4116 - Adaptor temperatura
Universal transmitter
4116
– Input for RTD, TC, Ohm, potentiometer, mA and V
– 2-wire supply > 16 V
– FM-approved for installation in Div. 2
– Output for current, voltage and 2 relays
– Universal AC or DC supply
Advanced features
• Programmable via detachable display front (4501), process
calibration, signal and relay simulation, password protection,
error diagnostics and selection of help text in several
languages.
Connections
Application
• Linearized, electronic temperature measurement with RTD or
TC sensor.
• Conversion of linear resistance variation to a standard analog
current / voltage signal, i.e. from solenoids and butterfly
valves or linear movements with attached potentiometer.
• Power supply and signal isolator for 2-wire transmitters.
• Process control with 2 pairs of potential-free relay contacts
and analog output.
• Galvanic separation of analog signals and measurement of
floating signals.
• The 4116 is designed according to strict safety requirements
and is therefore suitable for application in SIL 2 installations.
Technical characteristics
• When 4116 is used in combination with the 4501 display /
programming front, all operational parameters can be
modified to suit any application. As the 4116 is designed with
electronic hardware switches, it is not necessary to open the
device for setting of DIP-switches.
• A green / red front LED indicates normal operation and
malfunction. A yellow LED is ON for each active output relay.
• Continuous check of vital stored data for safety reasons.
• 4-port 2.3 kVAC galvanic isolation.
This page is automatically generated on the basis of information provided on www.prelectronics.com and affiliated websites. It is provided to you as a service and for information
purpose only. While we have attempted to maintain the information as accurately as possible, the page may contain errors or omissions for which we disclaim any and all liability
Environmental Conditions
Specifications range.......................................
Calibration temperature.................................
Relative humidity............................................
Protection degree...........................................
-20°C to +60°C
20...28°C
< 95% RH (non-cond.)
IP20
Mechanical specifications
Dimensions (HxWxD).....................................
Dimensions (HxWxD) w/ 4501
/ 4511.............................................................
Weight approx................................................
Weight incl. 4501 / 4511 (approx.).................
Wire size........................................................
Screw terminal torque....................................
109 x 23.5 x 104 mm
109 x 23.5 x 116 / 131 mm
170 g
185 g / 270 g
1 x 2.5 mm2 stranded wire
0.5 Nm
Common specifications
Supply voltage, universal............................... 21.6...253 VAC, 50...60 Hz or
19.2...300 VDC
Fuse............................................................... 400 mA SB / 250 VAC
Max. power consumption............................... ≤ 2.5 W
Isolation voltage, test /
working........................................................... 2.3 kVAC / 250 VAC
Communications interface............................. Programming front 4501
Communications interface............................. Modbus communication
enabler 4511
Signal / noise ratio......................................... Min. 60 dB (0...100 kHz)
Response time (0...90%, 100...10%):
Temperature input.......................................... ≤ 1 s
Response time (0...90%, 100...10%):
mA / V input.................................................... ≤ 400 ms
Accuracy........................................................ Better than 0.1% of selected
range
Auxiliary supplies: 2-wire
supply (terminal 44...43)................................ 25...16 VDC / 0...20 mA
EMC immunity influence................................ < ±0.5% of span
Extended EMC immunity: NAMUR
NE 21, A criterion, burst................................. < ±1% of span
Input specifications
Output specifications
Current output: Signal range......................... 0...20 mA
Programmable signal ranges......................... 0...20 / 4...20 / 20...0 and
20...4 mA
Load (max.).................................................... 20 mA/800 Ω/16 VDC
Load stability, current output.......................... ≤0.01% of span/100 Ω
Sensor error indication, current
output............................................................. 0 / 3.5 / 23 mA / none
NAMUR NE 43 Upscale/Downscale.............. 23 mA / 3.5 mA
Current limit.................................................... ≤ 28 mA
Voltage output: signal range.......................... 0...10 VDC
Programmable signal ranges,
VDC................................................................ 0/0.2...1; 0/1...5 ; 0/2...10;
1...0.2/0; 5...1/0; 10...2/0 V
Load (min.)..................................................... 500 kΩ
Relay output: Relay functions........................ Setpoint, Window, Sensor
error, Latch, Power and Off
Hysteresis...................................................... 0...100%
ON and OFF delay......................................... 0...3600 s
Max. voltage................................................... 250 VRMS
Max. current................................................... 2 AAC or 1 ADC
Max. AC power.............................................. 500 VA
Sensor error reaction..................................... Break / Make / Hold
*of span.......................................................... = of the currently selected
measurement range
Approvals
EMC............................................................... EN 61326-1
LVD................................................................ EN 61010-1
FM.................................................................. 3025177
UL................................................................... UL 508
GOST R......................................................... Yes
DNV Marine.................................................... Stand. f. Certific. No. 2.4
SIL.................................................................. Hardware assessed for use in
SIL applications
4116-042214
RTD input....................................................... Pt10, Pt20, Pt50, Pt100,
Pt200, Pt250, Pt300, Pt400,
Pt500, Pt1000 Ni50, Ni100,
Ni120, Ni1000, Cu10, Cu20,
Cu50, Cu100
RTD input....................................................... Linear resistance
RTD input....................................................... Potentiometer
Cable resistance per wire
(max.), RTD.................................................... 50 Ω
Sensor current, RTD...................................... Nom. 0.2 mA
Effect of sensor cable resistance
(3-/4-wire), RTD............................................. < 0.002 Ω / Ω
Sensor error detection, RTD.......................... Yes
Short circuit detection, RTD........................... < 15 Ω
TC input: Thermocouple type......................... B, E, J, K, L, N, R, S, T, U,
W3, W5, LR
Cold junction compensation
(CJC) via ext. sensor in
connector 5910.............................................. 20...28°C ≤ ±1°C, -20...20°C /
28...70°C ≤ 2°C
CJC via internally mounted
sensor............................................................ ±(2.0°C + 0.4°C * Δt)
Δt =................................................................. Internal temperature-ambient
temperature
Sensor error detection, TC............................. Yes
Sensor error current: When
detecting / else............................................... Nom. 2 μA / 0 μA
Current input: Measurement
range.............................................................. 0...20 mA
Current input: Programmable
measurement ranges..................................... 0...20 and 4...20 mA
Input resistance, current
input............................................................... Nom. 20 Ω + PTC 50 Ω
Voltage input: Measurement
range.............................................................. 0...12 VDC
Programmable measurement ranges,
VDC................................................................ 0/0.2...1, 0/1...5, 0/2...10 VDC
Input resistance, voltage
input............................................................... Nom. 10 MΩ