Bulletin B-33
Series 3000 Photohelic® Pressure Switch/Gage
Specifications - Installation and Operating Instructions
2-1/2 [63.50]
1/8 FEMALE NPT HIGH
2-1/16 [52.39]
PRESSURE CONNECTION
2 [50.80]
1/8 FEMALE NPT LOW
PRESSURE CONNECTION
Ø4-3/4
[120.65]
3-7/8 SQ
[98.43]
3/4 CONDUIT
CONNECTION
1-1/4
[31.75]
(4) 6-32 HOLES
EQUALLY SPACED ON
A 5-1/8 [130.18] B.C.
Ø4-47/64
[120.25] Ø5
[127.00]
3-7/8 [98.43]
5-1/8 [130.18]
6-3/8 [161.93]
4-3/8 [111.13]
(7-5/8 [193.68])
HOUSING REMOVAL
5/8 [15.88]
5/8 [15.88] PANEL
MAX
3/16 [4.76]
Ø4 [101.60]
FACE
5-1/2 [139.70]
O.D.
MOUNTING
RING
*Patent No. 3,862,416
The Photohelic® Switch/Gage is a very versatile, precise
pressure switch combined with the time-proven
Magnehelic® pressure gage. Models are available with one
or two phototransistor actuated relays. Gage reading is
unaffected by switch operation. Easy to adjust set points
have knob controls. Applied pressure and switch set points
are fully visible at all times. Deadband is one pointer width less than 1% of full scale. Double-pole double-throw relays
can be easily interlocked to provide variable deadband control. For positive, negative or differential pressure only on
3600S models. Full scale ranges available from 0-.25 in w.c.
to 0-6000 psig.
PHOTOHELIC® SENSING - HOW IT WORKS
In a typical control application, the Photohelic® switch/gage
controls between high and low pressure set points. When
pressure changes, reaching either set point pressure, the
beam from an LED to the limiting phototransistor will be cut
off by the helix-driven light shield. The resulting signal
change is electronically amplified to actuate its DPDT slave
relay and switching occurs. Dead band between make and
break is 1% of full scale or less - just enough to assure positive, chatter-free operation.
DWYER INSTRUMENTS, INC.
P.O. BOX 373 • MICHIGAN CITY, INDIANA 46361, U.S.A.
SPECIFICATIONS
GAGE SPECIFICATIONS
Service: Air and non-combustible, compatible gases.
Wetted Materials: Consult Factory.
Accuracy: Photohelic®, ±2% of full scale at 70°F (21.1°C). ±3%
on -0 and ±4% on -00 models.
Pressure Limits: Photohelic® -20" Hg. to 25 psig (-0.677 to
1.72 bar). MP option; 35 psig (2.41 bar), HP option; 80 psig
(5.52 bar). 36003S – 36010S; 150 psig (10.34 bar). 36020S and
higher; 1.2 x full scale pressure.
Temperature Limits: 20 to 120°F.
(-6.67 to 48.9°C) Low temperature option available.
Process Connections: Photohelic®, 1/8˝ female NPT.
Size: Photohelic®, 4˝ (101.6 mm) dial face, 5˝ (127 mm) O.D. x 81/4˝ (209.55 mm).
Weight: Photohelic®, 4 lbs. (1.81 kg).
SWITCH SPECIFICATIONS
Switch Type: Each setpoint has 2 Form C relays (DPDT).
Repeatability: ±1% of full scale.
Electrical Rating: Photohelic®, 10A @ 28 VDC, 10A @ 120,
240 VAC.
Electrical Connections: Screw Terminals.
Power Requirements: 120 VAC, 50/60 Hz; 240 VAC & 24 VAC
Power optional.
Mounting Orientation: Diaphragm in vertical position. Consult
factory for other position orientations.
Set Point Adjustment: Adjustable knobs on face.
Agency Approvals: Photohelic® UL, CSA, CE.
Phone: 219/879-8000
Fax: 219/872-9052
www.dwyer-inst.com
e-mail: [email protected]
B-33
7/3/03
3:53 PM
Page 2
Bulletin B-33
page 2
INSTALLATION
1. Location
All parts of the Dwyer Photohelic® pressure switch/gage are
ruggedly constructed and will stand a moderate amount of
vibration, physical shock, and handling. Normal care in handling and installation is all that is required. In cases where
instrument panel vibration is severe, the panel should be a
spring mounted or the amplifier-relay unit mounted remotely on a more stable surface.
Select a location where the ambient temperature will not
exceed 120°F. Pneumatic pressure sensing lines may be run
any necessary distance. For example, 250 foot sensing lines
will not affect accuracy but will damp the reading slightly. Do
not restrict lines. If pulsating pressure or vibration causes
excessive pointer oscillation or relay chatter, consult factory
for additional damping means.
3. Mounting
The Photohelic® is normally mounted before making electrical connections, as the electrical enclosure is independent
of the mounting means and may be removed at any time.
Panel Mounting
Normal mounting is flush or through panel is shown in Fig.
2. Be sure to allow 4-3/8˝ extra space behind the unit for
electrical enclosure removal. Make a single 4-13/16˝ diameter hole in the panel. Insert the entire Photohelic® unit from
the front, then slip on the mounting ring and snap ring from
the rear. Seat the snap ring in its groove, back up the
mounting ring against snap ring and tighten the four (4) 2˝
No. 6-32 clamp screws provided. If behind panel space is
critical, the amplifier-relay unit can be mounted remotely.
See the Remote-Relay Mounting Instructions for details.
2. Position
The Photohelic® may be mounted as an integral package or
the amplifier-load relay assembly and housing may be
mounted remotely from the indicating gage-phototransistor
unit. Extension cords with 7 pin plugs and receptacles are
available from Dwyer for interconnection of the two units.
The unit may be mounted in any desired position, scale vertical or horizontal, without affecting its accuracy, but must
be rezeroed if position is changed from horizontal to vertical
or vice versa. The -0 and -00 models must be mounted with
the scale vertical.
Through Panel Mounting
SNAP RING GROOVE
4-13/16˝ (122 mm)
DIA. HOLE REQUIRED
FOR PANEL MOUNTING
1/8˝ MALE NPT PRESSURE CONNECTIONS.
