ENDA ATC9311 Technical Specifications ANALOG THERMOSTAT with DIGITAL DISPLAY

ENDA ATC9311 Technical Specifications ANALOG THERMOSTAT with DIGITAL DISPLAY
Technical Specifications
english
ENVIRONMENTAL CONDITIONS
Ambient/storage temperature
Max. relative humidity
Rated pollution degree
Height
Read this document carefully before using this device. The guarantee will be
expired by damaging of the device if you don't attent to the directions in the user
manual. Also we don't accept any compansations for personal injury, material
damage or capital disadvantages.
0 ... +50°C/-25... +70°C, without condense
80% up to 31°C decreasing linearly 50% at 40°C.
According to EN 60529
Front panel : IP60
Rare panel : IP20
Max. 2000m
Do not use the device in locations subject to corrosive and flammable gases.
ENDA ATC9311
ELECTRICAL CHARACTERISTICS
Supply
Power consumption
Input / Wiring
Scale
Sensitivity
Accuracy
230V AC +10% -20%, 50/60Hz or 24V AC ±10%, 50/60Hz
Max. 5VA
Thermocouple “J” type / 1.5mm² screw-terminal connection.
0 ... 400°C
1°C
For adjustment ±4%, for display ±0,5% (of full scale) or ±1 digit.
3 digits, 7.62mm, 7 seven segment LED
EEPROM (>10 years)
EN 61326-1: 1997, A1: 1998, A2: 2001 ( For EMC tests performance criterion B is
satisfied.)
EN 61010-1: 2001 (Pollution degree 2, overvoltage category II)
Data retention
EMC
Safety requirements
ANALOG THERMOSTAT with DIGITAL DISPLAY
Thank you for choosing ENDA ATC9311 temperature controller.
Control output state LED
(Light is on when control output is energised)
SET
OUT
PRG
Set key
Temperature display
200
OUTPUT
150
CONTROL
Control type
Control algorithm
A/D converter
Proportional band
Control period
Hysteresis
Single-setpoint control
On-Off / time proportional (optional)
9 bits
2% (for time porportional control)
10 second (for time proportional control)
4°C (for On-Off control)
HOUSING
Housing type
Dimensions
Weight
Enclosure material
Suitable for flush-panel mounting.
W96xH96xD50mm
Approx. 340g (after packing)
Self extinguishing plastics
While cleaning the device, don`t use solvents (thinner, benzine, acid etc.) or corrosive materials
Dimensions
14mm
90.5mm
250
°C
300
50
99mm
96mm
200
100
105mm
90.5mm
Flush
mounting
adaptor
SET
OUT
150
Panel cut-out
Depth
50mm
350
0
400
ENDA
ATC9311
99mm
Rubber
packing
Panel
57mm
Note : Panel thickness
should be
max. 10mm.
up to date: 01022014, modification reserved and can be change any time previous notice !
Relay : 250V AC, 2A (for resistive load), NO+NC or 12V DC 20mA logic output
Mechanical 30.000.000 operation; electrical 300.000 operation
Control output
Life expentancy for relay
100
250
°C
300
Adjusting knob
50
RoHS
350
0
conform
ENDA
400
ATC9311
* 96 x 96mm sized.
* Digital display for measured temperature and set value.
* Selectable On-Off or time proportional control.
* Fe-CuNi “J” type thermocouple input.
* Output relay is deenergied in the case of sensor failure.
* Easy setting procedure.
Application areas
glass industry, chemistry and pharmacy, drinks industry, drying plant,
paper industry, food industry, baker`s plant, plastic indutry
1./2
ATC9311-E
ATC9311 Programming Diagram
Connection diagram
ENDA ATC9311 is intended for installation in control panels. Make sure that the device is
used only for intented purpose. The electrical connections must be carried on by a
qualified staff and must be according to the relevant locally applicable regulations.
During an installation, all of the cables that are connected to the device must be free of
energy. The device must be protected against inadmisible humidity, vibrations, severe
soiling and make sure that the operation temperature is not exceeded. All input and
output lines that are not connected to the supply network must be laid out as shielded
and twisted cables.These cables should not be close to the power cables or
components. The shielding must be grounded on the instrument side.
Set value
Temperature display
Process temperature value is seen.
SET
Terminal connection
ENDA
5
Fe-Const
TC
6
7
2
3
+
8
1
4
5
6
7
8
The fuse for the load is not considered !
Supply :
key, contol form chages and the related message
184-253V AC 4
50/60Hz 5VA 5
L
N
Fuse
F 100 mA 250V AC
Main switch
Cable size: 1,5mm²
SENSOR INPUT :
Use suitable compansation cables. Don't use jointed cables.
Pay attention to the polarities of the
thermocouple cables as shown in the figure below.
Error Messages
If this message is seen, it means temperature sesor was not disconnected
or over temperature condition was occured. When this message is seen,
If this message is seen, it means the device has a calibration error. In this
case, the device should be sent to your trader. or to a nearest ENDA local
representative for calibration and testing. When this message is seen, the
control output is deenergised.
230V AC +%10 -%20
24V AC ±%10
Tel.: +49 (0)7451 / 625 617
Fax: +49 (0)7451 / 625 0650
E-mail : [email protected]
Internet : www.suran-elektronik.de
7
TC
8
Note :
The time proportional function controls a temperature area near the
SET value. Out of this temperaturrange the relay is “OFF” by over the
SET value or “ON” under the SET value.
If the processvalue approximated to SET value, the “ON” time from the
relay will be shortly. The processtemperature will be prevent to swing
or will be very small.
Supply voltage
Logic output of the instrument ATC9311-SSR
is electrically not insulated from the
internal circuits. Therefore, when using a
grounding thermo-couple, do not connect
the logic output terminals to the ground.
230V AC Supply
Fuse must
be connected !
is seen on the display.
Dettinger Str. 9 / D-72160 Horb a.N
4
are seen.
NOTE :
SURAN Industrieelektronik
3
is seen.
and
If the device is energised while holding SET
2
-
-
+
1
+
230V AC +10% -20%
50/60Hz 5VA
SN: XXXXXXXXX
LOGIC OUT
12V DC 20mA
SN: XXXXXXXXX
When the device is energised, selected control form is seen on the display.
If On-Off control was selected,
INDUSTRIAL ELECTRONICS
ATC9311-230VAC-SSR
ANALOG THERMOSTAT
Selecting control form
If time proportional control was selected,
ENDA
INDUSTRIAL ELECTRONICS
ATC9311-230VAC
ANALOG THERMOSTAT
230V AC +10% -20%
50/60Hz 5VA
key is released, process temperature is seen again.
OUTPUT
250V AC 2A
RESISTIVE LOAD
SET
+
When
key is pressed, set value is seen.
-
SET
+
If
Fe-Const
TC
Terminal connection
Control output
Relay
Logic output
Relay
Logic output
Note :
1)Cables for supply must be
IEC60799 or IEC60245 conform.
2)Main switch should be with in
easy reach and should be
indicated !
Proportionalband 8°C
SET-value
196°C
200°C
204°C
2% from scale 400°C= 8°C
Order code
ATC9311
ATC9311-SSR
ATC9311-24
ATC9311-24-SSR