MS-135XXXX CB Cert

MS-135XXXX CB Cert
Page 2 of 62
Report No.:
11016241 001
Copy of marking plate:
Note:
The above labels are draft of an artwork for marking plate pending approval by National Certification Bodies
and it shall not be affixed to products prior to such an approval.
Summary of testing:
•
•
•
•
The maximum ambient temperature is specified as 40 °C.
The sources of LCD panel used in the equipment is supplied by LED backlight unit, the LED forward
voltage is 27.2 Vdc maximum which is considered as SELV circuit, therefore, no further testing
consideration in SELV circuit or Limited Current Circuits evaluation to be necessary.
The USB ports were complied with Limited Power Source, see sub-clause 2.5.
The EUT information for test:
a. CPU: Intel AtomTM 1.6GHz (for mainboard P/N MS-1351), Intel CoreTM 1.2GHz (for mainboard P/N
MS-1352)
b. RAM: DDR2 2GHz maximum
c. HDD: 250G maximum
TRF No.:IECEN60950_1B
TRF originator: SGS Fimko
Page 3 of 62
Report No.:
11016241 001
Particulars: test item vs. test requirements
Equipment mobility .......................................: Transportable
Operating condition .......................................: Continuous
Mains supply tolerance (%) ...........................: No direct mains connection
Tested for IT power systems ........................: No
IT testing, phase-phase voltage (V) ..............: N/A
Class of equipment .......................................: Class III
Mass of equipment (kg).................................: 1.28
Protection against ingress of water ..............: IPX0
Test case verdicts
Test case does not apply to the test object ..: N/A
Test item does meet the requirement ..........: P(ass)
Test item does not meet the requirement ....: F(ail)
Testing
Date of receipt of test item ...........................: March, 2009
Date(s) of performance of test .....................: March, 2009
General remarks
”This report is not valid as a CB Test Report unless appended by an approved CB Testing
Laboratory and appended to a CB Test Certificate issued by an NCB in accordance with IECEE 02”.
The test result presented in this report relate only to the object(s) tested.
This report shall not be reproduced, except in full, without the written approval of the Issuing testing
laboratory.
”(see Enclosure #)" refers to additional information appended to the report.
"(see appended table)" refers to a table appended to the report.
Throughout this report a point is used as the decimal separator.
The samples tested represent the products from each factory.
Comments:
Summary of compliance with National Differences (for explanation of codes see below):
EU Group Differences, EU Special National Conditions, EU A-Deviations, AR, AT, AU, BE, CA, CH, CN, CZ,
DE, FR, GB, GR, HU, IL, IN, IT, KE, KR, MY, NL, PL, SG, SI, SK, US.
AR=Argentina, AT=Austria, AU=Australia, BE=Belgium, CA=Canada, CH=Switzerland, CN=China,
CZ=Czech Republic, DE=Germany, DK=Denmark, FI=Finland, FR=France, GB=United Kingdom,
GR=Greece, HU=Hungary, IL=Israel, IN=India, IT=Italy, KE=Kenya, KR=Korea, MY=Malaysia, NL=The
Netherlands, NO=Norway, PL=Poland, SE=Sweden, SG=Singapore, SI=Slovenia, SK=Slovakia, US=United
States of America.
For National Differences see end of this test report.
Factories:
1. MSI Computer (Shenzhen) Co., Ltd.
Longma Information Technology Industrial Park, Tangtou Village Shiyan Town, Baoan District Shenzhen,
Guangdong 518108, P.R. China
2. MSI ELECTRONICS (KUNSHAN) CO.,LTD.
88E QIANJIN Rd., Kunshan City, Jiangsu 215300, P.R. China
TRF No.:IECEN60950_1B
TRF originator: SGS Fimko
Page 4 of 62
Report No.:
11016241 001
Definition of variables:
Variable:
Range of variable:
Content:
x
0-9, A-Z or blank
For marketing purpose, no safety impact.
General product information:
The equipment models MS-135xxx (x=0-9, A-Z or blank) are Notebook Computer for general office use.
The external power adapters are approved products which were CB-scheme evaluated according to IEC
60950-1:2001, for detail information see appended table 1.5.1.
There are two mainboard provided for this Notebook P/N MS-1351 and MS-1352, those two mainboard is
similar to each other except for CPU, USB ports (two or three provided) and with/without HDMI connector,
for mainboard details, see table 1.5.1.
This report contains all national deviation as the class III equipment itself is subject of this CB report, but CB
countries for external adapter should investigate this matter while the equipment under test is submitted for
national approval.
TRF No.:IECEN60950_1B
TRF originator: SGS Fimko
Page 5 of 62
Report No.:
11016241 001
IEC 60950-1 / EN 60950-1
Clause
Requirement – Test
1
GENERAL
P
1.5
Components
P
1.5.1
General
See below.
P
Comply with IEC 60950 or relevant component
standard
Components, which were found
to affect safety aspects, comply
with the requirements of this
standard or within the safety
aspects of the relevant IEC
component standards (see
appended table 1.5.1).
P
1.5.2
Evaluation and testing of components
Components, which are
certified to IEC and/or national
standards, are used correctly
within their ratings.
Components not covered by
IEC standards are tested under
the conditions present in the
equipment.
P
1.5.3
Thermal controls
No thermal control.
1.5.4
Transformers
Transformers used are suitable
for their intended application
and comply with the relevant
requirements of the standard.
1.5.5
Interconnecting cables
No interconnection cable.
1.5.6
Capacitors in primary circuits ...............................: Equipment is not directly
connected to the AC mains
supply.
N/A
1.5.7
Double insulation or reinforced insulation bridged
by components
N/A
1.5.7.1
General
N/A
1.5.7.2
Bridging capacitors
N/A
1.5.7.3
Bridging resistors
N/A
1.5.7.4
Accessible parts
N/A
1.5.8
Components in equipment for IT power systems
1.6
Power interface
1.6.1
AC power distribution systems
TRF No.:IECEN60950_1B
Result – Remark
No such components.
Not applied for.
Verdict
N/A
P
N/A
N/A
P
Equipment is not directly
connected to the AC mains
supply.
N/A
TRF originator: SGS Fimko
Page 6 of 62
Report No.:
11016241 001
IEC 60950-1 / EN 60950-1
Clause
Requirement – Test
Result – Remark
Verdict
1.6.2
Input current
Highest load according to
1.2.2.1 for this equipment which
its contains max. rating of the
optional optical drives and HDD
permanently access, brightness
and contrast for LCD back light
circuit and charged with empty
battery pack. Dummy load of
2.5W in connection to represent
the each USB load. The
operator can connect additional
options like a parallel printer or
a serial device. See appended
table 1.6.2.
1.6.3
Voltage limit of hand-held equipment
This appliance is a not hand
held equipment.
N/A
1.6.4
Neutral conductor
Equipment is not directly
connected to the AC mains
supply.
N/A
1.7
Marking and instructions
1.7.1
Power rating
P
P
Marking label is located on
bottom of enclosure.
Rated voltage(s) or voltage range(s) (V) .............: See copy of marking plate.
(no direct connection to the AC
mains supply)
Symbol for nature of supply, for d.c. only .............: D.C. symbol used. (no direct
connection to the AC mains
supply)
P
N/A
P
Rated frequency or rated frequency range (Hz) ..: No direct connection to the AC
mains supply.
N/A
Rated current (mA or A) ......................................: See copy of marking plate.
(no direct connection to the AC
mains supply)
N/A
Manufacturer’s name or trademark or
See copy of marking plate.
identification mark ............................................... :
P
Type/model or type reference...............................: See copy of marking plate.
P
Symbol for Class II equipment only .....................: Class III equipment.
N/A
Other symbols ......................................................: Additional symbols or markings
do not give rise to
misunderstanding.
P
Certification marks ...............................................: See copy of the marking plate.
N/A
TRF No.:IECEN60950_1B
TRF originator: SGS Fimko
Page 7 of 62
Report No.:
11016241 001
IEC 60950-1 / EN 60950-1
Clause
Requirement – Test
Result – Remark
1.7.2
Safety instructions
The user’s manual is provided
to the user.
Verdict
P
Marking for Class 1 laser type of
all optical drives, the wording:
Laser Class 1 Product
No other special installation
instruction required as the
equipment is class III.
1.7.3
Short duty cycles
1.7.4
Supply voltage adjustment ...................................: No voltage / Frequency setting.
N/A
Methods and means of adjustment; reference to
installation instructions .........................................:
N/A
1.7.5
Power outlets on the equipment ..........................: No power outlet.
N/A
1.7.6
Fuse identification (marking, special fusing
Fuse not located in operator
characteristics, cross-reference) .........................: access areas, unambiguous
fuse cross-reference provided.
1.7.7
Wiring terminals
1.7.7.1
Protective earthing and bonding terminals ..........: No direct connection to the AC
mains supply.
N/A
1.7.7.2
Terminal for a.c. mains supply conductors
No direct connection to the AC
mains supply.
N/A
1.7.7.3
Terminals for d.c. mains supply conductors
No direct connection to the DC
mains supply.
N/A
1.7.8
Controls and indicators
See below.
1.7.8.1
Identification, location and marking .....................: The marking of the stand-by
switch is located that indication
of function clearly.
P
1.7.8.2
Colours ...............................................................: No safety relevant control and
indicator.
N/A
1.7.8.3
Symbols according to IEC 60417 .........................: Marking for stand-by type switch
according 60417-1-IEC-5009
(line half inside circle) was
marked on stand-by type switch
button.
1.7.8.4
Markings using figures ........................................:
N/A
1.7.9
Isolation of multiple power sources .....................: No direct connection to the AC
mains supply.
N/A
1.7.10
IT power distribution systems
Not applied for.
N/A
1.7.11
Thermostats and other regulating devices
No such devices.
N/A
TRF No.:IECEN60950_1B
Equipment designed for
continuous operation.
See below.
N/A
P
N/A
P
P
TRF originator: SGS Fimko
Page 8 of 62
Report No.:
11016241 001
IEC 60950-1 / EN 60950-1
Clause
Requirement – Test
Result – Remark
1.7.12
Language(s) .........................................................: Marking label and user’s manual
are in English.
Verdict

Versions in other languages will
be provided when national
certificate approval.
1.7.13
Durability
The label was subjected to the
permanence of marking test.
The label was rubbed with cloth
soaked with water for 15 s and
then again for 15 s with the
cloth soaked with petroleum
spirit.
P
After this test there was no
damage to the label. The
marking on the label did not
fade. There was neither curling
nor lifting of the label edge.
1.7.14
Removable parts
No required markings placed
on removable parts.
P
1.7.15
Replaceable batteries
The Lithium type RTC battery
and battery pack are
exchangeable. Warning text
provided in user’s manual.
P
Language(s)..........................................................: English

1.7.16
Operator access with a tool ..................................: No operator accessible area
with a tool.
N/A
1.7.17
Equipment for restricted access locations ............: Use of equipment not limited to
restricted access locations.
N/A
2
PROTECTION FROM HAZARDS
P
2.1
Protection from electric shock and energy hazards
P
2.1.1
Protection in operator access areas
See below.
P
2.1.1.1
Access to energized parts
See below.
P
Test by inspection ................................................: The equipment is supplied from
an approved power adaptor or
battery pack that provides only
SELV.
P
Test with test finger ..............................................: See above.
N/A
Test with test pin ..................................................:
N/A
Test with test probe .............................................: No TNV circuits provided.
N/A
2.1.1.2
Battery compartments .........................................: No TNV circuits provided.
P
2.1.1.3
Access to ELV wiring
TRF No.:IECEN60950_1B
N/A
TRF originator: SGS Fimko
Page 9 of 62
Report No.:
11016241 001
IEC 60950-1 / EN 60950-1
Clause
Requirement – Test
Result – Remark
Working voltage (Vpeak or Vrms); minimum
distance (mm) through insulation
Verdict

2.1.1.4
Access to hazardous voltage circuit wiring
2.1.1.5
Energy hazards ....................................................: No energy hazard in operator
access area.
No hazardous voltage wiring in
operator accessible area.
N/A
P
The connectors on the backside
of the equipment below 240VA.
2.1.1.6
Manual controls
N/A
2.1.1.7
Discharge of capacitors in equipment
N/A
Time-constant (s); measured voltage (V) .............:

2.1.2
Protection in service access areas
N/A
2.1.3
Protection in restricted access locations
N/A
2.2
SELV circuits
P
Supply from an approved SPS adapter or battery pack which was considered to
carry SELV at below 240VA only. No higher voltages generated.
2.2.1
General requirements
2.2.2
Voltages under normal conditions (V) ..................: 42.4V peak or 60Vd.c. are not
exceeded in SELV circuit under
normal operation.
P
2.2.3
Voltages under fault conditions (V).......................: Single fault did not cause
excessive voltage in accessible
SELV circuits. Limits of 71V
peak and 120Vd.c. were not
exceeded within 0.2 s and
limits 42.4V peak and 60Vd.c.
were not exceeded for longer
than 0.2 seconds.
P
2.2.3.1
Separation by double insulation or reinforced
insulation (method 1)
2.2.3.2
Separation by earthed screen (method 2)
N/A
2.2.3.3
Protection by earthing of the SELV circuit
(method 3)
N/A
2.2.4
Connection of SELV circuits to other circuits........: See 2.2.2 and 2.2.3.
P
2.3
TNV circuits
P
The secondary circuits were
tested as SELV. See 2.2.1 to
2.2.4.
Cl ass III equipment.
P
N/A
No TNV circuits..
2.3.1
Limits
Type of TNV circuits .............................................:
TRF No.:IECEN60950_1B
N/A

TRF originator: SGS Fimko
Page 10 of 62
Report No.:
11016241 001
IEC 60950-1 / EN 60950-1
Clause
Requirement – Test
2.3.2
Separation from other circuits and from accessible
parts
N/A
Insulation employed..............................................:

2.3.3
Result – Remark
Separation from hazardous voltages
N/A
Insulation employed..............................................:
2.3.4
Verdict

Connection of TNV circuits to other circuits
N/A
Insulation employed..............................................:

2.3.5
Test for operating voltages generated externally
N/A
2.4
Limited current circuits
N/A
2.4.1
General requirements
N/A
2.4.2
Limit values
N/A
Frequency (Hz) .....................................................:

Measured current (mA).........................................:

Measured voltage (V) ...........................................:

Measured capacitance (µF) ..................................:

2.4.3
Connection of limited current circuits to other
circuits
2.5
Limited power sources
N/A
P
For USB ports only.
Inherently limited output
Impedance limited output
2.6
N/A
Results see appended table
2.5.
P
Overcurrent protective device limited output
N/A
Regulating network limited output under normal
operating and single fault condition
N/A
Regulating network limited output under normal
operating conditions and overcurrent protective
device limited output under single fault condition
N/A
Output voltage (V), output current (A), apparent
Results see appended table
power (VA)............................................................: 2.5.