SINGLE HIGH PRESSURE CONNECTION
FOR SERIES 36000A MODELS.
Fig. 2
B-33
7/3/03
3:53 PM
Page 3
Bulletin B-33
page 3
Gage Mounting with Relays Remote
Where it is desirable to mount the amplifier-relay unit separate from the gage-phototransistor unit, the gage may be
mounted either as shown in Fig. 2 (except less amplifierrelay portion) or surface mounted as shown in Fig. 3A. Use
the layout shown in Fig. 3B to locate holes. The complete
package cannot be surface mounted.
Remote Amplifier-Relay Unit
Surface Mounting
Fig. 4A
Hole Layout
Ø3/16
TYP 4 PLACES
Fig. 3A
4-9/32
[108.74]
Hole Layout (Front)
THREE 3/16 DIA.
HOLES AT 120°
SURFACE MTG.
3/4 DIA. HOLE
FOR WIRE CONN.
4-9/32
[108.74]
5
[127.00] SQ
Fig. 4B
1-1/8
[28.58]
1-1/8
[28.58]
Fig. 3B
Remote Relays Mounting
The amplifier - relay unit may be mounted remotely as
shown in Fig. 4A. Use the hole layout as shown in Fig. 4B
for this option.
Additional mounting information for special requirements is
available from the factory.
4. Pneumatic Connections & Zeroing
After installation but before making pressure connections,
set the indicating pointer exactly on the zero mark, using the
zero adjust screw located at the bottom of the front cover.
Note that this adjustment can only be made with the high
and low pressure taps both open to atmosphere.
Connect the high and low pressure taps to positive, negative, or differential pressure sensing points. Use 1/4˝ diameter metal or other instrument tubing and 1/8˝ NPT adaptors
at the Dwyer Photohelic® pressure switch gage. Adaptors
for rubber or soft plastic tubing are furnished with the instrument for use where this type of connection is preferred.
If the Photohelic® is not used to sense differential pressure,
one of the pressure taps must be left open to atmosphere.
This will allow the reference pressure to enter. In this case,
installation of a Dwyer No. A-331 Filter Plug or similar fitting
in the reference pressure tap is recommended to reduce the
possibility of dust entering the instrument.
NOTE: If the Photohelic® switch/gage is over pressured,
pointer may ‘jump” from full scale back to zero and remain
there until the excess pressure condition is relieved. Users
should be aware of possible false zero pressure indications
under this conditions.
B-33
7/3/03
3:53 PM
Page 4
Bulletin B-33
page 4
Terminal Board
ELECTRICAL CONNECTIONS
1. Cover
The amplifier-relay unit has an easy to remove housing.
Remove the three (3) screws as shown in Fig. 5 and slide
the housing off. Make all the electrical connections before
reinstalling and refastening the housing.
SECTION B
SECTION C
SECTION A
SECTION D
2. Conduit
Electrical access to the connection box portion of the relay
housing is by bottom opening for 3/4˝ conduit. Use of flexible conduit is recommended. It should be supported from
the panel or other suitable surface to prevent the wiring system from exerting undue strain on the instrument. See Fig.
5.
Mounting Details
SECTION E
CAUTION: Do not apply electrical
current to terminals in sections B and C.
COVER MOUNTING SCREWS
Fig. 6
4-3/8 [111.13]
COVER PULL
OUT
FLEXIBLE CONDUIT
SUPPORT CONDUIT
FROM PANEL
Fig. 5
3. Terminal or Connection Board Layout
In Fig. 6,”Terminal Board”, Section A contains the connections for the load or slave relay actuated by the high or right
set-point. This relay is a double pole, double throw type. The
two top connections are normally closed, the two middle
connections are normally open, and the bottom connections are the common pair. The relay is in its normal or DeEnergized position when pressure is below the right hand
set-point.
Section D is exactly the same as Section A except that its
load or slave relay is controlled by the low or left set-point.
The De-Energized position is below the left hand pointer
set-point.
Section B contains the external connections to the holding
coil circuit for the high or right set-point relay and Section
C contains similar connections for the low or left set-point
relay. The function and use of these connections varies
somewhat depending on the circuit style of the instrument.
See paragraphs 5 and 6 for details.
Section E contains the power connections for the control
unit transformer primary. The transformer in turn supplies
reduced voltage power for the LED, phototransistor, amplifier unit, and load relay pull in and holding coils. Connections
must always be made to this section in order to put the unit
in operation. Standard units are designed for 117 VAC input
to the transformer. Special units are also available for other
voltages.
Separate Ground Wire attachment is provided for by a
No. 6-32 screw on the mounting bracket near the conduit
opening. An additional ground wire connection is located on
the side of the gage body for use when the amplifier-relay
unit is mounted remotely.
Single Set-Point instruments are furnished with the right or
high set-point components and circuitry in place. These are
connected to Sections A and B of the terminal board. The
left or low set-point components are omitted.
4. Circuit Style
The Photohelic® is available with several factory installed
optional internal circuits. They are identified as to style by a
label shown in Fig. 7. This label is mounted prominently on
the terminal board of each instrument. The letter H denotes
a circuit in which the relay can be made to latch or remain
energized after pressure increase to its set-point.
Circuit Label
CIRCUIT:
POWER SUPPLY:
CONTACT RATING:
Fig. 7
B-33
7/3/03
3:53 PM
Page 5
Bulletin B-33
page 5
The letter “L” denotes a circuit in which the relay can be
made to latch or remain de-energized after pressure
decrease to its set-point. Two letters are required to fully
identify a dual set-point unit. Thus, circuit style HH, which is
standard, is a dual set-point circuit which has provisions for
latching on pressure increase to either set-point. Single relay
units are identified by the letters “SR” followed by “H” for the
standard unit or “L” for the special low latch unit. Units for
use with other than standard 117 VAC will be so indicated
on the label.
5. Dual Set Point Automatic Reset
Circuit Style HH is used for simple on-off switching applications. To place in service, connect load circuits to the appropriate terminals in Section A (Fig. 6) for the right set-point
and Section D for the left set-point. Note the the N.O. contacts are open when the gage pressure pointer is to the left
of the set-point pointers. No connections are necessary in
Section B and C. Make external ground connections as
required and connect power to Section E for the control
unit. To use circuit style LL for automatic reset, a jumper wire
must be installed between the upper and lower terminals in
sections B and/or C.
