Technical Datasheet 1SBC101413D0201 25/03/11

AF26-30-11-.. / AF26Z-30-11-.. 3-pole Contactors

AC / DC Operated - with Screw Terminals

AF26(Z) contactors are used for controlling power circuits up to 690 V AC and 220 V DC.

They are mainly used for controlling 3-phase motors, non-inductive or slightly inductive loads.

AF..(Z) contactors include an electronic coil interface providing reduced pull-in and holding consumption, particularly for AC control circuits

Only four coils are needed to cover control voltages between 24...500 V

50/60 Hz or 20...500 V DC.

AF..(Z) offer extended operating limits and are suitable worldwide for different control voltages. e.g.: the coil 100...250 V 50/60 Hz - DC is suitable for Europe (230 V

50 Hz) and for North America (120 V 60 Hz and 208 V 60 Hz). AF..(Z) contactors can manage large control voltage variations

AF..Z contactors equipped with a 24...60 V 50/60 Hz - 20...60 V DC coil allow direct control by 24 V DC 500 mA PLC-output

AF..Z contactors withstand short voltage dips and voltage sags (SEMI

F47-0706 compliance)

AF..(Z) contactors have built-in surge protection and do not require additional surge suppressors

2-stack contactors are mounted with a non-removable auxiliary contact block. They have mechanically-linked auxiliary contacts compliant with

Annex L of IEC 60947-5-1, including the "Mechanically Linked" symbol on their side

N.C. auxiliary contacts are mirror contacts in compliance with Annex F of

IEC 60947-4-1.

11 kW

15 hp

3D CAD outline drawings available on «Control Product 3D» portal

Ordering Details

IEC

Rated power

400 V

AC-3 kW

UL/CSA Control voltage

3-phase motor rating

Uc min. ... Uc max.

480 V hp V 50/60 Hz V DC

Main contacts

Auxiliary contacts fitted

Type Order code EAN

3-pole Contactors

11 15 24...60

48...130

100...250

250...500

20...60

48...130

100...250

250...500

3

3

3

3

0

0

0

0

1

1

1

1

1

1

1

1

AF26-30-11-11

AF26-30-11-12

AF26-30-11-13

AF26-30-11-14

1SBL 237 001 R1111

1SBL 237 001 R1211

1SBL 237 001 R1311

1SBL 237 001 R1411

3471523111011

3471523111028

3471523111035

3471523111042

Note: AF26-30-11-11 not suitable for a direct control by PLC-output. AF26-30-11-11 available in some countries: please consult your ABB representative.

Weight

Pack (ing)

1 piece kg

0.350

0.350

0.350

0.390

2-stack 3-pole Contactors - Low Consumption

11 15 -

24...60

48...130

100...250

12...20

20...60

48...130

100...250

3

3

3

3

0

0

0

0

1

1

1

1

1

1

1

1

AF26Z-30-11-20

AF26Z-30-11-21

AF26Z-30-11-22

AF26Z-30-11-23

1SBL 236 001 R2011

1SBL 236 001 R2111

1SBL 236 001 R2211

1SBL 236 001 R2311

3471523114203

3471523114210

3471523114227

3471523114234

0.390

0.390

0.390

0.390

Note: Only AF..Z contactors with DC control voltage 12...20 V DC need to respect the connection polarities indicated close to the coil terminals: A1+ for the positive pole and A2- for the negative pole

Certifications and Approvals

CE cULus CCC GOST C-Tick

ABB | Technical Datasheet 1SBC101413D0201 1

Main Pole - Utilization Characteristics according to IEC

Standards

Rated operational voltage Ue max.

