S UN AVER MPPT Installation and Operation Manual

Add to my manuals
49 Pages

advertisement

S UN AVER MPPT Installation and Operation Manual | Manualzz

S

UN

S

AVER MPPT

TM

WITH TRAKSTAR

TM

MPPT TECHNOLOGY

Installation and Operation Manual

Model: SS-MPPT-15L

www.morningstarcorp.com

SunSaver MPPT Dimensions

Specification Summary

System Voltage

Rated Battery Current

Rated Load Current

Maximum Input Voltage*

Nominal Maximum Input Power**

12 Volt System

24 Volt System

12 Volts / 24 Volts

15 Amps

15 Amps

75 Volts

200 Watts

400 Watts

See Section 7.0 for full technical specifications

* Array voltage should never exceed maximum input voltage. Refer to o the solar module documentation to determine the highest expected array

V oc

as defined by the lowest expected ambient temperature for the system location.

** These power levels refer to the maximum wattage the SS-MPPT-

15L can process at a certain system voltage. Higher power arrays can be used without damaging the controller, but array cost-benefit will be

Contents

1.0 Important Safety Information

1.0 Important Safety Instructions

2.0 General Information

4

4

9

Overview

Features

9

10

Optional

2.3 Regulatory Information 13

3.0 Installation Instructions 15

3.1 General Installation Notes

3.2 Configuration

Mounting

15

16

19

4.0 Operation

5.0 Troubleshooting

Error

5.2 Common Problems

28

LED

4.2 TrakStar

4.5

TM

MPPT Technology

4.3 Battery Charging Information

4.4 Load Control Information

Protections 37

4.6 Inspection and Maintenance

4.7 Programming Custom Setpoints

30

33

35

39

40

41

6.0 Warranty

7.0 Technical Specifications

Appendix A - Wire Chart

42

43

44

49

MORNINGSTAR CORPORATION 3

1.0 Important Safety Instructions

Save These Instructions

This manual contains important safety, installation and operating instructions for the SunSaver MPPT solar controller.

The following symbols are used throughout this manual to indicate potentially dangerous conditions or mark important safety instructions.

WARNING: Indicates a potentially dangerous condition. Use extreme caution when performing this task.

CAUTION: Indicates a critical procedure for safe and proper operation of the controller.

NOTE: Indicates a procedure or function that is important for the safe and proper operation of the controller.

General Safety Information

• Read all of the instructions and cautions in the manual before beginning installation.

• There are no user serviceable parts inside the

SunSaver MPPT. Do not disassemble or attempt to repair the controller.

• Disconnect all sources of power to the controller before installing or adjusting the SunSaver MPPT.

• There are no fuses or disconnects inside the SunSaver

MPPT. Install external fuses/breakers as required.

• Do not allow water to enter the controller.

• Confirm that power connections are tightened to avoid excessive heating from a loose connection.

1.0 IMPORTANT SAFETY INSTRUCTIONS

CAUTION:

A BATTERY CAN PRESENT A RISK OF ELECTRICAL

SHOCK, BURN FROM HIGH SHORTCIRCUIT

CURRENT, FIRE OR EXPLOSION FROM VENTED GASES.

OBSERVE PROPER PRECAUTIONS;

NOTE:

PROPER DISPOSAL OF BATTERIES IS REQUIRED. RE-

FER TO YOUR LOCAL CODES FOR DISPOSAL

REQUIREMENTS;

WARNING:

These servicing instructions are for use by qualified personnel only. To reduce the risk of electric shock, do not perform any servicing other than that specified in the operating instructions unless you are qualified to do so.

WARNING:

EXPLOSION HAZARD - DO NOT DISCONNECT WHILE

CIRCUIT IS LIVE UNLESS AREA IS

KNOWN TO BE NON-HAZARDOUS.

CAUTION:

To reduce the risk of fire, connect only to a circuit provided with a maximum branch-circuit overcurrent protection rating not to exceed the model current rating on page 2 and in accordance with the National Electrical

Code, ANSI/NFPA 70.

MORNINGSTAR CORPORATION 5

Informations de sécurité

• Installez des fusibles/coupe-circuits externes selon le besoin.

ATTENTION:

UNE BATTERIE PEUT PRÉSENTER UN RISQUE ÉLEVÉ

DE CHOC ÉLECTRIQUE, DE BRÛLURES SUITE À UN

COURANT DE COURT-CIRCUIT ÉLEVÉ, À UN INCENDIE

OU À UNE EXPLOSION PROVENANT DE GAZ REJETÉS

DANS L’AIR. VEUILLEZ PRENDRE LES PRÉCAUTIONS

NÉCESSAIRES.

AVERTISSEMENT:

Ces instructions d’entretien sont exclusivement réservées à des techniciens qualifiés. Pour réduire le risque de choc électrique, ne réalisez aucun entretien autre que celui stipulé dans les instructions de fonctionnement, à moins que vous ne possédiez les qualifications nécessaires en la matière.

AVERTISSEMENT:

RISQUE D’EXPLOSION. NE PAS DEBRANCHER TANT

QUE LE CIRCUIT EST SOUS TENSION, A MOINS QU’lL

NE S’AGISSE D’UN EMPLACEMENT NON DANGEREUX.

ATTENTION:

Pour diminuer le risque d’incendie, ne connectez l’alimentation qu’à un circuit équipé d’une protection maximum par dérivation contre les surintensités ne dépassant pas le courant nominal du modèle de la page 2, conformément à la norme du Code National de l’Électricité (NEC), ANSI/NFPA 70.

1.0 IMPORTANT SAFETY INSTRUCTIONS

Installation Safety Precautions

WARNING:

This unit is not provided with a GFDI device. This charge controller must be used with an external

GFDI device as required by the Article 690 of the National Electrical Code for the installation location.

• Use insulated tools when working with batteries.

• Avoid wearing jewelry during installation.

• Do not smoke in the vicinity of the battery bank.

• Use properly sized conductors and circuit interrupters.