6. Dual Set Point Manual Reset
Circuit Style HH may also be used for manual reset applications where it is desired to have maintained contact on
either relay following pressure increase above its set-point.
Load or signal connections are made to the appropriate terminals in Sections A and D (as in paragraph above).
Connect terminals in Sections B and C through normally
closed switches or push buttons as shown in Fig. 8. Use of
“dry-circuit” type switches such as Dwyer Part No. A-601
with paladium, gold, etc. or rotary wiping action type contacts is recommended. Make external ground connections
as required and connect power to Section E for the control
unit.
Circuit style LL is used for manual reset applications which
require that contact be maintained following pressure
decrease below the set-point. Load connections are made
to the appropriate terminals in Sections A and D. A normally open type manual reset switch such as Dwyer Part No. A601 is connected to the terminals in sections B and C. The
circuit must be “armed” by momentarily closing the switch
while the black pointer is to the right of the set-point. From
that point on, the circuit will latch on pressure decrease
below the set-point and remain latched on pressure
increase until manually reset with the optional switch.
Manual Reset with Circuit HH
RESET
RESET
CAUTION: Do not apply electrical
current to terminals in sections B and C.
Fig. 8
7. Dual Set Point Automatic and Manual Reset
Combinations
Circuit style HH may be used with either set-point wired and
operating as in paragraph 5 and other set-point wired and
operating as in paragraph 6.
8. High Low Limit Control - Dual Set-Point
Circuit style HH may be used to control fans, dampers,
pumps, etc. between the set-points of a Photohelic®. To
accomplish this, use one set-point relay to reset the other as
shown in the wiring diagram Fig. 9. In this typical application, the load (for instance a fan) would be connected to the
N.C. contacts of the right set-point relay, Section A (Fig. 6)/
On pressure rise to the right set-point, its relay would pull in
and hold even though pressure might then fall below that
set-point, its relay would automatically be De-Energized,
return to its normal position and in so doing, open the holding coil circuit from Section B (Fig. 6). The right set-point
relay would thus be reset and the cycle could repeat.
9. Dual Set-Point Special Purpose Circuits
Circuit Style LL may be used where manual reset following
maintained contact on pressure decrease to either set-point
is desired. Circuit Styles HL and LH are combination units.
For special combinations of features, special units, and
detailed instructions regarding their use, consult factory.
10. Single Set-Point Photohelic®
The single set-point photohelic® is furnished with the right
set-point only. Terminals in Section A and B (Fig. 6) are connected to this relay. Circuit Style SRH is wired or automatic
reset as in paragraph 5. Manual reset is accomplished by
adding a normally closed reset switch or push button to the
circuit as described in paragraph 6.
11. Single Set-Point Special
Manual reset after actuation on falling pressure can be
obtained by using Circuit Style SRL. Consult the factory for
special units and detailed instructions regarding their use.
12. Placing in Service
In normal operation each relay is de-energized when the
pressure applied to the instrument is below its set-point.
Special low-latching units will ordinarily have to be reset
before placing on the line in normal operation.
B-33
7/3/03
3:53 PM
Page 6
Bulletin B-33
page 6
High-Low Limit Control (Circuit HH)
RESET JUMPERS
MAINTENANCE
Dwyer Photohelic® Switch/Gages are precision instruments,
expertly assembled and calibrated at the factory. They
require no lubrication or periodic servicing. If the interior is
protected from dust, dirt corrosive gases and fluids, years of
trouble-free service may be expected. Zero adjustment
should be checked and reset occasionally to maintain accuracy. Any repairs necessary to either the Dwyer
Magnehelic® pressure gage or the electronic components
should be performed by a trained instrument mechanic. In
most cases, this is best accomplished by returning the
complete Photohelic® Switch/Gage to the Dwyer factory.
1/6 HP*
117 VOLT
LOAD
117 VOLT LINE
*NOTE: For larger motors, use the Photohelic®
in a maintained contact, 117 Volt Control or
Push Button Circuit of the motor starter.
Fig. 9
13. Failure Mode
The Photohelic® circuit design provides certain protection in
the event of a loss of pressure or electrical power. In either
case, both relays will de-energize, returning to their normal
“zero pressure” state. The exceptions to this are models
with center zero ranges. Because the relays on all standard
models are always energized when the indicating (black)
pointer is to the right of their respective set points, the relay
action on loss of pressure will depend on set-point position,
since either of them could be located to the left of zero. As
an example; if the left pointer were set at -2 in. w.c. and
negative pressure was -3 in. w.c., a loss of that pressure
would allow the black pointer to return to the center and
thus cause the low set-point relay to energize.
If the LED should burn out, only the left-lower relay will deenergize. The right-high relay will react as if pressure were
above its set-point and will remain energized even though
pressure might be below that setting. In this situation, only
termination of electrical power will allow the right-high relay
to de-energize.
B-33
7/3/03
3:53 PM
Page 7
Bulletin B-33
page 7
PHOTOHELIC®
PRESSURE SWITCH/GAGE
MODEL AND RANGES
Range,
Model
Inches Minor
Number of Water Div.
3000-00
3000-0
3001
0-.25
0-.50
.005
.01
0-1.0
.02
3002
0-2.0
.05
3003
0-3.0
.10
3004
0-4.0
.10
3005
0-5.0
.10
3006
3008
0-6.0
0-8.0
.20
.20
3010
0-10
.20
3015
0-15
.50
3020
0-20
.50
3025
0-25
.50
3030
0-30
1.0
3040
0-40
1.0
3050
0-50
1.0
3060
0-60
2.0
3080
0-80
2.0
3100
0-100
2.0
3150
0-150
5.0
Model
Number
3300-0
3301
3302
3304
3310
3320
3330
Model
Number
3201
3202
3203
3204
3205
3210
3215
3220
3230
36003S
36006S
36010S
36020S
36030S
36060S
36100S
36300S
36600S
Dual Scale Air Velocity Units
Range,
(for use with pitot tube)
Zero
Range,
Center
Ranges,
Air
Inches Minor
Model
Inches of Velocity
of Water Div.