Rated frequency limits

Conventional free-air thermal current Ith acc. to IEC 60947-4-1, open contactors, θ ≤ 40 °C with conductor cross-sectional area

AC-1 Utilization category for air temperature close to contactor

Ie / AC-1 rated operational current

Ue max. ≤ 690 V, 50/60 Hz

θ ≤ 40 °C

θ ≤ 60 °C

θ ≤ 70 °C with conductor cross-sectional area

AC-3 Utilization category for air temperature close to contactor θ ≤ 60 °C

(for 1500 r.p.m., 50 Hz or 1800 r.p.m., 60 Hz, 3-phase motors)

Ie / AC-3 max. rated operational current

3-phase motors

3

M

AC-3 rated operational power

3

M

1500 r.p.m. 50 Hz

1800 r.p.m. 60 Hz

3-phase motors

220-230-240 V

380-400 V

415 V

440 V

500 V

690 V

220-230-240 V

380-400 V

415 V

440 V

500 V

690 V

Rated making capacity AC-3

Rated breaking capacity AC-3

AC-8a Utilization category

(without thermal overload relay - Ue 400 V - θ ≤ 40 °C)

Ie / AC-8a rated operational current

AC-8a rated operational power

Short-circuit protection for contactors without thermal O/L relay - Motor protection excluded

Ue ≤ 500 V AC - gG type fuse

Rated short-time withstand current Icw at 40 °C ambient temperature, in free air from a cold state

Maximum breaking capacity cos φ = 0.45

Heat dissipation per pole

Max. electrical switching frequency

1 s

10 s

30 s

1 min

15 min at 440 V at 690 V

Ie / AC-1

Ie / AC-3

AC-1

AC-3

AC-2, AC-4

IEC 60947-1 / 60947-4-1 and EN 60947-1 / 60947-4-1

690 V

25 ... 400 Hz

50 A

10 mm²

45 A

40 A

32 A

10 mm²

26 A

26 A

26 A

26 A

23 A

17 A

6.5 kW

11 kW

11 kW

15 kW

15 kW

15 kW

10 x Ie AC-3 acc. to IEC 60947-4-1

8 x Ie AC-3 acc. to IEC 60947-4-1

30 A

15 kW

50 A

700 A

350 A

225 A

150 A

50 A

500 A

200 A

1.8 W

0.6 W

600 cycles/h

1200 cycles/h

150 cycles/h

2 Technical Datasheet 1SBC101413D0201 | ABB

Built-in Auxiliary Contacts according to IEC

Rated operational voltage Ue max.

Conventional free air thermal current Ith - θ ≤ 40 °C

Rated frequency limits

Rated operational current Ie / AC-15 acc. to IEC 60947-5-1 24-127 V 50/60 Hz

220-240 V 50/60 Hz

400-440 V 50/60 Hz

500 V 50/60 Hz

690 V 50/60 Hz

Making capacity AC-15

Breaking capacity AC-15

Rated operational current Ie / DC-13 acc. to IEC 60947-5-1 24 V DC

48 V DC

72 V DC

110 V DC

125 V DC

220 V DC

250 V DC

400 V DC

500 V DC

600 V DC

Short-circuit protection gG type fuse

Rated short-time withstand current Icw for 1.0 s for 0.1 s

Minimum switching capacity with failure rate acc. to IEC 60947-5-4

Non-overlapping time between N.O. and N.C. contacts

Heat dissipation per pole at 6 A

Max. electrical switching frequency AC-15

DC-13

690 V

16 A

25 ... 400 Hz

6 A

4 A

3 A

2 A

2 A

10 x Ie AC-15 acc. to IEC 60947-5-1

10 x Ie AC-15 acc. to IEC 60947-5-1

6 A / 144 W

2.8 A / 134 W

1 A / 72 W

0.55 A / 60 W

0.55 A / 69 W

0.27 A / 60 W

0.27 A / 68 W

0.15 A / 60 W

0.13 A / 65 W

0.1 A / 60 W

10 A

100 A

140 A

12 V / 3 mA

10 -7

≥ 2 ms

0.1 W

1200 cycles/h

900 cycles/h

Main Pole - Utilization Characteristics according to UL / NEMA / CSA

Standards

Rated operational voltage Ue max.