Direct Current Symbol

MORNINGSTAR CORPORATION 7

AVERTISSEMENT:

L’appareil n’est pas fourni avec un dispositif GFDI.

Ce contrôleur de charge doit être utilisé avec un dispositif GFDI externe tel que requis par l’Article

690 du Code électrique national de l’emplacement de l’installation.

• Utilisez des outils isolés pour travailler avec les batteries.

• Évitez le port de bijoux pendant l’installation.

• Ne fumez pas à proximité du groupe de batteries.

1.0 IMPORTANT SAFETY INSTRUCTIONS

2.0 General Information

2.1 Overview

Thank you for selecting the SunSaver MPPT charge controller with TrakStar Technology

TM

. The SunSaver-MPPT

(SS-MPPT) is an advanced maximum power point tracking solar battery charger and load controller for stand-alone PV systems. The controller features a smart tracking algorithm that maximizes the energy from the solar module(s) and also provides load control to prevent over-discharge of the battery.

The SS-MPPT battery charging process has been optimized for long battery life and improved system performance. Self-diagnostics and electronic error protection prevent damage when installation mistakes or system faults occur. The controller also features four (4) settings switches for adjustability, a meter port, and terminals for remote battery temperature measurement (optional).

Using MSView

TM

PC software, the SS-MPPT can be programmed with custom settings to function as a lighting controller to turn the system loads on and off at specified intervals throughout the day and night. See section 4.7 for

more information.

Although the SS-MPPT is very simple to configure and use, please take the time to read this operator’s manual and become familiar with the controller. This will help you make full use of the many advantages the SS-MPPT can provide for your PV system.

MORNINGSTAR CORPORATION 9

2.2 Features

The features of the SunSaver MPPT are shown in Figure 1 below. An explanation of each feature is provided.

8

7

1

6

2

5

4

3

Figure 1. SunSaver MPPT features.

1 - Status LED

An LED indicator that shows charging status and also indicates when a solar input fault condition exists.

2 - Power Terminal Block

Power terminations for system Solar, Battery, and Load connections.

3 - Battery Select Jumper

A removable jumper to select the battery type.

2.0 GENERAL INFORMATION

4 - Meter Connection

A communication port for the Morningstar Remote Meter or Personal Computer (PC) connection. A MSC adapter is required, available separately.

5 - Settings Switches

Adjustment switches that define the operating parameters of the SunSaver MPPT.

6 - Remote Temperature Sensor (RTS) Terminals

Connection point for a Morningstar RTS (optional) to remotely monitor battery temperature.

NOTE: The use of a Remote Temperature Sensor is strongly recommended. Controller location, air flow, and system power can drastically affect the local temperature sensor reading. A RTS will provide optimal charging performance.

7 - Local Temperature Sensor

Measures ambient temperature. Battery regulation is adjusted based on ambient temperature unless an optional

RTS is installed.

8 - Battery Status LEDs

Provides approximate battery state of charge indication and also indicates when a system or load fault condition exists.

MORNINGSTAR CORPORATION 11

2.3 Optional Accessories

The following accessories are available for purchase separately from your authorized Morningstar dealer.

Remote Temperature Sensor (Model: RTS)

The RTS measures battery temperature for accurate temperature compensation and is recommended when the ambient battery temperature differs from the ambient controller temperature by

+/- 5 degrees C or more. An RTS can be attached to the SunSaver

MPPT at any time. The SunSaver MPPT will automatically use the

RTS for battery temperature compensation when installed. The standard cable length is 33 ft (10 m), and can be extended to 100 ft (30 m) if required. Installation instructions are provided with the

RTS.

NOTE: The use of a Remote Temperature Sensor is strongly recommended. Controller location, air flow, and system power can drastically affect the local temperature sensor reading. A RTS will provide optimal charging performance.

Remote Meter (Model: RM-1)

The digital Remote Meter displays system operating information, error indications, and self-diagnostic read-out. Information is displayed on a backlit 4-digit custom LCD display. The large numerical display and icons are easy to read and large buttons make navigating the meter menus easy. Additionally, a status LED and three (3) battery SOC LEDs provide system status at a glance.

The meter can be flush mounted in a wall or surface mounted using the mounting frame (included). The RM-1 is supplied with 33 ft (10.0 m) of cable, a mounting frame, and mounting screws. The

RM-1 connects to the RJ- 11 Meter port on the SunSaver MPPT.

PC MeterBus Adapter

TM

(Model: MSC)

The MSC converts the MeterBus RJ-11 electrical interface to an isolated standard RS-232 interface which enables communication between the SunSaver MPPT and a personal computer (PC). The

MSC is required for programming custom charging setpoints and for logging data. See Section 4.7 Programming Custom Setpoints.

2.0 GENERAL INFORMATION

2.3 Regulatory Information

NOTE:

This section contains important information for safety and regulatory requirements.

The SunSaver-MPPT controller should be installed by a qualified technician according to the electrical rules of the country in which the product will be installed.

SunSaver-MPPT controllers comply with the following

EMC standards:

• Immunity: EN61000-6-2:1999

• Emissions: EN55022:1994 with A1 and A3 Class B1

• Safety: EN60335-1 and EN60335-2-29 (battery chargers)

A means shall be provided to ensure all pole disconnection from the power supply. This disconnection shall be incorporated in the fixed wiring.

Using the SunSaver-MPPT grounding terminal (in the wiring compartment), a permanent and reliable means for grounding shall be provided. The clamping of the earthing shall be secured against accidental loosening.

The entry openings to the SunSaver-MPPT wiring compartment shall be protected with conduit or with a bushing.

FCC requirements:

This device complies with Part 15 of the FCC rules.

Operation is subject to the following two conditions: (1)

This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.

MORNINGSTAR CORPORATION 13

Changes or modifications not expressly approved by

Morningstar for compliance could void the user’s authority to operate the equipment.

Note:

This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part

15 of the FCC rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communication. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment on and off, the user is encouraged to try to correct the interference by one or more of the following measures:

• Re-orient or relocate the receiving antenna.

• Increase the separation between the equipment and receiver.