Current rating of overcurrent protective device (A)

Provisions for earthing and bonding
N/A
Class III equipment.
2.6.1
Protective earthing
TRF No.:IECEN60950_1B
N/A
TRF originator: SGS Fimko
Page 11 of 62
Report No.:
11016241 001
IEC 60950-1 / EN 60950-1
Clause
Requirement – Test
Result – Remark
2.6.2
Functional earthing
N/A
2.6.3
Protective earthing and protective bonding
conductors
N/A
2.6.3.1
General
N/A
2.6.3.2
Size of protective earthing conductors
N/A
2
Rated current (A), cross-sectional area (mm ),
AWG .....................................................................:
2.6.3.3
Verdict

Size of protective bonding conductors
N/A
2
Rated current (A), cross-sectional area (mm ),
AWG .....................................................................:

2.6.3.4
Resistance (Ω) of earthing conductors and their
terminations, test current (A) ................................:
N/A
2.6.3.5
Colour of insulation ...............................................:
N/A
2.6.4
Terminals
N/A
2.6.4.1
General
N/A
2.6.4.2
Protective earthing and bonding terminals
N/A
Rated current (A), type and nominal thread
diameter (mm) ......................................................:

2.6.4.3
Separation of the protective earthing conductor
from protective bonding conductors
N/A
2.6.5
Integrity of protective earthing
N/A
2.6.5.1
Interconnection of equipment
N/A
2.6.5.2
Components in protective earthing conductors
and protective bonding conductors
N/A
2.6.5.3
Disconnection of protective earth
N/A
2.6.5.4
Parts that can be removed by an operator
N/A
2.6.5.5
Parts removed during servicing
N/A
2.6.5.6
Corrosion resistance
N/A
2.6.5.7
Screws for protective bonding
N/A
2.6.5.8
Reliance on telecommunication network or cable
distribution system
N/A
2.7
Overcurrent and earth fault protection in primary circuits
N/A
With SELV supply from approved power supply or battery pack, no primary circuits
inside.
2.7.1
2.7.2
Basic requirements
N/A
Instructions when protection relies on building
installation
N/A
Faults not covered in 5.3
N/A
TRF No.:IECEN60950_1B
TRF originator: SGS Fimko
Page 12 of 62
Report No.:
11016241 001
IEC 60950-1 / EN 60950-1
Clause
Requirement – Test
Result – Remark
Verdict
2.7.3
Short-circuit backup protection
N/A
2.7.4
Number and location of protective devices...........:
N/A
2.7.5
Protection by several devices
N/A
2.7.6
Warning to service personnel ...............................:
N/A
2.8
Safety interlocks
N/A
2.8.1
General principles
N/A
2.8.2
Protection requirements
N/A
2.8.3
Inadvertent reactivation
N/A
2.8.4
Fail-safe operation
N/A
2.8.5
Moving parts
N/A
2.8.6
Overriding
N/A
2.8.7
Switches and relays
N/A
2.8.7.1
Contact gaps (mm) ..............................................:
N/A
2.8.7.2
Overload test
N/A
2.8.7.3
Endurance test
N/A
2.8.7.4
Electric strength test
N/A
2.8.8
Mechanical actuators
N/A
2.9
Electrical insulation
P
The unit is supplied from an approved power supply or battery pack that provides
SELV. Only SELV and limited current circuit inside the unit.
2.9.1
Properties of insulating materials
2.9.2
Humidity conditioning
Natural rubber, asbestos or
hygroscopic material is not
used.
P
N/A
Humidity (%) ........................................................:

Temperature (°C) .................................................:

2.9.3
Grade of insulation
2.10
Clearances, creepage distances and distances through insulation
P
2.10.1
General
P
2.10.2
Determination of working voltage
N/A
2.10.3
Clearances
N/A
TRF No.:IECEN60950_1B
The adequate levels of safety
insulation is provided and
maintained to comply with the
requirements of this standard.
Functional insulation only.
P
TRF originator: SGS Fimko
Page 13 of 62
Report No.:
11016241 001
IEC 60950-1 / EN 60950-1
Clause
Requirement – Test
2.10.3.1
General
N/A
2.10.3.2
Clearances in primary circuits
N/A
2.10.3.3
Clearances in secondary circuits
N/A
2.10.3.4
Measurement of transient voltage levels
N/A
2.10.4
Creepage distances
N/A
CTI tests ...............................................................:
Result – Remark
Verdict

2.10.5
Solid insulation
N/A
2.10.5.1
Minimum distance through insulation
N/A
2.10.5.2
Thin sheet material
N/A
2.10.5.3
Number of layers (pcs) .........................................:

Electric strength test

Printed boards
N/A
Distance through insulation
N/A
Electric strength test for thin sheet insulating
material

Number of layers (pcs) .........................................:
N/A
Wound components
N/A
Number of layers (pcs) .........................................:
N/A
Two wires in contact inside wound component;
angle between 45° and 90° ..................................:
N/A
2.10.6
Coated printed boards
N/A
2.10.6.1
General
N/A
2.10.6.2
Sample preparation and preliminary inspection
N/A
2.10.6.3
Thermal cycling
N/A
2.10.6.4
Thermal ageing (°C) .............................................:
N/A
2.10.6.5
Electric strength test
2.10.6.6
Abrasion resistance test
2.10.5.4
Electric strength test
2.10.7
2.10.8

N/A

Enclosed and sealed parts ...................................:
N/A
Temperature T1=T2 + Tma – Tamb +10K (°C)....:
N/A
Spacings filled by insulating compound................:
N/A
Electric strength test

2.10.9
Component external terminations
N/A
2.10.10
Insulation with varying dimensions
N/A
TRF No.:IECEN60950_1B
TRF originator: SGS Fimko
Page 14 of 62
Report No.:
11016241 001
IEC 60950-1 / EN 60950-1
Clause
Requirement – Test
Result – Remark
Verdict
3
WIRING, CONNECTIONS AND SUPPLY
P
3.1
General
P
3.1.1
Current rating and overcurrent protection
All internal wires are UL
recognized wiring which is PVC
insulated, rated VW-1, min.
80°C. Internal wiring gauge is
suitable for current intended to
be carried.
P
3.1.2
Protection against mechanical damage
Wires do not touch sharp
edges and heatsinks which
could damage the insulation
and cause hazard.
P
3.1.3
Securing of internal wiring
The wires are secured by
soldering and quick connector
so that a loosening of the
terminal connection is unlikely.
P
3.1.4
Insulation of conductors
The insulation of the individual
conductors is suitable for the
application and the working
voltage. For the insulation
material see 3.1.1.
P
3.1.5
Beads and ceramic insulators
Not used.
N/A
3.1.6
Screws for electrical contact pressure
No such screws.
N/A
3.1.7
Insulating materials in electrical connections
All current carrying connections
are metal to metal.
N/A
3.1.8
Self-tapping and spaced thread screws
No self-tapping or spaced
thread screws used.
N/A
3.1.9
Termination of conductors
All conductors are reliably
secured.
P
10 N pull test
Applied and passed.
P
3.1.10
Sleeving on wiring
No sleeving used as
supplementary insulation.
3.2
Connection to an a.c. mains supply or a d.c. mains supply
N/A
N/A
No direct connection to the mains supply.
3.2.1
Means of connection ............................................:
N/A
3.2.1.1
Connection to an a.c. mains supply
N/A
3.2.1.2
Connection to a d.c. mains supply
N/A
3.2.2
Multiple supply connections
N/A
3.2.3
Permanently connected equipment
N/A
Number of conductors, diameter (mm) of cable
and conduits ........................................................:
TRF No.:IECEN60950_1B

TRF originator: SGS Fimko
Page 15 of 62
Report No.:
11016241 001
IEC 60950-1 / EN 60950-1
Clause
Requirement – Test
Result – Remark
3.2.4
Appliance inlets
N/A
3.2.5
Power supply cords
N/A
3.2.5.1
AC power supply cords
N/A
Type......................................................................:
2
Rated current (A), cross-sectional area (mm ),
AWG .....................................................................:
Verdict


3.2.5.2
DC power supply cords
N/A
3.2.6
Cord anchorages and strain relief
N/A
Mass of equipment (kg), pull (N) ........................:

Longitudinal displacement (mm) ..........................:

3.2.7
Protection against mechanical damage
N/A
3.2.8
Cord guards
N/A
D (mm); test mass (g) ..........................................:

Radius of curvature of cord (mm).........................:

3.2.9
Supply wiring space
N/A
3.3
Wiring terminals for connection of external conductors
N/A
Class III equipment.
3.3.1
Wiring terminals
N/A
3.3.2
Connection of non-detachable power supply
cords
N/A
3.3.3
Screw terminals
N/A
3.3.4
Conductor sizes to be connected
N/A
Rated current (A), cord/cable type, cross2
sectional area (mm ) ........................................ :
3.3.5
Wiring terminal sizes
Rated current (A), type and nominal thread
diameter (mm) .....................................................:

N/A

3.3.6
Wiring terminals design
N/A
3.3.7
Grouping of wiring terminals
N/A
3.3.8
Stranded wire
N/A
3.4
Disconnection from the mains supply
N/A
No direct connection to the mains supply.
3.4.1
General requirement
N/A
3.4.2
Disconnect devices
N/A
3.4.3
Permanently connected equipment
N/A
TRF No.:IECEN60950_1B
TRF originator: SGS Fimko
Page 16 of 62
Report No.:
11016241 001
IEC 60950-1 / EN 60950-1
Clause
Requirement – Test
3.4.4
Parts which remain energized
N/A
3.4.5
Switches in flexible cords
N/A
3.4.6
Single-phase equipment and d.c. equipment
N/A
3.4.7
Three-phase equipment
N/A
3.4.8
Switches as disconnect devices
N/A
3.4.9
Plugs as disconnect devices
N/A
3.4.10
Interconnected equipment
N/A
3.4.11
Multiple power sources
N/A
3.5
Interconnection of equipment
3.5.1
General requirements
3.5.2
Types of interconnection circuits ..........................: SELV
3.5.3
ELV circuits as interconnection circuits
4
PHYSICAL REQUIREMENTS
P
4.1
Stability
P
Angle of 10°
Result – Remark
Verdict
P
See below.
P
P
No ELV interconnection.
This appliance is of a stable
mechanical construction and
does not overbalance when
tilted to an angle of 10° from its
normal upright position with
and without LCD screen open
conditions (including worst
rotate positon of LCD panel).
Test: force (N).......................................................: Equipment is not a
floorstanding unit.
N/A
P
N/A
4.2
Mechanical strength
4.2.1
General
See below. After tests, unit
comply with 2.1.1, 2.10 and
4.4.1.
P
4.2.2
Steady force test, 10 N
10 N applied to components
other than parts serving as an
enclosure.
P
4.2.3
Steady force test, 30 N
No internal enclosure.
4.2.4
Steady force test, 250 N
250 N applied to outer
enclosure of notebook PC and
battery pack. No energy or other
hazards.
4.2.5
Impact test
Transportable equipment.
TRF No.:IECEN60950_1B
P
N/A
P
N/A
TRF originator: SGS Fimko
Page 17 of 62
Report No.:
11016241 001
IEC 60950-1 / EN 60950-1
Clause
Requirement – Test
Result – Remark
Verdict
Fall test
Transportable equipment.
N/A
Swing test
Transportable equipment.
N/A
4.2.6
Drop test
After the test, no hazards.
P
4.2.7
Stress relief test
After 7 h for Notebook PC and
battery pack enclosure at 70°C
cooling down to room
temperature, no shrinkage,
distortion or loosing of enclosure
of battery pack and notebook
PC was noticeable on this
equipment.
P
4.2.8
Cathode ray tubes
No CRT.
N/A
Picture tube separately certified ...........................:
N/A
4.2.9
High pressure lamps
4.2.10
Wall or ceiling mounted equipment; force (N) .....:
4.3
Design and construction
4.3.1
Edges and corners
4.3.2
Handles and manual controls; force (N) ...............: No handles or controls provided.
N/A
4.3.3
Adjustable controls
None that would cause hazard.
N/A
4.3.4
Securing of parts
Electrical and mechanical
connections can be expected
to withstand usual mechanical
stress. For the protection
solder pins are used.
P
4.3.5
Connection of plugs and sockets
Mismatch of connectors were
prevented by incompatible form
or location.
P
4.3.6
Direct plug-in equipment
Not direct plug-in type.
N/A
Dimensions (mm) of mains plug for direct plug-in : Not direct plug-in type.
N/A
Torque and pull test of mains plug for direct
Not direct plug-in type.
plug-in; torque (Nm); pull (N) ................................:
N/A
Heating elements in earthed equipment
N/A
4.3.7
TRF No.:IECEN60950_1B
No high pressure lamp.
N/A
N/A
P
Edges and corners of the
enclosure are rounded.
No heating elements.
P
TRF originator: SGS Fimko
Page 18 of 62
Report No.:
11016241 001
IEC 60950-1 / EN 60950-1
Clause
Requirement – Test
Result – Remark
4.3.8
Batteries
For rechargable battery packs:
•
Approved components and
used within it’s specified
rating.
•
No reverse polarity
installation is possible due
to socket design of battery
pack
Verdict
P
For non-rechargable lithium type
RTC battery:
•
Reverse polarity installation
is prevented by socket
design.
•
The battery is protected
from reverse charging by
diode and resistor.
Results see appended table
5.3.
4.3.9
Oil and grease
No oil or grease.
N/A
4.3.10
Dust, powders, liquids and gases
The equipment is intended use
not considered to be exposed to
dust, powers, liquids and gases.
N/A
4.3.11
Containers for liquids or gases
No container for liquid or gas.
N/A
4.3.12
Flammable liquids.................................................: No flammable liquid.
N/A
Quantity of liquid (l) ...............................................:
N/A
Flash point (°C).....................................................:
N/A
4.3.13
Radiation; type of radiation ..................................: See below.
P
4.3.13.1
General
See below.
P
4.3.13.2
Ionizing radiation
No ionizing radiation.
4.3.13.3
4.3.13.4
N/A
Measured radiation (pA/kg) .................................:

Measured high-voltage (kV) ................................:

Measured focus voltage (kV) ...............................:

CRT markings .....................................................:

Effect of ultraviolet (UV) radiation on materials
No UV radiation.
N/A
Part, property, retention after test, flammability
classification ........................................................:
N/A
Human exposure to ultraviolet (UV) radiation ......:
N/A
TRF No.:IECEN60950_1B
TRF originator: SGS Fimko
Page 19 of 62
Report No.:
11016241 001
IEC 60950-1 / EN 60950-1
Clause
Requirement – Test
Result – Remark
4.3.13.5
Laser (including LEDs)
LED power is far below LED
Class 1 limit.
Verdict
P
All optional optical drives were
evaluated according to relevant
standard for laser product.
Therefore, complied with this
clause without further test.
Class 1 laser symbol appeared
on all optional optical drives and
in user’s manual.
Laser class ...........................................................: Laser Class 1 for all optional
optical drives.