NEMA size

NEMA continuous amp rating

NEMA maximum H.P. ratings 1-phase, 60 Hz

NEMA maximum H.P. ratings 3-phase, 60 Hz thermal current

115 V AC

230 V AC

200 V AC

230 V AC

460 V AC

575 V AC

UL 508, CSA C22.2 N°14

600 V

1

27 A

2 hp

3 hp

7-1/2 hp

7-1/2 hp

10 hp

10 hp

UL General use rating

600 V AC

With conductor cross-sectional area

80 V DC - 1-pole

With conductor cross-sectional area

UL maximum 1-phase motor rating

Amp-rating

45 A

AWG 8

45 A

AWG 8

Motor power

120 V AC

240 V AC

120 V AC

240 V AC

24 A

17 A

2 hp

3 hp

UL maximum 3-phase motor rating

Amp-rating

Motor power

(for 1500 r.p.m., 50 Hz or 1800 r.p.m., 60 Hz 3-phase motors)

200-208 V AC

220-240 V AC

440-480 V AC

550-600 V AC

200-208 V AC

220-240 V AC

440-480 V AC

550-600 V AC

25.3 A

22 A

21 A

22 A

7.5 hp

7.5 hp

15 hp

20 hp

Short-circuit protection for contactors without thermal O/L relay - Motor protection excluded

Fuse rating

Fuse type, 600 V

Max. electrical switching frequency for general use for motor use

150 A

NTD

600 cycles/h

1200 cycles/h

ABB | Technical Datasheet 1SBC101413D0201 3

Built-in Auxiliary Contacts according to UL / CSA

Max. rated operational voltage Ue max.

Pilot duty

AC thermal rated current

AC maximum volt-ampere making

AC maximum volt-ampere breaking

DC thermal rated current

DC maximum volt-ampere making-breaking

600 V AC, 600 V DC

A600, Q600

10 A

7200 VA

720 VA

2.5 A

69 VA

General Technical Data

Rated insulation voltage Ui acc. to IEC 60947-4-1 acc. to UL /CSA

Rated impulse withstand voltage Uimp.

Electromagnetic compatibility

Ambient air temperature close to contactor

Operation fitted with thermal overload relay without thermal overload relay

Storage

Climatic withstand

Operating altitude

Mechanical durability

Number of operating cycles

Max. switching frequency

Shock withstand acc. IEC 60068-2-27 and EN 60068-2-27

Mounting position 1

C1

Closed or open position

A A B1 B2

Vibration withstand acc. to IEC 60068-2-6

C2

690 V

600 V

6 kV

Devices complying with IEC 60947-1 / EN 60947-1 - Environment A

-25 ... +60 °C

-40 ... +70 °C

-60 ... +80 °C

Category B according to IEC 60947-1 Annex Q

≤ 3000 m

10 millions operating cycles

3600 cycles/h

Shock direction

A

B1

B2

C1

C2

1/2 sinusoidal shock for 11 ms: no change in contact position

30 g

25 g Closed position / 5 g Open position

15 g

25 g

25 g

5 ... 300 Hz

4 g Closed position / 2 g Open position

Magnet System Characteristics

Coil operating limits acc. to IEC 60947-4-1

AC control voltage Rated control circuit voltage Uc

50/60 Hz Coil consumption Average pull-in value

Average holding value

DC control voltage Rated control circuit voltage Uc

Coil consumption Average pull-in value

Average holding value

PLC-Output control

Drop-out voltage in % of Uc min.

Voltage sag immunity according to SEMI F47-0706

Dips withstand (level 0% according to IEC 61000-4-11)

-20 °C ≤ θ ≤ +60 °C

Operating time between coil energization and: N.O. contact closing between coil de-energization and:

N.C. contact opening

N.O. contact opening

N.C. contact closing

AC supply

DC supply at θ ≤ 60 °C 0.85 x Uc min ... 1.1 x Uc max at θ ≤ 70 °C 0.85 x Uc min ... Uc max at θ ≤ 60 °C 0.85 x Uc min ... 1.1 x Uc max at θ ≤ 70 °C (AF) 0.85 x Uc min ... Uc max - (AF..Z) 0.85 x Uc min ... 1.1 x Uc max

24 ... 500 V AC

(AF) 50 VA - (AF..Z) 16 VA

(AF) 2.2 VA / 2 W - (AF..Z) 1.7 VA / 1.5 W

12 ... 500 V DC

(AF) 50 W - (AF..Z) 12 ... 16 W

(AF) 2 W - (AF..Z) 1.7 W

(AF..Z) ≥ 500 mA 24 V DC

≤ 60 % Uc min

(AF..Z) conditions of use on request

(AF..Z) 22 ms average for Uc = 24 ... 250 V 50/60Hz

40 ... 95 ms

38 ... 90 ms

11 ... 95 ms

13 ... 98 ms

4 Technical Datasheet 1SBC101413D0201 | ABB

Mounting Characteristics

Mounting positions

Mounting distances

Fixing on rail according to IEC 60715, EN 60715 by screws (not supplied)