This Class B digital apparatus complies with Canadian

ICES-003.

Cet appareil numerique de la classe B est conforme a la norme NMB-003 du Canada.

2.0 GENERAL INFORMATION

3.0 Installation Instructions

3.1 General Installation Notes

• Read through the entire installation section first before beginning installation.

• Be very careful when working with batteries. Wear eye protection. Have fresh water available to wash and clean any contact with battery acid.

• Use insulated tools and avoid placing metal objects near the batteries.

• Explosive battery gasses may be present during charging. Be certain there is sufficient ventilation to release the gasses.

• Do not install in locations where water can enter the controller.

• Loose power connections and/or corroded wires may result in resistive connections that melt wire insulation, burn surrounding materials, or

even cause

fire. Ensure tight connections and use cable clamps

to secure cables and prevent them from swaying in mobile applications.

• Only charge lead-acid or NiCd batteries.

• The SunSaver MPPT Battery connection may be wired to one battery or a bank of batteries. The following instructions refer to a singular battery, but it is implied that the battery connection can be made to either one battery or a group of batteries in a battery bank.

MORNINGSTAR CORPORATION 15

3.2 Configuration

The four (4) Settings Switches and the Battery Select

Jumper adjust the SS-MPPT battery type, load control, equalization, and communication settings. This section details the configuration for each setting.

Select a Battery Type

The SS-MPPT provides four (4) different battery types as shown in table 1 below. Use Settings Switch 1 and the

Battery Select Jumper to choose the battery type. See

Section 7.0 Technical Specifications for detailed charging information for each battery type.

The battery select jumper is secured in the terminal block between terminal #6 and terminal #7 as shown in figure 2.

The second column in table 1 specifies whether the jumper should be removed or remain in place, depending on the desired battery type.

Battery Type

Gel

1

Sealed

AGM

1

Flooded

Battery Jumper

INSERTED

INSERTED

REMOVED

REMOVED

Switch 1

ON (↑)

OFF (↓)

ON (↑)

OFF (↓)

(1) Setpoints for this battery type can be modified with custom programming. See Section 4.7 Programming Custom Setpoints for more information.

Table 1. Battery Type selection

3.0 INSTALLATION INSTRUCTIONS

Figure 2. Removing the Battery Select jumper.

Load Control – Low Voltage Disconnect / Reconnect

Choose between two (2) load control Low Voltage Discon-

nect / Reconnect settings.

SWITCH 2 OFF (↓):

SWITCH 2 ON (↑):

LVD = 11.50 V, LVR = 12.60 V

LVD = 11.00 V, LVR = 12.10 V

2

(2) These values can be modified with custom programming. See Section 4.7

Programming Custom Setpoints for more information.

Enable or Disable Auto-Equalization

Turn the auto-equalize feature OFF or ON. The autoequalize feature will administer an equalization charge

(flooded battery type only) every 28 days or if the battery discharges too low the previous night. There is no equalization charge for the gel or sealed battery type.

SWITCH 3 OFF (↓):

SWITCH 3 ON (↑):

AUTO-EQUALIZE OFF

AUTO-EQUALIZE ON

(agm, flooded battery type only)

MORNINGSTAR CORPORATION 17

Communication – Meter / MODBUS®

Choose the desired communication protocol for the RJ-11 meter connection. Select the Meter protocol to communicate with a Morningstar Remote Meter (optional accessory).

Select the MODBUS® protocol to communicate with a PC

2

and Morningstar’s MSView software. MODBUS® is an open communication protocol standard used by

Morningstar’s MSView PC software and other 3rd party hardware / software.

SWITCH 4 OFF (↓):

SWITCH 4 ON (↑):

MORNINGSTAR REMOTE METER

MODBUS® PROTOCOL FOR

MSVIEW, 3RD PARTY DEVICES

(2) Morningstar PC Meterbus Adapter (Model: MSC) required. Not included.

See Morningstar’s website for more information. www.morningstarcorp.com.

MODBUS® is a registered trademark of Modbus-IDA (www.modbus-ida.org)

3.0 INSTALLATION INSTRUCTIONS

3.3 Mounting

CAUTION: Equipment Damage or Risk of Explosion

Never install the SunSaver-MPPT in an enclosure with vented/flooded batteries. Battery fumes are flammable and will corrode and destroy the SunSaver circuits.

CAUTION: Equipment Damage

When installing the SunSaver-MPPT in an enclosure, ensure sufficient ventilation. Installation in a sealed enclosure will lead to over-heating and a decreased product lifetime.

PRUDENCE: Endommagement de l’équipement ou risque d’explosion

N’installez jamais le SunSaver-MPPT dans une enceinte avec des batteries à évent/à électrolyte liquide. Les vapeurs des batteries sont inflammables et corroderont et détruiront les circuits du SunSaver.

PRUDENCE: Endommagement de l’équipement

Assurez une ventilation suffisante en cas d’installation du SunSaver-MPPT dans une enceinte. L’installation dans une enceinte hermétique entraîne une surchauffe et une réduction de la durée de vie du produit.

Step 1: Choose Mounting Location

Locate the SunSaver-MPPT on a vertical surface protected from direct sun, high temperatures, and water.

Step 2: Check for Clearance

Place the SunSaver-MPPT in the location where it will be mounted. Verify that there is sufficient room to run wires and that there is ample room above and below the controller for air flow.

MORNINGSTAR CORPORATION 19

AT LEAST

6” (150 mm)

WARM AIR

AT LEAST

6” (150 mm)

COOL AIR

Figure 3. Mounting and cooling

Step 3: Mark Holes

Use a pencil or pen to mark the four (4) mounting hole locations on the mounting surface.

Step 4: Drill Holes

Remove the controller and drill 3/32” (2.5 mm) holes in the marked locations.

Step 5: Secure Controller

Place the controller on the surface and align the mounting holes with the drilled holes in step 4. Secure the controller in place using the mounting screws (included).

3.0 INSTALLATION INSTRUCTIONS

3.4 Wiring

NOTE: A recommended connection order has been provided for maximum safety during installation.