Number
Water
FPM
.25-0-.25 .01
3000-00AV
0-.25
300-2000
.5-0-.5
.02
.05 3000-0AV
1-0-1
0-50
500-2800
.10
2-0-2
0-1.0
500-4000
.20 3001-AV
5-0-5
.50 3002-AV
10-0-10
0-2.0
1000-5600
1.0
15-0-15
3010-AV
0-10
2000-12500
Minor
Div.
Range
Range,
PSIG
PSIG
Model
Minor Div.
MM of
Number
.02
0-1
MM
Water
.05
0-2
3000-6MM
.20
0-6
.10
0-3
.10 3000-10MM
0-4
.50
0-10
.10
0-5
3000-25MM
.50
0-25
.20
0-10
.50 3000-50MM
0-15
1.0
0-50
.50
0-20
2.0
0-80
1.0 3000-80MM
0-30
0-30
0-60
0-100
0-200
0-300
0-600
0-1000
0-3000
0-6000
1.0
2.0
2.0
5.0
10
20
20
100
200
3000-100MM
0-100
Model
Number
Range,
Zero
Center
Pascals
Minor Div.
Pascals
.50
3300-250Pa
125-0-125
125-0-125
.50
3300-500Pa
250-0-250
Range
KiloPascals
Minor Div.
KiloPascals
3000-1kPa
0-1.0
.02
3000-1.5kPa
0-1.5
.05
5.0
3000-2kPa
0-200
0-2.0
.05
5.0
3000-3kPa
3000-250CM
0-250
0-3.0
.10
5.0
3000-4kPa
3000-300CM
0-300
Range,
Zero
Center
Cm of
Water
0-4.0
.10
10.0
3000-5kPa
0-5.0
.10
3000-8kPa
0-8.0
.20
3000-10kPa
0-10
.20
3000-15kPa
0-15
.50
3000-20kPa
0-20
.50
3000-25kPa
0-25
.50
3000-30kPa
0-30
1.0
Range,
Zero
Center
Kilopascals
Minor
Div.
Kilopascals
Range
CM of
Water
Minor
Div.
CM
3000-15CM
0-15
3000-20CM
0-20
3000-25CM
0-25
.50
3000-50CM
0-50
1.0
Model
Number
3000-80CM
0-80
2.0
3000-100CM
0-100
2.0
3000-150CM
0-150
3000-200CM
Model
Number
Model
Number
3300-4CM
2-0-2
3300-10CM
5-0-5
3300-30CM
15-0-15
2.0
Model
Number
Model
Number
Range,
Zero
Center
MM
of Water
Minor
Div.
MM
3300-20MM
10-0-10
.50
Minor
Div.
CM
.10
.20
1.0
Minor
Range,
Div.
Pascals Pascals
250-0-250
3000-60Pa
0-60
2.0
3000-125Pa
0-125
5.0
3000-250Pa
0-250
5.0
Model
Number
3000-500Pa
0-500
10.0
3300-1kPa
.5-0-.5
.02
25.0
3300-3kPa
1.5-0-1.5
.10
3000-750Pa
0-750
*NOTE: The Photohelic® pressure switch/gage may be used in an Under writers Laboratories approved
industrial control panel if the usage conforms to UL specifications for the acceptance of unlisted components.
B-33 Spanish
7/3/03
3:54 PM
Page 1
Boletín B-33
El Interruptor/Indicador de Presión Photohelic Serie 3000*
INSTRUCCIONES Y OPERACION
2-1/2 [63.50]
1/8 FEMALE NPT HIGH
2-1/16 [52.39]
PRESSURE CONNECTION
2 [50.80]
1/8 FEMALE NPT LOW
PRESSURE CONNECTION
1-1/4
[31.75]
Ø4-3/4
[120.65]
3-7/8 SQ
[98.43]
3/4 CONDUIT
CONNECTION
(4) 6-32 HOLES
EQUALLY SPACED ON
A 5-1/8 [130.18] B.C.
Ø4-47/64
[120.25] Ø5
[127.00]
3-7/8 [98.43]
5-1/8 [130.18]
6-3/8 [161.93]
4-3/8 [111.13]
(7-5/8 [193.68])
HOUSING REMOVAL
5/8 [15.88]
5/8 [15.88] PANEL
MAX
3/16 [4.76]
Ø4 [101.60]
FACE
5-1/2 [139.70]
O.D.
MOUNTING
RING
Figura 1
* Patent No. 3,862,416
El Interruptor/Indicador de Presión Photohelic ® es un
an interruptor de presión muy versátile y preciso, combinado con el indicador de presión de respuesta rápida
Magnehelic. Los modelos están disponibles con uno o dos
fototransistores que actúan sobre relés. A la lectura del
indicador no le afecta la operación del interruptor. Facilidad
de ajuste del punto de trabajo mediante botones de control.
Las presión aplicada y los puntos do interrupción (disparos)
son claramente visibles en todo momento. La banda muerta tiene una anchura de menos del 1% del fondo de escala.
Los relés de doble circuito, doble disparo pueden ser facilmente entrelazados para proporcionar un control variable
de la banda muerta. Para presión positiva, negativa y diferencial; para models de un sólo relé, presión positiva sólo en
modelo 36000S. Rangos de fondo escala disponibles de 0
- 0.25” c.a. a 0 - 6000 psig.
SENTIDO DEL PHOTOHELIC SU FUNCIONAMIENTO
En una applicación de control tipica, el interruptor/indicador
Photohelic controla entre los puntos de trabajo de alta y
baja presión. Cuando la presión cambia, alcanzando
cualquier presión del punto de trabajo, el haz de lud de un
LED dirigido hacia el fototransistor limitador será interrumpido por el escudo de luz del eje helicoidal. El cambio
de la señal resultante es electronicamente amplificada para
actuar sobre su relé esclavo DPDT y ocasiona el disparo del
interruptor. La banda muerta entre lo marcado y el corte es
del 1% del fondo de escala o menor. Suficiente para asegurar una operación positiva y libre de errores.
DWYER INSTRUMENTS, INC.
P.O. BOX 373 • MICHIGAN CITY, INDIANA 46361, U.S.A.
ESPECIFICACIONES
GAGE SPECIFICATIONS
Service: Air and non-combustible, compatible gases.