4.3.13.6
Other types ..........................................................: No other types radiation.
4.4
Protection against hazardous moving parts
4.4.1
General
DC fan is protected by
enclosure. Other motors are
used in the certified HDD and all
optional optical drives.
P
4.4.2
Protection in operator access areas
See above.
P
4.4.3
Protection in restricted access locations
Not limited for restricted access
locations.
4.4.4
Protection in service access areas
4.5
Thermal requirements
4.5.1
Maximum temperatures
P
Resistance to abnormal heat
4.6
Openings in enclosures
4.6.1
Top and side openings
P
See appended table 4.5.1.
Bottoms of fire enclosures
N/A
P
Transportable equipment.
Same as above.
N/A

4.6.3
Doors or covers in fire enclosures
No such doors or covers.
4.6.4
Openings in transportable equipment
See appended table 4.6.1 and
4.6.2.
4.6.5
Adhesives for constructional purposes
TRF No.:IECEN60950_1B
N/A

Construction of the bottom ...................................: Same as above.
Conditioning temperature (°C)/time (weeks) ........:
P
P
Dimensions (mm) ................................................: Same as above.
4.6.2
N/A
N/A
Normal load condition per Annex L.......................: See 1.6.2.
4.5.2
N/A
N/A
P
N/A

TRF originator: SGS Fimko
Page 20 of 62
Report No.:
11016241 001
IEC 60950-1 / EN 60950-1
Clause
Requirement – Test
Result – Remark
Verdict
4.7
Resistance to fire
4.7.1
Reducing the risk of ignition and spread of flame
See below.
P
Method 1, selection and application of
components wiring and materials
Use of materials with the
required flammability classes.
P
P
Method 2, application of all of simulated fault
condition tests
N/A
4.7.2
Conditions for a fire enclosure
See below.
P
4.7.2.1
Parts requiring a fire enclosure
With having the following parts:
P
•
Components in secondary
(not supplied by LPS)
•
Insulated wiring
The fire enclosure is required.
4.7.2.2
Parts not requiring a fire enclosure
4.7.3
Materials
4.7.3.1
General
PCB is rated V-1 min.
P
4.7.3.2
Materials for fire enclosures
See appended table 1.5.1 for
enclosure material.
P
4.7.3.3
Materials for components and other parts outside
fire enclosures
None.
4.7.3.4
Materials for components and other parts inside
fire enclosures
Internal components except
small parts are V-2, HF-2 or
better.
4.7.3.5
Materials for air filter assemblies
No air filter assemblies.
N/A
4.7.3.6
Materials used in high-voltage components
No high voltage component.
N/A
5
ELECTRICAL REQUIREMENTS AND SIMULATED ABNORMAL CONDITIONS
P
5.1
Touch current and protective conductor current
P
5.1.1
General
5.1.2
Equipment under test (EUT)
5.1.3
Test circuit
5.1.4
Application of measuring instrument
N/A
5.1.5
Test procedure
N/A
5.1.6
Test measurements
See clause 4.7.2.1.
N/A
P
N/A
See below.
P
P
N/A
Using figure 5A.
P
See below.
P
Test voltage (V) ...................................................: See clause 5.1.8.1.

Measured touch current (mA) ..............................: See clause 5.1.8.1.

Max. allowed touch current (mA) .........................: See clause 5.1.8.1.

Measured protective conductor current (mA) ......:

TRF No.:IECEN60950_1B
TRF originator: SGS Fimko
Page 21 of 62
Report No.:
11016241 001
IEC 60950-1 / EN 60950-1
Clause
Requirement – Test
Result – Remark
Verdict
Max. allowed protective conductor current (mA) .:

5.1.7
Equipment with touch current exceeding 3.5 mA :
N/A
5.1.8
Touch currents to and from telecommunication
See below.
networks and cable distribution systems and from
telecommunication networks
P
5.1.8.1
Limitation of the touch current to a
telecommunication network and a cable
distribution system
P
See below.
Test voltage (V) ...................................................: 264Vac for power adapter.

Measured touch current (mA) ..............................: See appended table.

Max. allowed touch current (mA) .........................: 0.25

5.1.8.2
Summation of touch currents from
telecommunication networks ................................:
N/A
5.2
Electric strength
N/A
Class III equipment.
5.2.1
General
N/A
5.2.2
Test procedure
N/A
5.3
Abnormal operating and fault conditions
5.3.1
Protection against overload and abnormal
operation
See below.
P
5.3.2
Motors
Certified DC fan used, see table
1.5.1 for detail. Other motors
are used in the certified HDD
and all optional optical drives,
see appended table 1.5.1.
P
5.3.3
Transformers
No safety isolation transformer.
N/A
5.3.4
Functional insulation .............................................: Method c). Results see
appended table 5.3.
5.3.5
Electromechanical components
No electromechanical
component.
5.3.6
Simulation of faults
See appended table.
5.3.7
Unattended equipment
None of the listed components
was provided.
5.3.8
Compliance criteria for abnormal operating and
fault conditions
No fire occurred. No molten
metal was emitted.
6
CONNECTION TO TELECOMMUNICATION NETWORKS
TRF No.:IECEN60950_1B
P
P
N/A
P
N/A
P
N/A
TRF originator: SGS Fimko
Page 22 of 62
Report No.:
11016241 001
IEC 60950-1 / EN 60950-1
Clause
Requirement – Test
Result – Remark
Verdict
6.1
Protection of telecommunication network service persons, and users of other
equipment connected to the network, from hazards in the equipment
N/A
6.1.1
Protection from hazardous voltages
N/A
6.1.2
Separation of the telecommunication network from earth
N/A
6.1.2.1
Requirements
N/A
Test voltage (V) ...................................................:

Current in the test circuit (mA) .............................:

6.1.2.2
Exclusions.............................................................:
N/A
6.2
Protection of equipment users from overvoltages on telecommunication networks
N/A
6.2.1
Separation requirements
N/A
6.2.2
Electric strength test procedure
N/A
6.2.2.1
Impulse test
N/A
6.2.2.2
Steady-state test
N/A
6.2.2.3
Compliance criteria
N/A
6.3
Protection of the telecommunication wiring system from overheating.
N/A
Max. output current (A) .........................................:

Current limiting method ........................................:

7
CONNECTION TO CABLE DISTRIBUTION SYSTEMS
N/A
7.1
Protection of cable distribution system service
persons, and users of other equipment
connected to the system, from hazardous
voltages in the equipment
N/A
7.2
Protection of equipment users from overvoltages
on the cable distribution system
N/A
7.3
Insulation between primary circuits and cable
distribution systems
N/A
7.3.1
General
N/A
7.3.2
Voltage surge test
N/A
7.3.3
Impulse test
N/A
A
ANNEX A, TESTS FOR RESISTANCE TO HEAT AND FIRE
A.1
Flammability test for fire enclosures of movable equipment having a total mass
exceeding 18 kg, and of stationary equipment (see 4.7.3.2)
A.1.1
Samples................................................................:

Wall thickness (mm) .............................................:

TRF No.:IECEN60950_1B
P
N/A
TRF originator: SGS Fimko
Page 23 of 62
Report No.:
11016241 001
IEC 60950-1 / EN 60950-1
Clause
Requirement – Test
Result – Remark
A.1.2
Conditioning of samples; temperature (°C) ..........:
N/A
A.1.3
Mounting of samples ............................................:
N/A
A.1.4
Test flame (see IEC 60695-11-3)
N/A
Flame A, B, C or D ...............................................:
Verdict

A.1.5
Test procedure
N/A
A.1.6
Compliance criteria
N/A
Sample 1 burning time (s) ....................................:

Sample 2 burning time (s) ....................................:

Sample 3 burning time (s) ....................................:

A.2
Flammability test for fire enclosures of movable equipment having a total mass not
exceeding 18 kg, and for material and components located inside fire enclosures
(see 4.7.3.2 and 4.7.3.4)
P
A.2.1
Samples, material.................................................:

Wall thickness (mm) .............................................:

A.2.2
Conditioning of samples
N/A
A.2.3
Mounting of samples ...........................................:
N/A
A.2.4
Test flame (see IEC 60695-11-4)
N/A
Flame A, B or C ...................................................:

A.2.5
Test procedure
N/A
A.2.6
Compliance criteria
N/A
A.2.7
Sample 1 burning time (s) ....................................:

Sample 2 burning time (s) ....................................:

Sample 3 burning time (s) ....................................:

Alternative test acc. to IEC 60695-2-2, cl. 4 and 8
N/A
Sample 1 burning time (s) ....................................:

Sample 2 burning time (s) ....................................:

Sample 3 burning time (s) ....................................:

A.3
Hot flaming oil test (see 4.6.2)
N/A
A.3.1
Mounting of samples
N/A
A.3.2
Test procedure
N/A
A.3.3
Compliance criterion
N/A
B
ANNEX B, MOTOR TESTS UNDER ABNORMAL CONDITIONS (see 4.7.2.2 and
5.3.2)
N/A
B.1
General requirements
N/A
Position ................................................................:
TRF No.:IECEN60950_1B

TRF originator: SGS Fimko
Page 24 of 62
Report No.:
11016241 001
IEC 60950-1 / EN 60950-1
Clause
Requirement – Test
Result – Remark
Verdict
Manufacturer ........................................................:

Type .....................................................................:

Rated values .......................................................:

B.2
Test conditions
N/A
B.3
Maximum temperatures
N/A
B.4
Running overload test
N/A
B.5
Locked-rotor overload test
N/A
Test duration (days) .............................................:

Electric strength test: test voltage (V) ..................:

B.6
Running overload test for d.c. motors in
secondary circuits
N/A
B.7
Locked-rotor overload test for d.c. motors in secondary circuits
N/A
B.7.1
Test procedure
N/A
B.7.2
Alternative test procedure; test time (h)................:
N/A
B.7.3
Electric strength test
N/A
B.8
Test for motors with capacitors
N/A
B.9
Test for three-phase motors
N/A
B.10
Test for series motors
N/A
Operating voltage (V) ...........................................:
C

ANNEX C, TRANSFORMERS (see 1.5.4 and 5.3.3)
N/A
Position ................................................................:

Manufacturer ........................................................:

Type .....................................................................:

Rated values .......................................................:

Method of protection .............................................:

C.1
Overload test
N/A
C.2
Insulation
N/A
Protection from displacement of windings ............:
N/A
D
ANNEX D, MEASURING INSTRUMENTS FOR TOUCH-CURRENT TESTS
(see 5.1.4)
P
D.1
Measuring instrument
P
D.2
Alternative measuring instrument
N/A
E
ANNEX E, TEMPERATURE RISE OF A WINDING (see 1.4.13)
N/A
TRF No.:IECEN60950_1B
Complied.
TRF originator: SGS Fimko
Page 25 of 62
Report No.:
11016241 001
IEC 60950-1 / EN 60950-1
Clause
Requirement – Test
Result – Remark
F
ANNEX F, MEASUREMENT OF CLEARANCES AND CREEPAGE DISTANCES
(see 2.10)
N/A
G
ANNEX G, ALTERNATIVE METHOD FOR DETERMINING MINIMUM
CLEARANCES
N/A
G.1
Summary of the procedure for determining
minimum clearances
N/A
G.2
Determination of mains transient voltage (V) .......:
N/A
G.2.1
AC mains supply
N/A
G.2.2
DC mains supply
N/A
G.3
Determination of telecommunication network
transient voltage (V)..............................................:
N/A
G.4
Determination of required withstand voltage (V)...:
N/A
G.5
Measurement of transient levels (V).....................:
N/A
G.6
Determination of minimum clearances .................:
N/A
H
ANNEX H, IONIZING RADIATION (see 4.3.13)
N/A
J
ANNEX J, TABLE OF ELECTROCHEMICAL POTENTIALS (see 2.6.5.6)
N/A
Metal used ...........................................................:
Verdict

K
ANNEX K, THERMAL CONTROLS (see 1.5.3 and 5.3.7)
N/A
K.1
Making and breaking capacity
N/A
K.2
Thermostat reliability; operating voltage (V) .........:
N/A
K.3
Thermostat endurance test; operating voltage
(V) .......................................................................:
N/A
K.4
Temperature limiter endurance; operating voltage
(V) ........................................................................:
N/A
K.5
Thermal cut-out reliability
N/A
K.6
Stability of operation
N/A
L
ANNEX L, NORMAL LOAD CONDITIONS FOR SOME TYPES OF ELECTRICAL
BUSINESS EQUIPMENT (see 1.2.2.1 and 4.5.1)
L.1
Typewriters
N/A
L.2
Adding machines and cash registers
N/A
L.3
Erasers
N/A
L.4
Pencil sharpeners
N/A
TRF No.:IECEN60950_1B
P
TRF originator: SGS Fimko
Page 26 of 62
Report No.:
11016241 001
IEC 60950-1 / EN 60950-1
Clause
Requirement – Test
L.5
Duplicators and copy machines
N/A
L.6
Motor-operated files
N/A
L.7
Other business equipment
M
ANNEX M, CRITERIA FOR TELEPHONE RINGING SIGNALS (see 2.3.1)
N/A
M.1
Introduction
N/A
M.2
Method A
N/A
M.3
Method B
N/A
M.3.1
Ringing signal
N/A
M.3.1.1
Frequency (Hz) .....................................................:

M.3.1.2
Voltage (V) ...........................................................:

M.3.1.3
Cadence; time (s), voltage (V) .............................:

M.3.1.4
Single fault current (mA) .......................................:

M.3.2
Tripping device and monitoring voltage ................:
N/A
M.3.2.1
Conditions for use of a tripping device or a
monitoring voltage
N/A
M.3.2.2
Tripping device
N/A
M.3.2.3
Monitoring voltage (V)...........................................:
N/A
N
ANNEX N, IMPULSE TEST GENERATORS (see 2.10.3.4, 6.2.2.1, 7.3.2 and
clause G.5)
N/A
N.1
ITU-T impulse test generators
N/A
N.2
IEC 60065 impulse test generator
N/A
P
ANNEX P, NORMATIVE REFERENCES
Q
ANNEX Q, BIBLIOGRAPHY
N/A
R
ANNEX R, EXAMPLES OF REQUIREMENTS FOR QUALITY CONTROL
PROGRAMMES
N/A
R.1
Minimum separation distances for unpopulated
coated printed boards (see 2.10.6)
N/A
R.2
Reduced clearances (see 2.10.3)
N/A
S
ANNEX S, PROCEDURE FOR IMPULSE TESTING (see 6.2.2.3)
N/A
S.1
Test equipment
N/A
S.2
Test procedure
N/A
TRF No.:IECEN60950_1B
Result – Remark
See 1.6.2.
Verdict
P
P
TRF originator: SGS Fimko
Page 27 of 62
Report No.:
11016241 001
IEC 60950-1 / EN 60950-1
Clause
Requirement – Test
Result – Remark
Verdict
S.3
Examples of waveforms during impulse testing
N/A
T
ANNEX T, GUIDANCE ON PROTECTION AGAINST INGRESS OF WATER
(see 1.1.2)
N/A