The controller will not be damaged regardless of the sequence of connections.

NOTE: The SunSaver-MPPT is a negative ground controller. Any combination of negative connections can be earth grounded as required. Grounding is recommended, but not required for correct operation.

NOTE:

To comply with the NEC, the SunSaver-MPPT must be installed using wiring methods in accordance with

Article 690 of the latest edition of the National Electric

Code, NFPA 70.

NOTE:

The total current draw of all system loads connected to the SunSaver-MPPT LOAD terminals cannot exceed the controller’s load current rating.

NOTE:

For mobile applications, be sure to secure all wiring.

Use cable clamps to prevent cables from swaying when the vehicle is in motion. Unsecured cables create loose and resistive connections which may lead to excessive heating and/or fire.

WARNING:

EXPLOSION HAZARD - DO NOT DISCONNECT WHILE

CIRCUIT IS LIVE UNLESS AREA IS

KNOWN TO BE NON-HAZARDOUS.

AVERTISSEMENT:

RISQUE D’EXPLOSION. NE PAS DEBRANCHER TANT

QUE LE CIRCUIT EST SOUS TENSION, A MOINS QU’lL

NE S’AGISSE D’UN EMPLACEMENT NON DANGEREUX.

MORNINGSTAR CORPORATION 21

Step 1: Load Wiring

The SS-MPPT load output connection will provide battery voltage to system loads such as lights, pumps, motors, and electronic devices. See Section 4.4 Load Control

Information for more details about load control.

LOAD

POSITIVE (+)

25 AMP

FUSE

LOAD

NEGATIVE (-)

Figure 4. Load wiring

Connect load positive (+) and negative (-) load wires to the system load(s) or load distribution panel as shown in figure 4. Refer to the wire gauge chart on page 41 of this manual for correct wire size.

If required, the negative load connection may be earth grounded. Use appropriate gauge wire and proper grounding methods for the installation site.

An in-line fuse holder should be wired in series in the load positive (+) wire as shown. DO NOT INSERT A FUSE AT

THIS TIME.

If wiring the load connection to a load distribution panel, each load circuit should be fused separately. The total load draw should not exceed the 15 A load rating

3.0 INSTALLATION INSTRUCTIONS

Step 2: Battery Wiring

WARNING: Shock Hazard

Fuses, circuit breakers, and disconnect switches should never open grounded system conductors. Only GFDI devices are permitted to disconnect grounded conductors.

AVERTISSEMENT: Risque de décharge électrique

Les fusibles, coupe-circuits et interrupteurs ne doivent jamais ouvrir les conducteurs du système mis à la terre.

Seuls les dispositifs GFDI sont autorisés à déconnecter les conducteurs reliés mis à la terre.

BATTERY

POSITIVE (+)

25 AMP

FUSE

6 in (150 mm)

MAX.

+

-

12V / 24V

BATTERY

BATTERY

NEGATIVE (-)

EARTH

GROUND

Figure 5. Battery wiring.

Before connecting the battery, measure the battery voltage. It must be over 7 volts to power the controller.

For 24 volt systems, the battery voltage must be greater than 15.5 volts to properly detect a 24V battery. The 12/24 volt battery detection is automatic and the check is only performed at start-up.

MORNINGSTAR CORPORATION 23

Connect the battery to the SS-MPPT. Refer to the wire gauge chart on page 41 of this manual for correct wire size.

If required, the negative battery connection may be earth grounded. Use appropriate gauge wire and proper grounding methods for the installation site.

Wire an in-line fuse holder no more than 6 inches (150 mm) from the battery positive terminal. DO NOT INSERT A

FUSE AT THIS TIME.

3.0 INSTALLATION INSTRUCTIONS

Step 3: Solar Wiring

WARNING: Shock Hazard

The solar PV array can produce open-circuit voltages in excess of 60 Vdc when in sunlight. Verify that the solar input breaker or disconnect has been opened (disconnected) before installing the system wires.

AVERTISSEMENT: Risque de décharge électrique

Le réseau PV solaire peut produire des tensions de circuit ouvert supérieures à 60 V cc à la lumière du soleil.

Vérifiez que le coupe-circuit ou l’interrupteur d’entrée solaire a été ouvert (déconnexion) avant d’installer les câbles du système.

WARNING: Risk of Damage

Connecting the solar array to the battery terminal will permanently damage the SunSaver-MPPT.

AVERTISSEMENT : Risque d’endommagement

La connexion du réseau solaire sur la borne de la batterie endommagera le SunSaver de façon permanente.

The SunSaver MPPT can accept 12 V , 24 V, or 36

V nominal off-grid solar module arrays. Grid-tie solar module(s) may be used if the open circuit voltage (V oc

) does not exceed the SS-MPPT 75 Volt maximum solar input rating. The solar module(s) nominal voltage must be equal to or greater than the nominal battery voltage. For 24 V systems, a 24 V or 36 V nominal solar array must be used.

MORNINGSTAR CORPORATION 25

12 Volt

MODULE

36 V NOMINAL MAX.

12 Volt

MODULE

12 Volt

MODULE

SOLAR

POSITIVE (+)

SOLAR

NEGATIVE (-)

(

-

) (+) (

-

) (+) (

-

) (+)

EARTH

GROUND

Figure 6. Solar input wiring.

Connect the solar module(s) to the SS-MPPT. Refer to the wire gauge chart on page 41 of this manual for correct wire size.

If required, the negative solar connection may be earth grounded. Use appropriate gauge wire and proper grounding methods for the installation site.

3.0 INSTALLATION INSTRUCTIONS

Step 4: Accessories (optional)

Install the Remote Temperature Sensor and Remote

Meter (both purchased separately) if required. Refer to the instructions provided with each accessory for detailed installation procedures.

Step 5: Confirm Wiring

Double-check the wiring in steps 1 through 4. Confirm correct polarity at each connection. Verify that all seven (7)

SS-MPPT power terminals are tightened.