Wetted Materials: Consult Factory.
Accuracy: Photohelic®, ±2% of full scale at 70°F (21.1°C).
±3% on -0 and ±4% on -00 models.
Pressure Limits: Photohelic® -20" Hg. to 25 psig (-0.677
to 1.72 bar). MP option; 35 psig (2.41 bar), HP option; 80
psig (5.52 bar). 36003S – 36010S; 150 psig (10.34 bar).
36020S and higher; 1.2 x full scale pressure.
Temperature Limits: 20 to 120°F.
(-6.67 to 48.9°C) Low temperature option available.
Process Connections: Photohelic®, 1/8˝ female NPT.
Size: Photohelic®, 4˝ (101.6 mm) dial face, 5˝ (127 mm)
O.D. x 8-1/4˝ (209.55 mm).
Weight: Photohelic®, 4 lbs. (1.81 kg).
SWITCH SPECIFICATIONS
Switch Type: Each setpoint has 2 Form C relays (DPDT).
Repeatability: ±1% of full scale.
Electrical Rating: Photohelic®, 10A @ 28 VDC, 10A @
120, 240 VAC.
Electrical Connections: Screw Terminals.
Power Requirements: 120 VAC, 50/60 Hz; 240 VAC &
24 VAC Power optional.
Mounting Orientation: Diaphragm in vertical position.
Consult factory for other position orientations.
Set Point Adjustment: Adjustable knobs on face.
Agency Approvals: Photohelic® UL, CSA, CE.
Phone: 219/879-8000
Fax: 219/872-9052
www.dwyer-inst.com
e-mail: [email protected]
B-33 Spanish
7/3/03
3:54 PM
Page 2
Boletín B-33
P. 2
INSTALACION
Localización: Todas las partes del interruptor/indicador
Photohelic de Dwyer están robustamente construidas para
soportar una moderada cantidad de vibración, impacto físico y manejo del mismo. Un cuidado normal en su manejo
e instalación es todo lo que se precisa. En los casos en los
que la vibración del panel de instrumentos sea intensa, éste
deberá estar montado sobre algún resorte, o bien, la unidad
del relé-amplificador estar montada en una superficie más
estable.
Elegir un lugar donde la temperatura ambiente no exceda
de 120°F (49°C).
Las lineas sensoras de presión neumática deben alargarse
a la distancia que sea necesaria. Por ejemplo, 250 pies (75
m) de lineas sensoras no afectarán a la precisión, pero
amortiguarán la lectura ligeramente. Si la presión pulsante
o la vibración dan lugar a un punto de excesiva oscilación o
el relé castañea, consultar con la fábrica para medios adicionales de amortiguamiento. Ver accesorios adecuados
con el Boletín S-101.
Montaje: El Photohelic se monta normalmente antes de
hacer las conexiones eléctricas, por lo tanto la carcasa eléctrica es independiente de la forma me montaje y puede ser
quitada en cualquier momento.
Montaje en Panel: El montaje normal es embutir o atravesar el panel como muestra la Fig. 2. Asegúrase de que
deja un espacio extra de 4-3/8” (111 mm) detrás de la
unidad; quitar la carcasa eléctrica. Hacer un simple agujero
de 4 13/16˝ (122 mm) de diametro en el panel. Inserter todo
el Photohelic por el frontal del panel, luego deslizar el anillo
de sujección y encajar el anillo por la parte de atrás.
Coloque el anillo de sujección en su ranura, mueva hacia
atrás el anillo de sujección y una vez más encaje el anillo y
apriete los cuatro (4) tornillos de abrazadera de 2˝ (50 mm)
No. 6-32 que se suministran. Si el espacio detrás del panel
es crítico, la unidad relé-amplificador se puede montar de
forma remota. Ver Instrucciones de Mantaje de Relé
Remoto para más detalles.
Pocisión: El Photohelic debe ser montado como un conjunto compacto, o bien el modulo rele carga-amplificador
ensamblado y su carcasa se monta en un lugar remoto de
la unidad indicador-fototransistor. Los cables de extgension
con conexion de 7 pies y los conectores están disponibles
en Dwyer para interconectar las dos
unidades.
La unidad puede estar montada en la posición que se
desee, la escala vertical u horizontal, sin que ello afecta a la
precisión, pero debe ser recalibrado el cero si la posición
cambia de horizontal a vertical o viceversa. Los models - 0
y - 00 deben estar montados con la escala vertical.
Ranura Del Anillo De Suceccion
Ø4-13/16 [122.24]
Dianetroaguiero
Tapones De Presion
Neumatica
Figura 2
Atraves del Panel de Montaje
B-33 Spanish
7/3/03
3:54 PM
Page 3
Boletín B-33
P. 3
Montaje del Indicador con los Relés Remotos: Donde
se desee montar la unidad relé-amplificador separada de la
unidad indicador/fototransistor, el indicador puede montarse de cualquiera de las maneras mostra-das en la Fig. 2
(excepto la parte del relé-amplificador) o montarse sobre
superficie como se muestra en la Fig 3. Utilice el trazado
monstrado en la Fig. 4 para localizer los agujeros. El conjunto completo no se puede montar sobre superficie.
Figura 5
Unidad Relé-Amplificador Remota
Ø3/16
TYP 4 PLACES
Figura 3
Montaje Sobresuperficie
Tiesogujeros De Ø3/16 [4.76] Diam.
Separados 120° en la
superjiciede montaje
Agujerode 3/4" [19.05] de diam.
para conexion del cableado
4-9/32
[108.74]
4-9/32
[108.74]
5
[127.00] SQ
Figura 6
Esquema de los Agujeros
1-1/8
[28.58]
1-1/8
[28.58]
Figura 4
Esquema del Agujero (de frente)
Montaje Remoto de los Relés: La unidad relé-amplificador puede montarse remotamente como se muestra en
la Fig. 5. Ulice el trazado de agujeros que se muestra en la
Fig. 6 para esta opcion. Para mas información sobre el
montaje para requerimientos especiales, consulte con la
fabrica.
Conexiones Neumaticas y Ajuste del Cero: Después
de la instalación, pero antes de hacer las conexiones de
presión, coloque el puntero de indicación (la aguja) exactamente sobre la marca del cero, usando el tornillo de ajuste
del cero situado en la parte de abajo de la cubierta frontal.
