Asd Ems Instruction

Asd Ems Instruction
On the current driver we provide all the EMS command that available inside the ZONE2 controller “emsDvX and emsAvX”. See list below:
This is for all the command that will sent to the end device point.
Below is the example:
Please follow exactly as below to make the thing work.
I want to command the end device e.g. DO1, DO2 for equipment start/stop.
Now how this EMS will sent the update from the Niagara Asd Driver to specified end device point? So you need to use XPSI tool to access to the
end device to verify the EMS update sent to specific point.
Once you access to the end device go to DO:1 point. On the “DI” parameter key in “EMS:1:DV1”
DO:2 point. On the “DI” parameter key in “EMS:1:DV2”
I want to command the end device e.g. LOOP 1 setpoint
LOOP:1 point. On the “SP” parameter key in “EMS:1:AV1”
The last important part that you cannot miss this the EMS manager EMS:1. If this “ACTION” property other than “BLOCK USED” whatever you
command from the remote, it will not take any update from the front end. Even GCM too.
Do not turn off the “Ems Control” in the device it should be “True” all the time.
Now I should able to control the DO1 at the end device once I change the “emsDv1” from the Niagara Ax Asd driver “Asd Zone2 Point Manager” .