U
ANNEX U, INSULATED WINDING WIRES FOR USE WITHOUT INTERLEAVED
INSULATION (see 2.10.5.4)
N/A

V
ANNEX V, AC POWER DISTRIBUTION SYSTEMS (see 1.6.1)
N/A
V.1
Introduction
N/A
V.2
TN power distribution systems
N/A
V.3
TT power systems
N/A
V.4
IT power systems
N/A
W
ANNEX W, SUMMATION OF TOUCH CURRENTS
N/A
W.1
Touch current from electronic circuits
N/A
W.1.2
Earthed circuits
N/A
W.2
Interconnection of several equipments
N/A
W.2.1
Isolation
N/A
W.2.2
Common return, isolated from earth
N/A
W.2.3
Common return, connected to protective earth
N/A
X
ANNEX X, MAXIMUM HEATING EFFECT IN TRANSFORMER TESTS
(see clause C.1)
N/A
X.1
Determination of maximum input current
N/A
X.2
Overload test procedure
N/A
Y
ANNEX Y, ULTRAVIOLET LIGHT CONDITIONING TEST (see 4.3.13.3)
N/A
Y.1
Test apparatus .....................................................:
N/A
Y.2
Mounting of test samples .....................................:
N/A
Y.3
Carbon-arc light-exposure apparatus ..................:
N/A
Y.4
Xenon-arc light exposure apparatus ....................:
N/A
TRF No.:IECEN60950_1B
TRF originator: SGS Fimko
Page 28 of 62
Report No.:
11016241 001
IEC 60950-1 / EN 60950-1
Clause
Requirement – Test
Result – Remark
CENELEC COMMON MODIFICATIONS [C],
SPECIAL NATIONAL CONDITIONS [S] AND A-DEVIATIONS (NATIONAL DEVIATIONS) [A]
(EN 60950-1:2001, Annex ZB and Annex ZC)
General
C: Delete all the "country" notes in the reference
document according to the following list:
1.1.5
Note 2
1.7.2
Note 4
2.2.3
Note
2.3.3
Note 1, 2
2.10.3.1 Note 4
3.2.5.1 Note 2
4.7.3.1 Note 2
6.2.2
Note
7
Note 4
G2.1
Note 1, 2
1.5.8
1.7.12
2.2.4
2.3.4
3.2.1.1
4.3.6
6.1.2.1
6.2.2.1
7.1
Annex H
Note 2
Note 2
Note
Note 2,3
Note
Note 1,2
Note
Note 2
Note
Note 2
1.6.1
2.6
2.3.2
2.7.1
3.2.3
4.7.2.2
6.1.2.2
6.2.2.2
Deleted.
Verdict
P
P
Note
Note
Note 2, 7, 8
Note
Note 1, 2
Note
Note
Note
1.2.4.1
S (DK): Certain types of Class I appliances (see
3.2.1.1) may be provided with a plug not
establishing earthing conditions when inserted
into Danish socket-outlets.
No direct connection to the
mains supply.
N/A
1.5.1
A (SE, Ordinance 1990:944 and
CH, Ordinance on environmentally hazardous
substances SR 814.013, Annex 3.2, Mercury):
Add NOTE – Switches containing mercury such as
No such switch.
N/A
thermostats, relays and level controllers are not allowed.
1.5.8
S (NO): Due to the IT power system used (see
annex V, Fig. V.7), capacitors are required to be
rated for the applicable line-to-line voltage
(230 V).
Class III equipment.
N/A
1.7.2
S (FI, NO, SE): CLASS I PLUGGABLE EQUIPMENT
intended for connection to other
equipment or a network shall, if safety relies on
connection to protective earth or if surge
suppressors are connected between the network
terminals and accessible parts, have a marking
stating that the equipment must be connected to
an earthed mains socket-outlet.
Class III equipment.
N/A
FI: "Laite on liitettävä suojamaadoituskoskettimilla Class III equipment.
varustettuun pistorasiaan"
N/A
NO: "Apparatet må tilkoples jordet stikkontakt"
Class III equipment.
N/A
SE: "Apparaten skall anslutas till jordat uttag"
Class III equipment.
N/A
A (DK, Heavy Current Regulations): Supply cords Class III equipment.
of class I equipment, which is delivered without a
plug, must be provided with a visible tag with the
following text:
N/A
TYPE A
The marking text in the applicable countries shall
be as follows:
Vigtigt!
Lederen med grøn/gul isolation må kun tilsluttes
en klemme mærket
eller
TRF No.:IECEN60950_1B
TRF originator: SGS Fimko
Page 29 of 62
Report No.:
11016241 001
IEC 60950-1 / EN 60950-1
Clause
Requirement – Test
Result – Remark
Verdict
If essential for the safety of the equipment, the
tag must in addition be provided with a diagram
which shows the connection of the other
conductors, or be provided with the following text:
"For tilslutning af de øvrige ledere, se
medfølgende instalationsvejledning."
1.7.5
S (DK): Socket-outlets for providing power to
other equipment shall be in accordance with the
Heavy Current Regulations, Section 107-2-D1,
Standard Sheet DK 1-3a, DK 1-5a or DK 1-7a,
when used on Class I equipment. For stationary
equipment the socket-outlet shall be in accordance with Standard Sheet DK 1-1b or DK 1-5a.
1.7.5
A (DK, Heavy Current Regulations):
Class III equipment.
CLASS II EQUIPMENT shall not be fitted with socketoutlets for providing power to other equipment.
N/A
1.7.12
A (DE, Gesetz über technische Arbeitsmittel
Not technical labour
(Gerätesicherheitsgesetz) [Law on technical
equipment. User’s manual
rd
labour equipment {Equipment safety law}], of 23
provided in English.
rd
nd
October 1992, Article 3, 3 paragraph, 2
sentence, together with the "Allgemeine
Verwaltungsvorschrift zur Durchführung des
Zweiten Abschnitts des Gerätesicherheitsgesetzes" [General administrative regulation on
the execution of the Second Section of the
th
Equipment safety law], of 10 January 1996,
th
article 2, 4 paragraph item 2):
Directions for use with rules to prevent certain
hazards for (among others) maintenance of the
technical labour equipment, also for imported
technical labour equipment shall be written in the
German language.
N/A
No socket-outlets.
N/A
NOTE: Of this requirement, rules for use even only by service
personnel are not exempted.
1.7.15
A (CH, Ordinance on environmentally hazardous
substances SR 814.013):
Annex 4.10 of SR 814.013 applies for batteries.
Battery pack and RTC battery
are in compliance with
requirements of IEC 60950-1.
N/A
Overall compliance needs to be
evaluated during the national
approval process.
A (DE, Regulation on protection against hazards This national difference was
th
by X-ray, of 8 January 1987, Article 5 [Operation deleted by A11 of EN 60950-1.
of X-ray emission source], clauses 1 to 4):
a) A licence is required by those who operate an
X-ray emission source.
b) A licence in accordance with Cl. 1 is not
required by those who operate an X-ray emission
source on which the electron acceleration voltage
does not exceed 20 kV if
1) the local dose rate at a distance of 0,1 m from
the surface does not exceed 1 µSv/h and
TRF No.:IECEN60950_1B
N/A
TRF originator: SGS Fimko
Page 30 of 62
Report No.:
11016241 001
IEC 60950-1 / EN 60950-1
Clause
Requirement – Test
Result – Remark
Verdict
2) it is adequately indicated on the X-ray emission
source that
i) X-rays are generated and
ii) the electron acceleration voltage must not
exceed the maximum value stipulated by
the manufacturer or importer.
c) A licence in accordance with Cl. 1 is also not
required by persons who operate an X-ray
emission source on which the electron
acceleration voltage exceeds 20 kV if
1) the X-ray emission source has been granted a
type approval and
2) it is adequately indicated on the X-ray emission
source that
i) X-rays are generated
ii) the device stipulated by the manufacturer or
importer guarantees that the maximum
permissible local dose rate in accordance
with the type approval is not exceeded and
iii) the electron acceleration voltage must not
exceed the maximum value stipulated by the
manufacturer or importer.
d) Furthermore, a licence in accordance with
Cl. 1 is also not required by persons who operate
X-ray emission sources on which the electron
acceleration voltage does not exceed 30 kV if
1) the X-rays are generated only by intrinsically
safe CRTs complying with Enclosure III, No. 6,
2) the values stipulated in accordance with
Enclosure III, No. 6.2 are limited by technical
measures and specified in the device and
3) it is adequately indicated on the X-ray emission
source that the X-rays generated are adequately screened by the intrinsically safe CRT.
2.2.4
S (NO): Requirements according to this annex,
1.7.2 and 6.1.2.1 apply.
No TNV circuit provided.
N/A
2.3.2
S (NO): Requirements according to this annex,
6.1.2.1 apply.
No TNV circuit provided.
N/A
2.3.3 and
2.3.4
S (NO): Requirements according to this annex,
1.7.2 and 6.1.2.1 apply.
No TNV circuit provided.
N/A
2.6.3.3
S (GB): The current rating of the circuit shall be
taken as 13 A, not 16 A.
Class III equipment.
N/A
2.7.1
C: Replace the subclause as follows:
Replaced.
N/A
Basic requirements
To protect against excessive current, shortcircuits and earth faults in PRIMARY CIRCUITS,
protective devices shall be included either as
integral parts of the equipment or as parts of the
TRF No.:IECEN60950_1B
TRF originator: SGS Fimko
Page 31 of 62
Report No.:
11016241 001
IEC 60950-1 / EN 60950-1
Clause
Requirement – Test
Result – Remark
Verdict
building installation, subject to the following, a), b)
and c):
a) except as detailed in b) and c), protective
devices necessary to comply with the
requirements of 5.3 shall be included as parts of
the equipment;
b) for components in series with the mains input
to the equipment such as the supply cord,
appliance coupler, r.f.i. filter and switch, shortcircuit and earth fault protection may be provided
by protective devices in the building installation;
c) it is permitted for PLUGGABLE EQUIPMENT TYPE B
or PERMANENTLY CONNECTED EQUIPMENT, to rely
on dedicated overcurrent and short-circuit
protection in the building installation, provided
that the means of protection, e.g. fuses or circuit
breakers, is fully specified in the installation
instructions.
If reliance is placed on protection in the building
installation, the installation instructions shall so
state, except that for PLUGGABLE EQUIPMENT TYPE
A the building installation shall be regarded as
providing protection in accordance with the rating
of the wall socket outlet.
S (GB): To protect against excessive currents
Not direct plug-in equipment.
and short-circuits in the PRIMARY CIRCUIT OF
DIRECT PLUG-IN EQUIPMENT, protective device shall
be included as integral parts of the DIRECT PLUGIN EQUIPMENT.
N/A
2.7.2
C: Void.
Declared.
N/A
2.10.2
C: Replace in the first line "(see also 1.4.7)" by
"(see also 1.4.8)".
Replaced.
N/A
2.10.3.1
S (NO): Due to the IT power distribution system
used (see annex V, Fig. V.7), the A.C. MAINS
SUPPLY voltage is considered to be equal to the
line-to-line voltage and will remain at 230 V in
case of a single earth fault
No direct connection to the AC
mains supply.
N/A
TRF No.:IECEN60950_1B
TRF originator: SGS Fimko
Page 32 of 62
Report No.:
11016241 001
IEC 60950-1 / EN 60950-1
Clause
Requirement – Test
Result – Remark
Verdict
3.2.1.1
S (CH): Supply cords of equipment having a
not exceeding 10 A shall be
provided with a plug complying with SEV 1011 or
IEC 60884-1 and one of the following dimension
sheets:
No power supply cord provided.
N/A
No power supply cord provided.
N/A
No power supply cord provided.
N/A
No power supply cord provided.
N/A
RATED CURRENT
SEV 6532-2.1991, Plug type 15, 3P+N+PE 250/400 V, 10 A
SEV 6533-2.1991, Plug type 11, L+N
250 V, 10 A
SEV 6534-2.1991, Plug type 12, L+N+PE 250 V, 10 A
In general, EN 60309 applies for plugs for
currents exceeding 10 A. However, a 16 A plug
and socket-outlet system is being introduced in
Switzerland, the plugs of which are according to
the following dimension sheets, published in
February 1998:
SEV 5932-2.1998, Plug type 25, 3L+N+PE 230/400 V, 16 A
SEV 5933-2.1998, Plug type 21, L+N
250 V, 16 A
SEV 5934-2.1998, Plug type 23, L+N+PE 250 V, 16 A
S (DK): Supply cords of single-phase equipment
having a rated current not exceeding 13 A shall
be provided with a plug according to the Heavy
Current Regulations, Section 107-2-D1.
CLASS I EQUIPMENT provided with socket-outlets
with earth contacts or which are intended to be
used in locations where protection against
indirect contact is required according to the wiring
rules shall be provided with a plug in accordance
with standard sheet DK 2-1a or DK 2-5a.
If ply-phase equipment and single-phase
equipment having a RATED CURRENT exceeding
13 A is provided with a supply cord with a plug,
this plug shall be in accordance with the Heavy
Current Regulations, Section 107-2-D1 or
EN 60309-2.
S (ES): Supply cords of single-phase equipment
having a rated current not exceeding 10 A shall
be provided with a plug according to
UNE 20315:1994.
Supply cords of single-phase equipment having a
rated current not exceeding 2,5 A shall be
provided with a plug according to
UNE-EN 50075:1993.
CLASS I EQUIPMENT provided with socket-outlets
with earth contacts or which are intended to be
used in locations where protection against
indirect contact is required according to the wiring
rules, shall be provided with a plug in accordance
with standard UNE 20315:1994.
If poly-phase equipment is provided with a supply
cord with a plug, this plug shall be in accordance
with UNE-EN 60309-2.
S (GB): Apparatus which is fitted with a flexible
TRF No.:IECEN60950_1B
TRF originator: SGS Fimko
Page 33 of 62
Report No.:
11016241 001
IEC 60950-1 / EN 60950-1
Clause
Requirement – Test
Result – Remark
Verdict
cable or cord and is designed to be connected to
a mains socket conforming to BS 1363 by means
of that flexible cable or cord and plug, shall be
fitted with a 'standard plug' in accordance with
Statutory Instrument 1768:1994 – The Plugs and
Socket etc. (Safety) Regulations 1994, unless
exempted by those regulations.
NOTE – 'Standard plug' is defined in SI 1768:1994 and
essentially means an approved plug conforming to BS 1363
or an approved conversion plug.
S (IE): Apparatus which is fitted with a flexible
cable or cord and is designed to be connected to
a mains socket conforming to I.S. 411 by means
of that flexible cable or cord and plug, shall be
fitted with a 13 A plug in accordance with
Statutory Instrument 525:1997 – National
Standards Authority of Ireland (section 28) (13 A
Plugs and Conversion Adaptors for Domestic
Use) Regulations 1997.
No power supply cord provided.
N/A
3.2.3
C: Delete Note 1 and in Table 3A, delete the
conduit sizes in parentheses.
Deleted.
N/A
3.2.5.1
C: Replace
Replaced.
N/A
"60245 IEC 53" by "H05 RR-F";
"60227 IEC 52" by "H03 VV-F or H03 VVH2-F";
"60227 IEC 53" by "H05 VV-F or H05 VVH2-F2".
In Table 3B, replace the first four lines by the
following:
Up to and including 6
2)
Over 6 up to and including 10 (0,75)
3)
Over 10 up to and including 16 (1,0)
1)
0,75
1,0
1,5
In the Conditions applicable to Table 3B delete
1)
the words "in some countries" in condition .
In Note 1, applicable to Table 3B, delete the
second sentence.
3.2.5.1
S (GB): A power supply cord with conductor of
2
1,25 mm is allowed for equipment with a rated
current over 10 A and up to and including 13 A.
No power cord provided.
N/A
3.3.4
C: In table 3D, delete the fourth line: conductor
sizes for 10 to 13 A, and replace with the
following:
Deleted.
N/A
No power supply cord provided.
N/A
"Over 10 up to and including 16
1,5 to 2,5
1,5 to 4"
Delete the fifth line: conductor sizes for 13 to
16 A.
3.3.4
S (GB): The range of conductor sizes of flexible
cords to be accepted by terminals for equipment
with a RATED CURRENT of over 10 A up to and
including 13 A is:
2
2
- 1,25 mm to 1,5 mm nominal cross-sectional
area.
TRF No.:IECEN60950_1B
TRF originator: SGS Fimko
Page 34 of 62
Report No.:
11016241 001
IEC 60950-1 / EN 60950-1
Clause
Requirement – Test
Result – Remark
4.3.6
S (GB): The torque test is performed using a
socket outlet complying with BS 1363 and the
plug part of DIRECT PLUG-IN EQUIPMENT shall be
assessed to BS 1363: Part 1, 12.1, 12.2, 12.3,
12.9, 12.11, 12.12, 12.16 and 12.17, except that
the test of 12.17 is performed at not less than
125 °C.
Not direct plug-in equipment.
N/A
S (IE): DIRECT PLUG-IN EQUIPMENT is known as
Not direct plug-in equipment.
plug similar devices. Such devices shall comply
with Statutory Instrument 526:1997 – National
Standards Authority of Ireland (Section 28)
(Electrical plugs, plug similar devices and sockets
for domestic use) Regulations, 1997.
N/A
C: Add the following note:
Added.
N/A
No TNV circuit provided.
N/A
4.3.13.6
Verdict
NOTE Attention is drawn to 1999/519/EC: Council
Recommendation on the limitation of exposure of the general
public to electromagnetic fields 0 Hz to 300 GHz. Standards
taking into account this recommendation are currently under
development.
6.1.2.1
S (FI, NO, SE): Add the following text between
the first and second paragraph:
If this insulation is solid, including insulation
forming part of a component, it shall at least
consist of either
- two layers of thin sheet material, each of which
shall pass the electric strength test below, or
- one layer having a distance through insulation of
at least 0,4 mm, which shall pass the electric
strength test below.
If this insulation forms part of a semiconductor
component (e.g. an optocoupler), there is no
distance through insulation requirement for the
insulation consisting of an insulating compound
completely filling the casing, so that CLEARANCES
AND CREEPAGE DISTANCES do not exist, if the
component passes the electric strength test in
accordance with the compliance clause below
and in addition
- passes the tests and inspection criteria of 2.10.8
with an electric strength test of 1,5 kV multiplied
by 1,6 (the electric strength test of 2.10.7 shall be
performed using 1,5 kV), and
- is subject to ROUTINGE TESTING for electric
strength during manufacturing, using a test
voltage of 1,5 kV.
It is permitted to bridge this insulation with a
capacitor complying with EN 132400:1994,
subclass Y2.
A capacitor classified Y3 according to
EN 132400:1994, may bridge this insulation
TRF No.:IECEN60950_1B
TRF originator: SGS Fimko
Page 35 of 62
Report No.:
11016241 001
IEC 60950-1 / EN 60950-1
Clause
Requirement – Test
Result – Remark
Verdict
under the following conditions:
- the insulation requirements are satisfied by
having a capacitor classified Y3 as defined by
EN 132400, which in addition to the Y3 testing, is
tested with an impulse test of 2,5 kV defined in
EN 60950:2000, 6.2.2.1;
- the additional testing shall be performed on all
the test specimens as described in EN 132400;
- the impulse test of 2,5 kV is to be performed
before the endurance test in EN 132400, in the
sequence of tests as described in EN 132400.
6.1.2.2
S (FI, NO, SE): The exclusions are applicable for
No TNV circuit provided.
N/A
PERMANENTLY CONNECTED EQUIPMENT and
PLUGGABLE EQUIPMENT TYPE B and equipment
intended to be used in a RESTRICTED ACCESS
LOCATION where equipotential bonding has been
applied, e.g. in a telecommunication centre, and
which has provision for a permanently connected
PROTECTIVE EARTHING CONDUCTOR and is provided
with instructions for the installation of that
conductor by a service person.
7.1
S (FI, NO, SE): Requirements according to this
No cable distribution system
annex, 6.1.2.1 and 6.1.2.2 apply with the term
provided.
TELECOMMUNICATION NETWORK in 6.1.2 being
replaced by the term CABLE DISTRIBUTION SYSTEM.
N/A
G.2.1
S (NO): Due to the IT power distribution system
used (see annex V, Fig. V.7), the A.C. MAINS
SUPPLY voltage is considered to be equal to the
line-to-line voltage, and will remain at 230 V in
case of a single earth fault.
No direct connection to the AC
mains supply.
N/A
Annex H
C: Replace the last paragraph of this annex by:
No CRT.
N/A
Replaced.
P
At any point 10 cm from the surface of the
operator access area, the dose rate shall not
exceed 1 µSv/h (0,1 mR/h) (see note). Account is
taken of the background level.
Replace the notes as follows:
NOTE These values appear in Directive 96/29/Euratom.
Delete Note 2.
Annex P
C: Replace the text of this annex by:
See annex ZA.
Annex Q
C: Replace the title of IEC 61032 by "Protection of persons and equipment by
enclosures – Probes for verification".
N/A
Add the following notes for the standards indicated:
IEC 60127
IEC 60269-2-1
IEC 60529
IEC 61032
IEC 61140
TRF No.:IECEN60950_1B
NOTE Harmonized as EN 60127 (Series) (not modified)
NOTE Harmonized as HD 630.2.1 S4:2000 (modified)
NOTE Harmonized as EN 60529:1991 (not modified)
NOTE Harmonized as EN 61032:1998 (not modified)
NOTE Harmonized as EN 61140:2001 (not modified)
TRF originator: SGS Fimko
Page 36 of 62
Report No.:
11016241 001
IEC 60950-1 / EN 60950-1
Clause
Requirement – Test
Result – Remark
Verdict
ITU-T Recommendation K.31
NOTE in Europe, the suggested document is EN 50083-1.
Annex ZA
C: NORMATIVE REFERENCES TO INTERNATIONAL PUBLICATIONS WITH
THEIR RELEVANT EUROPEAN PUBLICATIONS
P
This European Standard incorporates, by dated or undated reference, provisions
from other publications. These normative references are cited at the appropriate
places in the text and the publications are listed hereafter. For dated references,
subsequent amendments to or revisions of any of these publications apply to this
European Standard only when incorporated in it by amendment or revision. For
undated references, the latest edition of the publication referred to applies
(including amendments).
NOTE When an international publication has been modified by common modifications, indicated by
(mod), the relevant EN/HD applies.