Tenga en cuenta que este ajuste sólo se pueda hacer con
las espitas de alta y baja presión abiertas a la atmósfera.
Conecte las espitas de alta y baja presión a los puntos de
presión positiva, negativa o diferencial. Utilice tubo metálico de 4” NPT (3.175 mm) del interruptor/indicador de presión Photohelic de Dwyer. Los adaptores para tubos de
caucho o de plástico blando son proporcionados con el
instrumento para utilizarlos cuando se prefiera este tipo de
conexión.
Si el Photohelic no se usa para detectar presión diferencial,
una de las espitas de presión debe abierta a la atmósfera.
Esto permitirá la entrada de la presión de referencia. En
este caso, se recomienda la instalación de un filtro de
Dwyer No. A-331 u otro similar apropiado en la espita de la
presión de referencia para reducir la posibilidad de entrada
de polvo en el instrumento.
Nota: Si el interruptor/indicador Photohelic está sobre-presionado, el puntero (aguja) “salta” desde el final de la escala
hasta el cero y se mantiene ahí hasta que la condición de
exceso de presión se alivia. Los usuarios deberían ser consecuentes de las posible indicaciones de falso cero bajo
esta condición.
B-33 Spanish
7/3/03
3:54 PM
Page 4
Boletín B-33
P. 4
CONEXIONES ELECTRICAS
1. Cubierta: La unidad relé-amplificador tiene una carcasa
fácil de quitar. Quite los tres (3) tornillos como se muestra
en la Fig. 7 y deslice hacia afuera la carcasa. Haga todas
las conexiones eléctircas antes de reinstaler y reasegurar la
carcasa.
2. Conducto: El acceso eléctrico a la parte de la carcasa
del relé de la caja de conexión se hace abriendo un tapón
para conductos de (19 mm). Se recomienda el uso de conductos flexibles. Este se sujetaría al panel u otra superficie
apta para prevenir el sistema de cableado de un esfuerso
de tensión indebido en el instrumento. Ver Fig. 7.
3. Esquema del Terminal o Placa de Conexión: En la
Fig. 8, “Placa de Terminales,” la Seccion A contiene las
conexiones para al relé de carga o esclavo actuado por el
punto de trabajo derecho o de alta. Este relé es de tipo
doble polo, de doble circuito. Las dos conexiones superiores son normalmente carradas, las dos del medio son normalmente abiertas y las dos de abajo son el común. El relé
está en su posición normal o des-energizado cuando la presión está por debajo del punto de trabejo del lado derecho
(del alta).
La Seccion D es exactamente igual que la Seccion A,
excepto que su relé de carga o esclavo está controlado por
el punto de trabajo izquierdo o de baja. La posición
des-energizada está pro debajo del punto de trabajo del
lado izquierdo (de baja).
La Seccion B contiene las conexiones externas para el
mantenimiento del circuito bobinado para relé del punto de
trabajo derecho o de alta y la Seccion C, contiene conexiones similares para el relé del punto de trabajo izquierdo o
de baja. La función y uso de estas conexiones varía algo
dependiendo del tipo de circuito del instrumento. Ver párrafos 5 y 6 para más detalles.
La Seccion E contiene las conexiones de alimentación
para el transformador primario de la unidad de control. El
transformador a cambio suministra un reducido voltaje de
alimentación para el LED, el fototransistor, la unidad amplificadora y tirar del relé descarga y mantener el bobinado.
Las unidades estánder están diseñadas para 117 VCA de
entrada al transformador. También están disponibles
unidades especiales para otros voltajes.
Está provisto de una atadura para Cable Separado a
Tierra mediante un tornillo No. 6-32 en la repisa montada
carca de la abertura del conducto. Está localizado un cable
adicional a tierra en el lateral del cuerpo de indicación para
usa lo cuando la unidad relé-amplificador está montada
remotamente.
Los instrumentos de un Punto de Trabajo se suministran
con los componentes del punto de trabajo de alta o derecho y la circuitería correspondiente. Esta está conectada a
las Secciones A y B de la placa de terminales. Los componentes del punto de trabajo izquierdo o de baja están
omitidos.
Seccion B
Tornillos De Montaje De La Cubierta
Seccion C
Seccion A
Seccion D
4-3/8 [111.13]
Espacio Para
Sacar La Cubierta
Conducto Flexible
Seccion E
Soporte Del Conducto
Del Panel
Figura 7
Detalles del Montaje
Figura 8
Placa de Terminales
B-33 Spanish
7/3/03
3:54 PM
Page 5
Boletín B-33
P. 5
4. Tipo de Circuito: El Photohelic está disponible con varios circuitos internos opcionales instalados en fábrica.
Están identificados como tipo por una etiqueta mostrada en
la Fig. 9. Esta ertiqueta se monta de forma prominente en
la placa de terminal de cada instrumento. La letra H indica
un circuito cuyo relé puede pasar a almacenar un estado
eléctrico o retenerse energizado (activado) después de que
la presión sobrepase or un incremento su punto de trabajo.
TIPO DE CIRCUITO:
TENSION DE ALLMENTACION:
RANGO DE CONTACTO:
6. Reset Manual de Doble Punto de Trabajo: El circuito
tipo HH también se puede utilizar para aplicaciones con
reset manual donda se desee hacer un contacto mantenido
sobra cualquier relé después de que la presión haya
aumentado por encima de su punto de trabajo. Las conexiones de carga o señal se hacen a los terminales apropiados en las Secciones A y D (como en el párrafo 5 anterior).
Connectar los terminales en las secciones B y C mediante
interruptores Nomalmente Cerrado (N.C.) o pulsadores
como se muestra en la Fig. 10. Se recomienda el uso de
interruptores tip “dry-circuit” (circuito seco), tales como el
Dwyer P/N A-601 con contactos de paladio, oro, etc, o de
tipo rotativo protegidos del exterior. Haga las conexiones
externas a tierra como se requiere y conecte la alimentación
a la Sección E para el control de la unidad.