3

+

-

2

1

Figure 7. System Wiring Review

Step 6: Install Fuses

Install a 25 Amp DC-rated fuse in each fuse holder in the following order:

1. Load circuit

2. Battery circuit

Step 7: Confirm Power-up

The SS-MPPT should begin the power-up LED sequence when battery power is applied. Observe that the Battery

Status LEDs blink in sequence one time.

If the SS- MPPT does not power up or a flashing LED error sequence exists, refer to Section 6.0 Troubleshooting.

MORNINGSTAR CORPORATION 27

4.0 Operation

4.1 LED Indications

STATUS LED

The Status LED indicates charging status and any existing solar input error conditions. The Status LED is on when charging during the day and off at night. The Status

LED will flash red whenever an error condition(s) exists.

Table 2 lists the Status LED indications.

Color

None

Green

Red

Red

Indication

Off (with heartbeat¹)

On Solid

( with heartbeat² )

Flashing

On Solid

( with heartbeat

2

)

Operating

State

Night

Charging

Error

Critical Error

¹ heartbeat indication flickers the Status LED on briefly every 5 seconds

² heartbeat indication flickers the Status LED off briefly every 5 seconds

Table 2. Status LED definitions

For more information on Status LED errors, see Section

5.1 Error Indications.

4.0 OPERATION

BATTERY SOC LEDS

Three (3) battery “state of charge” LEDs indicate the level of charge on the battery. The SOC indication is based on battery voltage setpoints alone, which only provides an approximation of the actual state of charge of the battery.

Table 3 lists the SOC LED indications.

SOC LED

Green

Green

Green

Green

Yellow

Red

Red

Indication

Fast Flashing

(2 Flash / sec)

Med. Flashing

(1 Flash / sec)

Slow Flashing

(1 Flash / 2 sec)

On solid

On solid

Flashing

(1 Flash / sec)

On solid

Battery Status

Equalize Charge

Absorption Charge

Float Charge

Nearly Full

Half Full

Battery Low

Battery Empty

Load Status

Load On

Load On

Load On

Load On

Load On

LVD Warning

(Load On)

LVD

(Load Off)

Table 3. Battery SOC LED definitions

NOTE:

An error condition exists if multiple Battery SOC LEDs are flashing. See Section 5.1 Error Indications for more information.

MORNINGSTAR CORPORATION 29

4.2 TrakStar

TM

MPPT Technology

The SS-MPPT utilizes Morningstar’s TrakStar Maximum

Power Point Tracking technology to extract maximum power from the solar module(s). The tracking algorithm is fully automatic and does not require user adjustment. Trakstar technology will track the array maximum power point voltage

(V mp

) as it varies with weather conditions, ensuring that maximum power is harvested from the array through the course of the day.

Current Boost

In many cases, TrakStar MPPT technology will “boost” the solar charge current. For example, a system may have 2

Amps of solar current flowing into the SS-MPPT and 5 Amps of charge current flowing out to the battery. The SS-MPPT does not create current! Rest assured that the power into the SS-MPPT is the same as the power out of the SS-MPPT.

Since power is the product of voltage and current (Volts x

Amps), the following is true*:

(1) Power Into the SS-MPPT = Power Out of the SS-MPPT

(2) Volts In x Amps In = Volts Out x Amps Out

* assuming 100% efficiency. losses in wiring and conversion exist.

If the solar module’s V mp

is greater than the battery voltage, it follows that the battery current must be proportionally greater than the solar input current so that input and output power are balanced. The greater the difference between the maximum power voltage and battery voltage, the greater the current boost. Current boost can be substantial in systems where the solar array is of a higher nominal voltage than the battery as described in the next section.

4.0 OPERATION

High Voltage Strings and Grid-tie Modules

Another benefit of TrakStar MPPT technology is the ability to charge 12 Volt or 24 Volt batteries with solar arrays of higher nominal voltages. A 12V battery bank can be charged with a 12 V, 24 V, or 36 V nominal off-grid solar array.

Certain grid-tie solar modules may also be used as long as the solar array open circuit voltage (V oc

) rating will not exceed the SS-MPPT 75 V maximum input voltage rating at worst-case (coldest) module temperature. The solar module documentation should provide V oc

vs. temperature data.

Higher solar input voltage results in lower solar input current for a given input power. High voltage solar input strings allow for smaller gauge solar wiring. This is especially helpful for systems with long wiring runs between the solar array and the SS-MPPT.

An Advantage Over Traditional Controllers

Traditional controllers connect the solar module directly to the battery when recharging. This requires that the solar module operate in a voltage range that is below the module’s V mp

. In a 12 V system for example, the battery voltage may range from 10 - 15 Vdc but the module’s V typically around 17 V. Figure 8 shows a typical current vs. voltage output curve for a nominal 12V off-grid module. mp

is

MAXIMUM

POWER

POINT

{

BATTERY

VOLTAGE

RANGE

10 V 15 V ~17 V

VOLTAGE

Figure 8. Nominal 12 V Solar Module I-V curve

MORNINGSTAR CORPORATION 31

The array V mp

is the voltage where the product of current and voltage (Amps x Volts) is greatest, which falls on the

“knee” of the solar module I-V curve as shown in Figure 8.

Because Traditional controllers do no operate at the V mp of the solar array, energy is wasted that could otherwise be used to charge the battery and power system loads. The greater the difference between battery voltage and the Vmp of the module, the more energy is wasted.

V

TrakStar MPPT technology will always operate at the mp resulting in less wasted energy compared to traditional controllers.

4.0 OPERATION

4.3 Battery Charging Information

The SunSaver MPPT has a 4-stage battery charging algorithm for rapid, efficient, and safe battery charging.

Figure 9 shows the sequence of the stages.

EQUALIZE

NIGHT

MPPT

CHARGE

ABSORPTION

FLOAT

NIGHT

TIME

Figure 9. SunSaver MPPT charging algorithm

Bulk Charge

In this stage, the battery voltage has not yet reached absorption voltage and 100% of available solar power is used to recharge the battery.

Absorption

When the battery has recharged to the Absorption voltage setpoint, constant-voltage regulation is used to prevent heating and excessive battery gassing.