Pos

. 2 +30° -30°

Pos . 4

Pos. 3

Pos. 1 Pos. 1 ± 30° Pos. 5

Max. N.C. built-in and add-on N.C. auxiliary contacts: see accessory fitting details for a

3-pole contactor AF09 ... AF38

The contactors can be assembled side by side.

35 x 7.5 mm or 35 x 15 mm

2 x M4 screws placed diagonally

Connecting Characteristics

Main terminals

Screw terminals with cable clamp

Connecting capacity (min. ... max.)

Main conductors (poles)

Rigid solid (≤ 4 mm ² ) stranded (≥ 6 mm²)

Flexible with non insulated ferrule

L

Flexible with insulated ferrule

Bars or lugs

6

Capacity according to UL/CSA

Stripping length

Auxiliary conductors

(built-in auxiliary terminals + coil terminals)

Rigid solid

1 x

2 x

1 x

2 x

1 x

2 x

L <

2.5 ... 10 mm²

2.5 ... 10 mm²

1.5 ... 10 mm²

1.5 ... 10 mm²

1.5 ... 10 mm²

1.5 ... 4 mm²

12.5 mm

1 or 2 x AWG 14 ... 8

14 mm

Flexible with non insulated ferrule

Flexible with insulated ferrule

1 x

2 x

1 x

2 x

1 x

2 x

L <

1 ... 2.5 mm²

1 ... 2.5 mm²

0.75 ... 2.5 mm²

0.75 ... 2.5 mm²

0.75 ... 2.5 mm²

0.75 ... 1.5 mm²

8 mm

1 or 2 x AWG 18 ... 14

10 mm

L Bars or lugs

6

Capacity according to UL/CSA

Stripping length

Degree of protection acc. to IEC 60947-1 / EN 60947-1 and IEC 60529 / EN 60529

Main terminals

Coil terminals

Built-in auxiliary terminals

Screw terminals

Main terminals

Coil terminals

Built-in auxiliary terminals

Screwdriver type

Tightening torque

Main pole terminals

Coil terminals

Built-in auxiliary terminals

IP20

IP20

IP20

(delivered in open position, screws of unused terminals must be tightened)

M4

M3.5

M3.5

Flat Ø 5.5 / Pozidriv 2

2.5 Nm / 22 lb.in

1.2 Nm / 11 lb.in

1.2 Nm / 11 lb.in

ABB | Technical Datasheet 1SBC101413D0201 5

Accessory Fitting Details for a 3-pole Contactor

Many configurations of accessories are possible depending on whether these are front-mounted or side-mounted.

Main poles

Built-in auxiliary contacts

3 0 1 1

Front-mounted accessories

Auxiliary contact blocks

1-pole CA4

1-pole CC4 2-pole CAT4-11 4-pole CA4

Electrical and mechanical interlock set

(between 2 contactors)

VEM4

Side-mounted accessories

Auxiliary contact blocks

Left side

2-pole CAL4-11

Max. N.C. built-in and add-on N.C. auxiliary contacts: 4 N.C. max. on positions 1, 2, 3, 4 and 3 N.C. max. on positions 1 ±30°, 5

– – – – 1 +

Right side

1

Overview of main accessories

(other accessories available)

Main poles

Built-in auxiliary contacts

3 0 0 0

Fixing clips

AF contactor

AF contactor

Front-mounted accessories

Auxiliary contact blocks Electrical and mechanical interlock set

(between 2 contactors)

Side-mounted accessories

Auxiliary contact blocks

1-pole CA4

1-pole CC4 2-pole CAT4-11 4-pole CA4 VEM4

Left side

2-pole CAL4-11

Max. N.C. built-in and add-on N.C. auxiliary contacts: 4 N.C. max. on positions 1, 2, 3, 4 and 3 N.C. max. on positions 1 ±30°, 5

4 max.

or 1 or 1 – + 1

2 max.