RESET
RESET
Figura 9
Etiqueta del Circuito
La letra L indica un circuito en el cual el relé pueda pasar a
almancer un estado eléctrico o retenerse des-energizado
después de que la presión sobrepase por decremento su
punto de trabajo. Se necesitan dos letras para indentificar
completamente una unidad de doble punto de trabajo. Así,
el ecicuito de tipo HH, el cual es el estándar, es un circuito
de doble punto de trabajo, el cual está provisto para el
almacenamiento do estados de corriente (latching) cuando
ambos puntos de trabajo son sobrepasados por un incremento de la presión. Las unidadas de un sólo relé están
identificadas por las retras SR seguidas de una H para la
unidad estánder o por una L para unidades especiales de
almacenamiento de estado de corriente (lach) en decremento. Las unidades para usar con otros estándares distinos de 117 VCA serán así indicados en la etiqueta.
5. Reset Automatico de Doble Punto de Trabajo: El
circuito tipo HH se usa para aplicaciones simples de interruptor on-off. Para ponerlo en sevicio conecte los circuitos
de carga a los terminales apropiados en la Sección A (Fig.
8) para el punto de trabajo derecho y en la Sección D para
el punto de trabajo izquierdo. No son necesarias las conexiones en las Secciones B y C. Tenga en cuente que los
contactos N.A. están abiertos cuando la aguja del indicador
de presión está a la izquierdo de los punteros de los puntos
de trabajo. No es necesaria ninguna conexión en las
Secciones B y C. Haga las conexiones externas a tierra
como se requieren y conecte la alimentación a la Sección E
para el control de la unidad.
Para usar el circuito tipo LL para reset automatico, se debe
instalar un puente de hilo entre los terminales superior e
inferior de las secciones b y/o C.
PRECAUCION: No applicar corriente eléctricas
a los terminales de las secciones B y C.
Figura 10
Reset Manual con Circuito HH
El circuito LL se usa para aplicaciones de reset manual el las
cuales se requiere que el contacto se mantenga despues
de que la presión haya disminuido por debajo del punto de
trabajo.
Las conexiones de carga se hacen a los terminales apropiados en las Secciones A y D. Se conecta un interruptor de
tipo N.A, para el reset manual, tal como el Dwyer P/N A601, a los terminales de las Secciones B y C. El circuito
puede quedar “arruinado” por un cierre momentáneo del
interruptor mientras la aguja negra está a la derecha del
punto de trabajo. Desde ese punto, el circuito almacena el
estado de corriente cuando la presión decrece por debajo
del punto de trabajo y retiene este estado de corriente
cuando la presión veulve a crecer, hasta que se hace un
reset manualmente con el interruptor opcional.
B-33 Spanish
7/3/03
3:54 PM
Page 6
Boletín B-33
P. 6
7. Combanaciones de Reset Manual y Automático de
Doble Punto de Trabajo: El circuito tipo HH puede usarse
con cualquiera de los puntos de trabajo, cableado y
operando como en el párrafo 5 anterior y el otro punto de
trabajo cableado y operando como en el párrafo 8.
Puentes De Reset
Carga
1/6 HP
117 V
Linea De 117 V
Nota: Para motores mayores, utilice el Photohelic
en un contacto mantenido, controle los 117 V ó
pulse el boton del circuito del estarter del motor.
Figura 11
Control de Limite Alta-Baja (Circuito HH)
8. Controlo del Límite Alta Baja-Doble Punto de
Trabajo: El circuito tipo HH puede usarse para controlar
ventiladores, tiros, bombas, etc., entre los puntos de tr bajo
de un Photohelic. Para efectuar esto, use el relé de un
punto de trabajo para hacer reset del otro como se muestra en el diagrama eléctrico de la Fig. 11. En esta típica aplicación la carga (por ejemplo, un ventilador) se conectaría a
los contactos N.C. del relé del punto de trabajo, Sección A
(Fig. 8). Al aumentar la presión en el punto de trabajo derecho, su relé se cargaría y se manendría aunqué la presión
pudiera caer por debajo de ese punto de trabajo. Si la presión continúa cayendo hasta el punto de trabajo izquierdo,
su relé se des-energizaria automáticamente, volviendo a su
posición normal y, en tal situación, se abre el circuito del
bobinado mantenido de la Sección B (Fig. 8). El relé del
punto de trabajo derecho se haría así un reset y el icilo se
repetiría.
9. Circuitos de Doble Punto de Trabajo de Propósito
Especial: El circuito tipo LL se puede usar donde se desee
de forma que al hacer un reset manual se mantenga el contacto al decrecer la presión en cualquiera de los puntos de
trabajo. Los circuitos tip LH y HL son unidades hechas con
combinaciones. Para características especiales de combinaciones, unidades especiales e instrucciones detalladas
en cuanto a su uso, consulte con la fábrica.
10. Photohelic de un Punto de Trabajo: El Photohelic
de un punto de trabajo derecho solamente. Los terminales
de las Secciones A y B (Fig. 8) están conectados a este relé.
El circuito tipo SRH está cableado para rese automático,
come se explica en el párrafo 5 anterior. El reset manual
está efectuado para añadir un interruptor de reset tipo N.C.
o un pulsador al circuito descrito en el párrafo 6 anterior.
11. Punto de Trabajo Unico Especial: Se puede obtener un reset manual después de la actuación en caida de
presión al usar un circuito tipo SRL. Consulte con la fábrica para unidades especiales e instrucciones detalladas en
cuanto a su uso.
12. Situación en Servicio: En operación normal cada rel
se des-energiza cuando la presión aplicada al instrumento
está por debajo de su punto de trabajo. Las uni-dades
especiales de almacenamiento de estado eléctrico en bajada, generalmente se les tendrá que hacer un reset antes de
situarías en la línea en operación normal.
13. Modo de Fallo: El diseño del circuito del Photo-helic
está provisto de cierta protección en caso de una pérdida
de presión o de alimentación eléctrica. En cualquier caso,
ambos relés se des-energizaran, volviendo a su estado normal de “Presión Cero.” Las excepciones a esto son modelos con rangos de cero centrado.