Float

After the battery is fully charged the SS-MPPT reduces the battery voltage to a float charge which is sometimes called a trickle charge.

Depending on battery history, the battery remains in the

MORNINGSTAR CORPORATION 33

absorption stage for 3 or 4 hours before transitioning to the float stage.

Equalize (flooded battery type only)

If the auto-equalize feature is enabled, the SS-MPPT will equalize a flooded battery for three (3) hours every 28 days. Equalize charging raises the battery voltage above the standard absorption voltage so that the electrolyte gasses. This process prevents electrolyte stratification and equalizesthe individual cell voltages within the battery.

WARNING: Risk of Explosion

Equalizing vented batteries produces explosive gases.

The battery bank must be properly ventilated.

CAUTION: Equipment Damage

Excessive overcharging and gassing too vigorously can damage the battery plates and cause shedding of active material from the plates. An equalization that is too high or for too long can be damaging. Review the requirements for the particular battery being used in your system.

AVERTISSEMENT: Risque d’explosion

Les batteries à évent et compensation produisent des gaz explosifs. Le groupe de batteries doit être correctement ventilé.

PRUDENCE: Endommagement de l’équipement

Une surcharge excessive et un dégagement gazeux trop vigoureux peuvent endommager les plaques de batteries et provoquer l’élimination du matériau actif des plaques. Une compensation trop élevée ou trop longue peut provoquer des dégâts. Examinez les exigences pour la batterie particulière utilisée dans votre système.

4.0 OPERATION

4.4 Load Control Information

The primary purpose of the load control function is to disconnect system loads when the battery has discharged to a low state of charge and reconnect system loads when the battery is sufficiently recharged. System loads may be lights, pumps, motors, DC appliances, and other electronic devices. The total current draw of all loads must not exceed the SS-MPPT 15 Amp maximum load rating.

CAUTION: Do not wire an AC inverter of any size to the load terminals of the SunSaver MPPT. Damage to the load control circuit may result. Wire inverters directly to the battery or battery bank.

Load Control Settings

Load control is fully automatic. Choose between two (2) factory Low Voltage Disconnect (LVD) and Low Voltage

Reconnect (LVR) settings by adjusting switch #2. See

Section 3.2 Configuration for more information.

Current Compensation

All LVD and LVR setpoints are current compensated.

Under load the battery voltage will sag in proportion to the current draw of the load. A short-term large load could cause a premature LVD without the current compensation feature.

LVD and LVR setpoints are adjusted lower per the following table.

System Voltage

12 Volt

24 Volt

Current Compensation

-15 mV per amp of load

-30 mV per amp of load

Table 4. Current compensation values.

MORNINGSTAR CORPORATION 35

LVD Warning

As the battery discharges the Battery Status LEDs will transition from green to yellow and then from yellow to flashing red. The flashing red indication is a warning that a low voltage disconnect event will occur soon. The amount of time between a green SOC indication and load disconnect will depend on many factors including:

• rate of discharge (amount of load draw)

• capacity of the battery

• health of the battery

• LVD setpoint

If the battery discharges to the LVD setpoint the load will disconnect and a solid red Battery Status LED indication will be displayed.

General Load Control Notes

• A 15 V maximum regulation voltage limit (30 V @ 24 V nominal) exists for all battery types. This limit ensures that the battery and load terminal voltages will never exceed 15 V/30 V. This protects certain DC loads that may be damaged by high input voltage.

Do not wire multiple SunSaver MPPT load outputs together in parallel to power DC loads with a current draw greater than 15A. Equal current sharing cannot be guaranteed and an over-load condition will likely occur on one or more controllers.

Exercise caution when connecting loads with specific polarity to a live load circuit. A reverse polarity connection may damage the load. Always double check load connections before applying power.

4.0 OPERATION

4.5 Protections

Solar Overload

(No LED indication) The SunSaver MPPT will limit battery current to the 15 Amp maximum rating. An over-sized solar array will not operate at peak power. The solar array should be less than the SS-MPPT nominal max. input power

rating for optimal performance. See Section 7.0 Technical

Specifications for more information.

Load Overload

(Battery Status LEDs: R/Y-G sequencing) If the load current exceeds the maximum load current rating, the SS-

MPPT will disconnect the load. The greater the overload the faster the load will be disconnected. A small overload could take a few minutes to disconnect.

The SS-MPPT will attempt to reconnect the load two (2) times. Each attempt is approximately 10 seconds apart. If the overload remains after two (2) attempts, the load will remain disconnected until power is removed and reapplied.

Solar Short Circuit

(Charging Status LED: OFF) Solar input power wires are short-circuited. Charging automatically resumes when the short is cleared.

Load Short Circuit

(Battery Status LEDs: R/Y-G sequencing) Fully protected against load wiring short-circuits. After two (2) automatic load reconnect attempts (10 seconds between each attempt), the fault must be cleared by removing and reapplying power.

MORNINGSTAR CORPORATION 37

High Voltage Input

(Charging Status LED: R flashing) If the solar input open circuit voltage (V oc

) exceeds the 75 volt maximum rating the array will remain disconnected until the V the maximum rating.

oc

falls safely below

Battery Reverse Polarity

(No LED indication, not powered) Fully protected against reverse battery connection. No damage to the controller will result. Correct the miswire to resume normal operation.

Damaged Local Temperature Sensor

(Charging Status LED: R on solid) The local ambient temperature sensor is short-circuited or damaged. Charging stops to avoid over- or under-charging. This is a critical error. Contact your authorized Morningstar dealer for service.

Damaged Internal Temperature Sensor

(Charging Status LED: R on solid) The internal heatsink temperature sensor is damaged. This is a critical error.

Contact your authorized Morningstar dealer for service.

High Temperature

(Battery Status LED: R-Y sequencing) The heatsink temperature has exceeded safe limits and the load is disconnected. The load will automatically reconnect when the heatsink cools to a safe temperature.