EN 60065:1998 + corr. June 1999
EN 60073:1996
HD 566 S1:1990
HD 214 S2:1980
HD 611.4.1.S1:1992
1)
HD 21 Series
2)
HD 22 Series
EN 60309 Series
EN 60317-43:1997
EN 60320 Series
HD 384.3 S2:1995
HD 384.4.41 S2:1996
4)
EN 132400:1994
+ A2:1998 + A3:1998 + A4:2001
EN 60417-1
HD 625.1 S1:1996 + corr. Nov. 1996
EN 60695-2-2:1994
EN 60695-2-11:2001




EN 60695-11-10:1999
EN 60695-11-20:1999
EN 60730-1:2000
EN 60825-1:1994 + corr. Febr. 1995 +
A11:1996 + corr. July 1997
EN 60825-2:2000

EN 60851-3:1996
EN 60851-5:1996
EN 60851-6:1996

EN 60990:1999

EN 61965:2001
EN ISO 178:1996
EN ISO 179 Series
TRF No.:IECEN60950_1B
IEC 60050-151
IEC 60050-195
IEC 60065 (mod):1998
IEC 60073:1996
IEC 60085:1984
IEC 60112:1979
IEC 60216-4-1:1990
IEC 60227 (mod) Series
IEC 60245 (mod) Series
IEC 60309 Series
IEC 60317-43:1997
IEC 60320 (mod) Series
IEC 60364-3 (mod):1993
3)
IEC 60364-4-41 (mod):1992
IEC 60384-14:1993
IEC 60417-1
IEC 60664-1 (mod):1992
IEC 60695-2-2:1991
IEC 60695-2-11:2000
IEC 60695-2-20:1995
IEC 60695-10-2:1995
IEC 60695-11-3:2000
IEC 60695-11-4:2000
IEC 60695-11-10:1999
IEC 60695-11-20:1999
IEC 60730-1:1999 (mod)
IEC 60825-1:1993
IEC 60825-2:2000
IEC 60825-9:1999
IEC 60851-3:1996
IEC 60825-5:1996
IEC 60851-6:1996
IEC 60885-1:1987
IEC 60990:1999
IEC 61058-1:2000
IEC 61965:2000
ISO 178:1993
ISO 179 Series
TRF originator: SGS Fimko
Page 37 of 62
Report No.:
11016241 001
IEC 60950-1 / EN 60950-1
Clause
Requirement – Test
EN ISO 180:2000