Debido a que los relés en todos los models estánder están
siempre energizados cuando la aguja inidcadora está a la
derecha de sus respectivos puntos de trabajo, la acción del
relé en la pérdida de presión dependerá de la posición del
punto de trabajo, desde cualquiera de ellos se podria
localizar a la izquierda del cero. Como ejemplo: Si el puntero izquierda estuviera ajustado a -2” c.a. y la presión negativa fuera de -3” c.a., una pérdida de esa presión permitiría
que la aguja indicadora (negra) volviera al centro y así causa
que el relé del punto de trabajo en baja se energiza.
Si el LED dejara de brillar, sólo se desenergizeria el relé de
baja-izquierdo. El relé de alta-derecho reaccionara como si
la presion estuviera por encima de su punto de trabajo y se
mantendrá energizado aunque la presion pudiera estár por
debajo de ese punto de trabajo. En esta situacion, sólo la
interrupción de la alimentacion eléctrica permitirá qu el relé
de alta-derecho se des-energice.
B-33 Spanish
7/3/03
3:54 PM
Page 7
Boletín B-33
P. 7
MANTENIMIENTO Y SERVICIO
Los Interruptores/Indicadores Photohelic de Dwyer son instrumentos de precisión, expertamente ensamblados y
calibrados en la fábrica. No necesitan lubricación o revisiones periódicas. Si el interior está protegido del polvo,
suciedad, gases corrosivos y fluídos, se pueden esperar años de servicio sin ningún problema.
El ajuste del cero debería ser revisado y reajustado de vez en cuando para mantener la precision.
Cualquier reparación necessaria para cualquiera de los indicadores de presión Magnehelic de Dwyer o para los
componentes electrónicos debería ser realizada por un mecánico entranado de instrumentos. En muchos casos,
la major elección es mandar al interruptor/indicador completo Photohelic a la fábrica de Dwyer.
El Interrutor/Indicador de Presión Photohelic
Los Modelos y Rangos
Model
Number
Range,
Inches Minor
of Water Div.
3000-00
0-.25
.005
3000-0
0-.50
.01
3001
0-1.0
.02
3002
0-2.0
.05
3003
0-3.0
.10
3004
0-4.0
.10
3005
0-5.0
.10
3006
3008
0-6.0
0-8.0
.20
.20
3010
0-10
.20
3015
0-15
.50
3020
0-20
.50
3025
0-25
.50
3030
0-30
1.0
3040
0-40
1.0
3050
0-50
1.0
3060
0-60
2.0
3080
0-80
2.0
3100
0-100
2.0
3150
0-150
5.0
Model
Number
3300-0
3301
3302
3304
3310
3320
3330
Model
Number
3201
3202
3203
3204
3205
3210
3215
3220
3230
36003S
36006S
36010S
36020S
36030S
36060S
36100S
36300S
36600S
Dual Scale Air Veloocityy Units
Range,
(for use with pitot tube)
Zero
Range,
Center
Ranges,
Air
Inches Minor
Model
Inches of Velocity
of Water Div.
Number
Water
FPM
.25-0-.25 .01
3000-00AV
0-.25
300-2000
.5-0-.5
.02
.05 3000-0AV
1-0-1
0-50
500-2800
.10
2-0-2
0-10
500-4000
.20 3001-AV
5-0-5
.50 3002-AV
10-0-10
0-20
1000-5600
1.0
15-0-15
3010-AV
0-10
2000-12500
Minor
Div.
Range
Range,
PSIG
PSIG
Model
Minor Div.
MM of
Number
.02
0-1
MM
Water
.05
0-2
3000-6MM
.20
0-6
.10
0-3
.10 3000-10MM
0-4
.50
0-10
.10
0-5
3000-25MM
.50
0-25
.20
0-10
.50 3000-50MM
0-15
1.0
0-50
.50
0-20
2.0
0-80
1.0 3000-80MM
0-30
0-30
0-60
0-100
0-200
0-300
0-600
0-1000
0-3000
0-6000
1.0
2.0
2.0
5.0
10
20
20
100
200
©Copyright 2003 Dwyer Instruments, Inc.
3000-100MM
0-100
Model
Number
Range,
Zero
Center
Pascals
Minor Div.
Pascals
.50
3300-250Pa
125-0-125
125-0-125
0-20
.50
3300-500Pa
0-25
.50
3000-50CM
0-50
1.0
Model
Number
250-0-250
Range
KiloPascals
Minor Div.
KiloPascals
3000-80CM
0-80
2.0
3000-1kPa
0-1.0
.02
3000-100CM
0-100
2.0
3000-1.5kPa
0-1.5
.05
3000-150CM
0-150
5.0
3000-2kPa
0-2.0
.05
3000-200CM
0-200
5.0
3000-3kPa
0-3.0
.10
3000-250CM
0-250
5.0
3000-4kPa
0-4.0
.10
3000-300CM
0-300
Range,
Zero
Center
Cm of
Water
10.0
3000-5kPa
0-5.0
.10
Minor
3000-8kPa
0-8.0
.20
Div.
CM
3000-10kPa
0-10
.20
3000-15kPa
0-15
.50
3300-4CM
2-0-2
.10
3000-20kPa
0-20
.50
3300-10CM
5-0-5
.20
3000-25kPa
0-25
.50
1.0 3000-30kPa
Minor
Range,
Div.
Pascals Pascals
0-30
1.0
Range,
Zero
Center
Kilopascals
Minor
Div.
Kilopascals
Range
CM of
Water
Minor
Div.
CM
3000-15CM
0-15
3000-20CM
3000-25CM
Model
Number
Model
Number
3300-30CM
2.0
Model
Number
Model
Number
Range,
Zero
Center
MM
of Water
Minor
Div.
MM
3300-20MM
10-0-10
.50
15-0-15
3000-60Pa
0-60
2.0
3000-125Pa
0-125
5.0
3000-250Pa
0-250
5.0
Model
Number
3000-500Pa
0-500
10.0
3300-1kPa
.5-0-.5
.02
25.0
3300-3kPa
1.5-0-1.5
.10
3000-750Pa
Printed in U.S.A. 7/03
DWYER INSTRUMENTS, INC.
P.O. BOX 373 • MICHIGAN CITY, INDIANA 46361, U.S.A.
250-0-250
Phone: 219/879-8000
Fax: 219/872-9057
0-750
FR# 13-440202-02 Rev. 2
www.dwyer-inst.com
e-mail: [email protected]