Remote Temperature Sensor (RTS)

(Battery Status LED: R/Y - G/Y sequencing) A bad RTS connection or a severed RTS wire has disconnected the temperature sensor during charging. Charging automatically resumes when the problem is fixed. To resume operation

4.0 OPERATION

without a RTS, disconnect all power to the SunSaver MPPT and then reconnect.

High Voltage Transients

Solar, battery, and load power connections are protected against high voltage transients. In lightning prone areas, additional external suppression is recommended.

4.6 Inspection and Maintenance

The following inspections and maintenance tasks are recommended at least two times per year for best controller performance.

• Tighten all terminals. Inspect for loose, broken, or

corroded connections.

• Verify that all wire clamps and tie-downs are secure.

• Check that the controller is mounted in a clean, protected environment; free of dirt, insects, nests,

and corrosion.

• If applicable, check enclosure ventilation and air flow holes for obstructions.

• Verify LED indication is consistent with the present system conditions.

• Verify that the Remote Temperature Sensor (if used) is securely attached to the RTS terminals.

MORNINGSTAR CORPORATION 39

4.7 Programming Custom Set-Points

CAUTION: This feature should only be used by advanced users who have very specific charging and/or load control requirements that are not met using the factory default charge and load control settings. The factory default settings will be sufficient for the vast majority of users.

Custom charging and load set-points can be programmed into SS-

MPPT non-volatile memory using a PC with Morningstar MSView software installed and a Meterbus to Serial Adapter (model: MSC).

Refer to the MSView help files for detailed instructions. MSView PC software is available for free on our website at: http://www.morningstarcorp.com/

A setup wizard will guide you through the set-point configuration process. Refer to MSView help files for more information.

To use custom set-points, the Settings Switches must be adjusted as follows:

SWITCH #1 ON (↑) TO USE CUSTOM CHARGING SET-POINTS.

USE THE BATTERY SELECT JUMPER TO SELECT BETWEEN

TWO SETS OF CUSTOM CHARGING SET-POINTS.

SWITCH #2 ON (↑) TO USE CUSTOM LOAD CONTROL SET-

POINTS.

NOTE: Use the custom settings wizard to configure and program the controller for Lighting load control. This functionality can only be enabled through custom settings.

NOTE: Programming custom set-points will overwrite the default Gel and AGM battery type values programmed into custom memory at the factory. Document the new custom values in this manual for future reference.

4.0 OPERATION

5.0 Trouble Shooting

5.1 Error Indications

NOTE: If an optional Morningstar Remote Meter is attached to the SunSaver MPPT , use the self-diagnostic feature to determine the cause of the error indication.

Refer to the Remote Meter Operator’s Manual for more information.

Status LED Error Indications

• PV High Voltage Disconnect

• RTS Shorted

• RTS Disconnected

• Damaged local temp. sensor

Flashing Red

Flashing Red

Flashing Red

Solid Red

1

• Damaged heatsink temp. sensor Solid Red

1

• Damaged input MOSFETs

• Firmware Error

Solid Red

1

Solid Red

1

1 - heartbeat indication flickers the Status LED off briefly every 5 seconds

Battery Status LED Error Indications

• Load High Voltage Disconnect

• High Temperature Disconnect

• Remote Temp. Sensor Error

• External Wiring Error

• Load Overcurrent

• Load Short Circuit

• Custom Setpoints Update

• Self-test Error

R-G Sequencing

R-Y Sequencing

Y/R - G/Y Sequencing

G/R-Y Sequencing

Y/R-G Sequencing

G/R-Y Sequencing

G/Y/R Flashing

R-Y-G Sequencing

MORNINGSTAR CORPORATION 41

5.2 Common Problems

Problem: No LED indications

Solution: With a multi-meter, check the voltage at the

battery terminals on the SS-MPPT. Battery voltage must be at least 7V to power the SS-MPPT.

Problem: The SS-MPPT is not charging the battery.

Solution: If the Status LED is solid or flashing red,

see Section 5.1 Error Indications. If the Status LED is off, measure the voltage across the Solar input terminals of the SS-MPPT. Input voltage must be greater than battery voltage. Check fuses and solar wiring connections. Check solar array for shading.

Full testing documentation is available on our website at:

http://support.morningstarcorp.com/

4.0 OPERATION

6.0 Warranty

The SunSaver MPPT charge controller is warranted to be free from defects in material and workmanship for a period of FIVE (5) years from the date of shipment to the original end user. Morningstar will, at its option, repair or replace any such defective products.

CLAIM PROCEDURE

Before requesting warranty service, check the Operator’s Manual to be certain that there is a problem with the controller. Return the defective product to your authorized Morningstar distributor with shipping charges prepaid. Provide proof of date and place of purchase.

To obtain service under this warranty, the returned products must include the model, serial number and detailed reason for the failure, the module type, array size, type of batteries and system loads. This information is critical to a rapid disposition of your warranty claim.

Morningstar will pay the return shipping charges if the repairs are covered by the warranty.

WARRANTY EXCLUSIONS AND LIMITATIONS

This warranty does not apply under the following conditions:

• Damage by accident, negligence, abuse or improper use.

• PV or load currents exceeding the ratings of the product.

• Unauthorized product modification or attempted repair.

• Damage occurring during shipment.

THE WARRANTY AND REMEDIES SET FORTH ABOVE ARE

EXCLUSIVE AND IN LIEU OF ALL OTHERS, EXPRESS OR IMPLIED.

MORNINGSTAR SPECIFICALLY DISCLAIMS ANY AND ALL IMPLIED

WARRANTIES, INCLUDING, WITHOUT LIMITATION, WARRANTIES OF

MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE.

No Morningstar distributor, agent or employee is authorized to make any modification or extension to this warranty.

MORNINGSTAR IS NOT RESPONSIBLE FOR INCIDENTAL OR

CONSEQUENTIAL DAMAGES OF ANY KIND, INCLUDING BUT NOT

LIMITED TO LOST PROFITS, DOWNTIME, GOODWILL OR DAMAGE TO

EQUIPMENT OR PROPERTY.

