obstructing
the unit’s air intake and exhaust, the
function of the actuator and valve, flow
temperature and internal temperature
sensor.
Check the external alarm.
41
GB
SIRe Advanced Air Curtains Water
Table - Error codes
Error code
Cause
Action
E1
Communication
SIReB1(X) has no contact with
SIReA1X.
Check connection between the boards.
Replace any modular cables.
E2
ID Error
Two or more SIReB1(X) have the
same ID-number.
Interrupt the current and select different ID
numbers for all SIReB1(X) in the system.
E3
ID Error
One or more SIReB1(X) do not
have programs.
Contact Frico for support.
E4
Room sensor
error
Fault on or missing external room
sensor SIReRTX connected to
SIReB1(X).
Always disconnect the power when
connecting or disconnecting sensors. Check
connection of the sensor.
E6
Sensor alarm
Return water
temp.
Fault on or missing return water
temp. sensor SIReWTA connected
to SIReB1(X).
Always disconnect the power when
connecting or disconnecting sensors. Check
connection of the sensor. If the sensor is
not used, it must not be activated (see the
Settings heating section)
E8
Internal sensor
faults
E10
ID Error
Two or more SIReB1(X) in the
system have different programs.
Contact Frico for support.
E12
Room sensor
error
Fault on or missing external room
sensor SIReRTX connected to
SIReA1X.
Always disconnect the power when
connecting or disconnecting sensors.
Check connection of the sensor.
E14
Outdoor sensor
fault
Fault on or missing outdoor
temperature sensor SIReOTX
connected to SIReA1X.
Always disconnect the power when
connecting or disconnecting sensors. Check
connection of the sensor.
E20
Communication
Control unit SIReUA1 has no
contact with SIReA1X.
Check the connection. Replace any
modular cables.
E21
Room sensor
error
Error in the internal room sensor
in the control unit SIReUA1.
Check connection between SIReUA1 and
SIReA1X. Replace any modular cables. If the
error is not rectified SIReUA1 must be replaced.
E23
Soft ware error
Contact Frico for support.
42
Fault on or missing internal sensor
in the unit.
(Only applies to units with internal
unit temperature.)
Check connection of the sensor. If there is
no sensor, contact Frico for support.
GB
SIRe Advanced Air Curtains Water
Connecting external control - including BMS functions
SIReA1X
Door contact
RPM indication
Ext. Heating control 0-10V DC IN
External on/off 5-30V AC/DC
Heating indication
External night reduction
7 8
on/off (potential-free switch)
Closes to activate the night reduction
function. Always active.
Outgoing alarm indication.
Always active.
Closed = buzzer alarm
Open = no alarm
(potential free contact) max 3A,
230V)
Outgoing operation indication.
Always active.
21 22
Operation indication OUT (BMS)
19 20
1112
+ -
Control fan control 0-100%.
Set parameter: >> Installer menu >
External control > 0-10V Fan control =
On
9 10
External rpm control 0-10V DC
SIReDC indicates door status.
Potential-free switch from door
automatic or BMS can also be used.
Closed = door open
Open = door closed
Alarm outgoing (BMS) (potential-free
switch, max 3A, 230V)
External alarm IN
(potential free contact)
An external filter guard closes to
indicate an alarm. Set Parameter: >>
Installer menu > Filter guard >
External filter guard = On
Door switch (obligatory)
(External potential-free switch)
17 18
(obligatory)
SIReOTX
External signal activates the unit.
Set parameter: >> Installer menu >
External control > External On/Off=
On
15 16
5 6
Outdoor temp. sensor
3 4
+ -
0-10V DC OUT (max 5 mA)
Signal from SIRe indicates connected
heating step. Always active. Control
signal to modulating actuator.
Activates heating. Set parameter: >>
Installer menu > External control>
0-10V heating control. = On
1314
+ -
1 2
+ -
0-10V DC OUT (max 5 mA)
Signal from SIRe indicates fan control,
corresponds to 0-100% fan control.
Always active.
21 22
Operation indication OUT (BMS)
19 20
ALARM OUT (BMS)
ROOM
Ext. Heating control 0-10V DC IN
External ON/OFF
111213 1415 161718
+ - + -
Ext. speed ctrl. 0-10V DC IN
BUS
External night reduction
External alarm IN
COM 2
Outdoor temp. sensor
COM 1
Heating indication
1 2 3 4 5 6 7 8 9 10
+ - + -
RPM indication
43
GB
C2
Pot.