EN ISO 527 Series

EN ISO 4892 Series

EN ISO 8256:1996

EN ISO 9773:1998


Result – Remark
Verdict
ISO 180:1993
ISO 261:1998
ISO 262:1998
ISO 527 Series
ISO 386:1984
ISO 4892 Series
ISO 7000:1989
ISO 8256:1990
ISO 9772:1994
ISO 9773:1998
ITU-T:1988 Recommendation K.17
ITU-T:2000 Recommendation K.21
1) The HD 21 series is related to, but not directly equivalent with the IEC 60227 series
2) The HD 22 series is related to, but not directly equivalent with the IEC 60245 series
3) IEC 60364-4-41:1992 is superseded by IEC 60364-4-41:2001
4) EN 132400, Sectional Specification: Fixed capacitors for electromagnetic interference suppression
and connection to the supply mains (Assessment level D), and its amendments are related to, but not
directly equivalent to IEC 60384-14
TRF No.:IECEN60950_1B
TRF originator: SGS Fimko
Page 38 of 62
1.5.1
Report No.:
11016241 001
TABLE: list of critical components
P
Object/part no.
Manufacturer/
trademark
Type/model
Technical data
Standard
Mark(s) of
1.
conformity
Switching
Power adapter
Enertronix
EXA0803YI
I/P: 100-240Vac,
50-6Hz, 1.2A
O/P: 20Vdc, 2A
Class I, Operated
Ambient 40°C
IEC 60950-1:
2001
EN 60950-1:
2001+A11
TÜV, UL, CB
(by TÜV
Rheinland)
Delta Eletronic
Inc.
ADP-40MH BD
I/P:100-240Vac,
50-60Hz,1.2A
O/P:20Vdc,2A
Class I, LPS,
Operated Ambient
40°C
IEC 60950-1:
2001
EN 60950-1:
2001+A11
TÜV, UL, CB
(by TÜV
Rheinland)
Delta Eletronic
Inc.
ADP-65HB BB
Output rated: 19
Vdc, 3.42 A.
Class I, LPS,
Operated Ambient
40°C
IEC 60950-1:
2001
EN 60950-1:
2001+A11
TÜV, UL, CB
(by TÜV
Rheinland)
Li Shin
Interational
Enterprise Corp
0335A1965
I/P: 100-240 Vac,
50-60 Hz, 1.7 A;
O/P: 19 Vdc, 3.42
A, Operated
Ambient 40°C.
IEC 60950-1:
2001
EN 60950-1:
2001+A11
TÜV, UL, CB
(by TÜV
Rheinland)
Li Shin
Interational
Enterprise Corp
0225A2040
I/P:100-240Vac,
50-60Hz, 1.7A
O/P:20Vdc, 2A
Class I, LPS,
Operated Ambient
40°C
IEC 60950-1:
2001
EN 60950-1:
2001+A11
TÜV, UL, CB
(by TÜV SÜD)
Enclosure for
all part (except
bottom side)
Sabic Innovative C7230P
Plastics Japan L
LC
V-1 minimum,
UL 94
85°C minimum,
1.2mm thickness
minimum
UL
Sabic Innovative C7230
Plastics Japan L
LC
V-1 minimum,
UL 94
60°C minimum,
1.0mm thickness
minimum
UL
Enclosure for
bottom
--
--
Metal, 0.8mm
thickness
minimum
--
--
PWB
--
--
V-1 minimum,
105°C minimum
UL796
UL
Panel
--
--
13.4”, TFT type
with LED backlight unit
--
--
DC fan
Tranyoung
Technology
Corp
6010H05F PFR
5Vdc, 0.55A
maximum, 3.62
CFM minimum
IEC 60950-1:
2001
EN 60950-1:
2001+A11
TÜV, UL
TRF No.:IECEN60950_1B
TRF originator: SGS Fimko
Page 39 of 62
Report No.:
11016241 001
BTY-S31
14.8Vdc, LithiumIon type.
2150mAh,
Class III.
IEC 60950-1:
2001
EN 60950-1:
2001+A11
TÜV, UL
Hard Disk Drive WD
(Optional)
(or equivalent)
WD2500BEVT
(or equivalent)
5Vdc, 1.5A
maximum; or
3.3/5Vdc,
1.5/1.5A
maximum.
Class III
IEC 60950-1:
2001
EN 60950-1:
2001+A11
TÜV, UL
SSD Drive
(Optional)
--
--
5Vdc, 100mA
maximum.
Class III
--
--
Speaker
(Optional)
--
--
Two provided, 4Ω -maximum, 2W
maximum.
--
TYCO
(Raychem)
MiniSMDC110
1.1A maximum,
6V minimum.
IEC 60730-1
clause 15, 17,
J15, J17;
UL1434
TÜV, UL
(E74889)
LITTELFUSE
1812L110 series
1.1A maximum,
6V minimum.
IEC 60730-1
clause 15, 17,
J15, J17;
UL1434
TÜV, UL
(E183209)
Polytronics
SMD1812P110T
F
1.1A maximum,
6V minimum.
IEC 60730-1
clause 15, 17,
J15, J17;
UL1434
TÜV, UL
(E201431)
VIC-DAWN
ENTERPRISE
CO LTD
CR1220
3Vdc, maximum
abnormal charge
current 5mA.
UL1642
UL (MH20550)
HITACHI
MAXELL LTD
CR1220
3.3Vdc,
maximum
abnormal charge
current 5mA.
UL1642
UL (MH12568)
TYCO
(Raychem)
MiniSMDC110
1.1A maximum,
6V minimum.
IEC 60730-1
clause 15, 17,
J15, J17;
UL1434
TÜV, UL
(E74889)
LITTELFUSE
1812L110 series
1.1A maximum,
6V minimum.
IEC 60730-1
clause 15, 17,
J15, J17;
UL1434
TÜV, UL
(E183209)
Polytronics
SMD1812P110T
F
1.1A maximum,
6V minimum.
IEC 60730-1
clause 15, 17,
J15, J17;
UL1434
TÜV, UL
(E201431)
VIC-DAWN
CR1220
3Vdc, maximum
UL1642
UL (MH20550)
Battery Pack
Simplo
Technology Co
Ltd
For Main board P/N: MS-1351
PTC Current
Limiters (FA1,
FB2)(for USB
ports)
RTC Battery
For Main board P/N: MS-1352
PTC Current
Limiters
(FA1)(for USB
ports)
RTC Battery
TRF No.:IECEN60950_1B
TRF originator: SGS Fimko
Page 40 of 62
ENTERPRISE
CO LTD
HITACHI
MAXELL LTD
Report No.:
11016241 001
abnormal charge
current 5mA.
CR1220
3.3Vdc,
maximum
abnormal charge
current 5mA.
UL1642
UL (MH12568)
Note(s):
1. An asterisk indicates a mark that assures the agreed level of surveillance.
1.6.2
Fuse #
TABLE: electrical data (in normal conditions)
Irated (A)
U (Vdc)
P
P (W)
I (A)
Ifuse (A)
Condition/status
Test with Main board P/N: MS-1351
--
2.0
20
38.60
1.93
--
Maximum Normal Load. (test with
adaptor output rating 20Vdc)
--
2.0
19
36.86
1.94
--
Maximum Normal Load. (test with
adaptor output rating 19Vdc)
Test with Main board P/N: MS-1352
--
2.0
20
40.20
2.01
--
Maximum Normal Load. (test with
adaptor output rating 20Vdc)
--
2.0
19
38.57
2.03
--
Maximum Normal Load. (test with
adaptor output rating 19Vdc)
Note(s):
2.1.1.5
TABLE: max. V, A, VA test
Voltage (rated)
(V)
2.1.1.7
Condition
Current (rated)
(A)
Voltage (max.)
(V)
Current (max.)
(A)
VA (max.)
(VA)
TABLE: discharge test
N/A
τ calculated τ measured
(s)
2.2.2
N/A
(s)
t u→ 0V
(s)
Comments
TABLE: Hazardous voltage measurement
Transformer
Location
N/A
max. Voltage
V peak
TRF No.:IECEN60950_1B
V d.c.
Voltage Limitation
Component
TRF originator: SGS Fimko
Page 41 of 62
2.2.3
TABLE: SEL voltage measurement
Location
2.4.2
Comments
TABLE: limited current circuit measurement
Voltage
(V)
11016241 001
N/A
Voltage measured (V)
Location
2.5
Report No.:
Current
(mA)
N/A
Freq.
(kHz)
Limit
(mA)
Comments
TABLE: limited power source measurement
Limits
P
Measured
Verdict
8
2.3
P
25.1 (5×Uoc)
8.64
P
8
2.2
P
25.15 (5×Uoc)
8.33
P
8
2.2
P
25.1 (5×Uoc)
9.08
P
Test with Main board P/N: MS-1351
For USB port:
According to Table 2B (normal condition) (for USB2, Uoc=5.02V)
current (in A)
apparent power (in VA)
According to Table 2B (normal condition) (for USB3 and USB4, Uoc=5.03V)
current (in A)
apparent power (in VA)
Test with Main board P/N: MS-1352
For USB port:
According to Table 2B (normal condition) (for USB3 and USB4, Uoc=5.02V)
current (in A)
apparent power (in VA)
Note(s):
2.6.3.4
TABLE: ground continue test
Location
TRF No.:IECEN60950_1B
N/A
Resistance measured (mΩ) Comments
TRF originator: SGS Fimko
Page 42 of 62
2.10.2
Report No.:
11016241 001
Table: working voltage measurement
Location
N/A
RMS voltage (V)
Peak voltage (V) Comments
2.10.3 and TABLE: clearance and creepage distance measurements
2.10.4
Clearance cl and creepage
distance dcr at/of:
2.10.5
U r.m.s.
(V)
Required
cl (mm)
cl
(mm)
Required
dcr (mm)
dcr
(mm)
TABLE: distance through insulation measurements
Distance through insulation di at/of:
4.5.1
Up
(V)
N/A
U r.m.s.
(V)
N/A
Test voltage
(V)
Required di
(mm)
di
(mm)
TABLE: temperature rise measurements
P
test voltage (V) ..................................................... : 1. DC 19V

2. Powered from battery pack
t1 (°C) .................................................................. : --

t2 (°C) .................................................................. : --

Maximum temperature T of part/at:
T (°C)
allowed Tmax (°C)
Test with Main board P/N: MS-1351
Test voltage
1.
2.
--
Max. ambient temperature Tma (°C):
Note: ambient air during test were Tamb =22.1°C and 22.7°C
respectively
40.0
40.0
--
PCB near CPU(U23)
69.9
63.7
105
PCB near (U22)
68.0
61.1
105
Memory board
66.2
61.1
105
RTC Battery body
53.8
51.1
105
HDD body
53.7
50.3
105
Keyboard body
44.3
43.3
95
TRF No.:IECEN60950_1B
TRF originator: SGS Fimko
Page 43 of 62
Report No.:
11016241 001
Panel
43.0
40.3
95
Metal Enclosure outside near CPU
56.3
48.1
70
Enclosure near Battery Connector
53.2
48.1
95
Battery pack enclosure
48.5
47.7
95
Metal Enclosure outside near HDD
49.3
47.7
70
1.
2.
--
Max. ambient temperature Tma (°C):
Note: ambient air during test were Tamb =22.1°C and 22.0°C
respectively
40.0
40.0
--
PWB near (U5)
41.7
58.8
105
PWB near CPU (U6)
41.7
58.8
105
PWB near (U2)
41.9
60.8
105
RTC Battery body
42.0
54.0
105
HDD body
41.6
52.0
105
Metal Enclosure inside near CPU
41.6
53.0
70
Keyboard body
40.8
43.8
95
Panel
40.0
40.4
95
Enclosure near Battery Connector
41.9
52.0
95
Battery pack enclosure
42.1
50.0
95
Metal Enclosure outside near CPU
41.7
45.1
70
Metal Enclosure outside near HDD
41.4
44.1
70
Test with Main board P/N: MS-1352
Test voltage
Temperature rise T of winding:
R1
(Ω)
R2
(Ω)
T
(°C)
allowed
Tmax (°C)
insulation
class
Note(s):
1. The temperatures were measured under worst case normal mode defined in 1.2.2.1 and as described in
1.6.2 at voltages as above.
2. The maximum ambient temperature permitted by the manufacturer’s specification is 40 °C.
3. All values for T(°C) are re-calculated from actual ambient respectively.
4.5.2
TABLE: ball pressure test of thermoplastic parts
N/A
allowed impression diameter (mm) ................... : ≤ 2 mm
Part
TRF No.:IECEN60950_1B

Test temperature
(°C)
Impression diameter
(mm)
TRF originator: SGS Fimko
Page 44 of 62
Report No.:
11016241 001
Note(s):
4.6.1, 4.6.2 Table: enclosure openings
Location
P
Size (mm)
Comments
Top, side, front, rear
-- None
Bottom
max. 0.8 × 20.7 Numerous rectangle openings provided.
Note(s):
4.7
Table: resistance to fire
Part
P
Manufacturer of material
Type of material
Thickness
(mm)
Flammability
class
Note(s):
See appended table 1.5.1 for details.
5.1.8.1
TABLE: touch current measurement
Condition
5.2
L → terminal A
(mA)
N/A
N → terminal A
(mA)
Limit
(mA)
Comments
TABLE: electric strength tests and impulse tests
Test voltage applied between:
N/A
Test voltage (V)
Breakdown
Note(s):
5.3
No.
TABLE: fault condition tests
P
ambient temperature (°C) ................................... :
See below.

model/type of power supply ................................. :
See appended table 1.5.1.

manufacturer of power supply ............................ :
See appended table 1.5.1.

rated markings of power supply .......................... :
See appended table 1.5.1.