3 max.

or 1

– +

1

+

+

1

1

+ or

Right side

1

1

2-pole CAL4-11

VM4

1-pole CA4, CC4

TF42

EF..

4-pole CA4

AF contactor

(without top mounted coil terminal block)

2-pole CAT4-11

2-pole CAL4-11

VEM4 mechanical and electrical interlock set including:

– VM4 mechanical interlock unit including 2 fixing clips

– VE4 electrical interlock block with A2-A2 connection

A2

A2

1-pole

CA4, CC4

1-pole

CA4, CC4

VE4

TF42

EF..

6 Technical Datasheet 1SBC101413D0201 | ABB

Main Accessories

Ordering Details

Description

Additional auxiliary contact blocks

Interlocks

Auxiliary contacts

Type Order code EAN

Side-mounted instantaneous auxiliary contact blocks

1 1 - CAL4-11 1SBN 010 120 R1011 3471523130043 1

1 1 - CAL4-11-T 1SBN 010 120 T1011 3471523130418 10

Pack (ing) piece

Weight kg

(1 pce)

0.040

0.040

VM4 1SBN 030 105 T1000 3471523130609 10 Mechanical interlock unit

Fixing clips

0.005

0.002

Connection accessories for starting

Connecting links with manual motor starters

Connection sets for reversing contactors

Additional coil terminal block

Additional coil terminal block

Protective covers Protective covers

Function markers Function markers

BB4

BEA26-4

BEA38-4

BER38-4

1SBN 110 120 W1000 3471523130722 50

1SBN 082 306 T1000 3471523130746 10

1SBN 082 306 T2000 3471523130753 10

1SBN 082 311 R1000 3471523130784 1

LDC4

BX4-CA

1SBN 070 156 T1000 3471523130678 10

1SBN 110 109 W1000 3471523130715 50

BA4 1SNA 235 156 R2700 3472592351568 16

HTP500-BA4 1SNA 235 712 R2400 3472592357126 1

SPRC 1 1SNA 360 010 R1500 3472593600108 1

0.025

0.030

0.100

0.010

0.001

0.011

0.220

0.290

Note: VM4 includes 2 fixing clips (BB4) to maintain together both contactors.

ABB | Technical Datasheet 1SBC101413D0201 7

Terminal Marking and Positioning

Standard devices without addition of auxiliary contacts

A1 1L1 3L2 5L3

1L1

A1 A2

3L2 5L3

13 21

NO NC

14 22

13

NO

21

NC

A2 2T1 4T2 6T3

NO

14

NC

22

AF26-30-11-.. / AF26Z-30-11-..

2T1 4T2

A1 A2

6T3

AF26-30-11-.. / AF26Z-30-11-..

Dimensions mm, inches

45 1.77" 45 1.77"

5.5 0.22"

111.5 4.39"

80 3.15"

5.5 0.22"

110.5 4.35"

10 0.39"

35 1.38"

ø 4.2 0.17"

2 x

35 1.38"

M4 8-32 UNC

2 x

M4 8-32 UNC

5.5 0.22" 5.5 0.22"

AF26

5 0.20"

AF26

5 0.20"

Note: contactor lateral distance to grounded component 2 mm 0.08" min.

8 Technical Datasheet 1SBC101413D0201 | ABB

Contact us

ABB France

Low Voltage Products Division

10, rue Ampère Z.I. - B.P. 114

F-69685 Chassieu cedex / France

You can find the address of your local sales organisation on the ABB home page http://www.abb.com/contacts -> Low Voltage products

Note

We reserve the right to make technical changes or modify the contents of this document without prior notice. With regard to purchase orders, the agreed particulars shall prevail. ABB does not accept any responsibility whatsoever for potential errors or possible lack of information in this document.

We reserve all rights in this document and in the subject matter and illustrations contained therein.

Any reproduction, disclosure to third parties or utilization of its contents – in whole or in parts – is forbidden without prior written consent of ABB.

Copyright© 2011 ABB

All rights reserved www.abb.com/lowvoltage

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals

Download PDF

advertisement