X5
Unit ID
C1
X4
ROOM
X3
~
21 22
19 20
111213 1415 161718
1 2 3 4 5 6 7 8 9 10
COM 2
COM 1
ALARM OUT (BMS)
(potential free contact,
max 3A, 230V)
EXTERNAL ON/OFF, 5-30V AC/DC
EXTERNAL HEAT 0-10V DC IN
EXTERNAL RPM 0-10V DC IN
EXTERNAL ALARM IN
(potential free contact)
EXTERNAL SETBACK TEMP.
on/off (potential free contact)
Black
Grey
Red
RPM INDICATION
0-10V DC out (max 5 mA)
SIReST23024
ACTUATOR SUPPLY
N L L PE N L
230V~
SIReB1
Internal PC Board Base
Wiring diagram - Advanced
212
BMS INDICATION OUT
(potential free contact
max 3A, 230V)
SIReSDM24
SIReWTA
(optional)
SIReA1X
BUS
ROOM
SIReDC
SIReRTX
(optional)
SIReOTX
SIReUA1
SIRe Advanced Air Curtains Water
Black
Grey
Red
GB
21 22
19 20
111213 1415 161718
+ - + -
ALARM OUT (BMS)
(potential free contact,
max 3A, 230V)
EXTERNAL ON/OFF, 5-30V AC/DC
EXTERNAL HEAT 0-10V DC IN
EXTERNAL RPM 0-10V DC IN
EXTERNAL ALARM IN
(potential free contact)
EXTERNAL SETBACK TEMP.
on/off (potential free contact)
Black
Grey
Red
RPM INDICATION
0-10V DC out (max 5 mA)
ST23024
Black
Grey
Red
~
N L L
PE N L
SDM24
1 2 3 4 5 6 7 8 9 10
+ -
COM 1
BMS INDICATION OUT
(potential free contact
max 3A, 230V)
C2
Pot.
X5
Unit ID
C1
X4
ROOM
X3
ACTUATOR SUPPLY
SIReWTA
(optional)
SIReA1X
For wiring of external PC board
base see separate manual for
for wiring of external PC board
base SIReB1X
SIReB1X
External PC Board Base
Wiring diagram - Advanced
COM 2
BUS
ROOM
SIReDC
SIReRTX
(optional)
SIReOTX
SIReUA1
SIRe Advanced Air Curtains Water
213
GB
214
SIReOTX
21 22
19 20
111213 1415 161718
ALARM OUT (BMS)
(potential free contact,
max 3A, 230V)
EXTERNAL ON/OFF, 5-30V AC/DC
EXTERNAL HEAT 0-10V DC IN
EXTERNAL RPM 0-10V DC IN
EXTERNAL ALARM IN
(potential free contact)
EXTERNAL SETBACK TEMP.
on/off (potential free contact)
Black
Grey
Red
RPM INDICATION
0-10V DC out (max 5 mA)
Black
Grey
Red
230V~
~
ROOM
X3
ACTUATOR SUPPLY
N L L PE N L
C1
X4
C2
Pot.
X5
Unit ID
SIReB1
C1
X4
C2
Pot.
X5
Unit ID
SIReB1
C2
Pot.
X5
Unit ID
C1
X4
ROOM
X3
ROOM
X3
~
~
ACTUATOR SUPPLY
N L L PE N L
ACTUATOR SUPPLY
N L L PE N L
230V~
230V~
ST23024
Black
Grey
Red
SDM24
1 2 3 4 5 6 7 8 9 10
COM 1
BMS INDICATION OUT
(potential free contact
max 3A, 230V)
SDM24
Black
Grey
Red
SIReB1
Wiring diagram - Advanced – parallel connection
SDM24
SIReA1X
COM 2
BUS
ROOM
SIReDC
SIReRTX
(optional)
SIReUA1
SIRe Advanced Air Curtains Water
Tel: +46 31 336 86 00
Fax: +46 31 26 28 25
[email protected]
www.frico.se
For latest updated information and information
about your local contact: www.frico.se