component
No.
fault
TRF No.:IECEN60950_1B
test voltage test time
(Vdc)
fuse
No.
fuse current
(A)
result
TRF originator: SGS Fimko
Page 45 of 62
Report No.:
11016241 001
Test with Main board P/N: MS-1351
1
Ventilation
openings
blocked
20Vdc
2.4 hrs
--
--
No damaged, No hazards.
Measured maximum temp.
for PWB near
CPU(U23)=54°C, Room
Ambient=22.3°C
2
DC Fan
locked
20Vdc
1.45 hrs
--
--
No damaged, No hazards.
Measured maximum temp.
for PWB near
CPU(U23)=59.2°C, Room
Ambient=22.3°C
3
R156 of
short
RTC battery
type CR1220
20Vdc
10mins
--
--
No damaged, no hazards.
Abnormal reverse current:
0mA. Not exceed the max.
of abnormal charging
current 5.0mA.
4
D23 (Pin YZ) of RTC
battery type
CR1220
20Vdc
10mins
--
--
No damaged, no hazards.
Abnormal reverse current:
3.14mA. Not exceed the
max. of abnormal charging
current 5.0mA.
short
Test with Main board P/N: MS-1352
1
Ventilation
openings
blocked
20Vdc
1.3 hrs
--
--
No damaged, No hazards.
Measured maximum temp.
for PWB near
(U2)=50.1°C, Room
Ambient=22.2°C
2
DC Fan
locked
20Vdc
2.45 hrs
--
--
No damaged, No hazards.
Measured maximum temp.
for PWB near CPU
(U6)=78.3°C, Room
Ambient=22.3°C
3
R17 of RTC
battery type
CR1220
short
20Vdc
10mins
--
--
No damaged, no hazards.
Abnormal reverse current:
0mA. Not exceed the max.
of abnormal charging
current 5.0mA.
4
D1 (Pin Y-Z) short
of RTC
battery type
CR1220
20Vdc
10mins
--
--
No damaged, no hazards.
Abnormal reverse current:
3.02mA. Not exceed the
max. of abnormal charging
current 5.0mA.
Note(s):
TRF No.:IECEN60950_1B
TRF originator: SGS Fimko
Page 46 of 62
Report No.:
11016241 001
National Differences
Clause
Result – Remark
Requirement − Test
APPENDIX Australian National Differences according to CB Bulletin No. 112A, December
2006 (AS/NZS 60950.1:2003)
Verdict
P
(IEC Publication 60950-1:2001)
EXPLANATION FOR ABBREVIATIONS
P=Pass, F=Fail, N/A=Not applicable. Placed in the column to the right.
Annex ZZ Variations
1.2
Between the definitions for "Person, service" and
"Range, rated frequency" insert the following:
Class III equipment.
N/A
After the definition of 1.2.12.15, add the following: Class III equipment.
N/A
Potential ignition source
1.2.12.15
1.2.12.201
1.2.12.201 Potential ignition source:
Possible fault which can start a fire if the opencircuit voltage measured across an interruption or
faulty contact exceeds a value of 50 V (peak) a.c.
or d.c. and the product of the peak value of this
voltage and the measured r.m.s. current under
normal operating conditions exceeds 15 VA.
Such a faulty contact or interruption in an
electrical connection includes those which may
occur in conductive patterns on printed boards.
NOTE 201: An electronic protection circuit may be
used to prevent such a fault from becoming a
potential ignition source.
NOTE 202: This definition is from AS/NZS
60065:2003.
1.5.1
Add the following to the end of first paragraph:
Added.
P
Add the following to the end of first and third dash Added.
items:
P
"or the relevant Australian/New Zealand
Standard."
1.5.2
"or the relevant Australian/New Zealand
Standard."
2.1
Delete the Note.
Deleted.
N/A
3.2.3
Delete Note 2.
Deleted.
N/A
3.2.5
Modify Table 3B as follows:
Modified.
N/A
Rated current of
equipment A
Over 0.2 up to
and including 3
Nominal
crosssectional
2
area mm
1)
0.5
AWG or kcmil
(cross-sectional
2
area in mm )
see note 2
18 [0.8]
Australian National Differences according to CB Bulletin No. 112A, December 2006
Page 47 of 62
Report No.:
11016241 001
National Differences
Clause
Result – Remark
Requirement − Test
Over 3 up to and
including 7.5
0.75
Over 7.5 up to
and including 10
(0.75) 1.00
Over 10 up to
and including 16
(1.0) 1.5
Verdict
16 [1.3]
2)
16 [1.3]
3)
14 [2]
Replace footnote 1) with the following:
1)
This nominal cross-sectional area is only
allowed for Class II appliances if the length of the
power supply cord, measured between the point
where the cord, or cord guard, enters the
appliances, and the entry to the plug does not
exceed 2 m (0.5 mm² three-core supply flexible
cords are not permitted; see AS/NZS 3191).
Delete Note 1.
4.3.6
Replace paragraph three with:
Replaced.
N/A
Equipment with a plug portion, suitable for
insertion into a 10 A 3-pin flat-pin socket-outlet
complying with AS/NZS 3112, shall comply with
the requirements in AS/NZS 3112 for equipment
with integral pins for insertion into socket-outlets.
4.3.13.5
Add the following to the end of the first paragraph: Complied.
P
", or AS/NZS 2211.1"
4.7
Add the following paragraph:
See below.
N/A
Add the following after clause 4.7.3.6:
Added.
N/A
4.7.201 Resistance to fire - Alternative tests
However, equipment under
test and materials used in
compliance with requirements
of IEC 60950-1. Alternative
test methods were not
considered.
General
Same as above.
For alternative tests refer to clause 4.7.201.
4.7.201
4.7.201.1
Parts of non-metallic material shall be resistant to
ignition and spread of fire.
This requirement does not apply to decorative
trims, knobs and other parts unlikely to be ignited
or to propagate flames originating from inside the
apparatus, or the following:
Components that are contained in an enclosure
having a flammability category of FV-0
according to AS/NSZ 4695.707 and having
openings only for the connecting wires filling
the openings completely, and for the
ventilation not exceeding 1 mm in width
Australian National Differences according to CB Bulletin No. 112A, December 2006
N/A
Page 48 of 62
Report No.:
11016241 001
National Differences
Clause
Requirement − Test
Result – Remark
Verdict
Same as above.
N/A
Same as above.
N/A
regardless of the length.
The following parts which would contribute
negligible fuel to a fire:
small mechanical parts, the mass of which does
not exceed 4 g, such as mounting parts,
gears, cams, belts and bearings;
small electrical components, such as capacitors
3
with a volume not exceeding 1750 mm ,
integrated circuits, transistors and optocoupler
packages, if these components are mounted
on material flammability category FV-1 or
better according to AS/NZS 4695.707
NOTE - In considering how to minimize
propagation of fire and what “small parts” are,
account should be taken of the cumulative effect
of small parts adjacent to each other for the
possible effect of propagating fire from one part to
another.
Compliance is checked by tests of 4.7.201.2,
4.7.201.3, 4.7.201.4 and 4.7.201.5.
For the base materials of printed boards,
compliance is checked by the test of 4.7.201.5.
The tests shall be carried out on parts of nonmetallic material, which have been removed from
the apparatus. When the glow-wire test is carried
out, the parts shall be placed in the same
orientation, as they would be in normal use.
These tests are not carried out on internal wiring.
4.7.201.2
Parts of non-metallic material are subjected to
glow wire test of AS/NZS 4695.2.11, which is
carried out at 550 °C.
Parts for which the glow-wire test cannot be
carried out, such as those made of soft or foamy
material, shall meet the requirements specified in
ISO 9772 for category FH-3 material. The glowwire test shall be not carried out on parts of
materials classified at least FH-3 according to
ISO 9772 provided that the sample was not
thicker than the relevant part.
4.7.201.3
Testing of insulating materials
Parts of insulating materials supporting potential
ignition sources shall be subject to the glow-wire
test of AN/NZS 4695.2.11, which is carried out at
750 °C.
The test shall be also carried out on other parts of
insulating material which are within a distance of
3 mm of the connection.
NOTE - Contacts in components such as switch
Australian National Differences according to CB Bulletin No. 112A, December 2006
Page 49 of 62
Report No.:
11016241 001
National Differences
Clause
Requirement − Test
Result – Remark
contacts are considered to be connections.
For parts, which withstand the glow-wire test but
produce a flame, other parts above the
connection within the envelope of a vertical
cylinder having a diameter of 20 mm and a height
of 50 mm shall be subjected to the needle-flame
test. However, parts shielded by a barrier which
meets the needle-flame test shall not be tested.
The needle-flame test shall be made in
accordance with AS/NZS 4695.2.2 with the
following modifications:
5 Severities
Replace with:
The duration of application of the test flame shall
be 30 s ± 1 s.
8 Test procedure
8.2 Modification:
Replace the first sentence with:
The specimen shall be arranged so that the flame
can be applied to a vertical or horizontal edge as
shown in the examples of figure 1.
8.4 Modification:
The first paragraph does not apply.
Addition:
If possible, the flame shall be applied at least
10 mm from a corner.
8.5 Replacement:
The test shall be made on one specimen. If the
specimen does not withstand the test, the test
may be repeated on two further specimens, both
of which shall then withstand the test.
10 Evaluation of test results
Replace with:
The duration of burning (tb) shall not exceed 30 s.
However, for printed circuit boards, it shall not
exceed 15 s.
The needle-flame test shall not be carried out on
parts of material classified as V-0 or V-1
according to IEC 60695-11-10, provided that the
sample tested was not thicker than the relevant
part.
Australian National Differences according to CB Bulletin No. 112A, December 2006
Verdict
Page 50 of 62
Report No.:
11016241 001
National Differences
Clause
Requirement − Test
Result – Remark
4.7.201.4
Testing in the event of non-extinguishing material Same as above.
Verdict
N/A
If parts, other than enclosures, do not withstand
the glow-wire tests of 4.7.201.3, by failure to
extinguish within 30 s after the removal of the
glow-wire tip, the needle-flame test detailed in
4.7.201.3 is made on all parts of non-metallic
material which are within a distance of 50 mm or
which are likely to be impinged upon by flame
during the tests of 4.7.201.3. Parts shielded by a
separate barrier which meets the needle-flame
test need not to be tested.
NOTE 1 - If the enclosure does not withstand the
glow-wire test the equipment is considered to
have failed to meet the requirement of clause
4.7.201 without the need for consequential
testing.
NOTE 2 - If other parts do not withstand the glowwire test due to ignition of the tissue paper and if
this indicates that burring or glowing particles can
fall onto an external surface underneath the
equipment, the equipment is considered to have
failed to meet the requirement of clause 4.7.201
without the need for consequential testing.
NOTE 3 - Parts likely to be impinged upon by the
flame are considered to be those within the
envelope of a vertical cylinder having a radius of
10 mm and a height equal to the height of the
flame, positioned above the point of the material
supporting in contact with or in close proximity to
connections.
4.7.201.5
Testing of printed boards
Same as above.
The base material of printed boards is subjected
to needle-flame test to Clause 4.7.201.3. The
flame is applied to the edge of the board where
the heat sink effect is lowest when the board is
positioned as in normal use. The flame shall not
be applied to an edge, consisting of broken
perforations, unless the edge is less than 3 mm
for a potential ignition source.
The test is not carried out if the –
Printed board does not carry any potential ignition
source;
Base material of printed boards, on which the
available apparent power at a connection
exceeds 15 VA operating at a voltage
exceeding 50 V and equal or less than 400 V
(peak) a.c. or d.c. under normal operating
conditions, is of flammability category FV-1 or
better according to AS/NZS 4695.707, or the
printed boards are protected by an enclosure
Australian National Differences according to CB Bulletin No. 112A, December 2006
N/A
Page 51 of 62
Report No.:
11016241 001
National Differences
Clause
Requirement − Test
Result – Remark
Verdict
meeting the flammability category FV-0
according to AS/NZS 4695.707, or made of
metal, having openings only for connecting
wires which fill the opening completely, or
Base material of printed boards, on which the
available apparatus power at a connection
exceeds 15 VA operating at a voltage
exceeding 400 V (peak) a.c. or d.c. under
normal operating conditions, and base material
printed boards supporting spark gaps which
provide protection against overvoltages, is of
flammability category FV-0 according to
AS/NSZ 4695.707 or the printed boards are
contained in a metal enclosure, having
openings only for connecting wires fill the
openings completely.
Compliance is determined using the smallest
thickness of the material.
NOTE - Available apparent power is the
maximum apparent power, which can be drawn
from the supplying circuit through a resistive load
whose value is chosen to maximise the apparent
power for more than 2 min when the circuit
supplied is disconnected.
6.2.2
Add the following after the first paragraph:
In Australia (this variation does not apply in New
Zealand), compliance with 6.2.2 is checked by the
tests of both 6.2.2.1 and 6.2.2.2.
See sub-clauses 6.2.2.1 and
6.2.2.2.
P
See IEC 60950-1 test report.
P
Delete the note.
6.2.2.1
Delete Note 2.
Add the following after the first paragraph:
In Australia (this variation does not apply in New
Zealand), the electrical separation is subjected to
10 impulses of alternating polarity, using the
impulse test generator of annex N for 10/700 µs
impulses. The interval between successive
impulses is 60 s and the initial voltage, Uc, is:
- for 6.2.1 a):
7.0 kV for hand-held telephones and for
headsets and 2.5 kV for other equipment; and
- for 6.2.1b) and 6.2.1c):
1.5 kV.
NOTE 201 - The 7 kV impulse simulates lightning
surges on typical rural and semi-rural network
lines.
NOTE 202 – The 2.5 kV impulse for 6.2.1a) was
chosen to ensure adequacy of the insulation
Australian National Differences according to CB Bulletin No. 112A, December 2006
Page 52 of 62
Report No.:
11016241 001
National Differences
Clause
Result – Remark
Requirement − Test
Verdict
concerned and does not necessarily simulate
likely overvoltages.
6.2.2.2
Delete the note.
See IEC 60950-1 test report.
P
Add the following after the second paragraph:
In Australia (this variation does not apply in New
Zealand), the a.c. test voltage is:
- for 6.2.1a):
3 kV; and
- for 6.2.1b) and 6.2.1c):
1.5 kV.
NOTE 201 – Where there are capacitors across
the insulation under test, it is recommended that
d.c. test voltages are used.
NOTE 202 – The 3 kV and 1.5 kV values have
been determined considering the low frequency
induced voltages from the power supply
distribution system.
Annex P
Add the following Normative References to Annex Added.
P:
IEC 60065, Audio, Video and similar electronic
apparatus - Safety requirements
AS/NZS 3112, Approval and test specification Plugs and socket-outlets
AS/NZS 3191, Approval and test specification Electric flexible cords
AS/NZS 4695.707, Fire hazard testing of
electrotechnical products - Methods of test for the
determination of the flammability of solid electrical
insulating materials when exposed to an igniting
source
Australian National Differences according to CB Bulletin No. 112A, December 2006
N/A
Page 53 of 62
Report No.:
11016241 001
National Differences
Clause
Result – Remark
Requirement − Test
APPENDIX Canadian National Differences according to CB Bulletin No. 112A, December
2006 (CAN/CSA C22.2 No. 60950-1/UL60950-1)
Verdict
P
(IEC Publication 60950-1:2001)
EXPLANATION FOR ABBREVIATIONS
P=Pass, F=Fail, N/A=Not applicable. Placed in the column to the right.
Special National Conditions
1.1.1
All equipment is to be designed to allow
installations in accordance with the National
Electrical Code (NEC), ANSI/NFPA 70,the
Canadian Electrical Code (CEC), Part I,
CAN/CSA C22.1, and when applicable, the
National Electrical Safety Code, IEEE C2. Also,
unless marked or otherwise identified, installation
is allowed per the Standard for the Protection of
Electronic Computer/Data-Processing Equipment,
ANSI/NFPA 75.
The equipment is designed to
be installed in accordance with
the National Electrical Code
ABSI/NFPA 70 and the
Canadian Electrical Code, Part
1.
1.4.14
For Pluggable Equipment Type A, the protection
in the installation is assumed to be 20A.
No direct mains connection.
N/A
1.5.5
For lengths exceeding 3.05 m, external
interconnecting flexible cord and cable
assemblies are required to be a suitable cable
type (e.g. DP, CL2) specified in the NEC.
No external interconnecting
cable provided.
N/A
Class III equipment.
N/A
P
For lengths 3.05 m or less, external
interconnecting flexible cord and cable
assemblies that are not types specified in the
NEC are required to have special construction
features and identification markings.
1.7.1
Equipment for use on a.c. mains supply systems
with a neutral and more than one phase
conductor (e.g. 120/240 V, 3-wire) require a
special marking format for electrical ratings.
A voltage rating that exceeds an attachment plug
cap rating is only permitted if it does not exceed
the extreme operating conditions in Table 2 of
CAN/CSA C22.2 No. 235, and if it is part of a
range that extends into the Table 2 “Normal
Operating Conditions.” Likewise, a voltage rating
shall not be lower than the specified “Normal
Operating Conditions,” unless it is part of a range
that extends into the “Normal Operating
Conditions.”
2.5
Where a fuse is used to provide Class 2, Limited No such fuse provided.
Power Source, or TNV current limiting, it shall not
be operator-accessible unless it is not
interchangeable.
Canadian National Differences according to CB Bulletin No. 112A, December 2006
N/A
Page 54 of 62
Report No.:
11016241 001
National Differences
Clause
Requirement − Test
Result – Remark
2.7.1
Suitable NEC/CEC branch circuit protection rated Class III equipment.
at the maximum circuit rating is required for all
standard supply outlets, receptacles and mediumbase or smaller lampholders if the supply branch
circuit protection is not suitable.
Verdict
N/A
Power distribution transformers distributing power
at 100 volts or more, and rated 10 kVA or more,
require transformer overcurrent protection.
3.2
Wiring methods (terminals, leads, etc.) used for
the connection of the equipment to the mains
shall be in accordance with the NEC/CEC.
Class III equipment.
N/A
3.2.1
Power supply cords are required to have
attachment plugs rated not less than 125 percent