1098 Washington Crossing Road,

Washington Crossing, PA 19877 USA

Email: [email protected]

Website: www.morningstarcorp.com

MORNINGSTAR CORPORATION 43

Electrical

7.0 Technical Specifications

Nominal system voltage

Max. battery current

Battery voltage range

Max. solar input voltage

Nominal Maximum Input Power*

12 Volt

24 Volt

Self-consumption

Accuracy

Voltage

Current

Meter Connection

Transient Surge Protection

Battery Charging

12 or 24 Vdc

15 A

7 – 36 V

75 V

200 Watts

400 Watts

35 mA

1.0 %

2.0 %

6-pin RJ-11

4 x 1500 W

Regulation Method

Temp. Compensation Coefficient

Temp. Compensation Range

Temp. Compensated Setpoints

Battery Status LEDs

G to Y

Falling V Rising V

12.1

Y to Flash R 11.7

Flash R to R 11.5

13.1

12.6

12.6

Y to G

Flash R to Y

R to Y

4 stage

-5 mV / °C / cell

(25°C reference)

- 30°C to + 60°C

Absorption,

Float

Equalize

Note: Multiply x2 for 24 Volt systems.

* These power levels refer to the maximum wattage the SS-MPPT-15L can process at a certain system voltage. Higher power arrays can be used without damaging the controller, but array cost-benefit will be reduced at power levels much beyond the nominal ratings.

7.0 TECHNICAL SPECIFICATIONS

Battery Setpoints (@ 25°C)

Absorption Voltage

Float Voltage

Time until Float

Equalize Voltage

Equalize Duration

Equalize Calendar

Max. Regulation Voltage

1

Low Voltage Disconnect

2

Low Voltage Reconnect

2

14.0 V 14.1 V 14.3 V 14.4 V

13.7 V 13.7 V 13.7 V 13.7 V

3 hr

N/A

N/A

N/A

3 hr

N/A

N/A

N/A

3 hr

14.5 V 14.9 V

3 hrs

28 days

3 hr

3 hrs

28 days

15 V / 30 V

11.5 V / 11.0 V

12.6 V / 12.1 V

1

2

Not temperature compensated. 15 V @ 12 V nominal, 30 V @ 24 V nominal

Adjustable by switch, not temperature compensated. 11.0 V / 12.1 V setting can be modified in custom settings.

NOTE: Temperature compensation increases regulation voltage in cold temperature. A 15 V (30 V @ 24 V nominal) maximum battery voltage limit prevents damage to sensitive DC loads.

Environmental

Ambient Temperature Range

Storage temperature

Humidity

Enclosure

-40°C to +60°C

-55°C to +100°C

100% N.C.

IP10 (indoor)

MORNINGSTAR CORPORATION 45

Mechanical

Power terminals wire size (max.)

Power terminals torque (max.)

Solid

Multistrand

Fine strand

Terminal Diameter

Wire gauge (min)

Wire gauge (max)

RTS terminals wire size (max.)

RTS terminals torque (max.)

Dimensions

Weight

Efficiency and Deratings

#6 AWG / 16 mm2

#6 AWG / 16 mm2

#8 AWG / 10 mm2

0.210 in / 5.4 mm

35 in-lb / 4 Nm

#22 AWG / 0.3 mm2

#12 AWG / 3.0 mm2

0.4 Nm / 3.5 in-lb see inside front cover

1.3 lbs / 0.60 kg

Figure 10. SS-MPPT 12 Volt Efficiency Curves

7.0 TECHNICAL SPECIFICATIONS

Figure 11. SS-MPPT 24 Volt Efficiency Curves

Figure 12. Output Current vs. Heatsink Temperature

MORNINGSTAR CORPORATION 47

Figure 13. Output Current vs. Array Voltage

Certifications

EMC Directives

• Immunity: EN61000-6-2:1999

• Emissions: EN55022:1994 with A1 and A3 Class B1

• Safety: EN60335-1 and EN60335-2-29 (battery chargers)

Specifications subject to change without notice.

Designed in the U.S.A.

Assembled in Taiwan

© 2013 Morningstar Corporation

MS-ZMAN-SSPPT-C v03

7.0 TECHNICAL SPECIFICATIONS

Appendix A - Wire Charts

amps

One-way Wire Distance (feet)

Wire Gauge (AWG)

One-way Wire Distance (meters)

Wire Gauge (mm 2 )

2

14

70

12

112

10

180

8

287

6

456

2.0

21

3.0

34

4

35 56 90 143 228

11 17

8

18 28 45 72 114

5 8

12

12 19 30 48 76

4 6

15

9 15 24 38 61

3

3% Voltage drop, Annealed copper wire at 20

°

C

5

24 Volt Nominal Wire Chart

5.0

55

27

14

9

7

8.0

87

44

22

15

12

13.0

139

69

35

23

19

amps

14

One-way Wire Distance (feet)

Wire Gauge (AWG)

12

12 Volt Nominal Wire Chart

10 8 6

One-way Wire Distance (meters)

Wire Gauge (mm

2

)

2.0

3.0

5.0

8.0

13.0

2

4

8

12

140

70

36

24

224

112

56

38

360

180

90

60

574

286

144

96

912

456

228

152

43

21

11

7

68

34

17

12

110

55

27

18.3

15

18 30 48 76 122

3% Voltage drop, Annealed copper wire at 20

5

°

C

9

36 Volt Nominal Wire Chart

15

175

87

44

29

23

278

139

69

46

37

amps

One-way Wire Distance (feet)

Wire Gauge (AWG)

14 12 10 8 6

2

4

8

12

210

105

54

36

336

168

84

57

540

270

135

90

861

429

216

144

1368

684

342

228

64

32

16

11

15

27 45 72 114 183

3% Voltage drop, Annealed copper wire at 20

8

°

C

One-way Wire Distance (meters)

Wire Gauge (mm

2

)

2.0

3.0

5.0

8.0

13.0

102

51

26

17

14

165

82

41

27

22

262

131

66

44

35

417

208

104

69

56

MORNINGSTAR CORPORATION 49

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals

Download PDF

advertisement

Languages