of the rated current of the equipment.
No power supply cord
provided.
N/A
3.2.3
Permanent connection of equipment to the mains Class III equipment. No direct
supply by a power supply cord is not permitted,
main connection.
except for certain equipment, such as ATMs.
N/A
3.2.5
Power supply cords are required to be no longer
than 4.5 m in length.
No power supply cord
provided.
N/A
Class III equipment. No direct
mains connection.
N/A
Flexible power supply cords are required to be
compatible with Article 400 of the NEC, and
Tables 11 and 12 of the CEC.
3.2.9
Permanently connected equipment is required to
have a suitable wiring compartment and wire
bending space.
3.3
Wiring terminals and associated spacings for field Class III equipment.
wiring connections shall comply with CSA C22.2
No. 0.
N/A
3.3.3
Wire binding screws are not permitted to attach
conductors larger than 10 AWG (5.3 mm²).
Class III equipment.
N/A
3.3.4
Terminals for permanent wiring, including
Class III equipment.
protective earthing terminals, are required to be
suitable for U.S./Canadian wire gauge sizes, rated
125 percent of the equipment rating, and be
specially marked when specified (1.7.7).
N/A
3.4.2
Motor control devices are required for cordNo motor control devices.
connected equipment with a motor if the
equipment is rated more than 12A, or if the motor
has a nominal voltage rating greater than 120V,
or is rated more than 1/3 hp (locked rotor current
over 43 A)
N/A
3.4.8
Vertically-mounted disconnect switches and
No such switch provided.
circuit breakers are required to have the ”on”
position indicated by the handle in the up position.
N/A
Canadian National Differences according to CB Bulletin No. 112A, December 2006
Page 55 of 62
Report No.:
11016241 001
National Differences
Clause
Requirement − Test
Result – Remark
Verdict
3.4.11
For computer room applications, equipment with
battery systems capable of supplying 750 VA for
five minutes are required to have a battery
disconnect means that may be connected to the
computer room remote power-off circuit.
No battery system
incorporated.
N/A
4.3.12
The maximum quantify of flammable liquid stored No flammable liquid.
in equipment is required to comply with NFPA 30.
4.3.13
Equipment with lasers is required to meet Code of
Federal Regulations 21 CFR 1040 (and the
Canadian Radiation Emitting Devices Act, REDR
C1370).
4.7
For computer room applications, automated
Not information storage
information storage systems with combustible
systems.
media greater than 27 cubic feet are required to
have a provision for connection of either
automatic sprinklers or a gaseous agent
extinguishing system with an extended discharge.
N/A
4.7.3.1
For computer room applications, enclosures with Not information storage
combustible material measuring greater than 0.9 systems.
m² or a single dimension greater than 1.8 m are
required to have a flame spread rating of 50 or
less. For other applications, enclosures with the
same dimensions require a flame spread rating of
200 or less.
N/A
Annex H
Equipment that produces ionizing radiation is
required to comply with the Code of Federal
Regulations, 21 CFR 1020 (and the Canadian
Radiation Emitting Devices Act, REDR C1370).
N/A
Optical radiation in compliance
with requirements of IEC
60825-1 (see corresponding
sections of this test report).
Laser Comply with FDA
No ionizing radiation.
N/A
P
Other differences
1.5.1
Components of equipment must be suitable for
the application, and must comply with the
requirements of the equipment standard and the
applicable national (Canadian and/or U.S.)
component or material standards, as far as they
may apply.
All components identified are
either comply with IEC
standards or relevant
requirements of CSA and UL
component standards.
The acceptance will be based on the following:
1) A component Certified by a Canadian or U.S.
National Certification Body (NCB) to a
Canadian or U.S. component standard will be
checked for correct application and use in
accordance with its specified rating. Where
necessary, it will also be subject to the
applicable tests of the equipment standard.
2) A component, which has a CB Test
Certificate for compliance with a relevant IEC
component standard, will be checked for
correct application and use in accordance
with its specified ratings. Where necessary, it
Canadian National Differences according to CB Bulletin No. 112A, December 2006
P
Page 56 of 62
Report No.:
11016241 001
National Differences
Clause
Requirement − Test
Result – Remark
Verdict
will also be subject to the applicable tests of
the equipment standard, and to the applicable
tests of the Canadian and/or U.S. component
or material standard, under the conditions
occurring in the equipment.
3) A component, which has no approval as in A)
or B) above or which is used not in
accordance with its specified ratings, will be
subject to the applicable tests of the
equipment standard, and to the applicable
tests of the Canadian and/or U.S. component
or material standard, under the conditions
occurring in the equipment.
4) Some components may require annual retesting, which may be carried out by the
manufacturer, CSA International or another
laboratory
2.3.1
For TNV-2 and TNV-3 circuits with other than
ringing signals and with voltages exceeding
42.4 Vpeak or 60 Vd.c., the maximum acceptable
current through a 2000 ohm resistor (or greater)
connected across the voltage source with other
loads disconnected is 7.1 mA peak or 30 mAd.c.
under normal operating conditions.
2.3.2
In the event of a single fault, the limits of 2.2.3
Complied.
apply to SELV Circuits and accessible conductive
parts.
2.6.3.3
When subject to impedance testing, protective
Class III equipment.
earthing and bonding are required to be subjected
to the additional test conditions specified.
N/A
3.2.1.2
Equipment connected to a centralized d.c. power No direct mains connection.
system, and having one pole of the DC mains
input terminal connected to the main protective
earthing terminal in the equipment, is required to
comply with special earthing, writing, marking and
installation instruction requirements.
N/A
4.2.8.1
Enclosures around CRTs with a face diameter of No CRT.
160mm or more are required to reduce the risk of
injury due to the implosion of the CRT.
N/A
4.3.2
Equipment with handles is required to comply with No handles.
special loading tests.
N/A
5.1.8.3
Equipment intended to receive telecommunication
ringing signals is required to comply with a special
touch current measurement tests.
N/A
6.2.1
Enamel coating on winding wire not considered
electrical separation unless subjected to special
investigation.
N/A
No used.
Canadian National Differences according to CB Bulletin No. 112A, December 2006
P
N/A
Page 57 of 62
Report No.:
11016241 001
National Differences
Clause
Requirement − Test
Result – Remark
6.4
Equipment intended for connection to
telecommunication network outside plant cable is
required to be protected against overvoltage from
power line crosses in accordance with 6.4 and
Annex NAC.
N/A
6.5
Equipment connected to a telecommunications
network and supplied with an earphone intended
to be held against, or in the ear is required to
comply with special acoustic pressure tests.
N/A
M.2
Continuous ringing signals up to 16 mA only are
permitted if the equipment is subjected to special
installation and performance restrictions.
N/A
Canadian National Differences according to CB Bulletin No. 112A, December 2006
Verdict
Page 58 of 62
Report No.:
11016241 001
National Differences
Clause
Requirement − Test
Result – Remark
APPENDIX Korean National Differences according to CB Bulletin No. 112A, December 2006
(K60950)
Verdict
P
(IEC Publication 60950-1:2001)
EXPLANATION FOR ABBREVIATIONS
P=Pass, F=Fail, N/A=Not applicable. Placed in the column to the right.
1.5.101
Addition:
No power cord provided.
N/A
The CISPR requirements have
to be considered during
national approval.
N/A
Plugs for the connection of the apparatus to the
supply mains shall comply with the Korean
requirement (KSC 8305).
7
Addition: EMC
The apparatus shall comply with the relevant
CISPR standards.
Korean National Differences according to CB Bulletin No. 112A, December 2006
Page 59 of 62
Report No.:
11016241 001
National Differences
Clause
Result – Remark
Requirement − Test
APPENDIX US National Differences according to CB Bulletin No. 112A, December 2006
(UL 60950-1)
Verdict
P
(IEC Publication 60950-1:2001)
EXPLANATION FOR ABBREVIATIONS
P=Pass, F=Fail, N/A=Not applicable. Placed in the column to the right.
Special National Conditions
1.1.1
All equipment is to be designed to allow
installations in accordance with the National
Electrical Code (NEC), ANSI/NFPA 70,the
Canadian Electrical Code (CEC), Part I,
CAN/CSA C22.1, and when applicable, the
National Electrical Safety Code, IEEE C2. Also,
unless marked or otherwise identified, installation
is allowed per the Standard for the Protection of
Electronic Computer/Data-Processing Equipment,
ANSI/NFPA 75.
The equipment is designed to
be installed in accordance with
the National Electrical Code
ABSI/NFPA 70 and the
Canadian Electrical Code, Part
1.
1.4.14
For Pluggable Equipment Type A, the protection
in the installation is assumed to be 20A.
No direct mains connection.
N/A
1.5.5
For lengths exceeding 3.05 m, external
interconnecting flexible cord and cable
assemblies are required to be a suitable cable
type (e.g. DP, CL2) specified in the NEC.
No external interconnecting
cable provided.
N/A
Class III equipment.
N/A
P
For lengths 3.05 m or less, external
interconnecting flexible cord and cable
assemblies that are not types specified in the
NEC are required to have special construction
features and identification markings.
1.7.1
Equipment for use on a.c. mains supply systems
with a neutral and more than one phase
conductor (e.g. 120/240 V, 3-wire) require a
special marking format for electrical ratings.
A voltage rating that exceeds an attachment plug
cap rating is only permitted if it does not exceed
the extreme operating conditions in Table 2 of
CAN/CSA C22.2 No. 235, and if it is part of a
range that extends into the Table 2 “Normal
Operating Conditions.” Likewise, a voltage rating
shall not be lower than the specified “Normal
Operating Conditions,” unless it is part of a range
that extends into the “Normal Operating
Conditions.”
2.5
Where a fuse is used to provide Class 2, Limited No such fuse provided.
Power Source, or TNV current limiting, it shall not
be operator-accessible unless it is not
interchangeable.
N/A
2.7.1
Suitable NEC/CEC branch circuit protection rated Class III equipment.
at the maximum circuit rating is required for all
standard supply outlets, receptacles and medium-
N/A
US National Differences according to CB Bulletin No. 112A, December 2006
Page 60 of 62
Report No.:
11016241 001
National Differences
Clause
Requirement − Test
Result – Remark
Verdict
base or smaller lampholders if the supply branch
circuit protection is not suitable.
Power distribution transformers distributing power
at 100 volts or more, and rated 10 kVA or more,
require transformer overcurrent protection.
3.2
Wiring methods (terminals, leads, etc.) used for
the connection of the equipment to the mains
shall be in accordance with the NEC/CEC.
Class III equipment.
N/A
3.2.1
Power supply cords are required to have
attachment plugs rated not less than 125 percent
of the rated current of the equipment.
No power supply cord
provided.
N/A
3.2.3
Permanent connection of equipment to the mains Class III equipment. No direct
supply by a power supply cord is not permitted,
mains connection.
except for certain equipment, such as ATMs.
N/A
3.2.5
Power supply cords are required to be no longer
than 4.5 m in length.
No power supply cord
provided.
N/A
Class III equipment. No direct
mains connection.
N/A
Flexible power supply cords are required to be
compatible with Article 400 of the NEC, and
Tables 11 and 12 of the CEC.
3.2.9
Permanently connected equipment is required to
have a suitable wiring compartment and wire
bending space.
3.3
Wiring terminals and associated spacings for field Class III equipment.
wiring connections shall comply with CSA C22.2
No. 0.
N/A
3.3.3
Wire binding screws are not permitted to attach
conductors larger than 10 AWG (5.3 mm²).
Class III equipment.
N/A
3.3.4
Terminals for permanent wiring, including
Class III equipment.
protective earthing terminals, are required to be
suitable for U.S./Canadian wire gauge sizes, rated
125 percent of the equipment rating, and be
specially marked when specified (1.7.7).
N/A
3.4.2
Motor control devices are required for cordNo motor control device.
connected equipment with a motor if the
equipment is rated more than 12A, or if the motor
has a nominal voltage rating greater than 120V,
or is rated more than 1/3 hp (locked rotor current
over 43 A)
N/A
3.4.8
Vertically-mounted disconnect switches and
No such switch provided.
circuit breakers are required to have the ”on”
position indicated by the handle in the up position.
N/A
3.4.11
For computer room applications, equipment with
battery systems capable of supplying 750 VA for
five minutes are required to have a battery
disconnect means that may be connected to the
computer room remote power-off circuit.
No battery system
incorporated.
US National Differences according to CB Bulletin No. 112A, December 2006
N/A
Page 61 of 62
Report No.:
11016241 001
National Differences
Clause
Requirement − Test
Result – Remark
4.3.12
The maximum quantify of flammable liquid stored No flammable liquid.
in equipment is required to comply with NFPA 30.
4.3.13
Equipment with lasers is required to meet Code of
Federal Regulations 21 CFR 1040 (and the
Canadian Radiation Emitting Devices Act, REDR
C1370).
4.7
For computer room applications, automated
Not information storage
information storage systems with combustible
systems.
media greater than 27 cubic feet are required to
have a provision for connection of either
automatic sprinklers or a gaseous agent
extinguishing system with an extended discharge.
N/A
4.7.3.1
For computer room applications, enclosures with Not information storage
combustible material measuring greater than 0.9 systems.
m² or a single dimension greater than 1.8 m are
required to have a flame spread rating of 50 or
less. For other applications, enclosures with the
same dimensions require a flame spread rating of
200 or less.
N/A
Annex H
Equipment that produces ionizing radiation is
required to comply with the Code of Federal
Regulations, 21 CFR 1020 (and the Canadian
Radiation Emitting Devices Act, REDR C1370).
N/A
Optical radiation in compliance
with requirements of IEC
60825-1 (see corresponding
sections of this test report).
Laser Comply with FDA
No ionizing radiation.
Verdict
N/A
P
Other differences
1.5.1
Some components and materials associated with All components identified are
the risk of fire, electric shock, or personal injury
either comply with IEC
are required to have component or material
standards or relevant
ratings in accordance with the applicable national requirements of CSA and UL
(U.S. and Canadian) component or material
component standards.
requirements. These components include:
attachment plugs, battery packs (rechargeable
type, used with transportable equipment), cathode
ray tubes, circuit breakers, communication circuit
accessories, connectors (used for current
interruption of non-LPS circuits), cord sets and
power supply cords, direct plug-in equipment,
enclosures (outdoor), flexible cords and cables,
fuses (branch circuit), fuseholders, ground-fault
current interrupters, industrial control equipment,
insulating tape, interconnecting cables,
lampholders, limit controls, printed wiring,
protectors for communications circuits,
receptacles, solid state controls, supplementary
protectors, surge suppressors, switches
(including interlock switches), thermal cut-offs,
thermostats, multi-layer transformer winding wire,
tubing, wire connectors, and wire and cables.
US National Differences according to CB Bulletin No. 112A, December 2006
P
Page 62 of 62
Report No.:
11016241 001
National Differences
Clause
Requirement − Test
Result – Remark
2.3.1
TNV-3 circuits without other
For TNV-2 and TNV-3 circuits with other than
than ring signals.
ringing signals and with voltages exceeding
42.4 Vpeak or 60 Vd.c., the maximum acceptable
current through a 2000 ohm resistor (or greater)
connected across the voltage source with other
loads disconnected is 7.1 mA peak or 30 mA d.c.
under normal operating conditions.
2.3.2
In the event of a single fault, the limits of 2.2.3
Complied.
apply to SELV Circuits and accessible conductive
parts.
2.6.3.3
When subject to impedance testing, protective
Class III equipment.
earthing and bonding are required to be subjected
to the additional test conditions specified.
N/A
3.2.1.2
Equipment connected to a centralized d.c. power No direct mains connection.
system, and having one pole of the DC mains
input terminal connected to the main protective
earthing terminal in the equipment, is required to
comply with special earthing, writing, marking and
installation instruction requirements.
N/A
4.2.8.1
Enclosures around CRTs with a face diameter of No CRT.
160mm or more are required to reduce the risk of
injury due to the implosion of the CRT.
N/A
4.3.2
Equipment with handles is required to comply with No handles.
special loading tests.
N/A
5.1.8.3
Equipment intended to receive telecommunication
ringing signals is required to comply with a special
touch current measurement tests.
N/A
6.2.1
Enamel coating on winding wire not considered
electrical separation unless subjected to special
investigation.
6.4
Equipment intended for connection to
telecommunication network outside plant cable is
required to be protected against overvoltage from
power line crosses in accordance with 6.4 and
Annex NAC.
N/A
6.5
Equipment connected to a telecommunications
network and supplied with an earphone intended
to be held against, or in the ear is required to
comply with special acoustic pressure tests.
N/A
M.2
Continuous ringing signals up to 16 mA only are
permitted if the equipment is subjected to special
installation and performance restrictions.
N/A
No used.
US National Differences according to CB Bulletin No. 112A, December 2006
Verdict
N/A
P
N/A
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertisement